20220214_LAFAYETTE HVAC_ CDs.pdf
PDF 2 MB Posted
- Attached to
- CHI memorial renovations
- Solicitation number
- PE-66717-NONST-2025-000000007
- Issued by
- Wilcox County, Georgia
About this file
This document appears to be a set of technical specifications and drawings for a partial HVAC upgrade of a medical office building located in Lafayette, Georgia. The project is being managed by the project architect, Jeffrey L. Rayburn, and is being constructed by the general contractor, ARTEC Mechanical.
The key details of the project include the removal of existing gas furnaces, condensing units, and associated ductwork, and the installation of new horizontal gas furnaces, condensing units, and associated ductwork and controls. An energy recovery ventilator (ERV) will also be installed in the attic to precondition outside air supplied to the new gas furnaces. The project includes new exhaust ductwork, rooftop exhaust fans, and a new kitchen range hood with associated ductwork. The project is scheduled to be completed by February 11, 2022.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| E1_2.pdf | ||
| E1_3.pdf | ||
| LaFayette Projects RFQ (RLR Edit).docx | DOCX document | |
| ARCHITECTURAL.pdf | ||
| One Medical Office Park _ Partial Upgrade Bui.pdf | ||
| E1_1.pdf | ||
| E2_1.pdf | ||
| E2_0.pdf | ||
| 20220214_LAFAYETTE PLBG_CDs.pdf | ||
| bee well clinic (RLR edit).docx | DOCX document |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
C O
W
AR
T
ST
R
EE
T
C
H
AT
TA
N
O O
G A, T N
W W
W .A
R
TE
C H
.P R
O37
3.
5.
JOB NO. D'WN CK'D
ISSUE DATES
INITIAL ISSUE
Wd-30 KDY JLR
PA
R
TI
A
L U
PG
R
A D
E B
U
IL
D
IN
G O
N E
LA
FA
YE
TT
E M
ED
IC
A L
O
FF
IC
E
PA
R
K
ST
A
TE
H
IG
H W
A Y
LA
FA
YE
TT
E G
EO
R
G
IA
02/11/22
N
J E
F
FREY L . RAYBU
R N
02/11/22
A/C AIR CONDITIONING
ACU AIR CONDITIONING UNIT
ADA AMERICANS WITH DISABILITIES ACT
AF AIRFOIL
AFF ABOVE FINISHED FLOOR
AHU AIR HANDLING UNIT
ARCH ARCHITECTURAL
BFF BELOW FINISHED FLOOW
BLDG BUILDING
BTU BRITISH THERMAL UNTIS
BTH BRITISH THERMAL UNITS PER HOUR
CD CONDENSATE DRAIN
CO CLEANOUTS
CONT'D CONTINUED
CW DOMESTIC COLD WATER
DN DOWN
DWG DRAWING
ECO EXTERIOR CLEANOUT
ELEC ELECTRIC, ELECTRICAL
EFF EFFICIENCY
ELEV ELEVATION
ESP EXTERNAL STATIC PRESSURE
°F DEGREES FAHRENHEIT
FD FLOOR DRAIN
FDC FIRE DEPARTMENT CONNECTION
FLA FULL LOAD AMPS
FOB FLAT ON BOTTOM
FOT FLAT ON TOP
FT FOOT, FEET
FS FLOOR SINK
G GAS
GAL GALLON, GALLONS
GI GREASE INTERCEPTOR
GM GAS METER
GPM GALLONS PER MINUTE
GW GREASE WASTE
HB HOSE BIB
HP HORSEPOWER
HW DOMESTIC HOT WATER
HWR DOMESTIC HOT WATER RECIRC.
HZ HERTZ (CYCLES PER SECOND)
IN INCH, INCHES
IN WG INCHES OF WATER GAUGE
INV INVERT ELEVATION
KW KILOWATTS
LAV LAVATORY
LBS POUNDS
LRA LOAD RATED AMPS
LWT LEAVING WATER TEMPERATURE
MAX MAXIMUM
MBH THOUSAND BRITISH THERMAL UNITS PER HOUR
MCA MINIMUM CIRCUIT AMPACITY
MIN MINIMUM
MS MOP SINK
OED OPEN ENDED DUCT
OSD OPEN SITE DRAIN
PD PRESSURE DROP
PH PHASE
PROP PROPELLER
PRV PRESSURE REDUCING VALVE
PSI POUNDS PER SQUARE IN
RD ROOF DRAIN
RH RELATIVE HUMIDITY
RL RAIN LEADER
RLA RATED LOAD AMPS
RPM REVOLUTIONS PER MINUTE
SAN SANITARY
SH SHOWER
SK SINK
SL SOUND LINING
SP STATIC PRESSURE
SQ.FT, SF SQUARE FOOT, FEET
SS SANITARY SEWER
TEMP TEMPERATURE
TP TRAP PRIMER
TUB BATHTUB
TYP TYPICAL
UR URINAL
V VENT
VAV VARIABLE AIR VOLUME
VD VOLUME DAMPER
VFD VARIABLE FREQUENCY DRIVE
VSD VARIABLE SPEED DRIVE
VTR VENT THROUGH ROOF
W/ WITH
WC WATER CLOSET
WG WATER GAUGE
WH WATER HEATER
WHA WATER HAMMER ARRESTOR
WMS WIRE MESH SCREEN
WYE STRAINER WITH DRAIN VALVE AND CAP
MANUAL AIR VENT
PRESSURE/TEMPERATURE TEST PORT
THERMOMETER
WATER PRESSURE GAUGE WITH COCK
PUMP
CONCENTRIC PIPE REDUCER/INCREASER
UNION
FLOW SWITCH
FLOW METER
TEMPERATURE SENSOR
FM
T
P PRESSURE SENSOR
PIPE CONTINUATION
FS
BACKFLOW PREVENTER
WATERTIGHT SLEEVE
FREEZE PROOF HOSE BIBB WITH SOV INLINE
ABBREVIATIONS
DUCTWORK
SYMBOL
PIPING SYSTEMS LEGEND
DESCRIPTION
THERMOSTAT / TEMPERATURE SENSOR
DUCT SMOKE DETECTOR
SUPPLY AIR FLOW DIRECTION
DUCT CONTINUATION
SUPPLY DIFFUSER BLANK OFF
M0.1 MECHANICAL COVER SHEET
M1.1 MECHANICAL HVAC DEMOLITION PLAN
M2.1 MECHANICAL HVAC NEW WORK PLAN
M2.2 MECHANICAL ATTIC HVAC NEW WORK PLAN
M2.3 MECHANICAL PIPING NEW WORK PLAN
M3.1 MECHANICAL SCHEDULES & SPECIFICATIONS
M3.2 MECHANICAL SPECIFICATIONS
M4.1 MECHANICAL DETAILS
M4.2 MECHANICAL DETAILS
INTAKE / EXHAUST / RETURN AIR FLOW DIRECTION
VALVES
GENERAL SYMBOLS
SHUT-OFF VALVE
COMBINATION BALANCING AND SHUT-OFF VALVE
BALL VALVE
BUTTERFLY VALVE
CHECK VALVE
PRESSURE REDUCING VALVE
GAS COCK
TWO-WAY CONTROL VALVE (ELECTRIC)
THREE-WAY CONTROL VALVE (ELECTRIC)
DRAWING LIST
M101
B
M101
C
PLAN IDENTIFIER
TITLE
SCALE
SECTION IDENTIFIER
DIRECTION OF VIEW
SHEET WHERE SECTION IS DRAWN
DETAIL IDENTIFIER
SHEET WHERE PLAN IS DRAWN
PLAN / DETAIL TITLE
SECTION INDICATION
DETAIL INDICATION
DIFFUSER TAG
SYMBOL DESCRIPTION
KEYED NOTE
POINT OF REMOVAL
POINT OF CONNECTION TO EXISTING
PIPING EQUIPMENT
DESIGN CRITERIA
CODES
1. SHEET METAL AND AIR CONDITIONING CONTRACTORS NATIONAL
ASSOCIATION, INC., (SMACNA):
HVAC DUCT CONSTRUCTION STANDARDS 2005 EDITION
2. INTERNATIONAL CODE COUNCIL (ICC):
INTERNATIONAL BUILDING CODE (IBC) - 2012
INTERNATIONAL MECHANICAL CODE (IMC) - 2012
INTERNATIONAL PLUMBING CODE (IPC) - 2012
INTERNATIONAL ENERGY CONSERVATION CODE (IECC) - 2012
3. NATIONAL FIRE PROTECTION ASSOCIATION (NFPA):
NFPA 90A - AIR CONDITIONING AND VENTILATING SYSTEMS - 2012
NFPA 90B - WARM AIR HEATING AND AIR CONDITIONS SYSTEMS - 2012
5. AMERICAN SOCIETY OF HEATING, REFRIGERATING, AND
AIR-CONDITIONING ENGINEERS (ASHRAE)
ASHRAE 170 - VENTILATION OF HEALTH CARE FACILITIES
GENERAL LINETYPES
DEMOLITION
EXISTING
NEW WORK
X CFM-S
SIZE
DIFFUSER TAG
GRILLE SIZE AND / OR DIFFUSER NECK SIZE
AIRFLOW AND DESIGNATOR
S = SUPPLY
R = RETURN
E = EXHAUST
DESCRIPTIONSYMBOL
DESCRIPTIONSYMBOL
HUMIDISTAT / HUMIDITY SENSORH
T
S
PRESSURE RELIEF VALVE
TWO-WAY CONTROL VALVE (PNEUMATIC)
THREE-WAY CONTROL VALVE (PNEUMATIC)
A. THE CONTRACTOR SHALL COMPLY WITH ALL THE LAWS, ORDINANCES, RULES AND
REGULATIONS OF ALL LOCAL AND STATE GOVERNMENTAL AUTHORITIES, THE RULES OF
THE NATIONAL FIRE PROTECTION ASSOCIATION AS INTERPRETED BY THE ENFORCING
AUTHORITY HAVING JURISDICTION AND OF THE PUBLIC UTILITIES HAVING CONNECTION
WITH ANY OF THE SYSTEMS HEREIN SPECIFIED.
B. THE CONTRACTOR SHALL SECURE AND PAY FOR ALL PERMITS AND INSPECTIONS
REQUIRED BY ANY OF THE FOREGOING AUTHORITIES, AND PAY FOR ALL OTHER COSTS
IN CONNECTION WITH THE WORK. ALL CERTIFICATES SHALL BE IN DUPLICATE AND
SHALL BE DELIVERED TO THE OWNER.
C. THE SITE, LOCATION AND ROUTING OF SYSTEMS INDICATED TO HAVE NEW
CONNECTIONS MADE TO THEM ARE SHOWN AS ACCURATELY AS FIELD CONDITIONS
WOULD PERMIT. CONTRACTOR SHALL VISIT THE SITE AND THOROUGHLY EXAMINE THE
CONTRACT DRAWINGS. ALL EXISTING CONDITIONS SHALL BE EXAMINED AND THEIR
EXACT LOCATIONS VERIFIED. THE CONTRACTOR SHALL REPORT TO THE ENGINEER ANY
CONDITIONS WHICH MIGHT MAKE INSTALLATION OF REQUIRED EQUIPMENT A PROBLEM.
NO CONSIDERATION OR ALLOWANCE WILL BE GRANTED FOR FAILURE TO INVESTIGATE
CONDITIONS OR MISUNDERSTANDINGS OF THE CONTRACTUAL REQUIREMENTS.
D. THE CONTRACTOR SHALL INSTALL AND CONNECT ALL EQUIPMENT AND MATERIALS IN
ACCORDANCE WITH THE BEST ENGINEERING PRACTICE AND, UNLESS OTHERWISE
SHOWN OR SPECIFIED, FOLLOW THE MANUFACTURER'S PRINTED INSTALLATION
REQUIREMENTS AND RECOMMENDATIONS AND FURNISH AND INSTALL ALL REQUIRED
AUXILIARY ITEMS COMPLETE.
E. THE CONTRACTOR SHALL REPAIR ALL WALLS, CEILING, FLOORS, ETC., THAT ARE
REQUIRED TO BE PENETRATED, OR OTHERWISE DISTURBED. THE REPAIRS SHALL BE
WITH MATERIALS AND FINISHES TO MATCH EXISTING. ALL FIRE WALL PENETRATIONS
SHALL BE SEALED WITH SUITABLE MATERIALS TO PRESERVE FIRE WALL INTEGRITY.
CONTRACTOR SHALL NOT CUT ANY STRUCTURAL MEMBER.
F. DRAWINGS SHALL BE CONSIDERED DIAGRAMMATIC. WHILE THE DRAWINGS ARE
GENERALLY TO SCALE AND ARE AS ACCURATE AS THE SCALE WILL PERMIT, ALL
IMPORTANT DIMENSIONS SHALL BE DETERMINED IN THE FIELD.
G. ALL BUILDING SYSTEMS SHALL REMAIN IN SERVICE UNLESS INDICATED OTHERWISE. ALL
OUTAGES OR INTERRUPTIONS SHALL BE KEPT TO MINIMUM DURATION. NOTIFY THE
OWNER 48 HOURS IN ADVANCE OF ANY OUTAGE OR INTERRUPTION.
H. COORDINATE WITH ALL TRADES TO AVOID INTERFERENCE AMONG MECHANICAL,
ELECTRICAL, ARCHITECTURAL AND STRUCTURAL ITEMS. PROVIDE ALL NECESSARY
OFFSETS IN PIPING, DUCTWORK AND FITTINGS ETC., REQUIRED TO PROPERLY INSTALL
THE WORK WITHOUT INTERFERENCES.
I. IF TEMPORARY CONNECTIONS ARE NECESSARY TO ASSURE THIS CONTINUITY OF
SERVICES, THEY SHALL BE FURNISHED BY THE CONTRACTOR WITHOUT ANY ADDITIONAL
CHARGE TO THE OWNER AND SHALL BE REMOVED WHEN NO LONGER NECESSARY.
J. THE CONTRACTOR SHALL SO ARRANGE AND EXECUTE HIS WORK THAT ANY
CONNECTIONS BOTH TEMPORARY OR PERMANENT TO, OR REARRANGEMENT OF,
PRESENT EQUIPMENT, PIPING, ETC., SHALL BE MADE IN SUCH A MANNER AS TO ASSURE
FULL RESUMPTION OF SERVICE AT THE TIME DESIGNATED BY THE OWNER.
K. THE CONTRACTOR SHALL LOCATE ALL EQUIPMENT WHICH MUST BE SERVICED,
OPERATED OR MAINTAINED IN FULL ACCESSIBLE POSITIONS. IF REQUIRED FOR BETTER
ACCESSIBILITY, FURNISH ACCESS DOORS FOR THIS PURPOSE. MINOR DEVIATIONS FROM
DRAWINGS MAY BE MADE TO ALLOW FOR BETTER ACCESSIBILITY, BUT CHANGES OF
MAGNITUDE WHICH INVOLVE EXTRA COSTS SHALL NOT BE MADE WITHOUT APPROVAL.
L. ALL DIMENSIONS FOR EXISTING DUCTWORK SHALL BE VERIFIED IN THE FIELD BY THE
CONTRACTOR PRIOR TO CONSTRUCTION, WHERE NEW WORK CONNECTIONS ARE
INDICATED. NEW DUCT DIMENSIONS SHOWN ARE INSIDE CLEAR DIMENSIONS.
M. OPENINGS REMAINING IN EXISTING PIPING/DUCTWORK AS A RESULT OF DEMOLITION
SHALL BE SEALED WITH AN AIRTIGHT/WATERTIGHT SHEET METAL CAP. WHERE EXISTING
SYSTEMS ARE INSULATED, WORK SHALL INCLUDE REPAIR AND REPLACEMENT OF
INSULATION EITHER DAMAGED OR REMOVED AS A RESULT OF DEMOLITION.
N. WHEN EXISTING SYSTEMS MUST BE INTERRUPTED, PERFORM WORK AS EXPEDITIOUSLY
AS POSSIBLE. CONTRACTOR SHALL NOTIFY THE OWNER 48 HRS IN ADVANCE OF ANY
INTERRUPTION AND SHALL OBTAIN PERMISSION FROM THE OWNER PRIOR TO
INITIATING THE INTERRUPTION.
GENERAL NOTES
A. ALL EXISTING EQUIPMENT AND MATERIALS TO BE REMOVED SHALL BE TAKEN TO
SALVAGE OR AS DIRECTED BY OWNER. ALL ITEMS WHICH ARE NOT TO BE STORED ON
SITE BY OWNER SHALL BE REMOVED FROM THE BUILDING IMMEDIATELY.
B. CONTRACTOR SHALL PATCH OPENINGS CREATED BY DEMOLITION ACTIVITIES WITH NEW
MATERIALS MATCHING ADJACENT SURFACES AND PAINT TO MATCH.
C. CONTRACTOR SHALL NOT CUT ANY STRUCTURAL MEMBER.
D. ALL DIMENSIONS INDICATED ARE BELIEVED TO BE ACCURATE, BUT ARE NOT
GUARANTEED TO BE SO. CONTRACTOR SHALL FIELD VERIFY ALL DIMENSIONS AND
REPORT ANY DISCREPANCIES TO THE PROJECT MANAGER AND ARCHITECT.CONTRACTOR
SHALL COORDINATE REMOVAL AND CLEAN-UP OF ALL DEBRIS CAUSED BY HIS WORK
DURING CONSTRUCTION AND THE STORAGE OF BUILDING MATERIALS. CLEAN ALL AREAS
TO "AS IS" CONDITIONS AT THE END OF EACH WORK DAY.
E. CONTRACTOR SHALL FIELD VERIFY ALL SITE CONDITIONS PRIOR TO SUBMITTING BID.
F. ALL PATCHING OF EXISTING CONSTRUCTION SHALL BE DONE TO MATCH EXISTING
MATERIALS AND FINISHES, UNLESS OTHERWISE NOTED.
G. CONTRACTOR SHALL BE RESPONSIBLE FOR THE COORDINATION OF WORK BY ALL SUB
CONTRACTORS.
H. CONTRACTORS ARE TO CONFINE CONSTRUCTION TRAFFIC AND DEBRIS REMOVAL TO
CONSTRUCTION AREA AS MUCH AS POSSIBLE TO MINIMIZE DUST.
GENERAL DEMOLITION NOTES
RETURN GRILLE; RETURN DUCT IN SECTION
SUPPLY DIFFUSER; SUPPLY DUCT IN SECTION
MANUAL BALANCING/VOLUME DAMPER
NEW DUCTWORK, PIPE OR EQUIPMENT
M
MOTORIZED DAMPER
EXISTING DUCTWORK, PIPE OR EQUIPMENT TO REMAIN
EXISTING DUCTWORK, PIPE OR EQUIPMENT TO BE DEMOLISHED
EXHAUST GRILLE; EXHAUST DUCT IN SECTION
24x12
24x24
24x12
24x12
24x12
24x12
24"
24x12
Ø
Ø
Ø
Ø
Ø
Ø
Ø
SQUARE TO ROUND CONCENTRIC TRANSITION
SQUARE DUCT TAKE OFF, TOP
SQUARE DUCT TAKE OFF, BOTTOM
ROUND DUCT TAKE OFF
ROUND DUCT ELEVATION CHANGE, UP
ROUND DUCT ELEVATION CHANGE, DOWN
ROUND ELBOW 45°, RADIUS
ROUND ELBOW 90°, RADIUS
DUCTWORK DIMENSION LABEL (24" DIAMETER)
SQUARE DUCT TAKE OFF, SIDE
SQUARE DUCT ELEVATION CHANGE, 90° UP
SQUARE DUCT ELEVATION CHANGE, 90° DOWN
SQUARE ELBOW 45°, MITERED
SQUARE ELBOW WITH DOUBLE THICKNESS TURNING VANES
DUCTWORK DIMENSION LABEL (24" WIDTH x 12" HEIGHT)
NEW FLEXIBLE DUCTWORK
SQUARE DUCT ELEVATION CHANGE, 45° RISE
D
R
SQUARE DUCT ELEVATION CHANGE, 45° DROP
Ø
Ø
FIRE DAMPER
BACKDRAFT DAMPER
FIRE SMOKE DAMPER
BDD
FSD
FD
DESCRIPTIONSYMBOL
FLOW DIRECTION
LPS LOW PRESSURE STEAM
LPC LOW PRESSURE CONDENSATE RETURN
CHWS CHILLED WATER SUPPLY
CHWR CHILLED WATER RETURN
CD CONDENSATE DRAIN
PIPE PITCHED IN DIRECTION OF FLOW
SYMBOL DESCRIPTION
PIPE 90° TURN DOWN
PIPE 90° TURN UP
PIPE TRANSITION
NEW PIPE
EXISTING PIPE TO BE DEMOLISHED
EXISTING PIPE TO REMAIN
PIPING WITH INSULATION
HWS HOT WATER SUPPLY
HWR HOT WATER RETURN
FLEXIBLE PIPE CONNECTOR
NOTE: DIFFUSER / GRILLE RUNOUT TO MATCH NECK SIZE.
DUCTWORK WITH EXTERNAL INSULATION
DUCTWORK WITH INTERNAL LINING
SCALE:
DETAIL TITLE
1/8" = 1'-0"
X
M0.1
COVER SHEET
AutoCAD SHX Text I
AutoCAD SHX Text S
AutoCAD SHX Text T
AutoCAD SHX Text E
AutoCAD SHX Text E
AutoCAD SHX Text I
AutoCAD SHX Text
PROFESSIONAL
AutoCAD SHX Text
PROFESSIONAL
AutoCAD SHX Text No. 28023
AutoCAD SHX Text E
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text G
AutoCAD SHX Text I
AutoCAD SHX Text N
AutoCAD SHX Text R
AutoCAD SHX Text G
AutoCAD SHX Text E
AutoCAD SHX Text G
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text A
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text D
AutoCAD SHX Text R
AutoCAD SHX Text O
AutoCAD SHX Text G
GF
(ETR)
GF
(ETR)
CU
(ETR)
UP TO
EF (ETR)
C O
W
AR
T
ST
R
EE
T
C
H
AT
TA
N
O O
G A, T N
W W
W .A
R
TE
C H
.P R
O37
3.
5.
JOB NO. D'WN CK'D
ISSUE DATES
INITIAL ISSUE
Wd-30 KDY JLR
PA
R
TI
A
L U
PG
R
A D
E B
U
IL
D
IN
G O
N E
LA
FA
YE
TT
E M
ED
IC
A L
O
FF
IC
E
PA
R
K
ST
A
TE
H
IG
H W
A Y
LA
FA
YE
TT
E G
EO
R
G
IA
02/11/22
N
J E
F
FREY L . RAYBU
R N
02/11/22
M1.1
HVAC DEMOLITION
PLAN
SCALE:
HVAC DEMOLITION PLAN
3/16" = 1' - 0"
DEMOLITION KEY NOTES:
A. REMOVE EXISTING GAS FURNACE, CONDENSING UNIT, AND
ALL ASSOCIATED REFRIGERANT LINE SETS, DUCTWORK, AIR
TERMINALS AND CONTROLS AS INDICATED. RETURN UNITS OR
DISPOSE OF AS DIRECTED BY OWNER (CHI)
B. REMOVE AIR TERMINALS / RUNOUTS AND BRANCH DUCTWORK
BACK TO POINTS INDICATED.
C. REMOVE EXISTING AIR TERMINAL / RUNOUT AS SHOWN.
EXISTING AIR TERMINAL IS TO BE RELOCATED TO NEW
LOCATION IN NEW RCP PER NEW WORK PLAN. CLEAN AND
PAINT AIR TERMINAL PRIOR TO BEING PUT BACK INTO
SERVICE.
D. EXISTING GAS FURNACE IS TO REMAIN AND BE REUSED.
EXISTING UNIT IS TO BE CLEANED AND SERVICED PRIOR TO
BEING PUT BACK INTO SERVICE.
E. REMOVE EXISTING EXHAUST FAN, DUCTWORK, CONTROLS
AND ELECTRICAL APPURTENANCES ASSOCIATED WITH
EXHAUST FAN SERVING EXISTING RESTROOM.
A
A
A
A
B
B
B
B
A A A
C
C
B
B
B
B
B
D
D
E
AutoCAD SHX Text I
AutoCAD SHX Text S
AutoCAD SHX Text T
AutoCAD SHX Text E
AutoCAD SHX Text E
AutoCAD SHX Text I
AutoCAD SHX Text
PROFESSIONAL
AutoCAD SHX Text
PROFESSIONAL
AutoCAD SHX Text No. 28023
AutoCAD SHX Text E
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text G
AutoCAD SHX Text I
AutoCAD SHX Text N
AutoCAD SHX Text R
AutoCAD SHX Text G
AutoCAD SHX Text E
AutoCAD SHX Text G
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text A
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text D
AutoCAD SHX Text R
AutoCAD SHX Text O
EXAM 3
E7
EXAM 4
E8
LAB
TOILET
E11
PROVIDER
E12
EXAM 5
E13
EXAM 6
E14
STORAGE
E19
OFFICE
E20
EXAM 16
E29
XRAY
BREAK ROOM
34 TOILET
E35
JENNIFER
E36
CARE TEAM
E37
TOILET
E38
OM
ELEC
E42
PROVIDER
EXAM
EXAM
EXAM
BARIATRIC
CLEAN
STAFF TOILET
50 CARE TEAM
52 CHECK IN
TOILET
STORAGE
EXAM
PROVIDER
EXAM
CALL CENTER
SOILED
EXAM
IT
E67
MEDS
CORRIDOR
A6.1
A6.1
WAITING
2 1
A 185-S
A 140-S 2408 A 140-S
A 140-S
A 140-S
A 140-S
A 140-S
A 125-S
A 125-S
A 55-S
A 100-S
A 80-S
A 75-S
A 50-S
A 50-S
A 50-S 1206 A 30-S
A 110-S
A 110-S
A 140-S
"ø
12"ø
14"ø
8"ø 10"ø
8" ø
10"ø 12"ø
"ø
14"ø
8"ø 10"ø
8"ø
8" ø
8"ø
"ø
10"ø
8"ø
8"ø
"ø
14"ø
"ø
"ø
14"ø
"ø (TYP OF 4)
B 125-E
B 150-E
B 85-E
B 125-E
10"ø8"ø
12"ø
B 90-R 2412 B 130-R
(TYP OF 2)
B 130-R
8" ø
8" ø
8" ø
12"ø
8" ø
8" ø
8" ø
B 60-R
B 310-R
B 110-R
B 110-R
(TYP OF 2)
B 110-R
B 110-R
B 40-R
(TYP OF 4)
B 675-R
B 525-R
A 50-S
VD
VD
VD VD
VD
VD VD
VD
VDVDVDVD
VD VD VD VD VD
VD
VD
VD
VD
VDVDVDVD VDVD
VD
VD VD VD VD VD
VD
VDVDVDVD
VD
VD
VD
VD
VD
VD
VDVD
VD VD
GF-1
GF-2
GF-3
GF-4
GF-5
GF
(ETR)
GF
(ETR)
CU
(ETR)
8"ø
EDH-1
12"ø
12"ø
EDH-2
EDH-3
6"ø 6"ø
VD
VD
CAP
CAPX 200-S
X 200-S
X 125-S
A 340-S
B 300-R
B 100-R
8"
10" 1-1/2"
1-1/2"
CU-1
CU-2 CU-3 CU-4 CU-5
TH
TH
TH
TH
T
T
HD-1
UP TO
EF (ETR)
B 500-E 24X24
EF-112X12
C O
W
AR
T
ST
R
EE
T
C
H
AT
TA
N
O O
G A, T N
W W
W .A
R
TE
C H
.P R
O37
3.
5.
JOB NO. D'WN CK'D
ISSUE DATES
INITIAL ISSUE
Wd-30 KDY JLR
PA
R
TI
A
L U
PG
R
A D
E B
U
IL
D
IN
G O
N E
LA
FA
YE
TT
E M
ED
IC
A L
O
FF
IC
E
PA
R
K
ST
A
TE
H
IG
H W
A Y
LA
FA
YE
TT
E G
EO
R
G
IA
02/11/22
N
J E
F
FREY L . RAYBU
R N
02/11/22
M2.1
HVAC NEW WORK
PLAN
SCALE:
HVAC NEW WORK PLAN
3/16" = 1' - 0"
NEW WORK KEY NOTES:
1. LOCATE NEW HORIZONTAL GAS FURNACE IN CEILING PLENUM AS
APPROXIMATELY INDICATED. ADJUST UNIT LOCATION, DUCT ROUTING, AND
SYSTEM CONFIGURATION TO ACCOMMODATE EXISTING CONDITIONS.
FURNACE IS TO BE INSTALLED PER MANUFACTURER'S WRITTEN
INSTRUCTIONS. SUSPEND UNIT FROM STRUCTURE USING VIBRATION
ISOLATORS AND PROVIDE CONDENSATE DRAIN PAN COMPLETE WITH
AUXILIARY LEAK DETECTOR AS NOTED ON THE INSTALLATION DETAIL ON
M4.2. ROUTE LINE SET TO CORRESPONDING CONDENSING UNIT ON GRADE.
PROVIDE ISOLATION VALVES IN LINE SET AT BOTH THE INDOOR AND
OUTDOOR UNITS FOR FUTURE SERVICE.
2. 8" OUTSIDE AIR DUCT (W/ VOLUME DAMPER) DOWN FROM ERV IN ATTIC.
SEE ATTIC HVAC PLAN ON M2.2 FOR DUCTWORK ASSOCIATED WITH ERV.
3. 8" EXHAUST AIR DUCT (W/ VOLUME DAMPER) DOWN FROM ERV IN ATTIC.
SEE ATTIC HVAC PLAN ON M2.2 FOR DUCTWORK ASSOCIATED WITH ERV.
4. 8" OUTSIDE AIR DUCT (W/ VOLUME DAMPER) DOWN FROM ATTIC. SEE ATTIC
HVAC PLAN ON M2.2 FOR CONTINUATION OF DUCTWORK.
5. PROVIDE FURNACE WITH 3" CONCENTRIC VENT KIT. ROUTE VENT PIPING UP
THROUGH ATTIC TO NEW ROOF CONCENTRIC VENT TERMINATION. SEE
DETAIL ON M4.2.
6. RELOCATE EXISTING AIR TERMINAL TO NEW LOCATION SHOWN IN RCP.
RECONNECT TO EXISTING SUPPLY DUCTWORK AS INDICATED.
7. LOCATE NEW CONDENSING UNIT ON NEW 6" HOUSEKEEPING PAD. ROUTE
REFRIGERANT PIPING FROM CONDENSING UNIT TO CORRESPONDING
FURNACE UNIT MINIMIZING PIPING EXPOSED ON EXTERIOR. SEAL ALL
PENETRATIONS TO EXTERIOR WEATHER TIGHT. MAINTAIN MANUFACTURERS
RECOMMENDED CLEARANCES.
8. RELOCATE EXISTING SYSTEM T'STAT TO NEW LOCATION IN X-RAY ROOM.
9. LOCATE RANGE HOOD OVER APPLIANCE AS SHOWN. ROUTE NEW 12" ROUND
DUCTWORK FROM HOOD'S TOP DISCHARGE UP TO ATTIC SPACE. CONNECT
TO MANUFACTURER PROVIDED INLINE EXHAUST FAN. ROUTE 12" DUCTWORK
THROUGH NEW ROOF PENETRATION PER DETAIL ON DETAILS SHEET. HOOD
IS TO BE PROVIDED WITH RANGE ELECTRICAL DISCONNECT.
a. ROUND DUCT RUNOUTS TO INDIVIDUAL DIFFUSERS TO BE SAME SIZE AS
DIFFUSER NECK UNLESS OTHERWISE NOTED.
GENERAL SHEET NOTES:
7 7 7
AutoCAD SHX Text I
AutoCAD SHX Text S
AutoCAD SHX Text T
AutoCAD SHX Text E
AutoCAD SHX Text E
AutoCAD SHX Text I
AutoCAD SHX Text
PROFESSIONAL
AutoCAD SHX Text
PROFESSIONAL
AutoCAD SHX Text No. 28023
AutoCAD SHX Text E
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text G
AutoCAD SHX Text I
AutoCAD SHX Text N
AutoCAD SHX Text R
AutoCAD SHX Text G
AutoCAD SHX Text E
AutoCAD SHX Text G
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text A
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text D
AutoCAD SHX Text R
AutoCAD SHX Text O
EXAM 4
E8
LAB
TOILET
E11
PROVIDER
E12
EXAM 5
E13
EXAM 6
E14
STORAGE
E19
OFFICE
E20
EXAM 16
E29
XRAY
BREAK ROOM
34 TOILET
E35
JENNIFER
E36
CARE TEAM
E37
TOILET
E38
OM
ELEC
E42
PROVIDER
EXAM
EXAM
EXAM
BARIATRIC
CLEAN
STAFF TOILET
50 CARE TEAM
52 CHECK IN
TOILET
STORAGE
EXAM
PROVIDER
EXAM
CALL CENTER
SOILED
EXAM
IT
E67
MEDS
CORRIDOR
A6.1
A6.1
WAITING
2 1
12"ø
"ø
"ø
12"ø
"ø
8" ø
8" ø
8"ø
8" ø
8"ø
8"ø
8"ø
8"ø
8"ø
"ø
8"ø
VD
VD
VD
VD
VD
VD
VD
VD
ERV-1
12X12
C O
W
AR
T
ST
R
EE
T
C
H
AT
TA
N
O O
G A, T N
W W
W .A
R
TE
C H
.P R
O37
3.
5.
JOB NO. D'WN CK'D
ISSUE DATES
INITIAL ISSUE
Wd-30 KDY JLR
PA
R
TI
A
L U
PG
R
A D
E B
U
IL
D
IN
G O
N E
LA
FA
YE
TT
E M
ED
IC
A L
O
FF
IC
E
PA
R
K
ST
A
TE
H
IG
H W
A Y
LA
FA
YE
TT
E G
EO
R
G
IA
02/11/22
N
J E
F
FREY L . RAYBU
R N
02/11/22
M2.2
ATTIC HVAC NEW
WORK PLAN
SCALE:
ATTIC HVAC NEW WORK PLAN
3/16" = 1' - 0"
NEW WORK KEY NOTES:
1. LOCATE NEW ENERGY RECOVERY UNIT (ERV) IN ATTIC AS
APPROXIMATELY INDICATED. SUSPEND UNIT FROM STRUCTURE USING
VIBRATION ISOLATORS. ADJUST UNIT LOCATION, DUCT ROUTING, AND
SYSTEM CONFIGURATION TO ACCOMMODATE EXISTING CONDITIONS.
2. 8" OUTSIDE AIR DUCT (W/ VOLUME DAMPER) DOWN TO FURNACE
RETURN DUCTWORK CONNECTION. SEE HVAC PLAN ON M2.1 FOR
CONTINUATION OF DUCTWORK.
3. 8" EXHAUST AIR DUCT (W/ VOLUME DAMPER) DOWN TO EXHAUST
GRILLE. SEE HVAC PLAN ON M2.1 FOR DUCTWORK ASSOCIATED WITH
ERV.
4. 8" OUTSIDE AIR DUCT (W/ VOLUME DAMPER) DOWN TO FURNACE
RETURN DUCTWORK CONNECTION. SEE HVAC PLAN ON M2.1 FOR
CONTINUATION OF DUCTWORK.
5. NEW 24x12 LOUVER IN EXTERIOR WALL TO DISCHARGE EXHAUST FROM
ERV-1. COORDINATE EXACT LOCATION WITH ARCHITECT. SLEEVE AND
SEAL BUILDING PENETRATION WATER TIGHT. LOUVER IS TO BE EQUAL
TO UNITED ENERTECH MODEL FL-D-4 SIZED TO PROVIDE A FREE AREA
OF 0.71sqft. FOR 485cfm AT A 683fpm FACE VELOCITY. PROVIDE 10FT
OF LINEAR SEPARATION FROM ALL OUTSIDE AIR INTAKES.
6. CONNECT 24X12 OUTSIDE AIR DUCTWORK TO EXISTING ATTIC
SIDEWALL OUTSIDE AIR INTAKE LOUVER AT APPROXIMATE LOCATION
INDICATED.
7. CONNECT 8X8 OUTSIDE AIR DUCTWORK TO EXISTING ATTIC SIDEWALL
OUTSIDE AIR INTAKE LOUVER AT APPROXIMATE LOCATION INDICATED.
8. NEW 12" ROUND DUCTWORK UP FROM HOOD DISCHARGE. CONNECT
TO MANUFACTURER PROVIDED INLINE EXHAUST FAN. ROUTE 12"
DUCTWORK THROUGH NEW ROOF PENETRATION PER DETAIL ON
DETAILS SHEET.
9. 12X12 EXHAUST DUCT UP TO NEW ROOF MOUNTED EXHAUST FAN.
3 3
AutoCAD SHX Text I
AutoCAD SHX Text S
AutoCAD SHX Text T
AutoCAD SHX Text E
AutoCAD SHX Text E
AutoCAD SHX Text I
AutoCAD SHX Text
PROFESSIONAL
AutoCAD SHX Text
PROFESSIONAL
AutoCAD SHX Text No. 28023
AutoCAD SHX Text E
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text G
AutoCAD SHX Text I
AutoCAD SHX Text N
AutoCAD SHX Text R
AutoCAD SHX Text G
AutoCAD SHX Text E
AutoCAD SHX Text G
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text A
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text D
AutoCAD SHX Text R
AutoCAD SHX Text O
EXAM 4
E8
LAB
TOILET
E11
PROVIDER
E12
EXAM 5
E13
EXAM 6
E14
STORAGE
E19
OFFICE
E20
EXAM 16
E29
XRAY
BREAK ROOM
34 TOILET
E35
JENNIFER
E36
CARE TEAM
E37
TOILET
E38
OM
ELEC
E42
PROVIDER
EXAM
EXAM
EXAM
BARIATRIC
CLEAN
STAFF TOILET
50 CARE TEAM
52 CHECK IN
TOILET
STORAGE
EXAM
PROVIDER
EXAM
CALL CENTER
SOILED
EXAM
IT
E67
MEDS
CORRIDOR
A6.1
A6.1
WAITING
2 1
GF-1
GF-2
GF-3
GF-4
GF-5
GF
(ETR)
GF
(ETR)
CU
(ETR)
EDH-1
EDH-2
EDH-3
CO
CO
1-1/2"
1-1/2"
CU-1
CU-2 CU-3 CU-4 CU-5
EF-1
C O
W
AR
T
ST
R
EE
T
C
H
AT
TA
N
O O
G A, T N
W W
W .A
R
TE
C H
.P R
O37
3.
5.
JOB NO. D'WN CK'D
ISSUE DATES
INITIAL ISSUE
Wd-30 KDY JLR
PA
R
TI
A
L U
PG
R
A D
E B
U
IL
D
IN
G O
N E
LA
FA
YE
TT
E M
ED
IC
A L
O
FF
IC
E
PA
R
K
ST
A
TE
H
IG
H W
A Y
LA
FA
YE
TT
E G
EO
R
G
IA
02/11/22
N
J E
F
FREY L . RAYBU
R N
02/11/22
M2.3
HVAC PIPING NEW
WORK PLAN
SCALE:
HVAC PIPING NEW WORK PLAN
3/16" = 1' - 0"
NEW WORK KEY NOTES:
1. ROUTE REFRIGERANT PIPING FROM CONDENSING UNIT TO
CORRESPONDING FURNACE UNIT MINIMIZING PIPING EXPOSED ON
EXTERIOR. SEAL ALL PENETRATIONS TO EXTERIOR WEATHER TIGHT.
2. PROVIDE NEW FULL SIZE CONDENSATE PIPING FROM FURNACE TO NEW
CONDENSATE MAIN PIPING AS INDICATED. PITCH CONDENSATE PIPING
1/8" PER FOOT IN THE DIRECTION OF FLOW.
3. SPILL CONDENSATE TO GRADE TO NEW DRY WELL.
AutoCAD SHX Text I
AutoCAD SHX Text S
AutoCAD SHX Text T
AutoCAD SHX Text E
AutoCAD SHX Text E
AutoCAD SHX Text I
AutoCAD SHX Text
PROFESSIONAL
AutoCAD SHX Text
PROFESSIONAL
AutoCAD SHX Text No. 28023
AutoCAD SHX Text E
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text G
AutoCAD SHX Text I
AutoCAD SHX Text N
AutoCAD SHX Text R
AutoCAD SHX Text G
AutoCAD SHX Text E
AutoCAD SHX Text G
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text A
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text D
AutoCAD SHX Text R
AutoCAD SHX Text O
W
AR
T
ST
R
EE
T
C
H
AT
TA
N
O O
G A, T N
W W
W .A
R
TE
C H
.P R
O37
3.
5.
JOB NO. D'WN CK'D
ISSUE DATES
INITIAL ISSUE
Wd-30 KDY JLR
PA
R
TI
A
L U
PG
R
A D
E B
U
IL
D
IN
G O
N E
LA
FA
YE
TT
E M
ED
IC
A L
O
FF
IC
E
PA
R
K
ST
A
TE
H
IG
H W
A Y
LA
FA
YE
TT
E G
EO
R
G
IA
02/11/22
N
J E
F
FREY L . RAYBU
R N
02/11/22
M3.1
SCHEDULES, SPECS, &
CONTROLS
GAS FURNACE SCHEDULE
MARK TONS AREA SERVED MFGR. & MODEL NO. TOTAL
CFM
O.A
CFM E.S.P MOTOR
HP COIL MODEL NO.
COOLING HEATING FILTERS CONDENSER COMPERSSOR ELECTRICAL
OUTDOOR
UNIT NOTES
E.A.T db
E.A.T wb TH SH INPUT OUTPUT TYPE THK. AREA FAN
HP EER KW STEPS V/HZ/P MCA MOCP
GF-1 1.5 CALL CENTER TRANE 4TXCB003DS3 600 120 0.5 1/3 S9X2B040D3PSB 75 64 16.7 12.5 40 38 MERV 8 1 - - 14.5 - APR 115/60/1 12 20 CU-1 ALL
GF-2 1.5 WEST EXPOSURE TRANE 4TXCB003DS3 600 120 0.5 1/3 S9X2B040D3PSB 75 64 16.7 12.5 40 38 MERV 8 1 - - 14.5 - APR 115/60/1 12 20 CU-2 ALL
GF-3 1.5 CENTRAL AREA TRANE 4TXCB003DS3 600 120 0.5 1/3 S9X2B040D3PSB 75 64 16.7 12.5 40 38 MERV 8 1 - - 14.5 - APR 115/60/1 12 20 CU-3 ALL
GF-4 1.5 EAST EXPOSURE TRANE 4TXCB003DS3 600 120 0.5 1/3 S9X2B040D3PSB 75 64 16.7 12.5 40 38 MERV 8 1 - - 14.5 - APR 115/60/1 12 20 CU-4 ALL
GF-5 2 WAITING ROOM TRANE 4TXCB003DS3 800 125 0.5 1/2 S9V2B060D3PSB 75 63 22.9 18.0 60 58 MERV 8 2 - - 14.75 - APR 115/60/1 18 30 CU-5 ALL
NOTES:
1. PROVIDE UNIT COMPLETE WITH THE FOLLOWING:
a. ELECTRONIC PROGRAMMABLE T'STAT
b. TWO STAGE COMPRESSOR
c. APR VALVE (APR-410-1)
d. TWO STAGE GAS VALVE
e. ECM VARIABLE SPEED FAN
f. DISCONNECT SWITCH
2. PROVIDE ISOLATION BALL VALVES IN ALL REFRIGERANT LINES TO ISOLATE EQUIPMENT FOR SERVICE. VALVES TO BE FULL PORT WITH ACCESS PORT BY MUELLER, STREAMLINE, CYCLEMASTER OR EQUAL
3. FOLLOW MANUFACTURERS GUIDELINES FOR REFRIGERANT LINE SIZING AND INSTALLATION.
AIR DISTRIBUTION SCHEDULE
MARK MANUFACTURER MODEL DESCRIPTION MATERIAL FINISH NOTES
A PRICE SPD SQUARE PLAQUE DIFFUSER STEEL WHITE 1
B PRICE 80 EGGCRATE RETURN / EXHAUST GRILLE STEEL WHITE 1, 2
X EXISTING TO REMAIN 3
NOTES:
1. CONTRACTOR PROVIDE COMPLETE WITH ALL MARGINS AND CLIPS REQUIRED FOR INSTALLATION.
2. PROVIDE WITH PLENUM AND NECESSARY ACCESSORIES TO ALLOW DUCTED CONNECTION AS REQ'D.
3. BALANCE EXISTING DIFFUSERS AND GRILLES TO SPECIFIED AIRFLOWS.
NOTES:
1. PROVIDE ERV COMPLETE WITH THE FOLLOWING OPTIONS:
a. ECM VARIABLE SPEED FANS
b. DISCONNECT SWITCH
c. SPARE FILTER SET
ENERGY RECOVERY VENTILATOR SCHEDULE
MARK MANUFACTURER MODEL NO.
SUPPLY FAN SECTION EXHAUST FAN SECTION SUMMER WINTER FILTRATION ELECTRICAL
NOTESTOTAL
CFM
ESP
(in. wc) HP TOTAL
CFM
ESP
(in. wc) BHP EAT (db / wb)
LAT
(db / wb)
EAT
(db / wb)
LAT
(db / wb) MERV TYPE V/HZ/P MCA MOCP
ERV-1 RENEWAIRE HE1X 485 0.5 1/2 485 0.5 1/2 95.0 / 78.0 19 / 15.3 8 TA 208/60/1 10.8 15 1
CONDENSING UNIT SCHEDULE
MARK MFGR. & MODEL NO.
OUT
DOOR
TEMP.
CONDENSER COMPRESSOR ELECTRICAL INDOOR
UNIT NOTES
AREA FAN HP EER kW STEPS V/HZ/P MCA MOCP
CU-1 TRANE 4TTR3018H1 95 - 1/8 14.5 - APR 208/60/1 GF-1 ALL
CU-2 TRANE 4TTR3018H1 95 - 1/8 14.5 - APR 208/60/1 GF-2 ALL
CU-3 TRANE 4TTR3018H1 95 - 1/8 14.5 - APR 208/60/1 GF-3 ALL
CU-4 TRANE 4TTR3018H1 95 - 1/8 14.5 - APR 208/60/1 GF-4 ALL
CU-5 TRANE 4TTR3024H1 95 - 1/8 14.75 - APR 208/60/1 GF-5 ALL
NOTES:
1. PROVIDE UNIT COMPLETE WITH DISCONNECT SWITCH AND COIL GUARD.
2. PROVIDE ISOLATION BALL VALVES IN ALL REFRIGERANT LINES TO ISOLATE EQUIPMENT FOR SERVICE. VALVES TO BE FULL PORT WITH
ACCESS PORT BY MUELLER, STREAMLINE, CYCLEMASTER OR EQUAL
3. FOLLOW MANUFACTURERS GUIDELINES FOR REFRIGERANT LINE SIZING AND INSTALLATION.
(MINIMUM THICKNESS, NOMINAL)
0.034 INCH (22 GAGE, GALV.)
0.040 INCH (20 GAGE, GALV.)
0.052 INCH (18 GAGE, GALV.)
0.028 INCH (24 GAGE, GALV.)
0.022 INCH (26 GAGE, GALV.)
(MINIMUM THICKNESS, NOMINAL)
0.051 INCH (NO. 16 B&S GAGE)
0.040 INCH (NO. 18 B&S GAGE)
0.032 INCH (NO. 20 B&S GAGE)
0.025 INCH (NO. 22 B&S GAGE)
0.020 INCH (NO. 24 B&S GAGE)
DUCT CONSTRUCTION MINIMUM SHEET METAL THICKNESSES
0.028 INCH (24 GAGE, GALV.)
(MINIMUM THICKNESS, NOMINAL)
0.040 INCH (20 GAGE, GALV.)
0.052 INCH (18 GAGE, GALV.)
0.019 INCH (28 GAGE, GALV.)
0.022 INCH (26 GAGE, GALV.)
0.028 INCH (24 GAGE, GALV.)
0.034 INCH (22 GAGE, GALV.)
0.040 INCH (20 GAGE, GALV.)
0.034 INCH (22 GAGE, GALV.)
(INCHES)
29 THROUGH 36
37 THROUGH 52
13 THROUGH 18
19 THROUGH 28
THROUGH 12
13 THROUGH 30
OVER 84
55 THROUGH 84
31 THROUGH 54
MAXIMUM SIZE
SPIRAL SEAM DUCT
STEEL
(MINIMUM THICKNESS, NOMINAL)
0.028 INCH (24 GAGE, GALV.)
0.034 INCH (22 GAGE, GALV.)
0.040 INCH (20 GAGE, GALV.)
0.052 INCH (18 GAGE, GALV.)
0.022 INCH (26 GAGE, GALV.)
LONGITUDINAL SEAM DUCT
ROUND DUCTS
STEEL
FITTINGS
STEEL
0.022 INCH (26 GAGE, GALV.)
(MINIMUM THICKNESS, NOMINAL)
THROUGH 12
(INCHES)
MAXIMUM SIZE
RECTANGULAR DUCTS
STEEL ALUMINUM
ELECTRIC DUCT HEAT SCHEDULE
MARK MFGR. & MODEL NO. TOTAL
CFM EAT LAT KW STEPS DUCT
SIZE
TEMP
RISE V/HZ/P NOTES
EDH-1 GREENHECK IDHC 600 55 75 4 2 12X12 18 208/60/1 1
EDH-2 GREENHECK IDHC 600 55 75 4 2 12X12 18 208/60/1 1
EDH-3 GREENHECK IDHC 600 55 75 4 2 12X12 18 208/60/1 1
NOTES:
1. DUCT MOUNTED TYPE WITH CONTROLLER AND AIR FLOW SWITCH.
GENERAL:
THE GAS FURNACES SERVING THE RENOVATED AREAS ARE PROVIDED FOR ROOM TEMPERATURE AND HUMIDITY CONTROL. THEY ARE EQUIPPED WITH ECM FANS, 2-STAGE GAS HEATING, 2 STAGE DX COOLING COIL, APR VALVE (FOR DX COIL CAPACITY MODULATION) AND DUCT MOUNTED RE-HEAT COIL (FOR SPACE
TEMPERATURE COIL DURING DEHUMIDIFICATION).
THE UNIT SHALL BE CONTROLLED BY THE FACTORY PROGRAMMABLE THERMOSTAT / HUMIDISTAT BASED ON THE FOLLOWING SEQUENCE OF OPERATION. THE UNIT SHALL OPERATE UNDER IT'S INTERNAL CONTROLS AND THERMOSTAT WILL CONTROL ALL GAS STAGES, COMPRESSOR STAGING, SUPPLY FAN
OPERATION, RE-HEAT COIL, ETC.
THIS SCOPE INCLUDES, BUT IS NOT LIMITED TO, INSTALLING ALL LOW VOLTAGE WIRING AND CONDUIT, AND PROGRAMING THE SYSTEM IN ORDER TO DELIVER A FULLY OPERATIONAL SYSTEM.
START/STOP/SPEED CONTROL:
THE THERMOSTAT WILL START/STOP THE UNIT SUPPLY FAN.
DURING OCCUPIED MODE, THE UNIT'S SUPPLY FAN SHALL RUN CONTINUOUSLY TO PROVIDE CODE
MANDATED VENTILATION REQUIREMENTS.
DURING UNOCCUPIED MODE, THE UNIT'S SUPPLY FAN SHALL RUN BASED UPON A CALL FOR HEATING OR
COOLING.
SPACE TEMPERATURE CONTROL:
THE THERMOSTAT SHALL ENERGIZE / DE-ENERGIZE THE UNIT'S COMPRESSORS (COOLING MODE) OR GAS
VALVE (HEATING) TO MAINTAIN A SPACE SETPOINT OF 74F (ADJ.).
DE-HUMIDIFICATION MODE (GF-2, 3 & 4 ONLY ):
IF THE SPACE RELATIVE HUMIDITY, AS MEASURED BY THE SPACE HUMIDISTAT, RISES ABOVE THE SET POINT OF 60% RH (ADJ.), THE SYSTEM IS TO ENTER DE-HUMIDIFICATION MODE. DURING THIS MODE, THE THERMOSTAT SHALL ENERGIZE THE UNIT'S COMPRESSORS AND THE ELECTRIC RE-HEAT COIL SHALL
REHEAT THE LEAVING AIR TO MAINTAIN THE SPACE TEMPERATURE.
THE UNIT SHALL REMAIN IN DE-HUMIDIFICATION MODE UNTIL THE SPACE HUMIDITY IS BELOW THE
RELATIVE HUMIDITY SETPOINT FOR 10 MINUTES (ADJ.)
GAS FURNACE SEQUENCE OF OPERATIONS
GENERAL:
THE ENERGY RECOVERY UNIT IS PROVIDED TO PRE-CONDITION CODE MANDATED OUTSIDE AIR SUPPLIED TO THE AREA GAS FURNACES. THE ERV IS EQUIPMENT WITH A STATIC PLATE HEAT EXCHANGER AND ECM
FANS.
THIS SCOPE INCLUDES, BUT IS NOT LIMITED TO, INSTALLING ALL LOW VOLTAGE WIRING AND CONDUIT, AND PROGRAMING THE SYSTEM IN ORDER TO DELIVER A FULLY OPERATIONAL SYSTEM.
START/STOP/SPEED CONTROL:
THE ERV FAN ENABLE SINGLE SHALL BE PROVIDED BY 7-DAY PROGRAMMABLE TIME CLOCK.
DURING OCCUPIED MODE, THE UNIT'S SUPPLY AND EXHAUST FANS SHALL RUN CONTINUOUSLY TO PROVIDE
CODE MANDATED VENTILATION REQUIREMENTS.
DURING UNOCCUPIED MODE, THE UNIT'S SUPPLY AND EXHAUST FAN SHALL BE OFF.
ALL UNIT FAN'S ARE ECM AND ARE PROVIDED WITH SPEED CONTROL.
ENERGY RECOVERY UNIT SEQUENCE OF OPERATIONS
EXHAUST FAN
HOOD SCHEDULE
MFGR. & MODEL #MARK
HD-1
OVERALL
SIZE CFM
GREENHECK GRRS-30 30 X 24 500
ESP
ELECTRICAL
VOLTS/ø AMPS
115/1 15
NOTES:
1. HOOD AND ALL APPURTENANCES TO BE FURNISHED & INSTALLED BY THE MECHANICAL
CONTRACTOR
2. PROVIDE COMPLETE WITH THE FOLLOWING OPTIONS:
· RANGE DISCONNECT
· MANUAL PULL STATION
· EXTERNAL EXHAUST FAN
· ROOF CAP
· PORTABLE FIRE EXTINGUISHER
NOTES
ALL
EXHAUST FAN SCHEDULE
ITEM MFGR. MODEL CFM
MOTOR SP
(in. wg) dBA VOLTS/∅ WEIGHT
(LB) NOTES
RPM HP
EF-1 GREENHECK CUE-090-VG 500 1725 1/10 0.5 54 115/1 50 ALL
NOTES:
1. PROVIDE FAN COMPLETE WITH THE FOLLOWING OPTIONS:
· VARI-GREEN EC MOTOR WITH SPEED DIAL
· DISCONNECT SWITCH
· INSULATED ROOF CURB MATCHING SLOPE.
· FAN SHALL RUN CONTINUOUSLY
AutoCAD SHX Text I
AutoCAD SHX Text S
AutoCAD SHX Text T
AutoCAD SHX Text E
AutoCAD SHX Text E
AutoCAD SHX Text I
AutoCAD SHX Text
PROFESSIONAL
AutoCAD SHX Text
PROFESSIONAL
AutoCAD SHX Text No. 28023
AutoCAD SHX Text E
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text G
AutoCAD SHX Text I
AutoCAD SHX Text N
AutoCAD SHX Text R
AutoCAD SHX Text G
AutoCAD SHX Text E
AutoCAD SHX Text G
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text A
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text D
AutoCAD SHX Text R
AutoCAD SHX Text O
W
AR
T
ST
R
EE
T
C
H
AT
TA
N
O O
G A, T N
W W
W .A
R
TE
C H
.P R
O37
3.
5.
JOB NO. D'WN CK'D
ISSUE DATES
INITIAL ISSUE
Wd-30 KDY JLR
PA
R
TI
A
L U
PG
R
A D
E B
U
IL
D
IN
G O
N E
LA
FA
YE
TT
E M
ED
IC
A L
O
FF
IC
E
PA
R
K
ST
A
TE
H
IG
H W
A Y
LA
FA
YE
TT
E G
EO
R
G
IA
02/11/22
N
J E
F
FREY L . RAYBU
R N
02/11/22
M3.1
SCHEDULES, SPECS, &
CONTROLS
GENERAL
1. THE MECHANICAL DRAWINGS ARE DIAGRAMMATIC AND ARE INTENDED TO CONVEY SCOPE AND
GENERAL ARRANGEMENT ONLY. DO NOT SCALE DRAWINGS.
2. THIS CONTRACTOR SHALL FIELD VERIFY ALL DIMENSIONS AND EXISTING CONDITIONS PRIOR
TO PROCEEDING WITH ANY WORK. WHERE DISCREPANCIES OCCUR BETWEEN THESE
DOCUMENTS AND EXISTING CONDITIONS, THE DISCREPANCY SHALL BE REPORTED TO THE
OWNER AND/OR ENGINEER FOR EXPEDITING AND RESOLVE.
3. ALL WORK SHALL CONFORM TO ALL STATE AND LOCAL CODES, RULES AND REGULATIONS AND
ORDINANCES.
4. CONTRACTOR SHALL PROVIDE ALL MATERIALS AND EQUIPMENT AND PROVIDE ALL LABOR
REQUIRED TO INSTALL A COMPLETE AND OPERABLE MECHANICAL SYSTEM AS INDICATED ON
THE DRAWINGS, AS SPECIFIED AND AS REQUIRED BY CODE.
5. CLEAN THE JOB SITE DAILY AND REMOVE FROM THE PREMISES ANY DIRT AND DEBRIS CAUSED
BY THE PERFORMANCE OF THE WORK INCLUDED IN THIS CONTRACT.
6. COORDINATE ALL MECHANICAL WORK WITH OTHER TRADES TO INSURE PROPER CLEARANCE
AND SPATIAL RELATIONSHIP TO OTHER EQUIPMENT.
7. ALL WORK SHALL BE PERFORMED IN A CLEAN AND WORKMANLIKE MANNER. CARE SHALL BE
EXERCISED TO MINIMIZE ANY INCONVENIENCE OR DISTURBANCE TO OTHER AREAS OF THE
BUILDING WHICH ARE TO REMAIN IN OPERATION. ISOLATE WORK AREAS BY MEANS OF
TEMPORARY PARTITIONS AND/OR TARPS TO DEEP DUST AND DIRT WITHIN THE CONSTRUCTION
AREA.
8. ALL ITEMS REMOVED SHALL BECOME PROPERTY OF THE OWNER AND SHALL BE DISPOSED OF AS
PER THE OWNER'S INSTRUCTIONS, UNLESS INDICATED OTHERWISE. ALL ITEMS WHICH ARE
NOT TO BE STORED ON SITE BY OWNERS SHALL BE REMOVED FROM THE BUILDING
IMMEDIATELY.
9. PROVIDE AND INSTALL ACCESS PANELS IN DUCTWORK AND HARD CEILINGS AS REQUIRED TO
SERVICE DAMPERS, VALVES, SMOKE DETECTORS AND OTHER CONCEALED MECHANICAL
EQUIPMENT.
10. LOCATION AND SIZE OF ALL FLOOR, WALL AND ROOF OPENINGS SHALL BE COORDINATED WITH
ALL OTHER TRADES. NO STRUCTURAL ELEMENT SHALL BE CUT OR MODIFIED WITHOUT
WRITTEN APPROVAL FROM THE STRUCTURAL ENGINEER.
11. COORDINATE DIFFUSER, REGISTER AND GRILLE LOCATIONS WITH THE ARCHITECTURAL
REFLECTED CEILING PLAN.
12. ALL EXTERIOR OPENINGS TO BE PROPERLY CAULKED AND SEALED WITH A SEALANT OF HIGH
QUALITY AND LONG LIFE, TO PREVENT INFILTRATION OF OUTSIDE AIR INTO CONDITIONED
SPACE.
MECHANICAL SPECIFICATIONS
EQUIPMENT:
1. INSTALL EQUIPMENT LEVEL AND PLUMB, PARALLEL AND PERPENDICULAR TO OTHER BUILDING
SYSTEMS AND COMPONENTS IN EXPOSED INTERIOR SPACES, UNLESS OTHERWISE INDICATED.
2. ALL EQUIPMENT SHALL BE INSTALLED IN STRICT COMPLIANCE WITH THE MANUFACTURER'S
WRITTEN INSTRUCTIONS. THE CONTRACTOR SHALL PROVIDE ALL HANGERS AND SUPPORTS
REQUIRED FOR A COMPLETE INSTALLATION.
3. COORDINATE ALL EQUIPMENT CONNECTIONS WITH MANUFACTURERS' CERTIFIED DRAWINGS.
COORDINATE AND PROVIDE ALL DUCT AND PIPE TRANSITIONS REQUIRED FOR FINAL
EQUIPMENT CONNECTIONS TO FURNISHED EQUIPMENT. FIELD VERIFY AND COORDINATE ALL
DUCT AND PIPE DIMENSIONS PRIOR TO FABRICATION.
4. INSTALL HVAC EQUIPMENT TO FACILITATE SERVICE, MAINTENANCE, AND REPAIR OR
REPLACEMENT OF COMPONENTS. CONNECT EQUIPMENT FOR EASE OF DISCONNECTING, WITH
MINIMUM INTERFERENCE TO OTHER INSTALLATIONS. EXTEND GREASE FITTINGS TO
ACCESSIBLE LOCATIONS.
5. LOCATE ALL MECHANICAL EQUIPMENT FOR UNOBSTRUCTED AIRFLOW AND ACCESS TO UNIT
ACCESS PANELS, CONTROLS AND VALVES AS REQUIRED BY THE EQUIPMENT MANUFACTURER
AND APPLICABLE CODES.
6. PROVIDE FLEXIBLE CANVAS/NEOPRENE CONNECTIONS BETWEEN ALL DUCTWORK AND AIR
HANDLING EQUIPMENT.
7. INSTALL EQUIPMENT TO ALLOW RIGHT OF WAY FOR PIPING INSTALLED AT REQUIRED SLOPE.
8. CONTRACTOR TO LABEL ALL EQUIPMENT PER THE OWNER'S DIRECTION.
9. DAMAGE AND TOUCHUP: REPAIR MARRED AND DAMAGED FACTORY-PAINTED FINISHES WITH
MATERIALS AND PROCEDURES TO MATCH ORIGINAL FACTORY FINISH.
DUCTWORK
1. INSTALL ALL DUCTWORK BEFORE INSTALLING INDOOR UNITS.
2. DUCT CONSTRUCTION, INCLUDING SHEET METAL THICKNESSES, SEAM AND JOINT
CONSTRUCTION, REINFORCEMENTS, AND HANGERS AND SUPPORTS, SHALL COMPLY WITH
SMACNA'S "HVAC DUCT CONSTRUCTION STANDARDS - METAL AND FLEXIBLE" AND
PERFORMANCE REQUIREMENTS AND DESIGN CRITERIA INDICATED IN "DUCT SCHEDULE"
ARTICLE.
3. STRUCTURAL PERFORMANCE: DUCT HANGERS AND SUPPORTS SHALL WITHSTAND THE EFFECTS
OF GRAVITY LOADS AND STRESSES WITHIN LIMITS AND UNDER CONDITIONS DESCRIBED IN
SMACNA'S "HVAC DUCT CONSTRUCTION STANDARDS - METAL AND FLEXIBLE".
4. AIRSTREAM SURFACES: SURFACES IN CONTACT WITH THE AIRSTREAM SHALL COMPLY WITH
REQUIREMENTS IN ASHRAE 62.1-2004.
5. SEAL DUCTS ACCORDING TO SMACNA'S "HVAC DUCT CONSTRUCTION STANDARDS - METAL AND
FLEXIBLE" BASED ON THE FOLLOWING SEAL CLASSES:
· UNCONDITIONED SPACE, SUPPLY-AIR DUCTS IN PRESSURE CLASSES 2-INCH WG AND
LOWER: SEAL CLASS B.
· UNCONDITIONED SPACE, EXHAUST DUCTS: SEAL CLASS C.
· UNCONDITIONED SPACE, RETURN-AIR DUCTS: SEAL CLASS B.
· CONDITIONED SPACE, SUPPLY-AIR DUCTS IN PRESSURE CLASSES 2-INCH WG AND LOWER:
SEAL CLASS C.
· CONDITIONED SPACE, EXHAUST DUCTS: SEAL CLASS B.
· CONDITIONED SPACE, RETURN-AIR DUCTS: SEAL CLASS C.
4. HVAC UNIT FLEXIBLE DUCT CONNECTIONS SHALL BE A MINIMUM OF 6 INCHES LONG AND BE HELD IN PLACE WITH HEAVY METAL BANDS. SECURELY ATTACHED TO PREVENT ANY LEAKAGE AT
THE CONNECTION POINTS. FLEXIBLE CONNECTIONS SHALL BE FABRICATED FROM APPROVED
FLAME PROOF FABRIC CONFORMING TO NFPA 90A. ASBESTOS CLOTH IS NOT ACCEPTABLE.
5. CONTRACTOR SHALL SPRAY PAINT INSIDE OF DUCT BLACK, BEHIND ALL GRILLES AND
REGISTERS.
6. THE MECHANICAL CONTRACTOR IS RESPONSIBLE FOR RELOCATING ANY SUPPLY DIFFUSER TO
INSURE A MINIMUM 36" CLEARANCE FROM ANY SMOKE DETECTOR AND SPRINKLER HEAD.
7. PROTECT DUCT INTERIORS FROM MOISTURE, CONSTRUCTION DEBRIS AND DUST, AND OTHER
FOREIGN MATERIALS
8. INSTALL ALL DUCTWORK TIGHT TO BOTTOM OF STRUCTURE TO MAXIMIZE HEADROOM
9. WHERE DUCTS PASS THROUGH FIRE-RATED INTERIOR PARTITIONS AND EXTERIOR WALLS,
INSTALL FIRE DAMPERS.
TEST & BALANCE
1. A COMPLETE TEST AND BALANCE OF THE SYSTEM IS TO BE PERFORMED BY A FIRM CERTIFIED
BY EITHER AABC , NEBB OR NBC. THE MECHANICAL CONTRACTOR SHALL BE RESPONSIBLE FOR
THE T&B CONTRACTOR. THE MECHANICAL CONTRACTOR SHALL BE ON SITE DURING TEST AND
BALANCE TO ASSIST IN ANY ISSUES RELATED TO THE SYSTEMS BEING BALANCED. WRITTEN
DOCUMENTATION OF TEST RESULTS IS TO BE SUBMITTED TO ENGINEER BEFORE WORK CAN BE
CONSIDERED COMPLETE.
DUCT INSULATION
1. THE INSTALLATION OF ALL INSULATION SHALL BE PERFORMED BY AN EXPERIENCED CRAFTSMAN
IN A NEAT WORKMANSHIP-LIKE MANNER AND SHALL BE IN ACCORDANCE WITH THE
MANUFACTURER'S WRITTEN PUBLISHED RECOMMENDATIONS FOR SERVICE INTENDED.
2. CONCEALED INDOOR SUPPLY, RETURN, & OUTSIDE AIR DUCTWORK SHALL BE PROVIDED WITH WRAPPED INSULATION ON DUCTWORK. INSULATION SHALL BE 2-1/3" INCH THICK GLASS FIBER FLEXIBLE DUCT INSULATION, 3/4 POUND DENSITY WITH UL APPROVED FOIL SCRIM KRAFT FRJ JACKET. SEAL ALL JOINTS AND SEAMS WITH STAPLES AND 3" WIDE FSK TAPE. ALL INSULATION
ON DUCTS OVER 24" WIDE SHALL BE SECURED WITH ADHESIVE HANGERS AND WASHERS,
TAPED WITH FSK TAPE 18" ON CENTER.
3. ALL DUCTWORK DIMENSIONS SHOWN ON DRAWINGS ARE INSIDE CLEAR DIMENSIONS. SHEET
METAL DIMENSIONS SHALL BE INCREASED TO ACCOMMODATE LINING THICKNESS.
4. MISCELLANEOUS APPURTENANCES TO MEET THE INTENT OF THESE DOCUMENTS.
REFRIGERANT PIPING:
1. DRAWING PLANS, SCHEMATICS, AND DIAGRAMS INDICATE GENERAL LOCATION AND
ARRANGEMENT OF PIPING SYSTEMS; REFRIGERANT PIPING SIZING AND ROUTING SHALL BE
SIZED BE MANUFACTURER. ALL ROUTING AND SIZING SHOWN ON THESE MECHANICAL PLANS
ARE FOR REFERENCE ONLY.
2. INSTALL REFRIGERANT PIPING ACCORDING TO ASHRAE 15.
3. ALL PIPING SHALL BE INSTALLED AS INDICATED ON THE DRAWINGS IN A NEAT
WORKMANSHIP-LIKE MANNER AND BE SUPPORTED AS REQUIRED BY CODES. PIPING SHALL BE
SET UP AND DOWN AND OFFSET AS REQUIRED TO SUIT FIELD CONDITIONS. DIELECTRIC
COUPLINGS SHALL BE USED WHERE DISSIMILAR METALS ARE JOINED.
4. PIPING HANGERS SHALL BE SPACED SO AS TO PREVENT SAG AND PERMIT PROPER DRAINAGE
AND SHALL NOT BE SPACED MORE THAN EIGHT FEET APART UNLESS A GREATER SPACE IS
DEFINITELY INDICATED ON THE DRAWINGS. A HANGER SHALL BE PLACED WITHIN (1) FOOT OF
EACH HORIZONTAL ELBOW.
5. REFRIGERANT PIPING OTHER THAN PRECHARGED TUBING SETS FURNISHED BY AIR
CONDITIONING MANUFACTURER SHALL BE PDM PRE-INSULATED GELCOPPER. PIPING SHALL BE
INSTALLED IN ACCORDANCE WITH ARI STANDARDS. USE EASY-FLO OR SAFETY SILVER BRAZING
ALLOY TO MAKE JOINTS. PROVIDE BALL VALVES IN ALL REFRIGERANT LINES AT EQUIPMENT
CONNECTIONS. SEE SCHEDULES FOR VALVE DETAILS AND MANUFACTURERS.
6. REFRIGERATION LINE EXTERIOR INSULATION SHALL BE COATED WITH ULTRAVIOLET RESISTANT
MATERIAL IN ACCORDANCE WITH THE MANUFACTURER'S RECOMMENDATIONS.
7. INSTALL PIPING IN CONCEALED LOCATIONS UNLESS OTHERWISE INDICATED AND EXCEPT IN
EQUIPMENT ROOMS AND SERVICE AREAS.
8. INSTALL PIPING INDICATED TO BE EXPOSED AND PIPING IN EQUIPMENT ROOMS AND SERVICE AREAS AT RIGHT ANGLES OR PARALLEL TO BUILDING WALLS. DIAGONAL RUNS ARE PROHIBITED
UNLESS SPECIFICALLY INDICATED OTHERWISE.
9. INSTALL PIPING ADJACENT TO MACHINES TO ALLOW SERVICE AND MAINTENANCE.
10. INSTALL PIPING FREE OF SAGS AND BENDS.
11. INSTALL FITTINGS FOR CHANGES IN DIRECTION AND BRANCH CONNECTIONS.
12. SELECT SYSTEM COMPONENTS WITH PRESSURE RATING EQUAL TO OR GREATER THAN SYSTEM
OPERATING PRESSURE.
13. INSTALL PIPING AS SHORT AND DIRECT AS POSSIBLE, WITH A MINIMUM NUMBER OF JOINTS, ELBOWS, AND FITTINGS.
14. ARRANGE PIPING TO ALLOW INSPECTION AND SERVICE OF REFRIGERATION EQUIPMENT.
INSTALL VALVES AND SPECIALTIES IN ACCESSIBLE LOCATIONS TO ALLOW FOR SERVICE AND
INSPECTION. INSTALL ACCESS DOORS OR PANELS AS IF VALVES OR EQUIPMENT REQUIRING
MAINTENANCE IS CONCEALED BEHIND FINISHED SURFACES.
15. WHEN BRAZING OR SOLDERING, REMOVE SOLENOID-VALVE COILS AND SIGHT GLASSES; ALSO
REMOVE VALVE STEMS, SEATS, AND PACKING, AND ACCESSIBLE INTERNAL PARTS OF
REFRIGERANT SPECIALTIES. DO NOT APPLY HEAT NEAR EXPANSION-VALVE BULB.
16. INSTALL PIPING WITH ADEQUATE CLEARANCE BETWEEN PIPE AND ADJACENT WALLS AND
HANGERS OR BETWEEN PIPES FOR INSULATION INSTALLATION.
17. INSTALL SLEEVES FOR PIPING PENETRATIONS OF WALLS, CEILINGS, AND FLOORS.
18. INSTALL SLEEVE SEALS FOR PIPING PENETRATIONS OF CONCRETE WALLS AND SLABS.
CONTROLS
1. ALL CONTROL WIRING SHALL BE ROUTED WITHIN CONDUIT, OR SHALL BE PLENUM RATED. ALL
WIRING SHALL BE SIZED / INSTALLED PER THE NATIONAL ELECTRIC CODE, LATEST EDITION.
2. CONTRACTOR SHALL PROVIDE ALL AIR TEMPERATURE CONTROLS INCLUDING WIRING, TUBING
AND THERMOSTATS (WITH LOCKING COVERS) AND ALL MISCELLANEOUS APPURTENANCES TO
MEET THE INTENT OF THESE DOCUMENTS.
3. COORDINATE ALL T'STAT LOCATIONS WITH THE OWNER / TENANT FOR OCCUPANT CONTROL,
UNLESS OTHERWISE NOTED.
4. UNLESS OTHERWISE SHOWN, LOCATE ALL ROOM SENSORS, THERMOSTATS, AND HUMIDISTATS
4'-6" ABOVE THE FINISHED FLOOR.
DUCT HANGER AND SUPPORT INSTALLATION
1. COMPLY WITH SMACNA'S "HVAC DUCT CONSTRUCTION STANDARDS - METAL AND FLEXIBLE,"
CHAPTER 4, "HANGERS AND SUPPORTS."
2. HANGER SPACING: COMPLY WITH SMACNA'S "HVAC DUCT CONSTRUCTION STANDARDS - METAL AND FLEXIBLE," TABLE 4-1, "RECTANGULAR DUCT HANGERS MINIMUM SIZE," AND TABLE 4-2, "MINIMUM HANGER SIZES FOR ROUND DUCT," FOR MAXIMUM HANGER SPACING; INSTALL
HANGERS AND SUPPORTS WITHIN 24 INCHES OF EACH ELBOW AND WITHIN 48 INCHES OF EACH
BRANCH INTERSECTION.
3. SUPPORT VERTICAL DUCTS WITH STEEL ANGLES OR CHANNEL SECURED TO THE SIDES OF THE
DUCT WITH WELDS, BOLTS, SHEET METAL SCREWS, OR BLIND RIVETS; SUPPORT AT EACH
FLOOR AND AT A MAXIMUM INTERVALS OF 16 FEET.
4. INSTALL UPPER ATTACHMENTS TO STRUCTURES. SELECT AND SIZE UPPER ATTACHMENTS WITH
PULL-OUT, TENSION, AND SHEAR CAPACITIES APPROPRIATE FOR SUPPORTED LOADS AND
BUILDING MATERIALS WHERE USED.
PIPE HANGERS
1. INSTALL THE FOLLOWING PIPE ATTACHMENTS:
· ADJUSTABLE STEEL CLEVIS HANGERS FOR INDIVIDUAL HORIZONTAL PIPING LESS THAN
20 FEET LONG.
· ADJUSTABLE ROLLER HANGERS AND SPRING HANGERS FOR INDIVIDUAL HORIZONTAL
PIPING 20 FEET OR LONGER.
· PIPE ROLLER: MSS SP-58, TYPE 44 FOR MULTIPLE HORIZONTAL PIPING 20 FEET OR
LONGER, SUPPORTED ON A TRAPEZE.
· SPRING HANGERS TO SUPPORT VERTICAL RUNS.
· PROVIDE COPPER-CLAD HANGERS AND SUPPORTS FOR HANGERS AND SUPPORTS IN
DIRECT CONTACT WITH COPPER PIPE.
2. INSTALL HANGERS FOR STEEL PIPING WITH THE FOLLOWING MAXIMUM SPACING AND MINIMUM
ROD SIZES:
§ NPS 3/4: MAXIMUM SPAN, 7 FEET; MINIMUM ROD SIZE, 3/8 INCH.
§ NPS 1: MAXIMUM SPAN, 7 FEET; MINIMUM ROD SIZE, 3/8 INCH.
§ NPS 1-1/4: MAXIMUM SPAN, 8 FEET; MINIMUM ROD SIZE, 3/8 INCH.
§ NPS 1-1/2: MAXIMUM SPAN, 9 FEET; MINIMUM ROD SIZE, 3/8 INCH.
§ NPS 2: MAXIMUM SPAN, 10 FEET; MINIMUM ROD SIZE, 3/8 INCH.
§ NPS 2-1/2: MAXIMUM SPAN, 11 FEET; MINIMUM ROD SIZE, 1/2 INCH.
§ NPS 3: MAXIMUM SPAN, 12 FEET; MINIMUM ROD SIZE, 1/2 INCH.
3. INSTALL HANGERS FOR DRAWN-TEMPER COPPER PIPING WITH THE FOLLOWING MAXIMUM
SPACING AND MINIMUM ROD SIZES:
· NPS 3/4: MAXIMUM SPAN, 5 FEET; MINIMUM ROD SIZE, 1/4 INCH.
· NPS 1: MAXIMUM SPAN, 6 FEET; MINIMUM ROD SIZE, 1/4 INCH.
· NPS 1-1/2: MAXIMUM SPAN, 8 FEET; MINIMUM ROD SIZE, 3/8 INCH.
· NPS 2: MAXIMUM SPAN, 8 FEET; MINIMUM ROD SIZE, 3/8 INCH.
· NPS 2-1/2: MAXIMUM SPAN, 9 FEET; MINIMUM ROD SIZE, 3/8 INCH.
· NPS 3: MAXIMUM SPAN, 10 FEET; MINIMUM ROD SIZE, 3/8 INCH.
AutoCAD SHX Text I
AutoCAD SHX Text S
AutoCAD SHX Text T
AutoCAD SHX Text E
AutoCAD SHX Text E
AutoCAD SHX Text I
AutoCAD SHX Text
PROFESSIONAL
AutoCAD SHX Text
PROFESSIONAL
AutoCAD SHX Text No. 28023
AutoCAD SHX Text E
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text G
AutoCAD SHX Text I
AutoCAD SHX Text N
AutoCAD SHX Text R
AutoCAD SHX Text G
AutoCAD SHX Text E
AutoCAD SHX Text G
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text A
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text D
AutoCAD SHX Text R
AutoCAD SHX Text O
W
AR
T
ST
R
EE
T
C
H
AT
TA
N
O O
G A, T N
W W
W .A
R
TE
C H
.P R
O37
3.
5.
JOB NO. D'WN CK'D
ISSUE DATES
INITIAL ISSUE
Wd-30 KDY JLR
PA
R
TI
A
L U
PG
R
A D
E B
U
IL
D
IN
G O
N E
LA
FA
YE
TT
E M
ED
IC
A L
O
FF
IC
E
PA
R
K
ST
A
TE
H
IG
H W
A Y
LA
FA
YE
TT
E G
EO
R
G
IA
02/11/22
N
J E
F
FREY L . RAYBU
R N
02/11/22
M4.1
DETAILS
NOTES:
1 SPIN IN CONICAL BRANCH TAP FITTING WITH MANUAL VOLUME DAMPER. BRANCH
RUNOUT DUCT SHALL BE THE SAME DIAMETER AS THE AIR TERMINAL INLET.
2 DUCT STRAP HANGER. ATTACH TO STRUCTURE.
3 STRAP HANGER REQUIRED IF BRANCH RUNOUT LENGTH IS GREATER THAN 4 FT.
4 MAXIMUM FLEXIBLE DUCT LENGTH IS 5 FT. FLEXIBLE DUCT SHALL BE THE SAME
DIAMETER AS THE AIR TERMINAL INLET. FLEXIBLE DUCT SHALL BE INSULATED.
STRETCH FLEXIBLE DUCT TO A MINIMUM OF 90% OF ITS FULLY EXTENDED LENGTH.
SEAL CONNECTIONS AIR TIGHT.
5 HARD ELBOW TO AIR TERMINAL CONNECTION.
6 COMPRESSION FITTING AT AIR TERMINAL CONNECTION.
7 PROVIDE ALL CLIPS AND MARGINS REQUIRED FOR A COMPLETE INSTALLATION.
COORDINATE LOCATION AND FINISH WITH OWNER/ARCHITECT.
2 3
SCALE:
TYPICAL SUPPLY AIR TERMINAL CONNECTION
NONE
1 1/2W
ROUND 90° ELBOW
CL
LC
CONSTRUCTION OF 90° ELBOWS
"W"
"W" "W"
"W"
SQUARE 90° ELBOW
"W"
"W""W"
"W"
CL
1 1/2W
SQUARE 45° ELBOW
CONSTRUCTION OF 45° ELBOWS
ROUND 45° ELBOW
TYPICAL RECTANGULAR TRANSITION TYPICAL RECTANGULAR TO ROUND TRANSITION
USE THIS DESIGN
WHERE ROUND 90° ELS
ARE SHOWN ON PLANS
TURN VANES-SEE DETAIL
THIS SHEET
USE THIS DESIGN WHERE
SQUARE 90° ELS ARE SHOWN ON
PLANS OR IF SPACE CONDITIONS
DO NOT PERMIT INSTALLATION
OF ROUND 90° ELLS
USE THIS DESIGN WHERE
ROUND 45° ELBOWS ARE
SHOWN ON PLANS
TURN VANES-SEE DETAIL
THIS SHEET
CL
LC
CL
CL
CL
LC LC
SLOPE NOT TO
EXCEED 1" IN 4" RECTANGULAR DUCT
LC LC
SLOPE NOT TO
EXCEED 1" IN 4"
ROUND DUCT
INSTALLATION NOTES
1. ALL DUCTS SHALL BE CONSTRUCTED AND ERECTED IN A NEAT
AND WORKMANLIKE MANNER.
2. DUCTS SHALL BE CONSTRUCTED OF THE WEIGHTS, GAGES AND
MATERIAL SHOWN IN THE SCHEDULE ON THESE DRAWINGS.
3. THE DIMENSION SHOWN FOR ALL DUCTS SHOWN IN PLAN GIVE
THE WIDTH FIRST AND THEN THE HEIGHT.
4. DUCT RISERS SHOULD BE SUPPORTED BY ANGLES AT EVERY
FLOOR.
5. AIR TURN SHALL BE INSTALLED IN ALL ABRUPT ELBOWS TO
PREVENT TURBULENCE.
6. DUCTS SHALL BE SECURELY ATTACHED TO THE BUILDING
CONSTRUCTION IN AN APPROVED MANNER.
7. DIVERGING TRANSITION PIECES SHALL BE MADE AS GRADUAL
AS POSSIBLE.
8. INSTALL FIRE DAMPERS IN ACCORDANCE WITH UL 555.
9. ACCESS PANELS SHOULD BE PLACED BEFORE AND/OR AFTER
EQUIPMENT INSTALLED IN THE DUCT.
10. DUCT AREA SHOULD NOT BE DECREASED MORE THAN 10
PERCENT WHEN OBSTRUCTIONS CANNOT BE AVOIDED, AND
THEN A STREAMLINED FITTING SHOULD BE USED.
11. FLEXIBLE FABRIC CONNECTIONS (OR EQUAL) SHOULD BE USED
ON BOTH INLETS AND OUTLETS OF ALL FANS AND AIR
HANDLING UNITS.
12. JOINTS AND SEAMS OF SUPPLY DUCTS SHALL BE FASTENED
SECURELY AND MADE AIR TIGHT.
ROUND DUCT
W
W
USE THIS DESIGN WHERE
ROUND 45° ELBOWS ARE
SHOWN ON PLANS
SEAL OPENING AIR TIGHT
LC
LC
RECTANGLE DUCT
SEAL OPENING AIR TIGHT
VOLUME DAMPER W/ END
BEARING & OPERATOR
LC
LC
SCALE:
LOW VELOCITY DUCT LAYOUT DETAILS
NONE
TYPE "A" TYPE "B", "C", "D"
MAX SIDE
MAX SIDE
(8 FT. MAX HANGER SPACING. ALSO
PROVIDE 3 HANGERS AT EACH TAKE-OFF
OR BRANCH.)
(8 FT. MAX HANGER SPACING )
NOTES:
DUCT SCHEDULE
DUCT
DIMENSIONS
(INCHES)
TYPE
HANGER
A A A/B B31 " 42
19 " 30 13 " 18
UP THRU 12
SCALE:
DUCT HANGER DETAILS
NONE
HANGER ROD
TYPE "B" 5/16" DIA.
TYPE "C" 3/8" DIA.
TYPE "D" 1/2" DIA.
1" X 16 GA GALV. IRON
STRAP OR ALUMINUM
SECURE TO STRUCTURE ABOVE AS
RECOMMENDED BY SMACNA
SECURE TO STRUCTURE ABOVE AS
RECOMMENDED BY SMACNA
SHEET METAL SCREW RIVET OR
BOLT TO BOTH SIDES OF DUCT & A
MIN. OF 1" BENEATH DUCT FOR
BOTH STRAPS
NUT & WASHER AT
END OF ROD
FOR BRACING ANGLES
SEE NOTES
1. FOR SEVERAL DUCTS ON ONE HANGER, TYPE "B", "C", OR
"D" MAY BE USED. SIZE OF HANGER WILL BE SELECTED ON
SUM OF DUCT WIDTHS EQUAL TO MAXIMUM WIDTH OF
DUCT SCHEDULE.
2. SCHEDULE FOR ANGLES FOR BRACING: TYPE "B" -1-1/2 X
1-1/2 X 1/8 ANGLE, MAX. SPACING 8'-0" CENTERS; TYPE "C"
- 1-1/2 X 1-1/2 X 3/16 ANGLE, MAX. SPACING 8'-0"
CENTERS; TYPE "D" - 2 X 2 X 1/4 ANGLE, MAX SPACING
4'-0" CENTERS.
EXISTING POURED CONCRETE
OR C.M.U. WALL
PROVIDE REMOVABLE FIBEROUS GLASS INSULATION
AT GAPS AROUND ELASTOMATIC SEAL AND FIXED
PIPE INSULATION. TYP. BOTH SIDES.
2" LONG WATER STOP AND ANCHOR
COLLAR OF EQUAL GAUGE AS SLEEVE
AT WALL CONSTRUCTION
CUT OPENING IN EXISTING MASONRY WALL
LARGER THAN THE SLEEVE AND FORM &
FILL WITH EXPANSIVE TYPE GROUT
PIPE INSULATION
(WHERE REQ'D)
PIPE SLEEVE
LINK-SEAL TYPE WALL
PENETRATION SEAL (3 REQ'D)
SCALE:
PIPE THROUGH CMU WALL DETAIL
NONE
NOTES:
1 SPIN IN CONICAL BRANCH TAP FITTING WITH MANUAL VOLUME DAMPER. BRANCH
RUNOUT DUCT SHALL BE THE SAME DIAMETER AS THE AIR TERMINAL INLET.
2 DUCT STRAP HANGER. ATTACH TO STRUCTURE.
3 STRAP HANGER REQUIRED IF BRANCH RUNOUT LENGTH IS GREATER THAN 4 FT.
4 MAXIMUM FLEXIBLE DUCT LENGTH IS 5 FT. FLEXIBLE DUCT SHALL BE THE SAME
DIAMETER AS THE AIR TERMINAL INLET. FLEXIBLE DUCT SHALL HAVE A MINIMUM
INSULATION VALUE OF R6. STRETCH FLEXIBLE DUCT TO A MINIMUM OF 90% OF ITS
FULLY EXTENDED LENGTH. SEAL CONNECTIONS AIR TIGHT.
5 HARD ELBOW TO AIR TERMINAL CONNECTION.
6 SHEET METAL PLENUM. PLENUM SHALL BE SAME SIZE AS GRILLE CONNECTION.
7 PROVIDE ALL CLIPS AND MARGINS REQUIRED FOR A COMPLETE INSTALLATION.
COORDINATE LOCATION AND FINISH WITH OWNER/ARCHITECT.
2 3
SCALE:
TYPICAL RETURN & EXHAUST AIR TERMINAL CONNECTION
NONE
LC LC
ROOF SYSTEM
AI
R
F
LO
W
12" HIGH, 1" INSULATED PREFABRICATED SLOPED EQUIPMENT
ROOF CURB WITH WOOD NAILER OR APPROVED EQUAL.
MECHANICAL CONTRACTOR TO SIZE CURB AS REQUIRED TO
ACCOMMODATE SCHEDULED EXHAUST FAN.
FURNISH 18 GAGE (.064") ALUMINUM CURB LINER.
PROVIDE LINKAGE ASSEMBLIES INCLUDING
CRANK ARMS, BALL JOINTS AND PUSH RODS AS
REQUIRED FOR PROPER DAMPER OPERATION.
SECURE CURB FLASHING COLLAR, DAMPER
TRAY TO STEEL DECK WITH MINIMUM (4) #10
DECK SCREWS EVENLY SPACED ON EACH SIDE.
PARALLEL LOW LEAK DAMPER. FURNISH DAMPER WITH
EXTRUDED VINYL BLADE SEALS AND "SINGLE" FLANGE
MOUNTING. PROVIDE ACTUATOR MOUNTING BRACKET KIT
AS REQUIRED. PROVIDE LINKAGE ASSEMBLIES INCLUDING
CRANK ARMS, BALL JOINTS AND PUSH RODS AS REQUIRED
FOR PROPER DAMPER OPERATION.
DUCTED EXHAUST: TRANSITION 0'-6" BELOW ROOF
DECK AS REQUIRED. SEE DRAWINGS AND
SPECIFICATIONS FOR EXHAUST DUCT FABRICATION
AND INSULATION REQUIREMENTS.
L4X4X1/4 PENETRATION FRAME BY OTHERS. COORDINATE
INSTALLATION SCHEDULE WITH C.M./G.C.
SIZE PENETRATION TO PROVIDE 1/2" MIN. CLEAR
AROUND PERIMETER OF THRU DUCT. ROOF OPENING
BY OTHERS. COORDINATE PENETRATION SIZE
REQUIREMENTS AND LOCATION WITH G.C.
WATER PROOF SEAL WITH FLASHING BY OTHERS.
COORDINATE INSTALLATION SCHEDULE WITH
C.M./G.C..
FOLD DAMPER TRAY FLANGE FLUSH WITH TRAY.
INSERT EXHAUST DUCT AND DAMPER AS SHOWN.
SECURE TO DAMPER TRAY WITH SELF TAPPING SHEET
METAL SCREWS.
UPBLAST EXHAUST FAN AS SCHEDULED. SECURE TO
EQUIPMENT CURB WITH A #10 X 1 1/2" PAN HEAD
WOOD SCREW AT EACH CORNER OF CURB CAP.
BALANCING CONTRACTOR SHALL PROVIDE SHEAVES,
PULLEYS AND BELTS AS REQUIRED TO ACHIEVE THE
SPECIFIED AIR FLOW (BELT DRIVE).