Attachment 0006 2022-0292 Appendix E - Asbestos Report.pdf
PDF 612 KB Posted
- Attached to
- Building 139 Roof and Exterior Repair
- Solicitation number
- W519TC-23-R-2051
About this file
This document is an asbestos sampling report for Building 139 at Rock Island Arsenal. Samples were taken from various roof materials and window glazing on September 17, 2021. Test results found asbestos present in samples of shingle-like flashing around the perimeter of the roof at levels of 2-7% chrysotile asbestos. Samples of tar-like sealants and patches associated with the flashing also tested positive for asbestos. All other roof material and window glazing samples did not contain detectable asbestos.
The related federal contract opportunity is solicitation number W519TC-23-R-2051 for repair work to Building 139's roof and exterior at Rock Island Arsenal. The Department of the Army Materiel Command Contracting Command is the issuing agency. The solicitation seeks offers for roof and exterior repairs, with consideration given to the asbestos findings detailed in the sampling report.
View the file
Other files
Show all 18
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SAMPLE
NUMBER
139R-21-FT1
139R-21-FT2
139R-21-FT3
139R-21-Fl1
139R-21-Fl2
139R-21-Fl3
139R-21-FS1
139R-21-FS2
139R-21-FS3
139R-21-TS1
139R-21-TS2
139R-21-TS3
139R-21-TS4
139R-21-P1
139R-21-WGSW
139R-21-WGSMid
139R-21-WGSE
139R-21-WGNW
DATE
9/17/2021
9/17/2021
9/17/2021
9/17/2021
9/17/2021
9/17/2021
9/17/2021
9/17/2021
9/17/2021
9/17/2021
9/17/2021
9/17/2021
9/17/2021
9/17/2021
9/17/2021
9/17/2021
9/17/2021
9/17/2021
Asbestos Sampling/Testing Log (PLM- Bulk)
Bldg. 139 - Roof materials
September 21, 2021
MATERIAL
TYPE
Field Tar
Field Tar
Field Tar
Tan/Brown insulation under Field Tar
Tan/Brown insulation under Field Tar
Tan/Brown insulation under Field Tar
Shingle like flashing around perimeter of roof
Shingle like flashing around perimeter of roof
Shingle like flashing around perimeter of roof
Tar like sealant associated with above flashing material
Tar like sealant associated with above flashing material
Tar like sealant associated with above flashing material
Tar like sealant around stack on north side of roof
Tar like patch in edge of northwest side of roof
Window glazing
Window glazing
Window glazing
Window glazing
BLDG.
NO.
AREA
NW Roof
North, Middle Roof
NE Roof
NW Roof
North, Middle Roof
NE Roof
NW Roof
North, Middle Roof
NE Roof
NW Roof
North, Middle Roof
NE Roof
Stack northside of roof
Patch on north side
Southwest area of upper windows
South Middle area of upper windows
Southeast area of upper windows
Northwest area of upper windows
CORL 13.0-4
RESULTS s.o. P.O.#
No Asbestos 1326-3 21-2492
Detected
No Asbestos 1326-3 21-2492
Detected
No Asbestos 1326-3 21-2492
Detected
No Asbestos 1326-3 21-2492
Detected
No Asbestos 1326-3 21-2492
Detected
No Asbestos 1326-3 21-2492
Detected
No Asbestos 1326-3 21-2492
Detected
No Asbestos 1326-3 21-2492
Detected
2%Asbestos 1326-3 21-2492
Chrysotlle
7%Asbestos 1326-3 21-2492
Chrysotile
7%Asbestos 1326-3 21-2492
Chrysotile
4% Asbestos 1326-3 21-2492
Chrysotile
No Asbestos 1326-3 21-2492
Detected
No Asbestos 1326-3 21-2492
Detected No Asbestos
1326-3 21-2492 Detected
No Asbestos 1326-3 21-2492
Detected
No Asbestos 1326-3 21-2492
Detected
No Asbestos 1326-3 21�2492
Detected