Attachment 003 - Plans and Drawings.pdf

PDF 1 MB Posted

Attached to
GAOA Bessey Group Electrical
Solicitation number
1282B125R0009
Issued by

About this file

This is a set of construction drawings for an electrical upgrade project at the Bessey Group and Cedar Loop Campgrounds in the Nebraska National Forests and Grasslands, Bessey Ranger District and Nursery. The drawings are dated July 1, 2024 and include 5 sheets covering electrical demolition plans, site plans, one-line diagrams, and electrical details.

The drawings detail the removal and replacement of electrical infrastructure including RV pedestals, panels, transformers, and underground electrical lines. Key specifications include installation of new 50-amp RV pedestals, a new 75KVA pad mount transformer, electrical panels, and associated conduit and wiring. The plans show specific demolition requirements for existing electrical components and precise installation locations for new equipment. Detailed electrical diagrams indicate power distribution requirements, panel schedules, and mounting specifications. The work encompasses both the Group Campground area and Cedar Loop Campground, with detailed site plans showing existing facilities and new installation locations.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

ELECTRICAL MOTOR

SURFACE MOUNTED POWER PANEL

ELECTRICAL SYMBOLS & ABBREVIATIONS

SURGE PROTECTION DEVICESPD

HATCHING INDICATED DEVICES TO BE REMOVED.

DISCONNECT SWITCH

PB PULL BOX

ELECTRICAL PEDESTAL TO BE REMOVED

NEW ELECTRICAL PEDESTAL

UNDERGROUND ELECTRICAL TO BE REMOVED OR ABANDONED

UNDERGROUND ELECTRICALUGE

ELECTRICAL SPLICE BOX

EXISTING UNDERGROUND ELECTRICAL

ELECTRICAL METER SOCKET

ELECTRICAL UTILITY TRANSFORMER

Project No:Sub Sheet:

OF

Sheet

Sheet Title:

GAOA FY 22 GROUP ELECTRICAL UPGRADE DESIGN

Design:

Drawn:

Checked:

Date:

FLE

EMK

FLE

07/01/2024

Forest Nebraska National Forests and Grasslands

U.S. Department of Agriculture Forest Service

R-2 Rocky Mountain Region Bessey Ranger District

GAOA 22 BESSEY GROUP ELECTRICAL UPGRADE DESIGN

NEBRASKA NATIONAL FORESTS and GRASSLANDS BESSEY RANGER DISTRICT and NURSERY

UNITED STATES DEPARTMENT OF AGRICULTURE

CONSTRUCTION DRAWINGS FOR

FOREST SERVICE

REGION 2

COVER SHEET

GROUP/CEDAR LOOP CAMPGROUNDS

Sheet List Table

NUMBER TITLE

GENERAL

1 COVER SHEET

ELECTRICAL

ELECTRICAL DEMOLITION SITE PLAN

ELECTRICAL SITE PLAN

4 ELECTRICAL ONE-LINE DIAGRAMS

5 ELECTRICAL DETAILS

Attachment #3- Plans and Drawings

X

X

X X

X X

X X

X X

X X

X

W

X

X

X

X

X

X

X

X

X

X

X

X

X X

X

X X

X X

X X

X

X X

X X

X X

X

X X

X

X

X

X

X

EXISTING

STREET

LIGHT

EXISTING LOAD CENTER/WELL

STARTER ENCLOSURE

EXISTING TRANSFORMER

AND DISTRIBUTION

BOARD LOCATION

MAIN ELECTRICAL

SERVICE LINE

EXISTING

STREET

LIGHT

EXISTING SPLICE BOX

EXISTING

AREA LIGHT

G1

G2

G3

G4

G5

G6

G7 G8

G9

G10

10 2

EXISTING

TOILETS12 EXISTING

WELL

EXISTING

SHELTER

PANEL

ELECTRICAL DEMOLITION SITE PLAN

GROUP/CEDAR LOOP CAMPGROUNDS

Project No:Sub Sheet:

OF

Sheet

Sheet Title:

GAOA FY 22 GROUP ELECTRICAL UPGRADE DESIGN

Design:

Drawn:

Checked:

Date:

FLE

EMK

FLE

07/01/2024

Forest Nebraska National Forests and Grasslands

U.S. Department of Agriculture Forest Service

R-2 Rocky Mountain Region Bessey Ranger District

SHEET KEYNOTES

1. EXISTING 30 AMP RV PEDESTAL TO BE REMOVED AND SALVAGED FOR

OWNER. EXISTING CONDUCTORS TO BE REMOVED TO BELOW GRADE AND

ABANDONED.

2. EXISTING 50 AMP RV PEDESTAL TO BE REMOVED AND SALVAGED FOR

OWNER. EXISTING CONDUCTORS TO BE REMOVED TO BELOW GRADE AND

ABANDONED.

3. EXISTING CONDUCTORS TO BE DISCONNECTED, REMOVED TO BELOW

GRADE AND ABANDONED.

4. EXISTING ELECTRICAL PANEL AND WELL STARTER ENCLOSURE WITH

SUPPORT STRUCTURE TO BE REMOVED. WELL STARTER ENCLOSURE TO

BE SALVAGED FOR RELOCATION TO SHELTER.

5. EXISTING SHELTER SPLICE BOX TO BE REMOVED.

6. EXISTING SHELTER ELECTRICAL PANEL TO REMAIN AS IS. REMOVE FEEDER

BACK TO SPLICE BOX.

7. EXISTING ELECTRICAL PANELS/ SPLICE BOX/SERVICE DISCONNECT AND

SUPPORT STRUCTURE TO BE REMOVED. EXISTING CONDUCTORS TO BE

REMOVED TO BELOW GRADE AND ABANDONED.

8. EXISTING UTILITY TRANSFORMER TO BE REPLACED WITH NEW BY UTILITY

COMPANY.

9. EXISTING UTILITY PRIMARY LINE TO REMAIN AS IS.

10. EXISTING AREA LIGHT TO REMAIN AS IS. EXISTING UNDERGROUND

CONDUCTORS TO BE DISCONNECTED AND REMOVED TO BELOW GRADE

AND ABANDONED.

11. EXISTING STREET LIGHT TO REMAIN AS IS. EXISTING UNDERGROUND

CONDUCTORS TO BE DISCONNECTED AND REMOVED TO BELOW GRADE

AND ABANDONED.

12. EXISTING CONDUCTORS TO BE REMOVED FROM CONDUIT. CONDUIT TO BE

ABANDONED IN PLACE.

GENERAL SHEET NOTES

A. CONTRACTOR SHALL BORE UNDER ANY PAVED SURFACES.

B. CONTRACTOR SHALL REMOVE FROM SITE ANY EXCESS SOIL AFTER

PROPER BACKFILL AND SETTLING OF TRENCH AND PADS.

C. ANY "AID-TO-CONSTRUCTION" FEES FROM UTILITY WILL BE PAID DIRECTLY

BY CONTRACTOR.

D. CONTRACTOR SHALL BASE BID ON FIELD MEASUREMENTS.

E. CONTRACTOR SHALL PROVIDE AS-BUILT DRAWINGS AT END OF

CONSTRUCTION PRIOR TO FINAL PAYMENTS.

F. CONTRACTOR SHALL LOCATE AND PROTECT ALL EXISTING UTILITIES

DURING TRENCHING/BORING ACTIVITIES.

G. OWNER SHALL HAVE FIRST RIGHT TO REFUSAL FOR ALL REMOVED PANELS

AND RV PEDESTALS. ANY ITEMS NOT WANTED BY OWNER SHALL BE

REMOVED FROM SITE AND DISPOSED OF PROPERLY BY CONTRACTOR.

H. COORDINATE ELECTRICAL SERVICE MODIFICATIONS WITH CUSTER PUBLIC

POWER.

I. ANY EXISTING ABANDONED DIRECT BURY CONDUCTORS SHALL BE

REMOVED IF LOCATED IN SAME LOCATION AS NEW CONDUIT PATH.

SCALE: 1" = 60'-0"1 ELECTRICAL DEMOLITION SITE PLAN

X

X X

X X

X X

X X

X X

X

W

W

X

X

X

X

X

X

X

X

X

X

X

X

X X

X

X X

X X

X X

X

X X

X X

X X

X

X X

X

X

X

X

X

EXISTING

STREET

LIGHT

MAIN ELECTRICAL

SERVICE LINE

EXISTING

STREET

LIGHT

EXISTING

AREA LIGHT

G1

G2

G3

G4

G5

G6

G7 G8

G9

G10

U G

E

UGE

UGE

U G

E

UGE

UGE

UGE

UGE UGE

U G

E

UG

E

UGE

UGE

UGE

UGE

U G

E

U G

E

UGE

UGE

UGE

U G

E

UGE

UGE

U G

E

EXISTING

TOILETS

UGE

C-9

G-6,8

G-5,73 G-2,4

NEW TRANSFORMER AND

DISTRIBUTION BOARD

C AND G LOCATION

G-1,3

PB

C-11

C-2,4 2

C-10 4

C-5,7 2

C-6,8 2

C-1,32

UGE

NEW ELECTRICAL

PANEL S1

RELOCATED WELL

STARTER/TIMER

ENCLOSURE

EXISTING

SHELTER

PANEL S2

EXISTING WELL

PANEL FEEDERUGE

UGE

ELECTRICAL SITE PLAN

GROUP/CEDAR LOOP CAMPGROUNDS

Project No:Sub Sheet:

OF

Sheet

Sheet Title:

GAOA FY 22 GROUP ELECTRICAL UPGRADE DESIGN

Design:

Drawn:

Checked:

Date:

FLE

EMK

FLE

07/01/2024

Forest Nebraska National Forests and Grasslands

U.S. Department of Agriculture Forest Service

R-2 Rocky Mountain Region Bessey Ranger District

SCALE: 1" = 60'-0"1 ELECTRICAL SITE PLAN

SHEET KEYNOTES

1. PROVIDE NEW 50 AMP RV PEDESTAL PER SPECIFICATIONS AND DETAILS.

2. PROVIDE 3-#4/0 AWG AL, #4 GND AL IN 2" CONDUIT ENTIRE CIRCUIT AND

CONNECT TO NEW BREAKER ON CIRCUIT SHOWN.

3. PROVIDE 3-#1/0 AWG AL, #6 GND AL IN 2" CONDUIT ENTIRE CIRCUIT AND

CONNECT TO NEW BREAKER ON CIRCUIT SHOWN.

4. PROVIDE 2-#8 AWG CU, #8 GND CU IN 3/4" CONDUIT ENTIRE CIRCUIT AND

CONNECT TO NEW BREAKER ON CIRCUIT SHOWN.

5. PROVIDE NEW JUNCTION BOX IN EXISTING RISER CONDUIT ON POLE TO

LOOP NEW CIRCUIT THROUGH. SPLICE INTO EXISTING RISER CONDUCTORS.

6. PROVIDE AN IN-GRADE PULL BOX TO CAPTURE EXISTING DIRECT BURY

CONDUCTORS FOR TOILET FACILITY AND CONNECT TO NEW CONDUCTORS.

PROVIDE 2-#12 AWG CU, #12 GND CU IN 3/4" CONDUIT FROM PULL BOX AND

CONNECT TO NEW BREAKER ON CIRCUIT SHOWN.

7. PROVIDE 2-#12 AWG CU, #12 GND CU IN 3/4" CONDUIT AND CONNECT TO

NEW BREAKER ON CIRCUIT SHOWN. CONNECT TO EXISTING LIGHT SWITCH

BOX ON POLE.

8. CONNECT NEW CIRCUIT TO EXISTING JUCTION BOX ON POLE.

9. PROVIDE 3-#2 AWG AL, #6 GND AL IN 1-1/4" CONDUIT FROM NEW PANEL S1

AND CONNECT TO NEW BREAKER ON CIRCUIT SHOWN.

10. PROVIDE 2-#12 AWG CU, #12 GND CU IN 3/4" CONDUIT. CONNECT TO WELL

PUMP AND RELOCATED WELL PUMP STARTER ENCLOSURE.

11. PROVIDE 2-#12 AWG CU, #12 GND CU IN 3/4" CONDUIT FROM RELOCATED

WELL PUMP STARTER ENCLOSURE AND CONNECT TO NEW 20/2 BREAKER IN

PANEL S1.

12. PROVIDE 3-#8 AWG CU, #10 GND CU IN 3/4" CONDUIT FROM EXISTING

SHELTER LOAD CENTER S2 AND CONNECT TO NEW 40/2 BREAKER IN PANEL

S1. PROVIDE GROUND BAR IN EXISTING LOAD CENTER S2 AND SEPARATE

BRANCH GROUND CONDUCTORS FROM NEUTRAL BUS.

13. MOUNT NEW PANEL S1 AND RELOCATED WELL PUMP STARTER ENCLOSURE

ON EXTERIOR OF EXISTING SHELTER.

GENERAL SHEET NOTES

A. CONTRACTOR SHALL BORE UNDER ANY PAVED SURFACES.

B. CONTRACTOR SHALL REMOVE FROM SITE ANY EXCESS SOIL AFTER

PROPER BACKFILL AND SETTLING OF TRENCH AND PADS.

C. ANY "AID-TO-CONSTRUCTION" FEES FROM UTILITY WILL BE PAID DIRECTLY

BY CONTRACTOR.

D. CONTRACTOR SHALL BASE BID ON FIELD MEASUREMENTS.

E. CONTRACTOR SHALL PROVIDE AS-BUILT DRAWINGS AT END OF

CONSTRUCTION PRIOR TO FINAL PAYMENTS.

F. CONTRACTOR SHALL LOCATE AND PROTECT ALL EXISTING UTILITIES

DURING TRENCHING/BORING ACTIVITIES.

G. OWNER SHALL HAVE FIRST RIGHT TO REFUSAL FOR ALL REMOVED PANELS

AND RV PEDESTALS. ANY ITEMS NOT WANTED BY OWNER SHALL BE

REMOVED FROM SITE AND DISPOSED OF PROPERLY BY CONTRACTOR.

H. COORDINATE ELECTRICAL SERVICE MODIFICATIONS WITH CUSTER PUBLIC

POWER.

I. ANY EXISTING ABANDONED DIRECT BURY CONDUCTORS SHALL BE

REMOVED IF LOCATED IN SAME LOCATION AS NEW CONDUIT PATH.

SCALE: 1" = 20'-0"2 ENLARGED ELECTRICAL SITE PLAN

EXISTING 37.5KVA, PAD MOUNT

TRANSFORMER

120/240V, 1Ø, 3W

EXISTING

METER

SOCKET

EXISTING 200 AMP

MAIN BREAKER

ENCLOSURE

EXISTING

200A MAIN

PANEL EXISTING

LOAD

CENTER #1

EXISTING

SPLICE

BOX

EXISTING

100 AMP

BREAKER

ENCLOSURE

EXISTING

SHELTER

SPLICE BOX

EXISTING

SHELTER

LOAD

CENTER #2

TO REMAIN

EXISTING

SITE LOAD

CENTER #3

SALVAGE AND RELOCATE

EXISTING WELL STARTER

ENCLOSURE W/TIMER SWITCH

1 HP

EXISTING WELL

PUMP TO REMAIN

SITE 10

PEDESTAL

SITE 9 STREET LIGHT

SITE 11

PEDESTAL

SITE 12

PEDESTAL

SITE 13

PEDESTAL

SITE 9

PEDESTAL

AREA LIGHT

TOILET LIGHTS

SITE 3

PEDESTAL

SITE 2

PEDESTAL

STREET LIGHT

SITE 4

PEDESTALSITE 8

PEDESTAL

SITE G3

PEDESTAL

SITE G4

PEDESTAL

SITE G5

PEDESTAL

SITE G6

PEDESTAL

SITE G7

PEDESTAL

SITE G8

PEDESTAL

SITE G9

PEDESTAL

SITE G1

PEDESTAL

SITE G2

PEDESTAL

SITE G10

PEDESTAL

SITE 7

PEDESTAL

SITE 6

PEDESTAL

NEW 75KVA PAD MOUNT

TRANSFORMER

120/240V, 1PH, 3W

BY UTILITY COMPANY

NEW METER SOCKET/

CONDUIT/ CABLING BY

UTILITY COMPANY

PANEL

'C'

STREET LIGHT

SITE 9 STREET

LIGHT

AREA LIGHT

TOILET LIGHTS

PANEL

'G'

PANEL

'S1'

EXISTING

SHELTER

LOAD

CENTER 'S2'

RELOCATED

WELL STARTER

ENCLOSURE

W/TIMER SWITCH

1 HP

WELL

PUMP

SITE G3

PEDESTAL

SITE G1

PEDESTAL

SITE G2

PEDESTAL

SITE G4

PEDESTAL

SITE G7

PEDESTAL

SITE G5

PEDESTAL

SITE G6

PEDESTAL

SITE G8

PEDESTAL

SITE G9

PEDESTAL

SITE G10

PEDESTAL

SITE 2

PEDESTAL

SITE 4

PEDESTAL

SITE 3

PEDESTAL

SITE 6

PEDESTAL

SITE 8

PEDESTAL

SITE 7

PEDESTAL

SITE 11

PEDESTAL

SITE 9

PEDESTAL

SITE 10

PEDESTAL

SITE 12

PEDESTAL

SITE 13

PEDESTAL

#2/0 #2/0

PB

2 SETS OF 3-#350 MCM CU IN 3" C.

UGE UGE

UGE

UGE

UGE

UGE UGE

UGEUGE

UGE

UGE

UGE UGE

UGEUGE

UGE

UGE

UGE UGE

UGE

UGEUGEUGEUGE

UGE UGE UGE UGE

UGE

UGE

PANEL NO.

SERVICE VOLTAGE

MAIN BREAKER SIZE

SITES 2,3,4

SITES 9,10,11

AREA LIGHT

TOILET LIGHTS

SPACE

SPACE

SPACE

SPACE

SPACE

SPACE

TOTAL PHASE A:

TOTAL PHASE C:

DESCRIPTION

553.8 554.2

C 120/240-1Ø 600A

AMPS

AMPS

66.5 66.5

C/B

AMP

150/2

150/2

20/1 20/1

KVA

KVA

TYPE

PHASE BUS RATING

NEUTRAL BUS RATING

VOLT AMPS

A

18000

18000

DISTRIBUTION

C

18000

18000

CKT.

NO.

600A 600A

CKT.

NO.

TOTAL CONNECTED LOADS:

ESTIMATED DEMAND LOADS:

VOLT AMPS

A

18000

12000

132.8

133.0

C

18000

12000

KVA

KVA

MOUNTING

SHORT CIRCUIT RATING

C/B

AMP

150/2

100/2

20/1

Surface 65kAIC

SITES 6,7,8

SITES 12,13

STREET LIGHTS

SPACE

SPACE

SPACE

SPACE

SPACE

SPACE

SPACE

DESCRIPTION

I-LINE STYLE

NEMA 3R

PANEL NO.

SITES G1,G2,G3,G4

SITES G9,G10

SPACE

SPACE

SPACE

SPACE

SPACE

SPACE

SPACE

SPACE

TOTAL PHASE A:

TOTAL PHASE C:

DESCRIPTION

533.6 533.6

G 120/240-1Ø 600A

AMPS

AMPS

64.0 64.0

C/B

AMP

200/2

100/2

KVA

KVA

TYPE

PHASE BUS RATING

NEUTRAL BUS RATING

VOLT AMPS

A

24000

12000

DISTRIBUTION

C

24000

12000

CKT.

NO.

600A 600A

CKT.

NO.

TOTAL CONNECTED LOADS:

ESTIMATED DEMAND LOADS:

VOLT AMPS

A

24000

126.9

128.1

C

24000

KVA

KVA

MOUNTING

SHORT CIRCUIT RATING

C/B

AMP

200/2

60/2

65kAIC

SITES G5,G6,G7,G8

SHELTER PANEL S1

SPACE

SPACE

SPACE

SPACE

SPACE

SPACE

SPACE

SPACE

DESCRIPTION

I-LINE STYLE

NEMA 3R

PANEL NO.

EXISTING SHELTER PANEL S2

SPACE

SPACE

SPACE

SPACE

SPACE

SPACE

SPACE

SPACE

SPACE

SPACE

TOTAL PHASE A:

TOTAL PHASE C:

DESCRIPTION

33.6 33.6

S1 120/240-1Ø

MLO

AMPS

AMPS

4.0 4.0

C/B

AMP

40/2

KVA

KVA

TYPE

PHASE BUS RATING

NEUTRAL BUS RATING

VOLT AMPS

A

DISTRIBUTION

C

CKT.

NO.

100A 100A

CKT.

NO.

TOTAL CONNECTED LOADS:

ESTIMATED DEMAND LOADS:

VOLT AMPS

A

6.9

8.1

C

KVA

KVA

MOUNTING

SHORT CIRCUIT RATING

C/B

AMP

20/2

22kAIC

WELL PUMP (1 HP)

SPACE

SPACE

SPACE

SPACE

SPACE

SPACE

SPACE

SPACE

SPACE

SPACE

DESCRIPTION

NEMA 3R

NOT TO SCALE

ELECTRICAL ONE-LINE DIAGRAM - EXISTING

Project No:Sub Sheet:

OF

Sheet

Sheet Title:

GAOA FY 22 GROUP ELECTRICAL UPGRADE DESIGN

Design:

Drawn:

Checked:

Date:

FLE

EMK

FLE

07/01/2024

Forest Nebraska National Forests and Grasslands

U.S. Department of Agriculture Forest Service

R-2 Rocky Mountain Region Bessey Ranger District

ELECTRICAL ONE-LINE DIAGRAMS

GROUP/CEDAR LOOP CAMPGROUNDS

NOT TO SCALE

ELECTRICAL ONE-LINE DIAGRAM - NEW

2 1/2" RIGID GALVANIZED

STEEL CONDUIT AND

GALVANIZED UNISTRUT

MOUNTING BRACKET

8"Ø CONCRETE PIER

TO 48" BELOW GRADE

(TYP. FOR THREE)

9'X5'X4"

CONCRETE

PAD

#4 BAR (TYP.)

NOT TO SCALE1 DOUBLE PANEL MOUNTING DETAIL

9'X5' CONCRETE PAD

3' -0

9'-0"

5' -0

"12"

10"

SUPPORT STRUCTURE

ELECTRICAL PANEL

32"

NOT TO SCALE2 DOUBLE PANEL PLAN DETAIL

12"

ELECTRICAL PANEL

3'-6"

CONCRETE

CONTROL JOINT

NEMA 3R PANEL

42" WIDE X 68" TALL

METAL CAP (TYP.)

FINISHED GRADE

MIN.

6"

OR

930"

MIN.

~ COPPER GROUND WIRE

CONNECT TO GROUND ROD.

(SIZE PER PLAN)

BILL OF MATERIAL

ITEM

GROUND WIRE, STRANDED DIRECT-BURRIED COPPER

FOR EACH ADDITIONAL CABLE CONNECTION ADD 1 CONNECTOR.

CONNECTOR, #8 SOLID THRU #4 STR. CABLE TO GND. ROD, BURNDY #GAR-644C

CONNECTOR, #2/0 SOLID THRU 250KCMIL STR. CABLE TO GND. ROD, BURNDY #GAR-6429

CONNECTOR, #4 SOLID THRU #2/0 STR. CABLE TO GND. ROD, BURNDY #GAR-6426

GROUND ROD, 3/4" DIA. x 10' LONG, COPPER CLAD STEEL

NOT TO SCALE3 GROUND ROD INSTALLATION

6"

MIN.

LEAVE RAKE FINISH FOR

EXPOSED EARTH AREAS.

2' -0

BACKFILL SHALL BE WITH CLEAN, DEBRIS

FREE EARTH (ABSOLUTELY NO ROCKS)

COMPACTED TO 90% OF UNDISTURBED

EARTH IN MAXIMUM 6" LIFTS.

SCHEDULE 40 PVC CONDUIT

PROVIDE UNDERGROUND

WARNING TAPE

M

IN

NOT TO SCALE5 TRENCH DETAIL

EXPANSION COUPLING

2' -0

" M

IN

PVC CONDUIT

(SCHEDULE 40)

GRADE LINE

GALVANIZED RIGID

STEEL CONDUIT

GALVANIZED RIGID

STEEL CONDUIT ABOVE

GRADE

ELECTRICAL DEVICE/

PANEL/DISCONNECT

M

IN

1'

-0

EXPOSED CONDUIT DETAIL

NOT TO SCALE6

A A

SECTION A-A

10" 15" 12"

A B C

APPROXIMATE DIMENSIONS

4"MIN.

A

C

B

" M

IN

. G

R A

V E

L O

R C

R U

S H

E D

R O

C K

6" M

IN

NOTES

9. PULL BOX COVERS SHALL BE OF HEAVY-DUTY

CONSTRUCTION TO WITHSTAND THE STRUCTURAL

REQUIREMENTS OF THE SPECIFICATIONS. COVERS SHALL

FIT SUFFICIENTLY TIGHT TO PREVENT THE ENTRANCE OF

RUN-OFF WATER. COVERS SHALL BE EMBOSSED WITH AN

ANTI-SLIP SURFACE, THE MANUFACTURER'S NAME AND THE

LOGO "ELECTRIC". COVERS SHALL BE HELD SECURELY IN

PLACE BY TWO OR MORE 3/8" (MIN. DIA.) STAINLESS STEEL

HEX HEAD BOLTS WITH FLAT WASHER. BOLTS SHALL BE

HELD CAPTIVE TO THE COVER. ALL COVERS SHALL BE

EQUIPPED WITH A RECESSED "LIFT PIN" AND HAVE A

MINIMUM 0.50 COEFFICIENT OF FRICTION SKID RESISTANT

SURFACE.

10. EACH PULL BOX ASSEMBLY (BOX WITH HEAVY-DUTY COVER

SECURELY ATTACHED) SHALL CONFORM TO ALL TEST

PROVISIONS AND REQUIREMENTS FOR TIER 15

APPLICATIONS AS OUTLINED IN THE LATEST ISSUE OF THE

ANSI/SCTE 77 2002 STANDARD TITLED "SPECIFICATION FOR

UNDER GROUND ENCLOSURE INTEGRITY". INDEPENDENT

THIRD-PARTY TEST REPORTS TOGETHER WITH

CERTIFICATION THAT ALL TEST PROVISIONS OF THE

ANSI/SCTE 77 2002 STANDARD HAVE BEEN MET WILL BE

REQUIRED FOR EACH TYPE OF PULL BOX BEING FURNISHED.

ALL TESTS SHALL BE DATED AND SIGNED BY A REGISTERED

PROFESSIONAL ENGINEER AND SHALL BEAR THE

LETTERHEAD OF THE TESTING AGENCY.

1. ACCESS DUCTS, BENDS AND/OR SWEEPS, ARE SUBSIDIARY

TO THE ITEM "PULL BOX, TYPE PB".

2. FILL MATERIAL SHALL BE GRAVEL OR CRUSHED ROCK

COMPOSED OF CLEAN, HARD, DURABLE AND UNCOATED

3. PROLONGED EXPOSURE OF THE PULL BOX AND COVER TO

SUNLIGHT, COMMON ICE MELTING CHEMICALS OR

FERTILIZERS SHALL NOT CAUSE SIGNIFICANT DAMAGE TO

THE PULL BOX OR COVER, OR IMPAIR ITS FUNCTION.

4. CONDUIT TERMINATIONS IN PULL BOX SHALL BE FITTED WITH

BELL OR FLARED END.

5. CONCRETE SHALL BE CLASS 47B-3000.

6. PULL BOXES ARE IN GROUND, GRADE LEVEL ENCLOSURES

INTENDED TO BE INSTALLED WHERE NON-DELIBERATE

VEHICULAR TRAFFIC IS ANTICIPATED.

7. PULL BOX ILLUSTRATIONS ARE TYPICAL AND ARE NOT

INTENDED TO LIMIT DESIGN. BOXES OF SQUARE OR

CIRCULAR PLAN-SECTION AND OF EQUAL OR GREATER

VOLUME ARE ACCEPTABLE. A MINIMUM DEPTH OF 18 INCHES,

MUST BE MAINTAINED.

8. THE PULL BOX ENCLOSURES (BOX AND COVER) SHALL BE

NON-METALLIC AND GREEN OR GRAY IN COLOR.

NOT TO SCALE4 IN-GRADE PULL BOX DETAIL

Project No:Sub Sheet:

OF

Sheet

Sheet Title:

GAOA FY 22 GROUP ELECTRICAL UPGRADE DESIGN

Design:

Drawn:

Checked:

Date:

FLE

EMK

FLE

07/01/2024

Forest Nebraska National Forests and Grasslands

U.S. Department of Agriculture Forest Service

R-2 Rocky Mountain Region Bessey Ranger District

ELECTRICAL DETAILS

GROUP/CEDAR LOOP CAMPGROUNDS

File details come from the government source that posted it. Updated .