This document outlines requirements for a Simplified Acquisition of Base Engineer Requirements (SABER) Indefinite Delivery Indefinite Quantity (IDIQ) contract to provide maintenance, repair, minor and new construction work at Joint Base Langley-Eustis in Virginia. Key details include: the contract is a single award IDIQ with a base year and four option years for a total potential value of $95 million; work will be on real property at JBLE; the competition is limited to 8(a) small businesses headquartered in SBA Region III which includes Delaware, Maryland, Pennsylvania, Virginia, Washington D.C. and West Virginia; the contract type is firm-fixed-price; a site visit will be held on 19 March 2021.
View the file
Other files
Show all 40
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Fort Eustis System Status, All
| FORT EUSTIS SUMMARY OF BUILDER UNIFORMAT II DATA COLLECTION -- ALL SYSTEMS | ||||||
| System (Level 2) | Req'd Sys by AFCEC? | Component | ||||
| (Level 3) | Section (Level 4) | Barcode Requirement | Applicable comments on sections inventoried and not inventoried | |||
| B20 EXTERIOR ENCLOSURE | Yes | B2010 EXTERIOR WALLS | B201001 EXTERIOR CLOSURE | No | ||
| B201002 EXTERIOR WALL BACKUP CONSTRUCTION | No | |||||
| B201003 INSULATION AND VAPOR RETARDER | No | |||||
| B201004 PARAPETS | No | |||||
| B201005 EXTERIOR LOUVERS AND SCREENS | No | |||||
| B201006 BALCONY WALLS AND HANDRAILS | No | |||||
| No | ||||||
| B201007 EXTERIOR SOFFITS | No | |||||
| B201008 FLASHING | No | |||||
| B201009 EXTERIOR PAINTING AND SPECIAL COATINGS | No | |||||
| B201010 EXTERIOR JOINT SEALANT | No | |||||
| B201011 SUN CONTROL DEVICES | No | |||||
| B201012 SCREEN WALLS | No | |||||
| B201090 OTHER EXTERIOR WALLS | No | |||||
| B2020 EXTERIOR WINDOWS | B202001 WINDOWS | No | ||||
| B202002 STOREFRONTS | No | |||||
| B202003 CURTAIN WALLS | No | |||||
| B202090 OTHER EXTERIOR WINDOWS | No | |||||
| B2030 EXTERIOR DOORS | B203001 SOLID DOORS | No | ||||
| B203002 GLAZED DOORS | No | |||||
| B203003 REVOLVING DOORS | No | |||||
| B203004 OVERHEAD AND ROLL-UP DOORS | No | |||||
| B203005 HANGAR DOORS | No | |||||
| B203006 BLAST RESISTANT DOORS | No | |||||
| B203007 GATES | No | |||||
| B203008 EXTERIOR DOOR HARDWARE | No | |||||
| B203090 OTHER EXTERIOR SPECIALTY DOORS | No | |||||
| B203091 OTHER EXTERIOR PERSONNEL DOORS | No | |||||
| B30 ROOFING | Yes | B3010 ROOF COVERINGS | B301001 STEEP SLOPE ROOF SYSTEMS | No | Need Photographs | |
| B301002 LOW SLOPE ROOF SYSTEMS | No | Need Photographs | ||||
| B301003 ROOF INSULATION & FILL | No | |||||
| B301004 FLASHINGS AND TRIM | No | |||||
| B301005 GUTTERS & DOWNSPOUTS | No | |||||
| B301006 ROOF OPENINGS AND SUPPORTS | No | |||||
| B301090 OTHER ROOFING | No | |||||
| C10 INTERIOR CONSTRUCTION | Yes | C1010 PARTITIONS | C101001 FIXED PARTITIONS | No | ||
| C101002 DEMOUNTABLE PARTITIONS | No | |||||
| C101003 RETRACTABLE PARTITIONS | No | |||||
| C101004 INTERIOR GUARDRAILS & SCREENS | No | |||||
| C101005 INTERIOR WINDOWS | No | |||||
| C101006 GLAZED PARTITIONS & STOREFRONTS | No | |||||
| C101007 INTERIOR GLAZING | No | |||||
| C101008 INTERIOR JOINT SEALANT | No | |||||
| C101090 OTHER PARTITIONS | No | |||||
| C1020 INTERIOR DOORS | C102001 STANDARD INTERIOR DOORS | No | ||||
| C102002 GLAZED INTERIOR DOORS | No | |||||
| C102003 FIRE DOORS | No | |||||
| C102004 SLIDING & FOLDING DOORS | No | |||||
| C102005 INTERIOR OVERHEAD DOORS | No | |||||
| C102006 INTERIOR GATES | No | |||||
| C102007 INTERIOR DOOR HARDWARE | No | |||||
| C102090 OTHER INTERIOR SPECIALTY DOORS | No | |||||
| C102091 OTHER INTERIOR PERSONNEL DOORS | No | |||||
| C1030 SPECIALTIES | C103001 COMPARTMENTS, CUBICLES & TOILET PARTITIONS | No | ||||
| C103002 TOILET & BATH ACCESSORIES | No | |||||
| C103003 MARKER BOARDS & TACK BOARDS | No | |||||
| C103004 IDENTIFYING DEVICES | No | |||||
| C103005 LOCKERS | No | |||||
| C103006 SHELVING | No | |||||
| C103007 FIRE EXTINGUISHER CABINETS | No | |||||
| C103008 COUNTERS | No | |||||
| C103009 CABINETS | No | |||||
| C103010 CASEWORK | No | |||||
| C103011 CLOSETS | No | |||||
| C103012 FIRESTOPPING PENETRATIONS | No | |||||
| C103013 SPRAYED FIRE RESISTANT MATERIALS | No | |||||
| C103014 ENTRANCE FLOOR GRILLS & MATS | No | |||||
| C103015 ORNAMETAL METAL WORK | No | |||||
| C103090 OTHER INTERIOR SPECIALTIES | No | |||||
| C20 STAIRS | No | Not applicable | Not applicable | No | ||
| C30 INTERIOR FINISHES | No | Not applicable | Not applicable | No | ||
| D20 PLUMBING * | Yes | D2010 PLUMBING FIXTURES | D201001 WATERCLOSETS | No | ||
| D201002 URINALS | No | |||||
| D201003 LAVATORIES | No | |||||
| D201004 SINKS | No | |||||
| D201005 SHOWERS/TUBS | No | |||||
| D201006 DRINKING FOUNTAINS AND COOLERS | No | |||||
| D201090 OTHER PLUMBING FIXTURES | Yes | Eye wash and eye wash / shower units that are hard piped. | ||||
| D2020 DOMESTIC WATER DISTRIBUTION | D202001 PIPES & FITTINGS | No | Distribution measurement | |||
| D202002 VALVES & HYDRANTS | Yes | Domestic water backflow preventers ≥ 1" only (no faucets or hose bibs). | ||||
| D202003 DOMESTIC WATER EQUIPMENT | Yes | 1. Yes, Pumps ≥ 1 hp and tanks/water heaters ≥ 50 gal. |
2. No, for water treatment, heat transfer package
| D202004 INSULATION & IDENTIFICATION | No | ||
| D202005 SPECIALTIES | No | ||
| D202006 BALL VALVES | No | ||
| D202007 GATE VALVES | No | ||
| D202008 VALVES, NON DRAIN | No | ||
| D202009 BUTTERFLY VALVES | No | ||
| D2020010 FLOW CONTROL VALVES | No | ||
| D2020011 GLOBE VALVES | No | ||
| D202012 PLUG VALVES | No | ||
| D2020013 SELENOID VALVES | No | ||
| D2020014 CHECK VALVES | No | ||
| D2020015 OTHER VALVES | No | ||
| D202090 OTHER DOMESTIC WATER SUPPLY | No | ||
| D202091 OTHER AUXILIARY EQUIPMENT | No | ||
| D2030 SANITARY WASTE | D203001 WASTE PIPE & FITTINGS | No | |
| D203002 VENT PIPE & FITTINGS | No | ||
| D203003 FLOOR DRAINS | No | ||
| D203004 SANITARY AND VENT EQUIPMENT | No | ||
| D203005 INSULATION & IDENTIFICATION | No | ||
| D203090 OTHER SANITARY WASTE | No | ||
| D2040 RAIN WATER DRAINAGE | D204001 PIPE & FITTINGS | No | |
| D204002 ROOF DRAINS | No | ||
| D204003 RAINWATER DRAINAGE EQMT | Yes | Sump pumps ≥ 1 hp. No other items in this category. | |
| D204004 INSULATION & IDENTIFICATION | No | ||
| D204090 OTHER RAIN WATER DRAINAGE | No | ||
| D2090 OTHER PLUMBING SYSTEMS | D209001 SPECIAL PIPING SYSTEMS | No | |
| D209002 ACID WASTE SYSTEMS | No | ||
| D209003 INTERCEPTORS | No | ||
| D209004 POOL PIPING AND EQUIPMENT | No | ||
| D209005 COMPRESSED AIR SYSTEM (NON-BREATHING) | Yes | 1. Compressors ≥ 1 hp |
2. Tanks ≥ 50 gal
3. Air dryers that are separate from the compressors.
| D209090 OTHER SPECIAL PLUMBING SYS | Yes | Oil / Water separators. Only if nameplate above ground. | |||
| D30 HVAC * | Yes | D3010 ENERGY SUPPLY | D301001 OIL SUPPLY SYSTEM | Yes | Heat oil tanks ≥ 50 gal |
| D301002 GAS SUPPLY SYSTEM | Yes | Fuel oil tanks ≥ 50 gal | |||
| D301003 STEAM SUPPLY SYSTEM (FROM CENTRAL PLANT) | No | Equipment is captured within the central plant building. | |||
| D301004 HOT WATER SUPPLY SYSTEM (FROM CENTRAL PLANT) | No | Equipment is captured within the central plant building. | |||
| D301005 SOLAR SYSTEM | Yes | Solar hot water equipment such as evacuated tube collector, flat plate collector, etc. | |||
| D301090 OTHER ENERGY SUPPLY | Yes | 1. Ice bank |
2. Tanks ≥ 50 gal; buffer tanks and thermal storage tanks ≥ 50 gal
| D3020 HEAT GENERATING SYSTEMS | D302001 BOILERS | Yes | All boiler types, all sizes. | ||
| D302002 FURNACES | Yes | Electric duct heater and furnaces | |||
| D302003 FUEL-FIRED UNIT HEATERS | Yes | All | |||
| D302004 AUXILIARY EQUIPMENT | Yes | All auxiliary boiler equipment ≥ 50 gal to include boiler feed water tanks, chemical feed water tanks, and expansion tanks. | |||
| D302005 EQUIPMENT THERMAL INSULATION | No | ||||
| D302090 OTHER HEAT SYSTEMS | Yes | ||||
| D3030 COOLING GENERATING SYSTEMS | D303001 CHILLED WATER SYSTEMS | Yes | Chillers and cooling towers. | ||
| D303002 DIRECT EXPANSION SYSTEMS | Yes | Any outdoor portion of a split DX system and packaged rooftop units. | |||
| D303004 AUXILIARY EQUIPMENT | Yes | Auxiliary chiller equipment ≥ 50 gal to include expansion tanks. | |||
| D30 HVAC (Continued) * | Yes | D3040 DISTRIBUTION SYSTEMS | D304001 AIR DISTRIBUTION, HEATING & COOLING | Yes | 1. All eqmt; Air separators, humidifiers, and dehumidifiers and VAV boxes. |
D304002 STEAM DISTRIBUTION SYSTEMS Yes 1. All eqmt; Pressure reducing stations inside the building, not part of the upper tier of distribution.
D304003 HOT WATER DISTRIBUTION SYSTEMS Yes 1. All eqmt; Heat exchangers and hot water pumps and condensate return pumps ≥ 1 hp.
2. Do not inventory other components that are distribution quantities related to ductwork or piping.
| D304004 CHANGE OVER DISTRIBUTION SYSTEMS | Yes | This is for a "dual temp" system, but General, Other, and Unknown. |
| D304005 GLYCOL DISTRIBUTION SYSTEMS | Yes | 1. All eqmt; Complete systems with holding tank, pump, controls ≥50 gal. |
2. Do not inventory other components that are distribution quantities related to ductwork or piping.
D304006 CHILLED WATER DISTRIBUTION SYSTEMS Yes 1. All eqmt; chilled water, condenser water, dual temp water, and glycol pumps ≥ 1 hp.
2. Do not inventory other components that are distribution quantities related to ductwork or piping.
| D304007 EXHAUST SYSTEMS | Yes | Powered ventilation / exhaust systems (no passive vents) to include exhausts for dust collection, glove box, and fume exhaust hood. | ||
| D304008 AIR HANDLING UNITS | Yes | All major air handling units. | ||
| D304090 OTHER DISTRIBUTION SYSTEMS | Yes | Special or unique items as required. | ||
| Yes | D3050 TERMINAL & PACKAGE UNITS | D305001 UNIT VENTILATORS | Yes | 1. Make-up air units, heat and vent units, stand-alone return fans, supply fans, and energy recovery units. |
2. Air curtains
| D305002 UNIT HEATERS | Yes | All types; hydronic, infrared, other | |||
| D305003 FAN COIL UNITS | Yes | All types | |||
| D305004 FIN TUBE RADIATION | Yes | Baseboard heating | |||
| D305005 ELECTRIC HEATING | Yes | All types | |||
| D305006 PACKAGE UNITS | Yes | All package units, no window units. | |||
| D305090 OTHER TERM & PACKAGE UNITS | Yes | Special or unique items as required. | |||
| D30 HVAC (Continued) * | Yes | D3060 CONTROLS & INSTRUMENTATION | D306001 HVAC CONTROLS | Yes | HVAC control panels and variable frequency drives |
| D306002 ELECTRONIC CONTROLS | No | ||||
| D306003 PNEUMATIC CONTROLS | No | ||||
| D306004 INSTRUMENT AIR COMPRESSORS | No | ||||
| D306005 GAS PURGING SYSTEMS | No | ||||
| D306090 OTHER CONTROLS INSTRUMENTATION | Yes | Energy Management and Control Systems. | |||
| D3070 SYSTEMS TESTING & BALANCING | D307001 WATER SIDE TESTING & BALANCING | No | |||
| D307002 AIR SIDE TESTING & BALANCING | No | ||||
| D307003 HVAC COMMISSIONING | No | ||||
| D307090 OTHER SYSTEMS TESTING & BALANCING | No | ||||
| D3090 OTHER HVAC SYSTEMS AND EQUIPMENT | D309002 REFRIGERATION SYSTEMS | Yes | 2-piece and 3-piece refrigeration system | ||
| D309090 OTHER SPECIAL MECHANICAL SYSTEMS | Yes | Special or unique items as required. | |||
| D40 FIRE PROTECTION * | Yes | D4010 FIRE ALARM AND DETECTION SYSTEMS | D401001 FIRE ALARM DISTRIBUTION | Yes | All equipment; fire alarm control panels, fire alarm power supply, and mass notification panel. |
| D401002 FIRE ALARM DEVICES | No | All devices are inventoried; pull stations, detectors, annunciators, strobes, etc. | |||
| D4020 FIRE SUPP WATER SUPPLY / EQUIP | D402001 FIRE PROTECTION WATER PIPING AND EQUIPMENT | Yes | All fire prevention (FP) equipment; water backflow preventers ≥ 1", FP expansion tanks ≥ 50 gallons, and FP air compressors and dryers. | ||
| D402002 FIRE PUMP | Yes | Fire prevention water pumps and jockey pumps ≥ 1 hp and their controllers (if separate) | |||
| D4030 STANDPIPE SYSTEMS | D403001 STANDPIPE EQUIPMENT & PIPING | Yes | Includes risers and fire hose equipment. | ||
| D4040 SPRINKLERS | D404001 SPRINKLERS AND RELEASING DEVICES | No | Includes inventory of specific system | ||
| D404002 SPRINKLER WATER SUPPLY EQUIPMENT AND PIPING | No | Sprinkler heads and piping | |||
| D4050 FIRE PROTECTION SPECIALTIES | D405001 PORTABLE EXTINGUISHERS | No | Not real property | ||
| D4090 OTHER FIRE PROTECTION SYSTEMS | D409001 CARBON DIOXIDE SYSTEMS | Yes | Previously, the only fire protection systems included in the inventory are those systems systems that were deficient with a Fire Safety Deficiency (FSD) rating. | ||
| D409002 FOAM GENERATING EQUIPMENT | |||||
| D409003 CLEAN AGENT SYSTEMS | |||||
| D409004 HOOD & DUCT FIRE PROTECTION | |||||
| D409090 OTHER SPECIAL FIRE PROTECTION SYSTEMS | |||||
| D50 ELECTRICAL * | YES | D5010 ELECTRICAL SERVICE & DISTRIBUTION | D501001 MAIN TRANSFORMERS | Yes | All transformers ≥50 kva. This data was input under D501090. |
| D501002 SERVICE ENTRANCE EQUIPMENT | Yes | 1. All switchboards ≥200 amps |
2. Meters owned by the government
| D501003 INTERIOR DISTRIBUTION TRANSFORMERS | Yes | All interior distribution transformers ≥50 kva | |
| D501004 PANELBOARDS | Yes | All indoor switchgears, panelboards, transfer switches, and safety switches ≥200 amps | |
| D501005 ENCLOSED CIRCUIT BREAKERS | Yes | All main circuit breakers and enclosed circuit breakers ≥200 amps | |
| D501006 MOTOR CONTROL CENTERS | Yes | All motor control centers | |
| D501090 OTHER SERVICE AND DISTRIBUTION | Yes | For special or unique items. Main Transformer and inverters were inventoried in this section. | |
| D5020 LIGHTING & BRANCH WIRING | D502001 BRANCH WIRING | No | Distribution wiring |
| D502002 LIGHTING EQUIPMENT | No | Exterior lighting, interior lighting, explosion proof lighting. | |
| D502090 OTHER LIGHTING AND BRANCH WIRING | No | For special or unique items. | |
| D5030 COMMUNICATIONS & SECURITY | D503001 TELECOMMUNICATIONS SYSTEMS | No | Comm equipment |
| D503002 PUBLIC ADDRESS SYSTEMS | No | Comm equipment | |
| D503003 INTERCOMMUNICATIONS SYSTEMS | No | Comm equipment | |
| D503004 TELEVISION SYSTEMS | No | Comm equipment | |
| D503005 SECURITY SYSTEMS | No | Comm equipment | |
| D503090 OTHER COMMUNICATIONS & ALARM SYSTEMS | No | Comm equipment | |
| D5090 OTHER ELECTRICAL SERVICES | D509002 EMERGENCY LIGHTING & POWER | Yes | 1. All emergency generators and uninterruptible power supplies. |
| D509003 GROUNDING SYSTEMS | No | |
| D509004 LIGHTNING PROTECTION | No | |
| D509090 OTHER SPECIAL SYSTEMS AND DEVICES | No | For special or unique items. |
* For applicable equipment items, AFCEC required only equipment that was visible
Fort Eustis Sys, No & Partial
FORT EUSTIS SUMMARY OF BUILDER UNIFORMAT II DATA COLLECTION
NO AND PARTIAL INVENTORY SUMMARY FOR AFCEC REQUIRED SYSTEMS
| System (Level 2) | Req'd Sys by AFCEC? | Component | ||
| (Level 3) | Section (Level 4) | Inventory reqmt per SIA or FORT EUSTIS contract, guide used for 20% annual inv. | Applicable comments on sections inventoried and not inventoried | Equipment barcoded & eqmt details populated? |
| A10 FOUNDATIONS | No | A1030 SLAB ON GRADE | A103001 STANDARD SLAB ON GRADE |
A103002 STRUCTURAL SLAB ON GRADE
A103003 TRENCHES
A103004 PITS AND BASES
A103005 FOUNDATION DRAINAGE
| A103090 OTHER | yes, for sections under component level 1030 only | This was required under the Fort Eustis follow on contract, but is not required by AFCEC. Currently, included in 20% inventory as a result. Should it? | ||||
| A20 BASEMENT CONSTRUCTION | No | Not applicable | Not applicable | Not applicable | ||
| B10 SUPERSTRUCTURE | No | Not applicable | Not applicable | Not applicable | ||
| B20 EXTERIOR ENCLOSURE | Yes | B2010 EXTERIOR WALLS | B201001 EXTERIOR CLOSURE | Yes | ||
| B20 EXTERIOR ENCLOSURE | B2010 EXTERIOR WALLS | B201002 EXTERIOR WALL BACKUP CONSTRUCTION | No | |||
| B201003 INSULATION AND VAPOR RETARDER | No | |||||
| B201004 PARAPETS | No | |||||
| B201005 EXTERIOR LOUVERS AND SCREENS | Yes | |||||
| B201006 BALCONY WALLS AND HANDRAILS | Yes | 1. Balcony wall under B201001 |
2. Handrails & Ladders under B201006
| No | Interior or exterior stair handrail or guardrail not assessed as that is part of C20 stairs, which is not required system by AFCEC | ||||||
| B201007 EXTERIOR SOFFITS | Yes | ||||||
| B201008 FLASHING | No | ||||||
| B201009 EXTERIOR PAINTING AND SPECIAL COATINGS | No | ||||||
| B201010 EXTERIOR JOINT SEALANT | No | ||||||
| B201011 SUN CONTROL DEVICES | No | Not real property | |||||
| B201012 SCREEN WALLS | Yes | ||||||
| B201090 OTHER EXTERIOR WALLS | Yes | Unique or special instances not covered in previous categories. Not used at Fort Eustis. | |||||
| B2020 EXTERIOR WINDOWS | B202001 WINDOWS | Yes | Report windows as "general" so that UOM can be recorded in SF. | ||||
| B202002 STOREFRONTS | Yes | ||||||
| B202003 CURTAIN WALLS | Yes | ||||||
| B202090 OTHER EXTERIOR WINDOWS | Yes | ||||||
| B2030 EXTERIOR DOORS | B203001 SOLID DOORS | Yes | |||||
| B203002 GLAZED DOORS | Yes | ||||||
| B203003 REVOLVING DOORS | Yes | ||||||
| B203004 OVERHEAD AND ROLL-UP DOORS | Yes | ||||||
| B203005 HANGAR DOORS | Yes | ||||||
| B203006 BLAST RESISTANT DOORS | Yes | ||||||
| B203007 GATES | Yes | ||||||
| B2030 EXTERIOR DOORS | B203008 EXTERIOR DOOR HARDWARE | No | Doors overall are inventoried | ||||
| B203090 OTHER EXTERIOR SPECIALTY DOORS | Yes | ||||||
| B203091 OTHER EXTERIOR PERSONNEL DOORS | Yes | ||||||
| B30 ROOFING | Yes | B3010 ROOF COVERINGS | B301001 STEEP SLOPE ROOF SYSTEMS | Yes | |||
| B301002 LOW SLOPE ROOF SYSTEMS | Yes | ||||||
| B301003 ROOF INSULATION & FILL | Yes | ||||||
| B30 ROOFING | B3010 ROOF COVERINGS | B301004 FLASHINGS AND TRIM | No | ||||
| B301005 GUTTERS & DOWNSPOUTS | Yes | ||||||
| B301006 ROOF OPENINGS AND SUPPORTS | Yes | ||||||
| B301090 OTHER ROOFING | Yes | ||||||
| C10 INTERIOR CONSTRUCTION | Yes | C1010 PARTITIONS | C101001 FIXED PARTITIONS | Yes | |||
| C101002 DEMOUNTABLE PARTITIONS | Yes | ||||||
| C101003 RETRACTABLE PARTITIONS | Yes | ||||||
| C101004 INTERIOR GUARDRAILS & SCREENS | Yes | ||||||
| C101005 INTERIOR WINDOWS | Yes | ||||||
| C101006 GLAZED PARTITIONS & STOREFRONTS | Yes | ||||||
| C101007 INTERIOR GLAZING | Yes | ||||||
| C10 INTERIOR CONSTRUCTION | C1010 PARTITIONS | C101008 INTERIOR JOINT SEALANT | No | ||||
| C101090 OTHER PARTITIONS | Yes | ||||||
| C1020 INTERIOR DOORS | C102001 STANDARD INTERIOR DOORS | Yes | |||||
| C102002 GLAZED INTERIOR DOORS | Yes | ||||||
| C102003 FIRE DOORS | Yes | ||||||
| C102004 SLIDING & FOLDING DOORS | Yes | ||||||
| C102005 INTERIOR OVERHEAD DOORS | Yes | ||||||
| C102006 INTERIOR GATES | Yes | ||||||
| C1020 INTERIOR DOORS | C102007 INTERIOR DOOR HARDWARE | No | Doors overall are inventoried | ||||
| C102090 OTHER INTERIOR SPECIALTY DOORS | Yes | ||||||
| C102091 OTHER INTERIOR PERSONNEL DOORS | Yes | ||||||
| C1030 SPECIALTIES | C103001 COMPARTMENTS, CUBICLES & TOILET PARTITIONS | Yes | |||||
| C1030 SPECIALTIES | C103002 TOILET & BATH ACCESSORIES | No | Not real property | ||||
| C103003 MARKER BOARDS & TACK BOARDS | No | Not real property | |||||
| C103004 IDENTIFYING DEVICES | No | Options are only "general", "other", or "unknown" | |||||
| C103005 LOCKERS | No | Not real property | |||||
| C103006 SHELVING | No | Not real property | |||||
| C103007 FIRE EXTINGUISHER CABINETS | No | Not real property | |||||
| C103008 COUNTERS | No | Not real property | |||||
| C103009 CABINETS | No | Not real property | |||||
| C103010 CASEWORK | No | Not real property | |||||
| C103011 CLOSETS | No | Not real property | |||||
| C103012 FIRESTOPPING PENETRATIONS | No | ||||||
| C103013 SPRAYED FIRE RESISTANT MATERIALS | No | ||||||
| C103014 ENTRANCE FLOOR GRILLS & MATS | No | ||||||
| C103015 ORNAMETAL METAL WORK | No | ||||||
| C103090 OTHER INTERIOR SPECIALTIES | Yes, Exit Signs | Moving Exit Signs to E502002, Exit Lighting | |||||
| C20 STAIRS | No | Not applicable | Not applicable | Not applicable | Not applicable | ||
| C30 INTERIOR FINISHES | No | Not applicable | Not applicable | Not applicable | Not applicable | ||
| D20 PLUMBING | Yes | D2010 PLUMBING FIXTURES | D201001 WATERCLOSETS | Yes | No | ||
| D201002 URINALS | Yes | No | |||||
| D201003 LAVATORIES | Yes | No | |||||
| D201004 SINKS | Yes | No | |||||
| D201005 SHOWERS/TUBS | Yes | No | |||||
| D201006 DRINKING FOUNTAINS AND COOLERS | Yes | Yes | |||||
| D201090 OTHER PLUMBING FIXTURES | Yes | Eye wash and eye wash / shower units that are hard piped. | Yes | ||||
| D20 PLUMBING * | D2020 DOMESTIC WATER DISTRIBUTION | D202001 PIPES & FITTINGS | No | Distribution measurement | Not applicable | ||
| D202002 VALVES & HYDRANTS | Partial | Domestic water backflow preventers ≥ 1" only (no faucets or hose bibs). | Yes | ||||
| D202003 DOMESTIC WATER EQUIPMENT | Partial | 1. Yes, Pumps ≥ 1 hp and tanks/water heaters ≥ 50 gal. | |||||
| 2. No, for water treatment, heat transfer package | Yes | ||||||
| D202004 INSULATION & IDENTIFICATION | No | Not applicable | |||||
| D202005 SPECIALTIES | No | Not applicable | |||||
| D202006 BALL VALVES | No | Not applicable | |||||
| D202007 GATE VALVES | No | Not applicable | |||||
| D202008 VALVES, NON DRAIN | No | Not applicable | |||||
| D202009 BUTTERFLY VALVES | No | Not applicable | |||||
| D2020010 FLOW CONTROL VALVES | No | Not applicable | |||||
| D2020011 GLOBE VALVES | No | Not applicable | |||||
| D202012 PLUG VALVES | No | Not applicable | |||||
| D2020013 SELENOID VALVES | No | Not applicable | |||||
| D2020014 CHECK VALVES | No | Not applicable | |||||
| D2020015 OTHER VALVES | No | Not applicable | |||||
| D202090 OTHER DOMESTIC WATER SUPPLY | No | Not applicable | |||||
| D202091 OTHER AUXILIARY EQUIPMENT | No | Not applicable | |||||
| D2030 SANITARY WASTE | D203001 WASTE PIPE & FITTINGS | No | Distribution unit of measure | Not applicable | |||
| D203002 VENT PIPE & FITTINGS | No | Not applicable | |||||
| D203003 FLOOR DRAINS | No | Not applicable | |||||
| D203004 SANITARY AND VENT EQUIPMENT | No | Not applicable | |||||
| D203005 INSULATION & IDENTIFICATION | No | Distribution unit of measure | Not applicable | ||||
| D203090 OTHER SANITARY WASTE | No | Not applicable | |||||
| D2040 RAIN WATER DRAINAGE | D204001 PIPE & FITTINGS | No | Not applicable | ||||
| D204002 ROOF DRAINS | No | Not applicable | |||||
| D204003 RAINWATER DRAINAGE EQMT | Partial | Sump pumps ≥ 1 hp. No other items in this category. | Yes | ||||
| D204004 INSULATION & IDENTIFICATION | No | Distribution unit of measure | Not applicable | ||||
| D204090 OTHER RAIN WATER DRAINAGE | No | Not applicable | |||||
| D2090 OTHER PLUMBING SYSTEMS | D209001 SPECIAL PIPING SYSTEMS | No | Distribution unit of measure | Not applicable | |||
| D209002 ACID WASTE SYSTEMS | No | Not applicable | |||||
| D209003 INTERCEPTORS | No | Not applicable | |||||
| D209004 POOL PIPING AND EQUIPMENT | No | Not real property | Not applicable | ||||
| D209005 COMPRESSED AIR SYSTEM (NON-BREATHING) | Partial | 1. Compressors ≥ 1 hp |
2. Tanks ≥ 50 gal
| 3. Air dryers that are separate from the compressors. | Yes | ||||||
| D209090 OTHER SPECIAL PLUMBING SYSTEMS | Partial | Oil / Water separators. Only if nameplate above ground. | Yes | ||||
| D30 HVAC * | Yes | D3010 ENERGY SUPPLY | D301001 OIL SUPPLY SYSTEM | Partial | Heat oil tanks ≥ 50 gal | Yes | |
| D301002 GAS SUPPLY SYSTEM | Partial | Fuel oil tanks ≥ 50 gal | Yes | ||||
| D301003 STEAM SUPPLY SYSTEM (FROM CENTRAL PLANT) | No | Equipment is captured within the central plant building. | No | ||||
| D301004 HOT WATER SUPPLY SYSTEM (FROM CENTRAL PLANT) | No | Equipment is captured within the central plant building. | No | ||||
| D301005 SOLAR SYSTEM | Yes | Solar hot water equipment such as evacutated tube collector, flat plate collector, etc. | Yes | ||||
| D301006 WIND ENERGY SYSTEM | Yes | Not applicable at Fort Eustis | Yes | ||||
| D301007 COAL SYSTEM | Yes | Not applicable at Fort Eustis | Yes | ||||
| D301090 OTHER ENERGY SUPPLY | Partial | 1. Ice bank | |||||
| 2. Tanks ≥ 50 gal, buffer tanks and thermal storage tanks ≥ 50 gal | Yes | ||||||
| D3020 HEAT GENERATING SYSTEMS | D302001 BOILERS | Yes | All boiler types, all sizes. | Yes | |||
| D302002 FURNACES | Yes | Electric duct heater and furnaces | Yes | ||||
| D302003 FUEL-FIRED UNIT HEATERS | Yes | All | Yes | ||||
| D3020 HEAT GENERATING SYSTEMS | D302004 AUXILIARY EQUIPMENT | Partial | All auxillary boiler equipment ≥ 50 gal to include boiler feedwater tanks, chemical feedwater tanks, and expansion tanks. | Yes | |||
| D302005 EQUIPMENT THERMAL INSULATION | No | Not applicable | Not applicable | ||||
| D302090 OTHER HEAT SYSTEMS | Yes | Currently, not applicable at Fort Eustis | Yes | ||||
| D3030 COOLING GENERATING SYSTEMS | D303001 CHILLED WATER SYSTEMS | Yes | Chillers and cooling towers. Any item with R-10, 12, 14, 20, 22 refrigerant gets, at the highest, an automatic "A+" rating. | Yes | |||
| D303002 DIRECT EXPANSION SYSTEMS | Yes | Any outdoor portion of a split DX system (and some packaged rooftop units fitting descriptions in this category). Any item with R-10, 12, 14, 20, 22 refrigerant gets, at the highest, an automatic "A+" rating. | Yes | ||||
| D3030 COOLING GENERATING SYSTEMS | D303003 "No longer a section level" | No | Not applicable | Not applicable | |||
| D302004 AUXILIARY EQUIPMENT | Partial | Auxillary chiller equipment ≥ 50 gal to include expansion tanks. | Yes | ||||
| D303090 OTHER COOLING GENERATING SYSTEMS | Yes | Normally not applicable. Use for special or unique items not covered in other categories. | Yes | ||||
| D3040 DISTRIBUTION SYSTEMS | D304001 AIR DISTRIBUTION, HEATING & COOLING | Partial | 1. All eqmt; Air separators, humidifiers, and dehumidifiers and VAV boxes. | ||||
| 2. Do not inventory other components that are distribution quantities related to ductwork or piping. | Yes for everything except VAV boxes. | ||||||
| D304002 STEAM DISTRIBUTION SYSTEMS | Partial | 1. All eqmt; Pressure reducing stations inside the building, not part of the upper tier of distribution. |
2. Do not inventory other components that are distribution quantities related to ductwork or piping.
| D304003 HOT WATER DISTRIBUTION SYSTEMS | Partial | 1. All eqmt; Heat exchangers and hot water pumps and condensate return pumps ≥ 1 hp. | |||||
| 2. Do not inventory other components that are distribution quantities related to ductwork or piping. | Yes | ||||||
| D304004 CHANGE OVER DISTRIBUTION SYSTEMS | Yes | Assume this is for a "dual temp" system, but General, Other, and Unknown are the only options. Dual temp pumps shall be placed in D304006. No other items to be collected in this category. | Yes | ||||
| D304005 GLYCOL DISTRIBUTION SYSTEMS | Partial | 1. All eqmt; Complete systems with holding tank, pump, controls ≥50 gal. | |||||
| 2. Do not inventory other components that are distribution quantities related to ductwork or piping. | Yes | ||||||
| D304006 CHILLED WATER DISTRIBUTION SYSTEMS | Partial | 1. All eqmt; chilled water, condenser water, dual temp water, and glycol pumps ≥ 1 hp. | |||||
| 2. Do not inventory other components that are distribution quantities related to ductwork or piping. | Yes | ||||||
| D304007 EXHAUST SYSTEMS | Yes | Powered ventilation / exhaust systems (no passive vents) to include exhausts for dust collection, glove box, and fume exhaust hood. | Yes | ||||
| D304008 AIR HANDLING UNITS | Yes | All major air handling units. Any item with R-10, 12, 14, 20, 22 refrigerant gets, at the highest, an automatic "A+" rating. | Yes | ||||
| D304090 OTHER DISTRIBUTION SYSTEMS | Yes | Special or unique items as required. | Yes | ||||
| Yes | D3050 TERMINAL & PACKAGE UNITS | D305001 UNIT VENTILATORS | Yes | 1. Make-up air units, heat and vent units, stand-alone return fans, supply fans, and energy recovery units. | |||
| 2. Air curtains | All items in 1 are barcoded, item 2 is inventory only. | ||||||
| D305002 UNIT HEATERS | Yes | All types; hydronic, infrared, other | Yes, if can be reached. Otherwise, include details as much as possible with a note in bar code column. | ||||
| D305003 FAN COIL UNITS | Yes | All types | Yes | ||||
| D305004 FIN TUBE RADIATION | Yes | Baseboard heating | Yes | ||||
| D305005 ELECTRIC HEATING | Yes | All types | Yes | ||||
| D305006 PACKAGE UNITS | Partial | All package units, no window units. Any item with R-10, 12, 14, 20, 22 refrigerant gets, at the highest, an automatic "A+" rating. | Yes | ||||
| D305090 OTHER TERM & PACKAGE UNITS | Yes | Special or unique items as required. | Yes | ||||
| D3060 CONTROLS & INSTRUMENTATION | D306001 HVAC CONTROLS | Yes | HVAC control panels and variable frequency drives | Yes | |||
| D3060 CONTROLS & INSTRUMENTATION | D306002 ELECTRONIC CONTROLS | No | Not applicable | ||||
| D306003 PNEUMATIC CONTROLS | No | Not applicable | |||||
| D306004 INSTRUMENT AIR COMPRESSORS | No | Not real property | Not applicable | ||||
| D306005 GAS PURGING SYSTEMS | No | Not applicable | |||||
| D306090 OTHER CONTROLS INSTRUMENTATION | Yes | Energy Management and Control Systems. However, should EMCS be moved to Electrical, D509060, EMCS? | Yes | ||||
| D3070 SYSTEMS TESTING & BALANCING | D307001 WATER SIDE TEST & BALANCING | No | Not applicable | ||||
| D307002 AIR SIDE TESTING & BALANCING | No | Not applicable | |||||
| D307003 HVAC COMMISSIONING | No | Not applicable | |||||
| D307090 OTHER SYSTEMS TESTING & BALANCING | No | Not applicable | |||||
| D3090 OTHER HVAC SYSTEMS AND EQUIPMENT | D309002 REFRIGERATION SYSTEMS | Yes | 2-piece and 3-piece refrigeration system | Yes | |||
| D309090 OTHER SPECIAL MECHANICAL SYSTEMS | Yes | Special or unique items as required. | Yes | ||||
| D40 FIRE PROTECTION | Yes | D4010 FIRE ALARM AND DETECTION SYSTEMS | D401001 FIRE ALARM DISTRIBUTION | Yes | All equipment; fire alarm control panels, fire alarm power supply, and mass notification panel. | Yes | |
| D401002 FIRE ALARM DEVICES | Yes | All devices are inventoried; pull stations, detectors, annunciators, strobes, etc. | No | ||||
| D40 FIRE PROTECTION * | D4020 FIRE SUPP WATER SUPPLY / EQUIP | D402001 FIRE PROTECTION WATER PIPING AND EQUIPMENT | Partial | All fire prevention (FP) equipment; water backflow preventers ≥ 1", FP expansion tanks ≥ 50 gallons, and FP air compressors and dryers. | Yes, Fire backflow preventors put with plumbing | ||
| D402002 FIRE PUMP | Partial | Fire prevention water pumps and jockey pumps ≥ 1 hp and their controllers (if separate) | |||||
| D4030 STANDPIPE SYSTEMS | D403001 STANDPIPE EQUIPMENT & PIPING | No, however, working with Fire tech to add info and barcode for the 20% | Includes risers and fire hose equipment. | Yes | |||
| D4040 SPRINKLERS | D404001 SPRINKLERS AND RELEASING DEVICES | No, however, working with Fire tech to add info for the 20% | Includes inventory of specific system | No | |||
| D404002 SPRINKLER WATER SUPPLY EQUIPMENT AND PIPING | No | Sprinkler heads and piping | No | ||||
| D4050 FIRE PROTECTION SPECIALTIES | D405001 PORTABLE EXTINGUISHERS | No | Not real property | No | |||
| D4090 OTHER FIRE PROTECTION SYSTEMS | D409001 CARBON DIOXIDE SYSTEMS | Partial, however, working with Fire Tech to include all systems for the 20% | Previously, the only fire protection systems included in the inventory are those systems systems that were deficient with a Fire Safety Deficiency (FSD) rating. | No | |||
| D409002 FOAM GENERATING EQUIPMENT | No | ||||||
| D409003 CLEAN AGENT SYSTEMS | No | ||||||
| D409004 HOOD & DUCT FIRE PROTECTION | No | ||||||
| D409090 OTHER SPECIAL FIRE PROTECTION SYSTEMS | No | ||||||
| D50 ELECTRICAL * | YES | D5010 ELECTRICAL SERVICE & DISTRIBUTION | D501001 MAIN TRANSFORMERS | Yes | All transformers ≥50 kva. This data was input under D501090. | Not applicable | |
| D501002 SERVICE ENTRANCE EQUIPMENT | Partial | 1. All switchboards ≥200 amps | |||||
| 2. Meters owned by the government | Yes | ||||||
| D501003 INTERIOR DISTRIBUTION TRANSFORMERS | Partial | All interior distribution transformers ≥50 kva | Yes | ||||
| D501004 PANELBOARDS | Partial | All indoor switchgears, panelboards, transfer switches, and safety switches ≥200 amps | Yes | ||||
| D501005 ENCLOSED CIRCUIT BREAKERS | Partial | All main circuit breakers and enclosed circuit breakers ≥200 amps | Yes | ||||
| D501006 MOTOR CONTROL CENTERS | Yes | All motor control centers | Yes | ||||
| D501090 OTHER SERVICE AND DISTRIBUTION | Yes | For special or unique items. | Yes | ||||
| D5020 LIGHTING & BRANCH WIRING | D502001 BRANCH WIRING | No | Distribution wiring | Not applicable | |||
| D502002 LIGHTING EQUIPMENT | No | Exterior lighting, interior lighting, explosion proof lighting. Also, exit lighting which was captured under C103090 will be moved to this section. | No | ||||
| D502090 OTHER LIGHTING AND BRANCH WIRING | Yes | For special or unique items. | Yes | ||||
| D5030 COMMUNICATIONS & SECURITY | D503001 TELECOMMUNICATIONS SYSTEMS | No | Comm equipment | Not applicable | |||
| D503002 PUBLIC ADDRESS SYSTEMS | No | Comm equipment | Not applicable | ||||
| D503003 INTERCOMMUNICATIONS SYSTEMS | No | Comm equipment | Not applicable | ||||
| D503004 TELEVISION SYSTEMS | No | Comm equipment | Not applicable | ||||
| D503005 SECURITY SYSTEMS | No | Comm equipment | Not applicable | ||||
| D503090 OTHER COMMUNICATIONS & ALARM SYSTEMS | No | Comm equipment | Not applicable | ||||
| D5090 OTHER ELECTRICAL SERVICES | D509002 EMERGENCY LIGHTING & POWER | Yes | 1. All energency generators and uninteruptible power supplies. | ||||
| 2. Emergency lights | Item 1 barcoded, item 2 not | ||||||
| D5090 OTHER ELECTRICAL SERVICES | D509003 GROUNDING SYSTEMS | No | Not applicable | ||||
| D509004 LIGHTNING PROTECTION | No | Not applicable | |||||
| D509005 ELECTRIC HEATING | No | Applicable electric heating captured under HVAC | Not applicable | ||||
| D509006 ENERGY MANAGEMENT CONTROL SYSTEM | Yes | Currently collected under HVAC, D306090 OTHER CONTROLS INSTRUMENTATION | Yes | ||||
| D509090 OTHER SPECIAL SYSTEMS AND DEVICES | No | For special or unique items. | No |
* For applicable equipment items, AFCEC required only equipment that was visible