Att_02_Asbestos_Containing_Materials_Survey_Report.pdf

PDF 11 MB Posted

Attached to
Golden Gate NRA, Fort Mason Pier 1 Hazmat Survey
Solicitation number
140P8624Q0028
Issued by

About this file

This document is an Asbestos-Containing Materials Survey Report related to the federal contract opportunity for a Hazardous Materials Survey at Golden Gate National Recreation Area, Fort Mason Pier One.

The report provides details on the comprehensive hazardous materials survey and hazard assessment to be conducted at the site. Key findings include the identification and assessment of asbestos-containing building materials, lead-based paint, and other hazardous materials. The report includes sample analysis results, a detailed inventory of hazardous materials, and recommendations for abatement and disposal. This information will be used to support the requirements outlined in the Performance Work Statement for the federal contract opportunity.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

ASBESTOS-CONTAINING MATERIALS

SURVEY REPORT

FOR

NATIONAL PARK SERVICE

UNITED STATES DEPARTMENT OF THE INTERIOR

GOLDEN GATE NATIONAL RECREATION AREA

SAN FRANCISCO, CALIFORNIA

Prepared For:

NATIONAL PARK SERVICE

1201 Eye Street NW, 10th Floor

Washington, DC 20006

Prepared By:

MACTEC ENGINEERING AND CONSULTING, INC.

396 Plasters Avenue, Atlanta, Georgia 30324

SEPTEMBER 28, 2012

MACTEC Project Number 6141-10-0320

National Park Service; GOGA, San Francisco, California Asbestos-Containing Materials Survey Report MACTEC Project 6141-10-0320 September 28, 2012

For reference, MACTEC developed room designations during our visual survey. Each room, area, or groups of rooms were assigned a unique (arbitrary) number. For the purposes of this survey effort, a room is a discrete area within the surveyed structure that may correspond to physical rooms (e.g., doors and walls), a discrete space (e.g., mezzanine or roof), or other identifiable space such as a department, suite, or group of rooms. When drawings for a building/structure were not provided by NPS, MACTEC may have designated an entire building as a single room and referenced areas/rooms within that building/structure based on the physical lay-out of the structure (i.e., northwest office, entrance, storage, kitchen, restroom, etc.).

4.2 Methodology

When supplemental sampling and analyses were performed, representative bulk samples (some with multiple layers) were collected of homogeneous suspect asbestos-containing materials located during the visual survey. The sampling was performed in general accordance with the sampling requirements of the Asbestos Hazard Emergency Response Act (AHERA) regulation [40 CFR 763.86] for each homogeneous material. The bulk samples were sealed in airtight containers, labeled, and delivered to Forensic Analytical Laboratories, Inc. National Voluntary Laboratory Accreditation Program (NVLAP) and California Environmental Laboratory Accreditation Program (ELAP) accredited laboratory in Hayward, California.

Samples were analyzed for asbestos content by Polarized Light Microscopy (PLM) in general accordance with EPA method 600/R-93/116.

4.3 Existing Data

There was no existing data or information related to asbestos provided to MACTEC for this Park.

4.4 Supplemental Sample Collection and Analysis

Sampling and analyses of suspect asbestos-containing materials were performed. The asbestos survey and sample collection were performed by Don Harman of MACTEC. Mr. Harman is an accredited asbestos Inspector and California Certified Asbestos Consultant (CAC); evidence of accreditation is provided in Appendix E. The site evaluation services were performed between May of 2011 and June of 2012.

A total of 5,657 samples were collected from structures at the Park. All samples were analyzed by PLM with limited additional analytical evaluation by PLM Point Count. The additional evaluation identified ACCM in eleven buildings. ACCM included: White Window Glazing (38276, 38295, 42013, 43422, 80489, 80673 and 86027), Tan Resilient Sheet Flooring (38353), Beige Circular Pattern Resilient Sheet Flooring (38353), Gray Resilient Sheet Flooring (38353 and 38371), Brown Resilient Sheet Flooring (38353), Light Gray Window Glazing (38378), and White Plaster (43432).

National Park Service; GOGA, San Francisco, California Asbestos-Containing Materials Survey Report MACTEC Project 6141-10-0320 September 28, 2012

Appendix C - ACM Detail and Photographs:

• Building/structure identification number;

• A representative photograph of the ACM homogeneous material;

• The information summarized in Table 2, and;

• Bulk sample information including sample location, sample results, homogeneous material locations, quantity and condition.

Laboratory results of bulk samples are included in Appendix D. Inspector and Laboratory Accreditations and Certifications are included in Appendix E.

5.1 LOCATED ACM

Asbestos-containing in the following buildings: Garage FB 541 (100405), Battery Spenor Admin Building FB 705a (108224), Battery Spenor Equip Room FB 705b (108225), Battery Spenor Sandy Sat FB 705d (108227), Battery Spenor latrine (108228), Battery Spena Power House FB 705e (108266), Lime Point Fog Signal Station (111054), Lt. Gr Shed @ FM: lay (111242), BADM Building 1003 (116385), BADM #567A (116386), Guard Tower SB-7 (14424), Snack Bar SB (14425), South Restroom SB-8 (14435), Central R/R SB-9 (14438), North R/R SB-10 (14442), Kiosk SB-6 (14446), Healing Arts Center FB-568 (226106), Building 100 FF-100 (38069), Building 01 FF-101Q (38070), LE Offices FF-104 (38072), Building 206 Hang Glider Building (38073), Cliff House (38099), Quarters 21 Octagon House SA-14 (38103), Well House Gazebo SH-007 (38123), OCBE Maint. Office FI304 (38140), Amari Youth Hostel Dorm FM-240 (38234), Bay Grounds Shop FM-112 (38244), Building 33 FM-33 (38248), Building 34 FM-34 (38250), Building 35 FM-35 (38252), Building 36 FM-36 (38254), Building 37 FM-37 (38255), Building 38 FM-38 (38257), Building 39 FM-39 (38258), Building A Lower Ft. Mason FM-308 (38259), Building B Lower Ft.

Mason FM-310 (38262), Building C Lower Ft. Mason FM-312 (38263), Building D Lower Ft. Mason FM- 314 (38264), Garage FM-5 (38275), GOGA Headquarters FM-201 (38276), GOG SPUG FM-204 (38277), Guard Station FM-303 (38280), Laundry FM-32 (38281), Main Switching Station FM-248 (38286), Officer’s Nest Course FM-1 (38289), Pier 1 Shed Lower Ft. Mason FM-317 (38295), Pier 2 Shed Lower Ft.

Mason FM-319 (38298), Pier 3 Shed Lower Ft. Mason FM-321 (38300), Projects Offices FM-101 (38305), Quarter #2 – Brooks FM-2 (38307), Quarter #3 – Haskell FM-3 (38308), Quarter #4 – Palmer Fm-4 (38309), Quarter #7 FM-7 (38310), Quarter 41 FM-41 (38311), Quarter #42 FM-42 (38312), Quarter #43 FM-43 (38313), Quarter #44 FM-44 (38314), Quarter #46 FM-46 (38316), Quarter #48 FM-48 (38318), Quarter #49 FM-49 (38319), Quarter #50 FM-50 (38320), Quarters 231 FM-231 (38321), Quarters 232 FM- 232 (38322), Quarters 234 FM-234 (38323), Quarters 235 FM-235 (38324), Quarters 238 FM-238 (38325), Quarters 239 Fm-239 (38326), SFCC FM-102 (38337), Barracks AL-64 (38353), Electric Shop Al-89 (38356), Guardhouse AL-22 (38371), Model Industries Building AL-82 (38376), Morgue AL-12 (38377), New Parson Industries AL-84 (38378), Prison/Cell Block AL-68 (38383), Quartermaster AL-79 (38384), Storage Vault AL-218 (38395), Fog Signal Building PB-002 (40751), Lighthouse Point Benito PB-001 (40755), Quarters 17 PB-008 (40758), Quarters 18 PB-009 (40759), Quarters 19 PB-010 (40760), NIKE Test Building FA-963 (40771), American Youth Hostel FA-941 (40772), American Youth Hostel FA-937 (40774), Balloon Hanger FA-905 (40778), Headlands Center for Arts FA-940 (40815), Headlands Center for Arts FA-944 (40816), Headlands Center for Arts FA-945 (40817), Headlands Center for Arts FA-952 (40818), Headlands Center for Arts FA-961 (40820), Headlands Center for Arts FA-962 (40821), Headlands Institute FA-936 (40822), Lift Station Capehart FA-840 (40823), Lift Station Horse Stable FA- 841 (40824), Lift Station Rodeo Lake FA-931 (40825), NIKE Paint Storage FA-972 (40831), NIKE Sentry Station FA-970 (40832), Quarters 806 FA-806 (40847), Quarters 810 FA-810 (40854), Quarters 870 FA-870 (40899), Range Building FA-828 (40905), NIKE Generator Building FA-966 (41852), NIKE Sentry Station FA-976 (41857), NIKE Missile Warhead FA-967 (41861), Stable East FA-902 (41879), Stable West FA-

TABLE 1.0 - SUMMARY OF SUSPECT ACM

Golden Gate National Recreation Area

San Francisco, California

September 28, 2012

Table 1.0 - Page 37 of 220

Suspect Material Description Material Category

Associated Facility System

Homogeneous Material ID Substrate/Component

Suspect Material Classification

Building 38289 - Officer's Club-Nest Course FM1

Built-Up Roofing System Materials, Black Misc.Roof DeckGOGA.38289.010a Roof Assumed ACM

Roof Shingles, Green Misc.Roof DeckGOGA.38289.011a Roof Sampled

9" x 9" Floor Tile, Green Misc.WoodGOGA.38289.012a Floor Sampled

Floor Tile Mastic, Black Misc.WoodGOGA.38289.012b Floor Sampled

Covebase, Black Misc.WallboardGOGA.38289.013a Wall Sampled

Covebase Mastic, Brown Misc.WallboardGOGA.38289.013b Wall Sampled

Plaster, White SurfacingLatheGOGA.38289.014a Wall/Ceiling Sampled

Covebase, Brown Misc.WallboardGOGA.38289.015a Wall Sampled

Covebase Mastic, Brown Misc.WallboardGOGA.38289.015b Wall Sampled

12" x 12" Floor Tile, White Misc.ConcreteGOGA.38289.016a Floor Sampled

Floor Tile Mastic, Beige Misc.ConcreteGOGA.38289.016b Floor Sampled

12" x 12" Floor Tile, Brown Misc.ConcreteGOGA.38289.017a Floor Sampled

Floor Tile Mastic, Beige Misc.ConcreteGOGA.38289.017b Floor Sampled

2' x 4' Ceiling Tile (Lay-in), White Misc.Metal GridGOGA.38289.018a Ceiling Sampled

Mud Pipe Fitting, White TSIPipe RunsGOGA.38289.019a Hot Water Assumed ACM

Suspect Material Description Material Category

Associated Facility System

Homogeneous Material ID Substrate/Component

Suspect Material Classification

Building 38295 - Pier 1 Shed Lower FM (FM317)

Plaster, White SurfacingLatheGOGA.38295.001a Wall Sampled

Floor Tile Mastic, Black Misc.ConcreteGOGA.38295.002a Floor Sampled

Corrugated Paper Insulation, Gray TSIPipe RunsGOGA.38295.003a Steam Sampled

Plaster Base Coats, White SurfacingLatheGOGA.38295.004a Wall Sampled

San Francisco, California

September 28, 2012

Table 1.0 - Page 38 of 220

Suspect Material Description Material Category

Associated Facility System

Homogeneous Material ID Substrate/Component

Suspect Material Classification

Building 38295 - Pier 1 Shed Lower FM (FM317)

Wallboard Joint Compound, White Misc.Wall StudsGOGA.38295.004b Wall Sampled

12" x 12" Floor Tile, Light Brown, Brown Streaks Misc.ConcreteGOGA.38295.005a Floor Sampled

Floor Tile Mastic, Black Misc.ConcreteGOGA.38295.005b Floor Sampled

Pipe Insulation, Brown TSIPipe RunsGOGA.38295.006a Steam Sampled

Resilient Sheet Flooring, Red Misc.WoodGOGA.38295.007a Floor Sampled

Sheet Flooring Adhesive, Black Misc.WoodGOGA.38295.007b Floor Sampled

Pipe Insulation, White TSIPipe RunsGOGA.38295.008a Steam Sampled

Mud Pipe Fitting, White TSIPipe ElbowsGOGA.38295.009a Steam Sampled

1' x 1' Ceiling Tile (Glued), White, Pindot Misc.PlasterGOGA.38295.010a Ceiling Sampled

Ceiling Tile Adhesive, Brown Misc.PlasterGOGA.38295.010b Ceiling Sampled

1' x 1' Ceiling Tile (Glued), White, Fissured Misc.PlasterGOGA.38295.011a Ceiling Sampled

Ceiling Tile Adhesive, Brown Misc.PlasterGOGA.38295.011b Ceiling Sampled

9" x 9" Floor Tile, Black Misc.ConcreteGOGA.38295.012a Floor Sampled

Floor Tile Mastic, Black Misc.ConcreteGOGA.38295.012b Floor Sampled

9" x 9" Floor Tile, Red, White Streaks Misc.ConcreteGOGA.38295.013a Floor Sampled

Floor Tile Mastic, Black Misc.ConcreteGOGA.38295.013b Floor Sampled

9" x 9" Floor Tile, Dark Brown Misc.ConcreteGOGA.38295.014a Floor Sampled

Floor Tile Mastic, Gray Misc.ConcreteGOGA.38295.014b Floor Sampled

Carpet Mastic, Beige Misc.ConcreteGOGA.38295.015a Floor Sampled

12" x 12" Floor Tile, Green, White Streaks Misc.ConcreteGOGA.38295.016a Floor Sampled

Floor Tile Mastic, Beige Misc.ConcreteGOGA.38295.016b Floor Sampled

Window Glazing, White Misc.WindowsGOGA.38295.018a Building Exterior Sampled

San Francisco, California

September 28, 2012

Table 1.0 - Page 39 of 220

Suspect Material Description Material Category

Associated Facility System

Homogeneous Material ID Substrate/Component

Suspect Material Classification

Building 38295 - Pier 1 Shed Lower FM (FM317)

9" x 9" Floor Tile, Green, White Streaks Misc.ConcreteGOGA.38295.019a Floor Sampled

Floor Tile Mastic, Black Misc.ConcreteGOGA.38295.019b Floor Sampled

Covebase, Black Misc.WallboardGOGA.38295.020a Wall Sampled

Covebase Mastic, Black Misc.WallboardGOGA.38295.020b Wall Sampled

12" x 12" Floor Tile, Gray, Black and White Streaks Misc.ConcreteGOGA.38295.021a Floor Sampled

Floor Tile Mastic, Gray Misc.ConcreteGOGA.38295.021b Floor Sampled

Rolled Roofing, Red Misc.Roof DeckGOGA.38295.022a Roof Sampled

Suspect Material Description Material Category

Associated Facility System

Homogeneous Material ID Substrate/Component

Suspect Material Classification

Building 38298 - Pier 2 Shed, L. Ft. Mason (FM 319)

Floor Coating, Black Misc.FloorGOGA.38298.001a Floor Sampled

Wallboard, White Misc.Wall StudsGOGA.38298.002a Wall Sampled

Wallboard Joint Compound, White Misc.Wall StudsGOGA.38298.002b Wall Sampled

Window Glazing, Gray Misc.WindowsGOGA.38298.003a Building Exterior Sampled

12" x 12" Floor Tile, Black, White Streaks Misc.ConcreteGOGA.38298.004a Floor Sampled

Floor Tile Mastic, Beige Misc.ConcreteGOGA.38298.004b Floor Sampled

Plaster, White SurfacingLatheGOGA.38298.005a Wall Sampled

9" x 9" Floor Tile, Light Gray, White Streaks Misc.ConcreteGOGA.38298.006a Floor Sampled

Floor Tile Mastic, Black Misc.ConcreteGOGA.38298.006b Floor Sampled

Spray Applied Acoustical Finish, White SurfacingWallboardGOGA.38298.007a Ceiling Sampled

Wall Panel Adhesive, Beige Misc.WallboardGOGA.38298.008a Wall Sampled

Covebase, Black Misc.WallboardGOGA.38298.009a Wall Sampled

TABLE 2.0 - SUMMARY OF IDENTIFIED ACM

San Francisco, California

September 28, 2012

Table 2.0 - Page 15 of 87

Suspect Material Description Material Category

Associated Facility System

Homogeneous Material ID Substrate/Component

Suspect Material Classification

Building 38289 - Officer's Club-Nest Course FM1

Friability

9" x 9" Floor Tile, Green Misc.WoodGOGA.38289.012a Floor SampledNon-Friable

12" x 12" Floor Tile, Brown Misc.ConcreteGOGA.38289.017a Floor SampledNon-Friable

Mud Pipe Fitting, White TSIPipe RunsGOGA.38289.019a Hot Water Assumed ACMFriable

Suspect Material Description Material Category

Associated Facility System

Homogeneous Material ID Substrate/Component

Suspect Material Classification

Building 38295 - Pier 1 Shed Lower FM (FM317)

Friability

Floor Tile Mastic, Black Misc.ConcreteGOGA.38295.002a Floor SampledNon-Friable

Corrugated Paper Insulation, Gray TSIPipe RunsGOGA.38295.003a Steam SampledFriable

Wallboard Joint Compound, White Misc.Wall StudsGOGA.38295.004b Wall SampledFriable

12" x 12" Floor Tile, Light Brown, Brown Streaks Misc.ConcreteGOGA.38295.005a Floor SampledNon-Friable

Floor Tile Mastic, Black Misc.ConcreteGOGA.38295.005b Floor SampledNon-Friable

Pipe Insulation, White TSIPipe RunsGOGA.38295.008a Steam SampledFriable

Mud Pipe Fitting, White TSIPipe ElbowsGOGA.38295.009a Steam SampledFriable

9" x 9" Floor Tile, Black Misc.ConcreteGOGA.38295.012a Floor SampledNon-Friable

Floor Tile Mastic, Black Misc.ConcreteGOGA.38295.012b Floor SampledNon-Friable

9" x 9" Floor Tile, Red, White Streaks Misc.ConcreteGOGA.38295.013a Floor SampledNon-Friable

9" x 9" Floor Tile, Dark Brown Misc.ConcreteGOGA.38295.014a Floor SampledNon-Friable

Window Glazing, White Misc.WindowsGOGA.38295.018a Building Exterior SampledNon-Friable

9" x 9" Floor Tile, Green, White Streaks Misc.ConcreteGOGA.38295.019a Floor SampledNon-Friable

12" x 12" Floor Tile, Gray, Black and White Streaks Misc.ConcreteGOGA.38295.021a Floor SampledNon-Friable

APPENDIX A - BUILDING SUMMARY

San Francisco, California

September 28, 2012

Building Size: 48,000 SF

ACM Identified

Construction Date: 1934

Building Use: Pier 1 Shed Lower FM (FM317)

Building 38295 - Pier 1 Shed Lower FM (FM317)

Previous Expense:

Current Expense:

Future Asbestos Clean-up Costs:

$0

$21,685

$105,372

Building Size: 53,295 SF

ACM Identified

Construction Date: 1912

Building Use: Pier 2 Shed, L. Ft. Mason (FM 319)

Building 38298 - Pier 2 Shed, L.

Ft. Mason (FM 319)

Previous Expense:

Current Expense:

Future Asbestos Clean-up Costs:

$0

$24,077

$1,500

APPENDIX B - NON-ACM DETAIL AND PHOTOGRAPHS

Building 38295 - Homogeneous Material GOGA-38295-001

Material Description Associated System Sampled/Assumed

Material Information

HM ID

Substrate/

Component (001a) Plaster, White Lathe Wall SampledGOGA.38295.001a

HM # Sample Location Lab Results

Bulk Sample Data

Sample ID Level 1 - Boiler Room None Detected001aB38295.001

Level 1 - Boiler Room None Detected001aB38295.002

Level 1 - Boiler Room None Detected001aB38295.003

Level 1 - Restroom None Detected001aB38295.004

Level 2 - Hall None Detected001aB38295.005

Golden Gate National Recreation Area San Francisco, California

September 28, 2012 Appendix B Page 315 of 1734

Building 38295 - Homogeneous Material GOGA-38295-004

Material Description Associated System Sampled/Assumed

Material Information

HM ID

Substrate/

Component (004a) Plaster Base Coats, White Lathe Wall SampledGOGA.38295.004a

HM # Sample Location Lab Results

Bulk Sample Data

Sample ID Level 1 - Storage None Detected004aB38295.011

Level 1 - Office None Detected004aB38295.012

Level 2 - Office None Detected004aB38295.013

Level 2 - Office None Detected004aB38295.014

Level 2 - Office None Detected004aB38295.015

Golden Gate National Recreation Area San Francisco, California

Appendix B Page 316 of 1734

Building 38295 - Homogeneous Material GOGA-38295-006

Material Description Associated System Sampled/Assumed

Material Information

HM ID

Substrate/

Component (006a) Pipe Insulation, Brown Pipe Runs Steam SampledGOGA.38295.006a

HM # Sample Location Lab Results

Bulk Sample Data

Sample ID Level 1 - No Access None Detected006aB38295.018

Level 1 - No Access None Detected006aB38295.019

Level 1 - No Access None Detected006aB38295.020

Golden Gate National Recreation Area San Francisco, California

Appendix B Page 317 of 1734

Building 38295 - Homogeneous Material GOGA-38295-007

Material Description Associated System Sampled/Assumed

Material Information

HM ID

Substrate/

Component (007a) Resilient Sheet Flooring, Red Wood Floor SampledGOGA.38295.007a

(007b) Sheet Flooring Adhesive, Black Wood Floor SampledGOGA.38295.007b

HM # Sample Location Lab Results

Bulk Sample Data

Sample ID Level 1 - No Access None Detected007aB38295.021

Level 1 - No Access None Detected007bB38295.021

Level 1 - No Access None Detected007aB38295.022

Level 1 - No Access None Detected007bB38295.022

Golden Gate National Recreation Area San Francisco, California

Appendix B Page 318 of 1734

Building 38295 - Homogeneous Material GOGA-38295-010

Material Description Associated System Sampled/Assumed

Material Information

HM ID

Substrate/

Component (010a) 1' x 1' Ceiling Tile (Glued), White, Pindot Plaster Ceiling SampledGOGA.38295.010a

(010b) Ceiling Tile Adhesive, Brown Plaster Ceiling SampledGOGA.38295.010b

HM # Sample Location Lab Results

Bulk Sample Data

Sample ID Level 1 - Office None Detected010aB38295.029

Level 1 - Office None Detected010bB38295.029

Level 1 - Office None Detected010aB38295.030

Level 1 - Office None Detected010bB38295.030

Golden Gate National Recreation Area San Francisco, California

Appendix B Page 319 of 1734

Building 38295 - Homogeneous Material GOGA-38295-011

Material Description Associated System Sampled/Assumed

Material Information

HM ID

Substrate/

Component (011a) 1' x 1' Ceiling Tile (Glued), White, Fissured Plaster Ceiling SampledGOGA.38295.011a

(011b) Ceiling Tile Adhesive, Brown Plaster Ceiling SampledGOGA.38295.011b

HM # Sample Location Lab Results

Bulk Sample Data

Sample ID Level 1 - Office None Detected011aB38295.031

Level 1 - Office None Detected011bB38295.031

Level 1 - Office None Detected011aB38295.032

Level 1 - Office None Detected011bB38295.032

Golden Gate National Recreation Area San Francisco, California

Appendix B Page 320 of 1734

Building 38295 - Homogeneous Material GOGA-38295-013

Material Description Associated System Sampled/Assumed

Material Information

HM ID

Substrate/

Component (013b) Floor Tile Mastic, Black Concrete Floor SampledGOGA.38295.013b

HM # Sample Location Lab Results

Bulk Sample Data

Sample ID Level 2 - Hall None Detected013bB38295.035

Level 2 - Hall None Detected013bB38295.036

Golden Gate National Recreation Area San Francisco, California

Appendix B Page 321 of 1734

Building 38295 - Homogeneous Material GOGA-38295-014

Material Description Associated System Sampled/Assumed

Material Information

HM ID

Substrate/

Component (014b) Floor Tile Mastic, Gray Concrete Floor SampledGOGA.38295.014b

HM # Sample Location Lab Results

Bulk Sample Data

Sample ID Level 2 - Hall None Detected014bB38295.037

Level 2 - Hall None Detected014bB38295.038

Golden Gate National Recreation Area San Francisco, California

Appendix B Page 322 of 1734

Building 38295 - Homogeneous Material GOGA-38295-015

Material Description Associated System Sampled/Assumed

Material Information

HM ID

Substrate/

Component (015a) Carpet Mastic, Beige Concrete Floor SampledGOGA.38295.015a

HM # Sample Location Lab Results

Bulk Sample Data

Sample ID Level 2 - Hall None Detected015aB38295.039

Level 2 - Office None Detected015aB38295.040

Golden Gate National Recreation Area San Francisco, California

Appendix B Page 323 of 1734

Building 38295 - Homogeneous Material GOGA-38295-016

Material Description Associated System Sampled/Assumed

Material Information

HM ID

Substrate/

Component (016a) 12" x 12" Floor Tile, Green, White

Streaks Concrete Floor SampledGOGA.38295.016a

(016b) Floor Tile Mastic, Beige Concrete Floor SampledGOGA.38295.016b

HM # Sample Location Lab Results

Bulk Sample Data

Sample ID Level 2 - Hall None Detected016aB38295.041

Level 2 - Hall None Detected016bB38295.041

Level 2 - Hall None Detected016aB38295.042

Level 2 - Hall None Detected016bB38295.042

Golden Gate National Recreation Area San Francisco, California

Appendix B Page 324 of 1734

Building 38295 - Homogeneous Material GOGA-38295-019

Material Description Associated System Sampled/Assumed

Material Information

HM ID

Substrate/

Component (019b) Floor Tile Mastic, Black Concrete Floor SampledGOGA.38295.019b

HM # Sample Location Lab Results

Bulk Sample Data

Sample ID Level 2 - Office None Detected019bB38295.045

Level 2 - Office None Detected019bB38295.046

Golden Gate National Recreation Area San Francisco, California

Appendix B Page 325 of 1734

Building 38295 - Homogeneous Material GOGA-38295-020

Material Description Associated System Sampled/Assumed

Material Information

HM ID

Substrate/

Component (020a) Covebase, Black Wallboard Wall SampledGOGA.38295.020a

(020b) Covebase Mastic, Black Wallboard Wall SampledGOGA.38295.020b

HM # Sample Location Lab Results

Bulk Sample Data

Sample ID Level 2 - Office None Detected020aB38295.047

Level 2 - Office None Detected020bB38295.047

Level 2 - Office None Detected020aB38295.048

Level 2 - Office None Detected020bB38295.048

Golden Gate National Recreation Area San Francisco, California

Appendix B Page 326 of 1734

Building 38295 - Homogeneous Material GOGA-38295-021

Material Description Associated System Sampled/Assumed

Material Information

HM ID

Substrate/

Component (021b) Floor Tile Mastic, Gray Concrete Floor SampledGOGA.38295.021b

HM # Sample Location Lab Results

Bulk Sample Data

Sample ID Level 2 - Office None Detected021bB38295.049

Level 2 - Office None Detected021bB38295.050

Golden Gate National Recreation Area San Francisco, California

Appendix B Page 327 of 1734

Building 38295 - Homogeneous Material GOGA-38295-022

Material Description Associated System Sampled/Assumed

Material Information

HM ID

Substrate/

Component (022a) Rolled Roofing, Red Roof Deck Roof SampledGOGA.38295.022a

HM # Sample Location Lab Results

Bulk Sample Data

Sample ID Roof None Detected022aB38295.051

Roof None Detected022aB38295.052

Golden Gate National Recreation Area San Francisco, California

Appendix B Page 328 of 1734

APPENDIX C - ACM DETAIL AND PHOTOGRAPHS

Building 38295 - Homogeneous Material GOGA-38295-002

Material Description Associated System Sampled/Assumed

Material Information

HM ID

Substrate/

Component (002a) Floor Tile Mastic, Black Concrete Floor SampledGOGA.38295.002a

HM # Sample Location Lab Results

Bulk Sample Data

Sample ID Level 1 - Boiler Room 5% Chrysotile002aB38295.006

Level 1 - Boiler Room 5% Chrysotile002aB38295.007

Material Locations and Condition

Material Location Quantity ConditionHM Level 1 - Boiler Room >25% Localized Damage100 S.F.002a

Golden Gate National Recreation Area San Francisco, California

Appendix C Page 156 of 878

Building 38295 - Homogeneous Material GOGA-38295-003

Material Description Associated System Sampled/Assumed

Material Information

HM ID

Substrate/

Component (003a) Corrugated Paper Insulation, Gray Pipe Runs Steam SampledGOGA.38295.003a

HM # Sample Location Lab Results

Bulk Sample Data

Sample ID Level 1 - Closet 48% Chrysotile/Amosite003aB38295.008

Level 1 - Closet 48% Chrysotile/Amosite003aB38295.009

Level 1 - Closet 65% Chrysotile003aB38295.010

Material Locations and Condition

Material Location Quantity ConditionHM Level 1 - Closet <1% Damage8 L.F.003a

Golden Gate National Recreation Area San Francisco, California

Appendix C Page 157 of 878

Building 38295 - Homogeneous Material GOGA-38295-004

Material Description Associated System Sampled/Assumed

Material Information

HM ID

Substrate/

Component (004b) Wallboard Joint Compound, White Wall Studs Wall SampledGOGA.38295.004b

HM # Sample Location Lab Results

Bulk Sample Data

Sample ID Level 1 - Storage None Detected004bB38295.011

Level 1 - Office 2% Chrysotile004bB38295.012

Level 2 - Office 2% Chrysotile004bB38295.013

Level 2 - Office None Detected004bB38295.014

Level 2 - Office Trace Chrysotile004bB38295.015

Material Locations and Condition

Material Location Quantity ConditionHM Level 1 - Restroom <1% Damage558 S.F.004b

Level 1 - Storage <1% Damage644 S.F.004b

Level 1 - Misc <1% Damage204 S.F.004b

Level 1 - Office <1% Damage716 S.F.004b

Level 2 - Office <1% Damage128 S.F.004b

Level 2 - Office <1% Damage223 S.F.004b

Level 2 - Office <1% Damage236 S.F.004b

Level 2 - Misc <1% Damage160 S.F.004b

Golden Gate National Recreation Area San Francisco, California

Appendix C Page 158 of 878

Building 38295 - Homogeneous Material GOGA-38295-005

Material Description Associated System Sampled/Assumed

Material Information

HM ID

Substrate/

Component (005a) 12" x 12" Floor Tile, Light Brown, Brown Streaks Concrete Floor SampledGOGA.38295.005a

(005b) Floor Tile Mastic, Black Concrete Floor SampledGOGA.38295.005b

HM # Sample Location Lab Results

Bulk Sample Data

Sample ID Level 1 - Storage 2% Chrysotile005aB38295.016

Level 1 - Storage 5% Chrysotile005bB38295.016

Level 1 - Storage 3% Chrysotile005aB38295.017

Level 1 - Storage 5% Chrysotile005bB38295.017

Material Locations and Condition

Material Location Quantity ConditionHM Level 1 - Storage <1% Damage196 S.F.005a

Level 1 - Storage <1% Damage196 S.F.005b

Golden Gate National Recreation Area San Francisco, California

Appendix C Page 159 of 878

Building 38295 - Homogeneous Material GOGA-38295-008

Material Description Associated System Sampled/Assumed

Material Information

HM ID

Substrate/

Component (008a) Pipe Insulation, White Pipe Runs Steam SampledGOGA.38295.008a

HM # Sample Location Lab Results

Bulk Sample Data

Sample ID Level 1 - No Access 15% Chrysotile/Amosite008aB38295.023

Level 1 - No Access 15% Chrysotile/Amosite008aB38295.024

Level 1 - No Access 18% Chrysotile/Amosite008aB38295.025

Material Locations and Condition

Material Location Quantity ConditionHM Level 1 - Main <1% Damage144 L.F.008a

Level M - Mezz above 5 <1% Damage12 L.F.008a

Golden Gate National Recreation Area San Francisco, California

Appendix C Page 160 of 878

Building 38295 - Homogeneous Material GOGA-38295-009

Material Description Associated System Sampled/Assumed

Material Information

HM ID

Substrate/

Component (009a) Mud Pipe Fitting, White Pipe Elbows Steam SampledGOGA.38295.009a

HM # Sample Location Lab Results

Bulk Sample Data

Sample ID Level 1 - No Access 18% Chrysotile/Amosite009aB38295.026

Level 1 - No Access 17% Chrysotile/Amosite009aB38295.027

Level 1 - No Access 17% Chrysotile/Amosite009aB38295.028

Material Locations and Condition

Material Location Quantity ConditionHM Level M - Mezz above 5 <1% Damage2 Each009a

Golden Gate National Recreation Area San Francisco, California

Appendix C Page 161 of 878

Building 38295 - Homogeneous Material GOGA-38295-012

Material Description Associated System Sampled/Assumed

Material Information

HM ID

Substrate/

Component (012a) 9" x 9" Floor Tile, Black Concrete Floor SampledGOGA.38295.012a

(012b) Floor Tile Mastic, Black Concrete Floor SampledGOGA.38295.012b

HM # Sample Location Lab Results

Bulk Sample Data

Sample ID Level 1 - Stairs 3% Chrysotile012aB38295.033

Level 1 - Stairs 2% Chrysotile012bB38295.033

Level 1 - Stairs 3% Chrysotile012aB38295.034

Level 1 - Stairs 3% Chrysotile012bB38295.034

Material Locations and Condition

Material Location Quantity ConditionHM Level 1 - Stairs <1% Damage0 S.F.012a

Level 2 - Misc <1% Damage16 S.F.012a

Level 1 - Stairs <1% Damage0 S.F.012b

Level 2 - Misc <1% Damage16 S.F.012b

Golden Gate National Recreation Area San Francisco, California

Appendix C Page 162 of 878

Building 38295 - Homogeneous Material GOGA-38295-013

Material Description Associated System Sampled/Assumed

Material Information

HM ID

Substrate/

Component (013a) 9" x 9" Floor Tile, Red, White Streaks Concrete Floor SampledGOGA.38295.013a

HM # Sample Location Lab Results

Bulk Sample Data

Sample ID Level 2 - Hall 3% Chrysotile013aB38295.035

Level 2 - Hall 5% Chrysotile013aB38295.036

Material Locations and Condition

Material Location Quantity ConditionHM Level 2 - Misc <1% Damage200 S.F.013a

Level 2 - Hall <1% Damage32 S.F.013a

Level 2 - Office <1% Damage180 S.F.013a

Level 2 - Misc <1% Damage560 S.F.013a

Golden Gate National Recreation Area San Francisco, California

Appendix C Page 163 of 878

Building 38295 - Homogeneous Material GOGA-38295-014

Material Description Associated System Sampled/Assumed

Material Information

HM ID

Substrate/

Component (014a) 9" x 9" Floor Tile, Dark Brown Concrete Floor SampledGOGA.38295.014a

HM # Sample Location Lab Results

Bulk Sample Data

Sample ID Level 2 - Hall 2% Chrysotile014aB38295.037

Level 2 - Hall 3% Chrysotile014aB38295.038

Material Locations and Condition

Material Location Quantity ConditionHM Level 2 - Hall <1% Damage42 S.F.014a

Level 2 - Office <1% Damage132 S.F.014a

Golden Gate National Recreation Area San Francisco, California

Appendix C Page 164 of 878

Building 38295 - Homogeneous Material GOGA-38295-018

Material Description Associated System Sampled/Assumed

Material Information

HM ID

Substrate/

Component (018a) Window Glazing, White Windows Building Exterior SampledGOGA.38295.018a

HM # Sample Location Lab Results

Bulk Sample Data

Sample ID Level 2 - Office 0.21% Chrysotile018aB38295.043

Level 2 - Office None Detected018aB38295.044

Material Locations and Condition

Material Location Quantity ConditionHM Level 1 - Main <1% Damage5472 L.F.018a

Level 2 - Misc <1% Damage5472 L.F.018a

Level 2 - Office <1% Damage240 L.F.018a

Level 2 - Office <1% Damage96 L.F.018a

Level 2 - Office <1% Damage96 L.F.018a

Level 2 - Misc <1% Damage240 L.F.018a

Level 2 - Misc <1% Damage96 L.F.018a

Level 2 - Misc <1% Damage132 L.F.018a

Level 2 - Office <1% Damage108 L.F.018a

Level 2 - Misc <1% Damage336 L.F.018a

Golden Gate National Recreation Area San Francisco, California

Appendix C Page 165 of 878

Building 38295 - Homogeneous Material GOGA-38295-019

Material Description Associated System Sampled/Assumed

Material Information

HM ID

Substrate/

Component (019a) 9" x 9" Floor Tile, Green, White Streaks Concrete Floor SampledGOGA.38295.019a

HM # Sample Location Lab Results

Bulk Sample Data

Sample ID Level 2 - Office 2% Chrysotile019aB38295.045

Level 2 - Office 2% Chrysotile019aB38295.046

Material Locations and Condition

Material Location Quantity ConditionHM Level 2 - Office <1% Damage132 S.F.019a

Level 2 - Misc <1% Damage99 S.F.019a

Golden Gate National Recreation Area San Francisco, California

Appendix C Page 166 of 878

Building 38295 - Homogeneous Material GOGA-38295-021

Material Description Associated System Sampled/Assumed

Material Information

HM ID

Substrate/

Component (021a) 12" x 12" Floor Tile, Gray, Black and

White Streaks Concrete Floor SampledGOGA.38295.021a

HM # Sample Location Lab Results

Bulk Sample Data

Sample ID Level 2 - Office 2% Chrysotile021aB38295.049

Level 2 - Office 2% Chrysotile021aB38295.050

Material Locations and Condition

Material Location Quantity ConditionHM Level 2 - Office <1% Damage384 S.F.021a

Golden Gate National Recreation Area San Francisco, California

Appendix C Page 167 of 878

Final Report

Bulk Asbestos Analysis (EPA Method 600/R-93-116, Visual Area Estimation)

Forensic Analytical Laboratories

A31417Client ID:Mactec Engineering & Consulting Inc B151739Report Number:Tod Dawson

Date Received:396 Plasters Avenue NE 07/27/11Date Analyzed:

07/27/11Date Printed:Atlanta, GA 30324

First Reported:

A31417-86141-10-0320 - GOGA - Building Number 38295 - PO# 201108307 FALI Job ID:Job ID/Site:

Date(s) Collected: 06/08/2011

07/13/11

07/27/11

Sample ID Lab Number Asbestos

Type Percent in

Layer Asbestos AsbestosPercent in Percent in

Type TypeLayer Layer

1_1_a 11141253 Layer: Off-White Plaster ND Layer: Paint ND

Asbestos (ND)Total Composite Values of Fibrous Components:

Cellulose (Trace)

2_1_a 11141254 Layer: Off-White Plaster ND Layer: Paint ND

Asbestos (ND)Total Composite Values of Fibrous Components:

Cellulose (Trace)

3_1_a 11141255 Layer: Off-White Plaster ND Layer: White Plaster ND Layer: Paint ND

Asbestos (ND)Total Composite Values of Fibrous Components:

Cellulose (Trace)

4_1_a 11141256 Layer: Off-White Plaster ND Layer: Paint ND

Asbestos (ND)Total Composite Values of Fibrous Components:

Cellulose (Trace)

5_1_a 11141257 Layer: Off-White Plaster ND Layer: White Plaster ND Layer: Paint ND

Asbestos (ND)Total Composite Values of Fibrous Components:

Cellulose (Trace)

6_2_a 11141258 Layer: Black Mastic Chrysotile 5 %

Asbestos (5%)Total Composite Values of Fibrous Components:

Cellulose (Trace)

3777 Depot Road, Suite 409, Hayward, CA 94545 / Telephone: (510) 887-8828 (800) 827-FASI / Fax: (510) 887-4218

Final Report

Bulk Asbestos Analysis (EPA Method 600/R-93-116, Visual Area Estimation)

Forensic Analytical Laboratories

A31417Client ID:AMEC B161670Report Number:Tod Dawson

Date Received:396 Plasters Avenue NE 04/23/12Date Analyzed:

04/25/12Date Printed:Atlanta, GA 30324

First Reported:

A31417-86141-10-0320 - GOGA - Building Number 41986 - PO # 201108307 FALI Job ID:Job ID/Site:

Date(s) Collected: 03/15/2012

03/22/12

04/25/12

Sample ID Lab Number Asbestos

Type Percent in

Layer Asbestos AsbestosPercent in Percent in

Type TypeLayer Layer

1_1_a 11238291 Layer: White Drywall ND

Asbestos (ND)Total Composite Values of Fibrous Components:

Cellulose (20 %)

1_1_b 11238292 Layer: Off-White Joint Compound ND

Asbestos (ND)Total Composite Values of Fibrous Components:

Cellulose (Trace)

1_1_c 11238293 Layer: Off-White Texture ND Layer: Paint ND

Asbestos (ND)Total Composite Values of Fibrous Components:

Cellulose (Trace)

2_1_a 11238294 Layer: White Drywall ND

Asbestos (ND)Total Composite Values of Fibrous Components:

Cellulose (20 %)

2_1_b 11238295 Layer: Off-White Joint Compound ND

Asbestos (ND)Total Composite Values of Fibrous Components:

Cellulose (Trace)

2_1_c 11238296 Layer: Off-White Texture ND Layer: Paint ND

Asbestos (ND)Total Composite Values of Fibrous Components:

Cellulose (Trace)

3_1_b 11238297 Layer: Off-White Joint Compound ND Layer: Paint ND

Asbestos (ND)Total Composite Values of Fibrous Components:

Cellulose (Trace)

3777 Depot Road, Suite 409, Hayward, CA 94545 / Telephone: (510) 887-8828 (800) 827-FASI / Fax: (510) 887-4218