This document is a set of architectural and engineering site security drawings for the Cincinnati VA Medical Center site security updates project (VA Project No. 539-22-208). The drawings comprise the bid set for construction work dated November 24, 2025, with addendum 2 dated May 8, 2024, and include overall campus site plans, building floor plans, ICRA (Infection Control Risk Assessment) details, electrical plans, technology/security system plans, and general construction details.

The scope encompasses demolition and installation of perimeter security improvements across the Cincinnati VA Medical Center campus at 3200 Vine Street, Cincinnati, Ohio 45220. Key security work includes removal and replacement of existing gates and controls at multiple site areas (Areas 1-7, with some areas designated 4-15), installation of sliding gates with ground loops and card readers, pedestrian gates with keypad/card reader access, swing gates with motorized operators, and bollard/planter arrangements for vehicle access control. Electrical work requires installation of power connections (20A at 120V and 208V) to support gate operators and access control devices across four electrical panels (BC1, LP2, EBCA, R1A) located in various buildings. The technology infrastructure involves installation of conduit runs, junction boxes, and connections to existing telecommunications closets to support access control system integration with the Johnson Controls P2000 Physical Access Control System (PACS). Work is restricted to evening hours after 5:00 PM and weekends in patient care areas, with full coordination required with the Contracting Officer's Representative (COR). Construction activities within buildings require ICRA Class III isolation procedures with negative air pressure and HEPA filtration in specified areas, including corridors, mechanical rooms, and electrical closets identified on detailed floor plans.

View the file

Other files for this federal contract opportunity

Other files attached to Z1DA--Site Security Updates at Cincinnati VAMC. Project No. 539-22-208, newest first.
File Type Posted
36C25026B0032 0003.pdf PDF
Attach 2.1 - RFI Responses.pdf PDF
Attach 2.2 - ICRA Permit.pdf PDF
36C25026B0032 0002.pdf PDF
Attach 1.1 - Site Visit Sign In Log.pdf PDF
36C25026B0032 0001.pdf PDF
36C25026B0032_1.pdf PDF
Attach IV - VAAR 852.219-75 VA NOTICE OF LIMITS ON SUBCONTRACTING_CERT OF COMPLIANCE JAN 2023 DEV.doc.docx DOCX document
Attach V - Sole Source JA - redact - 539-22-208.pdf PDF
Attach I - Wage Determination 1.2.2026.txt TXT text file
Attach II - Site Security Specifications 2.23.26.pdf PDF
Attach VI - RFI Site Security.doc DOC document
Show all 12

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

CINCINNATI VA MEDICAL CENTER

NRM Site Security Updates

US DEPARTMENT OF VETERANS AFFAIRS

VA CINCINNATI HEALTH CARE SYSTEM

VA PROJECT NUMBER: 539-22-208

OVERALL CAMPUS SITE PLAN, BUILDING NUMBER, AND PROJECT LOCATOR

PROJECT LOCATIONOVERALL CAMPUS

E

SHIELDS

ST

PUBLIC

R/W

VI

N

E

ST

PU

B

LI

C

R /W

GOODMANDRPUBLICR/W

G001

GENERAL - COVER SHEET

GI-001

CONSULTANTS: ARCHITECT/ENGINEERS:

Revisions: Date:

Drawing Title

VA Health Care System Approval:

Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

Drawing # of

Veterans Health

Administration www�daengineering�com www�daengineering�com voice �31�� 4�4-�0�0 2�0� Rand Road Indianapolis, Indiana 4�241 fa[ �31�� 4�4-�3�3

Mechanical, Electrical, and Energy Engineering

DESIGN-AIRE ENGINEERING, INC.

11-24-2025 DEH BZ

AE Site Security Updates (CIN) 539-22-208

CINCINNATI VA MEDICAL CENTER

3200 VINE STREET - CINCINNATI, OH 45220

SITE

For Official Use Only (FOUO)

BID SET

Kristina Amin Chief Engineer Cincinnati VA Medical Center

ADDENDUM 2 05/08/24

FENCING NOTES 11/24/25

E

SHIELDS

ST

VI

N

E

ST

AREA 2 AREA 1

AREA 12

AREA 13

AREA 8

AREA 5

AREA 14

AREA 12

AREA 12

AREA 11

AREA 15

AREA 15

AREA 15

AREA 15

CONSULTANTS: ARCHITECT/ENGINEERS:

Revisions: Date:

Drawing Title

VA Health Care System Approval:

Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

Drawing # of

Veterans Health

Administration www�daengineering�com www�daengineering�com voice �31�� 4�4-�0�0 2�0� Rand Road Indianapolis, Indiana 4�241 fa[ �31�� 4�4-�3�3

Mechanical, Electrical, and Energy Engineering

DESIGN-AIRE ENGINEERING, INC.

11-24-2025 DEH BZ

AE Site Security Updates (CIN) 539-22-208

CINCINNATI VA MEDICAL CENTER

3200 VINE STREET - CINCINNATI, OH 45220

SITE

For Official Use Only (FOUO)

BID SET

Kristina Amin Chief Engineer Cincinnati VA Medical Center

ADDENDUM 2 05/08/24

FENCING NOTES 11/24/25

PROJECT WORK AREAS

SITE PLAN - NORTH

GI-101

GOODMANDR

AREA 8

AREA 5

AREA 7

AREA 10

AREA 4

Drawing Title

VA Health Care System Approval:

Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

Drawing # of

Veterans Health

Administration www�daengineering�com www�daengineering�com voice �31�� 4�4-�0�0 2�0� Rand Road Indianapolis, Indiana 4�241 fa[ �31�� 4�4-�3�3

Mechanical, Electrical, and Energy Engineering

DESIGN-AIRE ENGINEERING, INC.

11-24-2025 DEH BZ

AE Site Security Updates (CIN) 539-22-208

CINCINNATI VA MEDICAL CENTER

3200 VINE STREET - CINCINNATI, OH 45220

SITE

For Official Use Only (FOUO)

BID SET

Kristina Amin Chief Engineer Cincinnati VA Medical Center

ADDENDUM 2 05/08/24

FENCING NOTES 11/24/25

PROJECT WORK AREAS

SITE PLAN - SOUTH

GI-102

ST

PUBLIC

R/W

VI

N

E

ST

PU

B

LI

C

R /W

CONSULTANTS: ARCHITECT/ENGINEERS:

Revisions: Date:

Drawing Title

VA Health Care System Approval:

Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

Drawing # of

Veterans Health

Administration www�daengineering�com www�daengineering�com voice �31�� 4�4-�0�0 2�0� Rand Road Indianapolis, Indiana 4�241 fa[ �31�� 4�4-�3�3

Mechanical, Electrical, and Energy Engineering

DESIGN-AIRE ENGINEERING, INC.

DEH BZ

AE Site Security Updates (CIN) 539-22-208

CINCINNATI VA MEDICAL CENTER

3200 VINE STREET - CINCINNATI, OH 45220

SITE

For Official Use Only (FOUO)

BID SET

Kristina Amin Chief Engineer Cincinnati VA Medical Center

ADDENDUM 2 05/08/24

EXISTING UTILITIES

SITE PLAN - NORTH

GI-201

REBID 08/30/24

11-24-2025

GOODMANDRPUBLICR/W

Revisions: Date:

Drawing Title

VA Health Care System Approval:

Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

Drawing # of

Veterans Health

Administration www�daengineering�com www�daengineering�com voice �31�� 4�4-�0�0 2�0� Rand Road Indianapolis, Indiana 4�241 fa[ �31�� 4�4-�3�3

Mechanical, Electrical, and Energy Engineering

DESIGN-AIRE ENGINEERING, INC.

DEH BZ

AE Site Security Updates (CIN) 539-22-208

CINCINNATI VA MEDICAL CENTER

3200 VINE STREET - CINCINNATI, OH 45220

SITE

For Official Use Only (FOUO)

BID SET

Kristina Amin Chief Engineer Cincinnati VA Medical Center

ADDENDUM 2 05/08/24

EXISTING UTILITIES

SITE PLAN - SOUTH

GI-202

11--24-2025

ST

VI

N

E

ST

AREA 2 AREA 1

CONSULTANTS: ARCHITECT/ENGINEERS:

Revisions: Date:

Drawing Title

VA Health Care System Approval:

Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

Drawing # of

Veterans Health

Administration www�daengineering�com www�daengineering�com voice �31�� 4�4-�0�0 2�0� Rand Road Indianapolis, Indiana 4�241 fa[ �31�� 4�4-�3�3

Mechanical, Electrical, and Energy Engineering

DESIGN-AIRE ENGINEERING, INC.

DEH DAE

AE Site Security Updates (CIN) 539-22-208

CINCINNATI VA MEDICAL CENTER

3200 VINE STREET - CINCINNATI, OH 45220

SITE

For Official Use Only (FOUO)

BID SET

Kristina Amin Chief Engineer Cincinnati VA Medical Center

ADDENDUM 2 05/08/24

SEE ENLARGED PLANS

FOR ICRA DETAILS

A1

GJ301

KEYED PLAN NOTES:

1. SPACE IS LOCATED ON THE EXTERIOR OF ALL BUILDINGS. ICRA IS NOT REQUIRED.

2. ELECTRICAL CONDUIT AND TECHNOLOGY CONDUITS THROUGH BUILDING. SEE

'EP' AND 'T' SHEETS.

GJ-101

OVERALL ICRA AREAS

SITE PLAN - NORTH

SEE ENLARGED PLANS

FOR ICRA DETAILS

A2

GJ302

SEE ENLARGED PLANS

FOR ICRA DETAILS

A1

GJ301

GENERAL PROJECT NOTES:

1. ALL INSIDE BUILDING WORK THAT IS IN CORRIDORS, PATIENT AREAS, AND IN

PUBLIC VIEW WILL BE DONE DURING EVENING HOURS AFTER 5:00PM (1700HRS) OR

ON WEEKENDS. ANY WORK IN AREAS #1, #4, AND #5 THAT INTERRUPTS OR

BLOCKS VEHICLES/PERSONS TRAFFIC SHALL ONLY BE DONE AFTER 5 PM OR ON

WEEKENDS. THESE AREAS CANNOT BE CLOSED DURING BUSINESS HOURS, 7 AM TO

5 PM. COORDINATE ALL WORK WITH THE COR

AREA 5

AREA 7

AREA 4

CONSULTANTS: ARCHITECT/ENGINEERS:

Revisions: Date:

Drawing Title

VA Health Care System Approval:

Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

Drawing # of

Veterans Health

Administration www�daengineering�com www�daengineering�com voice �317� 4�4-�0�0 2707 Rand Road Indianapolis, Indiana 4�241 fa[ �317� 4�4-�3�3

Mechanical, Electrical, and Energy Engineering

DESIGN-AIRE ENGINEERING, INC.

DEH DAE

AE Site Security Updates (CIN) 539-22-208

CINCINNATI VA MEDICAL CENTER

3200 VINE STREET - CINCINNATI, OH 45220

SITE

For Official Use Only (FOUO)

BID SET

Kristina Amin Chief Engineer Cincinnati VA Medical Center

ADDENDUM 2 05/08/24

A5

GJ304

A4

GJ302

SEE ENLARGED PLAN

FOR ICRA DETAILS

SEE ENLARGED PLAN

FOR ICRA DETAILS KEYED PLAN NOTES:

1. SPACE IS LOCATED ON THE EXTERIOR OF ALL BUILDINGS. ICRA IS NOT REQUIRED.

2. ELECTRICAL CONDUIT AND TECHNOLOGY CONDUITS THROUGH BUILDING. SEE

'EP' AND 'T' SHEETS.

GJ-102

OVERALL ICRA AREAS

SITE PLAN - SOUTH

A3

GJ303SEE ENLARGED PLAN

FOR ICRA DETAILS

1 1

A10

GJ306SEE ENLARGED PLANS

FOR ICRA DETAILS

A8, A9

GJ306

A6, A7

GJ305SEE ENLARGED PLANS

FOR ICRA DETAILS

GENERAL PROJECT NOTES:

1. ALL INSIDE BUILDING WORK THAT IS IN CORRIDORS, PATIENT AREAS, AND IN

PUBLIC VIEW WILL BE DONE DURING EVENING HOURS AFTER 5:00PM (1700HRS) OR

ON WEEKENDS. ANY WORK IN AREAS #1, #4, AND #5 THAT INTERRUPTS OR

BLOCKS VEHICLES/PERSONS TRAFFIC SHALL ONLY BE DONE AFTER 5 PM OR ON

WEEKENDS. THESE AREAS CANNOT BE CLOSED DURING BUSINESS HOURS, 7 AM TO

5 PM. COORDINATE ALL WORK WITH THE COR.

2. SEE ALL NOTES ON SHEET G101, GI102, GI201, & GI202.

4" RUBBER COVE

WITH 16 GA. METAL

STUDS AT 16" O.C.

BOARD EACH SIDE.

WITH 5/8" GYPSUM

AS SCHEDULED

ACOUSTICAL CEILING

2' X 4' SUSPENDED

WALL CONST. TYPES (DETAILS)

TYPE A

BASE @ BOTH SIDES

4" RUBBER COVE

3 5/8" 16 GA. METAL

STUDS AT 16" O.C.

BOARD EACH SIDE.

WITH 5/8" GYPSUM

W A

LL

H

EI

G H T

V

ER

IE

S

TYPE B

C

EI

LI

N G

H

EI

G H T

'-0

ON FLOOR PLAN.

FI

EL

D V

ER

IF

Y

C

EI

LI

N G

H

EI

G H T

'-0

4 7/8"4 7/8"

W A

LL

H

EI

G H T

V

ER

IE

S

FI

EL

D V

ER

IF

Y

TO MATCH EXISTING AREA TO MATCH EXISTING AREA

ROOF METAL DECKING

BASE @ BOTH SIDES

AS SCHEDULED

ACOUSTICAL CEILING

2' X 4' SUSPENDED

ON FLOOR PLAN.

3 5/8" INSULATED WALL

WALL TO EXTEND TO

ROOF METAL DECKING

OFFICE AREAS CARDIOLOGY CCU ANY AREA CARING FOR

ECHOCARDIOGRAPHY

ENDOSCOPY

NUCLEAR MEDICINE

PHYSICAL THERAPY

RADIOLOGY/MRI

RESPIRATORY THERAPY

EMERGENCY ROOM

LABOR & DELIVERY

LABORATORY (SPECIMEN)

NEWBORN NURSERY

OUTPATIENT SURGERY

PEDIATRICS

IMMUNOCOMPROMISED PATIENTS

BURN UNIT

CARDIAC CATH LAB

CENTRAL STERILE SUPPLY

INTENSIVE CARE UNITS

MEDICAL UNIT

PHARMACY

POST ANESTHESIA CARE UNIT

SURGICAL UNITS

NEGATIVE PRESSURE ISOLATION ROOMS

ONCOLOGY

OPERATING ROOMS INCLUDING

C-SECTION ROOMS

INFECTION CONTROL APPROVAL WILL BE REQUIRED WHEN THE CONSTRUCTION ACTIVITY AND RISK

LEVEL INDICATE THAT CLASS III OR CLASS IV CONTROL PROCEDURES ARE NECESSARY.

ROOM ELEVATION

AREA UNDER

FRAMED

PICTURE

OF

C.O.R.

ICRA, ILSM

FIRE WATCH

MISC. FORMS

PAPER

CADDY

CONSTRUCTION

RESTRICTED AREA

THIS IS A

CONST. SUPERVISOR

NAME AND

CELL PHONE

XXXXXX XXXX XXXX

CHILLER PLANT AFTER HOURS

CONTACT PHONE 82329

FIRE EMERGENCY DIAL 911

XXXXXX XXXX XXXX

XXXXXX XXXX XXXX

WITH CONTACT

INFORMATION

TYPICAL IDEAL

CONSTRUCTION LAYOUT

CLASS III

CROSS-SECTION 'A-A'

CROSS-SECTION 'A-A'

TYPICAL ALTERNATIVE

CONSTRUCTION LAYOUT

CLASS III

CLASS III (ALTERNATE)

CLASS III

1. REMOVE OR ISOLATE H.V.A.C. SYSTEM IN AREA WHERE WORK IS BEING DONE TO

PREVENT CONTAMINATION OF DUCT SYSTEM.

2. COMPLETE ALL CRITICAL BARRIERS IE. SHEETROCK, PLYWOOD, PLASTIC, TO SEAL

AREA FROM NON-WORK AREA OR IMPLEMENT CONTROL CUBE METHOD (CART WITH

PLASTIC COVERING AND SEALED CONNECTION TO WORK SITE WITH HEPA VACUUM FOR

VACUUMING PRIOR TO EXIT) BEFORE CONSTRUCTION BEGINS.

3. MAINTAIN NEGATIVE AIR PRESSURE WITHIN WORK SITE UTILIZING HEPA EQUIPPED AIR

FILTRATION UNITS IF INDICATED.

4. CONTAIN CONSTRUCTION WASTE BEFORE TRANSPORT IN TIGHTLY COVERED CONTAINERS.

5. COVER TRANSPORT RECEPTACLES OR CARTS. TAPE COVERING UNLESS SOLID LID.

6. DO NOT REMOVE BARRIERS FROM WORK AREA UNTIL COMPLETED PROJECT IS

INSPECTED BY THE OWNER'S SAFETY DEPARTMENT AND INFECTION CONTROL

DEPARTMENT AND THOROUGHLY CLEANED BY THE OWNER'S ENVIRONMENTAL SERVICES

DEPARTMENT.

1. REMOVE BARRIER MATERIALS CAREFULLY TO MINIMIZE SPREADING OF DIRT AND DEBRIS

ASSOCIATED WITH CONSTRUCTION.

2. VACUUM WORK AREA WITH HEPA FILTERED VACUUM.

3. WET MOP AREA WITH DISINFECTANT.

4. REMOVE ISOLATION OF H.V.A.C. SYSTEM IN AREAS WHERE WORK IS BEING PERFORMED.

CONSULTANTS: ARCHITECT/ENGINEERS:

Revisions: Date:

Drawing Title

VA Health Care System Approval:

Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

Drawing # of

Veterans Health

Administration www�daengineering�com www�daengineering�com voice �31�� 4�4-�0�0 2�0� Rand Road Indianapolis, Indiana 4�241 fa[ �31�� 4�4-�3�3

Mechanical, Electrical, and Energy Engineering

DESIGN-AIRE ENGINEERING, INC.

DEH DAE

AE Site Security Updates (CIN) 539-22-208

CINCINNATI VA MEDICAL CENTER

3200 VINE STREET - CINCINNATI, OH 45220

SITE

For Official Use Only (FOUO)

BID SET

Kristina Amin Chief Engineer Cincinnati VA Medical Center

ADDENDUM 2 05/08/24

GJ-201

TYPE III ICRA CONSTRUCTION

DETAILS

Electrical Closet A0004

Electric Closet A0005

Dietetics Kitchen A0011

Autopsy A004B

M . Tlt.

A004C

HAC

A004D

F. Tlt.

A004E

Storage A004F

Gross Specim en Storage A004G

Transfer Room A004A

Viewing Room A004

Gas Stor.

A005A

Gas Stor.

A005B

Pest Control A005C

Corridor C*B*13

Stor.

A007A

Hazard Chem

Stor.

A007B

Elec.

A003

Soil Linen A002

Drug Stor.

A001A

Alc. Vault A001B

Narc. Vault A001C

Elec.

A001D

M ech.

Room A005D

Stair 2 S*B*2

Corridor C*B*2

M ech. Stor.

A013

Ref. Equip.

Rm

A013A

M ech. Rm A013B

Form s Rm

A013D

Service Lobby A010

Shred Rm

A011

Nuclear Stor.

A015

Stor.

A016

PM

&R Stor.

A018

Elec.

A019

Loading Dock A017

Distribution A014

W arehouse

Receiving&Check-in A014A

Office A014B

Canteen Stor.

A014C

M ail Rm

B022

Clerk Office B022A

Receiving & Breakout

A021

Stor.

A021A

Stor.

A022C

Office A022B

Ref. Eq.

B020

Subsistence A022

Elec.

A022A

Supply Storage

A020

Em ergency

Generator B013 Transform er Room B013B

Electric Room B013A

Elec. Shop B001

Elec. Office B001A

Elec. Shop B001B

BioM ed

Chief B001C

BioM ed

Rep. Shop B004 Biom edical Engineering

B005

Stair 4 S*B*4

Biom edical

Eng.

B005A

BioM ed

W ork Area B006

BioM ed

Stor.

B006A

Super. Fee Service B006B

Stor.

B007B

Authoriz.

Clerk B007A

Lock sm ith

B021A

Locksm ith

B021

Elec.

B001D

Lead, Voucher

C&P Clerks B007

F. Tlt.

B008

M &R Stor.

B008A

M . Tlt.

B010

Stair 3 S*B*3

Sig B008B

Tele.

B008C

Soil. Linen B016

Library B015

B016A

Engineering Office B018

Eng. Stor.

B019

Fire Alarm Control B019A

Corridor C*B*6

Eng. Stor.

A023A

Stair 1 S*B*1

Tlt.

A025

Corridor C*B*1

Freezer A0012

Freezer A0007

Freezer A0008

Freezer

M isc.

Kitchen A0023

Freezer

A0010 HAC

A0021 HAC

A0019

HAC

A0018

Tele.

Equip. Rm

A035

Dry Goods/Paper

Storage A036

Office A0001

M ale Toilet A0003

Fem ale

Toilet A0002

Assistant Office A0017

Chief Office A0017A

Office A0016

Break Room A0006

Supply W arehouse A001

Stair A017A

Tele.

A025A

Office A0013

Office A0022

Gas M eter

Room A001e

Stair 11 S*B*11

M isc.

Kitchen A0020

M echanical Room A001f

UP

UP

DN

UP

UP

DN

UP

UP

DN

UP

DN

UP

DN

UP

UP

UP

ELEC

RM A0005

TELE

RM B008B

NEW 1-4"C.

PANEL

PANEL

1-1"C.

1-1"C.

CONSULTANTS: ARCHITECT/ENGINEERS:

Revisions: Date:

Drawing Title

VA Health Care System Approval:

Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

Drawing # of

Veterans Health

Administration www.daengineering.com www.daengineering.com voice �317� 464-9090 2707 Rand Road Indianapolis, Indiana 46241 fa[ �317� 464-9393

Mechanical, Electrical, and Energy Engineering

DESIGN-AIRE ENGINEERING, INC.

DEH DAE

AE Site Security Updates (CIN) 539-22-208

CINCINNATI VA MEDICAL CENTER

3200 VINE STREET - CINCINNATI, OH 45220

SITE

For Official Use Only (FOUO)

BID SET

Kristina Amin Chief Engineer Cincinnati VA Medical Center

ADDENDUM 2 05/08/24

A1

GJ301

KEYED PLAN NOTES:

1. ELECTRICAL CONDUIT AND TECHNOLOGY CONDUITS THROUGH BUILDING.

SEE 'EP' AND 'T' SHEETS.

2. ICRA III REQUIRED FOR THIS AREA.

3. AREA IS MECHANICAL AND ELECTRICAL ROOMS. ICRA IS NOT REQUIRED.

4. ICRA III REQUIRED FOR THIS AREA.

5. THIS AREA IS EXTERIOR OF BUILDING. ICRA NOT REQUIRED.

GJ-301

ENLARGED BUILDING

AREAS FOR ICRA DETAILS

GENERAL PROJECT NOTES:

1. ALL INSIDE BUILDING WORK THAT IS IN CORRIDORS, PATIENT AREAS, AND IN

PUBLIC VIEW WILL BE DONE DURING EVENING HOURS AFTER 5:00PM (1700HRS)

OR ON WEEKENDS. ANY WORK IN AREAS #1, #4, AND #5 THAT INTERRUPTS OR

BLOCKS VEHICLES/PERSONS TRAFFIC SHALL ONLY BE DONE AFTER 5 PM OR ON

WEEKENDS. THESE AREAS CANNOT BE CLOSED DURING BUSINESS HOURS, 7 AM

TO 5 PM. COORDINATE ALL WORK WITH THE COR

W aiting

C125 Consult C125A

Elec.

C126

Pharm acy

C140B

Signal C128

Tele.

C127

Stair 5 S*1*5

Tlt.

A158ACl. Lin.

Pub. Tlt.

A147B

Em ergency A147

Secl.

A154

Secl.

A152

Triage C120

Chief Off.

A151

Soil. Util.

A157 PCM

M Coordinator

A146A

Quality M anager A146B

Squad Stor.

A146

Heart Exam 1A148

Heart Exam 2A149

Restroom A149A

Heart Exam 3A150

M . Tlt.

C124

F. Tlt.

C123

Em ployee

Health C122A

Conference Room C122

Office C121

Exam C122D

Exam C122C

Police C119

Em ployee I.D.

C119A

Corridor C*1*11

W aiting

Room

Exam Room C104

HAC

C105

PEA

C106

C100

Corridor C*1*4

Office C122B

Entry A158B

Corridor C*1*13

DN

PANEL

PANEL

1-1"C.

1-1"C.

CONSULTANTS: ARCHITECT/ENGINEERS:

Revisions: Date:

Drawing Title

VA Health Care System Approval:

Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

Drawing # of

Veterans Health

Administration www.daengineering.com www.daengineering.com voice �317� 464-9090 2707 Rand Road Indianapolis, Indiana 46241 fax �317� 464-9393

Mechanical, Electrical, and Energy Engineering

DESIGN-AIRE ENGINEERING, INC.

DEH DAE

AE Site Security Updates (CIN) 539-22-208

CINCINNATI VA MEDICAL CENTER

3200 VINE STREET - CINCINNATI, OH 45220

SITE

For Official Use Only (FOUO)

BID SET

Kristina Amin Chief Engineer Cincinnati VA Medical Center

ADDENDUM 2 05/08/24

A2

GJ302

KEYED PLAN NOTES:

1. ELECTRICAL CONDUIT AND TECHNOLOGY CONDUITS THROUGH BUILDING.

SEE 'EP' AND 'T' SHEETS.

2. ICRA III REQUIRED FOR THIS AREA.

3. AREA IS MECHANICAL AND ELECTRICAL ROOMS. ICRA IS NOT REQUIRED.

4. ICRA III REQUIRED FOR THIS AREA.

5. THIS AREA IS EXTERIOR OF BUILDING. ICRA NOT REQUIRED.

GJ-302

ENLARGED BUILDING

AREAS FOR ICRA DETAILS

1 4

1 4 4

4 1 4

GENERAL PROJECT NOTES:

1. ALL INSIDE BUILDING WORK THAT IS IN CORRIDORS, PATIENT AREAS, AND IN

PUBLIC VIEW WILL BE DONE DURING EVENING HOURS AFTER 5:00PM (1700HRS) OR

ON WEEKENDS. ANY WORK IN AREAS #1, #4, AND #5 THAT INTERRUPTS OR

BLOCKS VEHICLES/PERSONS TRAFFIC SHALL ONLY BE DONE AFTER 5 PM OR ON

WEEKENDS. THESE AREAS CANNOT BE CLOSED DURING BUSINESS HOURS, 7 AM TO

5 PM. COORDINATE ALL WORK WITH THE COR

Pest Control A005C

Gas Stor.

A005B

M. Tlt.

A004C

HAC

A004D

F. Tlt.

A004E

Storage A004F

Storage A004G

Corridor C*B*13

Stair 2 S*B*2

Mech. Stor.

A013 Forms Rm.

A013D

Shred Rm.

Elec.

A003

Transfer Room A004A

Mech.

Room A005D

Autopsy Viewing Room A004

Narc. Vault A001C

Alc. Vault A001B

Drug Stor.

A001A

Elec.

A001D

Gas Stor.

A005A

Stor.

A007A

Hazard Chem.

Stor.

A007B

Mech. Rm A013B

Ref. Equip.

Rm.

A013A

Soil Linen A002

Office A0001

Female Toilet A0002

Male Toilet A0003

Supply Warehouse

A001

Mechanical Room A001f

Gas Meter Room A001e

Electric Closet A0005

Break Room A0006

Freezer A0007

Electrical Closet A0004

Freezer

A004C

Gross Specimen Storage

A004B

OIT Cage A001O

OIT Turn-In A001T

FA

A

U P

UP

CONSULTANTS: ARCHITECT/ENGINEERS:

Revisions: Date:

Drawing Title

VA Health Care System Approval:

Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

Drawing # of

Veterans Health

Administration www.daengineering.com www.daengineering.com voice �317� 464-�0�0 2707 Rand Road Indianapolis, Indiana 46241 fa[ �317� 464-�3�3

Mechanical, Electrical, and Energy Engineering

DESIGN-AIRE ENGINEERING, INC.

DEH DAE

AE Site Security Updates (CIN) 539-22-208

CINCINNATI VA MEDICAL CENTER

3200 VINE STREET - CINCINNATI, OH 45220

SITE

For Official Use Only (FOUO)

BID SET

Kristina Amin Chief Engineer Cincinnati VA Medical Center

ADDENDUM 2 05/08/24

KEYED PLAN NOTES:

1. THIS AREA IS IN AN OPEN GARAGE. ICRA IS NOT REQUIRED.

2. ELECTRICAL CONDUIT AND TECHNOLOGY CONDUITS THROUGH BUILDING.

SEE 'EP' AND 'T' SHEETS.

3. THIS AREA IS EXTERIOR OF BUILDING. ICRA NOT REQUIRED.

4. ICRA III REQUIRED FOR THIS AREA.

A4

GJ303

A3

EJ303

GJ-303

ELECTRICAL ROOM

4 2

ENLARGED BUILDING

AREAS FOR ICRA DETAILS

GENERAL PROJECT NOTES:

1. ALL INSIDE BUILDING WORK THAT IS IN CORRIDORS, PATIENT AREAS, AND IN

PUBLIC VIEW WILL BE DONE DURING EVENING HOURS AFTER 5:00PM (1700HRS) OR

ON WEEKENDS. ANY WORK IN AREAS #1, #4, AND #5 THAT INTERRUPTS OR

BLOCKS VEHICLES/PERSONS TRAFFIC SHALL ONLY BE DONE AFTER 5 PM OR ON

WEEKENDS. THESE AREAS CANNOT BE CLOSED DURING BUSINESS HOURS, 7 AM TO

5 PM. COORDINATE ALL WORK WITH THE COR

BEDROOM

BEDROOM

BEDROOM

BEDROOM

BATHROOM

1010A

BATHROOM

1015A

LINEN

CLOSET

DEN

NURSES

SUB-STATION

1027 CLOSET

SPECIAL

CARE

BATHROOM

1008A

SPECIAL

CARE

RESIDENT

ROOM

DINING

ROOM

LEISURE

Omnicells

NURSES'

STATION

1029A

VSO

CORRIDOR

SHARED

DIET./SUPRV

SOCIAL

WORKER

MDS RN

SUPPLY

CORRIDOR

C*1*1

ADMIN

S. MEN

WORK

ROOM

CORRIDOR

C*1*8

S. WOMEN

CORRIDOR

C*1*7

MD/NP

SHARED

OFFICE

RN MGR

RESTOR.

RN

SUPPORT

SHARED

MEDICAL

DIRECTOR

SOILED

UTILITY

LAUNDRY

1004 CLEAN

UTILITY

BATHING

SUITE

STORAGE

NURSING

HOME

ADMIN.

WAITING

VESTIBULE

STAIR 1

S*1*1 DN

V. WOMEN

V. MEN

RECEPTION

KITCHEN &

PANTRY

CORRIDOR

C*1*4

WORK

ROOM

1029B

LOBBY

LOUNGE

CHARTING

1029C

TECH

CLOSET

Chapel

BARBER

SHOP

ACTIVITIES

GROUP

ROOM

CLOSET

1025A

LIVING

ROOM

WHEELCHAIR

STORAGE

LAUNDRY

OXYGEN

STORAGE

STAFF

MEN'S

STAFF

WOMEN'S

BATHROOM

1009A

CORRIDOR

C*1*3

BEDROOM

BATHROOM

1123A

BEDROOM

BATHROOM

1014A

ELECTRIC

CLOSET

BATHROOM

1013A

BATHROOM

1012A

CLOSET

BATHROOM

1011A

BEDROOM

BEDROOM

BEDROOM

1122 BATHROOM

1122A

HAC

BATHROOM

1121A

BEDROOM

BATHROOM

1120A

LINEN

CLOSET

BEDROOM

BATHROOM

1119A

CONSULTANTS: ARCHITECT/ENGINEERS:

Revisions: Date:

Drawing Title

VA Health Care System Approval:

Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

Drawing # of

Veterans Health

Administration www.daengineering.com www.daengineering.com voice �317� 464-9090 2707 Rand Road Indianapolis, Indiana 46241 fa[ �317� 464-9393

Mechanical, Electrical, and Energy Engineering

DESIGN-AIRE ENGINEERING, INC.

DEH DAE

AE Site Security Updates (CIN) 539-22-208

CINCINNATI VA MEDICAL CENTER

3200 VINE STREET - CINCINNATI, OH 45220

SITE

For Official Use Only (FOUO)

BID SET

Kristina Amin Chief Engineer Cincinnati VA Medical Center

ADDENDUM 2 05/08/24

A5

GJ304

KEYED PLAN NOTES:

1. ELECTRICAL CONDUIT AND TECHNOLOGY CONDUITS THROUGH BUILDING.

SEE 'EP' AND 'T' SHEETS.

2. AREA IS MECHANICAL AND ELECTRICAL ROOMS. ICRA IS NOT REQUIRED.

3. ICRA III REQUIRED FOR THIS AREA.

GJ-304

ENLARGED BUILDING

AREAS FOR ICRA DETAILS

GENERAL PROJECT NOTES:

1. ALL INSIDE BUILDING WORK THAT IS IN CORRIDORS, PATIENT AREAS, AND IN

PUBLIC VIEW WILL BE DONE DURING EVENING HOURS AFTER 5:00PM (1700HRS) OR

ON WEEKENDS. ANY WORK IN AREAS #1, #4, AND #5 THAT INTERRUPTS OR

BLOCKS VEHICLES/PERSONS TRAFFIC SHALL ONLY BE DONE AFTER 5 PM OR ON

WEEKENDS. THESE AREAS CANNOT BE CLOSED DURING BUSINESS HOURS, 7 AM TO

5 PM. COORDINATE ALL WORK WITH THE COR

Electrical

Conference Room

Break Room 1A

Corridor C*B*2

Elev. Equip.

Vestibule

Lobby 010A

Pipe Basem ent

1B

Off.2A

Office2

HR Off 3A

HR Off.

HR Off.

HR Off.

Stairs S*B*2

HR Off.

HR Off.

Corridor C*B*1

Lobby

Bathroom 10B

HR Office

Clos.

10D

H.A.C.

Stairs S*B*1

DN

UP

UP

UP

UP

UP

UP

UP

UP

Chief

Asst. Chief 100A

Conference

Secretary

Corridor C*1*2

Storage

Lobby

Copy Room

P.M . Spec.

P.M . Spec

Office

Corridor C*1*3

Office

Pers. Asst.

P.M . Spec.

P.M . Spec.

108A

Office

Office

W ork Room

Stor.

111A

Stor.

112A

Payroll 112Corridor

C*1*1

Bathroom

Bathroom

Stairs S*1*1

Stairs S*1*2

Stor.

105A

Entry 120A

UP

UP

UP

UP

UP

UP

1-1 1/2"C. UP

1-1/2"C.

TR

2" SLEEVE

CONSULTANTS: ARCHITECT/ENGINEERS:

Revisions: Date:

Drawing Title

VA Health Care System Approval:

Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

Drawing # of

Veterans Health

Administration www.daengineering.com www.daengineering.com voice �317� 464-9090 2707 Rand Road Indianapolis, Indiana 46241 fa[ �317� 464-9393

Mechanical, Electrical, and Energy Engineering

DESIGN-AIRE ENGINEERING, INC.

DEH DAE

AE Site Security Updates (CIN) 539-22-208

CINCINNATI VA MEDICAL CENTER

3200 VINE STREET - CINCINNATI, OH 45220

SITE

For Official Use Only (FOUO)

BID SET

Kristina Amin Chief Engineer Cincinnati VA Medical Center

ADDENDUM 2 05/08/24

A6

GJ305

KEYED PLAN NOTES:

1. ELECTRICAL CONDUIT AND TECHNOLOGY CONDUITS THROUGH BUILDING.

SEE 'EP' AND 'T' SHEETS.

2. ICRA III REQUIRED FOR THIS AREA.

GJ-305

ENLARGED BUILDING

AREAS FOR ICRA DETAILS

A7

GJ305

GENERAL PROJECT NOTES:

1. ALL INSIDE BUILDING WORK THAT IS IN CORRIDORS, PATIENT AREAS, AND IN

PUBLIC VIEW WILL BE DONE DURING EVENING HOURS AFTER 5:00PM (1700HRS) OR

ON WEEKENDS. ANY WORK IN AREAS #1, #4, AND #5 THAT INTERRUPTS OR

BLOCKS VEHICLES/PERSONS TRAFFIC SHALL ONLY BE DONE AFTER 5 PM OR ON

WEEKENDS. THESE AREAS CANNOT BE CLOSED DURING BUSINESS HOURS, 7 AM TO

5 PM. COORDINATE ALL WORK WITH THE COR

UPPER LEVEL OF CATWALK

UP

DN

DN UPUP UP

FOYER

PLATFORM

LIFT

STOR.

UPPER LEVEL OF

UPPER LEVEL OF

ROOF

ROOF

KITCHEN

OFFICE

OFFICE

TOILET

#3

BOILER

#2

BOILER

#1

BOILER

INCINERATOR ROOM

SHELTER

BOILER ROOM

PUMP

HYDRAULICEXCHANGER

HEAT

PUMP

GLYCOL

EXCHANGER

HEAT

DN UP

UP

UP

TR

1-2 1/2" SLEEVE

1-2"C.

13A

FOYER

ELECT. RM.

ROOM

INCINERATOR

INCIN.

#3

BOILER

#2

BOILER

#1

BOILER

STORAGE

LOCKER ROOM

LAB

EMG. GEN. ROOM FOYER

CONTROL ROOM

BOILER ROOM

PUMP ROOM

UPPER LEVEL OFENCLOSURE

GAS BOOSTER

CONTROL PANEL

MAIN PLANT

WALK

SIDE-

SIDEWALK

DRIVE

CHIMNEY

PANEL

CONTROL

PANEL

CONTROL

PANEL

CONTROL

TANK

GEN DAY

PADS

COOLER

GAS

TURBINE

#2

GAS

VACUUM

PAD

CONCRETE

TANKS

FEED

CHEM.

COMP.

JOY AIR

SOFTENERS

ZEOLITE WATER

PAD

CONC.

ABSORBER

YORK

200 TON

DN UP

DN

UP

UP

DN

CARPENTRY

SHOP

1-2"C. UP

1-2"C.

UP

UP

UP

Locker Room

Storage 113C

Carpentry Shop

Chiller Plant

Mechanic Shop 113A

CONSULTANTS: ARCHITECT/ENGINEERS:

Revisions: Date:

Drawing Title

VA Health Care System Approval:

Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

Drawing # of

Veterans Health

Administration www.daengineering.com www.daengineering.com voice �317� 464-9090 2707 Rand Road Indianapolis, Indiana 46241 fa[ �317� 464-9393

Mechanical, Electrical, and Energy Engineering

DESIGN-AIRE ENGINEERING, INC.

DEH DAE

AE Site Security Updates (CIN) 539-22-208

CINCINNATI VA MEDICAL CENTER

3200 VINE STREET - CINCINNATI, OH 45220

SITE

For Official Use Only (FOUO)

BID SET

Kristina Amin Chief Engineer Cincinnati VA Medical Center

ADDENDUM 2 05/08/24

A10

GJ306

A8

GJ306

KEYED PLAN NOTES:

1. ELECTRICAL CONDUIT AND TECHNOLOGY CONDUITS THROUGH BUILDING.

SEE 'EP' AND 'T' SHEETS.

2. AREA IS MECHANICAL AND ELECTRICAL ROOMS. ICRA IS NOT REQUIRED.

3. ICRA III REQUIRED FOR THIS AREA.

4. AREA EXTERIOR OF BUILDING. ICRA NOT REQUIRED.

GJ-306

ENLARGED BUILDING

AREAS FOR ICRA DETAILS

1 1

A9

GJ306

1 2

4 4

GENERAL PROJECT NOTES:

1. ALL INSIDE BUILDING WORK THAT IS IN CORRIDORS, PATIENT AREAS, AND IN

PUBLIC VIEW WILL BE DONE DURING EVENING HOURS AFTER 5:00PM (1700HRS) OR

ON WEEKENDS. ANY WORK IN AREAS #1, #4, AND #5 THAT INTERRUPTS OR

BLOCKS VEHICLES/PERSONS TRAFFIC SHALL ONLY BE DONE AFTER 5 PM OR ON

WEEKENDS. THESE AREAS CANNOT BE CLOSED DURING BUSINESS HOURS, 7 AM TO

5 PM. COORDINATE ALL WORK WITH THE COR

772872

8 719

731 732 733

X

X

G G G G G

G G G G

G G

G

W W W W W W W W W W W

W W W

W W W W W

W

W W

W W

W W

W W

W W

W W

W W

W W

W W

W W

W W

W W

W

W

W W

W

WWWWWWWWW

W W

WWWWWW

W

W

W

W

W

W

W

W

W W

W W

W W

W W

W W

W W

W

W

W W

W W

W

W W

W W

W W

W W

UE

UE

UE

UE

UE

UE

UE

UE

W W

W

W

U E

U E

U E

U E

U E

U E

U E

U E

UE

U

E U

E U

E U

E

UE

UE

UE UE

UE

UE

UE

UE UE UE U

E

U E

U E

U E

U E

U E

U E

U E

UE UE UE UE

UE

UE

UE

UE

U E

U E

U E

U E

U E

U E

U E

U E

U E

U E

U E

U E

U E

U E

U E

U E

U E

U E

U E

U E

U E

U E

U E

U E

U E

U E

U E

UE

UE

UE

UE

UE

UE

U E

U E

U E

U E

U E

U E

U E

U E

U E

U E

UEUE

UE

W

U E

U E

U E

U E

UE

UE UE UE UE

UE

UE

UE

U E

U E

U E

UT UT

UT

UT

UT UT UT

U T

U T

U T

U T

UT

U

T U

T U

T U

T

U T

U T

UT

UT

UT

UT UT UT UT

UT

UT

UT

UT

UT

UT

UT

UT UT UT

U T

U T

U T

U T

U T

UT

UT

U T

U T

U T

UT

UT

UT

UT

UT

UT

UT

UT

UT

UT

UT

UT

UT

UT

UT

U T

U T

U T

U T

U T

U T

U T

U T

U T

U T

U T

U T

U T

U E

U E

U E

U E

U E

U E

UE

UE

U

E U

E U

E U

E U

E U

E U

E U

E

UE

UE UE

UE

UE

UE

UEUE

UE

U E

U E

UE

UEUEUE

UE UE UE UE UE UE UE UE UE UE

UEUE

UEU

E U

E U

E

UE

U E

U E

U E

UE

UEUEUE

UE

UEUEUEUEUEUEUEU

E

U E

U E

X

W W W W

W W

W

UE UE UE

A

B

C

D

E

F

G

H

IJ

CODED NOTES

PROVIDE SLIDING GATE WITH GROUND LOOP.

GROUND LOOP LOCATION TO BE COORDINATED

WITH ELECTRICAL PLAN AND PER

MANUFACTURER'S RECOMMENDATION. BASIS OF

DESIGN TYMETAL TYM-ST4000DC SLIDE GATE.

PROVIDE PEDESTRIAN GATE. REMOVE EXISTING

GRAVEL AND CONCRETE. REPAIR CURB. ADD

CONCRETE WALK AS NECESSARY TO CREATE

LANDING.

PROVIDE PIV CARD READER ON CONCRETE

ISLAND. COORDINATE LOCATION WITH

ELECTRICAL PLAN.

PROVIDE ENTRY AND EXIT GATES TO REPLACE

EXISTING. ENTRY TO BE ACCESSED WITH PIV

READER AND EXIT GATE TO BE ACCESSED WITH

GROUND LOOPS. LOCATION OF GROUND LOOPS

TO BE COORDINATED WITH ELECTRICAL PLANS

AND MANUFACTURER RECOMMENDATIONS.

REMOVE EXISTING GATES AND CONTROLS

COMPLETELY.

EXTEND FENCE BOTTOM TO EXISTING GRADE

WHERE GAP IS GREATER THAN 4". SEE DETAIL.

REMOVE EXISTING BOLLARDS. REPLACE WITH

ALTERNATING BOLLARDS AND PLANTERS

ACCORDING TO DETAILS. 4' SPACING EDGE OF

BOLLARD TO EDGE OF PLANTER.

EXTEND FENCE CORNER TO BE IN BETWEEN

EXISTING LIGHT POLE AND EXISTING TURN

SIGNAL. SEE DETAIL.

REPLACE BROKEN FENCE SECTION. CONTRACTOR

TO MATCH EXISTING FENCE STYLE AND COLOR.

PROVIDE BOLLARDS SPACED 4' FROM EDGE TO

EDGE. NON-CRASH RATED BOLLARD. INTENDED

FOR BUMPER POST ONLY.

SAWCUT EXISTING ASPHALT/CONCRETE.

COORDINATE LIMITS WITH INSTALLATION OF GATE

AND GROUND LOOP PER MANUFACTURES

DETAILS. CONTRACTOR TO REPAIR ASPHALT AS

NECESSARY.

EXISTING CONTROLLER TO BE MODIFIED TO

ACCEPT SIGNAL FROM SEPARATE SOURCE. SEE

ELECTRICAL PLANS

HEAVY DUTY MANUAL CANTILEVER SLIDE GATE

PROVIDE PIV READER ON WALK UP BOLLARD FOR

PEDESTRIAN ACCESS.

PROVIDE VIDEO INTERCOM WITH REMOTE

ACCESS. COORDINATE LOCATION WITH

ELECTRICAL PLAN.

PROVIDE A 21'-0" MANUAL LOCKABLE SWING GATE

TO MATCH EXISTING ON SITE MANUAL SWING

GATES. CONTRACTOR TO SUBMIT SHOP

DRAWINGS FOR OWNER APPROVAL.

SAWCUT OF CONCRETE/ASPHALT TO BE

COORDINATED WITH BOLLARD INSTALLATION

NEEDS. CONTRACTOR TO REPAIR ASPHALT AND

STRIPING AS NECESSARY.

PROVIDE 6" REMOVABLE BOLLARDS SPACED 4'

FROM EDGE TO EDGE. SEE DETAIL.

PROVIDE FIXED BOLLARD. SEE DETAIL.

(NOTE NOT USED)

SAWCUT OF SIDEWALK TO BE COORDINATED WITH

EXISTING FIRE HYDRANT.

6" CONCRETE PAD FOR GATE OPERATOR

PROVIDE PIN CARD READER ON PEDESTAL.

COORDINATE LOCATION WITH ELECTRICAL PLAN.

PROVIDE YELLOW PAINTED STRIPE ON SIDEWALK

AT 80" WEST OF GATE. PROVIDE SIGN MOUNTED

ON A 2X2 ALUMINUM POST. SIGN TO READ, "

STAND BEHIND YELLOW LINE WHEN OPENING

GATE."

CONSULTANTS: ARCHITECT/ENGINEERS:

Revisions: Date:

Drawing Title

VA Health Care System Approval:

Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

Drawing # of

Veterans Health

Administration www.daengineering.com www.daengineering.com voice (317) 464-9090 2707 Rand Road Indianapolis, Indiana 46241 fax (317) 464-9393

Mechanical, Electrical, and Energy Engineering

DESIGN-AIRE ENGINEERING, INC.

DEH BZ

AE Site Security Updates (CIN) 539-22-208

CINCINNATI VA MEDICAL CENTER

3200 VINE STREET - CINCINNATI, OH 45220

SITE

For Official Use Only (FOUO)

BID SET

Kristina Amin Chief Engineer Cincinnati VA Medical CenterADDENDUM 2 05/08/2024

H :\E ng in ee rin g2

9-

\P

\1

7\

7\

_D W

G

M is c\

S ite

S ec ur ity

P re lim in ar y.

dw g, /8

/2

9:

A

M , A nd re w B er nh ar d

0 6015 30

AE Site North

CS-101N

NOTES

1. UTILITY LOCATIONS SHOWN ARE APPROXIMATE LOCATIONS PER RECORD

2. PRIOR TO CONSTRUCTION, CONTRACTOR TO VERIFY DEPTH AND LOCATION

OF UTILITIES IN IMMEDIATE AREA.

3. CONTRACTOR TO SPECIFY MEANS AND METHODS OF EXCAVATION FOR

CONSTRUCTION. I.E HAND DIGGING OR DIRECTIONAL BORING.

4. CONTRACTOR IS RESPONSIBLE FOR ALL TRAFFIC CONTROL DURING

CONSTRUCTION.

CODED NOTES

BOLLARD

SIGN

FENCE POST

GATE STOP

LIGHT POLE BASE

SIDE WALK

CURB

FENCE

NEW PEDESTRIAN GATE AT THIS SECTION OF

FENCE

FILL IN OPEN SPACE WITH FENCE

A

B

C

D

E

F

G

H

I

J

0 205 10

15 40 10-21-2025

772872

731 732 733 734

X

X

G G G G G G G G

G G

G G

G G

G G G G G

G G G G G

G G

G G

G G

G G

G G

G

G G G G G G G G G G G G G

G G

G G

G G

G G

G G

G

W W

W

W W

WWWWWWWWW

W W

WWWWW

W W

W W

W W

W

W

W

WWWW

W W

W W

W W

W W

W W

W W

W W W

W W

W

W W W W W W W

WWWWWWWWWWWWWW

W

W

WW

WW

W

W W

W

U E

U E

U E

U E

U E

U E

U E

U E

UE UE

U E

U E

U E

U E

U E

UE

UE

U E

U E

U E

U E

U E

U E

UE

UE

UE UE

UE

UE

UE

UE UE UE U

E

U E

U E

UE

U E

U E

U E

U E

U E

UE UE UE UE

UE

UE

UE

UE

UE

U E

UE

UE

UE

UE

UE

UE

UE

U E

U E

U E

U E

UE

UE

UE

UEU

E

U E

U E

U E

U E

U E

U E

U E

U E

U E

U E

U E

U E

U E

U E

U E

U E

U E

UE

UEU

E U

E U

E U

E U

E U

E U

E U

E

UE

UE

UE

UE

UE

UE UE

U E

U E

U E

U E

U E

U E

U E

U E

U E

U E

U E

U E

U E

U E

U E

U E

U E

U E

U E

U E

U E

U E

U E

U E

UE

UE

UE

U E

U E

U E

U E

U E

UEUEUEUEUE

UE

UE UE UE UE

UE

UE

UE

U E

U E

U E

U E

U E

U E

U E

U E

U E

U E

UE UE UE

UE

UE

U T

UT

UT

UT

UT UT UT UT

UT

UT

UT

UT

UT

UT

UT

UT UT UT

U T

U T

U T

U T

U T

U T

UT

UT

UT

U T

U T

U T

U T

UT

UT

UT

UT

UT

UT

UTUT

UTUT

U T

UT

UT

UT

UT

UT

UE UE UE U

E

U E

U E

U E

UT

UT

U T

U T

U E

U E

U E

U E

U E

U E

U E

U E

U E

U E

U E

U E

X

X

X

UE

U E

U E

U E

U E

U E

U E

A

B

C

D

E

F

CODED NOTES

(NOTE NOT USED)

REMOVE EXISTING DOUBLE GATE AND POSTS

COMPLETELY. PROVIDE DOUBLE HEAVY DUTY

SWING GATES, MOTORIZED, FOR 30 FOOT

OPENING. 6" Ø HINGE POSTS. SEE ELECTRICAL

PLANS AND DETAIL.

(NOTE NOT USED)

LARGE BOULDERS TO PROTECT CORNER OF

BUILDING TO BE NO MORE THAN 5' APART WITH

MINIMUM SIZE OF 3' X 4' X 4'. SEE DETAIL.

(NOTE NOT USED)

EXTEND FENCE CORNER TO BE IN BETWEEN

EXISTING LIGHT POLE AND EXISTING TURN

SIGNAL. SEE DETAIL FOR FENCE.

EXTEND EXISTING MULCH BED TO INCORPORATE

PROPOSED BOULDERS. VERIFY WITH COR.

REPLACE EXISTING GATE WITH 8' TALL

SELF-CLOSING GATE INCLUDING PIV READER AND

ELECTRONIC LOCK PER ELECTRICAL PLANS. SEE

DETAIL.

(NOTE NOT USED)

(NOTE NOTE USED)

RELOCATE SIDEWALK TO THE WEST 16". REWORK

MULCH BED AND PLANTINGS AS REQUIRED.

CONSULTANTS: ARCHITECT/ENGINEERS:

Revisions: Date:

Drawing Title

VA Health Care System Approval:

Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

Drawing # of

Veterans Health

Administration www.daengineering.com www.daengineering.com voice (317) 464-9090 2707 Rand Road Indianapolis, Indiana 46241 fax (317) 464-9393

Mechanical, Electrical, and Energy Engineering

DESIGN-AIRE ENGINEERING, INC.

05-08-2024 DEH BZ

AE Site Security Updates (CIN) 539-22-208

CINCINNATI VA MEDICAL CENTER

3200 VINE STREET - CINCINNATI, OH 45220

SITE

For Official Use Only (FOUO)

BID SET

Kristina Amin Chief Engineer Cincinnati VA Medical CenterADDENDUM 2 05/08/2024

H :\E ng in ee rin g2

9-

\P

\1

7\

7\

_D W

G

M is c\

S ite

S ec ur ity

P re lim in ar y.

dw g, /8

/2

9:

A

M , A nd re w B er nh ar d

0 6015 30

AE Site South

CS-101S

NOTES

1. UTILITY LOCATIONS SHOWN ARE APPROXIMATE

LOCATIONS PER RECORD

2. PRIOR TO CONSTRUCTION CONTRACTOR TO VERIFY

DEPTH AND LOCATION OF UTILITIES IN IMMEDIATE AREA.

3. CONTRACTOR TO SPECIFY MEANS AND METHODS OF

EXCAVATION FOR CONSTRUCTION. I.E HAND DIGGING OR

DIRECTIONAL BORING.

4. CONTRACTOR IS RESPONSIBLE FOR ALL TRAFFIC

CONTROL DURING CONSTRUCTION.

5. CONTRACTOR IS RESPONSIBLE FOR NEW INSTALLATIONS

TO BE MINIMUM 1' FROM ANY UTILITY.

CODED NOTES

PROPOSED GATE POST ADJACENT TO EXISTING

CURB.

PROVIDE 38" MINIMUM CLEARANCE FOR GATE ARM

FROM BACK OF CURB.

PEDESTRIAN GATE.

RELOCATE SIDEWALK AND PLANTINGS AS

NECESSARY.

GATE OPERATOR

FENCE. MATCH EXISTING STYLE AND COLOR

A

B

C

D

E

F

0 205 10

16 40

Drawing Title

VA Health Care System Approval:

Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

Drawing # of

Veterans Health

Administration www.daengineering.com www.daengineering.com voice (317) 464-9090 2707 Rand Road Indianapolis, Indiana 46241 fax (317) 464-9393

Mechanical, Electrical, and Energy Engineering

DESIGN-AIRE ENGINEERING, INC.

05-08-2024 DEH BZ

AE Site Security Updates (CIN) 539-22-208

CINCINNATI VA MEDICAL CENTER

3200 VINE STREET - CINCINNATI, OH 45220

SITE

For Official Use Only (FOUO)

BID SET

Kristina Amin Chief Engineer Cincinnati VA Medical CenterADDENDUM 2 05/08/2024

GENERAL DETAILS

EXISTING FENCE

EXISTING GRADE

4" M

IN

OPENING 4"

OR GREATER

FILL GAP WITH SHEET METAL

BOLTED/SECURED TO EXISTING

FENCE. MATCH EXISTING COLOR.

EXISTING FENCE DETAIL

N.T.S.

102 6

CS-102

EXTERIOR CONCRETE

SLAB WALK DETAIL

N.T.S.

NOTES:

1. INSTALL EXPANSION JOINTS AT 30' OC MAXIMUM AND WHERE SLAB ABUTS

STRUCTURES. WHERE NEW WALK ABUTS ADJOINING WALK, SAWCUT EXISTING

WALK TO NEAREST JOINT AND INSTALL EXPANSION JOINT. EXPANSION JOINTS

SHALL BE 1/2" WIDE BY DEPTH OF SLAB. SEAL ALL EXPANSION JOINTS.

2. INSTALL CONTROL JOINTS AT 6' OC MAXIMUM. CONTROL JOINTS SHALL BE 3/8"

WIDE BY 1 1/2" DEEP AND TOOLED, SAWED JOINTS ARE NOT PERMITTED.

3. WALK SHALL HAVE A MINIMUM CROSS SLOPE OF 1.00%, MAXIMUM CROSS

SLOPE OF 2.00%.

4. WATER AND UTILITY BOXES IN THE WALK AREA SHALL BE ADJUSTED FLUSH

WITH THE FINAL SURFACE.

5. REFER TO ARCHITECTURAL PLANS FOR ADDITIONAL DETAIL AT ALL BUILDING

DOORS.

6. JOINTING PLANS MUST BE SUBMITTED FOR APPROVAL.

1/

2"

3/8"

CONTROL JOINT

1/2"

EXPANSION JOINT

2" TYP

EXPANSION JOINT

MATERIAL

JOINT SEALANT

WWR WWR

1/2"

WALK EDGE

AT BUILDING LINE

2"

EXPANSION JOINT

MATERIAL

JOINT SEALANT

WWR

BUILDING

LINE

1/2" R

7"

6"

WWR 2"

WALK EDGE

AT LAWN AREA

2"

5" ODOT

ITEM 304

5"

6x6 W1.4xW1.4

WWR

SLOPE

2"

WALK TYPICAL SECTION

PIPE BOLLARD DETAIL

N.T.S.

18" DIA.

CONC. BASE

FINISH GRADE

SEAL JOINT - TOTAL PERIMETER

SLOPE AWAY FOR PROPER DRAINAGE

6" DIA. GALV. STEEL PIPE -

FILL WITH CONCRETE -

CONC. TO BE 4000PSI WITH 4-5%

AIR ENTRAINMENT - PAINT SAFETY YELLOW

ROUND OFF CONC. TOP

TO SMOOTH FINISH

CONTRACTOR TO SUBMIT SHOP DRAWINGS

FOR OWNER'S APPROVAL

NOTES

1. MANUFACTURERS AND MODEL NUMBERS SHOWN ARE BASIS OF DESIGN.

CONCRETE FOOTING FOR POSTS

N.T.S.

18" DIA. MIN.

CONC. BASE

FINISH GRADE

PROPOSED POST VARIES. SEE PLAN

6" BEYOND POST

MIN. CONC. BASE

17 40

HYSECURITY

6705 S. 209 ST. SUITE 101

KENT, WA 98032-2327

TOLL FREE: 1-800-321-9947

PHONE: (253) 867-3700

FAX: (253) 867-3702

www.hysecurity.com

NOTES:

1. INSTALLATION TO BE COMPLETED IN ACCORDANCE WITH MANUFACTURER'S SPECIFICATIONS.

2. DO NOT SCALE DRAWING.

3. THIS DRAWING IS INTENDED FOR USE BY ARCHITECTS, ENGINEERS, CONTRACTORS, CONSULTANTS AND DESIGN PROFESSIONALS

FOR PLANNING PURPOSES ONLY. THIS DRAWING MAY NOT BE USED FOR CONSTRUCTION.

4. ALL INFORMATION CONTAINED HEREIN WAS CURRENT AT THE TIME OF DEVELOPMENT BUT MUST BE REVIEWED AND APPROVED BY

THE PRODUCT MANUFACTURER TO BE CONSIDERED ACCURATE.

5. CONTRACTOR'S NOTE: FOR PRODUCT AND COMPANY INFORMATION VISIT www.CADdetails.com/info AND ENTER

REFERENCE NUMBER 100277CGEN007

PROTECTED BY COPYRIGHT ©2024 CADDETAILS.COM LTD. CADdetails.com

08/05/2024100277CGEN007

PROTECTED BY COPYRIGHT ©2024 CADDETAILS.COM LTD.

REVISION DATE

BARRIER ARM OPERATOR, PARKING AND TRAFFIC CONTROL - STRONGARMPARK DC

TRAFFIC CONTROL / PARKING

SELECT DESIRED MODEL:

STRONGARMPARK DC 10

STRONGARMPARK DCS 10*

STRONGARMPARK DC 14

PERSPECTIVE

STRONGARMPARK DCS 14*

STRONGARMPARK

DC 10

STRONGARM™ MODELS

STRONGARMPARK

DCS 10

STRONGARMPARK

DC 14

STRONGARMPARK

DCS 14

MODEL

ARM LENGTH MAX.

OPEN/CLOSE TIME

DUTY CYCLE

HANDLING

DRIVE

FULL OPEN ANGLE

TEMP. RATING

FINISH

WARRANTY

SELECT DESIRED ACCESORY:

HY8RELAY

HY5B VEHICLE DETECTOR

HYNET COMMUNICATING GATE SYSTEM

PHOTO EYE

CONTINUOUS

ELECTROMECHANICAL

ADJUSTABLE 90° +/- 10°

-13°F TO 158°F (-25°C TO 70°C) NO HEATER

ZINC PLATED WITH POWDER COATING

2 YEARS

UP TO 10 FT (3 M)

3 SPEEDS: 1.5/2/2.5 SECONDS

LEFT HANDLING STANDARD. EASY TO

CONVERT RIGHT HANDING IN FIELD

10, 12, 14 FT (3, 3.7, 4.3 M)

3 SPEEDS: 2.5/3/3.5 SECONDS

LEFT HANDLING STANDARD.

RIGHT HANDING AVAILABLE

*DCS MODELS ARE SOLAR

DETAIL VIEW

STRAIGHT ARM

DETAIL VIEW

ARTICULATING ARM

STRAIGHT ARMS UP TO 14 FT (4.3 M)

ARTICULATING ARMS WITH 7, 8, OR 9 FT

VEHICLE CLEARANCE

HIGH VISIBILITY LED LIGHTING

ACROSS TOP OF ARM

RESILIENT BUMPER

ALONG BASE

CONSULTANTS: ARCHITECT/ENGINEERS:

Revisions: Date:

Drawing Title

VA Health Care System Approval:

Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

Drawing # of

Veterans Health

Administration www.daengineering.com www.daengineering.com voice (317) 464-9090 2707 Rand Road Indianapolis, Indiana 46241 fax (317) 464-9393

Mechanical, Electrical, and Energy Engineering

DESIGN-AIRE ENGINEERING, INC.

05-08-2024 DEH BZ

AE Site Security Updates (CIN) 539-22-208

CINCINNATI VA MEDICAL CENTER

3200 VINE STREET - CINCINNATI, OH 45220

SITE

For Official Use Only (FOUO)

BID SET

Kristina Amin Chief Engineer Cincinnati VA Medical CenterADDENDUM 2 05/08/2024

GENERAL DETAILS

CS-103

UTILITY CONDUIT

OPEN CUT DETAIL

N.T.S.

NOTES:

1. REFER TO OSHA REQUIREMENTS FOR MAXIMUM ALLOWABLE TRENCH

SLOPES.

2. THIS PORTION OF THE PIPE EMBEDMENT ZONE MUST BE RECOMPACTED TO

PROPER DENSITIES AFTER MOVING SUPPORT SYSTEM FORWARD.

3. PROVIDE FILTER FABRIC WHEN VERY FINE OR UNSTABLE MATERIAL IS

ENCOUNTERED.

4. APPLY ITEM 407 TACK COAT TO VERTICAL FACE OF SAWCUT PAVEMENT.

EXCAVATION & BACKFILL UNDER

INFLUENCE OF PAVEMENT

EXCAVATION & BACKFILL OUTSIDE

INFLUENCE OF PAVEMENT

18"18"

PAVEMENT REPLACEMENT

MATCH EXISTING SECTION MINIMUM 1.5" ITEM 441,

ASPHALT SURFACE COURSE, TYPE 1 OVER 2.5" ITEM 441,

ASPHALT INTERMEDIATE COURSE, TYPE 2

SAWCUTEX. PAVEMENT

ITEM 304, COMPACTED

GRANULAR MATERIAL

ITEM 613, LOW STRENGTH

MORTAR BACKFILL

INITIAL BACKFILL

SHAPE BELL HOLE

CONFORM AT PIPE O.D. IF UNSUITABLE MATERIAL OR ROCK

IS FOUND, OVER EXCAVATE 4" MIN.

AND PROVIDE GRANULAR BEDDING

FOR DEPTH OF COVER < 10'

PROVIDE A FLAT BOTTOM TRENCH.

FOR DEPTH OF COVER > 10'

PROVIDE 6" BEDDING NO. 57 STONE

ITEM 613, LOW

STRENGTH MORTAR

BACKFILL

NATIVE OR EXCAVATED

MATERIAL COMPACTED

TO MIN. 98% DRY DENSITY

6" TOPSOIL (OPEN AREAS)

EX. GRADE

M

AX

IM

U

M

" L

IF

TS

SE

E

N O

TE

2PIP

E I.D

CL

TRENCH WIDTH =

PIPE I.D. + 24"

GATE HANGER ASSEMBLY

BOTTOM GUIDE8

ELEVATION

PLAN VIEW

HEAVY DUTY CANTILEVER SLIDE GATE

ENLARGED SECTION

DESCRIPTION

CRITICAL DIMENSION CHART

CLEAR OPENING

HEIGHT TO TOP OF PICKET

PICKET HEIGHT

COUNTERBALANCE LENGTH

OVERALL GATE LENGTH

POST HEIGHT

F

SECTION

G

MARK

C

E D

A B

-F -G

DIM.

FORMULA

(A/2)-11" A x 1.5

E = F A x 0.5

A

COUNTERBALANCE POST SPACING C/C

CATCH ASSEMBLY

NOTES

1. MANUFACTURERS AND MODEL NUMBERS SHOWN ARE BASIS OF DESIGN.

NOTE: MATCH ADJACENT FENCE COLOR AND STYLE.

NOTE: MATCH EXISTING PICKET SIZE.

18 40

Drawing Title

VA Health Care System Approval:

Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

Drawing # of

Veterans Health

Administration www�daengineering�com www�daengineering�com voice (31�) 4�4-�0�0 2�0� Rand Road Indianapolis, Indiana 4�241 fa[ (31�) 4�4-�3�3

Mechanical, Electrical, and Energy Engineering

DESIGN-AIRE ENGINEERING, INC.

DEH DAE

AE Site Security Updates (CIN) 539-22-208

CINCINNATI VA MEDICAL CENTER

3200 VINE STREET - CINCINNATI, OH 45220

SITE

For Official Use Only (FOUO)

BID SET

Kristina Amin Chief Engineer Cincinnati VA Medical Center

ADDENDUM 2 05/08/24

EP-001

LP2-5

BPA-15

LABEL CKT. NO. OF EACH DEVICE ON REAR

SIDE OF COVER PLATE. USE PERMANENT

MARKER PEN, BRADY MARKING SYSTEM OR

OTHER METHOD APPROVED BY THE ENGINEER

JUNCTION BOXES (EXPOSED OR

CONCEALED ABOVE ACCESSIBLE

CEILING)

LABEL COVERS WITH CKT.'S

CONTAINED WITHIN. USE PERMANENT

MARKER PEN OR OTHER APPROVED

METHOD.

FOR J.B.'S CONTAINING OTHER

THAN POWER OR LIGHTING CKT.'S

LABEL COVERS INDICATING

SYSTEM TYPE AND ZONES.

LABEL EXAMPLES:

"FIRE ALARM-ZONES 2&3"

"P.A. ZONES 4,5,&6"

"DATA CIRCUITS A&B"

"EXIT SIGNS-EMI&2"

"EMERG. CKTS. BPEM-3,4"

CKT.S

LP4-13,15,17

REAR SIDE OF

PLATE

FRONT

DUPLEX RECEPTACLE

PLATE

STANDARD TOGGLE

SWITCH PLATE

FRONT

REAR SIDE OF PLATE

SCALE:

A

E001

ELECTRICAL IDENTIFICATION DETAIL

NTS

SIZE (AWG OR KCMIL)

AUTOMATIC OVER

CURRENT SETTING

(AMPS - NOT

EXCEEDING)

COOPER

ALUMINUM

OR COPPER

CLAD

ALUMINUM

15 14 12 20 12 10 60 10 8 100 8 6 200 6 4 300 4 2 400 3 1 500 2 1/0 600 1 2/0 800 1/0 3/0 1000 2/0 4/0 1200 3/0 250 1600 4/0 350 2000 250 400 2500 350 400 3000 400 600 4000 500 600 5000 700 750 6000 800 1200

CONDUIT LOCATION OR

APPLICATION

IN CONCRETE SLAB

(NOT LARGER THAN 1"C)

R

IG

ID

CONDUIT TYPE

NOTE:

- TYPE OF CONDUIT TO BE USED.

- E.M.T. SHALL NOT BE USED IN SIZES LARGER THAN 2 INCH.

- CONVERT TO RIGID OR INTER. THROUGH SLAB.

- USE THREADED FITTINGS ONLY.

BELOW LOWEST FLOOR SLAB

CONCEALED IN WALLS, ABOVE

CEILINGS AND IN FURRED SPACES

INSIDE, ABOVE BOTTOM OF

ROOF STEEL

FEEDER, POWER AND SIGNAL

CIRCUITS RUN EXPOSED

FINAL CONNECTION TO EQUIP.

SUBJECT TO VIBRATION

FINAL CONNECTION TO EQUIP.

IN DAMP LOCATIONS

SHORT CONNECTIONS WHERE

NON-FLEXIBLE CONDUIT IS

IMPRACTICAL

IN

TE

R M

ED

IA

TE

E.

M

.T

FL

EX

IB

LE

FL

EX

IB

LE

W / W

.P

JA

CK

ET

P.

V

.C . S

CH

ED

A .C

. C A

BL

E

SERVICE ENTRANCE

THHN-THWN

EXPOSED FEEDERS

CONCEALED FEEDERS

FEEDERS BELOW

CONCRETE

FEEDERS UNDERGROUND

FEEDERS BELOW

RAISED FLOORING

FEEDERS IN CABLE TRAY

EXPOSED BRANCH CIRCUITS

CONCEALED BRANCH CIRCUITS

BRANCH CIRCUITS BELOW CONCRETE

BRANCH CIRCUITS UNDERGROUND

BRANCH CIRCUITS BELOW

RAISED FLOORING

BRANCH CIRCUITS IN

CABLE TRAY

CLASS 1 CONTROL CIRCUITS

CLASS 2 CONTROL CIRCUITS

XHHW MI NM MC UF AC

J

BUILDING STRUCTURE

JUNCTION BOX

CEILING

JUNCTION BOX

SCALE:

B

EP-001

TYPICAL CONDUIT DROP AND WALL PENETRATION

NTS

CORE DRILL THROUGH EXISTING WALL

SLEEVE

SCALE:

C

EP-001

TYPICAL CONDUIT RISE AND WALL PENETRATION

NTS

OUTSIDE OF BUILDING

SCALE:

D

EP-001

SOUTH CONDUIT ROUTING (LOOKING NORTH)

NTS

PARKING GARAGE COLUMN

INCOMING CONDUIT FEED

INSIDE OF PARKING GARAGE OUTSIDE OF PARKING GARAGE

FACE OF PARKING GARAGE

TO AREA 4 VEHICLE GATE

SCALE:

F

EP-001

AREA 4 RETAINING WALL PLAN

NTS

RETAINING WALL

SURFACE OF ROAD

RECESSED JUNCTION BOX

INCOMING CONDUIT FEED

SURFACE MOUNTED CONDUIT

JUNCTION BOX

J

BUILDING STRUCTURE

CEILING OF BASEMENT

EXTERIOR FIRST FLOOR WALL OF BUILDING

INSIDE OF BUILDING

GRADE

CEILING OF FIRST FLOOR

CORE DRILL THROUGH EXISTING WALL

SLEEVE

SCALE:

G

EP-001

TYPICAL CONDUIT THOUGH AND WALL PENETRATION

NTS

JUNCTION BOX

J

BUILDING STRUCTURE

CEILING OF BASEMENT

INSIDE OF BUILDING

GRADE

CORE DRILL THROUGH EXISTING WALL

SLEEVE

OUTSIDE OF BUILDING

FIRST FLOOR

SCALE:

H

EP-001

TYPICAL CONDUIT RISE AND WALL PENETRATION

NTS

CEILING OF BASEMENT

INSIDE OF BUILDING

GRADE

CORE DRILL THROUGH EXISTING WALL

SLEEVE

OUTSIDE OF BUILDING

FIRST FLOORFIRST FLOOR

GRADE GRADE

CONDUIT

(TYPICAL)

CONDUIT

(TYPICAL)

EXTERIOR WALL

EXTERIOR WALL

GRADE

WALL MOUNTED CONDUIT

(TIGHT AGAINST WALL)

CONDUIT MOUNTED

TIGHT TO WALL

JUNCTION BOX (MOUNTED TO

STRUCTURE JOIST ,TYPICAL)

WALL MOUNTED CONDUIT

(TIGHT TO WALL)

JUNCTION BOX (MOUNTED TO

PARKING GARAGE COLUMN)

SCALE:

I

EP-001

TYPICAL CONDUIT INTERIOR WALL PENETRATION

NTS

CORE DRILL THROUGH EXISTING WALL

FIRE RATED SLEEVECONDUIT

(TYPICAL)

INTERIOR WALL

CEILING OF FIRST FLOOR

INSTALL FIRE RATED CAULKING

GENERAL NOTES:

A. ALL WORK SHALL BE IN ACCORDANCE WITH THE BEST QUALITY STANDARDS OF THE TRADE

AND SHALL CONFORM WITH ALL FEDERAL, STATE, AND LOCAL CODES AND STANDARDS.

B. THE CONTRACTOR SHALL INCLUDE IN BID PROPOSAL ALL COSTS REQUIRED TO

COMPLETELY AND PROPERLY INSTALL ALL WORK REQUIRED FOR THE PROJECT, AND

SHALL EXAMINE THE SCOPE OF WORK OF OTHER TRADES PRIOR TO SUBMITTING A BID

PROPOSAL.

C. CONSTRUCTION DOCUMENTS SHALL BE FOLLOWED AS CLOSELY AS POSSIBLE, HOWEVER,

SYSTEMS HAVE BEEN SHOWN DIAGRAMMATICALLY AND IN SOME CASES, ENLARGED FOR

CLARITY. ANY OFFSETS, ADDITIONAL FITTINGS, AND/OR APPURTENANCES REQUIRED TO

PROVIDE A COMPLETE AND COORDINATED SYSTEM SHALL BE BORNE BY THE

CONTRACTOR.

D. ALL CIRCUITS OVER 100' IN LENGTH SHALL BE A MINIMUM #10 AWG CONDUCTOR.

E. WIRING SYSTEM SHALL BE CONDUIT AND WIRE. MINIMUM WIRE SIZE SHALL BE #12 AWG.

USE STRANDED WIRE FOR ALL SIZES. CONTRACTOR SHALL NOT REUSE EXISTING

CONDUCTORS.

F. ALL COVER PLATES FOR ELECTRICAL DEVICES SHALL BE OF A COLOR TO MATCH THE AREA

COLOR SCHEME AS DIRECTED BY THE COR.

G. THE ELECTRICAL CONTRACTOR SHALL FURNISH AND INSTALL ALL NECESSARY CONDUIT,

WIRING, PANELS, LIGHTING, ELECTRICAL DEVICES, SWITCHES AND OTHER COMPONENTS IN

COMPLETE COMPLIANCE WITH ALL CURRENT FEDERAL, STATE AND LOCAL CODES AND

ORDINANCES.

H. INSTALL GROUND WIRE IN ALL FEEDERS AND BRANCH CIRCUITS.

I. MINIMUM CONDUIT SIZE SHALL BE 3/4", UNLESS NOTED OTHERWISE.

J. ALL DEDICATED RECEPTACLES SHALL BE 20 AMP RATED.

K. CONTRACTOR SHALL FIELD VERIFY LOCATION OF DISTRIBUTION PANEL AND PROVIDE AN

UPDATED PANEL SCHEDULE.

L. ALL EXTERIOR CONDUCTORS SHALL BE XHHW TYPE.

M. FIELD VERIFY THE CONDUIT AND CABLE ROUTING. THE ROUTING ON THIS DIAGRAM IS

SCHEMATIC IN NATURE AND NOT INTENDED TO SHOW EVERY OFFSET, TRANSITION, SPLICE,

ETC., THAT MAY BE REQUIRED.

N. ANY ROUTING INDICATED THROUGH EXISTING BUILDING WILL BE DEPENDANT ON THE

PATHWAYS AVAILABLE AND MAY REQUIRE WORK WITHIN THE BUILDING FOR NEW

CONDUITS, SLEEVES, PENETRATION, FIRESTOPPING, ETC.

O. ALL OUTAGES TO EXISTING UTILITIES REQUIRED TO SUPPORT THE INDICATED WORK

SHALL BE SCHEDULED AND APPROVED BY THE COR PRIOR TO EXECUTION.

P. E.C. SHALL PERFORM CIRCUIT TRACING TO LOCATE EXISTING CIRCUITS THAT ARE FEEDING

EXISTING EQUIPMENT AND/OR LIGHTING THAT ARE BEING REMOVED, AS REQUIRED.

Q. CONTRACTOR SHALL ENSURE THAT PROVIDED BREAKERS SHALL BE COMPATIBLE WITH

THEIR RESPECTIVE PANEL.

3 3

3 1

10-21-202511-24-2025

ST

VI

N

E

ST

AREA 2 AREA 1

CONSULTANTS: ARCHITECT/ENGINEERS:

Revisions: Date:

Drawing Title

VA Health Care System Approval:

Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

Drawing # of

Veterans Health

Administration www�daengineering�com www�daengineering�com voice �31�� 4�4-�0�0 2�0� Rand Road Indianapolis, Indiana 4�241 fa[ �31�� 4�4-�3�3

Mechanical, Electrical, and Energy Engineering

DESIGN-AIRE ENGINEERING, INC.

DEH DAE

AE Site Security Updates (CIN) 539-22-208

CINCINNATI VA MEDICAL CENTER

3200 VINE STREET - CINCINNATI, OH 45220

SITE

For Official Use Only (FOUO)

BID SET

Kristina Amin Chief Engineer Cincinnati VA Medical Center

ADDENDUM 2 05/08/24

SEE ENLARGED PLANSA2

EP-201

KEYED PLAN NOTES:

1. PROVIDE AND INSTALL (1) 20A, 208V-1Ø CONNECTION FOR SLIDING GATE

AND (1) 20A, 120V-1Ø CONNECTION FOR MAN GATE IN AREA 1. SEE DETAIL 'B1'

ON SHEET EP-102 FOR ADDITIONAL INFORMATION.

2. INSTALL 4-#10, 2-#10 GND IN A 3"C.

3. PROVIDE AND INSTALL (1) 20A, 120V-1Ø CONNECTION FOR VEHICLE GATE IN

AREA 2. SEE DETAIL 'B2' ON SHEET EP-102 FOR ADDITIONAL INFORMATION.

4. INSTALL 2-#8, 1-#8 GND IN A 3"C.

5. 24" X 36" X 24" JUNCTION BOX WITH PULL STRING. JUNCTION BOX SHALL BE

VEHICLE TRAFFIC RATED AND SHALL BE SIMILAR TO MODEL "OCAST

24361210". SEE DETAIL 'A' ON SHEET EP-301 FOR INSTALLATION.

6. INSTALL 6-#10, 3-#10 GND IN A 3"C.

7. (NOTE NOT USED).

8. E.C. SHALL SAW CUT AND CHANNEL AND PATCH WITH SIMILAR/MATCHING

MATERIAL FOR EXISTING DRIVE OR SIDEWALK AS NECESSARY TO INSTALL

NEW BRANCH CIRCUIT FEEDERS.

9. (NOTE NOT USED).

10. DROP CONDUIT TO GROUND AND RUN TO JUNCTION BOX.

11. CONDUIT SHALL REMAIN ON BUILDINGS EXTERIOR.

B2

EP-102SEE ENLARGED PLAN

SEE ENLARGED PLANSB1

EP-102

EP-100

KEYED DEMOLITION PLAN NOTES:

1. DISCONNECT EXISTING GATES. REMOVE EXISTING BRANCH CIRCUIT

CONDUIT AND WIRE COMPLETE BACK TO THE PANEL. ELECTRICAL

CONTRACTOR SHALL USE CIRCUIT TRACING TO IDENTIFY WHAT

BREAKERS WILL BE DISCONNECTED. GATES SHALL BE REMOVED BY G.C.

2. ELECTRICAL CONTRACTOR SHALL DISCONNECT EXISTING GROUND

MOUNTED BOLLARDS. REMOVE EXISTING CONDUIT AND WIRE COMPLETE

BACK TO THE PANEL. ELECTRICAL CONTRACTOR SHALL USE CIRCUIT

TRACING TO IDENTIFY WHAT BREAKERS SHALL BE DISCONNECTED.

BOLLARDS SHALL BE REMOVED BY G.C.

3 1

C

EP-001

A

EP-301

AREA 5

AREA 7

AREA 4

CONSULTANTS: ARCHITECT/ENGINEERS:

Revisions: Date:

Drawing Title

VA Health Care System Approval:

Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

Drawing # of

Veterans Health

Administration www�daengineering�com www�daengineering�com voice �317� 4�4-�0�0 2707 Rand Road Indianapolis, Indiana 4�241 fa[ �317� 4�4-�3�3

Mechanical, Electrical, and Energy Engineering

DESIGN-AIRE ENGINEERING, INC.

DEH DAE

AE Site Security Updates (CIN) 539-22-208

CINCINNATI VA MEDICAL CENTER

3200 VINE STREET - CINCINNATI, OH 45220

SITE

For Official Use Only (FOUO)

BID SET

Kristina Amin Chief Engineer Cincinnati VA Medical Center

ADDENDUM 2 05/08/24

A3

EP-202

A6

EP-202

A1 E201

SEE ENLARGED PLAN

SEE ENLARGED PLAN

SEE ENLARGED PLAN

B6

EP-102SEE ENLARGED PLAN

B4

EP-102SEE ENLARGED PLAN

B5

EP-102SEE ENLARGED PLAN

B7

EP-102SEE ENLARGED PLAN

EP-101

KEYED PLAN NOTES:

1. PROVIDE AND INSTALL (1) 20A, 120V-1Ø CONNECTION FOR MAN GATE IN

AREA 5. SEE DETAIL 'B6' ON SHEET EP-102 FOR ADDITIONAL INFORMATION.

2. INSTALL 2-#10, 1-#10 GND IN A 3"C.

3. PROVIDE AND INSTALL (1) 20A, 120V-1Ø CONNECTION FOR MAN GATE IN

AREA 7. SEE DETAIL 'B7' ON SHEET EP-102 FOR ADDITIONAL INFORMATION.

4. INSTALL 2-#4, 1-#4 GND IN A 3"C.

5. ALTERNATIVE OPTION: AREA 7 TO BE SUPPLIED POWER FROM A

EMERGENCY BATTERY BACKUP.

6. PROVIDE AND INSTALL (2) 20A, 208V-1Ø CONNECTIONS FOR OPENING GATE

AND (1) 20A, 120V-1Ø CONNECTION FOR MAN GATE IN AREA 4. SEE DETAIL

'B5' ON SHEET EP-102 FOR ADDITIONAL INFORMATION.

7. RUN CONDUIT ATTACHED TO STRUCTURE.

8. PROVIDE AND INSTALL (2) 20A, 120V-1Ø CONNECTIONS FOR VEHICLE GATE

IN AREA 3. SEE DETAILS 'B3' AND 'B4' ON SHEET EP-102 FOR ADDITIONAL

INFORMATION.

9. INSTALL 8-#10, 4-#10 GND IN A 3"C.

10. INSTALL 10-#10, 5-#10 GND IN A 3"C.

11. 24" X 24" X 6" JUNCTION BOX WITH PULL STRING. MOUNT TO CEILING OF

STRUCTURE.

12. E.C. SHALL SAW CUT AND CHANNEL AND PATCH WITH SIMILAR/MATCHING

MATERIAL FOR EXISTING DRIVE OR SIDEWALK AS NECESSARY TO INSTALL

NEW BRANCH CIRCUIT FEEDERS.

13. INSTALL 6-#10, 3-#10 GND IN A 3"C.

1 6

KEYED DEMOTION PLAN NOTES:

1. DISCONNECT EXISTING GATES. REMOVE EXISTING BRANCH CIRCUIT

CONDUIT AND WIRE COMPLETE BACK TO THE PANEL. ELECTRICAL

CONTRACTOR SHALL USE CIRCUIT TRACING TO IDENTIFY WHAT

BREAKERS SHALL BE DISCONNECTED. GATES SHALL BE REMOVED BY G.C.

D

EP-001

F

EP-001

B

EP-001

A5

EP-202SEE ENLARGED PLAN

A4

EP-202SEE ENLARGED PLAN

ST

CONSULTANTS: ARCHITECT/ENGINEERS:

Revisions: Date:

Drawing Title

VA Health Care System Approval:

Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

Drawing # of

Veterans Health

Administration www�daengineering�com www�daengineering�com voice �31�� 4�4-�0�0 2�0� Rand Road Indianapolis, Indiana 4�241 fa[ �31�� 4�4-�3�3

Mechanical, Electrical, and Energy Engineering

DESIGN-AIRE ENGINEERING, INC.

DEH DAE

AE Site Security Updates (CIN) 539-22-208

CINCINNATI VA MEDICAL CENTER

3200 VINE STREET - CINCINNATI, OH 45220

SITE

For Official Use Only (FOUO)

BID SET

Kristina Amin Chief Engineer Cincinnati VA Medical Center

ADDENDUM 2 05/08/24

KEYED PLAN NOTES:

1. 20A, 208V-1Ø CONNECTION FOR AREA 1 MOTORIZED SLIDING GATE.

COORDINATE LOCATION WITH GATE CONTRACTOR.

2. 20A, 120V-1Ø CONNECTION FOR AREA 1 PEDESTRIAN KEY CARD ACCESS

GATE. COORDINATE LOCATION WITH GATE CONTRACTOR.

3. 20A, 120V-1Ø CONNECTION FOR AREA 2 VEHICLE LIFTING…