Attach 08 - HVAC Sequence of Operation.pdf

PDF 53 KB Posted

Attached to
Repair HVAC Systems, B3331 Federal contract opportunity
Solicitation number
W50S8B22B0001
Issued by
Department of the Army National Guard

About this file

This document contains a sequence of operation for an HVAC system and details of a related federal contract opportunity. The federal contract opportunity, solicitation number W50S8B22B0001 from the Department of the Army National Guard, is for HVAC sustainment work to replace aging HVAC systems in Building 3331, including an exterior pad mounted condensing unit, air handler unit, and variable air volume boxes with a more energy efficient system. The majority of existing controls will also be converted to a digital control network. Response is due by an unspecified date, with award anticipated at an unspecified future date. Pricing, set aside provisions, and other contractual terms are not discussed.

View the file

Other files for this federal contract opportunity

Other files attached to Repair HVAC Systems, B3331, newest first.
File Type Posted
OF 1419 HVAC Systems-.pdf PDF
OF 1419A Replace HVAC Systems.pdf PDF
Attach 13 - NJ20220027 Wage Determination Updated Aug_5_2022.pdf PDF
SF 30 W50SS8B22B00010002 Amend 2_Updated Wage Determination.pdf PDF
SF 30 W50S8B22B00010001 Amend 0001.pdf PDF
Attach 18 - PreBid Conference Slides.pptx PPTX presentation
Attach 19 - Pre-Bid Conference_Site Visit Sign-in.pdf PDF
Attach 01 - Attachment Schedule Updated 7_28_2022.xlsx XLSX spreadsheet
SF 1442 W50S8B22B0001 Replace HVAC Systems - B3331.pdf PDF
Attach 07 - B3331-Avionics-Elect-Pwr.PDF PDF
Attach 03 - Bidder Instructions.docx DOCX document
Attach 04 - SOW -Replace HVAC Systems_B3331.pdf PDF
Attach 11 - B3331-Avionics-Lighting-Panels.PDF PDF
Attach 14 - Insurance Requirements.docx DOCX document
Attach 05 - B3331-Avionics-HVAC Controls.pdf PDF
Attach 10 - B3331-Avionics-Mech-Rm.PDF PDF
Attach 12 - B3331-Avionics-HVAC-Schedule.PDF PDF
Attach 16 - JB MDL Antiterrorism Awareness for Contractors.pdf PDF
Attach 17 - Appendix 4 to Annex C Contractor Appendix.DOCX DOCX document
Attach 01 - Attachment Schedule.xlsx XLSX spreadsheet
Attach 02 - Section 00010 Notes.docx DOCX document
Attach 06 - B3331 Avionics HVAC.pdf PDF
Attach 09 - B3331-Elect-Pwr-1994.pdf PDF
Attach 13 - DOL Wage Determination NJ20220027 06_24_2022.pdf PDF
Attach 15 - AT Statement.pdf PDF
Show all 25

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Air Condensing Unit - Sequence of Operation

Air Condensing Unit shall operate in accordance with a pre-programmed schedule written to the Supervisory Controller Scheduling Program. The system shall index from occupied to unoccupied and back in accordance with this schedule. The resident schedule shall also maintain holiday schedules and Daylight Savings changeover times.

Ventilation Delay Time Mode - Supervisory system shall maintain occupied enable times. The supervisory controller based upon ambient conditions and system historical performance data will calculate a time period. This time period shall represent the Ventilation Delay Mode Time. From the point the system is indexed to occupy, to the expiration of the Ventilation Delay Time, the ventilation mode of the unit's control loop shall remain disabled. Upon expiration of the VDT, the economized dampers shall be enabled as described below.

Fan Operation Occupied - When the system is indexed to the occupied mode, the Supply Fan's Variable Frequency Drives are enabled. Based on the Duct Static Pressure Setting, the fan will modulate in order to maintain the systems static pressure setting. Upon indexing the system to the unoccupied mode, the supply fan shall turn off and cycle based upon the unoccupied temperature set point.

Fan Operation Unoccupied - When the system is indexed to the unoccupied mode, the supply fan shall shut down.

Economizer – When the Outside Air Temperature (OAT) falls below 58 DegF (adjustable), economizer mode is enabled and mechanic cooling is locked out. Outside air dampers and return air dampers shall modulate to maintain mixed air temp on 55DegF (adjustable). When OAT is above 58 DegF, outside air dampers and return dampers shall go to minimum position and mechanical cooling is enabled.

Discharge Temperature Control Occupied - Discharge Temperature Sensor, DAS serving digital controller, shall operate the temperature control loop in the following sequence. Upon the start of supply fan, the controller, shall modulate 3 way hot water value in order to maintain a constant 58° F (adjustable) discharge air temperature. Upon a continued rise in Discharge Air Temperature, Controller shall modulate the outside dampers open and the return air damper closed. Upon a fall in Discharge Air Temperature, the reverse shall occur. Discharge air set point will be automatically reset by controller according to return air temp.

Hot water circulator pump and Boiler control: Hot water circulator and boiler will be enabled at OAT below 65 degF (Adjustable)

Three way hot water mixing wave will reset hydronic radiator loop water temperature to maintain temperature according to the following reset schedule: At 0 DegF OAT, water temperature is 180 DegF.

At 65 DegF OAT, water temperature is 100 DegF.

Safeties - A freeze stat, located in the hot water coil discharge, shall act to shut down the system in the event its set point is exceeded. A system shutdown shall cause the following actions to occur. Supply fan and return fan shall shut down and lock out. Power to the outside, return and relief air dampers shall be shutdown causing those dampers to return to their normal positions via a mechanical spring return action integral to the damper actuators. Power to the heating hot water valve actuator shall be shutdown causing the valve to return to its normal position (full open to the coil) via a mechanical spring return action integral to the valve actuator. This freezestat shall require manual reset. Actuation of the freezestat shall also initiate a network alarm at the Supervisory Controller.

Smoke Detectors - Smoke detectors (by others) located in the supply and return of the system shall operate to shut down the system in the event that products of combustion are sensed in the airstream.

Upon shutdown the supply fan and return fan shall stop and all dampers shall go to their normal positions. These detectors shall require manual reset. This sequence contains no allowances for the interface of duct smoke detectors to the building fire alarm system.

Sequence of Operation

Variable Air Volume Controls

The control damper of the VAV box shall modulate in response to the signal from a flow sensing element at the discharge or inlet of the VAV box to a microprocessor based VAV box velocity controller. The velocity controller shall modulate the box damper from the minimum position the full flow position based on a signal from a space mounted temperature sensor in a sequence designed to maintain an adjustable space set point. This sequence shall be as follows. Upon a rise in space temperature the VAV controller shall modulate the VAV damper open from minimum flow to maximum flow. Upon a fall in space temperature the reverse shall occur. On a rise in space temperature the reverse shall occur.

File details come from the government source that posted it. Updated .