Attachment 02 - Specifications.pdf
PDF 75 KB Posted
- Attached to
- Remove and Replace Highspeed Overhead Doors Federal contract opportunity
- Solicitation number
- FA5004-22-B-0009
About this file
This solicitation is for the removal and replacement of multiple overhead fabric and metal doors at multiple facilities on Eielson Air Force Base in Alaska. The contractor shall demolish existing doors and associated controls, conduit and electrical fixtures, and provide and install all new doors, ancillary controls and mounting for full door operation. A site visit will be conducted on July 21, 2022 at 10:00am AKDT with a limit of two attendees per prime contractor. Questions are due by July 26, 2022 and will be answered in an amendment posted to SAM.gov. Electronic bids only must be submitted to two specified individuals by August 16, 2022 at 2:00pm AKDT. The NAICS code is 236220 with a small business size standard of $39.5 million. The estimated value is between $1 million and $5 million. Payment and performance bonds are required. The period of performance is 225 calendar days from notice to proceed. The soliciting agency is the Department of the Air Force Pacific Air Forces.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Solicitation Amendment FA500422B00090003 SF 30.pdf | ||
| Site Visit Questions and Answers (High Speed Overhead Doors) Updated.pdf | ||
| FTQW 20-1011 Questions and Answers - High Speed Overhead Doors.pdf | ||
| FTQW 20-1011 Site Visit Sign In Sheet.pdf | ||
| Solicitation Amendment FA500422B00090002 SF 30.pdf | ||
| Solicitation Amendment FA500422B00090001 SF 30.pdf | ||
| Attachment 05 - Submittal Register.xlsx | XLSX spreadsheet | |
| Attachment 04 - Wage Determination AK20220001.pdf | ||
| Attachment 01 - HS OH Door Replacement Statement of Work.pdf | ||
| Solicitation - FA500422B0009.pdf | ||
| Attachment 03 - Drawings.pdf |
Show all 11
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
HIGH SPEED OVERHEAD DOOR REPLACEMENT (1306, 6203, 4105) FTQW 20-1011
SECTION 01 11 00 PAGE 1
SECTION 08 37 30
HIGH-SPEED RUBBER DOOR
PART 1 GENERAL
1.1 REFERENCES
The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.
ASTM INTERNATIONAL (ASTM)
ASTM A36/A36M (2019) Standard Specification for Carbon Structural Steel
ASTM A123/A123M (2017) Standard Specification for Zinc
(Hot-Dip Galvanized) Coatings on Iron and Steel Products
ASTM A653/A653M (2020) Standard Specification for
Steel Sheet, Zinc-Coated (Galvanized) or Zinc-Iron Alloy-Coated (Galvannealed) by the Hot-Dip Process
ASTM A992/A992M (2020) Standard Specification for Structural Steel Shapes
ASTM A1023/A1023M (2019) Standard Specification for
Stranded Carbon Steel Wire Ropes for General Purposes
ASTM B209 (2014) Standard Specification for
Aluminum and Aluminum-Alloy Sheet and Plate
ASTM B221 (2020) Standard Specification for
Aluminum and Aluminum-Alloy Extruded Bars, Rods, Wire, Profiles, and Tubes
ASTM D2136 (2002; R 2012) Coated Fabrics
- Low-Temperature Bend Test
ASTM E84 (2020) Standard Test Method for
Surface Burning Characteristics of Building Materials
NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION (NEMA)
NEMA AB 1 (2002) Molded-Case Circuit Breakers, Molded Case Switches, and Circuit- Breaker Enclosures
SECTION 01 11 00 PAGE 2
NEMA ICS 2 (2000; R 2020) Industrial Control and Systems Controllers, Contactors, and Overload Relays Rated 600 V
NEMA ICS 5 (2017) Industrial Control and
Systems: Control Circuit and Pilot Devices
NEMA ICS 6 (1993; R 2016) Industrial Control and
Systems: Enclosures
NEMA MG 1 (2018) Motors and Generators
UNDERWRITERS LABORATORIES (UL)
UL 698A (2018; Rev 2019) UL Standard for Safety Industrial Control Panels Relating to Hazardous (Classified) Locations
UL 1449 (2021) UL Standard for Safety Surge
Protective Devices
1.2 SYSTEM DESCRIPTION
Electrical Motor operated unit with manual override in case of power failure.
1.3 SUBMITTALS
Government approval is required for submittals with a "G" or "S" classification. Submittals not having a "G" or "S" classification are for information only. When used, a code following the "G" classification identifies the office that will review the submittal for the Government.
Submit the following:
SD-01 Preconstruction Submittals
Manufacturer's Qualifications; G
Installer's Qualifications; G
SD-02 Shop Drawings
Indicate pertinent dimensioning, anchorage methods, hardware locations and installation details specific to this project, sealed by the Door Manufacturer's Registered Professional Engineer;
Door Design; G
SD-03 Product Data
Provide general construction, component connections and details, electrical equipment, operation instructions and information.
Diagrams, performance curves and characteristic curves of equipment and systems.
SECTION 01 11 00 PAGE 3
Electric Operator; G
Motors; G
Doors; G
Controls; G
Door Fabric; G
Surge Protection Device (SPD); G
SD-10 Operation and Maintenance Data
Door Operation; G
Emergency and Routine Preventative Maintenance Plan; G
SD-11 Closeout Submittals
Acceptance Testing Procedure and Report; G
Manufacturer's Warranty; G
1.4 REGULATORY REQUIREMENTS
a. Electrical components UL/CUL listed.
b. Electrical enclosure NEMA approved and meet hazardous environmental requirements.
1.5 PERFORMANCE REQUIREMENTS
a. Panel to withstand high pressure and wind loads.
b. Panel to release upon accidental impact and be restored without tools or replacement parts.
c. Electric operator to be direct-drive—no counterbalance or springs.
d. Bottom bar to be wireless. Conform to railroad tracks as required
1.6 QUALITY ASSURANCE
Furnish high-speed roll doors and all components and accessories by one manufacturer.
1.7 FIELD MEASUREMENTS
Verify field measurements are indicated as shown on shop approved drawings.
1.8 COORDINATION
Coordinate the work with installation of electric power and locations and sizes of conduit.
SECTION 01 11 00 PAGE 4
1.9 WARRANTY
a. Two (2) year parts, one (1) year labor on the door.
b. SBR fabric material for the life of the door, labor limited to one (1) year.
c. Two (2) years on electrical, labor limited to one (1) year.
PART 2 PRODUCTS
2.1 PRODUCTS
a. Rytec Corporation Powerhouse SD high-speed rubber door.
b. Approved equal.
2.2 MATERIALS
Select materials based on durability, low maintenance, weather resistance and strength (permanent deformation from loading is not permitted). Comply with ASTM E84 for limited combustible construction for all door system materials.
2.2.1 Door Panel Fabric
a. Styrene butadiene rubber (SBR) panel 1/4” (6.35 mm) thick, made of two 1/8” (3.17 mm) thick layers, 70 durometer; sandwiched with 1-ply, 110lbs (50kg) polyester cord center.
b. Skived seams to connect SBR panel sections on doors under 24 feet wide
c. Panel includes bonded SBR beveled windlocks, providing normal resiliency and flexibility at temperatures ranging from -40° F to +180°F (-40°C to +85°C). Panels not using a SBR beveled windlock for wind or pressure retention will not be accepted.
d. Windlocks to be segmented (non-continuous) to allow the door panel to effectively release from the side frame in case of accidental impact.
e. Consult manufacturer for other fabric options.
2.2.2 Door Panel Wind and Pressure Resistance
The door design allows for the curtain to remain in the side frame guide in high wind and pressure situations.
2.2.3 Door Panel Other Characteristics
a. Vertical stripes of PET for reinforcement and visual safety awareness.
Doors without vertical stripes will not be accepted.
b. Standard color black.
c. Consult manufacturer for other panel materials and color options.
2.2.4 Door Header Truss
SECTION 01 11 00 PAGE 5
Reinforced truss design with angular frame made of steel.
2.2.5 Door Header Drum Roll
a. Fabricate minimum 8.5" (216 mm) outside diameter, steel tube with a wall thickness of 0.25” (6.35 mm) steel complying with ASTM A513.
b. Drive shafts within drum are constructed of 2.75” (69.85 mm) outside diameter steel shafts.
2.2.6 Door Header Idler Barrel
Front-mounted, fabric guiding (idler) barrel shall be constructed of minimum 4.5” (114.3 mm) outside diameter round tubing with a wall thickness of 0.13” (3.4 mm) to maximum 5.0” (127 mm) outside diameter round tubing with a wall thickness of 0.25” (6.35 mm) and supported by 2” (50.8 mm) diameter steel shafts.
2.2.7 Door Header End Plates
a. Constructed of minimum ¼” (6 mm) hot-rolled steel laser-cut plates with heavy-duty, self-aligning bearings with cast iron housings.
b. Bearings shall be load-rated at 14,000 lbs. (6350 kg) dynamic and 9,900 lbs. (4,490 kg) static.
2.2.8 Door Header Counterbalance System
Direct-drive operator only—no counterbalance. Any doors utilizing counterbalance, torsion springs or sprockets will not be accepted.
2.2.9 Side Frames
The structural columns consist of 5 x 2 x ¼” structural steel tubing, welded to a reinforced “Z” mounting bracket (0.22” thick steel) and hinged cover (0.18” thick steel).
2.2.10 Side Frames Wind Resistance
Windstops mounted at bottom of side columns maintain wind resistance in closed position.
2.2.11 Side Frames Paint
Painted with a durable, chemical and corrosion-resistant coating
2.2.11 Releasable Bottom Bar
a. Constructed of extruded aluminum and must be of a sufficient width and weight to maintain the bottom edge of the curtain parallel to the door threshold at all times. Doors using steel bottom bars will not be accepted.
b. Design allows for the bottom bar to release from the door without damage after accidental impact or sufficient windload. Doors requiring break-away center sections, notched bottom beams, shear bolts or knock-away sections will not be accepted.
SECTION 01 11 00 PAGE 6
c. After releasing, design allows for the bottom bar and panel to be restored with door controller. Doors requiring tools or replacement parts will not be accepted.
d. A minimum of 6” tall weatherproof rubber loop seal shall be made of EPDM and will be able to seal uneven finished floors.
e. Bottom bars with cords attached will not be accepted.
2.2.12 Wireless System
a. Wireless provides continuous and uninterruptible wireless signal which eliminates the need for cords on the bottom bar. Total frequency control eliminates interference.
b. Two-way communication ensures functioning wireless system. Doors without two-way communication to ensure functioning wireless system will not be accepted.
2.2.13 Control System
a. Digital controller housed in a NEMA-4X rated enclosure with factory set parameters.
b. Parameter changes and all door configurations can be made from the face of the control box, no exposure to high voltage.
c. Controls include a variable speed AC drive system capable of infinitely variable speed control in both the up and down direction.
d. Programmable inputs and outputs accommodate special control applications without the need for electrical components.
e. Self-diagnostic two-line vacuum fluorescent display (VFD) provides quick and straightforward installation, control adjustments and error reporting.
f. Control panels that require a portable computer unit, additional components, or other devices for programming and/or troubleshooting will not be accepted.
g. Control panels that require opening of the control box and reaching inside to make parameter changes will not be accepted.
h. Control panel (to be configurable in visible English, Spanish or French) communicates when the curtain is broken away and if necessary, how to bring the door back into operation.
2.2.14 Electric Operator
a. Door shall be electrically operated by a single direct-drive system. The motor and gearbox shall be designed for high-cycle operation. Basic operation features a manual chain hoist for non-powered operation.
b. Door must operate with an AC drive providing soft starting and soft stopping to reduce motor and brake wear. Doors without an AC drive will not be accepted.
SECTION 01 11 00 PAGE 7
c. Door to use absolute encoder to regulate door travel limits. Limits to be adjustable, without the use of tools, from the face of the control panel.
Doors using mechanical limit switches, pulse encoders or doors that require tools to access the operator in order to adjust limits will not be
d. Counterbalance System a. Direct-drive operator only. No counterbalance or torsion springs allowed in any size door.
2.2.15 Safety Features
a. One (1) in-line light curtain (mounted within side frame) projects a safety curtain directly in line with the panel, from the ground level to approximately 72” (1.82 m) in height. If an object interferes with the beams, the door must reverse automatically. Doors with light curtains mounted outside of the door line will not be accepted.
b. Four (4) threshold warning light strips include amber and red LED lights located on the front and back of both the left and right side columns to indicate door closing for added safety at the threshold. All wiring for warning lights to be concealed within the door construction.
c. Bottom bar to include a failsafe electric edge that must automatically reverse the door upon bottom edge impact.
d. 4Bottom bar will contain a kill switch that ceases door movement when the door is impacted. Doors which movement continues after impact will not be
2.2.16 Speed
a. Door to operate at a variable speed up to 50 inches per second, maximum speed is dependent on the size of the door and the type of controller and operator.
b. Door to use absolute encoder to regulate door travel limits. Limits to be adjustable, without the use of tools, from the face of the control panel.
Doors using mechanical limit switches, pulse encoders or doors that require tools to access the operator in order to adjust limits will not be
PART 3 EXECUTION
3.1 EXAMINATION
Verify that opening sizes, tolerances and conditions are acceptable.
3.2 INSTALLATION
a. Install door assembly in accordance with manufacturer's instructions.
b. Use anchorage devices to securely fasten assembly to wall constructions and building framing without distortion or stress.
c. Fit and align assembly including hardware; level and plumb to provide smooth operation.
SECTION 01 11 00 PAGE 8
d. Coordinate installation of electrical service. Complete wiring from disconnect to unit components.
e. Touch-up paint on frame and other painted surfaces in accord with painting section.
f. Upon completion of installation, including work by other trades, lubricate, test and adjust doors to operate in accordance with manufacturer's product data. Final adjustments shall be made by manufacturer's authorized representative.
g. Protect finished installations until Date of Substantial Completion.
Repair damage to door panel, hardware and operators.
3.3 ADJUSTING
a. Adjust door and operating assemblies.
b. Test and adjust door, if necessary, for proper operations.
3.4 CLEANING
Clean both the interior and exterior of doors after the completion of erection.
3.5 EXTRA MATERIALS
Supply a door fabric patch kit with approximately 45 square feet of fabric for each hangar door and all other materials required for door panel repair.
Provide all unique tools required to maintain the door system. Provide a patch kit with color matched fabric and associated repair materials and tools.
-- End of Section –
File details come from the government source that posted it. Updated .