Attach III - Site Security Drawings 2.23.26.pdf
PDF 31 MB Posted
- Attached to
- Z1DA--Site Security Updates at Cincinnati VAMC. Project No. 539-22-208 Federal contract opportunity
- Solicitation number
- 36C25026B0032_1
About this file
This document is a set of architectural and engineering site security drawings for the Cincinnati VA Medical Center site security updates project (VA Project No. 539-22-208). The drawings comprise the bid set for construction work dated November 24, 2025, with addendum 2 dated May 8, 2024, and include overall campus site plans, building floor plans, ICRA (Infection Control Risk Assessment) details, electrical plans, technology/security system plans, and general construction details.
The scope encompasses demolition and installation of perimeter security improvements across the Cincinnati VA Medical Center campus at 3200 Vine Street, Cincinnati, Ohio 45220. Key security work includes removal and replacement of existing gates and controls at multiple site areas (Areas 1-7, with some areas designated 4-15), installation of sliding gates with ground loops and card readers, pedestrian gates with keypad/card reader access, swing gates with motorized operators, and bollard/planter arrangements for vehicle access control. Electrical work requires installation of power connections (20A at 120V and 208V) to support gate operators and access control devices across four electrical panels (BC1, LP2, EBCA, R1A) located in various buildings. The technology infrastructure involves installation of conduit runs, junction boxes, and connections to existing telecommunications closets to support access control system integration with the Johnson Controls P2000 Physical Access Control System (PACS). Work is restricted to evening hours after 5:00 PM and weekends in patient care areas, with full coordination required with the Contracting Officer's Representative (COR). Construction activities within buildings require ICRA Class III isolation procedures with negative air pressure and HEPA filtration in specified areas, including corridors, mechanical rooms, and electrical closets identified on detailed floor plans.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| 36C25026B0032 0003.pdf | ||
| Attach 2.1 - RFI Responses.pdf | ||
| Attach 2.2 - ICRA Permit.pdf | ||
| 36C25026B0032 0002.pdf | ||
| Attach 1.1 - Site Visit Sign In Log.pdf | ||
| 36C25026B0032 0001.pdf | ||
| 36C25026B0032_1.pdf | ||
| Attach IV - VAAR 852.219-75 VA NOTICE OF LIMITS ON SUBCONTRACTING_CERT OF COMPLIANCE JAN 2023 DEV.doc.docx | DOCX document | |
| Attach V - Sole Source JA - redact - 539-22-208.pdf | ||
| Attach I - Wage Determination 1.2.2026.txt | TXT text file | |
| Attach II - Site Security Specifications 2.23.26.pdf | ||
| Attach VI - RFI Site Security.doc | DOC document |
Show all 12
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
CINCINNATI VA MEDICAL CENTER
NRM Site Security Updates
US DEPARTMENT OF VETERANS AFFAIRS
VA CINCINNATI HEALTH CARE SYSTEM
VA PROJECT NUMBER: 539-22-208
OVERALL CAMPUS SITE PLAN, BUILDING NUMBER, AND PROJECT LOCATOR
PROJECT LOCATIONOVERALL CAMPUS
E
SHIELDS
ST
PUBLIC
R/W
VI
N
E
ST
PU
B
LI
C
R /W
GOODMANDRPUBLICR/W
G001
GENERAL - COVER SHEET
GI-001
CONSULTANTS: ARCHITECT/ENGINEERS:
Revisions: Date:
Drawing Title
VA Health Care System Approval:
Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
Drawing # of
Veterans Health
Administration www�daengineering�com www�daengineering�com voice �31�� 4�4-�0�0 2�0� Rand Road Indianapolis, Indiana 4�241 fa[ �31�� 4�4-�3�3
Mechanical, Electrical, and Energy Engineering
DESIGN-AIRE ENGINEERING, INC.
11-24-2025 DEH BZ
AE Site Security Updates (CIN) 539-22-208
CINCINNATI VA MEDICAL CENTER
3200 VINE STREET - CINCINNATI, OH 45220
SITE
For Official Use Only (FOUO)
BID SET
Kristina Amin Chief Engineer Cincinnati VA Medical Center
ADDENDUM 2 05/08/24
FENCING NOTES 11/24/25
E
SHIELDS
ST
VI
N
E
ST
AREA 2 AREA 1
AREA 12
AREA 13
AREA 8
AREA 5
AREA 14
AREA 12
AREA 12
AREA 11
AREA 15
AREA 15
AREA 15
AREA 15
CONSULTANTS: ARCHITECT/ENGINEERS:
Revisions: Date:
Drawing Title
VA Health Care System Approval:
Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
Drawing # of
Veterans Health
Administration www�daengineering�com www�daengineering�com voice �31�� 4�4-�0�0 2�0� Rand Road Indianapolis, Indiana 4�241 fa[ �31�� 4�4-�3�3
Mechanical, Electrical, and Energy Engineering
DESIGN-AIRE ENGINEERING, INC.
11-24-2025 DEH BZ
AE Site Security Updates (CIN) 539-22-208
CINCINNATI VA MEDICAL CENTER
3200 VINE STREET - CINCINNATI, OH 45220
SITE
For Official Use Only (FOUO)
BID SET
Kristina Amin Chief Engineer Cincinnati VA Medical Center
ADDENDUM 2 05/08/24
FENCING NOTES 11/24/25
PROJECT WORK AREAS
SITE PLAN - NORTH
GI-101
GOODMANDR
AREA 8
AREA 5
AREA 7
AREA 10
AREA 4
Drawing Title
VA Health Care System Approval:
Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
Drawing # of
Veterans Health
Administration www�daengineering�com www�daengineering�com voice �31�� 4�4-�0�0 2�0� Rand Road Indianapolis, Indiana 4�241 fa[ �31�� 4�4-�3�3
Mechanical, Electrical, and Energy Engineering
DESIGN-AIRE ENGINEERING, INC.
11-24-2025 DEH BZ
AE Site Security Updates (CIN) 539-22-208
CINCINNATI VA MEDICAL CENTER
3200 VINE STREET - CINCINNATI, OH 45220
SITE
For Official Use Only (FOUO)
BID SET
Kristina Amin Chief Engineer Cincinnati VA Medical Center
ADDENDUM 2 05/08/24
FENCING NOTES 11/24/25
PROJECT WORK AREAS
SITE PLAN - SOUTH
GI-102
ST
PUBLIC
R/W
VI
N
E
ST
PU
B
LI
C
R /W
CONSULTANTS: ARCHITECT/ENGINEERS:
Revisions: Date:
Drawing Title
VA Health Care System Approval:
Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
Drawing # of
Veterans Health
Administration www�daengineering�com www�daengineering�com voice �31�� 4�4-�0�0 2�0� Rand Road Indianapolis, Indiana 4�241 fa[ �31�� 4�4-�3�3
Mechanical, Electrical, and Energy Engineering
DESIGN-AIRE ENGINEERING, INC.
DEH BZ
AE Site Security Updates (CIN) 539-22-208
CINCINNATI VA MEDICAL CENTER
3200 VINE STREET - CINCINNATI, OH 45220
SITE
For Official Use Only (FOUO)
BID SET
Kristina Amin Chief Engineer Cincinnati VA Medical Center
ADDENDUM 2 05/08/24
EXISTING UTILITIES
SITE PLAN - NORTH
GI-201
REBID 08/30/24
11-24-2025
GOODMANDRPUBLICR/W
Revisions: Date:
Drawing Title
VA Health Care System Approval:
Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
Drawing # of
Veterans Health
Administration www�daengineering�com www�daengineering�com voice �31�� 4�4-�0�0 2�0� Rand Road Indianapolis, Indiana 4�241 fa[ �31�� 4�4-�3�3
Mechanical, Electrical, and Energy Engineering
DESIGN-AIRE ENGINEERING, INC.
DEH BZ
AE Site Security Updates (CIN) 539-22-208
CINCINNATI VA MEDICAL CENTER
3200 VINE STREET - CINCINNATI, OH 45220
SITE
For Official Use Only (FOUO)
BID SET
Kristina Amin Chief Engineer Cincinnati VA Medical Center
ADDENDUM 2 05/08/24
EXISTING UTILITIES
SITE PLAN - SOUTH
GI-202
11--24-2025
ST
VI
N
E
ST
AREA 2 AREA 1
CONSULTANTS: ARCHITECT/ENGINEERS:
Revisions: Date:
Drawing Title
VA Health Care System Approval:
Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
Drawing # of
Veterans Health
Administration www�daengineering�com www�daengineering�com voice �31�� 4�4-�0�0 2�0� Rand Road Indianapolis, Indiana 4�241 fa[ �31�� 4�4-�3�3
Mechanical, Electrical, and Energy Engineering
DESIGN-AIRE ENGINEERING, INC.
DEH DAE
AE Site Security Updates (CIN) 539-22-208
CINCINNATI VA MEDICAL CENTER
3200 VINE STREET - CINCINNATI, OH 45220
SITE
For Official Use Only (FOUO)
BID SET
Kristina Amin Chief Engineer Cincinnati VA Medical Center
ADDENDUM 2 05/08/24
SEE ENLARGED PLANS
FOR ICRA DETAILS
A1
GJ301
KEYED PLAN NOTES:
1. SPACE IS LOCATED ON THE EXTERIOR OF ALL BUILDINGS. ICRA IS NOT REQUIRED.
2. ELECTRICAL CONDUIT AND TECHNOLOGY CONDUITS THROUGH BUILDING. SEE
'EP' AND 'T' SHEETS.
GJ-101
OVERALL ICRA AREAS
SITE PLAN - NORTH
SEE ENLARGED PLANS
FOR ICRA DETAILS
A2
GJ302
SEE ENLARGED PLANS
FOR ICRA DETAILS
A1
GJ301
GENERAL PROJECT NOTES:
1. ALL INSIDE BUILDING WORK THAT IS IN CORRIDORS, PATIENT AREAS, AND IN
PUBLIC VIEW WILL BE DONE DURING EVENING HOURS AFTER 5:00PM (1700HRS) OR
ON WEEKENDS. ANY WORK IN AREAS #1, #4, AND #5 THAT INTERRUPTS OR
BLOCKS VEHICLES/PERSONS TRAFFIC SHALL ONLY BE DONE AFTER 5 PM OR ON
WEEKENDS. THESE AREAS CANNOT BE CLOSED DURING BUSINESS HOURS, 7 AM TO
5 PM. COORDINATE ALL WORK WITH THE COR
AREA 5
AREA 7
AREA 4
CONSULTANTS: ARCHITECT/ENGINEERS:
Revisions: Date:
Drawing Title
VA Health Care System Approval:
Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
Drawing # of
Veterans Health
Administration www�daengineering�com www�daengineering�com voice �317� 4�4-�0�0 2707 Rand Road Indianapolis, Indiana 4�241 fa[ �317� 4�4-�3�3
Mechanical, Electrical, and Energy Engineering
DESIGN-AIRE ENGINEERING, INC.
DEH DAE
AE Site Security Updates (CIN) 539-22-208
CINCINNATI VA MEDICAL CENTER
3200 VINE STREET - CINCINNATI, OH 45220
SITE
For Official Use Only (FOUO)
BID SET
Kristina Amin Chief Engineer Cincinnati VA Medical Center
ADDENDUM 2 05/08/24
A5
GJ304
A4
GJ302
SEE ENLARGED PLAN
FOR ICRA DETAILS
SEE ENLARGED PLAN
FOR ICRA DETAILS KEYED PLAN NOTES:
1. SPACE IS LOCATED ON THE EXTERIOR OF ALL BUILDINGS. ICRA IS NOT REQUIRED.
2. ELECTRICAL CONDUIT AND TECHNOLOGY CONDUITS THROUGH BUILDING. SEE
'EP' AND 'T' SHEETS.
GJ-102
OVERALL ICRA AREAS
SITE PLAN - SOUTH
A3
GJ303SEE ENLARGED PLAN
FOR ICRA DETAILS
1 1
A10
GJ306SEE ENLARGED PLANS
FOR ICRA DETAILS
A8, A9
GJ306
A6, A7
GJ305SEE ENLARGED PLANS
FOR ICRA DETAILS
GENERAL PROJECT NOTES:
1. ALL INSIDE BUILDING WORK THAT IS IN CORRIDORS, PATIENT AREAS, AND IN
PUBLIC VIEW WILL BE DONE DURING EVENING HOURS AFTER 5:00PM (1700HRS) OR
ON WEEKENDS. ANY WORK IN AREAS #1, #4, AND #5 THAT INTERRUPTS OR
BLOCKS VEHICLES/PERSONS TRAFFIC SHALL ONLY BE DONE AFTER 5 PM OR ON
WEEKENDS. THESE AREAS CANNOT BE CLOSED DURING BUSINESS HOURS, 7 AM TO
5 PM. COORDINATE ALL WORK WITH THE COR.
2. SEE ALL NOTES ON SHEET G101, GI102, GI201, & GI202.
4" RUBBER COVE
WITH 16 GA. METAL
STUDS AT 16" O.C.
BOARD EACH SIDE.
WITH 5/8" GYPSUM
AS SCHEDULED
ACOUSTICAL CEILING
2' X 4' SUSPENDED
WALL CONST. TYPES (DETAILS)
TYPE A
BASE @ BOTH SIDES
4" RUBBER COVE
3 5/8" 16 GA. METAL
STUDS AT 16" O.C.
BOARD EACH SIDE.
WITH 5/8" GYPSUM
W A
LL
H
EI
G H T
V
ER
IE
S
TYPE B
C
EI
LI
N G
H
EI
G H T
'-0
ON FLOOR PLAN.
FI
EL
D V
ER
IF
Y
C
EI
LI
N G
H
EI
G H T
'-0
4 7/8"4 7/8"
W A
LL
H
EI
G H T
V
ER
IE
S
FI
EL
D V
ER
IF
Y
TO MATCH EXISTING AREA TO MATCH EXISTING AREA
ROOF METAL DECKING
BASE @ BOTH SIDES
AS SCHEDULED
ACOUSTICAL CEILING
2' X 4' SUSPENDED
ON FLOOR PLAN.
3 5/8" INSULATED WALL
WALL TO EXTEND TO
ROOF METAL DECKING
OFFICE AREAS CARDIOLOGY CCU ANY AREA CARING FOR
ECHOCARDIOGRAPHY
ENDOSCOPY
NUCLEAR MEDICINE
PHYSICAL THERAPY
RADIOLOGY/MRI
RESPIRATORY THERAPY
EMERGENCY ROOM
LABOR & DELIVERY
LABORATORY (SPECIMEN)
NEWBORN NURSERY
OUTPATIENT SURGERY
PEDIATRICS
IMMUNOCOMPROMISED PATIENTS
BURN UNIT
CARDIAC CATH LAB
CENTRAL STERILE SUPPLY
INTENSIVE CARE UNITS
MEDICAL UNIT
PHARMACY
POST ANESTHESIA CARE UNIT
SURGICAL UNITS
NEGATIVE PRESSURE ISOLATION ROOMS
ONCOLOGY
OPERATING ROOMS INCLUDING
C-SECTION ROOMS
INFECTION CONTROL APPROVAL WILL BE REQUIRED WHEN THE CONSTRUCTION ACTIVITY AND RISK
LEVEL INDICATE THAT CLASS III OR CLASS IV CONTROL PROCEDURES ARE NECESSARY.
ROOM ELEVATION
AREA UNDER
FRAMED
PICTURE
OF
C.O.R.
ICRA, ILSM
FIRE WATCH
MISC. FORMS
PAPER
CADDY
CONSTRUCTION
RESTRICTED AREA
THIS IS A
CONST. SUPERVISOR
NAME AND
CELL PHONE
XXXXXX XXXX XXXX
CHILLER PLANT AFTER HOURS
CONTACT PHONE 82329
FIRE EMERGENCY DIAL 911
XXXXXX XXXX XXXX
XXXXXX XXXX XXXX
WITH CONTACT
INFORMATION
TYPICAL IDEAL
CONSTRUCTION LAYOUT
CLASS III
CROSS-SECTION 'A-A'
CROSS-SECTION 'A-A'
TYPICAL ALTERNATIVE
CONSTRUCTION LAYOUT
CLASS III
CLASS III (ALTERNATE)
CLASS III
1. REMOVE OR ISOLATE H.V.A.C. SYSTEM IN AREA WHERE WORK IS BEING DONE TO
PREVENT CONTAMINATION OF DUCT SYSTEM.
2. COMPLETE ALL CRITICAL BARRIERS IE. SHEETROCK, PLYWOOD, PLASTIC, TO SEAL
AREA FROM NON-WORK AREA OR IMPLEMENT CONTROL CUBE METHOD (CART WITH
PLASTIC COVERING AND SEALED CONNECTION TO WORK SITE WITH HEPA VACUUM FOR
VACUUMING PRIOR TO EXIT) BEFORE CONSTRUCTION BEGINS.
3. MAINTAIN NEGATIVE AIR PRESSURE WITHIN WORK SITE UTILIZING HEPA EQUIPPED AIR
FILTRATION UNITS IF INDICATED.
4. CONTAIN CONSTRUCTION WASTE BEFORE TRANSPORT IN TIGHTLY COVERED CONTAINERS.
5. COVER TRANSPORT RECEPTACLES OR CARTS. TAPE COVERING UNLESS SOLID LID.
6. DO NOT REMOVE BARRIERS FROM WORK AREA UNTIL COMPLETED PROJECT IS
INSPECTED BY THE OWNER'S SAFETY DEPARTMENT AND INFECTION CONTROL
DEPARTMENT AND THOROUGHLY CLEANED BY THE OWNER'S ENVIRONMENTAL SERVICES
DEPARTMENT.
1. REMOVE BARRIER MATERIALS CAREFULLY TO MINIMIZE SPREADING OF DIRT AND DEBRIS
ASSOCIATED WITH CONSTRUCTION.
2. VACUUM WORK AREA WITH HEPA FILTERED VACUUM.
3. WET MOP AREA WITH DISINFECTANT.
4. REMOVE ISOLATION OF H.V.A.C. SYSTEM IN AREAS WHERE WORK IS BEING PERFORMED.
CONSULTANTS: ARCHITECT/ENGINEERS:
Revisions: Date:
Drawing Title
VA Health Care System Approval:
Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
Drawing # of
Veterans Health
Administration www�daengineering�com www�daengineering�com voice �31�� 4�4-�0�0 2�0� Rand Road Indianapolis, Indiana 4�241 fa[ �31�� 4�4-�3�3
Mechanical, Electrical, and Energy Engineering
DESIGN-AIRE ENGINEERING, INC.
DEH DAE
AE Site Security Updates (CIN) 539-22-208
CINCINNATI VA MEDICAL CENTER
3200 VINE STREET - CINCINNATI, OH 45220
SITE
For Official Use Only (FOUO)
BID SET
Kristina Amin Chief Engineer Cincinnati VA Medical Center
ADDENDUM 2 05/08/24
GJ-201
TYPE III ICRA CONSTRUCTION
DETAILS
Electrical Closet A0004
Electric Closet A0005
Dietetics Kitchen A0011
Autopsy A004B
M . Tlt.
A004C
HAC
A004D
F. Tlt.
A004E
Storage A004F
Gross Specim en Storage A004G
Transfer Room A004A
Viewing Room A004
Gas Stor.
A005A
Gas Stor.
A005B
Pest Control A005C
Corridor C*B*13
Stor.
A007A
Hazard Chem
Stor.
A007B
Elec.
A003
Soil Linen A002
Drug Stor.
A001A
Alc. Vault A001B
Narc. Vault A001C
Elec.
A001D
M ech.
Room A005D
Stair 2 S*B*2
Corridor C*B*2
M ech. Stor.
A013
Ref. Equip.
Rm
A013A
M ech. Rm A013B
Form s Rm
A013D
Service Lobby A010
Shred Rm
A011
Nuclear Stor.
A015
Stor.
A016
PM
&R Stor.
A018
Elec.
A019
Loading Dock A017
Distribution A014
W arehouse
Receiving&Check-in A014A
Office A014B
Canteen Stor.
A014C
M ail Rm
B022
Clerk Office B022A
Receiving & Breakout
A021
Stor.
A021A
Stor.
A022C
Office A022B
Ref. Eq.
B020
Subsistence A022
Elec.
A022A
Supply Storage
A020
Em ergency
Generator B013 Transform er Room B013B
Electric Room B013A
Elec. Shop B001
Elec. Office B001A
Elec. Shop B001B
BioM ed
Chief B001C
BioM ed
Rep. Shop B004 Biom edical Engineering
B005
Stair 4 S*B*4
Biom edical
Eng.
B005A
BioM ed
W ork Area B006
BioM ed
Stor.
B006A
Super. Fee Service B006B
Stor.
B007B
Authoriz.
Clerk B007A
Lock sm ith
B021A
Locksm ith
B021
Elec.
B001D
Lead, Voucher
C&P Clerks B007
F. Tlt.
B008
M &R Stor.
B008A
M . Tlt.
B010
Stair 3 S*B*3
Sig B008B
Tele.
B008C
Soil. Linen B016
Library B015
B016A
Engineering Office B018
Eng. Stor.
B019
Fire Alarm Control B019A
Corridor C*B*6
Eng. Stor.
A023A
Stair 1 S*B*1
Tlt.
A025
Corridor C*B*1
Freezer A0012
Freezer A0007
Freezer A0008
Freezer
M isc.
Kitchen A0023
Freezer
A0010 HAC
A0021 HAC
A0019
HAC
A0018
Tele.
Equip. Rm
A035
Dry Goods/Paper
Storage A036
Office A0001
M ale Toilet A0003
Fem ale
Toilet A0002
Assistant Office A0017
Chief Office A0017A
Office A0016
Break Room A0006
Supply W arehouse A001
Stair A017A
Tele.
A025A
Office A0013
Office A0022
Gas M eter
Room A001e
Stair 11 S*B*11
M isc.
Kitchen A0020
M echanical Room A001f
UP
UP
DN
UP
UP
DN
UP
UP
DN
UP
DN
UP
DN
UP
UP
UP
ELEC
RM A0005
TELE
RM B008B
NEW 1-4"C.
PANEL
PANEL
1-1"C.
1-1"C.
CONSULTANTS: ARCHITECT/ENGINEERS:
Revisions: Date:
Drawing Title
VA Health Care System Approval:
Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
Drawing # of
Veterans Health
Administration www.daengineering.com www.daengineering.com voice �317� 464-9090 2707 Rand Road Indianapolis, Indiana 46241 fa[ �317� 464-9393
Mechanical, Electrical, and Energy Engineering
DESIGN-AIRE ENGINEERING, INC.
DEH DAE
AE Site Security Updates (CIN) 539-22-208
CINCINNATI VA MEDICAL CENTER
3200 VINE STREET - CINCINNATI, OH 45220
SITE
For Official Use Only (FOUO)
BID SET
Kristina Amin Chief Engineer Cincinnati VA Medical Center
ADDENDUM 2 05/08/24
A1
GJ301
KEYED PLAN NOTES:
1. ELECTRICAL CONDUIT AND TECHNOLOGY CONDUITS THROUGH BUILDING.
SEE 'EP' AND 'T' SHEETS.
2. ICRA III REQUIRED FOR THIS AREA.
3. AREA IS MECHANICAL AND ELECTRICAL ROOMS. ICRA IS NOT REQUIRED.
4. ICRA III REQUIRED FOR THIS AREA.
5. THIS AREA IS EXTERIOR OF BUILDING. ICRA NOT REQUIRED.
GJ-301
ENLARGED BUILDING
AREAS FOR ICRA DETAILS
GENERAL PROJECT NOTES:
1. ALL INSIDE BUILDING WORK THAT IS IN CORRIDORS, PATIENT AREAS, AND IN
PUBLIC VIEW WILL BE DONE DURING EVENING HOURS AFTER 5:00PM (1700HRS)
OR ON WEEKENDS. ANY WORK IN AREAS #1, #4, AND #5 THAT INTERRUPTS OR
BLOCKS VEHICLES/PERSONS TRAFFIC SHALL ONLY BE DONE AFTER 5 PM OR ON
WEEKENDS. THESE AREAS CANNOT BE CLOSED DURING BUSINESS HOURS, 7 AM
TO 5 PM. COORDINATE ALL WORK WITH THE COR
W aiting
C125 Consult C125A
Elec.
C126
Pharm acy
C140B
Signal C128
Tele.
C127
Stair 5 S*1*5
Tlt.
A158ACl. Lin.
Pub. Tlt.
A147B
Em ergency A147
Secl.
A154
Secl.
A152
Triage C120
Chief Off.
A151
Soil. Util.
A157 PCM
M Coordinator
A146A
Quality M anager A146B
Squad Stor.
A146
Heart Exam 1A148
Heart Exam 2A149
Restroom A149A
Heart Exam 3A150
M . Tlt.
C124
F. Tlt.
C123
Em ployee
Health C122A
Conference Room C122
Office C121
Exam C122D
Exam C122C
Police C119
Em ployee I.D.
C119A
Corridor C*1*11
W aiting
Room
Exam Room C104
HAC
C105
PEA
C106
C100
Corridor C*1*4
Office C122B
Entry A158B
Corridor C*1*13
DN
PANEL
PANEL
1-1"C.
1-1"C.
CONSULTANTS: ARCHITECT/ENGINEERS:
Revisions: Date:
Drawing Title
VA Health Care System Approval:
Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
Drawing # of
Veterans Health
Administration www.daengineering.com www.daengineering.com voice �317� 464-9090 2707 Rand Road Indianapolis, Indiana 46241 fax �317� 464-9393
Mechanical, Electrical, and Energy Engineering
DESIGN-AIRE ENGINEERING, INC.
DEH DAE
AE Site Security Updates (CIN) 539-22-208
CINCINNATI VA MEDICAL CENTER
3200 VINE STREET - CINCINNATI, OH 45220
SITE
For Official Use Only (FOUO)
BID SET
Kristina Amin Chief Engineer Cincinnati VA Medical Center
ADDENDUM 2 05/08/24
A2
GJ302
KEYED PLAN NOTES:
1. ELECTRICAL CONDUIT AND TECHNOLOGY CONDUITS THROUGH BUILDING.
SEE 'EP' AND 'T' SHEETS.
2. ICRA III REQUIRED FOR THIS AREA.
3. AREA IS MECHANICAL AND ELECTRICAL ROOMS. ICRA IS NOT REQUIRED.
4. ICRA III REQUIRED FOR THIS AREA.
5. THIS AREA IS EXTERIOR OF BUILDING. ICRA NOT REQUIRED.
GJ-302
ENLARGED BUILDING
AREAS FOR ICRA DETAILS
1 4
1 4 4
4 1 4
GENERAL PROJECT NOTES:
1. ALL INSIDE BUILDING WORK THAT IS IN CORRIDORS, PATIENT AREAS, AND IN
PUBLIC VIEW WILL BE DONE DURING EVENING HOURS AFTER 5:00PM (1700HRS) OR
ON WEEKENDS. ANY WORK IN AREAS #1, #4, AND #5 THAT INTERRUPTS OR
BLOCKS VEHICLES/PERSONS TRAFFIC SHALL ONLY BE DONE AFTER 5 PM OR ON
WEEKENDS. THESE AREAS CANNOT BE CLOSED DURING BUSINESS HOURS, 7 AM TO
5 PM. COORDINATE ALL WORK WITH THE COR
Pest Control A005C
Gas Stor.
A005B
M. Tlt.
A004C
HAC
A004D
F. Tlt.
A004E
Storage A004F
Storage A004G
Corridor C*B*13
Stair 2 S*B*2
Mech. Stor.
A013 Forms Rm.
A013D
Shred Rm.
Elec.
A003
Transfer Room A004A
Mech.
Room A005D
Autopsy Viewing Room A004
Narc. Vault A001C
Alc. Vault A001B
Drug Stor.
A001A
Elec.
A001D
Gas Stor.
A005A
Stor.
A007A
Hazard Chem.
Stor.
A007B
Mech. Rm A013B
Ref. Equip.
Rm.
A013A
Soil Linen A002
Office A0001
Female Toilet A0002
Male Toilet A0003
Supply Warehouse
A001
Mechanical Room A001f
Gas Meter Room A001e
Electric Closet A0005
Break Room A0006
Freezer A0007
Electrical Closet A0004
Freezer
A004C
Gross Specimen Storage
A004B
OIT Cage A001O
OIT Turn-In A001T
FA
A
U P
UP
CONSULTANTS: ARCHITECT/ENGINEERS:
Revisions: Date:
Drawing Title
VA Health Care System Approval:
Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
Drawing # of
Veterans Health
Administration www.daengineering.com www.daengineering.com voice �317� 464-�0�0 2707 Rand Road Indianapolis, Indiana 46241 fa[ �317� 464-�3�3
Mechanical, Electrical, and Energy Engineering
DESIGN-AIRE ENGINEERING, INC.
DEH DAE
AE Site Security Updates (CIN) 539-22-208
CINCINNATI VA MEDICAL CENTER
3200 VINE STREET - CINCINNATI, OH 45220
SITE
For Official Use Only (FOUO)
BID SET
Kristina Amin Chief Engineer Cincinnati VA Medical Center
ADDENDUM 2 05/08/24
KEYED PLAN NOTES:
1. THIS AREA IS IN AN OPEN GARAGE. ICRA IS NOT REQUIRED.
2. ELECTRICAL CONDUIT AND TECHNOLOGY CONDUITS THROUGH BUILDING.
SEE 'EP' AND 'T' SHEETS.
3. THIS AREA IS EXTERIOR OF BUILDING. ICRA NOT REQUIRED.
4. ICRA III REQUIRED FOR THIS AREA.
A4
GJ303
A3
EJ303
GJ-303
ELECTRICAL ROOM
4 2
ENLARGED BUILDING
AREAS FOR ICRA DETAILS
GENERAL PROJECT NOTES:
1. ALL INSIDE BUILDING WORK THAT IS IN CORRIDORS, PATIENT AREAS, AND IN
PUBLIC VIEW WILL BE DONE DURING EVENING HOURS AFTER 5:00PM (1700HRS) OR
ON WEEKENDS. ANY WORK IN AREAS #1, #4, AND #5 THAT INTERRUPTS OR
BLOCKS VEHICLES/PERSONS TRAFFIC SHALL ONLY BE DONE AFTER 5 PM OR ON
WEEKENDS. THESE AREAS CANNOT BE CLOSED DURING BUSINESS HOURS, 7 AM TO
5 PM. COORDINATE ALL WORK WITH THE COR
BEDROOM
BEDROOM
BEDROOM
BEDROOM
BATHROOM
1010A
BATHROOM
1015A
LINEN
CLOSET
DEN
NURSES
SUB-STATION
1027 CLOSET
SPECIAL
CARE
BATHROOM
1008A
SPECIAL
CARE
RESIDENT
ROOM
DINING
ROOM
LEISURE
Omnicells
NURSES'
STATION
1029A
VSO
CORRIDOR
SHARED
DIET./SUPRV
SOCIAL
WORKER
MDS RN
SUPPLY
CORRIDOR
C*1*1
ADMIN
S. MEN
WORK
ROOM
CORRIDOR
C*1*8
S. WOMEN
CORRIDOR
C*1*7
MD/NP
SHARED
OFFICE
RN MGR
RESTOR.
RN
SUPPORT
SHARED
MEDICAL
DIRECTOR
SOILED
UTILITY
LAUNDRY
1004 CLEAN
UTILITY
BATHING
SUITE
STORAGE
NURSING
HOME
ADMIN.
WAITING
VESTIBULE
STAIR 1
S*1*1 DN
V. WOMEN
V. MEN
RECEPTION
KITCHEN &
PANTRY
CORRIDOR
C*1*4
WORK
ROOM
1029B
LOBBY
LOUNGE
CHARTING
1029C
TECH
CLOSET
Chapel
BARBER
SHOP
ACTIVITIES
GROUP
ROOM
CLOSET
1025A
LIVING
ROOM
WHEELCHAIR
STORAGE
LAUNDRY
OXYGEN
STORAGE
STAFF
MEN'S
STAFF
WOMEN'S
BATHROOM
1009A
CORRIDOR
C*1*3
BEDROOM
BATHROOM
1123A
BEDROOM
BATHROOM
1014A
ELECTRIC
CLOSET
BATHROOM
1013A
BATHROOM
1012A
CLOSET
BATHROOM
1011A
BEDROOM
BEDROOM
BEDROOM
1122 BATHROOM
1122A
HAC
BATHROOM
1121A
BEDROOM
BATHROOM
1120A
LINEN
CLOSET
BEDROOM
BATHROOM
1119A
CONSULTANTS: ARCHITECT/ENGINEERS:
Revisions: Date:
Drawing Title
VA Health Care System Approval:
Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
Drawing # of
Veterans Health
Administration www.daengineering.com www.daengineering.com voice �317� 464-9090 2707 Rand Road Indianapolis, Indiana 46241 fa[ �317� 464-9393
Mechanical, Electrical, and Energy Engineering
DESIGN-AIRE ENGINEERING, INC.
DEH DAE
AE Site Security Updates (CIN) 539-22-208
CINCINNATI VA MEDICAL CENTER
3200 VINE STREET - CINCINNATI, OH 45220
SITE
For Official Use Only (FOUO)
BID SET
Kristina Amin Chief Engineer Cincinnati VA Medical Center
ADDENDUM 2 05/08/24
A5
GJ304
KEYED PLAN NOTES:
1. ELECTRICAL CONDUIT AND TECHNOLOGY CONDUITS THROUGH BUILDING.
SEE 'EP' AND 'T' SHEETS.
2. AREA IS MECHANICAL AND ELECTRICAL ROOMS. ICRA IS NOT REQUIRED.
3. ICRA III REQUIRED FOR THIS AREA.
GJ-304
ENLARGED BUILDING
AREAS FOR ICRA DETAILS
GENERAL PROJECT NOTES:
1. ALL INSIDE BUILDING WORK THAT IS IN CORRIDORS, PATIENT AREAS, AND IN
PUBLIC VIEW WILL BE DONE DURING EVENING HOURS AFTER 5:00PM (1700HRS) OR
ON WEEKENDS. ANY WORK IN AREAS #1, #4, AND #5 THAT INTERRUPTS OR
BLOCKS VEHICLES/PERSONS TRAFFIC SHALL ONLY BE DONE AFTER 5 PM OR ON
WEEKENDS. THESE AREAS CANNOT BE CLOSED DURING BUSINESS HOURS, 7 AM TO
5 PM. COORDINATE ALL WORK WITH THE COR
Electrical
Conference Room
Break Room 1A
Corridor C*B*2
Elev. Equip.
Vestibule
Lobby 010A
Pipe Basem ent
1B
Off.2A
Office2
HR Off 3A
HR Off.
HR Off.
HR Off.
Stairs S*B*2
HR Off.
HR Off.
Corridor C*B*1
Lobby
Bathroom 10B
HR Office
Clos.
10D
H.A.C.
Stairs S*B*1
DN
UP
UP
UP
UP
UP
UP
UP
UP
Chief
Asst. Chief 100A
Conference
Secretary
Corridor C*1*2
Storage
Lobby
Copy Room
P.M . Spec.
P.M . Spec
Office
Corridor C*1*3
Office
Pers. Asst.
P.M . Spec.
P.M . Spec.
108A
Office
Office
W ork Room
Stor.
111A
Stor.
112A
Payroll 112Corridor
C*1*1
Bathroom
Bathroom
Stairs S*1*1
Stairs S*1*2
Stor.
105A
Entry 120A
UP
UP
UP
UP
UP
UP
1-1 1/2"C. UP
1-1/2"C.
TR
2" SLEEVE
CONSULTANTS: ARCHITECT/ENGINEERS:
Revisions: Date:
Drawing Title
VA Health Care System Approval:
Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
Drawing # of
Veterans Health
Administration www.daengineering.com www.daengineering.com voice �317� 464-9090 2707 Rand Road Indianapolis, Indiana 46241 fa[ �317� 464-9393
Mechanical, Electrical, and Energy Engineering
DESIGN-AIRE ENGINEERING, INC.
DEH DAE
AE Site Security Updates (CIN) 539-22-208
CINCINNATI VA MEDICAL CENTER
3200 VINE STREET - CINCINNATI, OH 45220
SITE
For Official Use Only (FOUO)
BID SET
Kristina Amin Chief Engineer Cincinnati VA Medical Center
ADDENDUM 2 05/08/24
A6
GJ305
KEYED PLAN NOTES:
1. ELECTRICAL CONDUIT AND TECHNOLOGY CONDUITS THROUGH BUILDING.
SEE 'EP' AND 'T' SHEETS.
2. ICRA III REQUIRED FOR THIS AREA.
GJ-305
ENLARGED BUILDING
AREAS FOR ICRA DETAILS
A7
GJ305
GENERAL PROJECT NOTES:
1. ALL INSIDE BUILDING WORK THAT IS IN CORRIDORS, PATIENT AREAS, AND IN
PUBLIC VIEW WILL BE DONE DURING EVENING HOURS AFTER 5:00PM (1700HRS) OR
ON WEEKENDS. ANY WORK IN AREAS #1, #4, AND #5 THAT INTERRUPTS OR
BLOCKS VEHICLES/PERSONS TRAFFIC SHALL ONLY BE DONE AFTER 5 PM OR ON
WEEKENDS. THESE AREAS CANNOT BE CLOSED DURING BUSINESS HOURS, 7 AM TO
5 PM. COORDINATE ALL WORK WITH THE COR
UPPER LEVEL OF CATWALK
UP
DN
DN UPUP UP
FOYER
PLATFORM
LIFT
STOR.
UPPER LEVEL OF
UPPER LEVEL OF
ROOF
ROOF
KITCHEN
OFFICE
OFFICE
TOILET
#3
BOILER
#2
BOILER
#1
BOILER
INCINERATOR ROOM
SHELTER
BOILER ROOM
PUMP
HYDRAULICEXCHANGER
HEAT
PUMP
GLYCOL
EXCHANGER
HEAT
DN UP
UP
UP
TR
1-2 1/2" SLEEVE
1-2"C.
13A
FOYER
ELECT. RM.
ROOM
INCINERATOR
INCIN.
#3
BOILER
#2
BOILER
#1
BOILER
STORAGE
LOCKER ROOM
LAB
EMG. GEN. ROOM FOYER
CONTROL ROOM
BOILER ROOM
PUMP ROOM
UPPER LEVEL OFENCLOSURE
GAS BOOSTER
CONTROL PANEL
MAIN PLANT
WALK
SIDE-
SIDEWALK
DRIVE
CHIMNEY
PANEL
CONTROL
PANEL
CONTROL
PANEL
CONTROL
TANK
GEN DAY
PADS
COOLER
GAS
TURBINE
#2
GAS
VACUUM
PAD
CONCRETE
TANKS
FEED
CHEM.
COMP.
JOY AIR
SOFTENERS
ZEOLITE WATER
PAD
CONC.
ABSORBER
YORK
200 TON
DN UP
DN
UP
UP
DN
CARPENTRY
SHOP
1-2"C. UP
1-2"C.
UP
UP
UP
Locker Room
Storage 113C
Carpentry Shop
Chiller Plant
Mechanic Shop 113A
CONSULTANTS: ARCHITECT/ENGINEERS:
Revisions: Date:
Drawing Title
VA Health Care System Approval:
Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
Drawing # of
Veterans Health
Administration www.daengineering.com www.daengineering.com voice �317� 464-9090 2707 Rand Road Indianapolis, Indiana 46241 fa[ �317� 464-9393
Mechanical, Electrical, and Energy Engineering
DESIGN-AIRE ENGINEERING, INC.
DEH DAE
AE Site Security Updates (CIN) 539-22-208
CINCINNATI VA MEDICAL CENTER
3200 VINE STREET - CINCINNATI, OH 45220
SITE
For Official Use Only (FOUO)
BID SET
Kristina Amin Chief Engineer Cincinnati VA Medical Center
ADDENDUM 2 05/08/24
A10
GJ306
A8
GJ306
KEYED PLAN NOTES:
1. ELECTRICAL CONDUIT AND TECHNOLOGY CONDUITS THROUGH BUILDING.
SEE 'EP' AND 'T' SHEETS.
2. AREA IS MECHANICAL AND ELECTRICAL ROOMS. ICRA IS NOT REQUIRED.
3. ICRA III REQUIRED FOR THIS AREA.
4. AREA EXTERIOR OF BUILDING. ICRA NOT REQUIRED.
GJ-306
ENLARGED BUILDING
AREAS FOR ICRA DETAILS
1 1
A9
GJ306
1 2
4 4
GENERAL PROJECT NOTES:
1. ALL INSIDE BUILDING WORK THAT IS IN CORRIDORS, PATIENT AREAS, AND IN
PUBLIC VIEW WILL BE DONE DURING EVENING HOURS AFTER 5:00PM (1700HRS) OR
ON WEEKENDS. ANY WORK IN AREAS #1, #4, AND #5 THAT INTERRUPTS OR
BLOCKS VEHICLES/PERSONS TRAFFIC SHALL ONLY BE DONE AFTER 5 PM OR ON
WEEKENDS. THESE AREAS CANNOT BE CLOSED DURING BUSINESS HOURS, 7 AM TO
5 PM. COORDINATE ALL WORK WITH THE COR
772872
8 719
731 732 733
X
X
G G G G G
G G G G
G G
G
W W W W W W W W W W W
W W W
W W W W W
W
W W
W W
W W
W W
W W
W W
W W
W W
W W
W W
W W
W W
W
W
W W
W
WWWWWWWWW
W W
WWWWWW
W
W
W
W
W
W
W
W
W W
W W
W W
W W
W W
W W
W
W
W W
W W
W
W W
W W
W W
W W
UE
UE
UE
UE
UE
UE
UE
UE
W W
W
W
U E
U E
U E
U E
U E
U E
U E
U E
UE
U
E U
E U
E U
E
UE
UE
UE UE
UE
UE
UE
UE UE UE U
E
U E
U E
U E
U E
U E
U E
U E
UE UE UE UE
UE
UE
UE
UE
U E
U E
U E
U E
U E
U E
U E
U E
U E
U E
U E
U E
U E
U E
U E
U E
U E
U E
U E
U E
U E
U E
U E
U E
U E
U E
U E
UE
UE
UE
UE
UE
UE
U E
U E
U E
U E
U E
U E
U E
U E
U E
U E
UEUE
UE
W
U E
U E
U E
U E
UE
UE UE UE UE
UE
UE
UE
U E
U E
U E
UT UT
UT
UT
UT UT UT
U T
U T
U T
U T
UT
U
T U
T U
T U
T
U T
U T
UT
UT
UT
UT UT UT UT
UT
UT
UT
UT
UT
UT
UT
UT UT UT
U T
U T
U T
U T
U T
UT
UT
U T
U T
U T
UT
UT
UT
UT
UT
UT
UT
UT
UT
UT
UT
UT
UT
UT
UT
U T
U T
U T
U T
U T
U T
U T
U T
U T
U T
U T
U T
U T
U E
U E
U E
U E
U E
U E
UE
UE
U
E U
E U
E U
E U
E U
E U
E U
E
UE
UE UE
UE
UE
UE
UEUE
UE
U E
U E
UE
UEUEUE
UE UE UE UE UE UE UE UE UE UE
UEUE
UEU
E U
E U
E
UE
U E
U E
U E
UE
UEUEUE
UE
UEUEUEUEUEUEUEU
E
U E
U E
X
W W W W
W W
W
UE UE UE
A
B
C
D
E
F
G
H
IJ
CODED NOTES
PROVIDE SLIDING GATE WITH GROUND LOOP.
GROUND LOOP LOCATION TO BE COORDINATED
WITH ELECTRICAL PLAN AND PER
MANUFACTURER'S RECOMMENDATION. BASIS OF
DESIGN TYMETAL TYM-ST4000DC SLIDE GATE.
PROVIDE PEDESTRIAN GATE. REMOVE EXISTING
GRAVEL AND CONCRETE. REPAIR CURB. ADD
CONCRETE WALK AS NECESSARY TO CREATE
LANDING.
PROVIDE PIV CARD READER ON CONCRETE
ISLAND. COORDINATE LOCATION WITH
ELECTRICAL PLAN.
PROVIDE ENTRY AND EXIT GATES TO REPLACE
EXISTING. ENTRY TO BE ACCESSED WITH PIV
READER AND EXIT GATE TO BE ACCESSED WITH
GROUND LOOPS. LOCATION OF GROUND LOOPS
TO BE COORDINATED WITH ELECTRICAL PLANS
AND MANUFACTURER RECOMMENDATIONS.
REMOVE EXISTING GATES AND CONTROLS
COMPLETELY.
EXTEND FENCE BOTTOM TO EXISTING GRADE
WHERE GAP IS GREATER THAN 4". SEE DETAIL.
REMOVE EXISTING BOLLARDS. REPLACE WITH
ALTERNATING BOLLARDS AND PLANTERS
ACCORDING TO DETAILS. 4' SPACING EDGE OF
BOLLARD TO EDGE OF PLANTER.
EXTEND FENCE CORNER TO BE IN BETWEEN
EXISTING LIGHT POLE AND EXISTING TURN
SIGNAL. SEE DETAIL.
REPLACE BROKEN FENCE SECTION. CONTRACTOR
TO MATCH EXISTING FENCE STYLE AND COLOR.
PROVIDE BOLLARDS SPACED 4' FROM EDGE TO
EDGE. NON-CRASH RATED BOLLARD. INTENDED
FOR BUMPER POST ONLY.
SAWCUT EXISTING ASPHALT/CONCRETE.
COORDINATE LIMITS WITH INSTALLATION OF GATE
AND GROUND LOOP PER MANUFACTURES
DETAILS. CONTRACTOR TO REPAIR ASPHALT AS
NECESSARY.
EXISTING CONTROLLER TO BE MODIFIED TO
ACCEPT SIGNAL FROM SEPARATE SOURCE. SEE
ELECTRICAL PLANS
HEAVY DUTY MANUAL CANTILEVER SLIDE GATE
PROVIDE PIV READER ON WALK UP BOLLARD FOR
PEDESTRIAN ACCESS.
PROVIDE VIDEO INTERCOM WITH REMOTE
ACCESS. COORDINATE LOCATION WITH
ELECTRICAL PLAN.
PROVIDE A 21'-0" MANUAL LOCKABLE SWING GATE
TO MATCH EXISTING ON SITE MANUAL SWING
GATES. CONTRACTOR TO SUBMIT SHOP
DRAWINGS FOR OWNER APPROVAL.
SAWCUT OF CONCRETE/ASPHALT TO BE
COORDINATED WITH BOLLARD INSTALLATION
NEEDS. CONTRACTOR TO REPAIR ASPHALT AND
STRIPING AS NECESSARY.
PROVIDE 6" REMOVABLE BOLLARDS SPACED 4'
FROM EDGE TO EDGE. SEE DETAIL.
PROVIDE FIXED BOLLARD. SEE DETAIL.
(NOTE NOT USED)
SAWCUT OF SIDEWALK TO BE COORDINATED WITH
EXISTING FIRE HYDRANT.
6" CONCRETE PAD FOR GATE OPERATOR
PROVIDE PIN CARD READER ON PEDESTAL.
COORDINATE LOCATION WITH ELECTRICAL PLAN.
PROVIDE YELLOW PAINTED STRIPE ON SIDEWALK
AT 80" WEST OF GATE. PROVIDE SIGN MOUNTED
ON A 2X2 ALUMINUM POST. SIGN TO READ, "
STAND BEHIND YELLOW LINE WHEN OPENING
GATE."
CONSULTANTS: ARCHITECT/ENGINEERS:
Revisions: Date:
Drawing Title
VA Health Care System Approval:
Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
Drawing # of
Veterans Health
Administration www.daengineering.com www.daengineering.com voice (317) 464-9090 2707 Rand Road Indianapolis, Indiana 46241 fax (317) 464-9393
Mechanical, Electrical, and Energy Engineering
DESIGN-AIRE ENGINEERING, INC.
DEH BZ
AE Site Security Updates (CIN) 539-22-208
CINCINNATI VA MEDICAL CENTER
3200 VINE STREET - CINCINNATI, OH 45220
SITE
For Official Use Only (FOUO)
BID SET
Kristina Amin Chief Engineer Cincinnati VA Medical CenterADDENDUM 2 05/08/2024
H :\E ng in ee rin g2
9-
\P
\1
7\
7\
_D W
G
M is c\
S ite
S ec ur ity
P re lim in ar y.
dw g, /8
/2
9:
A
M , A nd re w B er nh ar d
0 6015 30
AE Site North
CS-101N
NOTES
1. UTILITY LOCATIONS SHOWN ARE APPROXIMATE LOCATIONS PER RECORD
2. PRIOR TO CONSTRUCTION, CONTRACTOR TO VERIFY DEPTH AND LOCATION
OF UTILITIES IN IMMEDIATE AREA.
3. CONTRACTOR TO SPECIFY MEANS AND METHODS OF EXCAVATION FOR
CONSTRUCTION. I.E HAND DIGGING OR DIRECTIONAL BORING.
4. CONTRACTOR IS RESPONSIBLE FOR ALL TRAFFIC CONTROL DURING
CONSTRUCTION.
CODED NOTES
BOLLARD
SIGN
FENCE POST
GATE STOP
LIGHT POLE BASE
SIDE WALK
CURB
FENCE
NEW PEDESTRIAN GATE AT THIS SECTION OF
FENCE
FILL IN OPEN SPACE WITH FENCE
A
B
C
D
E
F
G
H
I
J
0 205 10
15 40 10-21-2025
772872
731 732 733 734
X
X
G G G G G G G G
G G
G G
G G
G G G G G
G G G G G
G G
G G
G G
G G
G G
G
G G G G G G G G G G G G G
G G
G G
G G
G G
G G
G
W W
W
W W
WWWWWWWWW
W W
WWWWW
W W
W W
W W
W
W
W
WWWW
W W
W W
W W
W W
W W
W W
W W W
W W
W
W W W W W W W
WWWWWWWWWWWWWW
W
W
WW
WW
W
W W
W
U E
U E
U E
U E
U E
U E
U E
U E
UE UE
U E
U E
U E
U E
U E
UE
UE
U E
U E
U E
U E
U E
U E
UE
UE
UE UE
UE
UE
UE
UE UE UE U
E
U E
U E
UE
U E
U E
U E
U E
U E
UE UE UE UE
UE
UE
UE
UE
UE
U E
UE
UE
UE
UE
UE
UE
UE
U E
U E
U E
U E
UE
UE
UE
UEU
E
U E
U E
U E
U E
U E
U E
U E
U E
U E
U E
U E
U E
U E
U E
U E
U E
U E
UE
UEU
E U
E U
E U
E U
E U
E U
E U
E
UE
UE
UE
UE
UE
UE UE
U E
U E
U E
U E
U E
U E
U E
U E
U E
U E
U E
U E
U E
U E
U E
U E
U E
U E
U E
U E
U E
U E
U E
U E
UE
UE
UE
U E
U E
U E
U E
U E
UEUEUEUEUE
UE
UE UE UE UE
UE
UE
UE
U E
U E
U E
U E
U E
U E
U E
U E
U E
U E
UE UE UE
UE
UE
U T
UT
UT
UT
UT UT UT UT
UT
UT
UT
UT
UT
UT
UT
UT UT UT
U T
U T
U T
U T
U T
U T
UT
UT
UT
U T
U T
U T
U T
UT
UT
UT
UT
UT
UT
UTUT
UTUT
U T
UT
UT
UT
UT
UT
UE UE UE U
E
U E
U E
U E
UT
UT
U T
U T
U E
U E
U E
U E
U E
U E
U E
U E
U E
U E
U E
U E
X
X
X
UE
U E
U E
U E
U E
U E
U E
A
B
C
D
E
F
CODED NOTES
(NOTE NOT USED)
REMOVE EXISTING DOUBLE GATE AND POSTS
COMPLETELY. PROVIDE DOUBLE HEAVY DUTY
SWING GATES, MOTORIZED, FOR 30 FOOT
OPENING. 6" Ø HINGE POSTS. SEE ELECTRICAL
PLANS AND DETAIL.
(NOTE NOT USED)
LARGE BOULDERS TO PROTECT CORNER OF
BUILDING TO BE NO MORE THAN 5' APART WITH
MINIMUM SIZE OF 3' X 4' X 4'. SEE DETAIL.
(NOTE NOT USED)
EXTEND FENCE CORNER TO BE IN BETWEEN
EXISTING LIGHT POLE AND EXISTING TURN
SIGNAL. SEE DETAIL FOR FENCE.
EXTEND EXISTING MULCH BED TO INCORPORATE
PROPOSED BOULDERS. VERIFY WITH COR.
REPLACE EXISTING GATE WITH 8' TALL
SELF-CLOSING GATE INCLUDING PIV READER AND
ELECTRONIC LOCK PER ELECTRICAL PLANS. SEE
DETAIL.
(NOTE NOT USED)
(NOTE NOTE USED)
RELOCATE SIDEWALK TO THE WEST 16". REWORK
MULCH BED AND PLANTINGS AS REQUIRED.
CONSULTANTS: ARCHITECT/ENGINEERS:
Revisions: Date:
Drawing Title
VA Health Care System Approval:
Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
Drawing # of
Veterans Health
Administration www.daengineering.com www.daengineering.com voice (317) 464-9090 2707 Rand Road Indianapolis, Indiana 46241 fax (317) 464-9393
Mechanical, Electrical, and Energy Engineering
DESIGN-AIRE ENGINEERING, INC.
05-08-2024 DEH BZ
AE Site Security Updates (CIN) 539-22-208
CINCINNATI VA MEDICAL CENTER
3200 VINE STREET - CINCINNATI, OH 45220
SITE
For Official Use Only (FOUO)
BID SET
Kristina Amin Chief Engineer Cincinnati VA Medical CenterADDENDUM 2 05/08/2024
H :\E ng in ee rin g2
9-
\P
\1
7\
7\
_D W
G
M is c\
S ite
S ec ur ity
P re lim in ar y.
dw g, /8
/2
9:
A
M , A nd re w B er nh ar d
0 6015 30
AE Site South
CS-101S
NOTES
1. UTILITY LOCATIONS SHOWN ARE APPROXIMATE
LOCATIONS PER RECORD
2. PRIOR TO CONSTRUCTION CONTRACTOR TO VERIFY
DEPTH AND LOCATION OF UTILITIES IN IMMEDIATE AREA.
3. CONTRACTOR TO SPECIFY MEANS AND METHODS OF
EXCAVATION FOR CONSTRUCTION. I.E HAND DIGGING OR
DIRECTIONAL BORING.
4. CONTRACTOR IS RESPONSIBLE FOR ALL TRAFFIC
CONTROL DURING CONSTRUCTION.
5. CONTRACTOR IS RESPONSIBLE FOR NEW INSTALLATIONS
TO BE MINIMUM 1' FROM ANY UTILITY.
CODED NOTES
PROPOSED GATE POST ADJACENT TO EXISTING
CURB.
PROVIDE 38" MINIMUM CLEARANCE FOR GATE ARM
FROM BACK OF CURB.
PEDESTRIAN GATE.
RELOCATE SIDEWALK AND PLANTINGS AS
NECESSARY.
GATE OPERATOR
FENCE. MATCH EXISTING STYLE AND COLOR
A
B
C
D
E
F
0 205 10
16 40
Drawing Title
VA Health Care System Approval:
Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
Drawing # of
Veterans Health
Administration www.daengineering.com www.daengineering.com voice (317) 464-9090 2707 Rand Road Indianapolis, Indiana 46241 fax (317) 464-9393
Mechanical, Electrical, and Energy Engineering
DESIGN-AIRE ENGINEERING, INC.
05-08-2024 DEH BZ
AE Site Security Updates (CIN) 539-22-208
CINCINNATI VA MEDICAL CENTER
3200 VINE STREET - CINCINNATI, OH 45220
SITE
For Official Use Only (FOUO)
BID SET
Kristina Amin Chief Engineer Cincinnati VA Medical CenterADDENDUM 2 05/08/2024
GENERAL DETAILS
EXISTING FENCE
EXISTING GRADE
4" M
IN
OPENING 4"
OR GREATER
FILL GAP WITH SHEET METAL
BOLTED/SECURED TO EXISTING
FENCE. MATCH EXISTING COLOR.
EXISTING FENCE DETAIL
N.T.S.
102 6
CS-102
EXTERIOR CONCRETE
SLAB WALK DETAIL
N.T.S.
NOTES:
1. INSTALL EXPANSION JOINTS AT 30' OC MAXIMUM AND WHERE SLAB ABUTS
STRUCTURES. WHERE NEW WALK ABUTS ADJOINING WALK, SAWCUT EXISTING
WALK TO NEAREST JOINT AND INSTALL EXPANSION JOINT. EXPANSION JOINTS
SHALL BE 1/2" WIDE BY DEPTH OF SLAB. SEAL ALL EXPANSION JOINTS.
2. INSTALL CONTROL JOINTS AT 6' OC MAXIMUM. CONTROL JOINTS SHALL BE 3/8"
WIDE BY 1 1/2" DEEP AND TOOLED, SAWED JOINTS ARE NOT PERMITTED.
3. WALK SHALL HAVE A MINIMUM CROSS SLOPE OF 1.00%, MAXIMUM CROSS
SLOPE OF 2.00%.
4. WATER AND UTILITY BOXES IN THE WALK AREA SHALL BE ADJUSTED FLUSH
WITH THE FINAL SURFACE.
5. REFER TO ARCHITECTURAL PLANS FOR ADDITIONAL DETAIL AT ALL BUILDING
DOORS.
6. JOINTING PLANS MUST BE SUBMITTED FOR APPROVAL.
1/
2"
3/8"
CONTROL JOINT
1/2"
EXPANSION JOINT
2" TYP
EXPANSION JOINT
MATERIAL
JOINT SEALANT
WWR WWR
1/2"
WALK EDGE
AT BUILDING LINE
2"
EXPANSION JOINT
MATERIAL
JOINT SEALANT
WWR
BUILDING
LINE
1/2" R
7"
6"
WWR 2"
WALK EDGE
AT LAWN AREA
2"
5" ODOT
ITEM 304
5"
6x6 W1.4xW1.4
WWR
SLOPE
2"
WALK TYPICAL SECTION
PIPE BOLLARD DETAIL
N.T.S.
18" DIA.
CONC. BASE
FINISH GRADE
SEAL JOINT - TOTAL PERIMETER
SLOPE AWAY FOR PROPER DRAINAGE
6" DIA. GALV. STEEL PIPE -
FILL WITH CONCRETE -
CONC. TO BE 4000PSI WITH 4-5%
AIR ENTRAINMENT - PAINT SAFETY YELLOW
ROUND OFF CONC. TOP
TO SMOOTH FINISH
CONTRACTOR TO SUBMIT SHOP DRAWINGS
FOR OWNER'S APPROVAL
NOTES
1. MANUFACTURERS AND MODEL NUMBERS SHOWN ARE BASIS OF DESIGN.
CONCRETE FOOTING FOR POSTS
N.T.S.
18" DIA. MIN.
CONC. BASE
FINISH GRADE
PROPOSED POST VARIES. SEE PLAN
6" BEYOND POST
MIN. CONC. BASE
17 40
HYSECURITY
6705 S. 209 ST. SUITE 101
KENT, WA 98032-2327
TOLL FREE: 1-800-321-9947
PHONE: (253) 867-3700
FAX: (253) 867-3702
www.hysecurity.com
NOTES:
1. INSTALLATION TO BE COMPLETED IN ACCORDANCE WITH MANUFACTURER'S SPECIFICATIONS.
2. DO NOT SCALE DRAWING.
3. THIS DRAWING IS INTENDED FOR USE BY ARCHITECTS, ENGINEERS, CONTRACTORS, CONSULTANTS AND DESIGN PROFESSIONALS
FOR PLANNING PURPOSES ONLY. THIS DRAWING MAY NOT BE USED FOR CONSTRUCTION.
4. ALL INFORMATION CONTAINED HEREIN WAS CURRENT AT THE TIME OF DEVELOPMENT BUT MUST BE REVIEWED AND APPROVED BY
THE PRODUCT MANUFACTURER TO BE CONSIDERED ACCURATE.
5. CONTRACTOR'S NOTE: FOR PRODUCT AND COMPANY INFORMATION VISIT www.CADdetails.com/info AND ENTER
REFERENCE NUMBER 100277CGEN007
PROTECTED BY COPYRIGHT ©2024 CADDETAILS.COM LTD. CADdetails.com
08/05/2024100277CGEN007
PROTECTED BY COPYRIGHT ©2024 CADDETAILS.COM LTD.
REVISION DATE
BARRIER ARM OPERATOR, PARKING AND TRAFFIC CONTROL - STRONGARMPARK DC
TRAFFIC CONTROL / PARKING
SELECT DESIRED MODEL:
STRONGARMPARK DC 10
STRONGARMPARK DCS 10*
STRONGARMPARK DC 14
PERSPECTIVE
STRONGARMPARK DCS 14*
STRONGARMPARK
DC 10
STRONGARM™ MODELS
STRONGARMPARK
DCS 10
STRONGARMPARK
DC 14
STRONGARMPARK
DCS 14
MODEL
ARM LENGTH MAX.
OPEN/CLOSE TIME
DUTY CYCLE
HANDLING
DRIVE
FULL OPEN ANGLE
TEMP. RATING
FINISH
WARRANTY
SELECT DESIRED ACCESORY:
HY8RELAY
HY5B VEHICLE DETECTOR
HYNET COMMUNICATING GATE SYSTEM
PHOTO EYE
CONTINUOUS
ELECTROMECHANICAL
ADJUSTABLE 90° +/- 10°
-13°F TO 158°F (-25°C TO 70°C) NO HEATER
ZINC PLATED WITH POWDER COATING
2 YEARS
UP TO 10 FT (3 M)
3 SPEEDS: 1.5/2/2.5 SECONDS
LEFT HANDLING STANDARD. EASY TO
CONVERT RIGHT HANDING IN FIELD
10, 12, 14 FT (3, 3.7, 4.3 M)
3 SPEEDS: 2.5/3/3.5 SECONDS
LEFT HANDLING STANDARD.
RIGHT HANDING AVAILABLE
*DCS MODELS ARE SOLAR
DETAIL VIEW
STRAIGHT ARM
DETAIL VIEW
ARTICULATING ARM
STRAIGHT ARMS UP TO 14 FT (4.3 M)
ARTICULATING ARMS WITH 7, 8, OR 9 FT
VEHICLE CLEARANCE
HIGH VISIBILITY LED LIGHTING
ACROSS TOP OF ARM
RESILIENT BUMPER
ALONG BASE
CONSULTANTS: ARCHITECT/ENGINEERS:
Revisions: Date:
Drawing Title
VA Health Care System Approval:
Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
Drawing # of
Veterans Health
Administration www.daengineering.com www.daengineering.com voice (317) 464-9090 2707 Rand Road Indianapolis, Indiana 46241 fax (317) 464-9393
Mechanical, Electrical, and Energy Engineering
DESIGN-AIRE ENGINEERING, INC.
05-08-2024 DEH BZ
AE Site Security Updates (CIN) 539-22-208
CINCINNATI VA MEDICAL CENTER
3200 VINE STREET - CINCINNATI, OH 45220
SITE
For Official Use Only (FOUO)
BID SET
Kristina Amin Chief Engineer Cincinnati VA Medical CenterADDENDUM 2 05/08/2024
GENERAL DETAILS
CS-103
UTILITY CONDUIT
OPEN CUT DETAIL
N.T.S.
NOTES:
1. REFER TO OSHA REQUIREMENTS FOR MAXIMUM ALLOWABLE TRENCH
SLOPES.
2. THIS PORTION OF THE PIPE EMBEDMENT ZONE MUST BE RECOMPACTED TO
PROPER DENSITIES AFTER MOVING SUPPORT SYSTEM FORWARD.
3. PROVIDE FILTER FABRIC WHEN VERY FINE OR UNSTABLE MATERIAL IS
ENCOUNTERED.
4. APPLY ITEM 407 TACK COAT TO VERTICAL FACE OF SAWCUT PAVEMENT.
EXCAVATION & BACKFILL UNDER
INFLUENCE OF PAVEMENT
EXCAVATION & BACKFILL OUTSIDE
INFLUENCE OF PAVEMENT
18"18"
PAVEMENT REPLACEMENT
MATCH EXISTING SECTION MINIMUM 1.5" ITEM 441,
ASPHALT SURFACE COURSE, TYPE 1 OVER 2.5" ITEM 441,
ASPHALT INTERMEDIATE COURSE, TYPE 2
SAWCUTEX. PAVEMENT
ITEM 304, COMPACTED
GRANULAR MATERIAL
ITEM 613, LOW STRENGTH
MORTAR BACKFILL
INITIAL BACKFILL
SHAPE BELL HOLE
CONFORM AT PIPE O.D. IF UNSUITABLE MATERIAL OR ROCK
IS FOUND, OVER EXCAVATE 4" MIN.
AND PROVIDE GRANULAR BEDDING
FOR DEPTH OF COVER < 10'
PROVIDE A FLAT BOTTOM TRENCH.
FOR DEPTH OF COVER > 10'
PROVIDE 6" BEDDING NO. 57 STONE
ITEM 613, LOW
STRENGTH MORTAR
BACKFILL
NATIVE OR EXCAVATED
MATERIAL COMPACTED
TO MIN. 98% DRY DENSITY
6" TOPSOIL (OPEN AREAS)
EX. GRADE
M
AX
IM
U
M
" L
IF
TS
SE
E
N O
TE
2PIP
E I.D
CL
TRENCH WIDTH =
PIPE I.D. + 24"
GATE HANGER ASSEMBLY
BOTTOM GUIDE8
ELEVATION
PLAN VIEW
HEAVY DUTY CANTILEVER SLIDE GATE
ENLARGED SECTION
DESCRIPTION
CRITICAL DIMENSION CHART
CLEAR OPENING
HEIGHT TO TOP OF PICKET
PICKET HEIGHT
COUNTERBALANCE LENGTH
OVERALL GATE LENGTH
POST HEIGHT
F
SECTION
G
MARK
C
E D
A B
-F -G
DIM.
FORMULA
(A/2)-11" A x 1.5
E = F A x 0.5
A
COUNTERBALANCE POST SPACING C/C
CATCH ASSEMBLY
NOTES
1. MANUFACTURERS AND MODEL NUMBERS SHOWN ARE BASIS OF DESIGN.
NOTE: MATCH ADJACENT FENCE COLOR AND STYLE.
NOTE: MATCH EXISTING PICKET SIZE.
18 40
Drawing Title
VA Health Care System Approval:
Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
Drawing # of
Veterans Health
Administration www�daengineering�com www�daengineering�com voice (31�) 4�4-�0�0 2�0� Rand Road Indianapolis, Indiana 4�241 fa[ (31�) 4�4-�3�3
Mechanical, Electrical, and Energy Engineering
DESIGN-AIRE ENGINEERING, INC.
DEH DAE
AE Site Security Updates (CIN) 539-22-208
CINCINNATI VA MEDICAL CENTER
3200 VINE STREET - CINCINNATI, OH 45220
SITE
For Official Use Only (FOUO)
BID SET
Kristina Amin Chief Engineer Cincinnati VA Medical Center
ADDENDUM 2 05/08/24
EP-001
LP2-5
BPA-15
LABEL CKT. NO. OF EACH DEVICE ON REAR
SIDE OF COVER PLATE. USE PERMANENT
MARKER PEN, BRADY MARKING SYSTEM OR
OTHER METHOD APPROVED BY THE ENGINEER
JUNCTION BOXES (EXPOSED OR
CONCEALED ABOVE ACCESSIBLE
CEILING)
LABEL COVERS WITH CKT.'S
CONTAINED WITHIN. USE PERMANENT
MARKER PEN OR OTHER APPROVED
METHOD.
FOR J.B.'S CONTAINING OTHER
THAN POWER OR LIGHTING CKT.'S
LABEL COVERS INDICATING
SYSTEM TYPE AND ZONES.
LABEL EXAMPLES:
"FIRE ALARM-ZONES 2&3"
"P.A. ZONES 4,5,&6"
"DATA CIRCUITS A&B"
"EXIT SIGNS-EMI&2"
"EMERG. CKTS. BPEM-3,4"
CKT.S
LP4-13,15,17
REAR SIDE OF
PLATE
FRONT
DUPLEX RECEPTACLE
PLATE
STANDARD TOGGLE
SWITCH PLATE
FRONT
REAR SIDE OF PLATE
SCALE:
A
E001
ELECTRICAL IDENTIFICATION DETAIL
NTS
SIZE (AWG OR KCMIL)
AUTOMATIC OVER
CURRENT SETTING
(AMPS - NOT
EXCEEDING)
COOPER
ALUMINUM
OR COPPER
CLAD
ALUMINUM
15 14 12 20 12 10 60 10 8 100 8 6 200 6 4 300 4 2 400 3 1 500 2 1/0 600 1 2/0 800 1/0 3/0 1000 2/0 4/0 1200 3/0 250 1600 4/0 350 2000 250 400 2500 350 400 3000 400 600 4000 500 600 5000 700 750 6000 800 1200
CONDUIT LOCATION OR
APPLICATION
IN CONCRETE SLAB
(NOT LARGER THAN 1"C)
R
IG
ID
CONDUIT TYPE
NOTE:
- TYPE OF CONDUIT TO BE USED.
- E.M.T. SHALL NOT BE USED IN SIZES LARGER THAN 2 INCH.
- CONVERT TO RIGID OR INTER. THROUGH SLAB.
- USE THREADED FITTINGS ONLY.
BELOW LOWEST FLOOR SLAB
CONCEALED IN WALLS, ABOVE
CEILINGS AND IN FURRED SPACES
INSIDE, ABOVE BOTTOM OF
ROOF STEEL
FEEDER, POWER AND SIGNAL
CIRCUITS RUN EXPOSED
FINAL CONNECTION TO EQUIP.
SUBJECT TO VIBRATION
FINAL CONNECTION TO EQUIP.
IN DAMP LOCATIONS
SHORT CONNECTIONS WHERE
NON-FLEXIBLE CONDUIT IS
IMPRACTICAL
IN
TE
R M
ED
IA
TE
E.
M
.T
FL
EX
IB
LE
FL
EX
IB
LE
W / W
.P
JA
CK
ET
P.
V
.C . S
CH
ED
A .C
. C A
BL
E
SERVICE ENTRANCE
THHN-THWN
EXPOSED FEEDERS
CONCEALED FEEDERS
FEEDERS BELOW
CONCRETE
FEEDERS UNDERGROUND
FEEDERS BELOW
RAISED FLOORING
FEEDERS IN CABLE TRAY
EXPOSED BRANCH CIRCUITS
CONCEALED BRANCH CIRCUITS
BRANCH CIRCUITS BELOW CONCRETE
BRANCH CIRCUITS UNDERGROUND
BRANCH CIRCUITS BELOW
RAISED FLOORING
BRANCH CIRCUITS IN
CABLE TRAY
CLASS 1 CONTROL CIRCUITS
CLASS 2 CONTROL CIRCUITS
XHHW MI NM MC UF AC
J
BUILDING STRUCTURE
JUNCTION BOX
CEILING
JUNCTION BOX
SCALE:
B
EP-001
TYPICAL CONDUIT DROP AND WALL PENETRATION
NTS
CORE DRILL THROUGH EXISTING WALL
SLEEVE
SCALE:
C
EP-001
TYPICAL CONDUIT RISE AND WALL PENETRATION
NTS
OUTSIDE OF BUILDING
SCALE:
D
EP-001
SOUTH CONDUIT ROUTING (LOOKING NORTH)
NTS
PARKING GARAGE COLUMN
INCOMING CONDUIT FEED
INSIDE OF PARKING GARAGE OUTSIDE OF PARKING GARAGE
FACE OF PARKING GARAGE
TO AREA 4 VEHICLE GATE
SCALE:
F
EP-001
AREA 4 RETAINING WALL PLAN
NTS
RETAINING WALL
SURFACE OF ROAD
RECESSED JUNCTION BOX
INCOMING CONDUIT FEED
SURFACE MOUNTED CONDUIT
JUNCTION BOX
J
BUILDING STRUCTURE
CEILING OF BASEMENT
EXTERIOR FIRST FLOOR WALL OF BUILDING
INSIDE OF BUILDING
GRADE
CEILING OF FIRST FLOOR
CORE DRILL THROUGH EXISTING WALL
SLEEVE
SCALE:
G
EP-001
TYPICAL CONDUIT THOUGH AND WALL PENETRATION
NTS
JUNCTION BOX
J
BUILDING STRUCTURE
CEILING OF BASEMENT
INSIDE OF BUILDING
GRADE
CORE DRILL THROUGH EXISTING WALL
SLEEVE
OUTSIDE OF BUILDING
FIRST FLOOR
SCALE:
H
EP-001
TYPICAL CONDUIT RISE AND WALL PENETRATION
NTS
CEILING OF BASEMENT
INSIDE OF BUILDING
GRADE
CORE DRILL THROUGH EXISTING WALL
SLEEVE
OUTSIDE OF BUILDING
FIRST FLOORFIRST FLOOR
GRADE GRADE
CONDUIT
(TYPICAL)
CONDUIT
(TYPICAL)
EXTERIOR WALL
EXTERIOR WALL
GRADE
WALL MOUNTED CONDUIT
(TIGHT AGAINST WALL)
CONDUIT MOUNTED
TIGHT TO WALL
JUNCTION BOX (MOUNTED TO
STRUCTURE JOIST ,TYPICAL)
WALL MOUNTED CONDUIT
(TIGHT TO WALL)
JUNCTION BOX (MOUNTED TO
PARKING GARAGE COLUMN)
SCALE:
I
EP-001
TYPICAL CONDUIT INTERIOR WALL PENETRATION
NTS
CORE DRILL THROUGH EXISTING WALL
FIRE RATED SLEEVECONDUIT
(TYPICAL)
INTERIOR WALL
CEILING OF FIRST FLOOR
INSTALL FIRE RATED CAULKING
GENERAL NOTES:
A. ALL WORK SHALL BE IN ACCORDANCE WITH THE BEST QUALITY STANDARDS OF THE TRADE
AND SHALL CONFORM WITH ALL FEDERAL, STATE, AND LOCAL CODES AND STANDARDS.
B. THE CONTRACTOR SHALL INCLUDE IN BID PROPOSAL ALL COSTS REQUIRED TO
COMPLETELY AND PROPERLY INSTALL ALL WORK REQUIRED FOR THE PROJECT, AND
SHALL EXAMINE THE SCOPE OF WORK OF OTHER TRADES PRIOR TO SUBMITTING A BID
PROPOSAL.
C. CONSTRUCTION DOCUMENTS SHALL BE FOLLOWED AS CLOSELY AS POSSIBLE, HOWEVER,
SYSTEMS HAVE BEEN SHOWN DIAGRAMMATICALLY AND IN SOME CASES, ENLARGED FOR
CLARITY. ANY OFFSETS, ADDITIONAL FITTINGS, AND/OR APPURTENANCES REQUIRED TO
PROVIDE A COMPLETE AND COORDINATED SYSTEM SHALL BE BORNE BY THE
CONTRACTOR.
D. ALL CIRCUITS OVER 100' IN LENGTH SHALL BE A MINIMUM #10 AWG CONDUCTOR.
E. WIRING SYSTEM SHALL BE CONDUIT AND WIRE. MINIMUM WIRE SIZE SHALL BE #12 AWG.
USE STRANDED WIRE FOR ALL SIZES. CONTRACTOR SHALL NOT REUSE EXISTING
CONDUCTORS.
F. ALL COVER PLATES FOR ELECTRICAL DEVICES SHALL BE OF A COLOR TO MATCH THE AREA
COLOR SCHEME AS DIRECTED BY THE COR.
G. THE ELECTRICAL CONTRACTOR SHALL FURNISH AND INSTALL ALL NECESSARY CONDUIT,
WIRING, PANELS, LIGHTING, ELECTRICAL DEVICES, SWITCHES AND OTHER COMPONENTS IN
COMPLETE COMPLIANCE WITH ALL CURRENT FEDERAL, STATE AND LOCAL CODES AND
ORDINANCES.
H. INSTALL GROUND WIRE IN ALL FEEDERS AND BRANCH CIRCUITS.
I. MINIMUM CONDUIT SIZE SHALL BE 3/4", UNLESS NOTED OTHERWISE.
J. ALL DEDICATED RECEPTACLES SHALL BE 20 AMP RATED.
K. CONTRACTOR SHALL FIELD VERIFY LOCATION OF DISTRIBUTION PANEL AND PROVIDE AN
UPDATED PANEL SCHEDULE.
L. ALL EXTERIOR CONDUCTORS SHALL BE XHHW TYPE.
M. FIELD VERIFY THE CONDUIT AND CABLE ROUTING. THE ROUTING ON THIS DIAGRAM IS
SCHEMATIC IN NATURE AND NOT INTENDED TO SHOW EVERY OFFSET, TRANSITION, SPLICE,
ETC., THAT MAY BE REQUIRED.
N. ANY ROUTING INDICATED THROUGH EXISTING BUILDING WILL BE DEPENDANT ON THE
PATHWAYS AVAILABLE AND MAY REQUIRE WORK WITHIN THE BUILDING FOR NEW
CONDUITS, SLEEVES, PENETRATION, FIRESTOPPING, ETC.
O. ALL OUTAGES TO EXISTING UTILITIES REQUIRED TO SUPPORT THE INDICATED WORK
SHALL BE SCHEDULED AND APPROVED BY THE COR PRIOR TO EXECUTION.
P. E.C. SHALL PERFORM CIRCUIT TRACING TO LOCATE EXISTING CIRCUITS THAT ARE FEEDING
EXISTING EQUIPMENT AND/OR LIGHTING THAT ARE BEING REMOVED, AS REQUIRED.
Q. CONTRACTOR SHALL ENSURE THAT PROVIDED BREAKERS SHALL BE COMPATIBLE WITH
THEIR RESPECTIVE PANEL.
3 3
3 1
10-21-202511-24-2025
ST
VI
N
E
ST
AREA 2 AREA 1
CONSULTANTS: ARCHITECT/ENGINEERS:
Revisions: Date:
Drawing Title
VA Health Care System Approval:
Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
Drawing # of
Veterans Health
Administration www�daengineering�com www�daengineering�com voice �31�� 4�4-�0�0 2�0� Rand Road Indianapolis, Indiana 4�241 fa[ �31�� 4�4-�3�3
Mechanical, Electrical, and Energy Engineering
DESIGN-AIRE ENGINEERING, INC.
DEH DAE
AE Site Security Updates (CIN) 539-22-208
CINCINNATI VA MEDICAL CENTER
3200 VINE STREET - CINCINNATI, OH 45220
SITE
For Official Use Only (FOUO)
BID SET
Kristina Amin Chief Engineer Cincinnati VA Medical Center
ADDENDUM 2 05/08/24
SEE ENLARGED PLANSA2
EP-201
KEYED PLAN NOTES:
1. PROVIDE AND INSTALL (1) 20A, 208V-1Ø CONNECTION FOR SLIDING GATE
AND (1) 20A, 120V-1Ø CONNECTION FOR MAN GATE IN AREA 1. SEE DETAIL 'B1'
ON SHEET EP-102 FOR ADDITIONAL INFORMATION.
2. INSTALL 4-#10, 2-#10 GND IN A 3"C.
3. PROVIDE AND INSTALL (1) 20A, 120V-1Ø CONNECTION FOR VEHICLE GATE IN
AREA 2. SEE DETAIL 'B2' ON SHEET EP-102 FOR ADDITIONAL INFORMATION.
4. INSTALL 2-#8, 1-#8 GND IN A 3"C.
5. 24" X 36" X 24" JUNCTION BOX WITH PULL STRING. JUNCTION BOX SHALL BE
VEHICLE TRAFFIC RATED AND SHALL BE SIMILAR TO MODEL "OCAST
24361210". SEE DETAIL 'A' ON SHEET EP-301 FOR INSTALLATION.
6. INSTALL 6-#10, 3-#10 GND IN A 3"C.
7. (NOTE NOT USED).
8. E.C. SHALL SAW CUT AND CHANNEL AND PATCH WITH SIMILAR/MATCHING
MATERIAL FOR EXISTING DRIVE OR SIDEWALK AS NECESSARY TO INSTALL
NEW BRANCH CIRCUIT FEEDERS.
9. (NOTE NOT USED).
10. DROP CONDUIT TO GROUND AND RUN TO JUNCTION BOX.
11. CONDUIT SHALL REMAIN ON BUILDINGS EXTERIOR.
B2
EP-102SEE ENLARGED PLAN
SEE ENLARGED PLANSB1
EP-102
EP-100
KEYED DEMOLITION PLAN NOTES:
1. DISCONNECT EXISTING GATES. REMOVE EXISTING BRANCH CIRCUIT
CONDUIT AND WIRE COMPLETE BACK TO THE PANEL. ELECTRICAL
CONTRACTOR SHALL USE CIRCUIT TRACING TO IDENTIFY WHAT
BREAKERS WILL BE DISCONNECTED. GATES SHALL BE REMOVED BY G.C.
2. ELECTRICAL CONTRACTOR SHALL DISCONNECT EXISTING GROUND
MOUNTED BOLLARDS. REMOVE EXISTING CONDUIT AND WIRE COMPLETE
BACK TO THE PANEL. ELECTRICAL CONTRACTOR SHALL USE CIRCUIT
TRACING TO IDENTIFY WHAT BREAKERS SHALL BE DISCONNECTED.
BOLLARDS SHALL BE REMOVED BY G.C.
3 1
C
EP-001
A
EP-301
AREA 5
AREA 7
AREA 4
CONSULTANTS: ARCHITECT/ENGINEERS:
Revisions: Date:
Drawing Title
VA Health Care System Approval:
Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
Drawing # of
Veterans Health
Administration www�daengineering�com www�daengineering�com voice �317� 4�4-�0�0 2707 Rand Road Indianapolis, Indiana 4�241 fa[ �317� 4�4-�3�3
Mechanical, Electrical, and Energy Engineering
DESIGN-AIRE ENGINEERING, INC.
DEH DAE
AE Site Security Updates (CIN) 539-22-208
CINCINNATI VA MEDICAL CENTER
3200 VINE STREET - CINCINNATI, OH 45220
SITE
For Official Use Only (FOUO)
BID SET
Kristina Amin Chief Engineer Cincinnati VA Medical Center
ADDENDUM 2 05/08/24
A3
EP-202
A6
EP-202
A1 E201
SEE ENLARGED PLAN
SEE ENLARGED PLAN
SEE ENLARGED PLAN
B6
EP-102SEE ENLARGED PLAN
B4
EP-102SEE ENLARGED PLAN
B5
EP-102SEE ENLARGED PLAN
B7
EP-102SEE ENLARGED PLAN
EP-101
KEYED PLAN NOTES:
1. PROVIDE AND INSTALL (1) 20A, 120V-1Ø CONNECTION FOR MAN GATE IN
AREA 5. SEE DETAIL 'B6' ON SHEET EP-102 FOR ADDITIONAL INFORMATION.
2. INSTALL 2-#10, 1-#10 GND IN A 3"C.
3. PROVIDE AND INSTALL (1) 20A, 120V-1Ø CONNECTION FOR MAN GATE IN
AREA 7. SEE DETAIL 'B7' ON SHEET EP-102 FOR ADDITIONAL INFORMATION.
4. INSTALL 2-#4, 1-#4 GND IN A 3"C.
5. ALTERNATIVE OPTION: AREA 7 TO BE SUPPLIED POWER FROM A
EMERGENCY BATTERY BACKUP.
6. PROVIDE AND INSTALL (2) 20A, 208V-1Ø CONNECTIONS FOR OPENING GATE
AND (1) 20A, 120V-1Ø CONNECTION FOR MAN GATE IN AREA 4. SEE DETAIL
'B5' ON SHEET EP-102 FOR ADDITIONAL INFORMATION.
7. RUN CONDUIT ATTACHED TO STRUCTURE.
8. PROVIDE AND INSTALL (2) 20A, 120V-1Ø CONNECTIONS FOR VEHICLE GATE
IN AREA 3. SEE DETAILS 'B3' AND 'B4' ON SHEET EP-102 FOR ADDITIONAL
INFORMATION.
9. INSTALL 8-#10, 4-#10 GND IN A 3"C.
10. INSTALL 10-#10, 5-#10 GND IN A 3"C.
11. 24" X 24" X 6" JUNCTION BOX WITH PULL STRING. MOUNT TO CEILING OF
STRUCTURE.
12. E.C. SHALL SAW CUT AND CHANNEL AND PATCH WITH SIMILAR/MATCHING
MATERIAL FOR EXISTING DRIVE OR SIDEWALK AS NECESSARY TO INSTALL
NEW BRANCH CIRCUIT FEEDERS.
13. INSTALL 6-#10, 3-#10 GND IN A 3"C.
1 6
KEYED DEMOTION PLAN NOTES:
1. DISCONNECT EXISTING GATES. REMOVE EXISTING BRANCH CIRCUIT
CONDUIT AND WIRE COMPLETE BACK TO THE PANEL. ELECTRICAL
CONTRACTOR SHALL USE CIRCUIT TRACING TO IDENTIFY WHAT
BREAKERS SHALL BE DISCONNECTED. GATES SHALL BE REMOVED BY G.C.
D
EP-001
F
EP-001
B
EP-001
A5
EP-202SEE ENLARGED PLAN
A4
EP-202SEE ENLARGED PLAN
ST
CONSULTANTS: ARCHITECT/ENGINEERS:
Revisions: Date:
Drawing Title
VA Health Care System Approval:
Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
Drawing # of
Veterans Health
Administration www�daengineering�com www�daengineering�com voice �31�� 4�4-�0�0 2�0� Rand Road Indianapolis, Indiana 4�241 fa[ �31�� 4�4-�3�3
Mechanical, Electrical, and Energy Engineering
DESIGN-AIRE ENGINEERING, INC.
DEH DAE
AE Site Security Updates (CIN) 539-22-208
CINCINNATI VA MEDICAL CENTER
3200 VINE STREET - CINCINNATI, OH 45220
SITE
For Official Use Only (FOUO)
BID SET
Kristina Amin Chief Engineer Cincinnati VA Medical Center
ADDENDUM 2 05/08/24
KEYED PLAN NOTES:
1. 20A, 208V-1Ø CONNECTION FOR AREA 1 MOTORIZED SLIDING GATE.
COORDINATE LOCATION WITH GATE CONTRACTOR.
2. 20A, 120V-1Ø CONNECTION FOR AREA 1 PEDESTRIAN KEY CARD ACCESS
GATE. COORDINATE LOCATION WITH GATE CONTRACTOR.
3. 20A, 120V-1Ø CONNECTION FOR AREA 2 VEHICLE LIFTING…