Att_02_Asbestos_Containing_Materials_Survey_Report.pdf
PDF 11 MB Posted
- Attached to
- Golden Gate NRA, Fort Mason Pier 1 Hazmat Survey
- Solicitation number
- 140P8624Q0028
About this file
This document is an Asbestos-Containing Materials Survey Report related to the federal contract opportunity for a Hazardous Materials Survey at Golden Gate National Recreation Area, Fort Mason Pier One.
The report provides details on the comprehensive hazardous materials survey and hazard assessment to be conducted at the site. Key findings include the identification and assessment of asbestos-containing building materials, lead-based paint, and other hazardous materials. The report includes sample analysis results, a detailed inventory of hazardous materials, and recommendations for abatement and disposal. This information will be used to support the requirements outlined in the Performance Work Statement for the federal contract opportunity.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Att_01_SOW_FOMA_Pier1_BldHazMatSurvey_TD_f2_5_15_23.pdf | ||
| Att_06_Wage_Determination_2015-5637_12-26-23.pdf | ||
| Att_05_Quote_Sheet.docx | DOCX document | |
| Att_03_GOGA_Pier1_floorplan.pdf | ||
| Att_04_Relevant_Experience.pdf | ||
| Sol_140P8624Q0028.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
ASBESTOS-CONTAINING MATERIALS
SURVEY REPORT
FOR
NATIONAL PARK SERVICE
UNITED STATES DEPARTMENT OF THE INTERIOR
GOLDEN GATE NATIONAL RECREATION AREA
SAN FRANCISCO, CALIFORNIA
Prepared For:
NATIONAL PARK SERVICE
1201 Eye Street NW, 10th Floor
Washington, DC 20006
Prepared By:
MACTEC ENGINEERING AND CONSULTING, INC.
396 Plasters Avenue, Atlanta, Georgia 30324
SEPTEMBER 28, 2012
MACTEC Project Number 6141-10-0320
National Park Service; GOGA, San Francisco, California Asbestos-Containing Materials Survey Report MACTEC Project 6141-10-0320 September 28, 2012
For reference, MACTEC developed room designations during our visual survey. Each room, area, or groups of rooms were assigned a unique (arbitrary) number. For the purposes of this survey effort, a room is a discrete area within the surveyed structure that may correspond to physical rooms (e.g., doors and walls), a discrete space (e.g., mezzanine or roof), or other identifiable space such as a department, suite, or group of rooms. When drawings for a building/structure were not provided by NPS, MACTEC may have designated an entire building as a single room and referenced areas/rooms within that building/structure based on the physical lay-out of the structure (i.e., northwest office, entrance, storage, kitchen, restroom, etc.).
4.2 Methodology
When supplemental sampling and analyses were performed, representative bulk samples (some with multiple layers) were collected of homogeneous suspect asbestos-containing materials located during the visual survey. The sampling was performed in general accordance with the sampling requirements of the Asbestos Hazard Emergency Response Act (AHERA) regulation [40 CFR 763.86] for each homogeneous material. The bulk samples were sealed in airtight containers, labeled, and delivered to Forensic Analytical Laboratories, Inc. National Voluntary Laboratory Accreditation Program (NVLAP) and California Environmental Laboratory Accreditation Program (ELAP) accredited laboratory in Hayward, California.
Samples were analyzed for asbestos content by Polarized Light Microscopy (PLM) in general accordance with EPA method 600/R-93/116.
4.3 Existing Data
There was no existing data or information related to asbestos provided to MACTEC for this Park.
4.4 Supplemental Sample Collection and Analysis
Sampling and analyses of suspect asbestos-containing materials were performed. The asbestos survey and sample collection were performed by Don Harman of MACTEC. Mr. Harman is an accredited asbestos Inspector and California Certified Asbestos Consultant (CAC); evidence of accreditation is provided in Appendix E. The site evaluation services were performed between May of 2011 and June of 2012.
A total of 5,657 samples were collected from structures at the Park. All samples were analyzed by PLM with limited additional analytical evaluation by PLM Point Count. The additional evaluation identified ACCM in eleven buildings. ACCM included: White Window Glazing (38276, 38295, 42013, 43422, 80489, 80673 and 86027), Tan Resilient Sheet Flooring (38353), Beige Circular Pattern Resilient Sheet Flooring (38353), Gray Resilient Sheet Flooring (38353 and 38371), Brown Resilient Sheet Flooring (38353), Light Gray Window Glazing (38378), and White Plaster (43432).
National Park Service; GOGA, San Francisco, California Asbestos-Containing Materials Survey Report MACTEC Project 6141-10-0320 September 28, 2012
Appendix C - ACM Detail and Photographs:
• Building/structure identification number;
• A representative photograph of the ACM homogeneous material;
• The information summarized in Table 2, and;
• Bulk sample information including sample location, sample results, homogeneous material locations, quantity and condition.
Laboratory results of bulk samples are included in Appendix D. Inspector and Laboratory Accreditations and Certifications are included in Appendix E.
5.1 LOCATED ACM
Asbestos-containing in the following buildings: Garage FB 541 (100405), Battery Spenor Admin Building FB 705a (108224), Battery Spenor Equip Room FB 705b (108225), Battery Spenor Sandy Sat FB 705d (108227), Battery Spenor latrine (108228), Battery Spena Power House FB 705e (108266), Lime Point Fog Signal Station (111054), Lt. Gr Shed @ FM: lay (111242), BADM Building 1003 (116385), BADM #567A (116386), Guard Tower SB-7 (14424), Snack Bar SB (14425), South Restroom SB-8 (14435), Central R/R SB-9 (14438), North R/R SB-10 (14442), Kiosk SB-6 (14446), Healing Arts Center FB-568 (226106), Building 100 FF-100 (38069), Building 01 FF-101Q (38070), LE Offices FF-104 (38072), Building 206 Hang Glider Building (38073), Cliff House (38099), Quarters 21 Octagon House SA-14 (38103), Well House Gazebo SH-007 (38123), OCBE Maint. Office FI304 (38140), Amari Youth Hostel Dorm FM-240 (38234), Bay Grounds Shop FM-112 (38244), Building 33 FM-33 (38248), Building 34 FM-34 (38250), Building 35 FM-35 (38252), Building 36 FM-36 (38254), Building 37 FM-37 (38255), Building 38 FM-38 (38257), Building 39 FM-39 (38258), Building A Lower Ft. Mason FM-308 (38259), Building B Lower Ft.
Mason FM-310 (38262), Building C Lower Ft. Mason FM-312 (38263), Building D Lower Ft. Mason FM- 314 (38264), Garage FM-5 (38275), GOGA Headquarters FM-201 (38276), GOG SPUG FM-204 (38277), Guard Station FM-303 (38280), Laundry FM-32 (38281), Main Switching Station FM-248 (38286), Officer’s Nest Course FM-1 (38289), Pier 1 Shed Lower Ft. Mason FM-317 (38295), Pier 2 Shed Lower Ft.
Mason FM-319 (38298), Pier 3 Shed Lower Ft. Mason FM-321 (38300), Projects Offices FM-101 (38305), Quarter #2 – Brooks FM-2 (38307), Quarter #3 – Haskell FM-3 (38308), Quarter #4 – Palmer Fm-4 (38309), Quarter #7 FM-7 (38310), Quarter 41 FM-41 (38311), Quarter #42 FM-42 (38312), Quarter #43 FM-43 (38313), Quarter #44 FM-44 (38314), Quarter #46 FM-46 (38316), Quarter #48 FM-48 (38318), Quarter #49 FM-49 (38319), Quarter #50 FM-50 (38320), Quarters 231 FM-231 (38321), Quarters 232 FM- 232 (38322), Quarters 234 FM-234 (38323), Quarters 235 FM-235 (38324), Quarters 238 FM-238 (38325), Quarters 239 Fm-239 (38326), SFCC FM-102 (38337), Barracks AL-64 (38353), Electric Shop Al-89 (38356), Guardhouse AL-22 (38371), Model Industries Building AL-82 (38376), Morgue AL-12 (38377), New Parson Industries AL-84 (38378), Prison/Cell Block AL-68 (38383), Quartermaster AL-79 (38384), Storage Vault AL-218 (38395), Fog Signal Building PB-002 (40751), Lighthouse Point Benito PB-001 (40755), Quarters 17 PB-008 (40758), Quarters 18 PB-009 (40759), Quarters 19 PB-010 (40760), NIKE Test Building FA-963 (40771), American Youth Hostel FA-941 (40772), American Youth Hostel FA-937 (40774), Balloon Hanger FA-905 (40778), Headlands Center for Arts FA-940 (40815), Headlands Center for Arts FA-944 (40816), Headlands Center for Arts FA-945 (40817), Headlands Center for Arts FA-952 (40818), Headlands Center for Arts FA-961 (40820), Headlands Center for Arts FA-962 (40821), Headlands Institute FA-936 (40822), Lift Station Capehart FA-840 (40823), Lift Station Horse Stable FA- 841 (40824), Lift Station Rodeo Lake FA-931 (40825), NIKE Paint Storage FA-972 (40831), NIKE Sentry Station FA-970 (40832), Quarters 806 FA-806 (40847), Quarters 810 FA-810 (40854), Quarters 870 FA-870 (40899), Range Building FA-828 (40905), NIKE Generator Building FA-966 (41852), NIKE Sentry Station FA-976 (41857), NIKE Missile Warhead FA-967 (41861), Stable East FA-902 (41879), Stable West FA-
TABLE 1.0 - SUMMARY OF SUSPECT ACM
Golden Gate National Recreation Area
San Francisco, California
September 28, 2012
Table 1.0 - Page 37 of 220
Suspect Material Description Material Category
Associated Facility System
Homogeneous Material ID Substrate/Component
Suspect Material Classification
Building 38289 - Officer's Club-Nest Course FM1
Built-Up Roofing System Materials, Black Misc.Roof DeckGOGA.38289.010a Roof Assumed ACM
Roof Shingles, Green Misc.Roof DeckGOGA.38289.011a Roof Sampled
9" x 9" Floor Tile, Green Misc.WoodGOGA.38289.012a Floor Sampled
Floor Tile Mastic, Black Misc.WoodGOGA.38289.012b Floor Sampled
Covebase, Black Misc.WallboardGOGA.38289.013a Wall Sampled
Covebase Mastic, Brown Misc.WallboardGOGA.38289.013b Wall Sampled
Plaster, White SurfacingLatheGOGA.38289.014a Wall/Ceiling Sampled
Covebase, Brown Misc.WallboardGOGA.38289.015a Wall Sampled
Covebase Mastic, Brown Misc.WallboardGOGA.38289.015b Wall Sampled
12" x 12" Floor Tile, White Misc.ConcreteGOGA.38289.016a Floor Sampled
Floor Tile Mastic, Beige Misc.ConcreteGOGA.38289.016b Floor Sampled
12" x 12" Floor Tile, Brown Misc.ConcreteGOGA.38289.017a Floor Sampled
Floor Tile Mastic, Beige Misc.ConcreteGOGA.38289.017b Floor Sampled
2' x 4' Ceiling Tile (Lay-in), White Misc.Metal GridGOGA.38289.018a Ceiling Sampled
Mud Pipe Fitting, White TSIPipe RunsGOGA.38289.019a Hot Water Assumed ACM
Suspect Material Description Material Category
Associated Facility System
Homogeneous Material ID Substrate/Component
Suspect Material Classification
Building 38295 - Pier 1 Shed Lower FM (FM317)
Plaster, White SurfacingLatheGOGA.38295.001a Wall Sampled
Floor Tile Mastic, Black Misc.ConcreteGOGA.38295.002a Floor Sampled
Corrugated Paper Insulation, Gray TSIPipe RunsGOGA.38295.003a Steam Sampled
Plaster Base Coats, White SurfacingLatheGOGA.38295.004a Wall Sampled
San Francisco, California
September 28, 2012
Table 1.0 - Page 38 of 220
Suspect Material Description Material Category
Associated Facility System
Homogeneous Material ID Substrate/Component
Suspect Material Classification
Building 38295 - Pier 1 Shed Lower FM (FM317)
Wallboard Joint Compound, White Misc.Wall StudsGOGA.38295.004b Wall Sampled
12" x 12" Floor Tile, Light Brown, Brown Streaks Misc.ConcreteGOGA.38295.005a Floor Sampled
Floor Tile Mastic, Black Misc.ConcreteGOGA.38295.005b Floor Sampled
Pipe Insulation, Brown TSIPipe RunsGOGA.38295.006a Steam Sampled
Resilient Sheet Flooring, Red Misc.WoodGOGA.38295.007a Floor Sampled
Sheet Flooring Adhesive, Black Misc.WoodGOGA.38295.007b Floor Sampled
Pipe Insulation, White TSIPipe RunsGOGA.38295.008a Steam Sampled
Mud Pipe Fitting, White TSIPipe ElbowsGOGA.38295.009a Steam Sampled
1' x 1' Ceiling Tile (Glued), White, Pindot Misc.PlasterGOGA.38295.010a Ceiling Sampled
Ceiling Tile Adhesive, Brown Misc.PlasterGOGA.38295.010b Ceiling Sampled
1' x 1' Ceiling Tile (Glued), White, Fissured Misc.PlasterGOGA.38295.011a Ceiling Sampled
Ceiling Tile Adhesive, Brown Misc.PlasterGOGA.38295.011b Ceiling Sampled
9" x 9" Floor Tile, Black Misc.ConcreteGOGA.38295.012a Floor Sampled
Floor Tile Mastic, Black Misc.ConcreteGOGA.38295.012b Floor Sampled
9" x 9" Floor Tile, Red, White Streaks Misc.ConcreteGOGA.38295.013a Floor Sampled
Floor Tile Mastic, Black Misc.ConcreteGOGA.38295.013b Floor Sampled
9" x 9" Floor Tile, Dark Brown Misc.ConcreteGOGA.38295.014a Floor Sampled
Floor Tile Mastic, Gray Misc.ConcreteGOGA.38295.014b Floor Sampled
Carpet Mastic, Beige Misc.ConcreteGOGA.38295.015a Floor Sampled
12" x 12" Floor Tile, Green, White Streaks Misc.ConcreteGOGA.38295.016a Floor Sampled
Floor Tile Mastic, Beige Misc.ConcreteGOGA.38295.016b Floor Sampled
Window Glazing, White Misc.WindowsGOGA.38295.018a Building Exterior Sampled
San Francisco, California
September 28, 2012
Table 1.0 - Page 39 of 220
Suspect Material Description Material Category
Associated Facility System
Homogeneous Material ID Substrate/Component
Suspect Material Classification
Building 38295 - Pier 1 Shed Lower FM (FM317)
9" x 9" Floor Tile, Green, White Streaks Misc.ConcreteGOGA.38295.019a Floor Sampled
Floor Tile Mastic, Black Misc.ConcreteGOGA.38295.019b Floor Sampled
Covebase, Black Misc.WallboardGOGA.38295.020a Wall Sampled
Covebase Mastic, Black Misc.WallboardGOGA.38295.020b Wall Sampled
12" x 12" Floor Tile, Gray, Black and White Streaks Misc.ConcreteGOGA.38295.021a Floor Sampled
Floor Tile Mastic, Gray Misc.ConcreteGOGA.38295.021b Floor Sampled
Rolled Roofing, Red Misc.Roof DeckGOGA.38295.022a Roof Sampled
Suspect Material Description Material Category
Associated Facility System
Homogeneous Material ID Substrate/Component
Suspect Material Classification
Building 38298 - Pier 2 Shed, L. Ft. Mason (FM 319)
Floor Coating, Black Misc.FloorGOGA.38298.001a Floor Sampled
Wallboard, White Misc.Wall StudsGOGA.38298.002a Wall Sampled
Wallboard Joint Compound, White Misc.Wall StudsGOGA.38298.002b Wall Sampled
Window Glazing, Gray Misc.WindowsGOGA.38298.003a Building Exterior Sampled
12" x 12" Floor Tile, Black, White Streaks Misc.ConcreteGOGA.38298.004a Floor Sampled
Floor Tile Mastic, Beige Misc.ConcreteGOGA.38298.004b Floor Sampled
Plaster, White SurfacingLatheGOGA.38298.005a Wall Sampled
9" x 9" Floor Tile, Light Gray, White Streaks Misc.ConcreteGOGA.38298.006a Floor Sampled
Floor Tile Mastic, Black Misc.ConcreteGOGA.38298.006b Floor Sampled
Spray Applied Acoustical Finish, White SurfacingWallboardGOGA.38298.007a Ceiling Sampled
Wall Panel Adhesive, Beige Misc.WallboardGOGA.38298.008a Wall Sampled
Covebase, Black Misc.WallboardGOGA.38298.009a Wall Sampled
TABLE 2.0 - SUMMARY OF IDENTIFIED ACM
San Francisco, California
September 28, 2012
Table 2.0 - Page 15 of 87
Suspect Material Description Material Category
Associated Facility System
Homogeneous Material ID Substrate/Component
Suspect Material Classification
Building 38289 - Officer's Club-Nest Course FM1
Friability
9" x 9" Floor Tile, Green Misc.WoodGOGA.38289.012a Floor SampledNon-Friable
12" x 12" Floor Tile, Brown Misc.ConcreteGOGA.38289.017a Floor SampledNon-Friable
Mud Pipe Fitting, White TSIPipe RunsGOGA.38289.019a Hot Water Assumed ACMFriable
Suspect Material Description Material Category
Associated Facility System
Homogeneous Material ID Substrate/Component
Suspect Material Classification
Building 38295 - Pier 1 Shed Lower FM (FM317)
Friability
Floor Tile Mastic, Black Misc.ConcreteGOGA.38295.002a Floor SampledNon-Friable
Corrugated Paper Insulation, Gray TSIPipe RunsGOGA.38295.003a Steam SampledFriable
Wallboard Joint Compound, White Misc.Wall StudsGOGA.38295.004b Wall SampledFriable
12" x 12" Floor Tile, Light Brown, Brown Streaks Misc.ConcreteGOGA.38295.005a Floor SampledNon-Friable
Floor Tile Mastic, Black Misc.ConcreteGOGA.38295.005b Floor SampledNon-Friable
Pipe Insulation, White TSIPipe RunsGOGA.38295.008a Steam SampledFriable
Mud Pipe Fitting, White TSIPipe ElbowsGOGA.38295.009a Steam SampledFriable
9" x 9" Floor Tile, Black Misc.ConcreteGOGA.38295.012a Floor SampledNon-Friable
Floor Tile Mastic, Black Misc.ConcreteGOGA.38295.012b Floor SampledNon-Friable
9" x 9" Floor Tile, Red, White Streaks Misc.ConcreteGOGA.38295.013a Floor SampledNon-Friable
9" x 9" Floor Tile, Dark Brown Misc.ConcreteGOGA.38295.014a Floor SampledNon-Friable
Window Glazing, White Misc.WindowsGOGA.38295.018a Building Exterior SampledNon-Friable
9" x 9" Floor Tile, Green, White Streaks Misc.ConcreteGOGA.38295.019a Floor SampledNon-Friable
12" x 12" Floor Tile, Gray, Black and White Streaks Misc.ConcreteGOGA.38295.021a Floor SampledNon-Friable
APPENDIX A - BUILDING SUMMARY
San Francisco, California
September 28, 2012
Building Size: 48,000 SF
ACM Identified
Construction Date: 1934
Building Use: Pier 1 Shed Lower FM (FM317)
Building 38295 - Pier 1 Shed Lower FM (FM317)
Previous Expense:
Current Expense:
Future Asbestos Clean-up Costs:
$0
$21,685
$105,372
Building Size: 53,295 SF
ACM Identified
Construction Date: 1912
Building Use: Pier 2 Shed, L. Ft. Mason (FM 319)
Building 38298 - Pier 2 Shed, L.
Ft. Mason (FM 319)
Previous Expense:
Current Expense:
Future Asbestos Clean-up Costs:
$0
$24,077
$1,500
APPENDIX B - NON-ACM DETAIL AND PHOTOGRAPHS
Building 38295 - Homogeneous Material GOGA-38295-001
Material Description Associated System Sampled/Assumed
Material Information
HM ID
Substrate/
Component (001a) Plaster, White Lathe Wall SampledGOGA.38295.001a
HM # Sample Location Lab Results
Bulk Sample Data
Sample ID Level 1 - Boiler Room None Detected001aB38295.001
Level 1 - Boiler Room None Detected001aB38295.002
Level 1 - Boiler Room None Detected001aB38295.003
Level 1 - Restroom None Detected001aB38295.004
Level 2 - Hall None Detected001aB38295.005
Golden Gate National Recreation Area San Francisco, California
September 28, 2012 Appendix B Page 315 of 1734
Building 38295 - Homogeneous Material GOGA-38295-004
Material Description Associated System Sampled/Assumed
Material Information
HM ID
Substrate/
Component (004a) Plaster Base Coats, White Lathe Wall SampledGOGA.38295.004a
HM # Sample Location Lab Results
Bulk Sample Data
Sample ID Level 1 - Storage None Detected004aB38295.011
Level 1 - Office None Detected004aB38295.012
Level 2 - Office None Detected004aB38295.013
Level 2 - Office None Detected004aB38295.014
Level 2 - Office None Detected004aB38295.015
Golden Gate National Recreation Area San Francisco, California
Appendix B Page 316 of 1734
Building 38295 - Homogeneous Material GOGA-38295-006
Material Description Associated System Sampled/Assumed
Material Information
HM ID
Substrate/
Component (006a) Pipe Insulation, Brown Pipe Runs Steam SampledGOGA.38295.006a
HM # Sample Location Lab Results
Bulk Sample Data
Sample ID Level 1 - No Access None Detected006aB38295.018
Level 1 - No Access None Detected006aB38295.019
Level 1 - No Access None Detected006aB38295.020
Golden Gate National Recreation Area San Francisco, California
Appendix B Page 317 of 1734
Building 38295 - Homogeneous Material GOGA-38295-007
Material Description Associated System Sampled/Assumed
Material Information
HM ID
Substrate/
Component (007a) Resilient Sheet Flooring, Red Wood Floor SampledGOGA.38295.007a
(007b) Sheet Flooring Adhesive, Black Wood Floor SampledGOGA.38295.007b
HM # Sample Location Lab Results
Bulk Sample Data
Sample ID Level 1 - No Access None Detected007aB38295.021
Level 1 - No Access None Detected007bB38295.021
Level 1 - No Access None Detected007aB38295.022
Level 1 - No Access None Detected007bB38295.022
Golden Gate National Recreation Area San Francisco, California
Appendix B Page 318 of 1734
Building 38295 - Homogeneous Material GOGA-38295-010
Material Description Associated System Sampled/Assumed
Material Information
HM ID
Substrate/
Component (010a) 1' x 1' Ceiling Tile (Glued), White, Pindot Plaster Ceiling SampledGOGA.38295.010a
(010b) Ceiling Tile Adhesive, Brown Plaster Ceiling SampledGOGA.38295.010b
HM # Sample Location Lab Results
Bulk Sample Data
Sample ID Level 1 - Office None Detected010aB38295.029
Level 1 - Office None Detected010bB38295.029
Level 1 - Office None Detected010aB38295.030
Level 1 - Office None Detected010bB38295.030
Golden Gate National Recreation Area San Francisco, California
Appendix B Page 319 of 1734
Building 38295 - Homogeneous Material GOGA-38295-011
Material Description Associated System Sampled/Assumed
Material Information
HM ID
Substrate/
Component (011a) 1' x 1' Ceiling Tile (Glued), White, Fissured Plaster Ceiling SampledGOGA.38295.011a
(011b) Ceiling Tile Adhesive, Brown Plaster Ceiling SampledGOGA.38295.011b
HM # Sample Location Lab Results
Bulk Sample Data
Sample ID Level 1 - Office None Detected011aB38295.031
Level 1 - Office None Detected011bB38295.031
Level 1 - Office None Detected011aB38295.032
Level 1 - Office None Detected011bB38295.032
Golden Gate National Recreation Area San Francisco, California
Appendix B Page 320 of 1734
Building 38295 - Homogeneous Material GOGA-38295-013
Material Description Associated System Sampled/Assumed
Material Information
HM ID
Substrate/
Component (013b) Floor Tile Mastic, Black Concrete Floor SampledGOGA.38295.013b
HM # Sample Location Lab Results
Bulk Sample Data
Sample ID Level 2 - Hall None Detected013bB38295.035
Level 2 - Hall None Detected013bB38295.036
Golden Gate National Recreation Area San Francisco, California
Appendix B Page 321 of 1734
Building 38295 - Homogeneous Material GOGA-38295-014
Material Description Associated System Sampled/Assumed
Material Information
HM ID
Substrate/
Component (014b) Floor Tile Mastic, Gray Concrete Floor SampledGOGA.38295.014b
HM # Sample Location Lab Results
Bulk Sample Data
Sample ID Level 2 - Hall None Detected014bB38295.037
Level 2 - Hall None Detected014bB38295.038
Golden Gate National Recreation Area San Francisco, California
Appendix B Page 322 of 1734
Building 38295 - Homogeneous Material GOGA-38295-015
Material Description Associated System Sampled/Assumed
Material Information
HM ID
Substrate/
Component (015a) Carpet Mastic, Beige Concrete Floor SampledGOGA.38295.015a
HM # Sample Location Lab Results
Bulk Sample Data
Sample ID Level 2 - Hall None Detected015aB38295.039
Level 2 - Office None Detected015aB38295.040
Golden Gate National Recreation Area San Francisco, California
Appendix B Page 323 of 1734
Building 38295 - Homogeneous Material GOGA-38295-016
Material Description Associated System Sampled/Assumed
Material Information
HM ID
Substrate/
Component (016a) 12" x 12" Floor Tile, Green, White
Streaks Concrete Floor SampledGOGA.38295.016a
(016b) Floor Tile Mastic, Beige Concrete Floor SampledGOGA.38295.016b
HM # Sample Location Lab Results
Bulk Sample Data
Sample ID Level 2 - Hall None Detected016aB38295.041
Level 2 - Hall None Detected016bB38295.041
Level 2 - Hall None Detected016aB38295.042
Level 2 - Hall None Detected016bB38295.042
Golden Gate National Recreation Area San Francisco, California
Appendix B Page 324 of 1734
Building 38295 - Homogeneous Material GOGA-38295-019
Material Description Associated System Sampled/Assumed
Material Information
HM ID
Substrate/
Component (019b) Floor Tile Mastic, Black Concrete Floor SampledGOGA.38295.019b
HM # Sample Location Lab Results
Bulk Sample Data
Sample ID Level 2 - Office None Detected019bB38295.045
Level 2 - Office None Detected019bB38295.046
Golden Gate National Recreation Area San Francisco, California
Appendix B Page 325 of 1734
Building 38295 - Homogeneous Material GOGA-38295-020
Material Description Associated System Sampled/Assumed
Material Information
HM ID
Substrate/
Component (020a) Covebase, Black Wallboard Wall SampledGOGA.38295.020a
(020b) Covebase Mastic, Black Wallboard Wall SampledGOGA.38295.020b
HM # Sample Location Lab Results
Bulk Sample Data
Sample ID Level 2 - Office None Detected020aB38295.047
Level 2 - Office None Detected020bB38295.047
Level 2 - Office None Detected020aB38295.048
Level 2 - Office None Detected020bB38295.048
Golden Gate National Recreation Area San Francisco, California
Appendix B Page 326 of 1734
Building 38295 - Homogeneous Material GOGA-38295-021
Material Description Associated System Sampled/Assumed
Material Information
HM ID
Substrate/
Component (021b) Floor Tile Mastic, Gray Concrete Floor SampledGOGA.38295.021b
HM # Sample Location Lab Results
Bulk Sample Data
Sample ID Level 2 - Office None Detected021bB38295.049
Level 2 - Office None Detected021bB38295.050
Golden Gate National Recreation Area San Francisco, California
Appendix B Page 327 of 1734
Building 38295 - Homogeneous Material GOGA-38295-022
Material Description Associated System Sampled/Assumed
Material Information
HM ID
Substrate/
Component (022a) Rolled Roofing, Red Roof Deck Roof SampledGOGA.38295.022a
HM # Sample Location Lab Results
Bulk Sample Data
Sample ID Roof None Detected022aB38295.051
Roof None Detected022aB38295.052
Golden Gate National Recreation Area San Francisco, California
Appendix B Page 328 of 1734
APPENDIX C - ACM DETAIL AND PHOTOGRAPHS
Building 38295 - Homogeneous Material GOGA-38295-002
Material Description Associated System Sampled/Assumed
Material Information
HM ID
Substrate/
Component (002a) Floor Tile Mastic, Black Concrete Floor SampledGOGA.38295.002a
HM # Sample Location Lab Results
Bulk Sample Data
Sample ID Level 1 - Boiler Room 5% Chrysotile002aB38295.006
Level 1 - Boiler Room 5% Chrysotile002aB38295.007
Material Locations and Condition
Material Location Quantity ConditionHM Level 1 - Boiler Room >25% Localized Damage100 S.F.002a
Golden Gate National Recreation Area San Francisco, California
Appendix C Page 156 of 878
Building 38295 - Homogeneous Material GOGA-38295-003
Material Description Associated System Sampled/Assumed
Material Information
HM ID
Substrate/
Component (003a) Corrugated Paper Insulation, Gray Pipe Runs Steam SampledGOGA.38295.003a
HM # Sample Location Lab Results
Bulk Sample Data
Sample ID Level 1 - Closet 48% Chrysotile/Amosite003aB38295.008
Level 1 - Closet 48% Chrysotile/Amosite003aB38295.009
Level 1 - Closet 65% Chrysotile003aB38295.010
Material Locations and Condition
Material Location Quantity ConditionHM Level 1 - Closet <1% Damage8 L.F.003a
Golden Gate National Recreation Area San Francisco, California
Appendix C Page 157 of 878
Building 38295 - Homogeneous Material GOGA-38295-004
Material Description Associated System Sampled/Assumed
Material Information
HM ID
Substrate/
Component (004b) Wallboard Joint Compound, White Wall Studs Wall SampledGOGA.38295.004b
HM # Sample Location Lab Results
Bulk Sample Data
Sample ID Level 1 - Storage None Detected004bB38295.011
Level 1 - Office 2% Chrysotile004bB38295.012
Level 2 - Office 2% Chrysotile004bB38295.013
Level 2 - Office None Detected004bB38295.014
Level 2 - Office Trace Chrysotile004bB38295.015
Material Locations and Condition
Material Location Quantity ConditionHM Level 1 - Restroom <1% Damage558 S.F.004b
Level 1 - Storage <1% Damage644 S.F.004b
Level 1 - Misc <1% Damage204 S.F.004b
Level 1 - Office <1% Damage716 S.F.004b
Level 2 - Office <1% Damage128 S.F.004b
Level 2 - Office <1% Damage223 S.F.004b
Level 2 - Office <1% Damage236 S.F.004b
Level 2 - Misc <1% Damage160 S.F.004b
Golden Gate National Recreation Area San Francisco, California
Appendix C Page 158 of 878
Building 38295 - Homogeneous Material GOGA-38295-005
Material Description Associated System Sampled/Assumed
Material Information
HM ID
Substrate/
Component (005a) 12" x 12" Floor Tile, Light Brown, Brown Streaks Concrete Floor SampledGOGA.38295.005a
(005b) Floor Tile Mastic, Black Concrete Floor SampledGOGA.38295.005b
HM # Sample Location Lab Results
Bulk Sample Data
Sample ID Level 1 - Storage 2% Chrysotile005aB38295.016
Level 1 - Storage 5% Chrysotile005bB38295.016
Level 1 - Storage 3% Chrysotile005aB38295.017
Level 1 - Storage 5% Chrysotile005bB38295.017
Material Locations and Condition
Material Location Quantity ConditionHM Level 1 - Storage <1% Damage196 S.F.005a
Level 1 - Storage <1% Damage196 S.F.005b
Golden Gate National Recreation Area San Francisco, California
Appendix C Page 159 of 878
Building 38295 - Homogeneous Material GOGA-38295-008
Material Description Associated System Sampled/Assumed
Material Information
HM ID
Substrate/
Component (008a) Pipe Insulation, White Pipe Runs Steam SampledGOGA.38295.008a
HM # Sample Location Lab Results
Bulk Sample Data
Sample ID Level 1 - No Access 15% Chrysotile/Amosite008aB38295.023
Level 1 - No Access 15% Chrysotile/Amosite008aB38295.024
Level 1 - No Access 18% Chrysotile/Amosite008aB38295.025
Material Locations and Condition
Material Location Quantity ConditionHM Level 1 - Main <1% Damage144 L.F.008a
Level M - Mezz above 5 <1% Damage12 L.F.008a
Golden Gate National Recreation Area San Francisco, California
Appendix C Page 160 of 878
Building 38295 - Homogeneous Material GOGA-38295-009
Material Description Associated System Sampled/Assumed
Material Information
HM ID
Substrate/
Component (009a) Mud Pipe Fitting, White Pipe Elbows Steam SampledGOGA.38295.009a
HM # Sample Location Lab Results
Bulk Sample Data
Sample ID Level 1 - No Access 18% Chrysotile/Amosite009aB38295.026
Level 1 - No Access 17% Chrysotile/Amosite009aB38295.027
Level 1 - No Access 17% Chrysotile/Amosite009aB38295.028
Material Locations and Condition
Material Location Quantity ConditionHM Level M - Mezz above 5 <1% Damage2 Each009a
Golden Gate National Recreation Area San Francisco, California
Appendix C Page 161 of 878
Building 38295 - Homogeneous Material GOGA-38295-012
Material Description Associated System Sampled/Assumed
Material Information
HM ID
Substrate/
Component (012a) 9" x 9" Floor Tile, Black Concrete Floor SampledGOGA.38295.012a
(012b) Floor Tile Mastic, Black Concrete Floor SampledGOGA.38295.012b
HM # Sample Location Lab Results
Bulk Sample Data
Sample ID Level 1 - Stairs 3% Chrysotile012aB38295.033
Level 1 - Stairs 2% Chrysotile012bB38295.033
Level 1 - Stairs 3% Chrysotile012aB38295.034
Level 1 - Stairs 3% Chrysotile012bB38295.034
Material Locations and Condition
Material Location Quantity ConditionHM Level 1 - Stairs <1% Damage0 S.F.012a
Level 2 - Misc <1% Damage16 S.F.012a
Level 1 - Stairs <1% Damage0 S.F.012b
Level 2 - Misc <1% Damage16 S.F.012b
Golden Gate National Recreation Area San Francisco, California
Appendix C Page 162 of 878
Building 38295 - Homogeneous Material GOGA-38295-013
Material Description Associated System Sampled/Assumed
Material Information
HM ID
Substrate/
Component (013a) 9" x 9" Floor Tile, Red, White Streaks Concrete Floor SampledGOGA.38295.013a
HM # Sample Location Lab Results
Bulk Sample Data
Sample ID Level 2 - Hall 3% Chrysotile013aB38295.035
Level 2 - Hall 5% Chrysotile013aB38295.036
Material Locations and Condition
Material Location Quantity ConditionHM Level 2 - Misc <1% Damage200 S.F.013a
Level 2 - Hall <1% Damage32 S.F.013a
Level 2 - Office <1% Damage180 S.F.013a
Level 2 - Misc <1% Damage560 S.F.013a
Golden Gate National Recreation Area San Francisco, California
Appendix C Page 163 of 878
Building 38295 - Homogeneous Material GOGA-38295-014
Material Description Associated System Sampled/Assumed
Material Information
HM ID
Substrate/
Component (014a) 9" x 9" Floor Tile, Dark Brown Concrete Floor SampledGOGA.38295.014a
HM # Sample Location Lab Results
Bulk Sample Data
Sample ID Level 2 - Hall 2% Chrysotile014aB38295.037
Level 2 - Hall 3% Chrysotile014aB38295.038
Material Locations and Condition
Material Location Quantity ConditionHM Level 2 - Hall <1% Damage42 S.F.014a
Level 2 - Office <1% Damage132 S.F.014a
Golden Gate National Recreation Area San Francisco, California
Appendix C Page 164 of 878
Building 38295 - Homogeneous Material GOGA-38295-018
Material Description Associated System Sampled/Assumed
Material Information
HM ID
Substrate/
Component (018a) Window Glazing, White Windows Building Exterior SampledGOGA.38295.018a
HM # Sample Location Lab Results
Bulk Sample Data
Sample ID Level 2 - Office 0.21% Chrysotile018aB38295.043
Level 2 - Office None Detected018aB38295.044
Material Locations and Condition
Material Location Quantity ConditionHM Level 1 - Main <1% Damage5472 L.F.018a
Level 2 - Misc <1% Damage5472 L.F.018a
Level 2 - Office <1% Damage240 L.F.018a
Level 2 - Office <1% Damage96 L.F.018a
Level 2 - Office <1% Damage96 L.F.018a
Level 2 - Misc <1% Damage240 L.F.018a
Level 2 - Misc <1% Damage96 L.F.018a
Level 2 - Misc <1% Damage132 L.F.018a
Level 2 - Office <1% Damage108 L.F.018a
Level 2 - Misc <1% Damage336 L.F.018a
Golden Gate National Recreation Area San Francisco, California
Appendix C Page 165 of 878
Building 38295 - Homogeneous Material GOGA-38295-019
Material Description Associated System Sampled/Assumed
Material Information
HM ID
Substrate/
Component (019a) 9" x 9" Floor Tile, Green, White Streaks Concrete Floor SampledGOGA.38295.019a
HM # Sample Location Lab Results
Bulk Sample Data
Sample ID Level 2 - Office 2% Chrysotile019aB38295.045
Level 2 - Office 2% Chrysotile019aB38295.046
Material Locations and Condition
Material Location Quantity ConditionHM Level 2 - Office <1% Damage132 S.F.019a
Level 2 - Misc <1% Damage99 S.F.019a
Golden Gate National Recreation Area San Francisco, California
Appendix C Page 166 of 878
Building 38295 - Homogeneous Material GOGA-38295-021
Material Description Associated System Sampled/Assumed
Material Information
HM ID
Substrate/
Component (021a) 12" x 12" Floor Tile, Gray, Black and
White Streaks Concrete Floor SampledGOGA.38295.021a
HM # Sample Location Lab Results
Bulk Sample Data
Sample ID Level 2 - Office 2% Chrysotile021aB38295.049
Level 2 - Office 2% Chrysotile021aB38295.050
Material Locations and Condition
Material Location Quantity ConditionHM Level 2 - Office <1% Damage384 S.F.021a
Golden Gate National Recreation Area San Francisco, California
Appendix C Page 167 of 878
Final Report
Bulk Asbestos Analysis (EPA Method 600/R-93-116, Visual Area Estimation)
Forensic Analytical Laboratories
A31417Client ID:Mactec Engineering & Consulting Inc B151739Report Number:Tod Dawson
Date Received:396 Plasters Avenue NE 07/27/11Date Analyzed:
07/27/11Date Printed:Atlanta, GA 30324
First Reported:
A31417-86141-10-0320 - GOGA - Building Number 38295 - PO# 201108307 FALI Job ID:Job ID/Site:
Date(s) Collected: 06/08/2011
07/13/11
07/27/11
Sample ID Lab Number Asbestos
Type Percent in
Layer Asbestos AsbestosPercent in Percent in
Type TypeLayer Layer
1_1_a 11141253 Layer: Off-White Plaster ND Layer: Paint ND
Asbestos (ND)Total Composite Values of Fibrous Components:
Cellulose (Trace)
2_1_a 11141254 Layer: Off-White Plaster ND Layer: Paint ND
Asbestos (ND)Total Composite Values of Fibrous Components:
Cellulose (Trace)
3_1_a 11141255 Layer: Off-White Plaster ND Layer: White Plaster ND Layer: Paint ND
Asbestos (ND)Total Composite Values of Fibrous Components:
Cellulose (Trace)
4_1_a 11141256 Layer: Off-White Plaster ND Layer: Paint ND
Asbestos (ND)Total Composite Values of Fibrous Components:
Cellulose (Trace)
5_1_a 11141257 Layer: Off-White Plaster ND Layer: White Plaster ND Layer: Paint ND
Asbestos (ND)Total Composite Values of Fibrous Components:
Cellulose (Trace)
6_2_a 11141258 Layer: Black Mastic Chrysotile 5 %
Asbestos (5%)Total Composite Values of Fibrous Components:
Cellulose (Trace)
3777 Depot Road, Suite 409, Hayward, CA 94545 / Telephone: (510) 887-8828 (800) 827-FASI / Fax: (510) 887-4218
Final Report
Bulk Asbestos Analysis (EPA Method 600/R-93-116, Visual Area Estimation)
Forensic Analytical Laboratories
A31417Client ID:AMEC B161670Report Number:Tod Dawson
Date Received:396 Plasters Avenue NE 04/23/12Date Analyzed:
04/25/12Date Printed:Atlanta, GA 30324
First Reported:
A31417-86141-10-0320 - GOGA - Building Number 41986 - PO # 201108307 FALI Job ID:Job ID/Site:
Date(s) Collected: 03/15/2012
03/22/12
04/25/12
Sample ID Lab Number Asbestos
Type Percent in
Layer Asbestos AsbestosPercent in Percent in
Type TypeLayer Layer
1_1_a 11238291 Layer: White Drywall ND
Asbestos (ND)Total Composite Values of Fibrous Components:
Cellulose (20 %)
1_1_b 11238292 Layer: Off-White Joint Compound ND
Asbestos (ND)Total Composite Values of Fibrous Components:
Cellulose (Trace)
1_1_c 11238293 Layer: Off-White Texture ND Layer: Paint ND
Asbestos (ND)Total Composite Values of Fibrous Components:
Cellulose (Trace)
2_1_a 11238294 Layer: White Drywall ND
Asbestos (ND)Total Composite Values of Fibrous Components:
Cellulose (20 %)
2_1_b 11238295 Layer: Off-White Joint Compound ND
Asbestos (ND)Total Composite Values of Fibrous Components:
Cellulose (Trace)
2_1_c 11238296 Layer: Off-White Texture ND Layer: Paint ND
Asbestos (ND)Total Composite Values of Fibrous Components:
Cellulose (Trace)
3_1_b 11238297 Layer: Off-White Joint Compound ND Layer: Paint ND
Asbestos (ND)Total Composite Values of Fibrous Components:
Cellulose (Trace)
3777 Depot Road, Suite 409, Hayward, CA 94545 / Telephone: (510) 887-8828 (800) 827-FASI / Fax: (510) 887-4218