Attachment 0001 - Bldg 148 FATA AS-BUILT SET_2024 31 dtd May 2024.pdf
PDF 14 MB Posted
- Attached to
- RFQ: Purchase and Installation of Exhaust System for Bldg. 148 Dining Facility at Fort Allen
- Solicitation number
- W912LR26QA041
- Issued by
-
Department of the Army National Guard
About this file
This document is an as-built drawing set for repairs to Building #148 Dining Facility at Fort Allen in Juana Diaz, Puerto Rico, prepared by the Puerto Rico Army National Guard and dated May 31, 2024.
The project encompasses comprehensive renovation of an existing dining facility with addition of a new annex. Scope includes demolition of selected interior and exterior elements, construction of a new annex with foundation and structural roof systems, and complete mechanical, electrical, plumbing, and fire protection systems. The architectural design provides multiple functional spaces including dining areas for officers and enlisted personnel, food preparation and storage areas with walk-in coolers and freezer units, scullery, hand wash areas, mechanical rooms, restrooms, storage, and support spaces. The structural work involves concrete foundation systems with reinforced concrete block walls, metal roof construction with appropriate drainage and vent systems, and new window and door installations with schedules. The mechanical systems include a direct expansion air handling unit serving variable air volume boxes for zone control, exhaust and supply fans with ductwork, and condensing units for refrigeration. Electrical work incorporates a new 400-ampere panelboard connected to existing service, branch circuits for equipment, lighting systems throughout, and fire alarm detection with manual pull stations and audible/visual alarm devices. Plumbing includes floor drains, fixture connections, roof vent pipes, and clean-out access points. The drawing set consists of 40 sheets organized by discipline with detailed plans, sections, elevations, schedules, and specifications for construction and installation.
View the file
Other files
Show all 11
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
PUERTO RICO ARMY NATIONAL GUARD
REPAIRS TO BUILDING #148 DINING FACILITY
FORT ALLEN JUANA DIAZ P.R
AS BUILT SET
COVER SHEET
DRAWING INDEX
SERIES
P
DRAWING NUMBER
P-1
DRAWING NUMBER
EP ELECTRICAL
DRAWING NUMBER
EP001
EP101
EP102
EP501
01 40
GI001
DESCRIPTION
SCHEDULE AND LEGENDS
ELECTRICAL FLOOR PLAN
ELECTRICAL ROOF PLAN
ELECTRICAL DETAILS
DESCRIPTION
DESCRIPTION
PROPOSED PLUMBING FLOOR PLAN
TI
TL
E
SH
EE
T
D
R
AW
IN
G
IN
D
EX
AS-BUILT SET
DATED: 31 May 2024
SERIES
GI
DRAWING NUMBER
GI001
CIVIL
DRAWING NUMBER
C
C-1
C-2A
C-3
A ARCHITECTURAL
DRAWING NUMBER
A-1
A-2
A-3
A-4
SB STRUCTURAL
DRAWING NUMBER
SB101
SB102
DESCRIPTION
ROOF OPENINGS PLANS
STRUCTURAL DETAILS
DESCRIPTION
DEMOLITION PLAN
DEMOLITION ELEVATIONS
PROPOSED FLOOR PLAN
REFLECTED CEILING PLAN
DESCRIPTION
PROPOSAL SITE PLAN
SERVICE AREA ENLARGED & DETAILS
SITE DETAILS
DESCRIPTION
TITLE SHEET & DRAWING INDEX
A-5 NEW ANNEX ROOF PLAN & DETAILS
A-6 PROPOSED EQUIPMENT LAYOUT
A-7 PROPOSED ELEVATIONS
A-8 PROPOSED SECTIONS
A-9 ENLARGED DETAILS
A-10 WINDOW & DOOR SCHEDULE
S-1 NEW ANNEX FOUNDATION & STRUCTURAL ROOF PLAN
S-2 FOUNDATION & ROOF STRUCTURAL DETAILS
S-3 STRUCTURAL NOTES & TYPICAL DETAILS
SD-1 SERVICE AREA METAL SHEET, ELEVATION & DETAIL
P-1 PROPOSED PLUMBING FLOOR PLAN
PLUMBING
MECHANICALMH
MH001
MH101
MH101-1
MH101-2
MH102
MH401
MH501
MH601
MH602
MH603
HVAC GENERAL SIMBOLS, NOTES AND ABBREVIATIONS
FIRST FLOOR PLAN HVAC LAYOUT
HVAC SUPPLY AIR DISTRIBUTION
HVAC RETURN AND EXHAUST AIR DISTRIBUTION
ROOF PLAN HVAC LAYOUT
HVAC DUCTWORK SECTION
HVAC DETAILS
HVAC SCHEDULES
HVAC CONTROLS
HVAC CONTROLS
E-3 LEGEND, SCHEDULE & NOTES
E-2 POWER FLOOR PLAN
E-1 LUMINARIES FLOOR PLAN
DRAWING NUMBER DESCRIPTION
FIRE PROTECTIONF
F-1 FIRE ALARM FLOOR PLAN
AutoCAD SHX Text
A. VARGAS
AutoCAD SHX Text
J. RUIZ
AutoCAD SHX Text 2020-01-14
AutoCAD SHX Text
AS SHOWN
POOL
BUILDING
BLDG. 147G
BLDG. 147
PROJECT LIMIT
BUILDING
BLDG. 146
NEW ANNEX
BLDG. 148
EXISTING BUILDING 148
MAIN
ENTRANCE
DRIVEWAY
PROJECT LIMIT
T O S H E E R A V E . S T R R E T # 3
N PROPOSAL SITE PLAN IMPORTANT NOTES:
PR
O
JE
C
T
LI
M
IT
PR
OJE
CT
L
IM
IT
AS-BUILT SET
DATED: 31 May 2024
02 40 C-1
AutoCAD SHX Text
EXISTING SIDEWALK TO REMAIN
AutoCAD SHX Text
EXISTING SIDEWALK TO REMAIN
AutoCAD SHX Text
EXISTING SIDEWALK TO REMAIN
EXISTING SIDEWALK TO REMAIN
PLAN VIEW COLUMN PLAN VIEW COLUMN PLAN VIEW COLUMN PLAN VIEW COLUMN
FOOTING DETAIL FOOTING DETAIL FOOTING DETAIL FOOTING DETAIL
CONCRETE FLOOR DETAIL FOUNDATION FOUNDATION
AS-BUILT SET
DATED: 31 May 2024
03 40 C-2A
CONCRETE SIDEWALK DETAIL
CONCRETE SIDEWALK DETAIL
AS-BUILT SET
DATED: 31 May 2024
04 40 C-3
GENERATOR
OFFICERS DINING AREA
DINING AREA
MECH. ROOM LOBBY
OFFICE SERVING AREA
DISH DROP OFF/
WASTE DISPOSAL
WALK IN COOLER
OFFICE
AREA
MAIN
ENTRANCE
FOOD PREP.
FOOD STORAGE DISH
WASHING
AREA
WALK IN FREEZER
WALK IN
COOLER
MECH.
ROOM
DEMOLITION NOTES: NOTES:
DEMOLITION PLAN
N
DEMOLITION LEGEND:
MITIGATION NOTES:
C O
N C
. S
LA
B
ST
O
R
AG
E
JA
N
IT
O
R
M
EN
R
ES
TR
O
O M
ST
O
R
AG
E
W O
M
EN
R
ES
TR
O
O M
ST
O
R
AG
E
R
ES
TR
O
O M
C O
O
LE
R
AS-BUILT SET
DATED: 31 May 2024
05 40 A-1
AutoCAD SHX Text
AutoCAD SHX Text
REMOVED EXISTING FIRE PANEL
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
DOOR TO BE REUSED.
AutoCAD SHX Text
AutoCAD SHX Text
(NOT IN CONTRACT)
(NOT IN CONTRACT)
SOUTH ELEVATION
EAST ELEVATION
WEST ELEVATION
ELEVATIONS DEMOLITION NOTES:
NOTES:
NORTH ELEVATION ELEVATION DETAIL
AS-BUILT SET
DATED: 31 May 2024
06 40 A-2
AutoCAD SHX Text
(REPAIRED BY OWNER)
(NOT IN CONTRACT)
SCULLERY
MEN
RESTROOM
OFFICERS DINING AREA
WOMEN
RESTROOM
DINING AREA
HAND WASH AREA
WALK IN COOLER
HALLWAY
MECH.
ROOM LOBBY
SERVING AREA OFFICE
AREA
STORAGE
ENTRANCE
ELEC.
ROOM
WALK IN FREEZER
MECH.
ROOM
SERVICE
ENTRANCE
FOOD STORAGE FOOD PREP.
WATER
HEATER/
SOFTENER
STO.
RESTROOM
SERVICE
AREA
PROPOSED FLOOR PLAN
N
LEGEND:
AS-BUILT SET
DATED: 31 May 2024
07 40 A-3
AutoCAD SHX Text
EXISTING WALL EXTENDED TO THE CEILING WITH GYPSUM BOARD AND METAL FRAME
AutoCAD SHX Text NEW HOLLOW METAL DOOR SINGLE DOOR INSTALLED, 3' X 6'-8" WITH FRAME, LOCKSET, HARDWARE & THRESHOLD WITH NOTES 1,2,3,4,5,6, AutoCAD SHX Text
EXISTING WALL EXTENDED TO THE CEILING WITH CMU 6"
AutoCAD SHX Text
DRIVEWAY BUILT WITH REINFORCED STEEL #4 @ 10" AND 5" DEEP
AutoCAD SHX Text
SS.WH.
AutoCAD SHX Text
SS.DW.
AutoCAD SHX Text
PP-3
EXISTING SIDEWALK TO REMAIN
MEN WOMEN
RESTROOM RESTROOM
SCULLERY
OFFICERS
DINING AREA
HAND WASH AREA
DINING AREA
MECH. ROOM WALK IN COOLER
HALLWAY
LOBBY SERVING AREA
OFFICE
AREA
WALK IN FREEZER
ENTRANCE STORAGE
MECH.
ROOM FOOD STORAGE EXISTING FOOD PREP.
SERVICE
ENTRANCE
WATER
HEATER/
SOFTENER
STO. REST.
LEGEND: NOTES:
REFLECTED CEILING PLAN
N
AS-BUILT SET
DATED: 31 May 2024
ELEC.
ROOM
08 40 A-4
AutoCAD SHX Text 9'-0" A.F.F.
AutoCAD SHX Text 9'-0" A.F.F.
AutoCAD SHX Text 9'-0" A.F.F.
AutoCAD SHX Text
EXISTING CEILING TILES
AutoCAD SHX Text
NEW CEILING TILES
AutoCAD SHX Text
NEW CEILING TILES
AutoCAD SHX Text
NEW CEILING TILES
AutoCAD SHX Text
NEW CEILING TILES
AutoCAD SHX Text
EXISTING CEILING TILES
AutoCAD SHX Text 2' x 2' - RECESSED FLUORESCENT FIXTURE
PP-3
ROOF SCOPE OF WORK:
ROOF DRAIN NOTE:
ROOF VENT PIPE (VTR)
TYPICAL CONCRETE SPLASH BLOCK DETAIL
NEW ANNEX ROOF PLAN RAIN LEADER DETAIL
EX
IS
TI
N
G R
O O
F
BU
IL
D
IN
G
AS-BUILT SET
DATED: 31 May 2024
09 40 A-5
SCULLERY
OFFICERS DINING AREA
DINING AREA
HAND WASH AREA
WALK IN COOLER
MECH.
ROOM LOBBY
OFFICE
AREA
HALLWAY
SERVING AREA
STORAGE
ENTRANCE
ELECTRICAL
ROOM
FOOD PREP.
WALK IN FREEZER
MECH.
ROOM
FOOD STORAGE
RESTROOM
WATER HEATER/
SOFTENER STORAGE
EQUIPMENT SCHEDULE
PROPOSED EQUIPMENT LAYOUT
N
NOTES:
AS-BUILT SET
DATED: 31 May 2024
10 40 A-6
AutoCAD SHX Text
SS.WH.
AutoCAD SHX Text
SS.DW.
PP-3
SOUTH ELEVATION
EAST ELEVATION
WEST ELEVATION
LEGEND:
NOTES:
NORTH ELEVATION ELEVATION DETAIL
AS-BUILT SET
DATED: 31 May 2024
11 40 A-7
AutoCAD SHX Text L
AutoCAD SHX Text
EXSITING METAL STAIR, SCRAPPED AND PAINTED
AutoCAD SHX Text
GLASS MULLIONS DIVISOR ELIMINATED AND FROSTED GLASS FILM INSTALLED
AutoCAD SHX Text
OPENING FILLED WITH CMU, CEMENT PLASTER AND PAINTED
OPEN TO BEYOND
LEGEND:
NOTES:
SERVICE
ENTRANCE
SECTION AA
LEGEND:
SECTION BB
AS-BUILT SET
DATED: 31 May 2024
12 40 A-8
AutoCAD SHX Text
NEW WALL, DENGLASS
AutoCAD SHX Text
NEW WALL, DENGLASS
AutoCAD SHX Text
OPEN TO BEYOND
FIRE CONTROL PANEL
HAND WASH AREA
SERVING AREA
ELEVATION 1
DETAIL 2:ELEVATION 1
DETAIL 3: CEMENT BOARD WALL
NOTES:
ELEVATION 2 DETAIL 2: ELEVATION 2 AS-BUILT SET
DATED: 31 May 2024
13 40 A-9
OPEN TO BEYOND
S T O R E F R O N T S & W I N D O W S C H E D U L E WINDOW NOTES
WINDOW ELEVATION
F I N I S H S C H E D U L E GENERAL NOTES:
PAINT NOTES:
DOOR ELEVATION
D O O R S C H E D U L E
TYPICAL DOOR JAMB DETAILS
LOCKSET SCHEDULE
F I N I S H L E G E N D
TYPICAL THRESHOLD DETAIL
WALL
NOTES:
CEILING
FLOOR
AS-BUILT SET
DATED: 31 May 2024
W
IN
D O
W
D O
O R
S C
H
ED
U
LE
14 40 A-10
AutoCAD SHX Text 4'-10
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
HOLLOW METAL
AutoCAD SHX Text 3'-0"
AutoCAD SHX Text 6'-8"
AutoCAD SHX Text
SINGLE DOOR, WITH FRAME, LOCKSET, HARDWARE & THRESHOLD
AutoCAD SHX Text 1,2,3,4,5,6
AutoCAD SHX Text
EXISTING DOOR WAS RE-USED
AutoCAD SHX Text 3'-0"
AutoCAD SHX Text
EXISTING DOOR WAS RE-USED
AutoCAD SHX Text
THREE (3)
AutoCAD SHX Text 6'-3
AutoCAD SHX Text
FIXED GLASS WINDOW
AutoCAD SHX Text 4'-9"
4'-9"
SERVICE
ENTRANCE
ROOF
EF-06
NEW
SB101
SB101
EF-08
NEW
EF-07
NEW
SF-07
NEW
SF-08
NEW
CU-01
SB101
SB101
3'-3"
1'-2"
4'-11"
5'-1"
5'-2"
'-3
0' -1
1"
3' -3
9'-8"
'-7
2'-8" 5'-4" 5'-5"
'-8
3'-5" 5'-1" 5'-1" 3'-5" 4'-5" 5'-8"
'-4
'-7
EXISTING
BEAM
BELOW
EXISTING
BEAM
BELOW
A
SB102
C
SB102
B
SB102
D
SB102
F
SB102
E
SB102
14'-73 8"
5' -9
7 16
CURB TO CONCRETE ANCHORS
UNIT
SIZE
TOTAL AMOUNT OF
ANCHOR BOLTS REQUIRED ANCHOR BOLTS DIAMETER
EF-06
EF-07
EF-08
8"
SF-07
SF-08
CU-01
8"
8"
8"
8"
2"
NOTES:
1. INSTALL 4 STEEL WIRE ROPE TIE DOWN PER UNIT 3
8" DIA.
2. ATTACH EQUIPMENT TO CURB AS PER MANUFACTURER
INDICATIONS.
3. NOTE GROUT:
UTILIZE HIGH EARLY STRENGTH PREMIXED NON-SHRINK
GROUT. APPLY SIKADUR 32 BONDING AGENT ON INTRFACE
BETWEEN EXISTING CONCRETE AND NEW MORTAR.
* 3
8" KWIK BOLT TZ EMBEDMENT DEPTH 2"
INSTALLER TO
SEAL AS
REQUIREDROOF CURB
M
IN
M
IN
2 7 8"
MIN.
8" KWIK BOLTS
2'-11 2"
'-1
1 2"
1'-111 2"
'-1
2"
2'-71 2"
'-7
1 2"
3'-71 2"
'-0
1 8"
1'-31 2"
'-3
1 2"
EXHAUST VENTILATOR
ABOVE. FOR DETAILS
SEE MECHANICAL DWGS.
SUPPLY PACKAGE
VENTILATOR. FOR
DETAILS SEE
MECHANICAL DWGS.
R O
O F
O
PE
N
IN
G
EXHAUST VENTILATOR
ABOVE. FOR DETAILS
SEE MECHANICAL DWGS.
'-2
10'-1"
SUPPLY PACKAGE
VENTILATOR. FOR
DETAILS SEE
MECHANICAL DWGS.
EXHAUST VENTILATOR
ABOVE. FOR DETAILS
SEE MECHANICAL DWGS.
REQUIRED OPENING
FOR EQUIPMENT
LIMIT OF SELECTIVE
DEMOLITION. DEMOLISH
CONCRETE ONLY. LEAVE
REBAR INTACT.
EXISTING REBAR
CUT EXIST. REBAR AT
CENTERLINE OF OPENING
NEW PERIMETER REBAR.
EXISTING REBAR
FINISH PERIMETER
OPENING WITH GROUT
SEE NOTE 1
4"
G
SB101
G
SB101
G
SB101
H
SB101
4"
4"
EX
H
AU
ST
V
EN
T.
BA
SE
'-0
EX
H
AU
ST
V
EN
T.
C
U R
B
'-8
'-7
1 2"
VE
N
TI
LA
TO
R
B
AS
E
4"
'-8
1 8"
VE
N
TI
LA
TO
R
C U
R B
R O
O F
O
PE
N
IN
G
ROOF OPENINGROOF OPENING
R O
O F
O
PE
N
IN
G
'-6
EX
H
AU
ST
V
EN
T.
BA
SE
'-2
EX
H
AU
ST
V
EN
T.
C U
R B
ROOF OPENING
4"
4"
R O
O F
O
PE
N
IN
G
ROOF OPENING
'-4
VE
N
TI
LA
TO
R B
AS
E
'-0
VE
N
TI
LA
TO
R C
U R
B
R O
O F
O
PE
N
IN
G
ROOF OPENING
1'-8"
EXHAUST VENT.BASE
'-4
EX
H
AU
ST
V
EN
T.
C U
R B
SEE SECTION H
BELOW
REQUIRED OPENING
FOR EQUIPMENT
LIMIT OF SELECTIVE DEMOLITION. DEMOLISH
CONCRETE ONLY. LEAVE REBAR INTACT.
CUT EXIST. REBAR AT CENTERLINE
NEW PERIMETER
REBAR
FILL WITH GROUT AND
PRODUCT SEE NOTE 1
4" 4" OPENING VARIES
N
R O
O F
O
PE
N
IN
G S
PL
AN
SCALE:
PARTIAL ROOF OPENINGS PLAN
3/16"=1'-0"
SCALE:
SECTIONG
3"=1'-0"SB101
SCALE:
DETAIL2
3/4"=1'-0"
EF-08 EXHAUST VENTILATOR FAN AND
SF-08 SUPPLY PACKAGE VENTILATOR
SB101
SCALE:
DETAIL3
3/4"=1'-0"
EF-06 EXHAUST VENTILATOR FAN
SB101
SCALE:
DETAIL1
3/4"=1'-0"
EF-07 EXHAUST VENTILATOR FAN AND
SF-07 SUPPLY PACKAGE VENTILATOR
SB101
SCALE:
DETAIL4
1/2"=1'-0"
CU-01
SB101
SCALE:
TYPICAL OPENING CONSTRUCTION DETAIL
3/4"=1'-0"
SCALE:
SECTIONH
1 1/2"=1'-0"SB101
6"
6"
18’’
1’
AS-BUILT SET
DATED: 31 May 2024
2020-01-14 3/16"=1'-0"
15 40
SB101
AutoCAD SHX Text
AND BEND AT 90°
AutoCAD SHX Text
OF OPENING AND BEND AT 90°
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
CU
AutoCAD SHX Text
ROOF
AutoCAD SHX Text
1. Colocar angular ¼" en acero (con
AutoCAD SHX Text protección de corrosión) con una
AutoCAD SHX Text dimensión de 4" X 4". se colocarán tres
AutoCAD SHX Text angulares de cada lado.
AutoCAD SHX Text
2. Colocar threaded rod (stainless steel) de
AutoCAD SHX Text ½"
AutoCAD SHX Text de diametro que traspase la base de la
AutoCAD SHX Text condensadora. Con sus arandelas y tuercas
AutoCAD SHX Text en stainless steel. Aplicar threadlocker (de
AutoCAD SHX Text alta resistencia ) en los rod.
AutoCAD SHX Text
3. Colocar threaded rod (stainless steel) ½"
AutoCAD SHX Text de diametro que traspase el suelo un
AutoCAD SHX Text mínimo de dos pulgadas. Aplicar
AutoCAD SHX Text threadlocker (de alta resistencia ) en los rod.
AutoCAD SHX Text
4. Colocar el "vibration isolation pad" de
AutoCAD SHX Text minimo ¼" de grosor, que cubra 18"
AutoCAD SHX Text debajo del marco de soporte de la maquina
AutoCAD SHX Text he incluya el angular. El pad debe tolerar
AutoCAD SHX Text más de 900 libras en cada punto .
AutoCAD SHX Text
5. Colocar threaded rood con epoxy.
Instrucciones
2'-8" 5'-4" 5'-5"
(2)HILTI ANCHOR
BOLTS
EXISTING
CONC.
BEAM
EXISTING
CONC.
SLAB
8" Ø BOLT, NUT
AND WASHER
(2)HILTI ANCHOR
BOLTS
W8x10
ROOF OPENING
HSS 3x3x1/4x3"(TYP.)NON-SHRINK GROUT(TYP.) PL 6x6x1
4" (TYP.) 3
16"
TYP.
5'-2"
EXISTING
CONC.
BEAM
16"
TYP.
W8x10
L 4x4x 3 8"x5"
(2)HILTI ANCHOR
BOLTS
8" Ø BOLT, NUT
AND WASHER
2'-8"
8" Ø BOLT, NUT
AND WASHER
W8x10
ROOF OPENING PL 6x1
4" (TYP.)
LENGTH VARIES
L 4x4x 3 8"x5"
3'-4"
PL 6x1
" (TYP.)
LENGTH VARIES
HSS 3x3x1/4x3"(TYP.)
16"
TYP.
W8x10
HSS 3x3x1/4x3"(TYP.)
W8x10
8" Ø BOLT, NUT
AND WASHER
NON-SHRINK
GROUT(TYP.)
NON-SHRINK
GROUT(TYP.)
EXISTING CONC.
SLAB
EXISTING
CONC.
SLAB
EXISTING
CONC.
BEAM
4'-1"
EXISTING CONC.
BEAM
(2)HILTI ANCHOR
BOLTS
HSS 3x3x1/4x3"(TYP.)
16"
TYP.NON-SHRINK
GROUT(TYP.)
EXISTING
CONC.
SLAB
W8x10 W8x10
3'-41 2" 5'-1" 5'-1"
(2)HILTI ANCHOR
BOLTS EXISTING CONC.
BEAM
EXISTING CONC.
SLAB
8" Ø BOLT, NUT
AND WASHER
(2)HILTI ANCHOR
BOLTS
W8x10
ROOF OPENING
HSS 3x3x1/4x3"(TYP.)
NON-SHRINK
GROUT(TYP.) PL 6x6x1
4" (TYP.) 3
16"
TYP.
PL 6x1
4" (TYP.)
LENGTH
VARIES
EXISTING CONC.
BEAM
EXISTING CONC.
SLAB
PL 6x6x1
4" (TYP.)NON-SHRINK
GROUT(TYP.)
ROOF OPENING5
8" Ø BOLT, NUT
AND WASHER
3'-5" 4'-5" 5'-8" 7" 7"
PL 6x1
4" (TYP.)
LENGTH VARIES
PL 6x1
4" (TYP.)
LENGTH VARIES
PL 6x1
4" (TYP.)
LENGTH
VARIES
7" 7"
NOTES:
1. STOP APPLY RED-OXIDE PRIMER ON ALL STEEL SURFACES.
INSPECT AND REPAINT ANY DAMAGED SURFACE DURING
INSTALLATION PROCESS.
3" 3"
6x1
4" STEEL PLATE, LENGTH VARIES.
THIS BASE PLATE APPLIES ONLY
BELOW ROOF SLAB
VARIES
1" 4"
1" 4" 1"
6x6x1
2" STEEL PLATE.
THIS BASE PLATE
APPLIES ONLY ABOVE
ROOF SLAB & BEAMS
4"
16"
TYP.
L 4x4x5x3 8"
PROVIDE (2) HOLES
TO ANCHOR BOLTS
TO EXIST. WALL
SB102
N
SCALE:
SECTIONA
3/4"=1'-0"SB101 SCALE:
SECTIONC
3/4"=1'-0"SB101
SCALE:
SECTIOND
3/4"=1'-0"SB101
SCALE:
SECTIONB
3/4"=1'-0"SB101
SCALE:
SECTIONE
3/4"=1'-0"SB101
SCALE:
SECTIONF
3/4"=1'-0"SB101
SCALE:
TYPICAL BASE PLATES DETAILS
1 1/2"=1'-0"
AS-BUILT SET
DATED: 29 May 2024
S T
R U
C T
U R
A L
D E
T A
IL
S
AS-BUILT SET
DATED: 31 May 2024
NEW ANNEX FOUNDATION PLAN NEW ANNEX STRUCTURAL ROOF PLAN
N N
LEGEND:
17 40 S-1
A A
PLAN
SECTION A-A SECTION B-B
FOUNDATION FOUNDATION FOUNDATION FOUNDATION
A A
PLAN
SECTION A-A SECTION B-B
FOUNDATION FOUNDATION FOUNDATION FOUNDATION
FOUNDATION BEAM SECTION BEAM SECTION BEAM SECTION BEAM SECTION FLASHING DETAIL
B B
B B
18 40 S-2
STRUCTURAL NOTES
RING TIE DETAILS
REINFORCED CONCRETE BLOCK WALL DETAIL
TYPICAL CMU ANCHORAGE
AT INTERSECTION WALL
TYPICAL CMU ANCHORAGE
AT CORNER WALL
TYPICAL REINFORCEMENT DETAIL AT OPENINGS
TYPICAL REINFORCEMENT
AT 8" CMU WALL
TYPICAL REINFORCEMENT
AT 6" CMU WALL
AS-BUILT SET
DATED: 31 May 2024
19 40 S-3
NEW METAL FACE &GATE AT EAST ELEVATION
SCALE: 3/8"=1'-0"
NEW METAL FACE & GATE AT WEST ELEVATION
SCALE: 3/8"=1'-0"
METAL CANE & PADLOCK DETAIL
SCALE: 3/4"=1'-0"
KEY-NOTE LEGEND:
1 1
1 2
1 2 1
SD-2
SD-2
SD-2
SD-2
2 6
4' -0
2"
1' -1
0"
1'-0"
3' -0
3 8" 9"
8"
4 1/2" 7"
8"
2"
SD-2
6'-0 1/4" 2"
2'-11 1/4" 2"
18'-0 3/4" 5'-10 1/2"
2' -0
2'
-0
2' -0
1'
-9
1. METAL SHEET PANEL.
2. 2" x 2" METAL TUBE.
3. 2"x2" METAL POST
4. METAL CANE.
5. PADLOCK
6. 1" x 1" METAL TUBE.
7' -8
1"
7' -9
6'-0 1/4" 6'-0 1/4" 2'-11 1/4"
AS-BUILT SET
DATED: 31 May 2024
20 40
SD-1
SE
R
VI
C
E
AR
EA
M
ET
AL
S H
EE
T
EL
EV
AT
IO
N S
AN
D
D
ET
AI
L
P-2
P-2
P-1 P-1
P-1 P-1
P-5
P-5
P-2
P-2
P-7
P-8
NEW
F.D.
NEW
F.D.1
NEW
F.D.2
FC0.-4
3" F.D.
P-6
FC0.-2
FD.-1 FC0.-3
NEW
F.D.1
ENTRANCE FD.-2
P-4
LEGEND:
P-2
F.C.O.-1
FD.-2
P-3 P-3 P-1
FC0.-1 F.C.O.-1
SERVICE
AREA
NOTES:
NEW
F.D.2
PROPOSED PLUMBING FLOOR PLAN
N
AS-BUILT SET
DATED: 31 May 2024
21 40 P-1
AutoCAD SHX Text 2.5"
2.5"
PLUMBING NOTES: BATHROOM FIXTURES SCHEDULE
PLUMBING SYMBOLS:
WALL MOUNTED HOSE BIBB ROOF VENT PIPE THROUGH SLAB
PLUMBING ABBREVIATIONS:
TYPICAL CLEAN-OUT FLUSH W/ FLOOR OR GRADE TYPICAL FLOOR DRAIN W/ P-TRAP
AS-BUILT SET
DATED: 31 May 2024
22 40 P-2
AutoCAD SHX Text (N.I.C.)
AutoCAD SHX Text (N.I.C.)
AutoCAD SHX Text (N.I.C.)
AutoCAD SHX Text (N.I.C.)
AutoCAD SHX Text (N.I.C.)
AutoCAD SHX Text (N.I.C.)
(N.I.C.)
LUMINARIES FLOOR PLAN
N
AS-BUILT SET
DATED: 31 May 2024
23 40 E-1
AutoCAD SHX Text
SS.WH.
AutoCAD SHX Text
SS.DW.
AutoCAD SHX Text
PP-3
AutoCAD SHX Text
SS-AHU1
AutoCAD SHX Text
VFD
AC COMM. BOXES
POWER FLOOR PLAN
AS-BUILT SET
DATED: 31 May 2024
24 40 E-2
ELECTRICAL SYMBOLS LEGEND:
DATED: 31 May 2024
25 40 E-3
HEAVY DUTY SAFETY SWITCH. SEE SCHEDULE FOR DETAILS. MOUNT TOP OF SWITCH AT
5'-0" A.F.F. CONTRACTOR SHALL PROVIDE ALL REQUIRED MOUNTING HARDWARE.
SINGLE POLE SWITCH, 20A, 120/277V. WITH PLASTIC COVER PLATE.
HOMERUN TO PANELBOARD. NUMBER OF CIRCUITS INDICATED BY NUMBER OF ARROWS.
NUMBERS AND LETTERS INDICATE CIRCUITS NUMBER AS PER PANEL SCHEDULE.
LEGEND:
NEW PANELBOARD 6'-6" A.F.F. SEE SCHEDULE FOR DETAILS.
NOTES:
1. NEW PANEL PP-3 WILL BE CONNECTED TO PANEL MDP (EXISTING)
WITH 2 SETS OF 4 #250 KCMIL AND 1 #1/0 IN A 3" EMT CONDUIT EACH
SET.
2. CONTRACTOR SHALL PROVIDE A 3P, 400A, 65 KAIC CIRCUIT BREAKER AT
PANEL MDP-1.
3. ALL INDOOR ELECTRICAL CONDUITS SHALL BE EMT (NOT EXPOSED TO PHYSICAL
DAMAGE).
4. ALL OUTDOOR ELECTRICAL CONDUITS SHALL BE RGS.
N
EXISTING PANELBOARD TO REMAIN.
E
S C
H E
D U
LE
S
A N
D L
E G
E N
D
M, RAMOS
M. FLORES
2020-01-14 NTS
AS-BUILT SET
DATED: 31 May 2024
J. PRATS
26 40
EP001
E
LE
C T
R
IC
A L
FL
O
O R
P
LA
N
EAEA
EF-01
AHU-01
EF-02
EF-04 EF-03
MECH.
ROOM VAV-05
RA
SASASASASA
SA
SA
SA
SA
SA
SA
TO LT
SWITCH
TO LT
SWITCH
TO LT
SWITCH
VAV-02
VAV-03
VAV-04
VAV-06
TO PP-3 #20
VAV-01
PP-3
TO PP-3
#2,4,6
MDP-1
E
N
F14
LAPTOP
AREA
VFD SS#4
NEW COMMUNICATION
CONDUIT 3/4"
CNTROL &
COMMUNICATION BOX
27 40
EP101
AutoCAD SHX Text
SS.WH.
SS.DW.
SERVICE
ENTRANCE
SERVICE
AREA
ROOF
EF-06
NEW
EF-08
NEW
EF-07
NEW
SF-07
TO PP-3
#14,16,18
SS-1
SS-3
SS-2
SS-4
SF-08
NEWCU-01
SS-6
TO PP-3.
#9,11,13
TO PP-3
#3,5,7
TO PP-3
#8,10,12
TO PP-3
#15,17,19
TO PP-3 #1
SS-7
N
E
LE
C T
R
IC
A L
R O
O F
P
LA
N
AS-BUILT SET
DATED: 31 May 2024
NEW FREEZER &
REFRIGERATOR
CONDENSING UNITS
8' -6
4'-6"
6' -9
5'-10"
5' -5
3'-7"
NEW
28 40
EP102
M. RAMOS
M.FLORES
J. PRATS
CONDUIT, TYP MINERAL WOOL
(FIRMLY PACKED)
FIRESTOP SEALANT
(3/8") MAX
9.52mm
JUNCTION BOX
(SIZE AS REQUIRED)
SPRING
NUT, TYP
INTEGRAL GALVANIZED
LIPPED STEEL MOUNTING
CHANNEL, TYP.
ROOF SLAB,
TYP. STEEL EXPANSION
ANCHOR, TYP
GENERAL NOTES:
LENGTH AS REQUIRED
LOCKING SQUARE
WASHER & LOCKNUT
WASHER &
LOCKNUT
INTEGRAL
GALVANIZED
LIPPED STEEL
MOUNTING
CHANNEL
TO EQUIPMENT
1 1/2" x 1 1/2" CHANNEL
SAFETY SWITCH
3" 6"
1/4" WELD
6" 3"
AS REQUIRED
SWITCH
6"3" 3"
AP
PR
O X.
4' -6
AS
R
EQ
U
IR
ED
(MINIMUM) (MINIMUM)
SCALE:
DETAIL1
NOT TO SCALE
ROOF SLAB PENETRATION
EP501 SCALE:
DETAIL1
NOT TO SCALE
CONDUIT TRAPEZE MOUNTING
EP501 SCALE:
DETAIL1
NOT TO SCALE
SAFETY SWITCH MOUNTING
EP501
1 2
6' -6
14"
"MDP-1 PP-3
SCALE:
ELECTRICAL RISER DIAGRAM
NOT TO SCALE
EXISTING MDP-1 PANEL 120/240V, 3P, 4W, 800A,
65 KAIC.
NEW PP-3 PANEL 120/208V, 3P, 4W, 400A, 22 KAIC
IN A NEMA 1 ENCLOSURE.
4#250 KCMIL THWN AND 1#1/0 THW-600V IN A 3"
EMT CONDUIT.
ELECTRICAL RISER DIAGRAM LEGEND:
9.52mm (3/8") MIN
GALVANIZED
THREADED ROD,
TYP.
REFER TO PLANS FOR
QUANTITY & SIZE OF
CONDUITS
CONDUIT
CLAMP. SIZE
AS REQUIRED
INTEGRAL
GALVANIZED
LIPPED STEEL
MOUNTING
CHANNEL
1. INTEGRAL GALVANIZED LIPPED STEEL
MOUNTING CHANNEL LONGER THAN 915mm (36")
SHALL BE INSTALLED WITH A CENTER SUPPORT
ROD.
2. FASTEN THREADED ROD TO STRUCTURE BY
APPROVED METHOD PER SPECIFICATION 26 05 33,
RACEWAY AND BOXES FOR ELECTRICAL
SYSTEMS. FIELD VERIFY EXACT CONDITIONS.
3. FOR TRAPEZE INSTALLATIONS IN SEISMIC
AREAS REFER TO SPECIFICATION SECTION
260529 - HANGERS AND SUPPORTS FOR
ELECTRICAL SYSTEMS.
1/2" x 3/4"
CHANNEL
LIQUIDTIGHT
FLEXIBLE
CONDUIT
1/2"Ø EXPANSION BOLTS
FLOOR OR ROOF LEVEL
1'-6" x 1'-0" x 1/4"
STAINLESS
STEEL PLATE
1/2"Ø
EXPANSION
BOLTS
FINISHED FLOOR
AS-BUILT SET
DATED: 31 May 2024
EL
EC
TR
IC
A L
D
ET
A
IL
S
29 40
EP501
G
EN
ER
AL
S
YM
BO
LS
, N O
TE
S
AN
D
A
BB
R
EV
IA
TI
O N
S
HVAC ABBREVIATIONS: HVAC SYMBOLS:
ACC
AD
AFF
ADJ
ACU
AHU
AP
AUX
BD
BDD
BFP
BHP
BOD
BOP
BTU
BTUH
CC
CD-"X"
CG-"X"
CH
CHWS
CHWR
CLG
CL
CR
CFM
CMU
COND
CONN
CP
CT
CTWS
CTWR
CU
CU FT
DET
DH
DIA
DIAG
DN
DIM
DL
DPT
DWG
EA
EFF
EP
EF
ER
EG
ET
EH
EXH
EXIST.
AIR COOLED CONDENSER
ACCESS DOOR
ADJUSTABLE
ABOVE FINISHED FLOOR
AIR CONDITIONING UNIT
AIR HANDLING UNIT
ACCESS PANEL
AUXILIARY
BYPASS DAMPER
BACKDRAFT DAMPER
BACK FLOW PREVENTER
BRAKE HORSEPOWER
BOTTOM OF DUCT
BOTTOM OF PIPE
BRITISH THERMAL UNIT
BTU PER HOUR
COOLING COIL
CEILING GRILLE
CEILING DIFFUSER
"X"=THROW DIRECTIONS NUMBERS
CHILLER
CHILLED WATER SUPPLY
CHILLED WATER RETURN
CEILING
CENTER LINE
CEILING REGISTER
CUBIC FEET PER MINUTE
CONCRETE MASONRY UNIT
CONDENSATE
CONNECTION
CONTROL PANEL
COOLING TOWER
COOLING TOWER WATER RETURN
COOLING TOWER WATER SUPPLY
CONDENSING UNIT
CUBIC FEET
DETAIL
DEHUMIDIFIER
DIAMETER
DIAGRAM
DIMENSION
DOWN
DOOR LOUVER
DIFFERENTIAL PRESSURE
TRANSMITTER/SWITCH
DRAWING
EXHAUST AIR
EFFICIENCY
ELECTRIC-PNEUMATIC SWITCH
EXHAUST AIR FAN
EXHAUST REGISTER
EXHAUST GRILLE
EXPANSION TANK
ELECTRICAL HEATER
EXHAUST
EXISTING
NC
N.I.C
No.
NS
NO
N.T.S
OA
OAL
OBD
OC
OPER
OPNG
P
PE
PH
PLN
PL
QTY
NORMALLY CLOSED (FAIL SAFE CLOSED)
NOT IN CONTRACT
NUMBER
NORMALLY OPEN (FAIL SAFE OPEN)
NATIONAL STANDARD
NOT TO SCALE
OUTSIDE AIR
OUTSIDE AIR LOUVER
OPPOSED BLADE DAMPER
ON CENTER
OPERATING
OPENING
PUMP
PNEUMATIC-ELECTRIC SWITCH
PHASE
PLENUM
PLATE
QUANTITY
LBS
LD
LG
LIQ
LL
LR
MAN
MATL
MAX
MBH
MCC
MD
MFR
MIN
MOD
GA
GALV
GPM
GV
HL
HOA
HP
HZ
IH
IN
GALLONS PER MINUTE
GAUGE
GALVANIZED
GRAVITY RELIEF VENT
HIGH LIMIT
HAND-0FF-AUTOMATIC SWITCH
HORSE POWER
HERTZ
AIR INTAKE HOOD
INCHES
POUNDS
LINEAR DIFFUSER
LONG
LIQUID
LOW LIMIT
LONG RADIUS
MANUAL
MATERIAL
MAXIMUM
1000 BTU PER HOUR
ELBOW WITH TURNING VANES
MOTOR CONTROL CENTER
MOTORIZED DAMPER
MANUFACTURER
MINIMUM
MODEL
TEMP
TG
TIP
TOC
TOD
TOP
TOS
TP
TYP
UH
U.O.N
V
VAV
VD
V.V
W/
W/O
WCC
WG
WS
WT
TEMPERATURE
TRANSFER GRILLE
TIE-IN POINT
TOP OF CONCRETE
TOP OF DUCT
TOP OF PIPE
TOP OF STEEL
TOTAL PRESSURE
TYPICAL
UNIT HEATER
UNLESS OTHERWISE NOTED
VOLTS
VARIABLE AIR VOLUME
VOLUME DAMPER
VARIABLE AIR VOLUME BOX
WITH
WITHOUT
WATER COOLED CONDENSER
WATER GAUGE
WALL SUPPORT
WEIGHT
CODES:
1. PR BUILDING CODE 2018
2. NG PAM 415.12
3. NGB-DG 415-5
4. VCF 4-010-01
5. NFPA 70
F
FAI
FC
FD
FLEX.
FOB
FOT
FSD
FUT
DEGREES FAHRENHEIT
FRESH AIR INTAKE
FAN COIL UNIT
FIRE DAMPER
FLEXIBLE
FLAT ON BOTTOM
FLAT ON TOP
COMBINATION FIRE/SMOKE DAMPER
FUTURE
R
RA
REF
RF
RG
RH
RHC
RHWR
RHWS
RL
RM
RPBP
RPM
RR
PRV
SA
SCH
SE
SF
SHT
SL
SOL
SPD
SQ HD
SP
SPECS
SR
SS
STD
STT
RADIUS
REFERENCE
RETURN AIR
D/L
RETURN AIR FAN
RETURN AIR GRILLE
RADIANT HEATER
REHEAT COIL
REFRIGERANT (LIQUID) LINE
REHEAT WATER RETURN
REHEAT WATER SUPPLY
ROOM
REDUCED PRESSURE BACKFLOW
REVOLUTIONS PER MINUTE
RETURN AIR REGISTER
PREVENTER
SD
SUPPLY AIR
SCHEDULE
SMOKE EXHAUST
SUPPLY FAN
SHEET
SUCTION LINE
SOLENOID VALVE
SPLITTER DAMPER
SQUARE HEAD
STATIC PRESSURE
SPECIFICATIONS
SUPPLY REGISTER
STAINLESS STEEL
STANDARD
SOUND TRAP, SOUND ATTENUATOR
24"x12"
DAMPER - MOTOR OPERATED
VARIABLE AIR VOLUME BOX
MOD
DAMPER - MOTORIZED VORTEX
DAMPER OPERATOR-MANUAL OVERRIDE
BRANCH CONNECTION-SUPPLY & RETURN
SPLITTER DAMPER W/ ADJUSTING ROD
T
DIRECTION OF FLOW
8. THE CONTRACTOR SHALL TAKE EVERY PRECAUTION IN ORDER TO MINIMIZE OR
DUCT - ACOUSTIC LINER
T
DUCT SIZE - FIRST DIMENSION
IS FOR SIDE SHOWN
DUCT - SUPPLY AIR
DUCT - EXHAUST OR RETURN AIR
DUCT - OUTSIDE AIR
DUCT - FLEXIBLE
DUCT - FLEXIBLE CONNECTION
DUCT - TRANSITION
SIZE SR
CFM
H
LS
FS
THERMOSTAT, REMOTE BULB
HUMIDISTAT
AIR FLOW SWITCH
LIMIT SWITCH
ELIMINATE THE TRANSMISSION OF NOISE OR VIBRATION FROM THE EQUIPMENT.
PIPING SYSTEM OR DUCT SYSTEM TO THE CONDITIONING SPACE.
SPECIFICATION AND/OR MANUFACTURER MODEL OR CATALOG NUMBER.
9. ALL EQUIPMENT, MATERIALS AND ACCESSORIES SHALL BE AS PER THE INDICATED.
10. UNLESS OTHERWISE NOTED IN DRAWINGS AND/OR SPECIFICATIONS ALL
EQUIPMENT AND ACCESSORIES SHALL BE FURNISHED AND INSTALLED BY THE
11. UNLESS OTHERWISE NOTED FOR ALL EQUIPMENT OUTSIDE BUILDING AND ON
LARGER CONCRETE SLABS OUTSIDE BUILDING, A 4-INCH THICK CONCRETE
CONTRACTOR.
HOUSEKEEPING PAD SHALL BE PROVIDED.
12. COORDINATE ROOF OPENING LOCATIONS FOR
MECHANICAL AND ELECTRICAL CONNECTIONS.
13. COORDINATION DURING THE CONSTRUCTION PHASE: STRUCTURAL, ELECTRICAL
AND MECHANICAL CONTRACTORS MUST COORDINATE THEIR WORK IN ORDER TO
PROVIDE THE REQUIRED CLEARANCES AND RIGHT OF WAYS FOR EACH OF THE
TRADES.
14. DESIGN WAS DONE BASED ON THE INTERNATIONAL CODES. CONTRACTOR MUST
PERFORM CONSTRUCTION AND INSTALLATIONS COMPLYING WITH THE CODES, STANDARDS
AND REGULATIONS INDICATED IN THE FOLLOWING 2018 INTERNATIONAL BUILDING CODE AND
INTERNATIONAL MECHANICAL CODE,
15. INSULATE ALL SUCTION REFRIGERANT PIPING WITH ARMAFLEX OR SIMILAR INSULATION.
16. INSULATE ALL CONDENSATE PIPING WITH INSULATION.
17. DUCT CONSTRUCTION AND INSTALLATION SHALL BE FLAT ON BOTTOM .
18. COORDINATE LOCATION OF BMS CENTRAL MONITORING AND CONTROL STATION WITH
FACILITIES PERSONNEL.
SUPLLY DIFFUSER
U/C
FD
3 HR FD
G
VD
AIR FLOW SUPPLY
AIR FLOW EXHAUST/RETURN
AIR FLOW THROUGH UNDERCUT DOOR
AIR FLOW THROUGH DOOR LOUVER
DAMPER - FIRE 3 HR RATED
DAMPER - FIRE 1HR RATED
DAMPER - MANUAL VOLUME
DAMPER - GRAVITY OPERATED
M FAN - CENTRIFUGAL
RISE OR DROP (IN RESPECT
TO AIR FLOW)
TRANSITION - RECTANGULAR TO ROUND
ROUND DUCT UP
ROUND DUCT DOWN
REDUCER (CONCENTRIC)
CAPPED DUCT
3. SECTIONS OF DUCT SHALL BE TESTED FOR LEAKAGE AT THE
4. DUCT WORK SUPPORTS SHALL COMPLY WITH SMACNA RECOMMENDATIONS
5. NO ELBOW SHALL BE MADE WITH AN INSIDE RADIUS OF LESS THAN
FOR TYPE OF DUCT CONSTRUCTION.
INDICATED PRESSURE CLASS.
THE WIDTH OF THE DUCT. SHALL ANY TURN BE NECESSARY WITH
INSIDE RADIUS LESS THAN 3/4 DEPTH OF THE DUCT, THEY MUST
BE FITTED WITH DOUBLE THICKNESS MULTIPLE VANES.
6. HVAC DUCT MATERIALS SHALL BE GALVANIZED STEEL, UNLESS
OTHERWISE INDICATED. EVS OR FUME HOOD EXHAUST DUCTWORK
SHALL BE CHEMICAL CORROSION RESISTANT.
7. THE MECHANICAL CONTRACTOR SHALL SUPPLY AND INSTALL ALL ELECTRICAL
EXHAUST/RETURN REGISTER
THERMOSTAT
CONTROLS, SAFETY SWITCHES AND ACCESSORIES NOT INDICATED IN THE
ELECTRICAL DRAWINGS AND NECESSARY FOR THE PROPER OPERATION OF THE
EQUIPMENT IN ACCORDANCE WITH THE MECHANICAL EQUIPMENTS
MANUFACTURERS RECOMMENDATIONS AND THE NATIONAL ELECTRIC CODE.
GENERAL NOTES
1. DUCTWORK FOR THE VENTILATION SYSTEMS SHALL BE MANUFACTURED AND
2. DUCTS SHALL BE RECTANGULAR OR ROUND AS INDICATED IN THE
ASSOCIATION, INC. SMACNA (LATEST EDITION).
INSTALLED IN ACCORDANCE WITH THE DUCT CONSTRUCTION STANDARDS
OF THE SHEET METAL AND AIR CONDITIONING CONTRACTORS NATIONAL
DRAWINGS.
GENERAL NOTES
1. THIS IS A GENERAL ABBREVIATION LIST. SOME
ABBREVIATIONS MAY NOT BE USED IN THIS PROJECT.
AS-BUILT SET
DATED: 31 May 2024
30 40
MH001
AutoCAD SHX Text
A. VARGAS
AutoCAD SHX Text
J. RUIZ
AutoCAD SHX Text 2020-01-14
" X
EF-01 EF-02
EF-04 EF-03EF-05
OFFICERS DINING AREA
LOBBY
WOMEN
RESTROOM
MEN
RESTROOM
MECH.
ROOM
FOOD PREP.
STO.
RESTROOM
WALK IN FREEZER
WALK IN COOLER
SCULLERY
MECH.
GENERATOR
OFFICE
AREA
STORAGE
ELEC.
ROOM
DINING AREA
ENTRANCE
WATER
HEATER/
SOFTENER
HALLWAY
SERVICE
ENTRANCE
SERVICE
AREA
VAV-02
VAV-04
VAV-05
VAV-06
EF-08
EF-07
SF-07
EA
MK'UP
VAV-07
20" X 18"
12"x12" EA DUCT
UP TO EF-06 AT
ROOF
CD-1 12"Ø
305 CFM SA
CD-1 12"Ø
305 CFM SA
EG-1 14"x12"
600 CFM EA
"x
6"
RG-1 10"Ø
220 CFM RA
12"x6"
"x
44"x22"
"x
"FOOD
STORAGE
RG-3 48" X 30"
4344 CFM RA
44"x22"
36"x18"
RG-2 14"x12"
504 CFM RA
CD-1 12"Ø
405 CFM SA
CD-1 12"Ø
405 CFM SA
CD-1 12"Ø
405 CFM SA
CD-1 12"Ø
405 CFM SA
CD-3 10"Ø
230 CFM SA
CD-4 10"Ø
240 CFM SA
CD-1 12"Ø
440 CFM SA
CD-1 12"Ø
445 CFM SA
LSD-1
4 SLOTS 3/4" x 8'-0"
1120 CFM SA
LSD-1
4 SLOTS 3/4" x 8'-0"
1120 CFM SA
LSD-1
4 SLOTS 3/4" x 8'-0"
1120 CFM SA
LSD-1
4 SLOTS 3/4" x 8'-0"
1120 CFM SA
LSD-1
4 SLOTS 3/4" x 2'-0"
280 CFM SA
LSD-2
4 SLOTS 3/4" x 4'-0"
560 CFM SA
LSD-2
6 SLOTS 3/4" x 4'-0"
840 CFM SA
LSD-2
6 SLOTS 3/4" x 4'-0"
840 CFM SA
LSD-2
6 SLOTS 3/4" x 4'-0"
840 CFM SA
LSD-2
6 SLOTS 3/4" x 4'-0"
840 CFM SA
O AL-1 78"x12"
1,587 C
FM
O A
LRD-2
6 SLOTS 3/4" x 8'-0"
2,560 CFM RA
LRD-1
4 SLOTS 3/4" x 8'-0"
1,505 CFM RA
HAND
WASH
AREA
VAV-01
"x
"x
SERVING
AREA
"x
AHU-01
SF-08
CD-1 12"Ø
405 CFM SA
LSD-3
8 SLOTS 1" x 10'-0"
3520 CFM SA
LSD-3
8 SLOTS 1" x 10'-0"
3520 CFM SA
18" X 16"
"x
"x
12" X 18"
20" X 28"
20" X 18" 16" X 14" 10" X 8"24" X 20"
"x
"x
14" X 12" 12" X 10"
" X
0"
12" X 6"
10" X 8"
12" X 10" 12" X 6"
18" X 10" 14" X 10"
" X
16" X 6"16"x16"
22" X 16"26" X 20" 22" X 16"
28" X 26"
"x
"x
12" X 10"
"x
"x
EG-3 18-3/4" X 13-3/4"
313 CFM EA
EG-3 18-3/4" X 13-3/4"
313 CFM EA
EG-3 18-3/4" X 13-3/4"
313 CFM EA
EG-3 18.75" X 13.75"
313 CFM EA
EG-3 18.75" X 13.75"
313 CFM EA
16"x10"
"x
"x
EAL-1 EAL-1
EAL-1 EAL-1 EAL-1
3HRFD
3HRFD 3HRFD
3HRFD
3HRFD
3HRFD
3HRFD
3HRFD
3HRFD 3HRFD
3HRFD
3HRFD
3HRFD
3HRFD
3HRFD
3HRFD 3HRFD
3HRFD
26"x10"
"x
"x
"x
"x
VAV-03
T
T
T
T
T
T
TVAV-02
VAV-01
VAV-04
VAV-07
VAV-03
VAV-06
VAV-05
SLOPE
12" x 18"
ACCESS HATCH
18" X 16"
ACCESS HATCH
14" X 12"
MH401
B
MH401
A
"x
22" X 16"
" X
"3HRFD
DUCT UP 45º
N
FI
R
ST
F
LO
O
R P
LA
N
H
VA
C L
AY
O
U T
NOTE:
FOR AS-BUILT, REFER TO
INDIVIDUAL DRAWINGS OF
SUPPLY AND RETURN SYSTEMS
ON NEXT PAGES
AS-BUILT SET
DATED: 31 May 2024
LSD-1
4 SLOTS 3/4" x 4'-0"
560 CFM SA
LSD-1
4 SLOTS 3/4" x 4'-0"
560 CFM SA
"x
31 40
MH101
AutoCAD SHX Text
SS.WH.
AutoCAD SHX Text
SS.DW.
AutoCAD SHX Text
A. VARGAS
AutoCAD SHX Text
J. RUIZ
AutoCAD SHX Text 2020-01-14
FOOD PREP.
OFFICE
HALLWAY
VAV-02
VAV-03
VAV-04
VAV-05
VAV-06
EF-08
CD-1 12"Ø
305 CFM SA
CD-1 12"Ø
305 CFM SA
12"x6"
44"x22"
44"x22"
CD-1 12"Ø
405 CFM SA
CD-1 12"Ø
405 CFM SA
CD-1 12"Ø
405 CFM SA
CD-1 12"Ø
405 CFM SA
CD-3 10"Ø
230 CFM SACD-4 10"Ø
240 CFM SA
CD-1 12"Ø
440 CFM SA
CD-1 12"Ø
445 CFM SA
LSD-1
4 SLOTS 3/4" x 8'-0"
1120 CFM SA
LSD-1
4 SLOTS 3/4" x 8'-0"
1120 CFM SA
LSD-1
4 SLOTS 3/4" x 8'-0"
1120 CFM SA
LSD-1
4 SLOTS 3/4" x 8'-0"
1120 CFM SA
LSD-1
4 SLOTS 3/4" x 2'-0"
280 CFM SA
LSD-2
6 SLOTS 3/4" x 4'-0"
840 CFM SA
LSD-2
6 SLOTS 3/4" x 4'-0"
840 CFM SA
LSD-2
6 SLOTS 3/4" x 4'-0"
840 CFM SA
LSD-2
6 SLOTS 3/4" x 4'-0"
840 CFM SA
LSD-1
4 SLOTS 3/4" x 4'-0"
560 CFM SA
LSD-1
4 SLOTS 3/4" x 4'-0"
560 CFM SA
O AL-1 78"x12"
1,587 C
FM
O A
HAND
WASH
AREA
26"x10"
VAV-01
"x
"x
"x
"x
AHU-01
CD-1 12"Ø
405 CFM SA
"x
"x
12" X 18"
20" X 28"
20" X 18" 16" X 14" 10" X 8"24" X 20"
"x
14" X 12" 12" X 10"
" X
0"
12" X 6"
10" X 8"
12" X 10" 12" X 6"
18" X 10" 14" X 10"
" X
16" X 6"
26" X 20"
12" X 10"
"x
"x
"x
"x
3HRFD
3HRFD
3HRFD
3HRFD
3HRFD
3HRFD
3HRFD
3HRFD
3HRFD
3HRFD
3HRFD
3HRFD
"x
T
T
T
T
T
T
TVAV-02
VAV-01
VAV-04
VAV-07
VAV-03
VAV-06
VAV-05
MH101-1
MH101-1
MH101-1
MH101-1
MH101-1
MH101-1
MH101-1
MH101-1
MH401
B
MH401
A
" X
VAV-07
16"x16"
16"x10"
"x
" X
3HRFD
DUCT UP 45º
P U
E R
T O
R
I C
A
M Y
T
I O
N
L
G U
A R
D
R E
P A
IR
S
T O
B U
IL
D
IN
G
D
IN
IN
G F
A C
IL
IT
Y F
O R
T A
LL
E
N J
U A
N A
D
IA
Z
P U
E R
T
IC
O
MH101-1
N
H
VA
C S
U
PP
LY
A
IR
D
IS
TR
IB
U
TI
O
N
SPINNING FITTING W/ MANUAL
DAMPERS AND FLEXIBLE
DUCTS OF 8".
SPINNING FITTING W/ MANUAL
DAMPERS AND FLEXIBLE
DUCTS OF 8".
AS-BUILT SET
DATED: 31 May 2024
CD-1 12"Ø
AutoCAD SHX Text
SS.WH.
SS.DW.
DATED: 31 May 2024 MH101-2
H
VA
C R
ET
U
R N
A N
D E
XH
AU
ST
A
IR
D
IS
TR
IB
U
TI
O
N
AutoCAD SHX Text
EF-01
AutoCAD SHX Text
EF-02
AutoCAD SHX Text
EF-04
AutoCAD SHX Text
EF-03
AutoCAD SHX Text
STO.
AutoCAD SHX Text
EF-08
AutoCAD SHX Text
EF-07
AutoCAD SHX Text
SF-07
AutoCAD SHX Text 20" X 18"
AutoCAD SHX Text 12"x12" EA DUCT
AutoCAD SHX Text
UP TO
AutoCAD SHX Text
EF-06
AutoCAD SHX Text
AT
AutoCAD SHX Text
ROOF
AutoCAD SHX Text EG-1 14"x12"
AutoCAD SHX Text
600 CFM EA
AutoCAD SHX Text 12"x6"
AutoCAD SHX Text
RG-1 10"Ø
AutoCAD SHX Text
220 CFM RA
AutoCAD SHX Text 12"x6"
AutoCAD SHX Text 40"x16"
AutoCAD SHX Text
4344 CFM RA
AutoCAD SHX Text 36"x18"
AutoCAD SHX Text RG-2 14"x12"
AutoCAD SHX Text
504 CFM RA
AutoCAD SHX Text OAL-1 78"x12"
AutoCAD SHX Text
1,587 CFM OA
AutoCAD SHX Text
LRD-2
AutoCAD SHX Text 6 SLOTS 3/4" x 8'-0"
AutoCAD SHX Text
2,560 CFM RA
AutoCAD SHX Text
LRD-1
AutoCAD SHX Text 4 SLOTS 3/4" x 8'-0"
AutoCAD SHX Text
1,505 CFM RA
AutoCAD SHX Text 26"x10"
AutoCAD SHX Text 26"x10"
AutoCAD SHX Text 26"x10"
AutoCAD SHX Text 30"x18"
AutoCAD SHX Text
AHU-01
AutoCAD SHX Text
SF-08
AutoCAD SHX Text
LSD-3
AutoCAD SHX Text 8 SLOTS 1" x 10'-0"
AutoCAD SHX Text
3520 CFM SA
AutoCAD SHX Text
LSD-3
AutoCAD SHX Text 8 SLOTS 1" x 10'-0"
AutoCAD SHX Text
3520 CFM SA
AutoCAD SHX Text 18" X 16"
AutoCAD SHX Text 14" X 8"
AutoCAD SHX Text 28" X 26"
AutoCAD SHX Text
EG-3 18-3/4" X 13-3/4"
AutoCAD SHX Text
313 CFM EA
AutoCAD SHX Text
EG-3 18-3/4" X 13-3/4"
AutoCAD SHX Text
313 CFM EA
AutoCAD SHX Text
EG-3 18-3/4" X 13-3/4"
AutoCAD SHX Text
313 CFM EA
AutoCAD SHX Text
EG-3 18.75" X 13.75"
AutoCAD SHX Text
313 CFM EA
AutoCAD SHX Text
EAL-1
AutoCAD SHX Text
EAL-1
AutoCAD SHX Text
EAL-1
AutoCAD SHX Text
3HRFD
AutoCAD SHX Text
3HRFD
AutoCAD SHX Text
3HRFD
AutoCAD SHX Text
3HRFD
AutoCAD SHX Text
3HRFD
AutoCAD SHX Text
KH-01
AutoCAD SHX Text
EXISTING
AutoCAD SHX Text
3HRFD
AutoCAD SHX Text 34"x12"
AutoCAD SHX Text
SLOPE
AutoCAD SHX Text
ACCESS HATCH
AutoCAD SHX Text 18" X 16"
AutoCAD SHX Text
ACCESS HATCH
AutoCAD SHX Text
AutoCAD SHX Text
MH101-2
AutoCAD SHX Text
AutoCAD SHX Text
MH101-2
AutoCAD SHX Text
AutoCAD SHX Text
MH101-2
AutoCAD SHX Text
AutoCAD SHX Text
MH101-2
AutoCAD SHX Text
AutoCAD SHX Text
MH101-2
AutoCAD SHX Text
MH401
AutoCAD SHX Text B
AutoCAD SHX Text
MH401
AutoCAD SHX Text A
AutoCAD SHX Text DUCT WORK, CONNECTION AND RELOCATIO OF THE EXISTING HOOD WERE DELETED FROM THIS JOB
AutoCAD SHX Text DUCT WORK, DIFFUSER AND CONNECTION TO THE EXISTING HOOD WERE DELETED FROM THIS JOB
AutoCAD SHX Text
SS.WH.
AutoCAD SHX Text
SS.DW.
AutoCAD SHX Text
A. VARGAS
J. RUIZ
MH102
4034AS-BUILT SET
DATED: 31 May 2024
R O
O F
PL
AN
H
VA
C L
AY
O
U T
AutoCAD SHX Text
SERVICE
AutoCAD SHX Text
ENTRANCE
AutoCAD SHX Text
SERVICE
AutoCAD SHX Text
AREA
AutoCAD SHX Text
ROOF
AutoCAD SHX Text
EF-06
AutoCAD SHX Text
NEW
AutoCAD SHX Text
EF-08
AutoCAD SHX Text
NEW
AutoCAD SHX Text
EF-07
AutoCAD SHX Text
NEW
AutoCAD SHX Text
SF-07
AutoCAD SHX Text
NEW
AutoCAD SHX Text
CU-01
AutoCAD SHX Text
OA
AutoCAD SHX Text
AutoCAD SHX Text
CFM
AutoCAD SHX Text
EA
AutoCAD SHX Text
SF-08
AutoCAD SHX Text
NEW
AutoCAD SHX Text
OA
AutoCAD SHX Text
AutoCAD SHX Text
CFM
AutoCAD SHX Text
EA
AutoCAD SHX Text
AutoCAD SHX Text
CFM
AutoCAD SHX Text
EA
AutoCAD SHX Text
AutoCAD SHX Text
CFM
AutoCAD SHX Text
SA
AutoCAD SHX Text
AutoCAD SHX Text
CFM
AutoCAD SHX Text
SA
AutoCAD SHX Text
REFRIGERANT LINES
AutoCAD SHX Text
DOWN TO AHU-01
AutoCAD SHX Text N
AutoCAD SHX Text
A. VARGAS
AutoCAD SHX Text
J. RUIZ
AutoCAD SHX Text 2020-01-14
AutoCAD SHX Text
AS SHOWN
NEW FREEZER & REFRIGERATOR CONDENSING UNITS
MH401
H
VA
C D
U C
TW
O
R K
SE
C
TI
O
N
1-1/2" INSULATION
CEILING
CEILING
LAMPS
SUPPLY CEILING DIFFUSER1-1/2" INSULATION
SECTIONA
SECTIONB
ROOF OPENING TO
EXHAUST FAN AND SUPPLY FAN
1'-6"
1' -0
'-4
8"
2'-2"
2'-2"
'-5
8"
9' -3
8"
2' -0
2'-0"
1' -0
1'-2"
'-6
2"
'-0
2"
9' -9
2"
9' -0
AS-BUILT SET
DATED: 31 May 2024
AutoCAD SHX Text
SCALE:
AutoCAD SHX Text 3/16"=1'-0"
AutoCAD SHX Text
HAND WASH
AutoCAD SHX Text
HVAC DUCT
AutoCAD SHX Text
MH401
AutoCAD SHX Text
SCALE:
AutoCAD SHX Text 3/16"=1'-0"
AutoCAD SHX Text
SERVING AREA
AutoCAD SHX Text
HVAC DUCT
AutoCAD SHX Text
MH401
AutoCAD SHX Text
A. VARGAS
AutoCAD SHX Text
J. RUIZ
AutoCAD SHX Text 2020-01-14
RECTANGULAR TO ROUND
TRANSITION
RECTANGULAR SUPPLY DUCT
UPSTREAM
STRAIGHT ROUND DUCT
4 DIA. (MIN. 2'-0")
FASTEN AND SEAL CONNECTION
VAV UNIT
CLINCH
CONNECTION
AI
R
F
LO
W
FASTEN AND SEAL
CONNECTION
ACOUSTICAL DUCT
LINING OR SOUND
ABSORBER AS
REQUIRED
MAIN
DUCT
NOTES:
1. THE OPERATION OF VARIABLE VOLUME TERMINAL UNITS ARE AFFECTED BY EXCESSIVE
TURBULENCE ON THE ENTERING SIDE OF EACH TERMINAL UNIT THEREFORE. TERMINAL
UNITS MUST NOT BE INSTALLED TOO CLOSE TO MAIN DUCTS, ELBOWS AND FITTINGS.
2. WHEN MINIMUM UPSTREAM STRAIGHT DUCT CONNECTION TO TERMINAL AS INDICATED
ABOVE CANNOT BE MAINTAINED, PROVIDE ORIFICE PLATE. STRAIGHTENING VANES OR
OTHER OTHER DEVICE AS RECOMMENDED BY TERMINAL UNT MANUFACTURER AND
SUBMIT TO ENGINEER FOR REVIEW PRIOR TO INSTALLATION.
3. MANUFACTURER OF TERMINAL UNIT SHALL PROVIDE CONTROLS ON LEFT OR RIGHT SIDE
AS REQUIRED BY FIELD CONDITIONS.
4. ARRANGE ACCESS TO PERMIT EASY FIELD BALANCE AND MAINTENANCE OF TERMINAL
UNIT
SCALE:
DETAIL9
NOT TO SCALE
VARIABLE AIR VOLUME
INSTALLATION
MH501
SMALL DOUBLE VANE
/11
UP TO 18"
AIR FLOW
1"R
"8 o90
2"R
AIR TURNED VANES
DOUBLE THICKNESS
SHEET METAL
90 ELBOW
DUCT
SHEET METAL
AIR FLOW
19" & 0VER
AIR FLOW
LARGE DOUBLE VANE
2 1/4"
4" R.
2" R.
o
DOUBLE THICKNESS
AIR FLOW
AIR TURNED VANES
SHEET METAL
DUCT
SHEET METAL
90 ELBOW
MAIN DUCT
LOCKING COLLAR
SPLITTER ROD
DAMPER
SPLITTER
AIR
FLOW
BRANCH DUCT
SECURE SAFING TO DUCT
CEILING
DIFFUSER
6"MIN.
FLOW
AIR
45°
"M
IN
IM
U M
6"M
IN 45°
OPPOSITE
BLADES DAMPER
SUPPLY AIR DUCT ACOUSTIC
LINED OR INSULATED AS
SCHEDULED
OPPOSED BLADE DAMPER,
INSTALL AS PER DIFFUSER
MANUFACTURER'S
RECOMMENDATIONS
DUCT DROP ACOUSTIC LINED
OR INSULATED AS
SCHEDULED
DUCT SEALANT
ALL AROUND
MAIN DUCT - ACOUSTIC
LINED OR INSULATED AS
SCHEDULED DOUBLE THICKNESS
VANES
POURED
CONCRETE OR
CMU WALL
RECTANGULAR
OR ROUND
DUCTWORK
SHEETMETAL SAFING ALL
AROUND (MIN 22 GA) TO
MATCH DUCTWORK
MATERIAL
DUCT EXTERIOR
INSULATION
NOTE: INTERIOR WALLS
REQUIRE SAFING ON ONE
SIDE ONLY ON CONCEALED
DUCTS AND ON BOTH SIDES
OF WALL ON EXPOSED
DUCTS
SHEETMETAL
DUCT
45 DEGREE ENTRY Ø = 45°
AT CORNERS
CLOSE OPENING
L=1/4" W, 4" MIN.
Ø
L
W
SCALE:
DETAIL1
NOT TO SCALE
CEILING DIFFUSER
MH501 SCALE:
DETAIL2
NOT TO SCALE
TYPICAL DAMPER
MH501 SCALE:
DETAIL3
NOT TO SCALE
SPLITTER DAMPER
MH501
SCALE:
DETAIL7
NOT TO SCALE
DUST PENETRATION NON-RATED WALLS
MH501
SCALE:
DETAIL12
NOT TO SCALE
BRANCH CONNECTION
MH501
VA
R
IE
S
C O
O R
D . I
N F
IE
LD
ANGLE SUPPORT
CONCRETE SLABEXPANSION
SELF-DRILLING
3/8" Ø
ALL THREADED ROD
SCALE:
DETAIL6
NOT TO SCALE
DUCTWORK SUPPORT
MH501
SI
ZE
V
AR
IE
S
(S
EE
D W
G S)
M
IN
2'
-0
SIZE VARIES
(SEE DWGS)
GALVANIZED
STEEL DUCT
(SEE SPECS)
BELLMOUTH
CONNECTION
WITH DAMPER
GYB.
FLEX DUCT CONN.
WITH METAL CLAMPS
HIGH CAPACITY
HEPA DIFFUSER
ACOUSTIC OR
GYP. CEILING
(SEE SPECS)
1-1/2" INSULATION
(SEE SPECS.)
SIZE VARIES
(SEE DWGS)
(S
EE
D W
G S)
SI
ZE
V
AR
IE
S
BELLMOUTH
CONNECTION WITH
DAMPER GYB.
FLEX DUCT CONN. WITH
METAL CLAMPS (THERMAFLEX
M-KC OR APPROVED EQUAL)
ACOUSTIC OR
GYP. CEILING (SEE
SPECS)
HIGH CAPACITY
ULPA DIFFUSER
1-1/2" INSULATION
(SEE SPECS.)
GALVANIZED
STEEL DUCT (SEE
SPECS)
SCALE:
DETAIL8
NOT TO SCALE
DIFFUSER FLEXIBLE CONNECTION
MH501
ISAT "ABHW" SEISMIC
BRACKET, ICBO #PFC 5566
OR APPROVED EQUAL.
THREADED ROD
SINGLE CHANNEL
TRAPEZE SUPPORT.
SINGLE CHANNEL DUCT
TOP REINFORCEMENT.
#10 SHEET METAL
SCREWS MAX. 12"O.C.
45°MAX.
ISAT "RCHW" SEISMIC
OR APPROVED EQUAL.
BRACKET, ICBO #PFC 5566
THREADED ROD
SECTION THRU HVAC DUCT
CONCRETE SLAB
EXPANSION
SELF-DRILLING
SCALE:
DETAIL4
NOT TO SCALE
ELBOW CONSTRUCTION
MH501
SCALE:
DETAIL10
NOT TO SCALE
TYPICAL DUCT SEISMIC RESTRAINT
2-WAY TRANSVERSE RIGID BRACING
MH501
"M
IN
.PREFABRICATED CURB AND
COUNTERFLASHING BY HVAC
CONTRACTOR
FLASHING BY G.C.
DUCTWORK - SEE PLAN
BACKDRAFT DAMPER
EXHAUST FAN
ROOF LEVEL
CONCRETE SLAB
SCALE:
DETAIL11
NOT TO SCALE
ROOF EXHAUST FAN INSTALLATION
MH501
AHU
TSP 1"
W
IT
H E
Q U
IP
M
EN
T
C O
O R
D . O
N F
IE
LD
MIN=FAN
2" DIA. PVC PIPE
SLOPE
6" DIA. FUNNEL
FINISH FLOOR
AHU CONDENSATE
ACCESS DRAIN FOR
FITTING CONNECTION
COORD. WITH EQUIPMENT
SCALE:
DETAIL5
NOT TO SCALE
CONDENSATE "P" TRAP AND
FUNNEL INSTALLATION
MH501
ELEVATION
CONCRETE SLAB
EXPANSION
SELF-DRILLING
BLADE LOCK
FUSIBLE LINK
FIRE RATED FLOOR
VERTICAL
WELD FIRE
DAMPER FRAME
TO SLEEVE
1 1/2" X 1 1/2" 1/8" ANGLE
IRON ALL AROUND DUCT,
WELD TO SLEEVE &
INSTALL TIGHT TO WALL
CONSTRUCTION.
BREAKAWAY TYPE
SLIP JOINT DUCT
CONNECTION
STAINLESS STEEL
NEGATOR CLOSURE
SPRING.
PACK VOID WITH 1/4"
MIN. TO 1/2" MAX.
NON-ASBESTOS
TYPE CAULKING.
#1Ø GAUGE BLACK
IRON SLEEVE ALL
AROUND
SCALE:
DETAIL13
NOT TO SCALE
FIRE DAMPER 3HR RATED
MH501
MH501
H
VA
C D
ET
AI
LS
AS-BUILT SET
DATED: 31 May 2024
AutoCAD SHX Text
A. VARGAS
AutoCAD SHX Text
J. RUIZ
AutoCAD SHX Text 2020-01-14
H
VA
C S
C H
ED
U
LE
S
D I R E C T E X P A N S I O N A I R H A N D L I N G U N I T S C H E D U L E
A I R S I D E
C O O L I N G C O I L
ENTERING LEAVING P.D.
INCH
WB.°FDB.°FWB.°FDB.°F
F/A
CFM
RETURN
CFMCFM
TOTAL
TYPEAREA SERVEDUNIT No.
TYPE (IN.
T.S.P.
W.G.)
PH.
VOLTSR.P.M.HP.
MOTOR
LOCATION
MOTOR
HZ.
F A N O P T I O N A L E Q U I P.
MIXING
BOX BOX
FILTER COMB.
F/M BOX
PRE
FILTER
EFF.
FINAL
FILTER
EFF.
SIMILAR TO REMARKS
TOTAL
CAPACITY
(MBH)
SENS.
CAPACITY
(MBH)
COIL
TYPE
FACE
AREA
EVAP.
TEMP.°F
ROWS
FPF
C O I L
W.G.
DESIGNATION TYPE FACE SIZEC F M REMARKSFINISH SIMILAR TO
AIR TERMINAL SCHEDULE
UNIT No. AREA SERVED TYPE FUNCTION CFM RPM.
TIP
SPEED
F.P.M.
S.P.
INCH
DRIVE SONES
HP R.P.M. VOLTS TYPEPH
HZ.
M O T O R
ACCESORIES SIMILAR TO REMARKS
F A N A N D V E N T I L A T O R S C H E D U L E
CLASS
PRESS
DUCTWORK CONSTRUCTION SCHEDULE
DC-DISCHARGE
AHU-SUPPLY/RETURN
DUCT SECTION
DC-SUCTION
GENERAL EXHAUST
TRANSVERSE
MATERIAL
CONSTRUCTION
CLASS
SEAL
CLASS CL
LEAKAGE
TEST
LEAK
JOINTS REMARKS
+4/-4
-22
+22
GALV. STEEL
GALV. STEEL
GALV. STEEL
-2 GALV. STEEL A
A
A
A
YES
YES
YES
YES
DUCTMATE OR
TDC
DUCTMATE OR
TDC
WELDED
WELDED
BASIS OF DESING-MANUFACTURER'S DATAMAXIMUM
SERVING
VARIABLE VOLUME BOX SCHEDULE
REMARK'S
MARK
IDENTIFICATION
CFM BOX
SIZE INLET (IN) NOISE CRITERIA BASIS
AIR RADIATED
CONTROL
VALVE
2 WAYOUTLET (IN)RM. #
P.D.
(IN.WG)
AT.MAX.CFM
SIMILAR TO
TEMP.°F
SUCTION
HZ.
PH.
COMPRESSORS WATER COOLED CONDENSERCONDENSER-FANS
AIR COOLED
TEMP.°F
SUCTION VOLTS.KW.CAPACITYQTY
SERVICEUNIT No.
HP.
MOTOR VOLTS.QTY HZ.
PH.
FACTOR
FOULING
FT. WG.
P.D.
TEMP.°F
COND. EWT.°F LWT,°F GPM
SIMILAR TO REMARKS
CONDENSING UNIT SCHEDULE
VAV-01 01,04 1910 PRICE SDV5
VAV-02 02 1680
VAV-03
VAV-04
VAV-05
VAV-06
VAV-07
09,11,18
16" X 15" 21
.54
.55
.64
.54
.21
.22
.35
AHU-01 BLDG.#148 AHU-01 10660 5760 - 82 73.5 54.97 54.83 .77 669.21 315.05 - 24.41 6
14 - 2.54 8.2 10 1800 208 - - - - CARRIER- 28ME ANTI CORROSION TREATMENT
CU-01 AHU-01 1 674.8 45 59.60 208 3
60 - 4 - 208 3
N/A N/A N/A N/A N/A N/A CARRIER 38APD
.016 - .095 METALAIRE 5750 SERIES 4- WAY CEILING DIFFUSERCD-1 395-470
.025-034 METALAIRE 4- WAY CEILING DIFFUSERCD-2
.080 METALAIRELRD-2
.037 METALAIRE CC5-1 -RG-1
.037 CC5-1 -RG-2 METALAIRE
275-325
320CFMFT
327-392
554-665
CONSTRUCTION
ALUMINUM
MATERIAL
ALUMINUM
ALUMINUM
ALUMINUM
ALUMINUM
P.D.
IN W.G
24" X 24"
24" X 24"
13" X 13"
17" X 15"
DAMPER
WHITE OBD
EF-01
EF-02
EF-03
EF-04
EF-06
EF-07
MEN BATHROOM
WOMEN BATHROOM
RESTROOM
STORAGE
SCULLERY
SERVING AREA
CEILING BLOWER EXHAUST 313
.75
1.5
13.4
.33
SF-07 SERVING AREA 1920 1269 3322 1.5 - 24 1.5 1725 208 3
EXHAUST
EXHAUST
EXHAUST
EXHAUST
EXHAUST
SUPPLY
CENTRIFUGAL
ROOF
CENTRIFUGAL
ROOF ODP-SE
ODP-PE
ODP-PE
ROOF CURB COOK ACRU-B
VCR-XP
ROOF CURB KSP-B
COOK
COOK
.50
.50
5.5
5.5
.15 115 -
- COOK
COOK GEMINI 200-700 SERIES
CEILING BLOWER 115 1
ANTI CORROSION TREATMENT,
HURRICANE RATED.
RIGHT
SIDE
BHP
FORWARD
CURVED
PRICE SDV5
PRICE SDV5
PRICE SDV5
PRICE SDV5
PRICE SDV5
PRICE SDV5
14" X 12-1/2"
24" X 18"
12" X 8"
12" X 10"
12" X 10"
16" X 15"
22 5 1725 208 3 60 ODP-PE ROOF CURB VCR-HPCOOKEF-08 FOO PREP 8800 958 7524 1.5 -EXHAUSTCENTRIFUGAL
ROOF
KITCHEN SUPPLY
PACKAGED
SF-08 FOOD PREP 7040 793 4152 1.5 - 31 5 1725 208 3
SUPPLY ODP-PE ROOF CURB KSP-BCOOKKITCHEN SUPPLY
PACKAGED
ALUMINUM WALL CAP
WCA-2
ALUMINUM WALL CAP
WCA-2
GEMINI 200-700 SERIES
NECK SIZE
12"Ø
10"Ø WHITE
WHITE
WHITE
WHITE
OBD
5750 SERIES
.037 COOK SG-12 FRAME AT A 40 DEGREE ANGLEEG-1
.500 SG-12 FRAME AT A 40 DEGREE ANGLEEG-2 COOK
SEE IN DWGS
SEE IN DWGS
ALUMINUM
ALUMINUM
17" X 15"
13-1/2" x 13-1/2" 12" X 12"
WHITE
WHITE
6675R SERIES
METALAIRECD-3 ALUMINUM WHITE OBD24" X 24" 10"Ø 5750 SERIES
METALAIRECD-4 ALUMINUM WHITE OBD24" X 24" 10"Ø 5750 SERIES
.129 METALAIRELSD-1 140 CFMFT ALUMINUM WHITE OBDSEE IN DWGS SEE IN DWGS 6675 SERIES
.129 METALAIRELSD-2 210 CFMFT ALUMINUM WHITE OBD 6675 SERIES
.080 METALAIRELRD-1 200 CFMFT ALUMINUM WHITE - 6675R SERIES
275-325 .025-034
275-325 .025-034
FUNCTION
SUPPLY
SUPPLY
SUPPLY
SUPPLY
SUPPLY
SUPPLY LINEAR
DIFFUSER
LINEAR
DIFFUSER
SEE IN DWGS SEE IN DWGS
4 SLOT 3/4"
6 SLOT 3/4"
RETURN
RETURN
LINEAR
DIFFUSER
LINEAR
DIFFUSER
SEE IN DWGS SEE IN DWGS
SEE IN DWGS SEE IN DWGS
RETURN RETURN
GRILL
RETURN RETURN
GRILL
CEILING
DIFFUSER
2- WAY CEILING DIFFUSER
3- WAY CEILING DIFFUSER
CEILING
DIFFUSER
CEILING
DIFFUSER
CEILING
DIFFUSER
4 SLOT 3/4"
6 SLOT 3/4"
10" X 10"
14" X 12"
EXHAUST
EXHAUST
EXHAUST
GRILL
EXHAUST
GRILL
14" X 12"
EXHAUST EXHAUST
GRILL
SEE IN DWGS 18-3/4" x 13-3/4" 16-3/8"X11-3/8" .500 ALUMINUM WHITE
COOK GEMINI ALUMINUM
GRILLEEG-3 -
.08 METALAIRELRD-3 560CFMFT ALUMINUM WHITE - 6610R SERIESRETURN LINEAR
DIFFUSER SEE IN DWGS SEE IN DWGS 8 SLOT 1"
ROOF CURB
MH601
INTAKE OUT SIDE
AIR
SEE IN DWGS SEE IN DWGS SEE IN DWGS .20 ALUMINUM MILL - RUSKIN EME420MDOAL-1 HIRRICANE RATED, ANTI CORROSION TREATMENT, BIRDSCREEN
.037 CC5-1 -RG-3 METALAIRE3840-4800 ALUMINUM49-3/4" X 31-3/4" WHITE -RETURN RETURN
GRILL
ALUMINUM
48" X 30"48" X 30"
CEILING BLOWER
CEILING BLOWER
313 1600 2644 60.50 - 5.5 - COOK115 1 ALUMINUM WALL CAP
WCA-2
GEMINI 200-700 SERIES
313 1600 2644 60.50 - 5.5 - COOK115 1 ALUMINUM WALL CAP
WCA-2
GEMINI 200-700 SERIES
.15
.15
.15
.129 METALAIRELSD-3 360 CFMFT ALUMINUM WHITE OBD 6675 SERIESSUPPLY LINEAR
DIFFUSER SEE IN DWGS SEE IN DWGS 8 SLOT 1"
EAL-1
EXHAUST AIR LOUVER
EXHAUST LOUVER 18" X 18".
GRAVITY EXHAUST COMBINATION.
LOUVER DAMPER 6" EXTRUDED.
ALUMINUM DRAINABLE.
ALUMINUM BLADES5
8" X .040".
ALUMINUM SCREEN.
ALUMINUM BACKDRAFT DAMPER COMBINED IN
COMMON FRAME.
45 % FREE AREA.
FINISH TO BE SELECTED BYARCHITECT.
SIMILAR TO RUSKIN - ELBD375E
REMARKS:
1. EXHAUST AND MAKE UP AIR FANS SHALL BE
CONTROLLED WITH THE LIGHT SWITCH OF THE
KITCHEN HOOD THEY SERVE. PROVIDE REQUIRED
ELECTRICAL CONNECTIONS.
2. ANTI CORROSION TREATMENT.
3. HURRICANE RATED.
4. BIRDSCREEN.
1,2
1,2
1,2
1,2
2,3,4
2,3
2,3
2,3
2,3
AS-BUILT SET
DATED: 31 May 2024
AutoCAD SHX Text
A. VARGAS
AutoCAD SHX Text
J. RUIZ
AutoCAD SHX Text 2020-01-14
AutoCAD SHX Text
AS SHOWN
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
BACnet MS/TP
SITE NETWORK
ARCHITECTURE
BUILDING MANAGEMENT SYSTEM
EC-B0S-8
CONTROLLER / SERVER
MEMORY EXPANSION MEMORY
WEB USER INTERFACE ADD-ON
DUAL PORT RS-485
POWER MODULE
DRIVER FOR MS/TP BACnet
EC-BOS-6 W/
EC-NPM-256
EC-NPB-2X-485
EC-WPM-US
EC-DIR-MSTP
EC-UI-SAX
MOUSE
WORK STATION
KEYBOARD
MONITOR
ETHERNET
TABLETSMART PHONE
EXHAUST FANS 01,02,03,04,05,06,07,08
D
IS
TE
C
H C
O N
TR
O
LS
AHU-1
EC
B
-X X
AHU-1
BACnetECB-VAVS
CONTROLS
DISTECH
DISTECH
CONTROLS CONTROLS
DISTECH
DISTECH
CONTROLS
ECB-VAVS BACnet
AHU-1 AHU-1
BACnetECB-VAVS
CONTROLS
DISTECH
DISTECH
CONTROLSCONTROLS
DISTECH
DISTECH
CONTROLS
ECB-VAVS BACnet
AHU-1 AHU-1
BACnetECB-VAVS
CONTROLS
DISTECH
DISTECH
CONTROLS
AHU-1
BACnetECB-VAVS
CONTROLS
DISTECH
DISTECH
CONTROLSCONTROLS
DISTECH
DISTECH
CONTROLS
ECB-VAVS BACnet
AHU-1
VAV-05 VAV-06 VAV-07VAV-03 VAV-04VAV-02VAV-01
D
IS
TE
C
H C
O N
TR
O
LS
EC
B
-X X
COMMUNICATION WIRES
FROM PREVIOUS BACnet VAV DDC CONTROLLER
ROOM TEMPERATURE SENSOR
COMMUNICATION WIRES
TO NEXT BACnet VAV DDC CONTROLLER
DISTECH-CONTROLS ; MODEL: ECB-VAVS
BACnet VAV CONTROLLER
VELOCITY PROBE
MODEL: EC-VUE
DISTECH-CONTROLS
CONTROL TRANSFORMER
120 VAC / 24VAC
DISTECH-CONTROLS
CONTRACTOR
120 VAC BY ELECTRICAL
GROUND
NEUTRAL
LINE
VAV DDC CONTROLLER CONTROL DIAGRAM
TYPICAL FOR ROOM TEMPERATURE CONTROL APPLICATION
NOTE: INTERLOCK WITH
AHU'S SCHEDULE
SATUSDI
M
CONTACTOR
120 Vac
EXHAUST FANS CONTROLS SCHEMATIC
CS-01 CURRENT SWITCHES ACIA/MCS
SIMILAR TODESCRIPTIONDESIGNATION
BILL OF MATERIAL
BC-1 BACnet CONTROLLER ECB-XXX DISTECH-CONTROLS
BC-XX
DISTECH CONTROLS
CONTROL
TRANSFORMER
TERMINALSBREAKER
CIRCUIT
FANS 1,2 & 3 LOCAL CONTROL PANEL
START/STOPDO
EXHAUST FANS 01,02,03,04,05,06,07,08
H O A
SUPPLY FANS 07,08
SIMILAR TO:
SUPPLY FANS 07,08
SIMILAR TO:
SIMILAR TO:
MH602
H
VA
C C
O N
TR
O
LS
AS-BUILT SET
DATED: 31 May 2024
NOTE:
EF-06 WILL BE THE ONLY FAN TO BE
CONTROLLED BY THE HVAC CONTROL SYSTEM
AutoCAD SHX Text
A. VARGAS
AutoCAD SHX Text
J. RUIZ
AutoCAD SHX Text 2020-01-14
AI
DTS-02
COIL
AI
DI
DO
AO
BC-XX
AIR HANDLING UNITS 01 CONTROL DIAGRAM
120 VAC
TO FIRE ALARM
SD-01
DI
FROM UNITS EQUIPMENT
INPUTS AND OUTPUTS
AI
LH
DPT-01 DTS-01
AI
D
SPEED CONTROL
STATUS
AO
DI
VFD
M
DO START/STOP
X
AIR
OUTSIDE
FILTERS
RETURN
AIR
DTS-03AI
COOLING
SYSTEM
BC-XX
DISTECH CONTROLS
CONTROL
TRANSFORMER
TERMINALSBREAKER
CIRCUIT
AHU-1 & 3 LOCAL CONTROL PANEL
2 SD-01 DUCT SMOKE DETECTOR SYSTEM SENSORD4120
2 CO2-01 & 02 CARBON DIOXIDE SENSORS KELEKCD
BAPIDTS-031
2 DTS-01 & 02 DUCT TEMPERATURE SENSORS- 12 INCHES BAPIBA/10K3-D12-WP
BILL OF MATERIAL
DUCT TEMPERATURE SENSORS- 8 INCHES BA/10K3-D8WP
BELIMONMX24-SRMODULATING DAMPER ACTUATORDA-01, 02 & 032
SUPPLY
AIR
AI CO2-02
AI CO2-01
AO
AO
616 DWYERDIFFERENTIAL PRESSURE TRANSMITTERDPT-01 & 022
1 BC-1 BACnet CONTROLLER- 12UI/12UO ECB-300 DISTECH-CONTROLS
TO CONDENSING UNIT
L
DPT-02
AI
H
DA
DA
1 VFD-01
1 VFD-03
SD-01
DI
TO FIRE ALARM
SYSTEM
AHU
1. THE BMS SHOULD START / STOP THE UNIT BASE ON A DAILY
SCHEDULE.
2. CONTROL BMS WILL MONITOR SUPPLY, RETURN AND MIX
TEMPERATURE SENSORS. A CARBON DIOXIDE SENSORS
FOR OUTSIDE AND RETURN AIR, STATIC PRESSURE
SENSOR, SMOKE DETECTOR, FILTER AND FAN STATUS.
3. VARIABLE FREQUENCY DRIVE WILL INCREASE OR
DECREASE HZ IN ORDER TO REACH DESIRE STATIC
PRESSURE SETPOINT. THE VFD WILL DECREASE UNTIL A
SPECIFIC HERTZ THAT WILL BE DETERMINE BY BALANCE
CONTRACTOR.
4. A SMOKE DETECTOR INSTALLED AT THE SUPPLY DUCT WILL
SHUTDOWN THE UNIT IN CASE OF ACTIVATION.
5. A SUPPLY TEMPERATURE SENSOR WILL MONITOR THE UNIT
TO ASSURE 55 °F.
6. CARBON DIOXIDE SENSOR INSTALLED AT THE RETURN
DUCT WILL MONITOR PPM AND COMPARE IT WITH OUTSIDE
CARBON DIOXIDE PPM. IF THE CO2 SENSOR FROM THE
RETURN IS HIGHER THAN 1,000 PPM AND 250 PPM FROM
OUTSIDE CO2 A CONTROL DAMPER AT THE FRESH AIR WILL
MODULATE TO OPEN AN A CONTROL DAMPER AT THE
RETURN WILL MODULATE TO CLOSE.
7. A DIFFERENTIAL PRESSURE TRANSMITTER WILL BE
INSTALLED TO MONITOR FILTER CONDITION.
EXHAUST FANS
1. THE BMS WILL START THE FANS EVERY TIME THE SYSTEM DETECT AN
AIR HANDLING UNIT RUN STATUS.
2. FANS WILL STOP WHEN THE BMS IDENTIFY THAT ALL UNITS HAS A
STOP STATUS.
3. CONTROL BMS WILL MONITOR FANS STATUS.
4. KITCHEN EXHAUST & SUPPLY FANS WILL BE CONTROL BYLOCAL
SWITCH @ KITCHEN HOOD .
VAV'S
1. CONTROLS VAV'S WILL BE INDIVIDUALLY PROGRAMMED BASED ON
THE DESIGN AIR FLOW (CFM)
2. A ZONE SENSOR WILL MONITOR ROOM TEMPERATURE AND MODULATE
THE BOX TO ASSURE THE 72 °F
3. CONTROL BMS WILL MONITOR BOX POSITION, CFM, MAX AND MIN.,
TEMPERATURE AND SETPOINT.
SEQUENCE OF OPERATION:
VARIABLE FREQUENCY DRIVE 7.5 HP 480/60/3
FOR AHU-1
VARIABLE FREQUENCY DRIVE 1 HP 208/3/60
FOR AHU-3
208 V FOR AHU-1
MH603
H
VA
C C
O N
TR
O
LS
AS-BUILT SET
DATED: 29 May 2024
QTY DESIGNATION DESCRIPTION SIMILAR TO
AutoCAD SHX Text
A. VARGAS
AutoCAD SHX Text
J. RUIZ
AutoCAD SHX Text 2020-01-14
FI
E
AL
AR
M
F
LO
O R
P
LA
N
LOBBY
WOMEN
RESTROOM
MEN
RESTROOM
MECH. ROOM
EXISTING FOOD PREP.
STO. REST.
WALK IN FREEZER
WALK IN COOLER
SCULLERY
MECH.
ROOM FOOD STORAGE
STORAGE
ELECTRICAL
ROOM
DINING AREA
ENTRANCE
WATER
HEATER/
SOFTENER
SERVICE
ENTRANCE
HAND WASH AREA
OFFICE
AREASERVING AREA
OFFICERS
DINING AREA
HALLWAY
FIRE ALARM FLOOR PLAN
LEGEND:
AS-BUILT SET
DATED: 31 May 2024 �� ��
F��
AutoCAD SHX Text 2020-01-14
| Sheets and Views |
| Model |
| Sheets and Views |
| Model |
| Sheets and Views |
| Model |
| Sheets and Views |
| Model |
| Sheets and Views |
| Model |
| Sheets and Views |
| Model |
| Sheets and Views |
| Model |
| Sheets and Views |
| Model |
| Sheets and Views |
| Model |
| Sheets and Views |
| Model |
| Sheets and Views |
| Model |
| Sheets and Views |
| Model |
| Sheets and Views |
| Model |
| Sheets and Views |
| Model |
| Sheets and Views |
| Model |
| Sheets and Views |
| Model |
| Sheets and Views |
| Model |
| Sheets and Views |
| Model |
| Sheets and Views |
| Model |
| Sheets and Views |
| Model |
| Sheets and Views |
| Model |
| Sheets and Views |
| Model |
| Sheets and Views |
| Model |
| Sheets and Views |
| Model |
| Sheets and Views |
| Model |
| Sheets and Views |
| Model |
| Sheets and Views |
| Model |
| Sheets and Views |
| Model |
| Sheets and Views |
| Model |
| Sheets and Views |
| Model |
| Sheets and Views |
| Model |
| Sheets and Views |
| Model |
| Sheets and Views |
| Model |
| Sheets and Views |
| Model |
| Sheets and Views |
| Model |
| Sheets and Views |
| Model |
| Sheets and Views |
| Model |
| Sheets and Views |
| Model |
| Sheets and Views |
| Model |
| Sheets and Views |
| Model |
File details come from the government source that posted it. Updated .