Attachment 01 - Statement of Objectives - Frequency Converter.pdf
PDF 118 KB Posted
- Attached to
- RAF Akrotiri - Frequency Converter
- Solicitation number
- FA557026QBA02
About this file
This is a Statement of Objectives (SOO) issued by the Department of the Air Force, 1st Expeditionary Rescue Squadron Mission Support Flight (USAFE), dated 01 September 2026, for providing power infrastructure to a new facility at RAF Akrotiri, Cyprus.
The contractor shall supply all labor, equipment, and materials to deliver the following core requirements: one frequency converter converting 50Hz to 60Hz with supply power of 220/415V, 50Hz, 3-Phase and output of 120/208V, 200 Amp, 60Hz, 3-Phase; one weatherproof distribution board rated for 120/208V, 200 Amp, 60Hz, 3-Phase with a deep panel measuring approximately 6 to 8 inches depth capable of accommodating a 100 Amp, 5-Wire Type-G cable connector; one 200 Amp, 3-Phase main breaker compatible with the distribution panel; one 100 Amp, 3-Phase breaker compatible with the distribution panel; and all associated wire and connectors between the frequency converter and distribution board. All components must be rated to withstand external environmental conditions including wind, dust, and rain. The SOO includes an optional line item for one additional frequency converter with identical specifications (50Hz to 60Hz conversion, 220/415V, 50Hz, 3-Phase supply power, and 120/208V, 200 Amp, 60Hz, 3-Phase load). No response dates, award dates, pricing information, or set-asides are specified in this SOO document.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
DEPARTMENT OF THE AIR FORCE
1ERS Mission Support Flight (USAFE)
01 September 2026
Statement of Objectives (SOO) New Facility Power
1. RAF Akrotiri, Cyprus has an urgent need to provide power to a new facility. The contractor shall provide all labor, equipment, and materials to deliver equipment that meets or exceeds the following minimum specifications.
1. One Frequency Converter, 50Hz to 60Hz
a. Supply power: 220/415V, 50Hz, 3-Phase
b. Load: 120/208V, 200 Amp, 60Hz, 3-Phase
2. One Weatherproof distribution board
a. Rated for: 120/208V, 200 Amp, 60Hz, 3-Phase
b. Needs to be a deep panel, approximately 6 to 8 inches
c. Example: Main load cable coming out of this panel will be a 100 Amp, 5- Wire, Type-G cable with appropriate connector must be able to fit
3. 200 Amp, 3-Phase Main Breaker compatible with distribution panel above
4. 100 Amp, 3-Phase, Breaker also compatible with distribution panel above
5. All associated wire and connectors between Frequency Converter and distribution board
6. All parts need to be rated to withstand outside elements to include wind, dust and rain.
Option 01:
One additional Frequency Converter, 50Hz to 60Hz
a. Supply power: 220/415V, 50Hz, 3-Phase
b. Load: 120/208V, 200 Amp, 60Hz, 3-Phase
END OF SOO