This file is a comprehensive set of plumbing design drawings for the Create Cardiovascular Center project at Lake Nona VA Medical Center in Orlando, Florida. The document contains detailed plumbing plans, isometrics, schedules, and technical specifications for a new cardiovascular facility, covering both demolition and new work areas. The drawings include extensive details for gravity and pressure piping systems, medical gas installations, plumbing fixtures, storm drainage, and medical gas outlet and valve box configurations.
Key technical elements include medical gas systems with multiple gas types (oxygen, medical air, medical vacuum, nitrous oxide, carbon dioxide), medical gas zone valve boxes, alarm panels, and manifold systems. The project is phased, with specific instructions for connecting to existing infrastructure and coordinating work across different building areas. Plumbing systems are designed to meet VA design standards, NFPA codes, and include specialized components like thermostatic mixing valves, trap primers, and specific fixture types tailored for healthcare environments. The drawings are part of a 100% Construction Documents - Bid Set dated 03/07/2025, with the project number 675-103 and Kevin Glover listed as the Contracting Officer's Representative.
View the file
Other files
Show all 20
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
1. DRAWINGS ARE DIAGRAMMATIC AND INDICATE GENERAL ARRANGEMENT OF SYSTEMS. PROVIDE COMPONENTS INDICATED IN DETAILS AND/OR RISER DIAGRAMS WHETHER OR NOT INDICATED ON PLANS AND VICE VERSA. WHERE A DISCREPANCY OR CONFLICT IS FOUND BETWEEN ONE DRAWING AND ANOTHER, OR BETWEEN A DRAWING AND APPLICABLE SPECIFICATIONS, NOTIFY THE ARCHITECT/ENGINEER IMMEDIATELY IN WRITTEN FORM. IN GENERAL, THE MOST STRINGENT REQUIREMENT SHALL GOVERN UNLESS THE DISCREPANCY CONFLICTS WITH APPLICABLE CODES OR OWNER'S DESIGN
STANDARDS, WHEREIN THE CODE OR OWNER'S DESIGN STANDARDS SHALL GOVERN.
2. LOCATE VALVES IN ACCESSIBLE AREAS WHERE NECESSARY. (12"X12" MIN.)
3. COORDINATE ACTUAL LOCATIONS OF MECHANICAL FLOOR DRAINS WITH FINAL EQUIPMENT LOCATIONS ON SHOP
DRAWINGS.
4. VENT PIPING SHOWN IS ONLY FOR DIAGRAMMATIC PURPOSES. COORDINATE VTRS WITH HVAC AIR INTAKES.
5. PROVIDE BACKWATER VALVES FOR CONDENSATE PIPING CONNECTIONS TO STORM SEWER.
6. PROVIDE PIPE MARKER FOR ALL PIPING ABOVE THE CEILING SPACES IN ACCORDANCE WITH DIVISION 22 SPECIFICATION
SECTION. "IDENTIFICATION FOR PLUMBING PIPING AND EQUIPMENT".
7. LABEL VALVES ABOVE CEILINGS AND IN CONCEALED SPACES AT CEILING TILE WITH METAL CEILING TACKS INDICATING VALVE # AND TYPE OF WATER. (i.e.; BLUE= COLD WATER, LETTERING CW VLV1-001).
8. PROVIDE AND INSTALL WATER HAMMER ARRESTORS IN ACCORDANCE WITH PDI-WH201 IN ALL HW AND CW SUPPLY PIPING WITH QUICK CLOSING VALVES AS REQUIRED. AIR CHAMBERS ARE NOT ACCEPTABLE SUBSTITUTIONS.
9. PROVIDE THERMAL INSULATION FOR HOT WATER AND HOT WATER RETURN PIPING IN ACCORDANCE WITH THE ENERGY
EFFICIENCY CODE FOR BUILDING CONSTRUCTION AND PER SPECIFICATIONS.
10. PROVIDE CLEANOUTS AT THE BASE OF EACH SANITARY STACK. SIZE CLEANOUTS TO MATCH THE PIPING SERVED. SPACE FLOOR CLEANOUTS AT 100'-0" MAX. ALSO PROVIDE CLEANOUTS IN HORIZONTAL CHANGE OF DIRECTION > 45°.
11. THE MANUFACTURERS OF EQUIPMENT SHOWN ARE THE BASIS OF DESIGN. SEE SPECIFICATION FOR OTHER ACCEPTABLE
MANUFACTURERS.
12. FIRE CAULK AND SLEEVE PENETRATIONS THROUGH FIRE RATED ASSEMBLIES. REFER TO LIFE SAFETY PLANS FOR RATED ASSEMBLY LOCATIONS. REFER TO ARCHITECTURAL SHEETS FOR DETAILS AND UL ASSEMBLY NUMBERS.
13. REFER TO ARCHITECTURAL SHEETS FOR FIXTURE MOUNTING.
14. COORDINATE UNDERGROUND PIPING INVERT ELEVATIONS WITH STRUCTURAL FOOTING ELEVATIONS AND CIVIL INVERT
CONNECTIONS PRIOR TO ANY UNDERGROUND PIPING INSTALLATIONS.
15. COORDINATE CEILING PIPING AND ELEVATIONS IN SHOP DRAWINGS WITH ALL OTHER TRADES (I.E. HVAC, FIRE PROTECTION, ELECTRICAL, TELECOMM, STRUCTURAL, ETC.) PRIOR TO ANY INSTALLATION TO ENSURE PROPER
CLEARANCES AND PENETRATIONS.
16. SLOPE SANITARY PIPING 2-1/2" OR LESS AT 1/4" PER FOOT. SLOPE SANITARY PIPING 3" AND LARGER AT 1/8" PER FOOT.
17. VALVES AND FITTINGS SHALL BE THE SAME SIZE AS THE PIPING WHERE THEY ARE LOCATED UNLESS NOTED OTHERWISE.
18. PROVIDE ALL NECESSARY SUPPORTING DEVICES FOR FIXTURES PER MANUFACTURER INSTALLATION INSTRUCTIONS.
19. PROVIDE ALL FLOOR DRAINS, FLOOR SINKS AND HUB DRAINS WITH DEEP SEAL P-TRAPS. ALL DRAINS NOT RECEIVING CONTINUOUS DISCHARGE SHALL BE PROVIDED WITH TRAP PRIMER CONNECTIONS TO ENSURE TRAP SEAL PROTECTION.
20. ROUGH-IN WASTE AND WATER SUPPLIES FOR FIXTURES AND PERFORM FINAL CONNECTIONS PER MANUFACTURER
RECOMMENDATIONS.
21. THE CONTRACTOR SHALL BASE THEIR PROPOSAL UPON THE EQUIPMENT AS SCHEDULED USING THE MANUFACTURERS AND MODEL NUMBERS AS SCHEDULED ON THE DRAWINGS. IF THE CONTRACTOR WISHES TO USE EQUIPMENT NOT SCHEDULED, THEY MAY SUBMIT TO ENGINEER FOR REVIEW AND COMPLIANCE WITH CONTRACT DOCUMENTS.
22. ROUGH IN FLUSH VALVE WATER CLOSETS SO THAT THE FLUSH VALVE HANDLE IS TO THE WIDE SIDE OF THE ROOM.
23. COMPLY WITH THE AMERICANS WITH DISABILITIES ACT (ADA) ACCESSIBILITY GUIDELINES FOR BUILDINGS AND FACILITIES.
24. ALL AUTOMATIC CONTROL, PROTECTIVE OR SIGNAL DEVICES REQUIRED FOR THE OPERATION SPECIFIED, SHALL BE
PROVIDED WITH ANY CONTROL WIRING AND INSTALLED PER MANUFACTURER'S REQUIREMENTS.
25. THE PRIMARY ROOF DRAIN SYSTEM HAVE BEEN DESIGNED TO HANDLE 100 YEAR FOR ONE HOUR AT 4.5" PER HOUR
RAINFALL RATE.
26. PROVIDE AN AIR GAP, WHEN REQUIRED BY CODE, SERVING INDIVIDUAL FIXTURES, DEVICES, APPLIANCES AND APPARATUS.
27. SHOP DRAWING SUBMITTALS SHALL BE FULLY COORDINATED PRIOR TO SUBMITTAL.
28. ALL CONNECTIONS OF NEW DOMESTIC COLD, HOT, AND HOT WATER PIPING TO EXISTING PIPING MAINS SHALL BE ACCOMPLISHED VIA A FREEZE-TAP AND SHALL NOT REQUIRE COMPLETE SHUTDOWNS OF THE SYSTEMS.
PLUMBING ABBREVIATIONSPLUMBING SYMBOL LEGEND
SYMBOL DESCRIPTION
NOTE: SOME SYMBOLS SHOWN ON THIS LEGEND MAY NOT PERTAIN TO THIS PROJECT
MEDICAL COMPRESSED AIR PIPINGMA
HOT WATER PIPINGHW
HOT WATER RETURN PIPINGHWR
STO STORM OVERFLOW (SECONDARY)
ST STORM (PRIMARY)
SANITARY DRAINAGE PIPING (UNDERGROUND)SAN U/G
SANITARY DRAINAGE PIPING (ABOVE SLAB)SAN
V VENT PIPING
GATE VALVE
PRESSURE GAUGE
CHECK VALVE
BALL VALVE
CIRCULATING PUMP
PIPE END CAP
PIPE TURNING DOWN
PIPE TURNING UP
PIPE TURNING DOWN (TEE)
NATURAL GAS PIPING
CLEANOUTS
CW COLD WATER PIPING
CD CONDENSATE PIPING
CIRCUIT SETTER VALVE
OR
PDI-"A" WATER HAMMER ARRESTER & SIZE
THERMOSTATIC MIXING VALVE
HB-1 OR WHY-1 HOSE BIBB / WALL HYDRANT
FLOW ARROW
P-TRAP
ROLL DOWN
PIPING TEE
ST U/G STORM PIPING (UNDERGROUND)
G
PRESSURE REGULATING VALVE
BUTTERFLY VALVE
A
B
SIM
A
SECTION SYMBOL:
A = IDENTIFYING LETTER
B = SHEET WHERE SECTION IS SHOWN
SIM =
(ONLY NOTED IF IT APPLIES)
PLUMBING RISER DESIGNATION:
A = RISER IDENTIFYING SYSTEM TYPE
1 =
REVISION CLOUD AND
REVISION NUMBER
SHEET NOTE CALLOUT
A TITLE SYMBOL ON SHEET WHERE SHOWN
A = IDENTIFYING NUMBER/LETTER
RISER IDENTIFYING SYSTEM NUMBER
SIMILAR
ABBR. DESCRIPTION ABBR. DESCRIPTION
PLUMBING GENERAL NOTES
WATER HAMMER ARRESTOR
SYMBOL
1/2"
PIPE SIZE PDI STANDARD FIXTURE UNIT CAP.
3/4"
1"
1-1/4"
A
B
C
D
1 TO 11
12 TO 32
33 TO 60
61 TO 113
DEMOLISH TO POINT INDICATED
CONNECT TO EXISTING
DEMOLISHED PIPING
EXISTING PIPING
NEW PIPING
AS ABOVE SLAB
ADA AMERICANS WITH DISABILITIES ACT
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
ANSI AMERICAN NATIONAL STANDARDS INSTITUTE
AP ACCESS PANEL
ASTM AMERICAN STANDARDS TESTING MATERIALS
AWWA AMERICAN WATER WORKS ASSOCIATION
BFP BACKFLOW PREVENTER
BS BELOW SLAB
BF BELOW FLOOR
BG BELOW GRADE
CA COMPRESSED AIR
CD CONDENSATE
CO CLEANOUT
CONN CONNECTION
CONT CONTINUOUS
CP CIRCULATING PUMP
CW COLD WATER
DF DRINKING FOUNTAIN
DFU DRAINAGE FIXTURE UNITS
DIA DIAMETER
DN DOWN
DWG DRAWING
DW DOMESTIC WATER
ECO EXTERIOR CLEANOUT
ELEV ELEVATION
EQUIP EQUIPMENT
EWC ELECTRIC WATER COOLER
EWH ELECTRIC WATER HEATER
EX EXISTING
EXIST EXISTING
ºF DEGREES FAHRENHEIT
FCO FLOOR CLEANOUT
FD FLOOR DRAIN
FIN FINISH
FL FLOOR
FPS FEET PER SECOND
FT FEET
FU FIXTURE UNITS
G NATURAL GAS
GAL GALLON(S)
GPM GALLONS PER MINUTE
GR GREASE WASTE
HB HOSE BIBB
HP HORSEPOWER
HR HOUR
HW HOT WATER
HWR HOT WATER RETURN
HZ HERTZ
IE INVERT ELEVATION
ID INTERNAL DIAMETER
IN INCHES
IPS INTERNATIONAL PIPE STANDARD
IRR IRRIGATION WATER
KW KILOWATT
LAV LAVATORY
LF LINEAR FEET
MAP MEDICAL GAS ALARM PANEL (AREA ALARM)
MAX MAXIMUM
MIN MINIMUM
MNTG MOUNTING
MS MOP SINK
NA NOT APPLICABLE
NC NORMALLY CLOSED
NIC NOT IN CONTRACT
NO NORMALLY OPEN
NSF NATIONAL SANITATION FOUNDATION
NTS NOT TO SCALE
OD OUTSIDE DIAMETER
ORWL OVERFLOW RAIN WATER LEADER
PDI PLUMBING DRAINAGE INSTITUTE
PH PHASE
PPP PRECISION PLUMBING PRODUCTS
PSI POUNDS PER SQUARE INCH
RD ROOF DRAIN
RPM REVOLUTIONS PER MINUTE
RWL RAIN WATER LEADER
RX REMOVE EXISTING
S SANITARY
SAN SANITARY
SH SHOWER
SK SINK
SL SODA LINE
SPEC SPECIFICATION
SQ SQUARE
SS STAINLESS STEEL
STD STANDARD
ST STORM
TDH TOTAL DYNAMIC HEAD
TEMP TEMPERATURE
TET THERMAL EXPANSION TANK
TMV THERMOSTATIC MIXING VALVE
TOF TOP OF FOOTING
TP TRAP PRIMER
TYP TYPICAL
UL UNDERWRITER'S LABORATORY
U/G UNDERGROUND
UNO UNLESS NOTED OTHERWISE
UR URINAL
V VENT
VTR VENT THROUGH ROOF
VIV VALVE IN VERTICAL
VLV VALVE
VOL VOLUME
W WATTS
W/ WITH
WC WATER CLOSET
WCO WALL CLEANOUT
WHA WATER HAMMER ARRESTOR
WHY WALL HYDRANT
WFU WATER SUPPLY FIXTURE UNITS
ZVB MEDICAL GAS ZONE VALVE BOX
APPLICABLE CODES
1. VA PLUMBING DESIGN MANUAL 2023 EDITION
2. VA PULMONARY MEDICINE SERVICE DESIGN GUIDE 2011 EDITION
3. INTERNATIONAL BUILDING CODE: CONFORM IN STRICT COMPLIANCE TO THE FLORIDA BUILDING CODE (IBC) AND THE
AMENDMENTS WHICH ARE ENFORCED BY THE LOCAL AUTHORITY HAVING JURISDICTION.
A. INTERNATIONAL BUILDING CODE - PLUMBING (IPC) 2021 EDITION
B. INTERNATIONAL BUILDING CODE - FUEL GAS (IFGC) 2021 EDITION
C. INTERNATIONAL BUILDING CODE - ENERGY CONSERVATION (IECC) 2021 EDITION
4. NATIONAL FIRE PROTECTION ASSOCIATION (NFPA), INCLUDING (BUT NOT LIMITED TO):
A. COMPRESSED GASES AND CRYOGENIC FLUIDS CODE, NFPA 55 2023 EDITION
B. NATIONAL ELECTRICAL CODE (NEC) 2023 EDITION
C. HEALTH CARE FACILITIES CODE (NFPA 99) 2021 EDITION
D. LIFE SAFETY CODE (NFPA 101) 2021 EDITION
5. OCCUPATIONAL SAFETY AND HEALTH ACT (OSHA)
6. ARCHITECTURAL BARRIERS ACT ACCESSIBILITY STANDARD (ABAAS)
7. AMERICAN SOCIETY OF TESTING AND MATERIALS (ASTM)
8. APPLICABLE STANDARDS, REGULATIONS, AND PRACTICES OF THE OWNER
SYMBOL DESCRIPTION
CONTROL VALVE
BUTTERFLY VALVE
CALIBRATING BALANCING VALVE
BALL VALVE
STRAINER
UNION
THERMOMETER
PSI REG.
FLOW SWITCH
CHECK VALVE
THREE-WAY CONTROL VALVE
FLEX CONNECTION
RELIEF VALVE
VALVE ON RISER
TEST PLUG
GLOBE VALVE
PSI REG.
FLOW SWITCH
PRESSURE SWITCH
AUTOMATIC AIR VENT
MEDICAL COMPRESSED AIR INTAKE PIPINGMAI
MEDICAL VACUUM PIPINGMV
MEDICAL VACUUM EXHAUST PIPINGMVE
WASTE ANESTHETIC GAS DISPOSAL PIPINGWAGD
WASTE ANESTHETIC GAS DISPOSAL EXHAUST PIPINGWAGDE
NITROGEN PIPINGN2
OXYGEN PIPINGO2
NITROUS OXIDE PIPINGNO
CARBON DIOXIDE PIPINGCO2
LABORATORY COMPRESSED AIR PIPINGLA
LABORATORY COMPRESSED AIR INTAKE PIPINGLAI
LABORATORY VACUUM PIPINGLV
LABORATORY VACUUM EXHAUST PIPINGLVE
PROCESS COMPRESSED AIR PIPINGPA
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10 www.abovegroupinc.com COA/CA Lic. No. 31120
FULLY SPRINKLERED305 East Dr., Suite H, Melbourne, Florida 32904
PH: 321.345.9026
A u to d e s k D o c s
/F lo ri d a
O rl a n d o
V A
/0
V A
L a k e N o n a C a rd io lo g y
R
M
E P
F P
F A
T .r v t
/7
/2
:3
:1
A M
P-001
PLUMBING NOTES, LEGENDS, &
SYMBOLS
Create Cardiovascular Center at Lake Nona
Orlando, Florida
675-103
Kevin Glover - COR
03/07/2025 JMC AJZ
100% CONSTRUCTION
DOCUMENTS - BID SET
ALLEN D. LANTZ, P.E.
FL License #98984
SHEET LIST
SHEET NUMBER SHEET NAME
P-001 PLUMBING NOTES, LEGENDS, & SYMBOLS
PC101 PLUMBING PHASING PLANS
PC102 PLUMBING PHASING PLANS
PD101 PARTIAL UNDERSLAB PLAN - PLUMBING GRAVITY - DEMO - AREA A
PD102 PARTIAL UNDERSLAB PLAN - PLUMBING GRAVITY - DEMO - AREA B
PD111 PARTIAL LEVEL 1 PLAN - PLUMBING GRAVITY - DEMO - AREA A
PD112 PARTIAL LEVEL 1 PLAN - PLUMBING GRAVITY - DEMO - AREA B
PD113 PARTIAL LEVEL 1 PLAN - PLUMBING PRESSURE - DEMO - AREA A
PD114 PARTIAL LEVEL 1 PLAN - PLUMBING PRESSURE - DEMO - AREA B
PD121 PARTIAL LEVEL 1 INTERSTITIAL PLAN - PLUMBING GRAVITY - DEMO - AREA A
PD122 PARTIAL LEVEL 1 INTERSTITIAL PLAN - PLUMBING GRAVITY - DEMO - AREA B
PD123 PARTIAL LEVEL 1 INTERSTITIAL PLAN - PLUMBING PRESSURE - DEMO - AREA A
PD124 PARTIAL LEVEL 1 INTERSTITIAL PLAN - PLUMBING PRESSURE - DEMO - AREA B
PS101 PARTIAL UNDERSLAB PLAN - PLUMB. GRAVITY - NEW WORK - AREA A
PS102 PARTIAL UNDERSLAB PLAN - PLUMB. GRAVITY - NEW WORK - AREA B
PS111 PARTIAL LEVEL 1 PLAN - PLUMBING GRAVITY - NEW WORK - AREA A
PS112 PARTIAL LEVEL 1 PLAN - PLUMBING GRAVITY - NEW WORK - AREA B
PS112.D PARTIAL LEVEL 1 PLAN - PLUMBING GRAVITY - NEW WORK - AREA B DEDUCT
PS121 PARTIAL LEVEL 1 INTERSTITIAL PLAN - PLUMBING GRAVITY - NEW WORK - AREA A
PS122 PARTIAL LEVEL 1 INTERSTITIAL PLAN - PLUMBING GRAVITY - NEW WORK - AREA B
PS122.D PARTIAL LEVEL 1 INTERSTITIAL PLAN - PLUMBING GRAVITY - NEW WORK - AREA B DEDUCT
PS132 PARTIAL LEVEL1 - ROOF PLUMBING GRAVITY PLAN - NEW WORK - AREA B
PP111 PARTIAL LEVEL 1 PLAN - PLUMBING PRESSURE - NEW WORK - AREA A
PP112 PARTIAL LEVEL 1 PLAN - PLUMBING PRESSURE - NEW WORK - AREA B
PP112.D PARTIAL LEVEL 1 PLAN - PLUMBING PRESSURE - NEW WORK - AREA B DEDUCT
PP121 PARTIAL LEVEL 1 INTERSTITIAL PLAN - PLUMBING PRESSURE - NEW WORK - AREA A
PP122 PARTIAL LEVEL 1 INTERSTITIAL PLAN - PLUMBING PRESSURE - NEW WORK - AREA B
PP122.D PARTIAL LEVEL 1 INTERSTITIAL PLAN - PLUMBING PRESSURE - NEW WORK - AREA B DEDUCT
PG111 PARTIAL LEVEL 1 PLAN - PLUMBING MED GAS - NEW WORK - AREA A
PG112 PARTIAL LEVEL 1 PLAN - PLUMBING MED GAS - NEW WORK - AREA B
PG112.D PARTIAL LEVEL 1 PLAN - PLUMBING MED GAS - NEW WORK - AREA B DEDUCT
PG121 PARTIAL LEVEL 1 INTERSTITIAL PLAN - MED GAS - AREA A
PG122 PARTIAL LEVEL 1 INTERSTITIAL PLAN - MED GAS - AREA B
PG122.D PARTIAL LEVEL 1 INTERSTITIAL PLAN - MED GAS - AREA B DEDUCT
P-501 PLUMBING DETAILS
P-502 PLUMBING DETAILS
P-601 PLUMBING ISOMETRICS
P-602 PLUMBING ISOMETRICS
P-603 PLUMBING ISOMETRICS
P-604 PLUMBING ISOMETRICS
P-605 PLUMBING ISOMETRICS
P-606 PLUMBING ISOMETRICS
P-801 PLUMBING SCHEDULES
524 Fernwood Drive, Altamonte Springs, Florida 32701 |www.rdcjpa.com| 800.362.1523 Revisions Date
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10 www.abovegroupinc.com COA/CA Lic. No. 31120
FULLY SPRINKLERED305 East Dr., Suite H, Melbourne, Florida 32904
PH: 321.345.9026
A u to d e s k D o c s
/F lo ri d a
O rl a n d o
V A
/0
V A
L a k e N o n a C a rd io lo g y
R
M
E P
F P
F A
T .r v t
/7
/2
:3
:2
A M
PC101
PLUMBING PHASING PLANS Create Cardiovascular Center at Lake Nona
Orlando, Florida
675-103
Kevin Glover - COR
03/07/2025 JMC AJZ
100% CONSTRUCTION
DOCUMENTS - BID SET
ALLEN D. LANTZ, P.E.
FL License #98984
CODED NOTES:
CONNECT NEW SANITARY PIPING INTO EXISTING UNDERSLAB SANITARY PIPING AT THIS LOCATION AS SHOWN ON PS101.1
PHASING NOTES
1. REFER TO ARCHITECTURAL PHASING PLANS ON GC101 AND GC102 FOR MORE INFORMATION.
FIRST FLOOR:
• INSTALL ALL UNDERGROUND SANITARY IN PHASE 1 AREA OF WORK AS SHOWN ON PS101 AND PS102.
• INSTALL ALL VENT, CW, HW, AND HWR PIPING SERVING NEW PLUMBING FIXTURES IN PHASE 1 AREA OF WORK.
INTERSTITIAL:
• INSTALL ALL VENT, CW, HW, AND HWR PIPING AND EXTEND DOWN TO FIRST FLOOR PLUMBING FIXTURES.
• CONNECT TO EXISTING O2, MV, MA, AND WAGD PIPING AND EXTEND NEW MAINS IN INTERSTITIAL AREA. PROVIDE
VALVES AND CAPS AT TAPS TO AREAS IN FUTURE PHASES.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10 www.abovegroupinc.com COA/CA Lic. No. 31120
FULLY SPRINKLERED305 East Dr., Suite H, Melbourne, Florida 32904
PH: 321.345.9026
A u to d e s k D o c s
/F lo ri d a
O rl a n d o
V A
/0
V A
L a k e N o n a C a rd io lo g y
R
M
E P
F P
F A
T .r v t
/7
/2
:3
:4
A M
PC102
PLUMBING PHASING PLANS Create Cardiovascular Center at Lake Nona
Orlando, Florida
675-103
Kevin Glover - COR
03/07/2025 JMC AJZ
100% CONSTRUCTION
DOCUMENTS - BID SET
ALLEN D. LANTZ, P.E.
FL License #98984
PHASING NOTES
1. REFER TO ARCHITECTURAL PHASING PLANS ON GC101 AND GC102 FOR MORE INFORMATION.
PHASE 2:
FIRST FLOOR:
• INSTALL ALL UNDERGROUND SANITARY PIPING IN PHASE 2 AREA OF WORK.
• INSTALL ALL VENT, CW, HW, AND HWR PIPING SERVING NEW PLUMBING FIXTURES.
INTERSTITIAL:
• INSTALL ALL VENT, CW, HW, AND HWR PIPING AND EXTEND DOWN TO FIRST FLOOR PLUMBING FIXTURES.
• CONNECT TO EXISTING O2, MV, MA, AND WAGD PIPING TAPS AND EXTEND TO SERVE ROOMS IN PHASE 2 AREA OF
WORK.
PHASE 3:
FIRST FLOOR:
• INSTALL ALL UNDERGROUND SANITARY PIPING IN PHASE 2 AREA OF WORK.
• INSTALL ALL VENT, CW, HW, AND HWR PIPING SERVING NEW PLUMBING FIXTURES.
INTERSTITIAL:
• INSTALL ALL VENT, CW, HW, AND HWR PIPING AND EXTEND DOWN TO FIRST FLOOR PLUMBING FIXTURES.
• CONNECT TO EXISTING O2, MV, MA, AND WAGD PIPING TAPS AND EXTEND TO SERVE ROOMS IN PHASE 2 AREA OF
WORK.
A.5
A.7
B.1
C.1
C.15
C.3
C.5
D.1
A.1
8.1 7.7 7.17.3 6.7 6.1 5.7 5.1 4.7
4.1
32.2
30.5
30.230
27.7
A732.532.4
J.12
RX 3"
RX 4"
RX 4"
M A
T C
H
LI
N E
R
E F
E R
T O
P
LA
N
/ P D
F O
R C
O N
T
IN
U A
T
IO
N
EX 8" ST UP
EX 15" ST U/G
EX 15" ST
RX 4"
RX 2"
RX 3" SAN U/G
RX 3" SAN U/G
EX 3" SAN U/G
UP TO EXISTING FCO
UP TO EXISTING FCO
RX 2" SAN U/G
EX INVERT ELEVATION -4'-6" AT THIS LOCATION.
COORDINATE WITH CIVIL FOR CONTINUATION.
LOCATION OF EXISTING PIPING IS PRESUMED
AND SHALL BE FULLY CONFIRMED PRIOR TO ANY
NEW WORK.
EX INVERT ELEVATION IS APPROXIMATELY -4'-8"
AT THIS LOCATION. COORDINATE WITH CIVIL FOR
CONTINUATION. LOCATION OF EXISTING PIPING
IS PRESUMED AND SHALL BE FULLY CONFIRMED
PRIOR TO ANY NEW WORK.
RX 8" SAN U/G
RX 4" SAN U/G
EX 3" SAN U/G
RX 4" SAN U/G
NO CONTINUATION
N O
C O
N T
IN
U
A T
IO
N
NO CONTINUATION
Area - BArea - A
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10 www.abovegroupinc.com COA/CA Lic. No. 31120
FULLY SPRINKLERED305 East Dr., Suite H, Melbourne, Florida 32904
PH: 321.345.9026
A u to d e s k D o c s
/F lo ri d a
O rl a n d o
V A
/0
V A
L a k e N o n a C a rd io lo g y
R
M
E P
F P
F A
T .r v t
/7
/2
:3
:4
A M
PD101
PARTIAL UNDERSLAB PLAN - PLUMBING
GRAVITY - DEMO - AREA A
Create Cardiovascular Center at Lake Nona
Orlando, Florida
675-103
Kevin Glover - COR
03/07/2025 JMC AJZ
100% CONSTRUCTION
DOCUMENTS - BID SET
ALLEN D. LANTZ, P.E.
FL License #98984
N 0 4' 8' 16' 24'
1/8" = 1'-0"
N 0 4' 8' 16' 24'
1/8" = 1'-0"
N 0 4' 8' 16' 24'
1/8" = 1'-0"
CODED NOTES:
DRAWING NOTES:
1. EXISTING PIPING SYSTEMS DRAWN ON PLANS ARE BASED ON LIMITED EXISTING DOCUMENTATION AND FIELD VERIFICATION. THE CONTRACTOR SHALL CONFIRM THE SIZE AND SYSTEM TYPE FOR PIPING LOCATED WITHIN AND ADJACENT TO THE PROJECT SCOPE BOUNDARY BEFORE FABRICATION OF ANY NEW PIPING SHOWN ON PLANS.
CONTRACTOR SHALL NOTIFY COR OF ANY DEVIATIONS.
REMOVE EXISTING SANITARY PIPING BACK TO MAIN.
EXISTING CONCRETE FLOOR SLAB TO BE REMOVED AND REPLACED IN THIS AREA TO ALLOW FOR MODIFICATION OF EXISTING UNDERSLAB SANITARY SEWER PIPING SYSTEM. REFER TO ARCHITECTURAL AND STRUCTURAL DRAWINGS FOR FLOOR SLAB SCOPE OF WORK. COORDINATE PIPING CONNECTIONS AND ACCESS AT EDGES OF WORK TO PERMIT PLUMBING NEW WORK TO
BE COMPLETED.
REMOVE EXISTING CONCRETE SLAB THIS AREA IN PREPARATION FOR NEW WORK CONNECTIONS. CLEAN AND INSPECT EXISTING PIPING LATERAL BACK TO MAIN. NOTIFY COR IF ANY CONDITIONS ARE PRESENT TO NOT PERMIT THE COMPLETION
OF NEW WORK SHOWN ON SHEETS PS101 AND PS102.
EXISTING 15" STORM TO REMAIN. PROTECT PIPING DURING ALL CONSTRUCTION ACTIVITIES.
EXISTING 15" STORM UP TO INTERSTITIAL SPACE. SEE SHEET PD121 FOR CONTINUATION.
EXISTING STRUCTURAL FOOTINGS SHOWN FOR COORDINATION ONLY. TYPICAL.
EXISTING PLUMBING FIXTURES IN THIS AREA SHALL REMAIN. COORDINATE SHUTDOWN TIMES WITH UNDERSLAB WORK TO
MINIMIZE DISRUPTION.
REMOVE EXISTING 2" SANITARY RISER UP. REFER TO PD111 FOR CONTINUATION.
1/8" = 1'-0"
1 PARTIAL UNDERSLAB PLUMBING GRAVITY PLAN - DEMOLITION - AREA A
N.T.S.
Key Plan - Area A
REFER TO ARCHITECTURAL
DRAWING AND SHEETS
PC101 AND PC102 FOR
PHASING INFORMATION.
B.1
C.1
C.15
C.3
C.5
D.1
A.1
3.74.1 3.1 2.7 2.1 1.7 1.1
B.5
A.9
RX 3"
EX 8" ST
EX. INVERT
ELEV. -2'-2"
M A
T C
H
LI
N E
R
E F
E R
T O
P
LA
N
/ P D
F O
R C
O N
T
IN
U A
T
IO
N
EX 8" ST UP
Area - BArea - A
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10 www.abovegroupinc.com COA/CA Lic. No. 31120
FULLY SPRINKLERED305 East Dr., Suite H, Melbourne, Florida 32904
PH: 321.345.9026
A u to d e s k D o c s
/F lo ri d a
O rl a n d o
V A
/0
V A
L a k e N o n a C a rd io lo g y
R
M
E P
F P
F A
T .r v t
/7
/2
:3
:5
A M
PD102
PARTIAL UNDERSLAB PLAN - PLUMBING
GRAVITY - DEMO - AREA B
Create Cardiovascular Center at Lake Nona
Orlando, Florida
675-103
Kevin Glover - COR
03/07/2025 JMC AJZ
100% CONSTRUCTION
DOCUMENTS - BID SET
ALLEN D. LANTZ, P.E.
FL License #98984
N 0 4' 8' 16' 24'
1/8" = 1'-0"
N 0 4' 8' 16' 24'
1/8" = 1'-0"
N 0 4' 8' 16' 24'
1/8" = 1'-0"
CODED NOTES:
DRAWING NOTES:
1. EXISTING PIPING SYSTEMS DRAWN ON PLANS ARE BASED ON LIMITED EXISTING DOCUMENTATION AND FIELD VERIFICATION. THE CONTRACTOR SHALL CONFIRM THE SIZE AND SYSTEM TYPE FOR PIPING LOCATED WITHIN AND ADJACENT TO THE PROJECT SCOPE BOUNDARY BEFORE FABRICATION OF ANY NEW PIPING SHOWN ON PLANS.
CONTRACTOR SHALL NOTIFY COR OF ANY DEVIATIONS.
REMOVE EXISTING SANITARY PIPING BACK TO MAIN. SANITARY PIPING SERVES STAIRWELL FCU(S) CONDENSATE DRAINAGE.
REMOVE PIPING TO ABOVE FLOOR. REFER TO PD112 FOR CONTINUATION.
EXISTING CONCRETE FLOOR SLAB TO BE REMOVED AND REPLACED IN THIS AREA TO ALLOW FOR MODIFICATION OF EXISTING AND NEW UNDERSLAB SANITARY SEWER PIPING SYSTEM. REFER TO ARCHITECTURAL AND STRUCTURAL DRAWINGS FOR FLOOR SLAB SCOPE OF WORK. COORDINATE PIPING CONNECTIONS AND ACCESS AT EDGES OF WORK TO PERMIT PLUMBING
NEW WORK TO BE COMPLETED.
1/8" = 1'-0"
1 PARTIAL UNDERSLAB PLUMBING GRAVITY PLAN - DEMOLITION - AREA B
N.T.S.
Key Plan - Area B
REFER TO ARCHITECTURAL
DRAWING AND SHEETS
PC101 AND PC102 FOR
PHASING INFORMATION.
B.1
C.1
C.15
C.3
C.5
D.1
A.1
8.1 7.7 7.17.3 6.7 6.1 5.7 5.1 4.7
4.1
32.2
30.5
30.2
27.7
A7
32.5 32.4
J.12
M A
T C
H
LI
N E
R
E F
E R
T O
P
LA
N
/ P D
F O
R C
O N
T
IN
U A
T
IO
N
Escort Services
1B703
Vre Office
1C902
Elevator
1BE01
Elevator
1BE02
Hac
1B604
Electric
1C102a
Job Lab
1C403
Storage
1C605
VRE File Room
1C804
VRE Office
1C603
VRE Office
1C904
VRE Office
1C903
VRE Office
1C905 VRE Office
1C907
VRE Office
1C909 VRE Office
1C911
VRE Office
1C908
VRE Office
1C910
Cubicles
1C602
Cubicles
1C606
Cubicles
1C802
Vre Supervisor
1C212
Interview
1C218
Vre Office
1C219
Interview
1C220
Public Tlt Male
1C287
Public Tlt Female
1C288
Office Of Decedent Affairs
1C289
Hearing Rm
1C290
Elevator
1C294
Elevator
1C295
Cubicles
1C345
Storage
1C348
Toilet-Staff
1C349
Toilet-Patient
1C350
Staff Lounge
1C351
Conference
1C352
Training
1C353
1C354
Testing
1C355
HAC
1C356
Closet
1C357
Closet
1C358
VRE Office
1C363
Waiting
1C375
EX FCO
EX 15" ST DOWNSPOUT
NOZZLE UP TO LOCATION
SHOWN ON PD121.
EX L EX U
EX WCEX WC
EX WC EX WC EX WC EX WC
EX L
EX MB
EX EWC
EX 12" ST UP/DN
EX 12" STO UP
EX U
EX 12" STO DOWNSPOUT
EX. INVERT ELEV. -4.50'
EX FCO
NO CONTINUATION
N O
C O
N T
IN
U
A T
IO
N
NO CONTINUATION
EX FCO
EX 15" ST UP
EX 8" SAN UP
RX FCO
EX 2" SAN UP/DN
Area - BArea - A
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10 www.abovegroupinc.com COA/CA Lic. No. 31120
FULLY SPRINKLERED305 East Dr., Suite H, Melbourne, Florida 32904
PH: 321.345.9026
A u to d e s k D o c s
/F lo ri d a
O rl a n d o
V A
/0
V A
L a k e N o n a C a rd io lo g y
R
M
E P
F P
F A
T .r v t
/7
/2
:3
:5
A M
PD111
PARTIAL LEVEL 1 PLAN - PLUMBING
GRAVITY - DEMO - AREA A
Create Cardiovascular Center at Lake Nona
Orlando, Florida
675-103
Kevin Glover - COR
03/07/2025 JMC AJZ
100% CONSTRUCTION
DOCUMENTS - BID SET
ALLEN D. LANTZ, P.E.
FL License #98984
N 0 4' 8' 16' 24'
1/8" = 1'-0"
N 0 4' 8' 16' 24'
1/8" = 1'-0"
N 0 4' 8' 16' 24'
1/8" = 1'-0"
1/8" = 1'-0"
1 PARTIAL LEVEL 1 PLUMBING GRAVITY PLAN - DEMOLITION - AREA A
CODED NOTES:
DRAWING NOTES:
1. EXISTING PIPING SYSTEMS DRAWN ON PLANS ARE BASED ON LIMITED EXISTING DOCUMENTATION AND FIELD VERIFICATION. THE CONTRACTOR SHALL CONFIRM THE SIZE AND SYSTEM TYPE FOR PIPING LOCATED WITHIN AND ADJACENT TO THE PROJECT SCOPE BOUNDARY BEFORE FABRICATION OF ANY NEW PIPING SHOWN ON PLANS.
CONTRACTOR SHALL NOTIFY COR OF ANY DEVIATIONS.
2. FIELD VERIFY ALL FIXTURES AND PIPING AFFECTED BY DEMOLITION.
3. CONTRACTOR SHALL COORDINATE ANY SYSTEM DOWNTIME WITH OWNER PRIOR TO START OF WORK.
REMOVE EXISTING PLUMBING FIXTURE, SANITARY PIPING, AND VENT PIPING BACK TO MAIN. CAP PIPING AT FITTING. 1
N.T.S.
Key Plan - Area A
REFER TO ARCHITECTURAL
DRAWING AND SHEETS
PC101 AND PC102 FOR
PHASING INFORMATION.
B.1
C.1
C.15
C.3
C.5
D.1
A.1
3.74.1 3.1 2.7 2.1 1.7 1.1
B.5
A.9
M A
T C
H
LI
N E
R
E F
E R
T O
P
LA
N
/ P D
F O
R C
O N
T
IN
U A
T
IO
N
Electric
1C924 Comm
1C926
Cubicles
1C125
Files
1C121a
Passage
1CC09a
Cubicles
1C921
Conference
1C339
Asst. Manager
1C340
Storage
1C341
EX ST FCO
EX 8" ST UP/DN EX 8" STO UP
RX FCO
EX 8" STO
DOWNSPOUT
Area - BArea - A
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10 www.abovegroupinc.com COA/CA Lic. No. 31120
FULLY SPRINKLERED305 East Dr., Suite H, Melbourne, Florida 32904
PH: 321.345.9026
A u to d e s k D o c s
/F lo ri d a
O rl a n d o
V A
/0
V A
L a k e N o n a C a rd io lo g y
R
M
E P
F P
F A
T .r v t
/7
/2
:3
:0
A M
PD112
PARTIAL LEVEL 1 PLAN - PLUMBING
GRAVITY - DEMO - AREA B
Create Cardiovascular Center at Lake Nona
Orlando, Florida
675-103
Kevin Glover - COR
03/07/2025 JMC AJZ
100% CONSTRUCTION
DOCUMENTS - BID SET
ALLEN D. LANTZ, P.E.
FL License #98984
N 0 4' 8' 16' 24'
1/8" = 1'-0"
N 0 4' 8' 16' 24'
1/8" = 1'-0"
N 0 4' 8' 16' 24'
1/8" = 1'-0"
1/8" = 1'-0"
1 PARTIAL LEVEL 1 PLUMBING GRAVITY PLAN - DEMOLITION - AREA B
CODED NOTES:
DRAWING NOTES:
1. EXISTING PIPING SYSTEMS DRAWN ON PLANS ARE BASED ON LIMITED EXISTING DOCUMENTATION AND FIELD VERIFICATION. THE CONTRACTOR SHALL CONFIRM THE SIZE AND SYSTEM TYPE FOR PIPING LOCATED WITHIN AND ADJACENT TO THE PROJECT SCOPE BOUNDARY BEFORE FABRICATION OF ANY NEW PIPING SHOWN ON PLANS.
CONTRACTOR SHALL NOTIFY COR OF ANY DEVIATIONS.
2. FIELD VERIFY ALL FIXTURES AND PIPING AFFECTED BY DEMOLITION.
3. CONTRACTOR SHALL COORDINATE ANY SYSTEM DOWNTIME WITH OWNER PRIOR TO START OF WORK.
REMOVE EXISTING SANITARY PIPING UP TO INTERSTITIAL LANDING ON STAIRWELL. SANITARY PIPING SERVES CONDENSATE
DRAINAGE FROM FCU'S IN STAIRWELL.
N.T.S.
Key Plan - Area B
REFER TO ARCHITECTURAL
DRAWING AND SHEETS
PC101 AND PC102 FOR
PHASING INFORMATION.
B.1
C.1
C.15
C.3
C.5
D.1
A.1
8.1 7.7 7.17.3 6.7 6.1 5.7 5.1 4.7
4.1
32.2
30.5
30.230
27.7
A732.532.4
J.12
M A
T C
H
LI
N E
R
E F
E R
T O
P
LA
N
/ P D
F O
R C
O N
T
IN
U A
T
IO
N
Escort Services
1B703
Vre Office
1C902
Elevator
1BE01
Elevator
1BE02
Hac
1B604
Electric
1C102a
Job Lab
1C403
Storage
1C605
VRE File Room
1C804
VRE Office
1C603
VRE Office
1C904
VRE Office
1C903
VRE Office
1C905 VRE Office
1C907
VRE Office
1C909 VRE Office
1C911
VRE Office
1C908
VRE Office
1C910
Cubicles
1C602
Cubicles
1C606
Cubicles
1C802
Vre Supervisor
1C212
Interview
1C218
Vre Office
1C219
Interview
1C220
Public Tlt Male
1C287
Public Tlt Female
1C288
Office Of Decedent Affairs
1C289
Hearing Rm
1C290
Elevator
1C294
Elevator
1C295
Cubicles
1C345
Storage
1C348
Toilet-Staff
1C349
Toilet-Patient
1C350
Staff Lounge
1C351
Conference
1C352
Training
1C353
1C354
Testing
1C355
HAC
1C356
Closet
1C357
Closet
1C358
VRE Office
1C363
Waiting
1C375
EX L EX U
EX WCEX WC
EX WC EX WC EX WC EX WC
EX L
EX MB
EX EWC
EX U
RX 1/2" CW AND 1/2"
HW UP.
RX 1/2" CW AND 1/2" HW UP.
RX 1/2" CW AND
1/2" HW UP.RX 1" CW UP.
RX 1" CW UP.
RX 1/2" CW AND
1/2" HW UP.
NO CONTINUATION
N O
C O
N T
IN
U
A T
IO
N
NO CONTINUATION
Area - BArea - A
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10 www.abovegroupinc.com COA/CA Lic. No. 31120
FULLY SPRINKLERED305 East Dr., Suite H, Melbourne, Florida 32904
PH: 321.345.9026
A u to d e s k D o c s
/F lo ri d a
O rl a n d o
V A
/0
V A
L a k e N o n a C a rd io lo g y
R
M
E P
F P
F A
T .r v t
/7
/2
:3
:0
A M
PD113
PARTIAL LEVEL 1 PLAN - PLUMBING
PRESSURE - DEMO - AREA A
Create Cardiovascular Center at Lake Nona
Orlando, Florida
675-103
Kevin Glover - COR
03/07/2025 JMC AJZ
100% CONSTRUCTION
DOCUMENTS - BID SET
ALLEN D. LANTZ, P.E.
FL License #98984
N 0 4' 8' 16' 24'
1/8" = 1'-0"
N 0 4' 8' 16' 24'
1/8" = 1'-0"
N 0 4' 8' 16' 24'
1/8" = 1'-0"
1/8" = 1'-0"
1 PARTIAL LEVEL 1 PLUMBING PRESSURE PLAN - DEMOLITION - AREA A
CODED NOTES:
DRAWING NOTES:
1. EXISTING PIPING SYSTEMS DRAWN ON PLANS ARE BASED ON LIMITED EXISTING DOCUMENTATION AND FIELD VERIFICATION. THE CONTRACTOR SHALL CONFIRM THE SIZE AND SYSTEM TYPE FOR PIPING LOCATED WITHIN AND ADJACENT TO THE PROJECT SCOPE BOUNDARY BEFORE FABRICATION OF ANY NEW PIPING SHOWN ON PLANS.
CONTRACTOR SHALL NOTIFY COR OF ANY DEVIATIONS.
2. FIELD VERIFY ALL FIXTURES AND PIPING AFFECTED BY DEMOLITION.
3. CONTRACTOR SHALL COORDINATE ANY SYSTEM DOWNTIME WITH COR PRIOR TO START OF WORK.
REMOVE EXISTING PLUMBING FIXTURE, CW, HW, & HWR PIPING BACK TO EXISTING MAIN LOCATED IN FIRST FLOOR
INTERSTITIAL SPACE.
N.T.S.
Key Plan - Area A
REFER TO ARCHITECTURAL
DRAWING AND SHEETS
PC101 AND PC102 FOR
PHASING INFORMATION.
B.1
C.1
C.15
C.3
C.5
D.1
A.1
3.74.1 3.1 2.7 2.1 1.7 1.1
B.5
A.9
Electric
1C924 Comm
1C926
Cubicles
1C125
Files
1C121a
Passage
1CC09a
Cubicles
1C921
Conference
1C339
Asst. Manager
1C340
Storage
1C341
Equipment
1C346
M A
T C
H
LI
N E
R
E F
E R
T O
P
LA
N
/ P D
F O
R C
O N
T
IN
U A
T
IO
N
EX HB
EX HB
EX 1/2" CW UP
EX 1/2" CW UP
Area - BArea - A
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10 www.abovegroupinc.com COA/CA Lic. No. 31120
FULLY SPRINKLERED305 East Dr., Suite H, Melbourne, Florida 32904
PH: 321.345.9026
A u to d e s k D o c s
/F lo ri d a
O rl a n d o
V A
/0
V A
L a k e N o n a C a rd io lo g y
R
M
E P
F P
F A
T .r v t
/7
/2
:3
:0
A M
PD114
PARTIAL LEVEL 1 PLAN - PLUMBING
PRESSURE - DEMO - AREA B
Create Cardiovascular Center at Lake Nona
Orlando, Florida
675-103
Kevin Glover - COR
03/07/2025 JMC AJZ
100% CONSTRUCTION
DOCUMENTS - BID SET
ALLEN D. LANTZ, P.E.
FL License #98984
N 0 4' 8' 16' 24'
1/8" = 1'-0"
N 0 4' 8' 16' 24'
1/8" = 1'-0"
N 0 4' 8' 16' 24'
1/8" = 1'-0"
1/8" = 1'-0"
1 PARTIAL LEVEL 1 PLUMBING PRESSURE PLAN - DEMOLITION - AREA B
DRAWING NOTES:
1. EXISTING PIPING SYSTEMS DRAWN ON PLANS ARE BASED ON LIMITED EXISTING DOCUMENTATION AND FIELD VERIFICATION. THE CONTRACTOR SHALL CONFIRM THE SIZE AND SYSTEM TYPE FOR PIPING LOCATED WITHIN AND ADJACENT TO THE PROJECT SCOPE BOUNDARY BEFORE FABRICATION OF ANY NEW PIPING SHOWN ON PLANS.
CONTRACTOR SHALL NOTIFY COR OF ANY DEVIATIONS.
2. FIELD VERIFY ALL FIXTURES AND PIPING AFFECTED BY DEMOLITION.
N.T.S.
Key Plan - Area B
REFER TO ARCHITECTURAL
DRAWING AND SHEETS
PC101 AND PC102 FOR
PHASING INFORMATION.
B.1
C.1
C.15
C.3
C.5
D.1
A.1
8.1 7.7 7.17.3 6.7 6.1 5.7 5.1 4.7
4.1
32.2
30.5
30.2
27.7
A7
32.5 32.4
J.12
EX 4" V
RX 2" V DN
RX 2" V
EX 15" STO DN
EX 12" STO UP
21,575 SQFT
1,015 GPM
EX 12" STO UP
23,176 SQFT
1,090 GPM
EX 12" ST UP
23,176 SQFT
1,090 GPM
EX 12" ST UP
21,575 SQFT
1,015 GPM
EX 12" ST
EX 12" ST
EX 15" ST DN
44751 SQFT
2105 GPM
EX 15" ST
EX 15" STO
EX 12" STO
EX 1 1/2" V DN RX 1 1/2" V RX 2" V DN
RX 1 1/2" V DN
RX 2" V
RX 1 1/2" V DN
EX 12" ST
EX 12" STO
EX 6" ST
EX 6" STO
EX 4" STO
EX 4" ST
EX 6" ST
EX 6" STO
EX 10" ST
EX 10" STO
EX 8" STO
EX 8" ST
EX 6" ST
EX 6" STO
EX 4" ST
EX 4" STO
EX 8" ST
EX 8" STO
EX 6" STO
EX 4" ST
EX 4" STO
EX 4" ST
EX 4" STO
EX 12" STO DN
24,110 SQFT
1,135 GPM
EX 12" ST DN
24,110 SQFT
1,135 GPM
EX 6" STO UP
EX 6" ST UP
EX 6" STO UP
EX 6" ST UP
EX 4" STO UP
EX 4" ST UP
EX 4" STO UP
EX 4" ST UP
M A
T C
H
LI
N E
R
E F
E R
T O
P
LA
N
/ P D
F O
R C
O N
T
IN
U A
T
IO
N
EX 4" STO UP
EX 4" ST UP
EX 4" STO UP
EX 4" ST UP
EX 4" V UP
EX 4" V
NO CONTINUATION
N O
C O
N T
IN
U
A T
IO
N
NO CONTINUATION
Area - BArea - A
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10 www.abovegroupinc.com COA/CA Lic. No. 31120
FULLY SPRINKLERED305 East Dr., Suite H, Melbourne, Florida 32904
PH: 321.345.9026
A u to d e s k D o c s
/F lo ri d a
O rl a n d o
V A
/0
V A
L a k e N o n a C a rd io lo g y
R
M
E P
F P
F A
T .r v t
/7
/2
:3
:1
A M
PD121
PARTIAL LEVEL 1 INTERSTITIAL PLAN -
PLUMBING GRAVITY - DEMO - AREA A
Create Cardiovascular Center at Lake Nona
Orlando, Florida
675-103
Kevin Glover - COR
03/07/2025 JMC AJZ
100% CONSTRUCTION
DOCUMENTS - BID SET
ALLEN D. LANTZ, P.E.
FL License #98984
N 0 4' 8' 16' 24'
1/8" = 1'-0"
N 0 4' 8' 16' 24'
1/8" = 1'-0"
N 0 4' 8' 16' 24'
1/8" = 1'-0"
DRAWING NOTES:
1. EXISTING PIPING SYSTEMS DRAWN ON PLANS ARE BASED ON LIMITED EXISTING DOCUMENTATION AND FIELD VERIFICATION. THE CONTRACTOR SHALL CONFIRM THE SIZE AND SYSTEM TYPE FOR PIPING LOCATED WITHIN AND ADJACENT TO THE PROJECT SCOPE BOUNDARY BEFORE FABRICATION OF ANY NEW PIPING SHOWN ON PLANS.
CONTRACTOR SHALL NOTIFY COR OF ANY DEVIATIONS.
2. FIELD VERIFY ALL FIXTURES AND PIPING AFFECTED BY DEMOLITION.
1/8" = 1'-0"
1 PARTIAL LEVEL 1 INTERSTITIAL PLUMBING GRAVITY PLAN - DEMOLITION - AREA A
N.T.S.
Key Plan - Area A
REFER TO ARCHITECTURAL
DRAWING AND SHEETS
PC101 AND PC102 FOR
PHASING INFORMATION.
B.1
C.1
C.15
C.3
C.5
D.1
A.1
3.74.1 3.1 2.7 2.1 1.7 1.1
B.5
A.9
EX 8" STO
M A
T C
H
LI
N E
R
E F
E R
T O
P
LA
N
/ P D
F O
R C
O N
T
IN
U A
T
IO
N EX 6" STO UP
EX 6" ST UP
EX 6" STO UP
EX 6" ST UP
EX 6" STO UP
EX 6" ST UP
EX 8" ST DN
5,787 SQFT
270 GPM
EX 8" STO DN
5,787 SQFT
270 GPM
EX 6" ST
EX 6" STO
EX 6" ST
EX 6" ST
EX 8" ST
RX 3" ST
Area - BArea - A
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10 www.abovegroupinc.com COA/CA Lic. No. 31120
FULLY SPRINKLERED305 East Dr., Suite H, Melbourne, Florida 32904
PH: 321.345.9026
A u to d e s k D o c s
/F lo ri d a
O rl a n d o
V A
/0
V A
L a k e N o n a C a rd io lo g y
R
M
E P
F P
F A
T .r v t
/7
/2
:3
:1
A M
PD122
PARTIAL LEVEL 1 INTERSTITIAL PLAN -
PLUMBING GRAVITY - DEMO - AREA B
Create Cardiovascular Center at Lake Nona
Orlando, Florida
675-103
Kevin Glover - COR
03/07/2025 JMC AJZ
100% CONSTRUCTION
DOCUMENTS - BID SET
ALLEN D. LANTZ, P.E.
FL License #98984
N 0 4' 8' 16' 24'
1/8" = 1'-0"
N 0 4' 8' 16' 24'
1/8" = 1'-0"
N 0 4' 8' 16' 24'
1/8" = 1'-0"
CODED NOTES:
DRAWING NOTES:
1. EXISTING PIPING SYSTEMS DRAWN ON PLANS ARE BASED ON LIMITED EXISTING DOCUMENTATION AND FIELD VERIFICATION. THE CONTRACTOR SHALL CONFIRM THE SIZE AND SYSTEM TYPE FOR PIPING LOCATED WITHIN AND ADJACENT TO THE PROJECT SCOPE BOUNDARY BEFORE FABRICATION OF ANY NEW PIPING SHOWN ON PLANS.
CONTRACTOR SHALL NOTIFY COR OF ANY DEVIATIONS.
2. FIELD VERIFY ALL FIXTURES AND PIPING AFFECTED BY DEMOLITION.
REMOVE EXISTING SANITARY PIPING AS INDICATED. SANITARY PIPING SERVES CONDENSATE DRAINAGE FROM FCU'S IN
STAIRWELL.
1/8" = 1'-0"
1 PARTIAL LEVEL 1 INTERSTITIAL PLUMBING PLAN - DEMOLITION - AREA B
N.T.S.
Key Plan - Area B
REFER TO ARCHITECTURAL
DRAWING AND SHEETS
PC101 AND PC102 FOR
PHASING INFORMATION.
B.1
C.1
C.15
C.3
C.5
D.1
A.1
8.1 7.7 7.17.3 6.7 6.1 5.7 5.1 4.7
4.1
32.2
30.5
30.2
27.7
A7
32.5 32.4
J.12
RX 1/2" HW
RX 1/2" CW
RX 2 1/2" CW
RX 1" HW
EX 1 1/4" HWR
M A
T C
H
LI
N E
R
E F
E R
T O
P
LA
N
/ P D
F O
R C
O N
T
IN
U A
T
IO
N
RX 1/2" HWR
RX 1/2" HWR
EX 3/4" HW
EX 3/4" CW
EX 1" CW
EX 2 1/2" CW
EX 1 1/4" HW
EX 3/4" CW
EX 2 1/2" CW
EX 1 1/4" HW
EX 4" CW
EX 3" HW
EX 2" HW
EX 2 1/2" CW
EX 4" CW
EX 2" HW
EX 3" HW
EX 1 1/4" HWR
EX 4" CW
RX 1/2" HWR
RX 2" CW
RX 1/2" HW
RX 1" CW
RX 1/2" CW
RX 1/2" HW
RX 1/2" CW
RX 1/2" HW
RX 1/2" HWR
RX 1/2" HW
RX 2" CW
1 2
1 2
3 3
EX 3/4" CW
EX 4" HW
EX 2" HWR
EX 6" CW
EX 3" HW
EX 2" HWR
EX 6" CW
EX 3" HW
EX 2" HWR
EX 6" CW
NO CONTINUATION
N O
C O
N T
IN
U
A T
IO
N
NO CONTINUATION
Area - BArea - A
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10 www.abovegroupinc.com COA/CA Lic. No. 31120
FULLY SPRINKLERED305 East Dr., Suite H, Melbourne, Florida 32904
PH: 321.345.9026
A u to d e s k D o c s
/F lo ri d a
O rl a n d o
V A
/0
V A
L a k e N o n a C a rd io lo g y
R
M
E P
F P
F A
T .r v t
/7
/2
:3
:2
A M
PD123
PARTIAL LEVEL 1 INTERSTITIAL PLAN -
PLUMBING PRESSURE - DEMO - AREA A
Create Cardiovascular Center at Lake Nona
Orlando, Florida
675-103
Kevin Glover - COR
03/07/2025 JMC AJZ
100% CONSTRUCTION
DOCUMENTS - BID SET
ALLEN D. LANTZ, P.E.
FL License #98984
N 0 4' 8' 16' 24'
1/8" = 1'-0"
N 0 4' 8' 16' 24'
1/8" = 1'-0"
N 0 4' 8' 16' 24'
1/8" = 1'-0"
CODED NOTES:
DRAWING NOTES:
1. EXISTING PIPING SYSTEMS DRAWN ON PLANS ARE BASED ON LIMITED EXISTING DOCUMENTATION AND FIELD VERIFICATION. THE CONTRACTOR SHALL CONFIRM THE SIZE AND SYSTEM TYPE FOR PIPING LOCATED WITHIN AND ADJACENT TO THE PROJECT SCOPE BOUNDARY BEFORE FABRICATION OF ANY NEW PIPING SHOWN ON PLANS.
CONTRACTOR SHALL NOTIFY COR OF ANY DEVIATIONS.
2. FIELD VERIFY ALL FIXTURES AND PIPING AFFECTED BY DEMOLITION.
EXISTING COLD WATER PIPING DOWN TO EXISTING FIXTURES TO REMAIN.
EXISTING HOT WATER PIPING DOWN TO EXISTING FIXTURES TO REMAIN.
REMOVE EXISTING COLD, HOT, AND HOT WATER RETURN PIPING BACK TO LOCATION SHOWN AND CAP.
1/8" = 1'-0"
1 PARTIAL LEVEL 1 INTERSTITIAL PLUMBING PRESSURE PLAN - DEMOLITION - AREA A
N.T.S.
Key Plan - Area A
REFER TO ARCHITECTURAL
DRAWING AND SHEETS
PC101 AND PC102 FOR
PHASING INFORMATION.
B.1
C.1
C.15
C.3
C.5
D.1
A.1
3.74.1 3.1 2.7 2.1 1.7 1.1
B.5
A.9
EX 1/2" CW
EX 1/2" CW
EX 1/2" CW
M A
T C
H
LI
N E
R
E F
E R
T O
P
LA
N
/ P D
F O
R C
O N
T
IN
U A
T
IO
N
EX 1/2" CW DN
EX 1/2" CW DN
Area - BArea - A
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10 www.abovegroupinc.com COA/CA Lic. No. 31120
FULLY SPRINKLERED305 East Dr., Suite H, Melbourne, Florida 32904
PH: 321.345.9026
A u to d e s k D o c s
/F lo ri d a
O rl a n d o
V A
/0
V A
L a k e N o n a C a rd io lo g y
R
M
E P
F P
F A
T .r v t
/7
/2
:3
:2
A M
PD124
PARTIAL LEVEL 1 INTERSTITIAL PLAN -
PLUMBING PRESSURE - DEMO - AREA B
Create Cardiovascular Center at Lake Nona
Orlando, Florida
675-103
Kevin Glover - COR
03/07/2025 JMC AJZ
100% CONSTRUCTION
DOCUMENTS - BID SET
ALLEN D. LANTZ, P.E.
FL License #98984
N 0 4' 8' 16' 24'
1/8" = 1'-0"
N 0 4' 8' 16' 24'
1/8" = 1'-0"
N 0 4' 8' 16' 24'
1/8" = 1'-0"
DRAWING NOTES:
1. EXISTING PIPING SYSTEMS DRAWN ON PLANS ARE BASED ON LIMITED EXISTING DOCUMENTATION AND FIELD VERIFICATION. THE CONTRACTOR SHALL CONFIRM THE SIZE AND SYSTEM TYPE FOR PIPING LOCATED WITHIN AND ADJACENT TO THE PROJECT SCOPE BOUNDARY BEFORE FABRICATION OF ANY NEW PIPING SHOWN ON PLANS.
CONTRACTOR SHALL NOTIFY COR OF ANY DEVIATIONS.
2. FIELD VERIFY ALL FIXTURES AND PIPING AFFECTED BY DEMOLITION.
1/8" = 1'-0"
1 PARTIAL LEVEL 1 INTERSTITIAL PLUMBING PRESSURE PLAN - DEMOLITION - AREA B
N.T.S.
Key Plan - Area B
REFER TO ARCHITECTURAL
DRAWING AND SHEETS
PC101 AND PC102 FOR
PHASING INFORMATION.
B.1
C.1
C.15
C.3
C.5
D.1
A.1
8.1 7.7 7.17.3 6.7 6.1 5.7 5.1 4.7
4.1
32.2
30.5
30.2
27.7
A7
32.5 32.4
J.12
M A
T C
H
LI
N E
R
E F
E R
T O
P
LA
N
/ P S
F O
R C
O N
T
IN
U A
T
IO
N
EX 8" SAN INVERT ELEVATION -4'-6" AT THIS
LOCATION. COORDINATE WITH CIVIL FOR
CONTINUATION. LOCATION OF EXISTING PIPING
IS PRESUMED AND SHALL BE FULLY CONFIRMED
PRIOR TO ANY NEW WORK.
6" ST UP
2" SAN UP
2" SAN UP
2" SAN UP
2" SAN UP 2" SAN UP
2" SAN UP
2" SAN UP
2" SAN UP 2" SAN UP
2" SAN UP 2" SAN UP 2" SAN UP 2" SAN UP 2" SAN UP 2" SAN UP
2" SAN UP
2" SAN UP 2" SAN UP
2" SAN UP
2" SAN UP
2" SAN UP
2" SAN UP
2" SAN UP
8" ST UP
4" SAN UP TO
FCO
4" SAN UP
4" SAN UP TO
FCO
4" SAN UP
4" SAN UP
3" SAN UP TO
FCO
4" SAN UP
EX 4" SAN UP
TO FCO
BACKWATER VALVE
2" SAN UP
INV. ELEV -3'-7"
INV. ELEV -3'-0"
INV. ELEV -1'-6"
2" SAN UP
EX 8" SAN INVERT ELEVATION IS
APPROXIMATELY -4'-8" AT THIS LOCATION.
COORDINATE WITH CIVIL FOR CONTINUATION.
LOCATION OF EXISTING PIPING IS PRESUMED
AND SHALL BE FULLY CONFIRMED PRIOR TO ANY
NEW WORK.
UP TO EXISTING FCO
3" SAN3" SAN UP TO
FCO
3" SAN
EX 4" SAN
INV. ELEV -3'-8"
INV. ELEV -3'-0"
INV. ELEV -2'-9"
INV. ELEV -2'-0"
2" SAN
2" SAN
4" SAN
4" SAN4" SAN
EX 4" SAN
EX 3" SAN
EX 4" SAN
EX 8" SAN
EX 8" SAN EX 8" SAN
EX 8" SAN
4" SAN
3" SAN
3" SAN
3" SAN
4" SAN
12" ST UP
4" SAN
2" SAN UP
EX 15" ST
EX 8" SAN
EX 15" ST INVERT ELEVATION IS
APPROXIMATELY -2'-7" AT THIS LOCATION.
COORDINATE WITH CIVIL FOR CONTINUATION.
LOCATION OF EXISTING PIPING IS PRESUMED
AND SHALL BE FULLY CONFIRMED PRIOR TO ANY
NEW WORK.
EX 12" ST INVERT ELEVATION IS
APPROXIMATELY -4'-6" AT THIS LOCATION.
COORDINATE WITH CIVIL FOR CONTINUATION.
LOCATION OF EXISTING PIPING IS PRESUMED
AND SHALL BE FULLY CONFIRMED PRIOR TO ANY
NEW WORK.
2" SAN
3" SAN UP
TO FCO
EX 2" SAN UP
2" SAN UP
3 INV. ELEV -3'-7"
INV. ELEV -1'-6"
2" SAN UP
3" SAN UP
TO FCO
6" ST
ST INV. ELEV. = -3'-0"
SEE CIVIL FOR CONTINUATION.
NO CONTINUATION
N O
C O
N T
IN
U
A T
IO
N
NO CONTINUATION
TWO-WAY COTG
3" V UP
Area - BArea - A
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10 www.abovegroupinc.com COA/CA Lic. No. 31120
FULLY SPRINKLERED305 East Dr., Suite H, Melbourne, Florida 32904
PH: 321.345.9026
A u to d e s k D o c s
/F lo ri d a
O rl a n d o
V A
/0
V A
L a k e N o n a C a rd io lo g y
R
M
E P
F P
F A
T .r v t
/7
/2
:3
:2
A M
PS101
PARTIAL UNDERSLAB PLAN - PLUMB.
GRAVITY - NEW WORK - AREA A
Create Cardiovascular Center at Lake Nona
Orlando, Florida
675-103
Kevin Glover - COR
03/07/2025 JMC AJZ
100% CONSTRUCTION
DOCUMENTS - BID SET
ALLEN D. LANTZ, P.E.
FL License #98984
N 0 4' 8' 16' 24'
1/8" = 1'-0"
N 0 4' 8' 16' 24'
1/8" = 1'-0"
N 0 4' 8' 16' 24'
1/8" = 1'-0"
1/8" = 1'-0"
1 PARTIAL UNDERSLAB PLUMBING GRAVITY PLAN - NEW WORK - AREA A
DRAWING NOTES:
1. MODIFY EXISTING PIPING AT POINTS OF CONNECTION INDICATED TO FACILITATE NEW PIPING CONNECTION AND
INSTALLATION AS REQUIRED.
2. CONTRACTOR SHALL COORDINATE ANY SYSTEM DOWNTIME WITH OWNER PRIOR TO START OF WORK.
CODED NOTES:
EXISTING 8" SANITARY RISER UP TO FLOORS ABOVE TO REMAIN.
EXISTING 15" STORM RISER UP TO FLOORS ABOVE TO REMAIN.
OFFSET SANITARY PIPING UP UTILIZING 1/16TH BENDS TO THE INVERT ELEVATIONS SHOWN TO PROVIDE CLEARANCE AND
NECESSARY SOIL COVER ABOVE FOOTING FOR PROPER COMPACTION.
OFFSET SANITARY PIPING UP UTILIZING 1/8TH BENDS TO THE INVERT ELEVATION SHOWN TO PROVIDE CLEARANCE AND
NECESSARY SOIL COVER ABOVE FOOTING FOR PROPER COMPACTION.
SANITARY PIPING TO ROUTE OFF TOP OF EX 8" MAIN TO ABOVE THE EX STRUCTURAL FOOTING TO PROVIDE CLEARANCE AND
NECESSARY SOIL COVER ABOVE FOOTING FOR PROPER COMPACTION.
ROUTE 2" SANITARY PIPING ABOVE EXISTING FOOTING AND CONNECT INTO TOP OF 3" SANITARY BRANCH AS SHOWN.
EXISTING CONCRETE FLOOR SLAB TO BE REMOVED AND REPLACED IN THIS AREA TO ALLOW FOR MODIFICATION OF EXISTING UNDERSLAB SANITARY SEWER PIPING SYSTEM. REFER TO ARCHITECTURAL AND STRUCTURAL DRAWINGS FOR FLOOR SLAB SCOPE OF WORK. COORDINATE PIPING CONNECTIONS AND ACCESS AT EDGES OF WORK TO PERMIT PLUMBING NEW WORK
TO BE COMPLETED.
2" SANITARY PIPING ROUTED ABOVE TOF AND BETWEEN EXISTING COLUMNS. COORDINATE FULLY WITH STRUCTURAL.
N.T.S.
Key Plan - Area A
REFER TO ARCHITECTURAL
DRAWING AND SHEETS
PC101 AND PC102 FOR
PHASING INFORMATION.
B.1
C.1
C.15
C.3
C.5
D.1
A.1
3.74.1 3.1 2.7 2.1 1.7 1.1
B.5
A.9
M A
T C
H
LI
N E
R
E F
E R
T O
P
LA
N
/ P S
F O
R C
O N
T
IN
U A
T
IO
N
8" ST
-2'-6" INV
EX 8" ST
2" SAN UP
2" SAN UP
2" SAN UP
2" SAN UP2" SAN UP
2" SAN UP
2" SAN UP2" SAN UP
2" SAN UP
2" SAN UP
2" SAN UP
4" SAN UP
4" SAN UP
4" SAN UP TO
FCO
4" SAN UP
4" SAN UP
3" SAN UP TO
FCO
3" SAN UP TO
FCO
3" SAN UP
3" SAN UP
3" V UP
3" V UP
2" SAN UP
2" V UP
EX 8" ST UP
2" SAN UP
1 1/2" SAN UP
3" SAN UP TO
WCO
4" SAN UP TO
FCO
INV. ELEV -2'-10"
INV. ELEV -2'-0"
INV. ELEV -2'-7"
INV. ELEV -1'-11"
2" SAN UP
2" V UP
3" SAN
4" SAN
4" SAN
4" SAN
4" SAN
4" SAN
4" SAN
2" SAN
2" V UP
2" SAN UP
2" SAN UP
2" V UP
3" SAN UP
4" SAN UP TO FCO
3" SAN
2" V UP
3" SAN UP
BACKWATER VALVE
Area - BArea - A
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10 www.abovegroupinc.com COA/CA Lic. No. 31120
FULLY SPRINKLERED305 East Dr., Suite H, Melbourne, Florida 32904
PH: 321.345.9026
A u to d e s k D o c s
/F lo ri d a
O rl a n d o
V A
/0
V A
L a k e N o n a C a rd io lo g y
R
M
E P
F P
F A
T .r v t
/7
/2
:3
:3
A M
PS102
PARTIAL UNDERSLAB PLAN - PLUMB.
GRAVITY - NEW WORK - AREA B
Create Cardiovascular Center at Lake Nona
Orlando, Florida
675-103
Kevin Glover - COR
03/07/2025 JMC AJZ
100% CONSTRUCTION
DOCUMENTS - BID SET
ALLEN D. LANTZ, P.E.
FL License #98984
N 0 4' 8' 16' 24'
1/8" = 1'-0"
N 0 4' 8' 16' 24'
1/8" = 1'-0"
N 0 4' 8' 16' 24'
1/8" = 1'-0"
1/8" = 1'-0"
1 PARTIAL UNDERSLAB PLUMBING GRAVITY PLAN - NEW WORK - AREA B
DRAWING NOTES:
1. MODIFY EXISTING PIPING AT POINTS OF CONNECTION INDICATED TO FACILITATE NEW PIPING CONNECTION AND
INSTALLATION.
2. CONTRACTOR SHALL COORDINATE ANY SYSTEM DOWNTIME WITH OWNER PRIOR TO START OF WORK.
CODED NOTES:
EXTEND 6" ST AND CONNECT INTO EXISTING STORM SYSTEM. REFER TO CIVIL DRAWINGS FOR CONTINUATION.
ROUTE SANITARY PIPING OFF TOP OF SANITARY MAIN PIPING AND OVER TO FIXTURES AS SHOWN ABOVE FOOTINGS.
PROVIDE CLEARANCE AND NECESSARY SOIL COVER ABOVE FOOTING FOR PROPER COMPACTION.
SANITARY PIPING IS ROUTED ABOVE STRUCTURAL FOOTINGS. SEE STRUCTURAL FOR TOF. PROVIDE CLEARANCE AND
NECESSARY SOIL COVER ABOVE FOOTING FOR PROPER COMPACTION.
OFFSET SANITARY PIPING HORIZONTALLY AS SHOWN UNDERSLAB TO AVOID EXISTING STRUCTURAL FOOTINGS.
OFFSET SANITARY PIPING UP UTILIZING 1/16TH BENDS TO THE INVERT ELEVATIONS SHOWN TO PROVIDE PROPER DEPTH
FROM FIXTURE OUTLETS TO TRAP WEIR.
EXISTING CONCRETE FLOOR SLAB TO BE REMOVED AND REPLACED IN THIS AREA TO ALLOW FOR MODIFICATION OF EXISTING UNDERSLAB SANITARY SEWER PIPING SYSTEM. REFER TO ARCHITECTURAL AND STRUCTURAL DRAWINGS FOR FLOOR SLAB SCOPE OF WORK. COORDINATE PIPING CONNECTIONS AND ACCESS AT EDGES OF WORK TO PERMIT PLUMBING NEW WORK
TO BE COMPLETED.
N.T.S.
Key Plan - Area B
REFER TO ARCHITECTURAL
DRAWING AND SHEETS
PC101 AND PC102 FOR
PHASING INFORMATION.
B.1
C.1
C.15
C.3
C.5
D.1
A.1
8.1 7.7 7.17.3 6.7 6.1 5.7 5.1 4.7
4.1
32.2
30.5
30.2
27.7
A7
32.5 32.4
J.12
P-418
P-418 P-418
P-418
P-101
P-114
P-114
P-101
P-528
P-404
P-404
P-404
P-404P-404
P-404P-404
P-404
P-404
P-404
P-404
P-404
P-404
P-404P-404P-404P-404P-404P-404P-404P-404
P-404
M A
T C
H
LI
N E
R
E F
E R
T O
P
LA
N
/ P S
F O
R C
O N
T
IN
U A
T
IO
N
4" FCO
WCO
3" FCO 4" FCO
3" FCO
PROVIDERS
1C171
DEVICE CLINIC
1C131
STRESS TEST
1C132
HOLTER
1C135
TECH SUPERVISOR
1C133
ECHO
1C136
ECHO
1C137
ECHO
1C138
ECHO
1C139
INPATIENT HOLDING
1C130
CORRIDOR-1
1CC04-1ECG
1C128
ECG
1C129
CLEAN
1C126
STAFF
TOILET
1C125
ECHO
1C127
CORRIDOR
1CC05
ECHO
1C140
STAFF LOUNGE
1C141
STAFF
TOILET
1C142
CARDIO CHIEF
1C145
NON-INV LEAD
1C146
EP LEAD
1C164
CVT
1C163
ASSIST. NURSE MANAGER
1C165
PATIENT TOILET
1C143
EXAM
1C117
EXAM
1C118
EXAM
1C119
EXAM
1C120
EXAM
1C121
EXAM
1C122
EXAM
1C123
EXAM
1C124
TOUCHDOWN WORKSTATION
1C116
EXAM
1C106
EXAM
1C110
EXAM
1C109
PATIENT
TOILET
1C108
CORRIDOR
1CC02
FELLOWS
1C103
WAITING
1C101
ELECTRIC
1C102C
Elevator
1BE04
Space
1BC10
PROVIDERS
1C104
CONFERENCE
1C105
EXAM
1C111
EXAM
1C112
CORRIDOR
1CC06
EXAM
1C114
CORRIDOR
1CC07
BIOMED
1C144
EX FCO
444444
4 4
2" V
6" STO DN TO
DOWNSPOUT. REFER
TO DETAIL
4" ST4" ST 6" ST
4" STO
CO
EX UEX L
EX U EX WC EX WC
EX WC EX WC EX WC EX WC
EX L
4" SAN DN
4" STO
P-404
6" STO
CO
4" ST & STO
UP TO RD
4" ST & STO
UP TO RD
EX 15" STO UP
21,575 SQFT
1,010 GPM
EX FCO
EX 12" ST UP/DN
EX 12" STO UP
P-404
P-608
EX 2" SAN
UP
P-404
2" SAN
3" FCO
2" V UP
2" V
2" V
2" V
P-404
3" V UP TO INTERSTITIAL
SPACE
3" V
3" V2" V 3" V3" V
3" V
2" V
3" V
CORRIDOR-2
1CC04-2
2" V
2" V
3" V UP TO INTERSTITIAL
SPACE
3" V
3" FCO
EX 12" STO DN TO
DOWNSPOUT.
NO CONTINUATION
N O
C O
N T
IN
U
A T
IO
N
NO CONTINUATION
EX L EX L
EX MS
EX L EX L
Area - BArea - A
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10 www.abovegroupinc.com COA/CA Lic. No. 31120
FULLY SPRINKLERED305 East Dr., Suite H, Melbourne, Florida 32904
PH: 321.345.9026
A u to d e s k D o c s
/F lo ri d a
O rl a n d o
V A
/0
V A
L a k e N o n a C a rd io lo g y
R
M
E P
F P
F A
T .r v t
/7
/2
:3
:4
A M
PS111
PARTIAL LEVEL 1 PLAN - PLUMBING
GRAVITY - NEW WORK - AREA A
Create Cardiovascular Center at Lake Nona
Orlando, Florida
675-103
Kevin Glover - COR
03/07/2025 JMC AJZ
100% CONSTRUCTION
DOCUMENTS - BID SET
ALLEN D. LANTZ, P.E.
FL License #98984
N 0 4' 8' 16' 24'
1/8" = 1'-0"
N 0 4' 8' 16' 24'
1/8" = 1'-0"
N 0 4' 8' 16' 24'
1/8" = 1'-0"
1/8" = 1'-0"
1 PARTIAL LEVEL 1 PLUMBING GRAVITY PLAN - NEW WORK - AREA A
DRAWING NOTES:
1. MODIFY EXISTING PIPING AT POINTS OF CONNECTION INDICATED TO FACILITATE NEW PIPING CONNECTION AND
INSTALLATION.
2. CONTRACTOR SHALL COORDINATE ANY SYSTEM DOWNTIME WITH OWNER PRIOR TO START OF WORK.
3. INSTALL ALL FIXTURES AND EQUIPMENT PER MANUFACTURER INSTALLATION INSTRUCTIONS.
4. VENT PIPING SHOWN ON PLAN IS LOCATED ABOVE CEILING AND BELOW INTERSTITIAL SPACE.
CODED NOTES:
CONNECT TO EXISTING 2" SAN RISER UP TO INTERSTITIAL SPACE. OFFSET AS SHOWN.
6" STORM PIPING DOWN IN CHASE AND OUT TO EXISTING STORM MAIN. REFER TO CIVIL DRAWINGS FOR CONTINUATION.
4" SAN DN, 3" VENT UP, 4" SAN TO FIXTURE
2" SAN DN, 2" VENT UP, 1-1/2" SAN TO FIXTURE. VENT PIPING SHOWN OFFSET FOR CLARITY.
N.T.S.
Key Plan - Area A
REFER TO ARCHITECTURAL
DRAWING AND SHEETS
PC101 AND PC102 FOR
PHASING INFORMATION.
B.1
C.1
C.15
C.3
C.5
D.1
A.1
3.74.1 3.1 2.7 2.1 1.7 1.1
B.5
A.9
P-101
P-418
P-418
P-101
P-114
P-418
P-418 P-418 P-418
P-418
P-418
P-404
P-519
P-519
P-502
M A
T C
H
LI
N E
R
E F
E R
T O
P
LA
N
/ P S
F O
R C
O N
T
IN
U A
T
IO
N
3" FCO
3" FCO
4" FCO
EX ST FCO
NURSE MANAGER
1C148
CASE MANAGER
1C150
HF PACT
1C151
HOLD / RECOVERY
1C152
HOLD / RECOVERY
1C153
HOLD / RECOVERY
1C155
STAIR
1C197
CORRIDOR
1CC08
HOLD / RECOVERY
1C157
HOLD / RECOVERY
1C158
CORRIDOR
1CC09NURSE STATION
1C159
PATIENT TOILET
1C160
HAC
1C168
CLEAN
1C169
MEDICATION
1C170
CORRIDOR
1CC10
MALE TOILET / SHOWER
1C177
TEE / CARDIO VERSION
1C174
EQUIPMENT
1C173
SOILED UTILITY
1C166
CLINICAL DIETICIAN
1C167
READING
1C161
COMM
1C926/C
ELECTRIC
1C924
ADVANCED IMAGING
1C162
HYBRID CATH LAB
1C186
EP LAB
1C191
STERILE SUPPLIES
1C189
CORRIDOR
1CC12
ICR
1C190
ICR
1C188
EP LAB CONTROL ROOM
1C192
HYBRID CATH LAB CONTROL ROOM
1C187
CORRIDOR
1CC11
FEMALE TOILET / SHOWER
1C179
FEMALE LOCKER ROOM
1C178
ANESTHESIA
1C180
Clean
1C183
GAS STORAGE
1C185
ANESTHESIA EQPT. STR.
1C184
2 2
4" FD-D
P-408
P-521
P-408
P-521
P-502
HAC
1C183
CARDIO PHARMACY
1C172
MALE LOCKER ROOM
1C176
TRANSITION AREA
1C175
3" SAN DN
2" VENT UP
2" VENT DN
3" VENT DN
P-6…