ARCHITECTURAL.pdf
PDF 3 MB Posted
- Attached to
- CHI memorial renovations
- Solicitation number
- PE-66717-NONST-2025-000000007
- Issued by
- Wilcox County, Georgia
About this file
This document contains details for a partial upgrade to Building One of the Lafayette Medical Office Park located on State Highway 136 in Lafayette, Georgia. The project involves architectural, mechanical, plumbing, and electrical work, including floor plan renovations, finish upgrades, HVAC system modifications, plumbing fixture replacements, and electrical system improvements. The project is being overseen by the Owner, Memorial Hospital, and the Architect, Artech Design Group. No bid dates, due dates, or award information is provided.
The document outlines detailed requirements for the work, including ADA compliance standards, floor plans, finishes, millwork, reflected ceiling plans, and door/window schedules. Pricing terms, set asides, and funding sources are not specified. The building is currently occupied and must remain open during construction, requiring the contractor to take measures to protect the existing space from disruption.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 20220214_LAFAYETTE HVAC_ CDs.pdf | ||
| E1_2.pdf | ||
| E1_3.pdf | ||
| LaFayette Projects RFQ (RLR Edit).docx | DOCX document | |
| One Medical Office Park _ Partial Upgrade Bui.pdf | ||
| E1_1.pdf | ||
| E2_1.pdf | ||
| E2_0.pdf | ||
| 20220214_LAFAYETTE PLBG_CDs.pdf | ||
| bee well clinic (RLR edit).docx | DOCX document |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
EXAM 3
E7
EXAM 4
E8
LAB
TOILET
E11PROVIDER
E12
EXAM 5
E13
EXAM 6
E14
STORAGE
E19
OFFICE
E20
EXAM 16
E29
XRAY
BREAK ROOM
TOILET
E35
JENNIFER
E36CARE TEAM
E37
TOILET
E38
OM
ELEC
E42
PROVIDER
EXAM
EXAM
EXAM
BARIATRIC
CLEAN
STAFF TOILET
CARE TEAM
CHECK IN
TOILET
STORAGE
EXAM
PROVIDER
59 EXAM
CALL CENTER
SOILED
EXAM
IT
E67
9' - 0 5/8" 9' - 6" 9' - 6" 9' - 6" 7' - 4 1/8"
N59 N66
N56 N62 N55 E54
N50
N35
N49 N48
N53
N46 N45N44N43
N40
R63
EQ
EQ
2'
3/
5'
0"
N65
N36A
11' - 3 1/8"
CN-1
CN-1
CN-1
CN-2
ALIGN
ALIGN
MEDS
CORRIDOR
A6.1
A6.1
WAITING
N36B
3 1
A6.16
A6.1
A6.1 1
A6.1 1
Si m
A6.11
Si m
A6.11
Si m
A6.11
Si m
A6.11
Si m
NO WORK IN AREA SHOW WITHIN HATCH
CLOSET
6' - 3 1/8" 5' - 4 1/8" 6' - 4" 7' - 5 3/8" 6' - 4 1/2" 9' - 0" 6' - 9 1/4" N44
C O W A R T
S T R E E T
C H A T T A N O O G A
T N
W W W A R T E C H P R O
JOB NO. D'WN CK'D
ISSUE DATES
INITIAL ISSUE
#21-041 ER/LC KA
PA
R
TI
A
L U
PG
R
A D
E B
U
IL
D
IN
G O
N E
LA
FA
YE
TT
E M
ED
IC
A L
O
FF
IC
E
PA
R
K
ST
AT
E
H
IG
H W
AY
L
AF
AY
ET
TE
G
EO
R G
IA
A1.1
FLOOR PLAN
02/11/22
N
SCALE: 3/16" = 1'-0" 1 LEVEL 1 FLOOR PLAN
GENERAL CONSTRUCTION NOTES:
A. DO NOT SCALE DRAWINGS. VERIFY ALL CONDITIONS AND DIMENSIONS BEFORE PROCEEDING - NOTIFY ARCHITECT IF DISCREPANCIES ARE ENCOUNTERED.
B. IF DISCREPANCIES ARE FOUND BETWEEN THE DRAWINGS AND THE SPECIFICATIONS, CONTACT ARCHITECT TO RESOLVE PRIOR TO PERFORMING THAT WORK
C. ALL DIMENSIONS ARE TO FACE OF STUD U.N.O., FACE OF NEW DRYWALL TO ALIGN WITH EXISTING FACES WHERE APPLICABLE
D. CONTRACTOR TO PROVIDE UL RATED PENETRATIONS/FIRESTOPPING FOR ALL PENETRATIONS THROUGH RATED PARTITIONS (I.E. ELECTRICAL, MECHANICAL, PLUMBING, ETC.)
E. WHERE EXISTING WALLS ARE SCHEDULED TO RECEIVE NEW FINISHES REMOVE EXISTING FINISH. PATCH WALL AS NECESSARY AND PREPARE FOR NEW FINISH AS SCHEDULED.
F. WHERE EXISTING FLOORS ARE SCHEDULED TO RECEIVE NEW FINISHES REMOVE EXISTING FINISH AND ADHESIVE, PATCH FLOOR AND PREPARE FOR NEW FINISH AS SCHEDULED.
G. EXTEND NEW WALLS TO FLOOR/ROOF DECK ABOVE AT TENANT SEPARATION WALLS. ALL OTHERS EXTEND 6" ABOVE CEILING.
H. REFER TO SHEET T1.2 FOR WALL TYPES, SYMBOLS AND MATERIALS
I. ADD ACOUSTICAL INSULATION IN WALL AND ABOVE CEILING 2FT WIDE ALONG ENTIRE PERIMETER OF ALL EXAM ROOMS, OFFICES AND TOILETS.
J. INSTALL ALL FINISHES PER MFG. RECOMMENDATIONS
CONSTRUCTION NOTES
CN-1 INFILL OPENING WITH NEW GYP. BD. WALL TO MATCH SURROUNDING CONDITIONS
CN-2 BRACKET AND STANDARDS SHELVING. SEE DETAIL ON A600 SHEETS
0 2'-8" 5'-4" 10'-8"
NOTE:
THIS BUILDING IS OCCUPIED AND MUST REMAIN OPEN DURING CONSTRUCTION
CONTRACTOR SHALL TAKE ALL MEASURE NECESSARY TO PROTECT EXISTING
OCCUPIED SPACE FROM DUST, NOISE, AND DAMAGE. IN ADDITION CONTRACTOR
SHALL NOT BLOCK EXITS THE BUILDING IS OCCUPIED.
WALL LEGEND
EXISTING WALLS
NEW WALLS
EXAM 4
E8
LAB
TOILET
E11
EXAM 5
E13
STORAGE
E19
EXAM 16
E29
XRAY
BREAK ROOM
TOILET
E35
JENNIFER
E36CARE TEAM
E37
TOILET
E38
OM
ELEC
E42
PROVIDER
EXAM
EXAM
EXAM
BARIATRIC
CLEAN
STAFF TOILET
CARE TEAM
CHECK IN
TOILET
54STORAGE
EXAM
PROVIDER
EXAM
CALL CENTER
SOILED
EXAM
IT
E67
MEDS
TR-1
TR-1
TR-1
TR-2
TR-1
TR-1
PNT-6
CORRIDOR
E43
WP-4
WP-4
ACCENT FINISH
CORNER GUARD
FLOOR TRANSITION
LVT
CPT
FINISH LEGEND
EXISTING TO REMAIN
C O W A R T
S T R E E T
C H A T T A N O O G A
T N
W W W A R T E C H P R O
JOB NO. D'WN CK'D
ISSUE DATES
INITIAL ISSUE
#21-041 ER/LC KA
PA
R
TI
A
L U
PG
R
A D
E B
U
IL
D
IN
G O
N E
LA
FA
YE
TT
E M
ED
IC
A L
O
FF
IC
E
PA
R
K
ST
AT
E
H
IG
H W
AY
L
AF
AY
ET
TE
G
EO
R G
IA
A1.1F
FINISH PLAN
02/11/22
ROOM FINISH SCHEDULE
ROOM
NUMBER
ROOM NAME FLOORS
BASE
MATERIAL
BASE WALLS
TRIM FINISH
CEILINGS CASEWOK COMMENTS
MATERIAL COLOR COLOR MATERIAL COLOR TYPE FINISH COUNTERS
BASE
CABINETS
WALL
CABINETS
10 LAB LVT 2 RB 1 P 1 MATCH TO
EXISTING
ACT 1 SS-1 PL-2 PL-2 PL-3 ON DESK FRONT; SEE DETAILS
33 XRAY EXISTING 1 EXISTING P 1 MATCH TO
EXISTING
EXISTIN
G CT
EXISTING
34 BREAK ROOM LVT 2 RB 1 P 1 MATCH TO
EXISTING
ACT 1 SS-1 PL-2 PL-2
35 MEDS LVT 1 RB 1 P 1 P-1 ACT 1
36 WAITING LVT 1 RB 2 P 1 P-1 ACT 1
40 OM LVT 2 RB 1 P 1 MATCH TO
EXISTING
ACT 1
41 CORRIDOR LVT 1 RB 1 P 1 P-1 ACT 1
43 PROVIDER LVT 1 RB 1 P 1 P-1 ACT 1
44 EXAM LVT 1 RB 2 P / PL 4 / 3 P-1 ACT 1 SS-1 PLAM-2 PLAM-3 ABOVE CASEWORK; SEE ELEVATIONS
44 CLOSET
45 EXAM LVT 1 RB 2 P / PL 4 / 3 P-1 ACT 1 SS-1 PLAM-2 PLAM-3 ABOVE CASEWORK; SEE ELEVATIONS 46 EXAM LVT 1 RB 2 P / PL 4 / 3 P-1 ACT 1 SS-1 PLAM-2 PLAM-3 ABOVE CASEWORK; SEE ELEVATIONS 48 BARIATRIC LVT 1 RB 1 P / PL 4 / 3 P-1 ACT 1 SS-1 PLAM-2 PLAM-3 ABOVE CASEWORK; SEE ELEVATIONS
49 CLEAN LVT 1 RB 1 P 1 P-1 ACT 1 PL-2 PL-2
50 STAFF TOILET SV 1 RB 1 P / WP 1 / 4 P-1 ACT 1 WP-4 ON WET WALL; 4'-0" AFF
52 CARE TEAM LVT 1 RB 1 P 1 P-1 ACT 1 PL-2 PL-2 PL-2
53 CHECK IN LVT 1 RB 1 P 1, 6 P-1 ACT 1 SS-1 PL-2 PNT-6 AS ACCENT; SEE FINISH PLAN
54 TOILET SV 1 RB 1 P / WP 1 / 4 P-1 ACT 1 WP-4 ON WET WALL; 4'-0" AFF
55 STORAGE LVT 1 RB 1 P 1 P-1 ACT 1
56 EXAM LVT 1 RB 2 P / PL 4 / 3 P-1 ACT 1 SS-1 PL-2 PLAM-3 ABOVE CASEWORK; SEE ELEVATIONS
59 PROVIDER LVT 1 RB 1 P 1 P-1 ACT 1
62 EXAM LVT 1 RB 2 P / PL 4 / 3 P-1 ACT 1 SS-1 PL-2 PLAM-3 ABOVE CASEWORK; SEE ELEVATIONS
63 CALL CENTER CPT 1 RB 1 P 1 P-1 ACT 1
65 SOILED LVT 1 RB 1 P 1 P-1 ACT 1 PL-2 PL-2
66 EXAM LVT 1 RB 2 P / PL 4 / 3 P-1 ACT 1 SS-1 PL-2 PLAM-3 ABOVE CASEWORK; SEE ELEVATIONS
E43 CORRIDOR EXISTING MATCH TO
EXISTING
MATCH TO
EXISTING
MATCH TO
EXISTING
SCALE: 3/16" = 1'-0" 1 FINISH PLAN
0 2'-8" 5'-4" 10'-8"
FINISH LEGEND
SYMBOL COLOR DESCRIPTION MANUFACTURER PRODUCT FINISH NOTES
FLOOR
CPT 1 CARPET TILE PATRACFT REASON I0459 METHOD 00500 24" X 24"; QUARTER TURN INSTALL
LVT 1 RESILIENT TILE MOHAWK INDUSTRIES HOT & HEAVY SECOYA 152 ARROWHEAD 6" X 48"
LVT 2 RESILIENT TILE PATRACFT MARK MAKING I509V LOAM 00700 6" X 48"
SV 1 RESILIENT SHEET TARKETT ARIA - MELODIA 3.0 21020 VOLCANIC ASH 708 W/ INTEGRAL COVE BASE
TR 1 FLOOR TRANSITION ROPPE REDUCER STRIP COLOR 178 PEWTER
TR 2 FLOOR TRANSITION ROPPE CARPET TILE TO LVT COLOR 178 PEWTER
TRIM
CR 1 CHAIR RAIL ACROVYN 1' TALL CHAIR RAIL MISSION WHITE #933; SUEDE TOP OF CR TO BE 3'-0" AFF
RB 1 RESILIENT BASE JOHNSONITE DC-XXX-4 SHARK FIN TG2 COVE REVEAL
RB 2 RESILIENT BASE JOHNSONITE TIGHTLOCK RESILIENT SHARK FIN TG2 4.25" REVEAL
WALLS
P 1 PAINT BENJAMIN MOORE SWISS COFFEE OC-45 EGGSHELL
P 2 PAINT (NOT USED) BENJAMIN MOORE CHANTILLY LACE OC-65 MATTE
P 3 PAINT (NOT USED) BENJAMIN MOORE STORM AF-700 EGGSHELL
P 4 PAINT SHERWIN WILLIAMS MODERN GRAY SW 7632 EGGSHELL
P 6 PAINT (CHI) BENJAMIN MOORE LAKESIDE CABIN 1658 EGGSHELL
MILLWORK
PL 2 PLASTIC LAMINATE WILSONART HPL VAPOR STRANDZ 4939K-18 LINEARITY
PL 3 PLASTIC LAMINATE FORMICA HPL WHITE DROPS 8824-58 MATTE
SS 1 SOLID SURFACE STARON TEMPEST COCONUT FC112
WALL PROTECTION
CG 1 CORNER GUARDS ACROVYN MISSION WHITE #933; SUEDE
WP 4 WALL PROTECTION WILSONART FRL REINFORCED LAMINATE ASTRO STRANDZ 4940K-18 LINEARITY, AEON SCRATCH RESISTANCE
CEILINGS
ACT 1 ACOUSTICAL CEILING TILE ARMSTRONG ULTIMA TEGULAR; 15/16" 2' X 2'
CR-1;
TYP.
NOTES:
1. J MOULD AT RECEPTION DESK TO BE NICKEL FINISH.
2. WINDOW TRIM TO BE P-1.
3. PROVIDE CORNER GUARDS ON ALL OUTSIDE CORNER
NOTE:
WALL PAINT, WALL BASE AND DOOR TRIM
TO MATCH EXISTING IN CORRIDOR E43.
ADD ALTERNATE 1:
PRICE PLASTIC LAMINATE COUNTERTOPS
IN PLACE OF SOLID SURFACE.
A6.1 A6.1
CHECK IN
A6.1
A6.1 5
A6.1 5
A6.1
SOILED
CLEAN
STAFF TOILET
MEDS
CARE TEAM
B AND S SHELVING;
SEE DETAIL 3/A6.2
6' - 3 3/8" 7' - 5 3/8" 6' - 8 1/8"
5'
1/
4" 5'
1/ 4"
7'
1/
4"
5'
0" 2'
3/ 8"
1' - 6"
EQEQ
1' - 6"
2'
6" 2'
0"
2'
6"
A6.2
A6.2
2'
6"
1' - 6" 1' - 6"
4'
6"
A6.2
A6.2
A6.2
3'
6"
2'
6"
A6.2
A6.2
A6.2
3 3/4"
3 3/4"
3 3/4"
8 13/16" 4' - 1" 11 3/16" 4' - 1"
3 3/4"
ALIGN WITH
WINDOW
ALIGN WITH
WINDOW
J MOULD J MOULD J MOULD
3'
1/
8"
ALIGN
HEAD
HGTS
3' - 0"1' - 9" 3' - 0"2' - 0" 3' - 9" 3' - 0"
2'
6" 1'
6"
3'
0"
6"6"
A6.2
A6.2
A6.2
A6.2
A6.2SIM
6"
5'
9"
2'
6" 1'
6"
3'
0"
1' - 6"11 7/8"2' - 0"2' - 11 5/8"1' - 0"2' - 7 1/2"
A6.2
A6.2
A6.2
A6.2 SIMSIM
9"
REFRIGERATOR
NIC
PL-3
4'
0"
EQUIPMENT RAIL;
ALIGN W/ RT. SIDE OF
PANEL MOUNT
ACCESSORIES W/ UNIVERSAL CLIP
PAPER TOWEL DISPENSER
SOAP DISPENSER
GLOVE DISPENSOR
WIRELESS OTO/OPTHA
SCOPES
SHARPS CONTAINER
OPEN
A6.2
1' - 6 1/4" 3' - 0 3/4"
2'
A6.2
3'
0"
1' - 3" 1' - 3"
A6.2
A6.2
3'
6"
8" 4' - 0" 4' - 0" 8"
C O W A R T
S T R E E T
C H A T T A N O O G A
T N
W W W A R T E C H P R O
JOB NO. D'WN CK'D
ISSUE DATES
INITIAL ISSUE
#21-041 ER/LC KA
PA
R
TI
A
L U
PG
R
A D
E B
U
IL
D
IN
G O
N E
LA
FA
YE
TT
E M
ED
IC
A L
O
FF
IC
E
PA
R
K
ST
AT
E
H
IG
H W
AY
L
AF
AY
ET
TE
G
EO
R G
IA
A6.1
ENLARGED PLANS
AND ELEVATIONS
02/11/22
SCALE: 1/2" = 1'-0" 2 ENLARGED PLAN RECEPTION
SCALE: 1/2" = 1'-0" 3 ENLARGED PLAN CARE TEAM
SCALE: 1/2" = 1'-0" 4 ELEVATION CARE TEAM
SCALE: 1/2" = 1'-0" 7 ELEVATION RECEPTION
SCALE: 1/2" = 1'-0" 8 ELEVATION RECEPTION
SCALE: 1/2" = 1'-0" 6 ELEVATION LAB CASEWORK
SCALE: 1/2" = 1'-0" 9 ELEVATION BREAKROOM
SCALE: 1/2" = 1'-0" 1 TYPICAL EXAM ROOM
SCALE: 1/2" = 1'-0" 5 ELEVATION SOILED/CLEAN
SCALE: 1/2" = 1'-0" 10 BREAK ROOM
SCALE: 1/2" = 1'-0" 11 BREAK ROOM
RELOCATED
STOVE/OVEN/MICROWAVE UNIT
RELOCATED
DISHWASHER
OPEN OPEN OPEN
OPEN
1X4 BACKSPLASH W/
PLASTIC LAMINATE
3/4" PLYWOOD COUNTERTOP
W/ PLASTIC LAMINATE
1X4 BLOCKING
SUPPORT BRACKET
AS NEEDED
2' - 1"
SE
E
EL
EV
AT
IO
N
1/
2" 4"
3/4" PLYWOOD COUNTERTOP
W/ SOLID SURFACE
TYPICAL WALL
CONSTRUCTION
SCHEDULED BASE
SLIDING GLASS WINDOW
(SEE SHEET A8.1)
9"
J MOULD
J MOULD
PLAM PANEL ON Z CLIPS
PLAM PANEL ON Z CLIPS
PLAM CLAD
3/4" PLYWOOD
BRACE AS
NEEDED TO
SUPPORT TOP 1X4 BACKSPLASH W/
PLASTIC LAMINATE
1X4 BLOCKING
3/4" PLYWOOD
W/ PLASTIC LAMINATE
KNEE SPACE
SUPPORT BRACKET
AS NEEDED
3/4" PLYWOOD
ADJUSTABLE SHELF
W/ MELAMINE
1X4 BLOCKING
1X4 BLOCKING
3/4" FINISH PLYWOOD
1X BLOCKING
3/4" PLYWOOD
W/ MELAMINE
1X BLOCKING
SE
E
EL
EV
AT
IO
N 2'
6"
2'
0"
3/4"
2' - 1"
1/
2" 4"
1' - 0"
SE
E
EL
EV
AT
IO
N
4"
2' - 1"
3 3/4"
1X4 BACKSPLASH W/
PLASTIC LAMINATE
3/4" PLYWOOD COUNTERTOP
W/ PLASTIC LAMINATE
1X4 BLOCKING
3/4" PLYWOOD
W/ PLASTIC LAMINATE
1/4" PLYWOOD PAINTED
3/4" PLYWOOD W/ MELAMINE
1X4 BLOCKING
2X4 BLOCKING
3/4" PLYWOOD W/ MELAMINE
1X BLOCKING
6'
1' - 0"
3/4" PLYWOOD ADJUSTABLE
SHELF W/ MELAMINE
1X4 BLOCKING
1X4 BLOCKING
3/4" FINISH PLYWOOD
1X BLOCKING
3/4" PLYWOOD
W/ MELAMINE
1X BLOCKING
1/4" PLYWOOD PAINTED
2'
6" 2'
0"
9"
3/ 4"
3 3/4"
1X4 BACKSPLASH W/
PLASTIC LAMINATE
3/4" PLYWOOD COUNTERTOP
W/ PLASTIC LAMINATE
1X4 BLOCKING
3/4" PLYWOOD
W/ PLASTIC LAMINATE
1/4" PLYWOOD PAINTED
3/4" PLYWOOD
W/ MELAMINE
1X4 BLOCKING
3/4" PLYWOOD ADJUSTABLE
SHELF W/ MELAMINE
2X4 BLOCKING
3/4" PLYWOOD
W/ MELAMINE
1X BLOCKING
3/4" PLYWOOD ADJUSTABLE
SHELF W/ MELAMINE
1X4 BLOCKING
1X4 BLOCKING
3/4" FINISH PLYWOOD
1X BLOCKING
3/4" PLYWOOD
W/ MELAMINE
1X BLOCKING
SE
E
EL
EV
AT
IO
N 1'
6"
2'
6"
1/
2"
1/ 4"
5/
8"
1' - 0"
3/
8"
1/
2"
3 3/4"1X4 BACKSPLASH W/
PLASTIC LAMINATE
3/4" PLYWOOD COUNTERTOP
W/ PLASTIC LAMINATE
1X4 BLOCKING
3/4" PLYWOOD
W/ PLASTIC LAMINATE
3/4" PLYWOOD
W/ MELAMINE
1X4 BLOCKING
2X4 BLOCKING
1X BLOCKING
2'
1/
4"
3/4" PLYWOOD
ADJUSTABLE SHELF
W/ MELAMINE
1X4 BLOCKING
1X4 BLOCKING
3/4" FINISH PLYWOOD
1X BLOCKING
3/4" PLYWOOD
W/ MELAMINE
1X BLOCKING
SE
E
EL
EV
AT
IO
N 2'
0"
2'
6" 1' - 0"
1X4 BACKSPLASH W/
SOLID SURFACE
3/4" PLYWOOD COUNTERTOP
W/ SOLID SURFACE
1X4 BLOCKING
3/4" PLYWOOD
W/ MELAMINE
1X4 BLOCKING
2X4 BLOCKING
SE
E
EL
EV
AT
IO
N
1/
2"
2' - 1"3/4"
4"
SOLID SURFACING ON PLYWOOD
AND BLOCKING TO CREATE PROFILE
SHOWN
3"
PLAM CLAD
3/4" PLYWOOD
BRACE AS
NEEDED TO
SUPPORT TOP
2'
6"
2' - 8 1/2"
SLIDING GLASS WINDOW
(SEE SHEET A8.1)
SCHEDULED BASE
TYPICAL WALL CONSTRUCTION
J MOULD
PLAM PANEL ON Z CLIPS
/8
EQ
EQ
2' - 1"
PLAM TOP PLAM
BACKSPLASH
PLAM DRAWER FACE
MELAMINE DRAWER
BOXES ON DRAWER
SLIDES. TYP.
SE
E
EL
EV
AT
IO
N S
FACE OF WALL
1'-6"
2' -3
2'
-3
2' -3
3/4" PARTICLE
BD. SHELVES
W/ MELAMINE
ON HEAVY DUTY
STANDARDS
& BRACKETS
@ 16" O.C.
(SOLID BLKG.
AT STANDARDS)
SE
E
EL
EV
AT
IO
N S
4"
2' - 1"
3 3/4"
1X4 BACKSPLASH W/
PLASTIC LAMINATE
3/4" PLYWOOD COUNTERTOP
W/ PLASTIC LAMINATE
1X4 BLOCKING
3/4" PLYWOOD
W/ PLASTIC LAMINATE
1/4" PLYWOOD
PAINTED
3/4" PLYWOOD
W/ MELAMINE
1X4 BLOCKING
3/4" PLYWOOD
ADJUSTABLE SHELF
W/ MELAMINE
2X4 BLOCKING
3/4" PLYWOOD
W/ MELAMINE
1X BLOCKING
1/
4"
3/ 8"
2' - 0"
2'
2'
3"
1/
2"
1/ 2"
QUARTZ 2
(SEE FINISH LEGEND)
QUARTZ 2 APRON
(SEE FINISH LEGEND)
PLAM ON 1/2" PLYWOOD (TYP.)
(SEE FINISH LEGEND)
2X4's AT 26" O.C.
QUARTZ BACKSPLASH
(SEE FINISH LEGEND)
REMOVABLE PANEL
6" 8" MIN
C O W A R T
S T R E E T
C H A T T A N O O G A
T N
W W W A R T E C H P R O
JOB NO. D'WN CK'D
ISSUE DATES
INITIAL ISSUE
#21-041 ER/LC KA
PA
R
TI
A
L U
PG
R
A D
E B
U
IL
D
IN
G O
N E
LA
FA
YE
TT
E M
ED
IC
A L
O
FF
IC
E
PA
R
K
ST
AT
E
H
IG
H W
AY
L
AF
AY
ET
TE
G
EO
R G
IA
A6.2
INTERIOR DETAILS
02/11/22
SCALE: 1" = 1'-0" 1 DETAIL - COUNTERTOP W/ TRANSACTION
SCALE: 3/4" = 1'-0" 4 DETAIL - UPPER CAB. W/ COUNTERTOP
SCALE: 3/4" = 1'-0" 5 DETAIL - UPPER CAB. W/ DRAWER BASE
SCALE: 3/4" = 1'-0" 9 DETAIL - TYPICAL CABINETS
SCALE: 3/4" = 1'-0" 10 DETAIL - TYPICAL SINK BASE
SCALE: 1" = 1'-0" 8 DETAIL - LINEN DROP BASE
MILLWORK GENERAL NOTES:
1. ALL MILLWORK CONSTRUCTION TO BE PLASTIC LAMINATE COVERED,
AWI SECTION 400 CUSTOM GRADE, FLUSH OVERLAY CONSTRUCTION.
2. CONTRACTOR SHALL INSTALL ADEQUATE WOOD BLOCKING IN ALL
STUD WALLS RECEIVING CASEWORK ANCHORS AND ATTACHMENTS.
3. CONTRACTOR TO PROVIDE MILLWORK SHOP DRAWINGS.
4. CONTRACTOR TO FIELD VERIFY ALL DIMENSIONS.
5. ALL OPEN SHELVING TO COMPLY WITH AWI SECTION 400B CUSTOM GRADE
6. DOOR AND DRAWER FRONTS TO BE 3/4" SUBSTRATE WITH PLASTIC
LAMINATE FINISH ON ALL EXPOSED SURFACES.
7. BODY OF DRAWERS TO BE 3/4" SUBSTRATE WITH MELAMINE FINISH ON
ALL SURFACES.
8. INTERIOR SHELVES TO BE 3/4" SUBSTRATE WITH MELAMINE FINISH ON ALL
SIDES, COLOR TO MATCH THE INTERIOR OF THE CABINET IN WHICH IT
OCCURS, UNLESS NOTED OTHERWISE.
9. ALL SURFACE ON THE INTERIOR OF THE CABINETS TO BE MELAMINE CLAD.
10 USE 2" GROMMETS AT COMPUTER STATIONS. FIELD INSTALL AT OWNERS
DIRECTION.
11. ALL NON METAL UNDERCOUNTER SUPPORT BRACKETS TO BE PLASTIC
LAMINATE CLAD.
12. ALL EXPOSED CORNERS ON WORKSURFACES TO HAVE A RADIUSED EDGE.
13. HARDWARE TO BE EQUAL TO:
HINGES: CONCEALED, SELF CLOSING GRASS 1003
SLIDES: BLUM 230M
BUMPERS: BLUM #TP-1950
STANDARDS AND CLIPS: KV225, ZING OR HOLES BORED
AT 32MM CENTERS WITH HAFELE PINS 282.04.711 NICKEL
PULLS: EQUAL TO OUTWATER PLASTICS PULL 5 1/16" C/C
BRUSHED STAINLESS STEEL #PULL-DMZ128-SS
SCALE: 1" = 1'-0" 6 ADA RECEPTION
SCALE: 1" = 1'-0" 2 BASE CABINET
SCALE: 1" = 1'-0" 3 BRACKET AND STANDARDS
SCALE: 1" = 1'-0" 7 TYPICAL BUILT-IN WORK SURFACE
SCALE: 3/4" = 1'-0" 11 SECTION (ADA VANITY)
2'
0"
2' - 0"
A7.1
A7.1
ALIGN WIDTH OF LIGHT
POCKET TO EDGES OF TRANSOM
ALIGN WIDTH OF LIGHT
POCKET TO EDGES OF TRANSOM
LEGEND
24" X 24" ACOUSTIC SEILING TILE
24" X 48" LED TROFFER
48" LED STRIP
24" x 24" SUPPLY DIFFUSER
24" x 24" RETURN DIFFUSER
12" x 12" SUPPLY DIFFUSER
12" x 24" RETURN DIFFUSER
2x2 LAY-IN CEILING
(REFER TO PLAN)
EXTEND 5/8" G.W.B. 6"
ABOVE CEILING
G.W.B. HEADER @ 24" O.C.
(3 5/8" METAL STUD
FRAMING TO DECK)
EXTEND 5/8" G.W.B 6"
ABOVE CEILING
2x2 GYP. BOARD4"
EXISTING
TRANSOM1"
C O W A R T
S T R E E T
C H A T T A N O O G A
T N
W W W A R T E C H P R O
JOB NO. D'WN CK'D
ISSUE DATES
INITIAL ISSUE
#21-041 ER/LC KA
PA
R
TI
A
L U
PG
R
A D
E B
U
IL
D
IN
G O
N E
LA
FA
YE
TT
E M
ED
IC
A L
O
FF
IC
E
PA
R
K
ST
AT
E
H
IG
H W
AY
L
AF
AY
ET
TE
G
EO
R G
IA
A7.1
REFLECTED CEILING
PLAN
02/11/22
SCALE: 3/16" = 1'-0" 1 REFLECTED CEILING PLAN
SCALE: 1 1/2" = 1'-0" 2 DETAIL - HEADER
0 2'-8" 5'-4" 10'-8"
EXISTING
EXISTING
ALL CEILING HEIGHTS ARE 8'-6" UNLESS NOTED
OTHERWISE
PE
R
D O
O R
H
EI
G H
T
WIDTH
PER DOOR
A
PE
R
D O
O R
H
EI
G H
T
WIDTH
PER DOOR
B
PE
R
D O
O R
H
EI
G H
T
WIDTH
PER DOOR
C
PE
R
D O
O R
H
EI
G H
T
WIDTH
PER DOOR
2"
A
DOOR
METAL STUD HEADER
METAL FRAME
SEALANT BOTH SIDES
DRYWALL ON METAL
STUD FRAMING
DOOR
(3) STEEL STUD JAMB
ANCHORS & FLOOR
ANCHOR EACH JAMB, TYP
METAL FRAME, SPOT GROUT
SEALANT BOTH SIDES
DRYWALL ON METAL
STUD FRAMING
2"
HEAD JAMB
CL
O
FIXED PANEL
X
SLIDING PANEL
SEE ELEVATION
1/8"
3/
1/ 8"
1/8"
EK671 - ROLLER ASSEMBLY
CB1 - CLEAR
PLASTIC
BUMPERS
LK49 - PUSH BUTTON LOCK
SE
E
EL
EV
AT
IO
N
1'
/8
A8.1
A8.1
A8.1
2"
7/8"
/1
6"
1/
2"
1/ 4"
D
LO
R O
CLEAR SILICONE SET
D26 - FIXED LITE INSERT
D24 - OVERHEAD
TRACK
FASTERNER BY INSTALLER
DK14LGH1CH-ASSY
EK671 - ROLLER
ASSEMBLY
CLERK SIDE CUSTOMER SIDE
D281 GUIDES
D281 GUIDES
LK51 - DOOR PULL/STRIKE
D631 - BOTTOM U-CHANNEL WITH
PSB125 SETTING BLOCKS
LK49 - PUSH BUTTON
LOCK
CUSTOMER SIDE
CLERK SIDE
CUSTOMER SIDE
CLERK SIDE
1/8"
6 1/8"
1/8"
6 1/8"
7/
7/
9/
2"
CL
CB1 - CLEAR PLASTIC
BUMPERS
CB1 - CLEAR PLASTIC
BUMPERS
SE
E
EL
EV
AT
IO
N
1'
/8
3/
GAP
7/16"
1/
2"
2"
CLERK SIDE CUSTOMER SIDE
9/16" 7/16" 9/16" 7/16"
3/
7/
1/ 8"
5/
7/8"
1/4" 7/16" 1/4"
7/
R O D
LO D281 GUIDE
D631 - BOTTOM RAIL WITH
PSB125 SETTING BLOCKS
SILICONE SEAL
1/4" TEMPERED GLASS
CLERK SIDE CUSTOMER SIDE
C O W A R T
S T R E E T
C H A T T A N O O G A
T N
W W W A R T E C H P R O
JOB NO. D'WN CK'D
ISSUE DATES
INITIAL ISSUE
#21-041 ER/LC KA
PA
R
TI
A
L U
PG
R
A D
E B
U
IL
D
IN
G O
N E
LA
FA
YE
TT
E M
ED
IC
A L
O
FF
IC
E
PA
R
K
ST
AT
E
H
IG
H W
AY
L
AF
AY
ET
TE
G
EO
R G
IA
A8.1
DOOR SCHEDULE &
DETAILS
02/11/22
SCALE: 1/4" = 1'-0"
DOOR TYPE
DOOR SCHEDULE
MARK ROOM NAME
DOOR DOOR SIZE FRAME HARDWARE FIRE RATING COMMENTSTYPE MATERIAL DOOR FINISH DOOR WIDTH DOOR HEIGHT TYPE MATERIAL FINISH HEAD JAMB
N35 MEDS C SC WD STAINED TO MATCH
EXISTING 6' - 0" 7' - 0" A HM PNT 1/A8.1 1/A8.1 1 N/A
N36A WAITING B SC WD STAINED TO MATCH
EXISTING 3' - 0" 7' - 0" A HM PNT 1/A8.1 1/A8.1 2 N/A
N36B WAITING B SC WD STAINED TO MATCH
EXISTING 3' - 0" 7' - 0" A HM PNT 1/A8.1 1/A8.1 2 N/A
N40 OFFICE
MANAGER
A SC WD STAINED TO MATCH
EXISTING 3' - 0" 7' - 0" A HM PNT 1/A8.1 1/A8.1 3 N/A
N43 PROVIDER A SC WD STAINED TO MATCH
EXISTING 3' - 0" 7' - 0" A HM PNT 1/A8.1 1/A8.1 3 N/A
N44 EXAM A SC WD STAINED TO MATCH
EXISTING 3' - 0" 7' - 0" A HM PNT 1/A8.1 1/A8.1 4 N/A
N44 STORAGE A SC WD STAINED TO MATCH
EXISTING 3' - 0" 7' - 0" A HM PNT 1/A8.1 1/A8.1 1 N/A
N45 EXAM A SC WD STAINED TO MATCH
EXISTING 3' - 0" 7' - 0" A HM PNT 1/A8.1 1/A8.1 4 N/A
N46 EXAM A SC WD STAINED TO MATCH
EXISTING 3' - 0" 7' - 0" A HM PNT 1/A8.1 1/A8.1 4 N/A
N48 BARIATRIC SC WD STAINED TO MATCH
EXISTING 4' - 0" 7' - 0" A HM PNT 1/A8.1 1/A8.1 4 N/A
N49 CLEAN A SC WD STAINED TO MATCH
EXISTING 3' - 0" 7' - 0" A HM PNT 1/A8.1 1/A8.1 5 N/A
N50 TOILET A SC WD STAINED TO MATCH
EXISTING 3' - 0" 7' - 0" A HM PNT 1/A8.1 1/A8.1 6 N/A
N53 CHECK IN A SC WD STAINED TO MATCH
EXISTING 3' - 0" 7' - 0" A HM PNT 1/A8.1 1/A8.1 8 N/A
N55 STORAGE A SC WD STAINED TO MATCH
EXISTING 3' - 0" 7' - 0" A HM PNT 1/A8.1 1/A8.1 7 N/A
N56 EXAM A SC WD STAINED TO MATCH
EXISTING 3' - 0" 7' - 0" A HM PNT 1/A8.1 1/A8.1 4 N/A
N59 PROVIDER A SC WD STAINED TO MATCH
EXISTING 3' - 0" 7' - 0" A HM PNT 1/A8.1 1/A8.1 3 N/A
N62 EXAM A SC WD STAINED TO MATCH
EXISTING 3' - 0" 7' - 0" A HM PNT 1/A8.1 1/A8.1 4 N/A
N65 SOILED A SC WD STAINED TO MATCH
EXISTING 3' - 0" 7' - 0" A HM PNT 1/A8.1 1/A8.1 5 N/A
N66 EXAM A SC WD STAINED TO MATCH
EXISTING 3' - 0" 7' - 0" A HM PNT 1/A8.1 1/A8.1 4 N/A
SCALE: 1/4" = 1'-0"
FRAME TYPE
SCALE: 3" = 1'-0" 1 DOOR DETAIL - INTERIOR, HEAD & JAMB DETAIL METAL STUD
NOTES:
1. DOOR HARDWARE STYLE AND FINISH TO MATCH EXISTING.
SCALE: 3/4" = 1'-0" 2 PASS THROUGH ELEVATION - CLERK SIDE
SCALE: 6" = 1'-0" 3 PASS THROUGH HEAD
SCALE: 3" = 1'-0" 4 PASS THROUGH PLAN VIEW
SCALE: 3/4" = 1'-0" 6 PASS THROUGH SECTION
SCALE: 6" = 1'-0" 7 PASS THROUGH SILL
DOOR HARDWARE
1. HINGES, CLASSROOM SET, CLOSER
2. HINGES, PASSAGE SET, CLOSER
3. HINGES, OFFICE SET, DOOR STOP
4. HINGES, PRIVACY SET, DOOR STOP
5. HINGES, CLASSROOM SET
6. HINGES, PRIVACY SET, CLOSER, DOOR STOP
7. HINGES, CLASSROOM SET, DOOR STOP
C O W A R T
S T R E E T
C H A T T A N O O G A
T N
W W W A R T E C H P R O
JOB NO. D'WN CK'D
ISSUE DATES
INITIAL ISSUEREVISION HISTORY
REVISION REVISION DESCRIPTIONDATE
#21-041 ER/LC KA
PA
R
TI
A
L U
PG
R
A D
E B
U
IL
D
IN
G O
N E
LA
FA
YE
TT
E M
ED
IC
A L
O
FF
IC
E
PA
R
K
ST
AT
E
H
IG
H W
AY
L
AF
AY
ET
TE
G
EO
R G
IA
T1.1
TITLE SHEET
02/11/22
PARTIAL UPGRADE BUILDING ONE
LAFAYETTE MEDICAL OFFICE PARK
STATE HIGHWAY 136
LAFAYETTE GEORGIA
8 Sheet Name
(0 2-
-2
2) Is su e
Da te
GENERAL
T1.1 TITLE SHEET X
T1.2 BUILDING CODE SUMMARY X
T1.3 LIFE SAFETY PLAN X
T1.4 ADA COMPLIANCE STANDARDS X
T1.5 ADA COMPLIANCE STANDARDS X
T1.6 ADA COMPLIANCE STANDARDS X
T1.7 ADA COMPLIANCE STANDARDS X
T7.8 SPECIFICATIONS X
T7.9 SPECIFICATIONS X
ARCHITECTURAL
A1.1 FLOOR PLAN X
A1.1D DEMOLITION PLAN X
A1.1F FINISH PLAN X
A6.1 ENLARGED PLANS AND ELEVATIONS X
A6.2 INTERIOR DETAILS X
A7.1 REFLECTED CEILING PLAN X
A8.1 DOOR SCHEDULE & DETAILS X
MECHANICAL
M0.1 COVER SHEET X
M1.1 HVAC DEMOLITION PLAN X
M2.1 HVAC NEW WORK PLAN X
M2.2 ATTIC HVAC NEW WORK PLAN X
M2.3 HVAC PIPING NEW WORK PLAN X
M3.1 SCHEDULES, SPECS, & CONTROLS X
M4.1 SCHEDULES, SPECS, & CONTROLS X
M4.2 DETAILS X
PLUMBING
P0.1 COVER SHEET X
P1.1 SOIL, WASTE AND VENT DEMOLITION PLAN X
P1.2 DOMESTIC WATER DEMOLITION PLAN X
P1.3 NATURAL GAS DEMOLITION PLAN X
P2.1 SOIL, WASTE AND VENT NEW WORK PLAN X
P2.2 DOMESTIC WATER NEW WORK PLAN X
P2.3 NATURAL GAS NEW WORK PLAN X
P3.1 SCHEDULES & SPECIFICATIONS X
P3.2 PLUMBING DETAILS X
ELECTRICAL
E1.1 FLOOR PLAN X
E1.2 FLOOR PLAN X
E1.3 FLOOR PLAN X
E2.0 SCHEDULES, LEGEND, AND DETAILS X
E2.1 SCHEDULES, LEGEND, AND DETAILS X
INDEX OF DRAWINGS
1 View Name
SCALE:1/8" = 1'-0"
1i
XX
+XX'
TITLE SYMBOL
SECTION SYMBOL
SECTION #X
SHEET #AX.X
DETAIL SYMBOL
DETAIL #X
SHEET #AX.X
ENLARGED DETAIL SYMBOL
DETAIL #X
SHEET #AX.X
INTERIOR ELEVATION SYMBOL
ELEVATION #XX
SHEET #AX.X
EXTERIOR ELEVATION SYMBOL
ELEVATION #XX
SHEET #AX.X
INTERIOR ROOM SYMBOL
ROOM #XXX
DOOR SYMBOL
DOOR #XXX
STOREFRONT SYMBOL
SEE STOREFRONT SCHEDULE
WALL TYPES SYMBOL
SEE WALL/PARTITION LEGEND
FINISH ELEVATION SYMBOL
ELEVATION NUMBER
REVISION SYMBOL
AX.X
XX
AX.X XX
AX.X
SIM
AX.X
SIM
AX.X
SIM
XX
XX
Room Name
NAME OF PROJECT:
ADDRESS:
PROPOSED USE:
OWNER/CONTACT PERSON:
CODE ENFORCEMENT JURISDICTION:
LAFAYETTE MEDICAL OFFICE PARK
STATE HIGHWAY 136
PHYSICIAN OFFICE
DAVID HAMILTON
LAFAYETTE
PHONE: (706) 639-1501
PROJECT INFORMATION
APPLICABLE CODES
ARCHITECTURAL:
ELECTRICAL:
PLUMBING:
MECHANICAL:
LIFE SAFETY:
GAS:
ENERGY:
ACCESSIBILITY:
IBC 2021
DESIGNER OF RECORD
DESIGNER
ARCHITECTURAL:
ELECTRICAL:
PLUMBING:
MECHANICAL:
STRUCTURAL:
CIVIL:
NAME LICENSE # TELEPHONE #
N/A
DAVID HUDSON RA006113 (423) 265-4313
N/A
JEFF RAYBURN 28023 (423) 304-9699
JEFF RAYBURN 28023 (423) 304-9699
HAROLD DAMRON 46889 (865) 567-3582
BUILDING DATA
OCCUPANCY TYPE:
MIXED OCCUPANCY:
CONSTRUCTION TYPE:
SPRINKLED:
FIRE DISTRICT:
BUILDING HEIGHT:
MEZZANINE:
HIGH RISE:
GROSS BUILDING AREA:
TOTAL GROSS AREA:
AREA INCREASE:
BUSINESS
NO
NO
(YES/NO)
NO
NO
NO
VB MIXED CONSTRUCTION: (YES/NO)
SEPARATION: (HR)
(EX: NFPA-13, NFPA-13R, NFPA13-D)
EXISTING NUMBER OF STORIES: 1
FIRE RESISTANCE RATINGS
EXTERIOR BEARING WALLS:
EXTERIOR NON-BEARING WALLS:
NORTH
EAST
WEST
SOUTH
NORTH
EAST
WEST
SOUTH
INTERIOR WALLS:
BEARING
NON-BEARING
PARTY/FIRE WALLS:
REQUIRED
HOURLY
DETAIL # &
SHEET #
% WALL
OPENING
DESIGN # FOR RATED
ASSEMBLIES
NA NA NA NA
NA NA NA NA
NA NA NA NA
NA NA NA NA
NA NA NA NA
NA NA NA NA
NA NA NA NA
NA NA NA NA
NA NA NA NA
NA NA NA NA
NA NA NA NA
CEILING-FLOORS ASSEMBLY:
BEAMS:
COLUMNS:
CEILING-ROOF ASSEMBLY:
VERTICAL SHAFTS:
CHASES - P.E.M.:
MIXED OCCUPANCY SEPARATION:
TENANT SEPARATION:
NA NA NA NA
NA NA NA NA
NA NA NA NA
NA NA NA NA
NA NA NA NA
NA NA NA NA
NA NA NA NA
NA NA NA NA
LIFE SAFETY SYSTEMS
EMERGENCY LIGHTING AND EXIT SIGNS:
FIRE ALARM AND SMOKE DETECTOR SYSTEMS:
PANIC HARDWARE:
EXIT REQUIREMENTS
DEAD END LIMIT-MAXIMUM CONDITION:
TRAVEL DISTANCE TO EXIT - MAXIMUM CONDITION:
NOTE: SEE LIFE SAFETY PLAN ON SHEET T1.3
YES
YES
YES
20 FEET
200 FEET
TOTAL FIXTURE SUMMARY
TOTAL OCCUPANT LOAD: 108
FIXTURES - MALE & FEMALE
LAVATORIES
WATER CLOSETS
REQUIRED PROVIDED
4 8
4 8
NEC 2011
IPC 2012
IMC 2012
NFPA 101 2012
IFGC 2012
IECC 2012
2012 ADA
10776 SQ. FEET 4,340 SQ. FT RENOVATED
10776 SQ. FEET
7/
8" 3 5/8" STEEL STUDS @ 24" O.C. TO BOTTOM OF STRUCTURE1
ONE LAYER 5/8" GYPSUM BOARD EACH SIDE TO 6" ABOVE CEILING2
(3 5/8" STEEL STUD WALL NON-RATED)
1/
4" 6" STEEL STUDS @ 16" O.C. TO BOTTOM OF STRUCTURE1
ONE LAYER 5/8" GYPSUM BOARD EACH SIDE TO 6" ABOVE CEILING2
(6" STEEL STUD WALL NON-RATED)
(3 5/8" STEEL STUD WALL NON-RATED W/ INSULATION)
7/
8" 3 5/8" STEEL STUDS @ 24" O.C. TO BOTTOM OF STRUCTURE1
ONE LAYER 5/8" GYPSUM BOARD EACH SIDE TO 6" ABOVE CEILING2
BATT INSULATION2
BATT INSULATION2
C O W A R T
S T R E E T
C H A T T A N O O G A
T N
W W W A R T E C H P R O
JOB NO. D'WN CK'D
ISSUE DATES
INITIAL ISSUE
#21-041 ER/LC KA
PA
R
TI
A
L U
PG
R
A D
E B
U
IL
D
IN
G O
N E
LA
FA
YE
TT
E M
ED
IC
A L
O
FF
IC
E
PA
R
K
ST
AT
E
H
IG
H W
AY
L
AF
AY
ET
TE
G
EO
R G
IA
T1.2
BUILDING CODE
SUMMARY
02/11/22
1. REFER TO WALL SECTIONS FOR CONSTRUCTION OF EXTERIOR WALLS.
2. SPECIAL CONDITIONS AND SPECIAL PARTITIONS ARE INDICATED ON PLANS AND DETAILS.
3. WALLS SHOWN WITH MORE THAN ONE INDICATOR SHALL CONTAIN ALL COMPONENTS OF THE WALL TYPES INDICATED.
4. ALL INTERIOR STUD SPACING TO BE 24" O.C. UNLESS NOTED OTHERWISE.
5. ALL INTERIOR METAL STUD WALLS TO BE 20 GAUGE UNLESS NOTED OTHERWISE.
6. WHERE STUDS EXTEND TO ROOF DECK, PROVIDE A SLIP JOINT TRACK (SUPERIOR METAL TRIM, SFT TYPE 53 OR EQUAL)
7. PROVIDE SOLID WOOD BLOCKING IN WALLS AT ALL TOILET ACCESSORY, DOOR STOP AND TOILET PARTITION LOCATIONS, AS REQUIRED.
1. WHERE A DETAIL IS SHOWN OR NOTE IS DESCRIBED FOR ONE CONDITION IT SHALL
APPLY FOR ALL LIKE OR SIMILAR CONDITIONS EVEN THOUGH NOT SPECIFICALLY MARKED
ON THE DRAWINGS
2. CONTRACTOR SHALL FIELD VERIFY ALL DIMENSIONS AND LOCATIONS AFFECTING
THIS PROJECT PRIOR TO FABRICATION OR INSTALLATION OF NEW WORK. NOTIFY
ARCHITECT OF ANY DISCREPANCIES FROM DIMENSIONS SHOWN, NOTED OR REQUIRED.
ADJUST DIMENSIONS OF NEW CONSTRUCTION AT DIRECTION OF ARCHITECT TO ALLOW FOR
ACTUAL FIELD DIMENSIONS.
3. PROVIDE OPENINGS WITH LINTELS OR HEADERS IN WALLS/PARTITIONS AS
REQUIRED FOR MECHANICAL, ELECTRICAL AND PLUMBING WORK.
4. PROVIDE WOOD BLOCKING AS REQUIRED IN WALLS FOR ALL WALL MOUNTED
CASEWORK, SHELVES, EQUIPMENT, ACCESSORIES, AND AS INDICATED FOR INSTALLATION
OF EQUIPMENT BY OTHERS.
5. WOOD BLOCKING AND/OR NAILERS ARE GENERALLY SHOWN IN A GENERIC
FASHION - CONTRACTOR MUST COORDINATE EXACT BLOCKING REQUIREMENTS WITH
COMPONENT MANUFACTURER'S SUGGESTIONS OR STANDARDS, AND WITH OTHER TRADES.
ARCHITECT:
ARTECH DESIGN GROUP
1410 COWART STREET CHATTANOOGA, TN 37408
CONTACT: VALERIE MELCHER P:(423) 643-0606
EMAIL: VALERIEM@artech.pro
OWNER CONTACT:
MEMORIAL HOSPITAL
725 GLENWOOD DRIVE, STE 890 CHATTANOOGA, TN 37404
CONTACT: DUSTIN EDGE P:(423) 495-7862
EMAIL: Dustin_Edge@memorial.org
ENGINEERS:
COMPASS COMISSIONING AND DESIGN
1605 HAMIL ROAD CHATTANOOGA TENNESSEE
CONTACT: JEFF RAYBURN P:(423) 304-9699
EMAIL: JRAYBURN@COMPASSCX.COM
WALL LEGEND
WALL/PARTITION NOTES:
PARTITION LEGEND:
GENERAL NOTES
SYMBOLS
CONTACT LIST
VICINITY MAP CODE SUMMARY
KEY PLAN
N
N
117' TRAVEL DISTANCE PROVIDED
(200' MAXIMUM ALLOWED)
105' TRAVEL DISTANCE PROVIDED
(200' MAXIMUM ALLOWED)
NO WORK IN AREA SHOW WITHIN HATCH
EXIT WIDTH PROVIDED
LEGEND FIRST FLOOR
AREA
4340 SF BUSINESS @ 1/100 = 44 OCCUPANTS
PERSONS PROVIDED
EGRESS CAPACITY
PATH OF TRAVEL
EGRESS
BUILDING CODE
2012 I.B.C.
FEC FIRE EXTINGUISHER CABINET
44 PEOPLE x 0.2 = 6.4" OF EGRESS REQUIRED
2 DOORS @ 64" = 128"
FOR A TOTAL OF 128" OF EGRESS WIDTH PROVIDED
C O W A R T
S T R E E T
C H A T T A N O O G A
T N
W W W A R T E C H P R O
JOB NO. D'WN CK'D
ISSUE DATES
INITIAL ISSUE
#21-041 ER/LC KA
PA
R
TI
A
L U
PG
R
A D
E B
U
IL
D
IN
G O
N E
LA
FA
YE
TT
E M
ED
IC
A L
O
FF
IC
E
PA
R
K
ST
AT
E
H
IG
H W
AY
L
AF
AY
ET
TE
G
EO
R G
IA
T1.3
LIFE SAFETY PLAN
02/11/22
SCALE: 1/8" = 1'-0" 1 LIFE SAFETY PLAN
0 8' 16'4'
1O
PE
N
IN
G A
T
O
C C
U
PA
N
TS
AC
TU
AL
1OPENING AT 68"/.2 = 340 OCCUPANTS
ACTUAL 44
704 Telephones
704.1 General. Public telephones shall comply with 704.
704.2 Wheelchair Accessible Telephones. Wheelchair accessible telephones shall comply with 704.2.
704.2.1 Clear Floor or Ground Space. A clear floor or ground space complying with 305 shall be provided. The clear floor or ground space shall not be obstructed by bases, enclosures, or seats.
Advisory 704.2.1 Clear Floor or Ground Space. Because clear floor and ground space is required to be unobstructed, telephones, enclosures and related telephone book storage cannot encroach on the required clear floor or ground space and must comply with the provisions for protruding objects. (See Section 307).
704.2.1.1 Parallel Approach. Where a parallel approach is provided, the distance from the edge of the telephone enclosure to the face of the telephone unit shall be 10 inches (255 mm) maximum.
M
AX10
" M
AX
Figure 704.2.1.1 Parallel Approach to Telephone
704.2.1.2 Forward Approach. Where a forward approach is provided, the distance from the front edge of a counter within the telephone enclosure to the face of the telephone unit shall be 20 inches (510
mm) maximum.
Figure 704.2.1.2 Forward Approach to Telephone
704.2.2 Operable Parts. Operable parts shall comply with 309. Telephones shall have push-button controls where such service is available.
704.2.3 Telephone Directories. Telephone directories, where provided, shall be located in accordance with 309.
704.2.4 Cord Length. The cord from the telephone to the handset shall be 29 inches (735 mm) long minimum.
704.3 Volume Control Telephones. Public telephones required to have volume controls shall be equipped with a receive volume control that provides a gain adjustable up to 20 dB minimum. For incremental volume control, provide at least one intermediate step of 12 dB of gain minimum. An automatic reset shall be provided.
Advisory 704.3 Volume Control Telephones. Amplifiers on pay phones are located in the base or the handset or are built into the telephone. Most are operated by pressing a button or key. If the microphone in handset is not being used, a mute button that temporarily turns off the microphone can also reduce the amount of background noise which the person hears in the earpiece. If a volume adjustment is provided that allows the user to set the level anywhere from the base volume to the upper requirement of 20 dB, there is no need to specify a lower limit. If a stepped volume control is provided, one of the intermediate levels must provide 12 dB of gain. Consider compatibility issue when matching an amplified handset with a phone or phone system. Amplified handset that can be switched with pay telephone handsets are available. Portable and in-line amplifiers can be used with some phones but are not practical at most public phones covered by these requirements.
704.4 TTYs. TTYs required at a public pay telephone shall be permanently affixed within, or adjacent to, the telephone enclosure. Where an acoustic coupler is used, the telephone cord shall be sufficiently long to allow connection of the TTY and the telephone receiver.
Advisory 704.4 TTYs. Ensure that sufficient electrical service is available where TTYs are to be installed.
704.4.1 Height. When in use, the touch surface of TTY keypads shall be 34 inches (865 mm) minimum above the finish floor.
EXCEPTION: Where seats are provided, TTYs shall not be required to comply with 704.4.1.
Advisory 704.4.1 Height. A telephone with a TTY installed underneath cannot also be a wheelchair accessible telephone because the required 34 inches (865 mm) minimum keypad height can cause the highest operable part of the telephone, usually the coin slot, to exceed the maximum permitted side and forward reach ranges. (See Section 308).
Advisory 704.4.1 Height Exception. while seats are not required at TTYs, reading and typing at TTY is more suited to sitting than standing. Facilities that often provide seats at TTY's include, but are not limited to, airports and other passenger terminals or stations, courts, art galleries, and convention centers.
704.5 TTY Shelf. Public pay telephones required to accommodate portable TTYs shall be equipped with a shelf and an electrical outlet within or adjacent to the telephone enclosure. The telephone handset shall be capable of being placed flush on the surface of the shelf. The shelf shall be capable of accommodating a TTY and shall have 6 inches (150 mm) minimum vertical clearance above the area where the TTY is to be placed.
705 Detectable Warnings
705.1 General. Detectable warnings shall consist of a surface of truncated domes and shall comply with 705.
705.1.1 Dome Size. Truncated domes in a detectable warning surface shall have a base diameter of 0.9 inch (23 mm) minimum and 1.4 inches (36 mm) maximum, a top diameter of 50 percent of the base diameter minimum to 65 percent of the base diameter maximum, and a height of 0.2 inch (5.1 mm).
705.1.2 Dome Spacing. Truncated domes in a detectable warning surface shall have a center-to-center spacing of 1.6 inches (41 mm) minimum and 2.4 inches (61 mm) maximum, and a base-to-base spacing of 0.65 inch (17 mm) minimum, measured between the most adjacent domes on a square grid.
705.1.3 Contrast. Detectable warning surfaces shall contrast visually with adjacent walking surfaces either light-on-dark, or dark-on-light.
1.6" - 2.4"
1.
6"
2.
4"
0.
" M
IN
0.
2"
(b) plan
(a) elevation (enlarged) top diameter of 50%-65% of the base diameter base diameter of 0.9-1.4
(23-36 mm)
Figure 705.1 Size and Spacing of Truncated Domes
705.2 Platform Edges. Detectable warning surfaces at platform boarding edges shall be 24 inches (610 mm) wide and shall extend the full length of the public use areas of the platform.
707 Automatic Teller Machines and Fare Machines
Advisory 707 Automatic Teller Machines and Fare Machines. Interactive transaction machines (ITMs) , other than ATMs, are not covered by Section 707. However, for entities covered by the ADA, the Department of Justice regulations that implement the ADA provide additional guidance regarding the relationship between these requirements and elements that are not directly addressed by these requirements. Federal procurement law requires that ITMs purchase by Federal government comply with standards issue by the Access Board under Section 508 of the Rehabilitation Act of 1973, as amended. This law covers a variety of products, including computer hardware and software, websites, phone systems, fax machines, copiers, and similar technologies.
For more information on Section 508 consult Access Board's website at www.access-board.gov.
707.1 General. Automatic teller machines and fare machines shall comply with 707.
Advisory 707.1 General. If farecards have one tactually distinctive corner they can be inserted with accuracy. Token collection devices that are designed to accommodate tokens which are perforated can allow a person to distinguish more readily between tokens and common coins. Place accessible gates and fare vending machines in close proximity to other accessible elements when feasible so the facility is easier to use.
707.2 Clear Floor or Ground Space. A clear floor or ground space complying with 305 shall be provided.
EXCEPTION: Clear floor and ground space shall not be required at drive-up only automatic teller machines and fare machines.
707.3 Operable Parts. Operable parts shall comply with 309. Unless a clear or correct key is provided, each operable part shall be able to be differentiated by sound or touch, without activation.
EXCEPTION: Drive-up only automatic teller machines and fare machines shall not be required to comply with 309.2 and 309.3.
707.4 Privacy. Automatic teller machines shall provide the opportunity for the same degree of privacy of input and output available to all individuals.
Advisory 707.4 Privacy. In addition to people who are blind or visually impaired, people with limited reach who wheelchairs or have short stature, who cannot effectively block the ATM screen with their bodies, may prefer to use speech output. Speech output users can benefit from an option to render the visible screen blank, thereby affording them greater personal security and privacy.
707.5 Speech Output. Machines shall be speech enabled. Operating instructions and orientation, visible transaction prompts, user input verification, error messages, and all displayed information for full use shall be accessible to and independently usable by individuals with vision impairments.
Speech shall be delivered through a mechanism that is readily available to all users, including but not limited to, an industry standard connector or a telephone handset. Speech shall be recorded or digitized human, or synthesized.
EXCEPTIONS:
1. Audible tones shall be permitted instead of speech for visible output that is not displayed for security purpose, including but not limited to, asterisks representing personal identification numbers.
2. Advertisements and similar information shall not be required to be audible unless they convey information that can be used in the transaction being conducted.
3. Where speech synthesis cannot be supported, dynamic alphabetic output shall not be required to be audible.
Advisory 707.5 Speech Output. If an ATM provides additional functions such as dispensing coupons, selling theater tickets, or providing copies of monthly statements, all such functions must be available to customers using speech output. To avoid confusion at the ATM, the method of initiating the speech mode should be easily discoverable and should not require specialized training.
For example, if a telephone handset is provided, lifting the handset can initiate the speech mode.
707.5.1 User Control. Speech shall be capable of being repeated or interrupted. Volume control shall be provided for the speech function.
EXCEPTION: Speech output for any single function shall be permitted to be automatically interrupted when a transaction is selected.
707.5.2 Receipts. Where receipts are provided, speech output devices shall provide audible balance inquiry information, error messages, and all other information on the printed receipt necessary to complete or verify the transaction.
EXCEPTION:
1. Machine location, date and time of transaction, customer account number, and machine identifier shall not be required to be audible.
2. Information on printed receipts that are duplicate information available on-screen shall not be required to be presented in a form of audible receipt.
3. Printed copies of bank statements and checks shall not be required to be audible.
707.6 Input. Input devices shall comply with 707.6.
707.6.1 Input Controls. At least one tactilely discernible input control shall be provided for each function. Where provided, key surfaces not on active areas of display screens, shall be raised above surrounding surfaces. Where membrane keys are the only method of input, each shall be tactilely discernable from surrounding surfaces and adjacent keys.
707.6.2 Numeric Keys. Numeric keys shall be arranged in a 12-key ascending or descending telephone keypad layout. The number five key shall be tactilely distinct from the other keys.
Advisory 707.6.2 Numeric Keys. Telephone keypads and computer keyboards differ in one significant feature, ascending versus descending numerical order. Both types of keypads are acceptable, provided the computer-style keypad is organized similarly to the number pad located at the right on most computer keyboards, and does not resemble the line of numbers located above the computer keys.
1 2 3
4 5 6
7 8 9
* 0 #
(a) 12-key ascending Figure 707.6.2
Numeric Key Layout
7 8 9
4 5 6
1 2 3
* 0 #
(b) 12-key descending
707.6.3 Function Keys. Function keys shall comply with 707.6.3.
707.6.3.1 Contrast. Function keys shall contrast visually from background surfaces. Characters and symbols on key surfaces shall contrast visually from key surfaces. Visual contrast shall be either light-on-dark or dark-on-light.
EXCEPTION: Tactile symbols required by 707.6.3.2 shall not be required to comply with 707.6.3.1.
707.6.3.2 Tactile Symbols. Function key surfaces shall have tactile symbols as follows: Enter or Proceed key: raised circle; Clear or Correct key: raised left arrow; Cancel key: raised letter ex; Add Value key: raised plus sign; Decrease Value key: raised minus sign.
707.7 Display Screen. The display screen shall comply with 707.7.
EXCEPTION: Drive-up only automatic teller machines and fare machines shall not be required to comply with 707.7.1.
707.7.1 Visibility. The display screen shall be visible from a point located 40 inches (1015 mm) above the center of the clear floor space in front of the machine.
707.7.2 Characters. Characters displayed on the screen shall be in a sans serif font. Characters shall be 3/16 inch (4.8 mm) high minimum based on the uppercase letter "I". Characters shall contrast with their background with either light characters on a dark background or dark characters on a light background.
707.8 Braille Instructions. Braille instructions for initiating the speech mode shall be provided.
Braille shall comply with 703.3.
CHAPTER 9: BUILT-IN ELEMENTS
902 Dining Surfaces and Work Surfaces
902.1 General. dining surfaces and work surfaces shall comply with 902.2 and 902.3.
EXCEPTION: Dining surfaces and work surfaces for children's use shall be permitted to comply with 902.4.
Advisory 902.1 General. Dining surfaces include, but are not limited to, bars, tables, lunch counters, and booths. Example of work surfaces, including writing surfaces, study carrels, student laboratory stations, baby changing and other tables or fixtures for personal grooming, coupon counters, and where covered by the ABA scoping provisions, employee work stations.
902.2 Clear Floor or Ground Space. A clear floor space complying with 305 positioned for a forward approach shall be provided. Knee and toe clearance complying with 306 shall be provided.
902.3 Height. The tops of dining surfaces and work surfaces shall be 28 inches (710 mm) minimum and 34 inches (865 mm) maximum above the finish floor or ground.
902.4 Dining Surfaces and Work Surfaces for Children's Use. Accessible dining surfaces and work surfaces for children's use shall comply with 902.4.
EXCEPTION: Dining surfaces and work surfaces that are used primarily by children 5 years and younger shall not be required to comply with 902.4 where a clear floor or ground space complying with 305 positioned for a parallel approach is provided.
902.4.1 Clear Floor or Ground Space. A clear floor space complying with 305 positioned for forward approach shall be provided. Knee and toe clearance complying with 306 shall be provided, except that knee clearance 24 inches (610 mm) minimum above the finish floor or ground shall be permitted.
902.4.2 Height. The tops of tables and counters shall be 26 inches (660 mm) minimum and 30 inches (760
mm) maximum above the finish floor or ground.
903 Benches
903.1 General. Benches shall comply with 903.
903.2 Clear Floor or Ground Space. Clear floor or ground space complying with 305 shall be provided and shall be positioned at the end of the bench seat and parallel to the short axis of the bench.
903.3 Size. Benches shall have seats that are 42 inches (1065 mm) long minimum and 20 inches (510 mm) deep minimum and 24 inches (610 mm) deep maximum.
903.4 Back Support. The bench shall provide for back support or shall be affixed to a wall. Back support shall be 42 inches (1065 mm) long minimum and shall extend from a point 2 inches (51 mm) maximum above the seat surface to a point 18 inches (455 mm) minimum above the seat surface. Back support shall be 2 1/2 inches (64 mm) maximum from the rear edge of the seat measured horizontally.
Advisory 903.4 Back Support. To assist in transferring to a bench, consider providing grab bars on a wall adjacent to bench, but not on the bench seat. If provided, grab bars cannot obstruct transfer to the bench.
2" M
AX 18
" M
AX
2 1/2" MAX
(a) (b)
Figure 903.4 Bench Back Support
903.5 Height. The top of the bench seat surface shall be 17 inches (430 mm) minimum and 19 inches (485
mm) maximum above the finish floor or ground.
903.6 Structural Strength. Allowable stresses shall not be exceeded for materials used when a vertical or horizontal force of 250 pounds (1112 N) is applied at any point on the seat, fastener, mounting device, or supporting structure.
903.7 Wet Locations. Where installed in wet locations, the surface of the seat shall be slip resistant and shall not accumulate water.
904 Check-Out Aisles and Sales and Service Counters
904.1 General. Check-out aisles and sales and service counters shall comply with the applicable requirements of 904.
904.2 Approach. All portions of counters required to comply with 904 shall be located adjacent to a walking surface complying with 403.
Advisory 904.2 Approach. If cash register is provided at the sales or service counter, locate the accessible counter close to the cash register so that a person using a wheelchair is visible to sales or service personnel and to minimize the reach for a person with a disability.
904.3 Check-Out Aisles. Check-out aisles shall comply with 904.3.
904.3.1 Aisle. Aisles shall comply with 403.
904.3.2 Counter. The counter surface height shall be 38 inches (965 mm) maximum above the finish floor or ground. The top of the counter edge protection shall be 2 inches (51 mm) maximum above the top of the counter surface on the aisle side of the check-out counter.
2" M
AX
" M
AX
Figure 904.3.2 Check-Out Aisle Counters
904.3.3 Check Writing Surfaces. Where provided, check writing surfaces shall comply with 902.3.
904.4 Sales and Service Counters. Sales counters and service counters shall comply with 904.4.1 or
904.4.2. The accessible portion of the counter top shall extend the same depth as the sales or service counter top.
EXCEPTION: In alteration, when the provision of a counter complying with 904.4 would result in a reduction of the number of existing counters at work stations or a reduction of the number of existing mail boxes, counter shall be permitted to have a portion which is 24 inches (610 mm) long minimum complying with 904.4.1 provided that the required clear floor or ground space is centered on the accessible length of the counter.
plan counter
24" MIN
Figure 904.4 (Exception) Alteration of Sales and Service Counters
904.4.1 Parallel Approach. A portion of the counter surface that is 36 inches (915 mm) long minimum and 36 inches (915 mm) high maximum above the finish floor shall be provided. A clear floor or ground space complying with 305 shall be positioned for a parallel approach adjacent to the 36 inch (915 mm) minimum length of counter.
EXCEPTION: Where the provided counter surface is less than 36 inches (915 mm) long, the entire counter surface shall be 36 inches (915 mm) high maximum above finish floor.
904.4.2 Forward Approach. A portion of the counter surface that is 30 inches (760 mm) long minimum and 36 inches (915 mm) high maximum shall be provided. Knee and toe space complying with 306 shall be provided under the counter. A clear floor or ground space complying with 305 shall be positioned for a forward approach to the counter.
904.5 Food Service Lines. Counters in food service lines shall comply with 904.5.
904.5.1 Self-Service Shelves and Dispensing Devices. Self-service shelves and dispensing devices for tableware, dishware, condiments, food and beverages shall comply with 308.
904.5.2 Tray Slides. The tops of tray slides shall be 28 inches (710 mm) minimum and 34 inches (865 mm) maximum above the finish floor or ground.
904.6 Security Glazing. Where counters or teller windows have security glazing to separate personnel from the public, a method to facilitate voice communication shall be provided. Telephone handset devices, if provided, shall comply with 704.3.
Advisory 904.6 Security Glazing. Assistive listening devices complying with 706 can facilitate voice communications at counters or teller windows where there is security glazing which promotes distortion in audible information. Where assistive listening devices are installed. place signs complying with 703.7.2.4 to identify those facilities which are so equipped. Other voice communications methods include, but are not limited to, grilles, slats, talk-through baffles, intercoms, or telephone handset devices.
C O W A R T
S T R E E T
C H A T T A N O O G A
T N
W W W A R T E C H P R O
JOB NO. D'WN CK'D
ISSUE DATES
INITIAL ISSUE
#21-041 ER/LC KA
PA
R
TI
A
L U
PG
R
A D
E B
U
IL
D
IN
G O
N E
LA
FA
YE
TT
E M
ED
IC
A L
O
FF
IC
E
PA
R
K
ST
AT
E
H
IG
H W
AY
L
AF
AY
ET
TE
G
EO
R G
IA
T1.4
ADA COMPLIANCE
STANDARDS
02/11/22
18" MIN
" M
IN
" M
IN
12" MIN
" M
IN
36" MIN
" M
IN
42" MIN 54
" M
IN
" M
IN
22" MIN
" M
IN
22" MIN
" M
IN
24" MIN
" M
IN
24" MIN
24" MIN 42
" M
IN
24" MIN 48
" M
IN
(a) front approach, pull side
(b) front approach, push side
(c) front approach, push side, door provided with both closer and latch
(d) hinge approach, pull side
(e) hinge approach, pull side
(f) hinge approach, push side
(g) hinge approach, push side, door provided with both closer and latch
(h) latch approach, pull side
(i) latch approach, pull side, door provided with closer
(j) latch approach, push side
(k) latch approach, push side, door provided with closer
Figure 404.2.4.1 Maneuvering Clearances at Manual Swinging Doors and Gates
(c) push side, door provided with both closer and latch
Figure 404.2.4.3 Maneuvering Clearances at Recessed Doors and Gates
Type of Use Minimum Maneuvering Clearance
Approach Direction Door or Gate Side Perpendicular to Doorway
Parallel to Doorway (Beyond latch side unless noted) From front Pull 60 inches 18 inches
From front Push 48 inches 0 inches¹
From hinge side Pull 36 inches
From hinge side Pull 54 inches 42 inches
Fom hinge side Push 42 inches² 22 inches³
From latch side Pull 48 inches⁴ 24 inches
Push 42 inches⁴From latch side
60 inches
24 inches
1. Add 12 inches if closer and latch are provided.
2. Add 6 inches if closer and latch are provided.
3. Beyond hinge side.
4. Add 6 inches if closer is provided.
404.2.4 Maneuvering Clearances. Minimum maneuvering clearances at doors and gates shall comply with 404.2.4. Maneuvering clearances shall extend the full width of the doorway and the required latch side or hinge side clearance.
EXCEPTION: Entry doors to hospitals patient rooms shall not be required to provide the clearance beyond the latch side of the door.
404.2.4.1 Swinging Doors and Gates. swinging doors and gates shall have maneuvering clearance complying with Table 404.2.4.1.
404.2.4.3 Recessed Doors and Gates. Maneuvering clearances for forward approach shall be provided when any obstruction within 18 inches (455 mm) of the latch side of a doorway projects more than 8 inches (205 mm) beyond the face of the door, measured perpendicular to the face of the door or gate.
Advisory 404.2.4.3 Recessed Doors and Gates. A door can be recessed due to wall thickness or because of the placement of casework and other fixed elements adjacent to the doorway. This provision must be applied wherever doors are recessed.
Adjoining surface maximum slope
Curb ramp slope
Figure 406.2 Counter Slope of Surfaces Adjacent to Curb Ramps
Flared sides 1:10 max slope slope slope
Figure 406.3 Sides of Curb Ramps
" M
IN At least as wide as curb ramp
(a) flare ramps raised curb landscape area
" M
IN At least as wide as curb ramp
(b) ramps without flares with landscape and curb
Figure 406.4 Landings at the Top of Curb Ramps
406 Curb Ramps
406.1 General. Curb ramps on accessible routes shall comply with 406, 405.2 through 405.5, and 405.10.
406.2 Counter Slope. Counter slopes of adjoining gutters and road surfaces immediately adjacent to the curb ramp shall not be steeper than 1:20. The adjacent surfaces at transitions at curb ramps to walks, gutters, and streets shall be at the same level.
406.3 Sides of Curb Ramps. Where provided, curb ramp flares shall not be steeper than 1:10.
406.4 Landings. Landings shall be provided at the tops of curb ramps. The landing clear length shall be 36 inches (915 mm) minimum. The landing clear width shall be at least as wide as the curb ramp, excluding flared sides, leading to the landing.
406.5 Location. Curb ramps and the flared sides of curb ramps shall be located so that they do not project into vehicular traffic lanes, parking spaces, or parking access aisles.
Curb ramps at…
This is the start of the file's text. The full file is on GovTribe.
File details come from the government source that posted it. Updated .