This is a technical specification document from the California Department of General Services (DGS) for bid specification BU 7760 IFB 0000033681 detailing requirements for one Trane Centrifugal Water Chiller model CVHF048. The specifications describe a 485 nominal ton capacity chiller with AdaptiView controls, two-stage compressor, 460V/3-phase power supply, R514A refrigerant, and factory-installed adaptive frequency drive. Key components include a 358kW compressor motor, evaporator and condenser with two-pass water boxes rated for 150 psig, thermal dispersion flow switches, and comprehensive control and monitoring capabilities through the AdaptiView control panel.

The unit includes a 5-year limited Leak-Tight Warranty valid for 60 months from initial startup or 66 months from shipment date. Factory startup by Trane Service is required for warranty validation. The specification provides detailed requirements for installer responsibilities including foundation preparation, isolation pad installation, water piping connections with strainers, and startup supervision by a qualified Trane field engineer. The unit must comply with ASHRAE 90.1 standards from 2007-2016 and includes factory performance testing with standard air run and vibration test. Operating weights are specified as 20,598 lbs with shipping weight of 18,547 lbs.

View the file

Other files

File Type Posted
Att_4_-_Narrative_Response.docx DOCX document
Att_2_-_Admin_Requirements.docx DOCX document
Att_5_-_Work_Authorization_Form.docx DOCX document
Att_3_-_Cost_Worksheet.xlsx XLSX spreadsheet
IFB_-_7760-0000033681_DGS_Chillers_(LTB).pdf PDF
APP_Cover_Page.doc DOC document
Addendum_1__Questions___Answers__Chillers_DGS.pdf PDF
Addendum_1_BU_7760_EVENT_0000033681.pdf PDF
Att_2A_-_ExhibitA_-_Additional_Admin_Requirements.docx DOCX document
Addendum_1__Att_2_-_Admin_Requirements.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

State of California Bid Specification

Trane Centrifugal Water Chiller Department of General Services (DGS)

BU 7760 IFB 0000033681

Attachment 1

Table of Contents

Product Summary

Centrifugal Water Chiller (Item A1) Tag Data Product Data Product Report Pressure Drop Curve Mechanical Specifications Dimensional Drawings Weight, Clearance & Rigging Accessory Field Wiring

Field Installed Options - Part/Order Number Summary Centrifugal Water Chiller

Equipment Submittal Page 3 of 26

Tag Data - Centrifugal Water Chiller (Qty: 1)

Item Tag(s) Qty Description Model Number

A1 CH-1 new, 1 Centrifugal Chiller ( CTV ) CVHF048

Product Data - Centrifugal Water Chiller Item: A1 Qty: 1 Tag(s): CH-1 new

Standard ship cycle CVHE, CVHF & CVHG with customer witness test or wi/AFDU AFD North America region Centrifugal liquid chiller with 2 stage compressor Compressor size: 485 nominal tons Adaptiview controls Without enhanced electrical package Incoming line hertz: 60 Compressor motor hertz: 60.

Incoming line voltage: 460 volt Compressor motor voltage: 460 volt 3 phase Startup Included - Trane Service must start equipment for warranty to be honored Compressor motor power: 358 kW Motor frame size: 440E Compressor impeller cutback: 279 Economizer: Single stage standard Standard cooling Evaporator shell size: 050 long Evaporator bundle size: 390 nominal tons Evaporator tubes: 0.75 inch (19.1 mm) dia. internally enhanced copper Evaporator tube wall: .028 inch (0.7 mm) thick Evaporator fluid type: Water No Evaporator waterbox type: Non-marine Evaporator waterbox construction: Standard Evaporator water box passes: Two pass Evaporator waterbox pressure: 150 psig (1034 kPa) Evaporator waterbox connection: Victaulic Evap waterbox arrangement: in LH end - out LH end Thermal dispersion flow switch (IFM) - Field Installed (Field Installed) Condenser shell size: 050 long Condenser bundle size: 400 nominal tons Condenser tube: 0.75 inch (19.1 mm) internally enhanced copper Condenser tube wall: .028 inch (0.7 mm) thick Condenser shell construction: Standard Condenser fluid type: Water Without condenser variable flow Condenser waterbox type: non-marine Condenser waterbox construction: Standard Condenser water box passes: Two pass Condenser waterbox pressure: 150 psig (1034 kPa) Condenser waterbox connection: Victaulic Condenser waterbox arrangement: in RH end - out RH end Standard tube sheet construction Thermal dispersion flow switch (IFM) - Field Installed (Field Installed) Orifice size: 650 nominal tons Agency listing: U.L. listed unit (United States requirement) Factory performance test: Standard air run and vibration test Selection tolerance: AHRI Standard tolerance Mylar (plastic) logo Factory testable - yes Don't apply special ton tolerance Don't apply special kW/ton tolerance Shipping package: Domestic without skid

Equipment Submittal Page 4 of 26

Liquidated damages delivery: No Liquidated damages performance: NO Without China Energy Efficiency Unit option: Insulation package No Requirement Certified Complies with ASHRAE 90.1 - 2007 Complies with ASHRAE 90.1 - 2007 Addendum M Complies with ASHRAE 90.1 - 2010 No requirement Complies with ASHRAE 90.1 - 2013 Operating Status Complies with ASHRAE 90.1 - 2016 Without Generic BAS Without enhanced protection R514 Refrigerant Accessory line item 1 Accessory line item 2 Accessory line item 3 Trane Supplied Refrigerant BCU Panel Refrigerant Cooled AFD Unit mounted refrigerant cooled adaptive frequency drive Adaptive frequency drive maximum RLA: 405 amps Starter power connection: Circuit breaker Standard enclosure - Nema 1 Year 2nd-5th Parts Warranty Unit No parts less motor & cmpr warranty No motor & compressor warranty 1st Year Labor Warranty Whole Unit with Trane Supplied Starter 2nd-5th Year Labor Warranty Whole Unit with Trane supplied starter 1st year refrigerant quality warranty

Equipment Submittal Page 5 of 26

Product Report - Centrifugal Water Chiller Item: A1 Qty: 1 Tag(s): CH-1 new

Equipment Submittal Page 6 of 26

Product Report - Centrifugal Water Chiller

Equipment Submittal Page 7 of 26

Pressure Drop Curve - Centrifugal Water Chiller

Equipment Submittal Page 8 of 26

Equipment Submittal Page 10 of 26

Operating Data including:

*operating hours *number of starts *chilled water setpoint *evaporator and condenser water flow status *evaporator entering and leaving water temperatures *evaporator saturated refrigerant temperatures *evaporator approach temperature *evaporator refrigerant pressure *condenser entering and leaving water temperatures *condenser saturated refrigerant temperatures *condenser approach temperature *condenser refrigerant pressure *oil differential pressure *oil tank temperature *purge mode *purge average daily pump-out time *% RLA per phase for motor *RLA per phase *volts per phase *power factor *kw *kwh *frequency

The AdaptiView also contains the following dedicated reports:

Evaporator, Condenser, Compressor, Motor, Purge, and ASHRAE. Each report is comprised of a detailed listing of operational data relative to that chiller subsystem.

Control functions including:

*leaving chilled water temperature *percent demand limit *chiller water reset (based on return water temperature *front panel control type *setpoint source *differential to start *differential to stop

Status data including:

*waiting to start *running *run limit *run inhibit (adaptive) *auto *free cooling (option) *preparing to shutdown *shutting down (post lube) *stopped

Safeties including:

Automatic safety shutdown for:

*Low chilled water temperature, *low evaporator refrigerant temperature *high condenser refrigerant pressure *evaporator and condenser flow status *low evaporator/condenser differential refrigerant pressure *low oil pressure *oil pressure overdue *high or low oil temperature *high bearing oil temperature (requires enhanced protection option)

Equipment Submittal Page 11 of 26

*high motor current *high motor temperature *starter function faults *critical temperature and pressure sensor faults

The devices are of a latching trip out type requiring manual reset. Non-latching safety trip outs for operating conditions external to the chiller automatically permits unit to resume normal operation when condition is corrected.

Advanced motor protection monitors 3-phase current to provide latching trip out protection from adverse effects of phase loss, phase unbalance, phase reversal, loss of phase reversal protection, and electrical distribution faults (momentary power loss) by instantaneous trip out of motor.

Surge protection - Detects surge and limits chiller loading through inlet vane modulation. Head relief through lowering cooling tower water temperature can be requested. If not corrected within 7 minutes, chiller is shut down.

Enhanced Adaptive Control(TM) - Built in intelligence to keep the chiller on line (safely making maximum tons) while simultaneously preventing chiller damage/failure. During any chiller limiting mode of operation, the control panel enunciates the condition via a relay output.

Trending:

The controller provides 10 standard graphs for trending multiple parameters, The operator can add an additional 6 custom graphs if desired. On any one custom graph, the operator can choose to trend up to 10 unique parameters from a more comprehensive list. Two Y axes are available for any graph to facilitate readability.

Diagnostics:

AdaptiView includes comprehensive diagnostic monitoring. All active diagnostics are available, and up to 20 historic diagnostics are communicated to the operator via the 12 1/8" LCD display with graphic navigation system. Each diagnostic is time and date stamped.

Service Tool:

A PC-based service tool called Tracer TU, connected to the chiller via USB port, is available for additional cost and displays the last 100 diagnostics, indicating the time, date of occurrence, and system parameters at the time of the diagnostic. The service tool provides advanced troubleshooting and access to sophisticated configuration settings not needed during operation of the chiller.

Security:

The AdaptiView can be set to prevent unauthorized access to the chiller settings. The operator can choose to secure the operating settings with a password. Data and reports can still be accessed once the settings are locked out.

The memory for the AdaptiView is non-volatile type, so if power is lost, operating settings are retained. A life time battery is standard, which is used only to support the clock function for the chiller.

Chilled and Condenser water pump relays:

Chilled water and condenser water pump relays are provided and it is recommended that they be used for pump control.

Operating Status:

The following hardwire binary outputs are available:

Compressor running relay Alarm relay - manual reset Alarm relay - auto reset Limit warning relay Purge alarm relay Head relief request relay Maximum capacity relay

Evaporator Proof of Flow - Thermal Dispersion A factory provided, field installed thermal dispersion type proof of flow switch (IFM) is provided. The thermal dispersion controller is mounted in the chiller control panel, the piping probe and wiring is shipped lose for field installation in the ship with components box. Follow the installation instructions in the chiller installation manual.

Equipment Submittal Page 12 of 26

Reference specific IFM Installation manual (PART-SVN223*-EN) notes shipped with your rupture guard /contact local Trane sales office

Condenser Proof of Flow - Thermal Dispersion A factory provided, field installed thermal dispersion type proof of flow switch (IFM) is provided. The thermal dispersion controller is mounted in the chiller control panel, the piping probe and wiring is shipped lose for field installation in the ship with components box. Follow the installation instructions in the chiller installation manual.

Reference specific IFM Installation manual (PART-SVN223*-EN) notes shipped with your rupture guard /contact local Trane sales office

Paint All CenTraVac(TM) painted surfaces are coated with a primer and an air-dry beige primer-finisher prior to shipment.

Isolation All units ship with neoprene isolator pads as standard, except when spring isolators are chosen. Enough pads are provided to cover the area under the chiller supports.

Shipment All units are of hermetic design, leak tested, charged to 5.00 psi and shipped as a single factory assembled package.

Full oil charge shipped in oil sump. Refrigerant shipped to jobsite from refrigerant manufacturer. The entire chiller is shrink wrapped for protection.

Insulation Factory applied insulation. All low temperature surfaces are covered with 3/4" Armaflex ll or equal (thermal conductivity=0.28 BTU/hr-ft sq.) (1.59 W/m2-K), including the evaporator, water boxes and suction elbow. The economizer is insulated with 3/8" insulation. The chiller feet are not insulated. On units with the water box hinges option, the hinges are not factory insulated. On units with the free cooling option, the condenser is not factory insulated.

TRANE Adaptive Frequency Drive (AFD) The Trane AFD is a closed-loop, liquid refrigerant cooled, microprocessor based pulsed width modulation design. The AFD is both voltage and current regulated. Output power devices: IGBT transistors.

The AFD is factory mounted on the chiller and ships completely assembled, wired and tested. Patented Trane AFD control logic is specifically designed to interface with the centrifugal water chiller controls. AFD control adapts to the operating ranges and specific characteristics of the chiller, and chiller efficiency is optimized by coordinating compressor motor speed and compressor inlet guide vane position. Chilled water control and AFD control work together to maintain the chilled water setpoint, improve efficiency and avoid surge. If a surge is detected, AFD surge avoidance logic will make adjustments to move away from and avoid surge at similar conditions in the future. Use only copper conductors for terminal connections. Failure to do so may cause corrosion or overheating, and starter damage.

This unit mounted AFD is supported by three cantilevered support brackets. These support brackets are normally welded to the side of the evaporator shell and extend out the depth of the AFD. For some AFD sizes and chiller configurations, the support brackets have a bolt plate which allows the majority of the length of these support brackets to be removable.

Frame 3 (405A/608A): AFD Support brackets are welded to the evaporator shell.

Exceptions: The following compressor/shell combinations have supports with bolt plate as standard for a Frame

3 AFD:

- compressor sizes 620/760/870 on 080 evaporator with 080 condenser shells

- compressor sizes 1070/1300 on 142 evaporator with 210 condenser shells.

Frame 4 (900A/1210A): AFD Support brackets have bolt plate so most of the bracket is removable.

AFD Design Features

* NEMA 1 ventilated enclosure with a hinged, locking door is tested to a short circuit rating of 65,000 amps. It includes a padlockable door-mounted circuit breaker/shunt trip with AIC rating of 65,000 amps. The circuit breaker is interlocked with the enclosure door. The entire package is UL/CUL listed.

* Simple modular construction.

* The drive is rated for maximum 480/60/3 input power, +/-10%.

* Displacement power factor of .98 at full load, minimum of .96 at all other part loads.

* Minimum efficiency of 97% at rated load and 60 hertz.

Equipment Submittal Page 13 of 26

* Full motor voltage is applied regardless of the input voltage.

* Soft-start; linear acceleration; coast to stop.

* Adjustable output frequency from 38 to 60 hertz.

* All control circuit voltages are physically and electrically isolated from power circuit voltage.

* 150% instantaneous torque available for improved surge control.

* Output line-to-line and line-to-ground short circuit protection.

* Harmonic attenuation- integrated active rectification control of the building AC power assures low line-generated harmonics back to the user's power grid. The AFD has less than or equal to 5% current total demand distortion (TDD) as measured at the AFD. This is based on an electrical system with voltage distortion less than 1.5 %.

Chiller Unit Control Features for AFD Chiller Unit Control Features for AFD The chiller unit control panel capabilities provide for the control/configuration interface to, and the retrieval/display of, AFD-related data. AFD standard design features controlled through AdaptiView include:

* Current limited to 100%

* Motor overload protection.

* Motor overtemperature protection.

* Phase loss, reversal, imbalance protection.

* Overvoltage/undervoltage protection.

Digitally displayed on the AdaptiView panel: output speed in hertz, input frequency, output speed in rpm, input line voltage, output voltage, input line kw, output kw, input line amps per phase, average input line amps, output/motor amps average current in % RLA, load power factor, fault, AFD transistor temperature.

Environmental Ratings:

* 32F to 104 (0C to 40) operating ambient temperature

* Altitude to 3300 feet (1000m), amperage derate of 1% per every 300 feet above 3300 feet

* Humidity, 95% non-condensing

Required Installer Responsibilities The following are considered functions normally required of the equipment installer./n

Install unit on a foundation with flat support surfaces level within 1/16" and of sufficient length to support concentrated loading. (Spring isolators should be considered whenever chiller installation is planned for an upper story location.)

Place isolation pads or optional spring type isolators provided by the chiller manufacturer under the unit. When spring isolators are chosen, no pads are provided.

Install unit per applicable Trane Installation Manual.

Complete all water and electrical connections.

Where specified, provide and install valves in water piping upstream and downstream of the evaporator and condenser water boxes as means of isolating shells for maintenance and to balance and trim system.

Furnish and install a flow switch or equivalent device in both the chilled water and condenser water piping properly interlocked to insure that unit can operate only when water flow is established.

Furnish and install taps for thermometers and pressure gauges in water piping adjacent to inlet and outlet connections of both evaporator and condenser.

Furnish and install drain valves to each water box.

Install vent cocks on each water box.

Furnish and install strainers upstream of chiller evaporator and condenser bundles to protect tubes from potential damage caused by debris in the circulating water. Note: Failure to install strainers in all water piping entering the chiller could result in tube plugging conditions that could damage unit components. If the circulating pumps are immediately upstream of the chiller bundles, then the strainer can be installed immediately ahead of the pumps. If the

Equipment Submittal Page 14 of 26 circulating pumps are downstream of the chiller bundles, then the strainers should be installed immediately ahead of the chiller bundles.

Furnish sufficient refrigerant 25.0 lb per machine and dry nitrogen 50.0 lb per machine for pressure testing under manufacturer's supervision.

Start-up unit under supervision of a qualified Trane field engineer.

Where specified, insulate evaporator and any other portions of machine required to prevent sweating under normal operating conditions.

Water connection piping must not transfer forces to the chiller. Because of cumulative tolerances in manufacture and field installation, prepiping of water connections closer than 36" is not recommended. Any problems associated with prepiping of water connections closer than 36" to the chiller are the responsibility of the installing contractor.

Furnish and install vent lines for rupture disk and purge venting to atmosphere per ASHRAE 15 and unit installation manual. If RuptureGuard-Relief Valve option is ordered, remove factory rupture disk and install RuptureGuard-Relief Valve per the IOM manual. In some chiller configurations the RuptureGuard may not bolt directly to the chiller flange.

Locally sourced and approved piping may be required between the chiller and the RuptureGuard.

Field Disassembly With chillers that may require field disassembly (for example due to clearance concerns during unit installation) reference the Disassembly and Reassembly manual and your Trane Sales representative prior to the order being placed. Caution: if certain components are removed in the field, for example the economizer, the necessary components (gaskets, seals, etc.) are not provided as standard.

Leak-Tight Warranty The CenTraVac chiller features a 5-year limited Leak-Tight Warranty which is valid for the lesser of 60 months from initial start-up or 66 months from date of shipment. The limited Leak-Tight Warranty covers models CVHE/F/L, CVHS, CVHM and CDHF chillers installed in the United States or Canada. The Company's obligations and liabilities under this warranty are limited to furnishing replacement refrigerant; no other parts or labor are covered under this limited warranty. No liability whatever shall attach to the Company until appropriate actions have been taken (acceptable to Company) to eliminate the source of the leak, and then said liability shall be limited to furnishing the replacement refrigerant.

If the chiller is placed under a comprehensive Trane service and maintenance agreement (Trane Select Agreement or better) prior to the expiration of the standard Leak-Tight Warranty, the protection against refrigerant loss shall continue under the Trane Select Agreement for as long as an active Trane Select Agreement remains in effect without interruption.

If a 10-Year Parts, Labor and Refrigerant Warranty was purchased for the chiller and the chiller is placed under a Trane Select Agreement (or better) prior to the expiration of the 10-Year Parts, Labor and Refrigerant Warranty, the protection against refrigerant loss shall continue under the Trane Select Agreement for as long as an active Trane Select Agreement remains in effect without interruption

Equipment Submittal Page 15 of 26

Dimensional Drawings - Centrifugal Water Chiller

Equipment Submittal Page 16 of 26

Equipment Submittal Page 17 of 26

Equipment Submittal Page 18 of 26

Equipment Submittal Page 19 of 26

Equipment Submittal Page 20 of 26

Equipment Submittal Page 21 of 26

Weight, Clearance & Rigging - Centrifugal Water Chiller

Equipment Submittal Page 22 of 26

Weight, Clearance & Rigging - Centrifugal Water Chiller

Equipment Submittal Page 23 of 26

Accessory - Centrifugal Water Chiller ersid

Equipment Submittal Page 24 of 26

Accessory - Centrifugal Water Chiller

Equipment Submittal Page 25 of 26

Field Wiring - Centrifugal Water Chiller

Equipment Submittal Page 26 of 26

Field Installed Options - Part/Order Number Summary

This is a report to help you locate field installed options that arrive at the jobsite. This report provides part or order numbers for each field installed option, and references it to a specific product tag. It is NOT intended as a bill of material for the job.

Product Family - Centrifugal Water Chiller Item Tag(s) Qty Description Model Number

A1 CH-1 new, 1 Centrifugal Chiller ( CTV ) CVHF048

Field Installed Option Description Part/Ordering Number

Thermal dispersion flow switch (IFM) - Field Installed Thermal dispersion flow switch (IFM) - Field Installed

Procurement_Packet_168322.FMD.TraneChillers.pdf
4 - Centrifugal Water Chiller Specs