This specification sheet details a Generac SD600 Industrial Diesel Generator Set, an EPA Certified Stationary Emergency generator with a 600 kW standby power rating and 750 kVA capacity at 60 Hz. The generator is designed for industrial applications, featuring a Perkins 6-cylinder engine with 18.1L displacement, turbocharged and intercooled. The unit offers multiple configuration options including open set, weather protected enclosure, and sound-attenuated enclosures with various run time and fuel capacity combinations ranging from no tank to 2,002 gallons.

The generator set includes comprehensive standard features such as a UL2200 GENprotect™ control system, Power Zone® Pro Sync Controller, and a 7-inch color touch screen display with multi-lingual capabilities. Key specifications include a 24 VDC electrical system, electronic isochronous governor, and a digital voltage regulator. The generator provides multiple protective functions, extensive alarm and warning capabilities, and meets various industry standards including NFPA 110 Level 1 compliance. Weight and dimension variations are provided for different enclosure types, with weights ranging from approximately 1,180 to 13,928 pounds depending on configuration and fuel tank capacity.

View the file

Other files

Show all 11

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

SP

EC

SH

EE

T

Standby Power Rating 600 kW, 750 kVA, 60 Hz

Prime Power Rating 540 kW, 675 kVA, 60 Hz

*EPA Certified Prime ratings are not available in the US or its Territories. Image used for illustration purposes only

Codes and Standards

Not all codes and standards apply to all configura-tions. Contact factory for details.

UL2200, UL6200, UL1236, UL489,

UL142

CSA C22.2, ULC S601

TM

BS5514 and DIN 6271

SAE J1349

NFPA 37, 70, 99, 110

NEC700, 701, 702, 708

NEMA ICS10, MG1, 250, ICS6,

AB1

ANSI C62.41

Powering Ahead

For over 60 years, Generac has provided innovative design and superior manufacturing.

Generac ensures superior quality by designing and manufacturing most of its generator components, including alternators, enclosures and base tanks, control systems and communications software.

Generac gensets utilize a wide variety of options, configurations and arrangements, allowing us to meet the standby power needs of practically every application.

Generac searched globally to ensure the most reliable engines power our generators. We choose only engines that have already been proven in heavy-duty industrial applications under adverse conditions.

Generac is committed to ensuring our customers’ service support continues after their generator purchase.

SD600 | 18.1L | 600 kW

INDUSTRIAL DIESEL GENERATOR SET

EPA Certified Stationary Emergency

SH

EE

T

STANDARD FEATURES

ENGINE SYSTEM

• Oil Drain Extension

• Heavy Duty Air Cleaner

• Level 1 Fan and Belt Guards (Open Set Only)

• Stainless Steel Flexible Exhaust Connection

• Critical Silencer (Enclosed Units Only)

• Factory Filled Oil and Coolant

• Radiator Duct Adapter (Open Set Only)

FUEL SYSTEM

• Primary Fuel Filter

• Secondary Fuel Filter

COOLING SYSTEM

• Closed Coolant Recovery System

• UV/Ozone Resistant Hoses

• Factory-Installed Radiator

• 50/50 Ethylene Glycol Antifreeze

• Radiator Drain Extension

ELECTRICAL SYSTEM

• Battery Charging Alternator

• Battery Cables

• Battery Tray

• Rubber-Booted Engine Electrical Connections

• Solenoid Activated Starter Motor

ALTERNATOR SYSTEM

• UL2200 GENprotect™

• 12 Leads (3-Phase, Non 600V)

• Class H Insulation Material

• Vented Rotor

• 2/3 Pitch

• Skewed Stator

• Auxiliary Voltage Regulator Power Winding

• Amortisseur Winding

• Permanent Magnet Excitation

• Sealed Bearings

• Automated Manufacturing (Winding, Insertion, Lacing and Varnishing)

• Full Load Capacity Alternator

• Protective Thermal Switch

GENERATOR SET

• Internal Genset Vibration Isolation

• Separation of Circuits - High/Low Voltage

• Separation of Circuits - Multiple Breakers

• Wrapped Exhaust Piping (Enclosed Units Only)

• Standard Factory Testing

• 2 Year Limited Warranty (Standby Rated Units)

• 1 Year Limited Warranty (Prime Rated Units)

• Silencer Mounted in the Discharge Hood

(Enclosed Units Only)

ENCLOSURE (If Selected)

• Rust-Proof Fasteners with Nylon Washers to

Protect Finish

• High Performance Sound-Absorbing Material

(Sound Attenuated Enclosures)

• Gasketed Doors

• Upward Facing Discharge Hoods (Radiator and

Exhaust)

• Stainless Steel Lift Off Door Hinges

• Stainless Steel Lockable Handles

• RhinoCoat™ - Textured Polyester Powder Coat

Paint

FUEL TANKS (If Selected)

• UL 142/ULC S601 Tank

• Double Wall

• Vents

• Sloped Top

• Sloped Bottom

• Factory Pressure Tested (2 psi)

• Rupture Basin Alarm

• Fuel Level

• Check Valve in Supply and Return Lines

• RhinoCoat™ - Textured Polyester Powder Coat

Paint

CONTROL SYSTEM

Power Zone® Pro Sync Controller

• NFPA 110 Level 1 Compliant

• Engine Protective Functions

• Alternator Protective Functions

• Digital Engine Governor Control

• Digital Voltage Regulator

• Multiple Programmable Inputs and Outputs

• Remote Display Capability

• Remote Communication via Modbus® RTU, Modbus TCP/IP, and Ethernet 10/100

• Alarm and Event Logging with Real Time

Stamping

• Expandable Analog and Digital Inputs and Outputs

• Remote Wireless Software Update Capable

• BMS and Remote Telemetry

• Built-In Programmable Logic Eliminates the Need for External Controllers Under Most Conditions

• Ethernet Based Communications Between

Generators

• Programmable I/O Channel Properties

• Built-In Diagnostics

• On-Board Manual Storage

• Arc Flash Maintenance Mode (When Properly

Equipped)

Alarms and Warnings

• Low Oil Pressure

• Low Coolant Level

• High/Low Coolant Temperature

• Sensor Failure

• Oil Temperature

• Over/Under Speed

• Over/Under Voltage

• Over/Under Frequency

• Over/Under Current

• Over Load

• High/Low Battery Voltage

• Battery Charger Current

• Phase to Phase and Phase to Neutral Short

Circuits (I2T Algorithm)

7 Inch Color Touch Screen Display

• Resistive Color Touch Screen

• Sunlight Readable (1400 NITS)

• Easily Identifiable Icons

• Multi-Lingual

• On Screen Editable Parameters

• Key Function Monitoring

• Three Phase Voltage, Amperage, kW, kVA, and kVAr

• Selectable Line to Line or Line to Neutral

Measurements

• Frequency

• Engine Speed

• Engine Coolant Temperature

• Engine Oil Pressure

• Engine Oil Temperature

• Battery Voltage

• Hourmeter

• Warning and Alarm Indication

• Diagnostics

• Maintenance Events/Information

SD600 | 18.1L | 600 kW

SH

EE

T

CONFIGURABLE OPTIONS

ENGINE SYSTEM

• Oil Heater

• Critical Grade Silencers (Open Set Only)

• Level 1 Fan and Belt Guards (Enclosed Units Only)

• Radiator Stone Guard (Open Set Only)

FUEL SYSTEM

• NPT Flexible Fuel Line

ELECTRICAL SYSTEM

• 10A UL Listed Battery Charger

• Battery Warmer

ALTERNATOR SYSTEM

• Alternator Upsizing

• Anti-Condensation Heater

CIRCUIT BREAKER OPTIONS

• Main Line Circuit Breaker

• 2nd Main Line Circuit Breaker

• Shunt Trip and Auxiliary Contact

• Electronic Trip Breaker

GENERATOR SET

• 12 Position Load Center

• Extended Factory Testing

ENCLOSURE

• Weather Protected Enclosure

• Level 1 Sound Attenuated

• Level 2 Sound Attenuated

• Level 2 Sound Attenuated with Motorized

Dampers

• Level 3 Sound Attenuated (Steel Only)

• Steel Enclosure

• Aluminum Enclosure

• IBC Seismic Certification

• Up to 200 MPH Wind Load Rating (Contact

Factory for Availability)

• AC/DC Enclosure Lighting Kit

• Enclosure Heaters (with Motorized Dampers Only)

CONTROL SYSTEM

• NFPA 110 Level 1 Compliant 21-Light Remote

Annunciator

• Remote Relay Assembly (8 or 16)

• Ground Fault Annunciator

• 10A Engine Run Relay

• 120V GFCI and 240V Outlets

• Oil Temperature Indication and Alarm

• Remote E-Stop Break Glass-Type, Surface Mount

• Remote E-Stop Red Mushroom-Type, Surface

Mount

• Remote E-Stop Red Mushroom-Type, Flush Mount

• Damper Alarm Contacts (with Motorized Dampers

Only)

• 100 dBA Alarm Horn

WARRANTY (Standby Gensets Only)

• 2 Year Extended Limited Warranty

• 5 Year Limited Warranty

• 5 Year Extended Limited Warranty

• 7 Year Extended Limited Warranty

• 10 Year Extended Limited Warranty

ENGINEERED OPTIONS

ENGINE SYSTEM

• Fluid Containment Pan

• Coolant Heater Ball Valves

CIRCUIT BREAKERS

• 3rd Breaker Systems

CONTROL SYSTEM

• Spare Inputs (x4) / Outputs (x4)

GENERATOR SET

• Special Testing

• Battery Box

ENCLOSURE

• Door Open Alarm Horn

FUEL TANKS

• Overfill Protection Valve

• UL 2085 Tank

• Stainless Steel Tank

• Special Fuel Tanks

• Vent Extensions

• 5 Gallon Spill Containment Box

• Dealer Supplied AHJ Requirements

SD600 | 18.1L | 600 kW

SH

EE

T

APPLICATION AND ENGINEERING DATA

ENGINE SPECIFICATIONS

General

Make Perkins Cylinder # 6 Type In-Line Displacement - in³ (L) 1,106.36 (18.13) Bore - in (mm) 5.71 (145) Stroke - in (mm) 7.20 (183) Compression Ratio 14.5:1 Intake Air Method Turbocharged/Intercooled Cylinder Head Type 4 Valve Piston Type Aluminum Crankshaft Type I-Beam Section

Engine Governing

Governor Electronic Isochronous Frequency Regulation (Steady State) ±0.25%

Lubrication System

Oil Pump Type Gear Driven Oil Filter Type Full Flow Crankcase Capacity - qt (L) 47.55 (45)

Cooling System

Cooling System Type Centrifugal Fan Type Pusher Fan Speed - RPM 1,439 Fan Diameter - in (mm) 38 (965)

Fuel System

Fuel Type Ultra Low Sulfur Diesel #2 Carburetor ASTM Fuel Filtering (Microns) Primary 10 - Secondary 2 Fuel Inject Pump Electronic Injector Type MEUI Engine Type Pre-Combustion Fuel Supply Line - in (mm) 0.5 (12.7) NPT Fuel Return Line - in (mm) 0.5 (12.7) NPT

Engine Electrical System

System Voltage 24 VDC Battery Charger Alternator 70 A Battery Size See Battery Index 0161970SBY Battery Voltage (2) - 12 VDC Ground Polarity Negative

ALTERNATOR SPECIFICATIONS

Standard Model K0600124Y23 Poles 4 Field Type Revolving Insulation Class - Rotor H Insulation Class - Stator H Total Harmonic Distortion <3% Telephone Interference Factor (TIF) <50

Standard Excitation Permanent Magnet Bearings Single Sealed Cartidge Coupling Direct via Flexible Disc Prototype Short Circuit Test Yes Voltage Regulator Type Digital Number of Sensed Phases All Regulation Accuracy (Steady State) ±0.25%

SD600 | 18.1L | 600 kW

SH

EE

T

OPERATING DATA

POWER RATINGS — DIESEL

Standby Three-Phase 120/208 VAC @0.8pf 600 kW Amps: 2,082 Three-Phase 120/240 VAC @0.8pf 600 kW Amps: 1,804 Three-Phase 277/480 VAC @0.8pf 600 kW Amps: 902 Three-Phase 346/600 VAC @0.8pf 600 kW Amps: 722

MOTOR STARTING CAPABILITIES (SKVA)

skVA vs. Voltage Dip

277/480 VAC 30% 208/240 VAC 30%

K0600124Y23 1,560 K0600124Y23 1,120 K0832124Y23 2,800 K0832124Y23 2,090

FUEL CONSUMPTION RATES*

Diesel - gph (Lph) Fuel Pump Lift- ft (m) Percent Load Standby

12 (3.7) 25% 18.4 (69.7) 50% 28.2 (88.7)

Total Fuel Pump Flow (Combustion + Return) - gph (Lph) 75% 35.6 (124.8) 121 (457) 100% 41.4 (156.7)

*Fuel supply installation must accommodate fuel consumption rates at 100% load.

COOLING

Standby Coolant Flow gpm (Lpm) 114.1 (432) Coolant System Capacity gal (L) 15.5 (58.6) Heat Rejection to Coolant BTU/hr (kW) 1,589,760 (466) Air Flow (Fan Air Flow Across Radiator) - Open Set cfm (m³/min) 30,088 (852) Maximum Operating Ambient Temperature °F (°C) 122 (50) Maximum Operating Ambient Temperature (Before Derate) See Bulletin No. 0199280SSD Maximum Additional Radiator Backpressure in H2O (kPa) 0.5 (0.12)

COMBUSTION AIR REQUIREMENTS

Standby Flow at Rated Power cfm — (m³/min) 1,836 (52)

ENGINE

Standby Rated Engine Speed rpm 1,800 Horsepower at Rated kW** hp 909 Piston Speed ft/min (m/min) 2,161 (659) BMEP psi (kPa) 361 (2,489) ** See “Emissions Data Sheet” for maximum bHP for EPA and SCAQMD permitting purposes.

EXHAUST

Standby Exhaust Flow (Rated Output) cfm (m³/min) 5,085 (144) Maximum Allowable Back Pressure (Post Silencer) inHg (kPa) 2.13 (6.9)

Exhaust Temp (Rated Output - Post Turbo) °F (°C) 1,155 (624)

Deration – Operational characteristics consider maximum ambient conditions. Derate factors may apply under atypical site conditions.

Please contact a Generac Power Systems Industrial Dealer for additional details. All performance ratings in accordance with ISO3046, BS5514, ISO8528, and DIN6271 standards.

Standby - See Bulletin 0187500SSB Prime - See Bulletin 0187510SSB

SD600 | 18.1L | 600 kW

SH

EE

T

Generac Power Systems, Inc. | S45 W29290 HWY. 59 | Waukesha, WI 53189 | generac.com ©2024 Generac Power Systems, Inc. All rights reserved. All specifications are subject to change without notice.

Part No. A0001404642 Rev. B 02/12/2024

SD600 | 18.1L | 600 kW

INDUSTRIAL DIESEL GENERATOR SET

EPA Certified Stationary Emergency

DIMENSIONS AND WEIGHTS*

OPEN SET

Run Time Hours**

Usable Capacity Gal

(L) L x W x H - in (mm) Weight - lbs (kg) No Tank — 154.4 (3,923) x 71.0 (1,803) x 67.5 (1,715) 8,520 - 10,778 (3,464 - 4,889)

8 334 (1,264) 158.5 (4,025) x 71.0 (1,803) x 81.5 (2,071) 10,195 - 12,453 (4,224 - 5,649) 24 1,001 (3,789) 158.5 (4,025) x 71.0 (1,803) x 103.5 (2,629) 11,120 - 13,378 (4,643 - 6,068) 24 1,001 (3,789) 228.0 (5,791) x 71.0 (1,803) x 92.5 (2,350) 11,670 - 13,928 (4,893 - 6,318) 48 2,002 (7,578) 290.0 (7,366) x 71.0 (1,803) x 103.5 (2,629) 13,370 - 15,628 (5,664 - 7,089)

WEATHER PROTECTED ENCLOSURE

Run Time Hours**

Usable Capacity Gal

(L) L x W x H - in (mm) Weight - lbs (kg) Enclosure Only

No Tank — 207.4 (5,268) x 71.0 (1,800) x 80.0 (2,032)

Steel: 2,267 (1,129) Aluminum: 1,180 (536)

8 334 (1,264) 207.4 (5,268) x 71.0 (1,800) x 94.0 (2,388) 24 1,001 (3,789) 207.4 (5,268) x 71.0 (1,800) x 116.0 (2,946) 24 1,001 (3,789) 228.0 (5,791) x 71.0 (1,800) x 105.0 (2,667) 48 2,002 (7,578) 290.0 (7,366) x 71.0 (1,800) x 116.0 (2,946)

LEVEL 1 SOUND ATTENUATED ENCLOSURE

Run Time Hours**

Usable Capacity Gal

(L) L x W x H - in (mm) Weight - lbs (kg) Enclosure Only

No Tank — 247.5 (6,285) x 71.0 (1,800) x 80.0 (2,032)

Steel: 3,273 (1,485) Aluminum: 1,613 (732)

8 334 (1,264) 247.5 (6,285) x 71.0 (1,800) x 94.0 (2,388) 24 1,001 (3,789) 247.5 (6,285) x 71.0 (1,800) x 116.0 (2,946) 24 1,001 (3,789) 247.5 (6,285) x 71.0 (1,800) x 105.0 (2,667) 48 2,002 (7,578) 290.0 (7,366) x 71.0 (1,800) x 116.0 (2,946)

LEVEL 2 SOUND ATTENUATED ENCLOSURE

Run Time Hours**

Usable Capacity Gal

(L) L x W x H - in (mm) Weight - lbs (kg) Enclosure Only

No Tank — 207.4 (5,268) x 71.0 (1,800) x 114.1 (2,899)

3,610 (1,638) Aluminum: 1,758 (798)

8 334 (1,264) 207.4 (5,268) x 71.0 (1,803) x 128.1 (3,255) 24 1,001 (3,789) 207.4 (5,268) x 71.0 (1,803) x 150.1 (3,813) 24 1,001 (3,789) 228.0 (5,791) x 71.0 (1,803) x 139.1 (3,534) 48 2,002 (7,578) 290.0 (7,366) x 71.0 (1,803) x 150.1 (3,813)

*All measurements are approximate and for estimation purposes only.

YOUR FACTORY RECOGNIZED GENERAC INDUSTRIAL DEALER

Specification characteristics may change without notice. Dimensions and weights are for preliminary purposes only. Please consult a Generac Power Systems Industrial Dealer for detailed installation drawings.

File details come from the government source that posted it. Updated .