Appendix F1 - Ft Lyon Em Generator Design Drawings 10.11.2024.pdf
PDF 980 KB Posted
- Attached to
- Ft. Lyon Emergency Generator Upgrades
- Solicitation number
- IFB1-NHAA-2025000102
- Issued by
- Larimer County, Lakewood City, Colorado
About this file
The document is a set of electrical design drawings for the Fort Lyon Emergency Generator Replacement project, prepared by McShea Consulting for the Colorado Department of Corrections. The project involves replacing and upgrading emergency generators and electrical systems for Buildings 4, 6, and 8 located at 30999 CO Road 15 in Las Animas, Colorado. The design drawings include detailed electrical plans, one-line diagrams, symbol legends, and general electrical notes, with multiple revisions from June 2024 to October 2024, culminating in a bid set dated 10.11.2024.
The drawings specify technical details for emergency generator replacements, including 750 KVA generators for Buildings 4 and 8, and a 400 KVA generator for Building 6. Each building will receive a new service-rated automatic 3-pole transfer switch, transformer, and electrical system upgrades. The designs incorporate compliance with the 2021 International Energy Conservation Code (IECC) and 2023 National Electric Code (NEC), with specific requirements for electrical systems, lighting controls, receptacle placement, and energy efficiency. The project appears to be a comprehensive electrical infrastructure improvement focusing on emergency power reliability and code compliance for the Fort Lyon campus facilities.
View the file
Other files
Show all 11
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
1. GENERAL: THESE DRAWINGS REMAIN THE SOLE PROPERTY OF MCSHEA CONSULTING AND MAY BE USED ONLY FOR THE PROJECT AS INDICATED BY NAME AND LOCATION. ANY OTHER USE REQUIRES PRIOR, WRITTEN PERMISSION. THE CONTRACTOR WILL PROVIDE ALL MATERIALS, LABOR, EQUIPMENT, TOOLS, TRANSPORTATION, LICENSES, FEES, PERMITS, ETC. TO COMPLETE THE ELECTRICAL WORK DESCRIBED ON THE DRAWINGS. THE CONTRACTOR WILL WARRANT EQUIPMENT, MATERIAL AND WORKMANSHIP FOR A MINIMUM PERIOD OF ONE YEAR FROM THE DATE OF ACCEPTANCE. WARRANTY SHALL INCLUDE REPLACEMENTS OR REPAIRS WITHOUT COST TO THE OWNER DURING THE WARRANTY PERIOD. ELECTRICAL WORK SHALL BE PERFORMED IN ACCORDANCE WITH THE 2018 NATIONAL ELECTRICAL CODE (NEC) AND ALL OTHER APPLICABLE LOCAL CODES AND ORDINANCES. ALL EQUIPMENT SHALL BE
INSTALLED IN ACCORDANCE WITH MANUFACTURERS' RECOMMENDATIONS.
2. USE OF DRAWINGS: DO NOT SCALE FROM THE ELECTRICAL DRAWINGS. FOR EXACT LOCATIONS USE ARCHITECT'S DIMENSIONED DRAWINGS, SHOP DRAWINGS AND FIELD MEASUREMENTS. VERIFY ALL LOCATIONS WITH THE
ARCHITECT PRIOR TO ELECTRICAL ROUGH-IN.
3. WIRING: ALL WIRING FOR LIGHTING AND POWER SYSTEMS WILL BE IN CONDUIT OR CABLE ASSEMBLIES APPROVED BY THE GOVERNING AUTHORITIES. CONDUCTOR SIZES SHOWN ARE BASED ON AMPACITIES FOR COPPER CONDUCTORS, UNLESS OTHERWISE NOTED. WHEN APPROVED BY ENGINEER, FEEDERS MAY BE ALUMINUM CONDUCTORS OF EQUIVALENT AMPACITIES. GROUNDING CONDUCTORS SHALL BE PROVIDED FOR ALL CIRCUITS SHOWN ON THE DRAWINGS. PROVIDE BLOCKING AND OTHER NECESSARY SUPPORTS IN WALLS AND CEILINGS FOR MATERIAL AND EQUIPMENT TO BE PROVIDED. BRANCH CIRCUIT NUMBERS SHOWN ON THE DRAWINGS MAY BE REARRANGED WITHIN A GIVEN PANELBOARD TO SUIT THE NEEDS OF THE INSTALLATION. ELECTRICAL BRANCH CIRCUITS SHALL BE
BALANCED BETWEEN LINES AND PHASES.
4. UTILITY COORDINATION: PROVIDE ALL COORDINATION WITH THE UTILITY INCLUDING LOAD DATA FORMS AND APPLICATION FOR SERVICE AS APPLICABLE. INSTALLATION OF SERVICE, PRIMARY OR SECONDARY FEEDERS AND
METERING SHALL BE PERFORMED IN ACCORDANCE WITH THE UTILITIY REQUIREMENTS.
5. GROUNDING: PROVIDE A COMPLETE GROUNDING SYSTEM AS REQUIRED BY THE NEC AND LOCAL AUTHORITIES HAVING JURISDICTION. ALL BRANCH CIRCUITS SHALL INCLUDE A GROUND CONDUCTOR. USE OF RACEWAY FOR
GROUNDING IS NOT PERMITTED. GALVANIZED GROUND RODS ARE NOT PERMITTED.
6. PANELBOARDS: PROVIDE MINIMUM INTEGRATED EQUIPMENT SHORT CIRCUIT RATING AS INDICATED ON PANEL SCHEDULES. PROVIDE BOLT-ON BREAKERS UNLESS OTHERWISE NOTED. PROVIDE CIRCUIT BREAKERS SHOWN ON THE PANELBOARD SCHEDULES. ALL TERMINATIONS AND LUGS SHALL BE RATED FOR 75-DEGREE CONDUCTORS.
7. PROVIDE TYPEWRITTEN CIRCUIT SCHEDULES TO IDENTIFY PANELBOARD AND EACH BRANCH BREAKER. ACCEPTABLE
MANUFACTURERS ARE SQUARE D, SIEMENS AND EATON.
8. WIRING DEVICES: PROVIDE SPECIFICATION GRADE 15 AND 20- AMPERE SWITCH AND RECEPTACLE DEVICES, AS APPLICABLE. OTHER DEVICES SHALL BE PROVIDED AS INDICATED AND SHALL MATCH PLUG-CONNECTED EQUIPMENT FURNISHED FOR THE PROJECT. DEVICE WALL PLATES SHALL BE SMOOTH, NYLON TYPE AND SHALL BE OFFICE WHITE
IN COLOR OR AS OTHERWISE SPECIFIED. DEVICE COLOR SHALL MATCH WALL PLATES.
9. DISCONNECT SWITCHES: HEAVY DUTY QUICK-MAKE, QUICK-BREAK TYPE, NON-FUSED UNLESS OTHERWISE NOTED.
PROVIDE MEANS TO LOCK SWITCH IN OFF POSITION WITH PAD-LOCK. ENCLOSURES SHALL BE NEMA TYPE 1 OR NEMA TYPE 3R FOR OUTDOOR INSTALLATION. PROVIDE PERMANENT LABELS FOR DISCONNECTS TO INDICATE EQUIMENT
SERVED.
10. LIGHTING FIXTURES: SEE LIGHT FIXTURE SCHEDULE. PROVIDE ALL FIXTURES WITH LAMPS AS INDICATED. WHERE REQUIRED, FIXTURES SHALL BE WET OR DAMP LOCATION LABELED. VERIFY MOUNTING HEIGHTS PRIOR TO
ELECTRICAL ROUGH-IN.
11. ALTERNATES NOT ACCEPTABLE UNLESS NOTED AS "OR EQUAL" ON LIGHT FIXTURE SCHEDULE.
12. VOICE/DATA: RACEWAY SYSTEM BY CONTRACTOR. ALL RACEWAYS SHALL BE PROVIDED WITH PULLSTRINGS OF MINIMUM OF 400-LB. TEST STRENGTH. ALL EQUIPMENT, RECEPTACLES AND CABLING BY OTHERS. PROVIDE BLANK COVERS OVER ALL UNUSED OUTLETS. CABLES, DEVICES AND CABLE TERMINATION IS BY OTHERS.
13. ELECTRICAL CONTRACTOR TO VERIFY CONNECTION TYPE, POWER REQUIREMENTS, MOUNTING HEIGHTS, AND LOCATIONS OF ALL EQUIPMENT WITH TENANT PRIOR TO ROUGH IN. SEE MANUFACTURER'S INSTALLATION MANUALS
FOR SPECIFIC DETAILS ON ALL EQUIPMENT.
14. (E) DENOTES DEVICE IS EXISTING. EXISTING DEVICES TO REMAIN ON EXISTING CIRCUIT AND/OR SWITCHES UNLESS
SHOWN OTHERWISE.
15. (R) DENOTES DEVICE IS BEING RELOCATED FROM WITHIN EXISTING SPACE AND TO REMAIN ON EXISTING CIRCUIT
AND/OR SWITCH UNLESS SHOWN OTHERWISE.
16. INFORMATION ON EXISTING CONDITIONS ARE BASED ON EXISTING PANEL DIRECTORIES, AVAILABLE DRAWINGS FROM LOCAL BUILDING DEPARTMENTS, AND ON SITE VERIFICATIONS WHERE POSSIBLE. ELECTRICAL CONTRACTOR TO
COORDINATE WITH ALL EXISTING CONDITIONS PRIOR TO NEW CONSTRUCTION.
17. VERIFY THAT ALL EXISTING EQUIPMENT SCHEDULED TO BE REUSED IS IN GOOD WORKING CONDITION. REPAIR AND
REPLACE AS NEEDED.
18. CONTRACTORS AND SUB-CONTRACTORS SHALL CAREFULLY REVIEW THE CONSTRUCTION DOCUMENTS.
INFORMATION REGARDING THE COMPLETE WORK IS DISPERSED THROUGHOUT THE DOCUMENT SET AND CANNOT BE
ACCURATELY DETERMINED WITHOUT REFERENCE TO THE COMPLETE DOCUMENT SET.
19. DEMOLITION PLANS SHOW GENERAL DEMOLITION WORK TO BE PERFORMED. NOT ALL EXISTING CONDITIONS SHOWN.
CONTRACTOR TO PERFORM ALL NECESSARY DEMOLITION WORK REQUIRED TO PRODUCE THE BUILDING MODIFICATIONS SHOWN ON THE CONTRACT DOCUMENTS. COORDINATE WITH BUILDING OWNER PRIOR TO DISPOSAL
OF ANY EXISTING EQUIPMENT.
20. ALL ABANDONED UTILITIES ARE TO HAVE CONDUITS, PIPING, OR WIRES REMOVED BACK TO SOURCE OR CAPPED OFF
IN CONCEALED SPACES WHERE POSSIBLE.
21. VERIFY ALL EQUIPMENT REQUIREMENTS AND FINAL LOCATIONS WITH TENANT AND MANUFACTURER.
22. ALL EXPOSED CONDUIT SHALL BE ROUTED PERPENDICULAR, PARALLEL, AND TIGHT TO NEW/EXISTING STRUCTURAL
ELEMENTS.
23. GFI PROTECTION (WHERE REQUIRED PER CODE) TO BE LOCATED ON FACEPLATE OF RECEPTACLE. IF FACEPLATE IS NOT EASILY ACCESSIBLE THEN PROVIDE GFI CIRCUIT BREAKER. GFCI DEVICES MAY NOT BE LOCATED ABOVE OR
BEHIND APPLIANCES.
24. CONNECT EGRESS LIGHTING FIXTURES AND EXIT SIGNS TO AREA LIGHTING CIRCUIT AHEAD OF ANY SWITCH PER NEC 700-12(F) INCLUDING ANY NIGHT LIGHTS. FIXTURES SHOWN SHADED OR LABELED ARE EMERGENCY EGRESS (EM)
WITH BATTERY PACK, NIGHT LIGHT (N) OR BOTH (EM/N).
25. COORDINATE TELECOM, DATA, SECURITY, AND AV EQUIPMENT WITH TENANT AND EQUIPMENT PROVIDERS.
26. ALL DEDICATED CIRCUITS SHALL HAVE THEIR OWN SEPARATE HOT, NEUTRAL, AND GROUND WIRES. CONDUIT SHALL
NOT BE USED AS A GROUND. NEUTRAL AND GROUNDS SHALL NOT BE SHARED.
27. MC CABLE ONLY ALLOWED IN CONCEALED AREAS THAT WILL NOT BE SUBJECTED TO DAMAGE. EXAMPLES ARE ABOVE
CEILINGS AND WITHIN WALLS.
28. ELECTRICAL CONTRACTOR TO COORDINATE ALL LOW VOLTAGE, SPEAKER, AND VOLUME CONTROL WORK. SINGLE GANG PRE-CONSTRUCTION RING FOR EACH VOLUME CONTROL LOCATION WITH PULL STRING, CONDUIT STUB UP
WHERE REQUIRED AT 48" FROM FINISHED FLOOR
29. CONTRACTOR TO REVIEW ENTIRE CONSTRUCTION DOCUMENT SET OF PROJECT TO COORDINATE ALL NECESSARY WORK. THIS INCLUDES MECHANICAL DRAWINGS FOR ALL SWITCHES, CONTROLS, AND INTERLOCKS.
2021 INTERNATIONAL BUILDING CODE
2021 INTERNATIONAL FIRE CODE
2021 INTERNATIONAL MECHANICAL CODE
2021 INTERNATIONAL FUEL GAS CODE
2021 INTERNATIONAL PLUMBING CODE
2021 INTERNATIONAL ENERGY CONSERVATION CODE
2023 NATIONAL ELECTRIC CODE (NEC)
2021 INTERNATIONAL EXISTING BUILDING CODE
HEALTH DEPARTMENT RULES AND REGULATIONS
NATIONAL FIRE PROTECTION ASSOCIATION STANDARDS
IN CASE OF CONFLICTS WITH CODE, DRAWINGS OR SPECIFICATION, THE MORE STRINGENT SHALL PREVAIL.
GENERAL ELECTRICAL NOTES
WIRING NOTES
NO.4 AWG
NO.6 AWG
NO.8 AWG
NO.10 AWG
NO.12 AWG
HOMERUN WIRE SIZE
NO.10 AWG191FT TO 300FT
NO.10 AWG121FT TO 190FT
NO.12 AWG
NO.12 AWG
NO.10 AWG
CIRCUIT WIRE SIZELENGTH
1FT TO 50FT
76FT TO 120FT
51FT TO 75FT
HOMERUNS AND BRANCH WIRING FOR 20 AMP CIRCUITS SHALL BE AS FOLLOWS:
FIRE ALARM WIRING:
1. FIRE ALARM INSTALLER TO COORDINATE WITH FIRE MARSHALL ON REQUIRED
DOCUMENTATION NEEDED.
2. FIRE ALARM INSTALLER TO VERIFY LOCATION OF FIRE ALARM PANEL.
3. FIRE ALARM INSTALLER TO PROVIDE DUCT SMOKE DETECTORS FOR HVAC UNITS PER
SECTION 606 OF THE INTERNATIONAL MECHANICAL CODE. REFER TO MECHANICAL
RTU SCHEDULE FOR DETERMINATION OF UNITS TO RECEIVE SMOKE DETECTORS.
MOUNTING HEIGHT NOTES
MOUNTING HEIGHT OF ALL EXISTING AND NEW ELECTRICAL RECEPTACLES, SWITCHES
AND CONTROLS SHALL COMPLY WITH ICC/ANSI A117.1-2017
· PER SECTION 308.2 FORWARD REACH.
·· UNOBSTRUCTED - MINIMUM OF 15 INCHES AND A MAXIMUM OF 48 INCH ABOVE
FINISHED FLOOR.
·· OBSTRUCTED - WHERE OBSTRUCTION IS 20 INCHES MAX A MAXIMUM OF 48
INCHES ABOVE FINISHED FLOOR. WHERE OBSTRUCTION EXCEEDS 20 INCHES A
MAXIMUM OF 44 INCHES ABOVE FINISHED FLOOR.
· PER SECTION 308.3 SIDE REACH.
·· UNOBSTRUCTED - MINIMUM OF 15 INCHES AND A MAXIMUM OF 48 INCHES ABOVE
FINISHED FLOOR.
·· OBSTRUCTED - WHERE OBSTRUCTION HEIGHT IS 34 INCHES MAX AND DEPTH IS
GREATER THAN 10 AND 24 INCHES MAX A MAXIMUM OF 46 INCHES ABOVE
FINISHED FLOOR. WHERE OBSTRUCTION HEIGHT IS 34 INCHES MAX AND DEPTH
IS 10 INCHES MAX A MAXIMUM OF 48 INCHES ABOVE FINISHED FLOOR.
LIGHTING SYMBOLS
DESCRIPTIONSYMBOL
UNO
ELECTRICAL SYMBOL LEGEND
X
X
X
X X
X
D
OC
SPECIAL SYSTEMS SYMBOLS
S
S
E
N
PUSH BUTTON DOOR BELLDB
REMOTE RELEASE. PROVIDE JUNCTION BOX WITH 3/4" CONDUIT UP IN WALL WITH PULL
STRING STUBBED 24" ABOVE CEILING.KE
ALARM CONTROL KEYPAD. PROVIDE JUNCTION BOX WITH 3/4" CONDUIT UP IN WALL WITH
PULL STRING STUBBED 24" ABOVE CEILING.AK
ACCESS CONTROL KEYPAD. PROVIDE JUNCTION BOX WITH 3/4" CONDUIT UP IN WALL
WITH PULL STRING STUBBED 24" ABOVE CEILING.KP
INTERCOM. PROVIDE JUNCTION BOX WITH 3/4" CONDUIT UP IN WALL WITH PULL STRING
STUBBED 24" ABOVE CEILING.I
PANIC BUTTON. PROVIDE JUNCTION BOX WITH 3/4" CONDUIT UP IN WALL WITH PULL
STRING STUBBED 24" ABOVE CEILING.P
AMBUSH MONITOR. PROVIDE JUNCTION BOX WITH 3/4" CONDUIT UP IN WALL WITH PULL
STRING STUBBED 24" ABOVE CEILING.AM
CCTV CAMERA LOCATION. PROVIDE JUNCTION BOX WITH 3/4" CONDUIT UP IN WALL WITH
PULL STRING STUBBED 24" ABOVE CEILING.
POWER SYMBOLS
M
J J
ABBREVIATIONS
COMMUNICATION SYSTEM SYMBOLS
CIRCUITING SYSTEM SYMBOLS
FIRE ALARM SYMBOLS
F F
F
F
S
H
S
ONE-LINE SYMBOLS
ID
AMPS
VOLTS
G
N L
NOTE: NOT ALL SYMBOLS ARE USED. VERIFY ALL CONNECTIONS AND RECEPTACLE TYPES FOR EQUIPMENT FROM APPROVED MECHANICAL AND EQUIPMENT SUBMITTALS PRIOR TO INSTALLATION.
DESCRIPTIONSYMBOL
DESCRIPTIONSYMBOL
DESCRIPTIONSYMBOL
DESCRIPTIONSYMBOL
DESCRIPTIONSYMBOL
DESCRIPTIONSYMBOL
DESCRIPTIONSYMBOL
FACP
ACC
W
X
X
C
X xxAnP
M
L
ROCKER DIMMER WITH SIDE ADJUSTABLE SLIDE, SINGLE POLE SWITCH, 1000W, 120V,
UNO., MOUNT 48" AFF.
4-WAY, TOGGLE SWITCH, 20A, SINGLE POLE, VOLTAGE AS REQUIRED. MOUNT 48" AFF.
3-WAY, TOGGLE SWITCH, 20A, SINGLE POLE, VOLTAGE AS REQUIRED. MOUNT 48" AFF.
TOGGLE SWITCH, 20A, SINGLE POLE, VOLTAGE AS REQUIRED. MOUNT 48" AFF.
EXIT SIGN, ALL EXITS LIGHTS TO HAVE 1HR MINIMUM BATTERY BACKUP. SHADING
INDICATES ILLUMINATED FACE, PROVIDE CHEVRONS AS INDICATED. MOUNT 7'6" TO
BOTTOM OF FIXTURE ABOVE FINISHED FLOOR.
EMERGENCY LIGHT FIXTURE, IE FROGEYE, ALL EMERGENCY LIGHTS TO HAVE 1HR
MINIMUM BATTERY BACKUP.
LIGHT FIXTURE WITH EM BALLAST, EM BALLAST TO PROVIDE 1000 LUMENS MINIMUM.
TRACK HEAD, CAPITAL LETTER DENOTES TYPE.
POLE LIGHT, SEE LIGHT FIXTURE SCHEDULE AND DETAILS FOR POLE SPECIFICATION.
CAPITAL LETTER DENOTES TYPE.
BOLLARD, CAPITAL LETTER DENOTES TYPE.
SPOT LIGHT, CAPITAL LETTER DENOTES TYPE.
CEILING MTD. LIGHT FIXTURE, IE. GLOBE, DOWNLIGHT, PENDANT, ETC. SEE LIGHT
FIXTURE SCHEDULE FOR SIZE AND MOUNTING. CAPITAL LETTER DENOTES TYPE, LOWER
CASE LETTER DENOTES SWITCH LEG.
WALL MTD. LIGHT FIXTURE, IE. WALL PACK, SCONCE, CYLINDER, ETC. CAPITAL LETTER
DENOTES TYPE, LOWER CASE LETTER DENOTES SWITCH LEG.
WALL BRACKET LIGHT FIXTURE, SEE LIGHT FIXTURE SCHEDULE FOR SIZE. CAPITAL
LETTER DENOTES TYPE, LOWER CASE LETTER DENOTES SWITCH LEG.
STRIP LIGHT FIXTURE, SEE LIGHT FIXTURE SCHEDULE FOR SIZE AND MOUNTING.
CAPITAL LETTER DENOTES TYPE, LOWER CASE LETTER DENOTES SWITCH LEG.
LIGHT FIXTURE, SEE LIGHT FIXTURE SCHEDULE FOR SIZE AND MOUNTING. CAPITAL
LETTER DENOTES TYPE, LOWER CASE LETTER DENOTES SWITCH LEG.
NURSE CALL LIGHT
NURSE/EMERGENCY CALL BUTTON
WALL MTD. SPEAKER
CEILING MTD. SPEAKER
PUSHBUTTON OPERATOR.
LOW VOLTAGE SWITCH, WALL MTD., 48" AFF.
DUAL TECH OCCUPANCY SENSOR, CEILING MTD.
PHOTOCELL SWITCH, MOUNT ON NORTH FACING EXTERIOR WALL, UNO.
TELEPHONE OUTLET. WIRING BY OTHERS, UNO. MOUNT 18" AFF.
TELEPHONE OUTLET. WIRING BY OTHERS, UNO. WALL PHONE, MOUNT 48" AFF.
DATA OUTLET. WIRING BY OTHERS, UNO. MOUNT 18" AFF.
DATA/TELEPHONE OUTLET, WIRING BY OTHERS UNO. MOUNT 18" AFF.
CATV OUTLET, WIRING BY OTHERS, UNO. MOUNT 18" AFF.
CIRCUIT RUN, #12W, 1/2" CONDUIT UNO.
HOMERUN, #12W, 1/2" CONDUIT UNO., ARROWS INDICATE QUANTITY.
CIRCUIT RUN, UNDER FLOOR OR GROUND, #12W, 1/2" CONDUIT UNO.
BRANCH CIRCUIT WITH REQUIRED EQUIPMENT CONNECTION.
BRANCH CIRCUIT BREAK
HORN ONLY
HORN AND STROBE
STROBE ONLY
MANUAL PULL STATION
SMOKE DETECTOR
HEAT DETECTOR
DUCT SMOKE DETECTOR
MAGNETIC DOOR HOLD OPEN
FIRE/ SMOKE DAMPER
FIRE ALARM CONTROL PANEL
ANNUNCIATION PANEL
CIRCUIT BREAKER, FRAME AND TRIP AS INDICATED.
POWER TRANSFORMER, RATING AS INDICATED.
GROUND ELECTRODE
CURRENT TRANSFORMER (CT)
NON-FUSIBLE SWITCH, RATING AS INDICATED.
FUSIBLE SWITCH, RATING AND FUSE SIZE AS INDICATED.
FEEDER SCHEDULE KEY TAG
UTILITY TRANSFORMER
UTILITY ELECTRIC METER
MOTOR WITH DISCONNECT
MOTOR WITH CONTROLLER AND DISCONNECT
GENERATOR
TRANSFER SWITCH
WEATHERHEAD
PANELBOARD OR LOADCENTER, IDENTIFICATION, AMPERES AND VOLTAGE.
OVERHEAD DOOR
TAMPER-PROOF
MOUNT DEVICE 6" AFF, HORIZONTALLY.
ELECTRIC WATER COOLER
TRANSIENT VOLTAGE SURGE SUPPRESSOR
UNDER COUNTER, MOUNT RECEPTACLE HORIZONTALLY,
1" ABOVE BACKSPLASH. OVER COUNTER, MOUNT RECEPTACLE HORIZONTALLY,
UNLESS NOTED OTHERWISE.
FLUSH MTD. PANELBOARD/LOADCENTER.
SURFACE MTD. PANELBOARD/LOADCENTER.
FUSIBLE DISCONNECT SWITCH, RATING AS INDICATED.
NON FUSIBLE DISCONNECT SWITCH, RATING AS INDICATED. RATING AS INDICATED.
MOTOR
POWER POLE WITH COMM AND POWER.
4"X4" JUNCTION BOX, FLUSH/SURFACE MTD.
FLOOR BOX, FLUSH MOUNTED PROVIDE DEVICE, BOX AND COVER AS SPECIFIED.
MANUAL MOTOR STARTER WITH THERMAL OVERLOAD
PLUGMOLD, MULTI-OUTLET RACEWAY, RECEPTACLES SPACED 12" OC, UNO. MOUNT
ABOVE COUNTER.
SPECIAL PURPOSE RECEPTACLE, NEMA TYPE AS INDICATED. MOUNT AT HEIGHT AS
REQUIRED PER EQUIPMENT.
DUPLEX RECEPTACLE, 20A, 120V, 3 WIRE GROUNDED, NEMA 5-20R, UNO. WITH TIE-BAR
REMOVED FOR SWITCHING. MOUNT 18" AFF.
SPECIAL RECEPTACLE, 220V, TYPE AS INDICATED OR MATCH EQUIPMENT CAP. MOUNT
AT HEIGHT AS REQUIRED PER EQUIPMENT.
SIMPLEX RECEPTACLE, 20A, 120V, 3 WIRE GROUNDED, NEMA 5-20R, UNO. SUBSCRIPT 'C'
DENOTES CLOCK RECEPTACLE, MOUNT AT HEIGHT DIRECTED BY ARCHITECT.
QUAD RECEPTACLE, 20A, 120V, 3 WIRE GROUNDED, NEMA 5-20R, UNO. MOUNT 18" AFF.
SUBSCRIPT DENOTES TYPE. IE. IG=ISOLATED GROUND, GFI=GFCI, WP=WEATHERPROOF.
DUPLEX RECEPTACLE, 20A, 120V, 3 WIRE GROUNDED, NEMA 5-20R, UNO. MOUNT 18" AFF.
SUBSCRIPT DENOTES TYPE. IE. IG=ISOLATED GROUND, GFI=GFCI, WP=WEATHERPROOF,
C=CONTROLLED RECEPTACLE WITH ONE RECEPTACLE CONTROLLED VIA OCCUPANCY
SENSOR AND BE MARKED PER NEC 406.3(E).
T TIME SWITCH, WALL MTD., 48" AFF.
D DAYLIGHT SENSOR, MOUNT ON NORTH FACING EXTERIOR WALL, UNO.
OC
UC
TVSS
EWC
H
TP
OHD
DUPLEX RECEPTACLE SAME AS ABOVE BUT WITH (2)USB PORTS.
DUAL TECH OCCUPANCY SENSOR, WALL MTD., 48" AFF. PROVIDE 0-10V DIMMING
ADJUSTABLE SLIDE.
DUAL TECH OCCUPANCY SENSOR, WALL MTD.
X
X
X
X
X
PC
OC
OC
xxAnP
X
CEILING MOUNTEDCLG
DROP CORDD
X
2021 IECC COMPLIANCE
THE 2021 INTERNATIONAL ENERGY CODE (IECC) SHALL BE FOLLOWED FOR THESE SET OF DOCUMENTS. THE FOLLOWING
CODE SECTIONS ARE HIGHLIGHTED BUT DO NOT INCLUDE EVERYTHING REQUIRED.
401 GENERAL REQUIREMENTS
402 BUILDING ENVELOPE REQUIREMENTS
402.5.10 RECESSED LIGHTING
403 BUILDING MECHANICAL SYSTEMS
403.4.1.4 HEATED OR COOLED VESTIBULES
THE HEATING SYSTEM FOR HEATED VESTIBULES AND AIR CURTAINS WITH INTEGRAL HEATING SHALL BE PROVIDED WITH CONTROLS CONFIGURED TO SHUT OFF THE SOURCE OF HEATING WHEN THE OUTDOOR AIR TEMPERATURE IS GREATER THAN 45°F (7°C). VESTIBULE HEATING AND COOLING SYSTEMS SHALL BE CONTROLLED BY A THERMOSTAT LOCATED IN THE VESTIBULE CONFIGURED TO LIMIT HEATING TO A TEMPERATURE NOT GREATER THAN 60°F (16°C) AND COOLING TO A TEMPERATURE NOT LESS THAN 85°F (29°C).
403.13 MECHANICAL SYSTEMS LOCATED OUTSIDE OF THE BUILDING THERMAL ENVELOPE
SECTIONS 403.13.1 THROUGH 403.13.3 SHALL APPLY TO MECHANICAL SYSTEMS PROVIDING HEAT
OUTSIDE OF THE THERMAL ENVELOPE OF A BUILDING.
405 ELECTRICAL POWER AND LIGHTING SYSTEMS
405.2.1.1 OCCUPANT SENSOR CONTROL FUNCTION
OCCUPANT SENSOR CONTROLS IN WAREHOUSES SHALL COMPLY WITH SECTION 405.2.1.2. OCCUPANT SENSOR CONTROLS IN OPEN PLAN OFFICE AREAS SHALL COMPLY WITH SECTION 405.2.1.3. OCCUPANT SENSOR CONTROLS IN CORRIDORS SHALL COMPLY WITH SECTION 405.2.1.4. OCCUPANT SENSOR
CONTROLS FOR ALL OTHER SPACES SPECIFIED IN SECTION 405.2.1 SHALL COMPLY WITH THE
FOLLOWING:
1. THEY SHALL AUTOMATICALLY TURN OFF LIGHTS WITHIN 20 MINUTES AFTER ALL OCCUPANTS HAVE
LEFT THE SPACE.
2. THEY SHALL BE MANUAL ON OR CONTROLLED TO AUTOMATICALLY TURN ON THE LIGHTING TO NOT
MORE THAN 50% POWER.
3. THEY SHALL INCORPORATE A MANUAL CONTROL TO ALLOW OCCUPANTS TO TURN OFF LIGHTS.
405.2.2.1 TIME-SWITCH CONTROL FUNCTION
405.2.3.1 LIGHT-REDUCTION CONTROL FUNCTION
405.2.4 DAYLIGHT-RESPONSIVE CONTROLS
SECTIONS 405.2.4.1 THROUGH 405.2.4.4 SHALL APPLY TO DAYLIGHT-RESPONSIVE CONTROLS.
405.2.5 SPECIFIC APPLICATION CONTROLS
405.2.7 EXTERIOR LIGHTING CONTROLS
SECTIONS 405.2.7.1 THROUGH 405.2.7.4 SHALL APPLY TO EXTERIOR LIGHTING CONTROLS.
405.2.8 PARKING GARAGE LIGHTING CONTROL
405.4 LIGHTING FOR PLANT GROWTH AND MAINTENANCE
405.7 ELECTRICAL TRANSFORMERS:
ELECTRICAL TRANSFORMERS SHALL MEET THE MINIMUM EFFICIENCY REQUIREMENTS OF TABLE 405.7 AS TESTED AND RATED IN ACCORDANCE WITH THE TEST PROCEDURES LISTED IN DOE 10 CFR 431.
405.8 ELECTRICAL MOTORS:
ELECTRICAL MOTORS SHALL MEET THE MINIMUM EFFICIENCY REQUIREMENTS OF TABLES 405.8(1)
THROUGH 405.8(4) WHEN TESTED AND RATED IN ACCORDANCE WITH THE DOE 10 CFR 431.
405.11 AUTOMATIC RECEPTACLE CONTROL
THE FOLLOWING SHALL HAVE AUTOMATIC RECEPTACLE CONTROL COMPLYING WITH SECTION 405.11.1:
1. AT LEAST 50% OF ALL 125V, 15- AND 20-AMP RECEPTACLES INSTALLED IN ENCLOSED OFFICES, CONFERENCE ROOMS, ROOMS USED PRIMARILY FOR COPY OR PRINT FUNCTIONS, BREAKROOMS, CLASSROOMS AND INDIVIDUAL WORKSTATIONS, INCLUDING THOSE INSTALLED IN MODULAR
FURNITURE NOT SHOWN ON THE CONSTRUCTION DOCUMENTS.
2. AT LEAST 25% OF BRANCH CIRCUIT FEEDERS INSTALLED FOR MODULAR FURNITURE NOT SHOWN ON
THE CONSTRUCTION DOCUMENTS.
405.11.1 AUTOMATIC RECEPTACLE CONTROL FUNCTION
406 ADDITIONAL EFFICIENCY REQUIREMENTS
406.1 NEW BUILDINGS SHALL ACHIEVE A TOTAL OF 10 CREDITS FROM TABLES 406.1(1) THROUGH 406.1(5) WHERE THE TABLE IS SELECTED BASED ON THE USE GROUP OF THE BUILDING AND FROM CREDIT
CALCULATIONS AS SPECIFIED IN RELEVANT SUBSECTIONS OF SECTION 406.
408 SYSTEM COMMISSIONING
408.2.1 COMMISSIONING PLAN REQUIRED
408.3.1 FUNCTIONAL TESTING
PRIOR TO PASSING FINAL INSPECTION, THE REGISTERED DESIGN PROFESSIONAL OR APPROVED AGENCY SHALL PROVIDE EVIDENCE THAT THE LIGHTING CONTROL SYSTEMS HAVE BEEN TESTED TO ENSURE THAT CONTROL HARDWARE AND SOFTWARE ARE CALIBRATED, ADJUSTED, PROGRAMMED AND
IN PROPER WORKING CONDITION IN ACCORDANCE WITH THE CONSTRUCTION DOCUMENTS AND
MANUFACTURER'S INSTRUCTIONS. FUNCTIONAL TESTING SHALL BE IN ACCORDANCE AND PER THE PROCEDURES WITHIN SECTIONS 408.3.1.1 AND 408.3.1.3 FOR THE APPLICABLE CONTROL TYPE.
408.3.2 DOCUMENTATION REQUIREMENTS
A FINAL COMMISSIONING REPORT SHALL BE DELIVERED TO THE BUILDING OWNER PER SECTION 408.2.5
OF THE 2021 IECC.
C CO DETECTOR
OWNERSHIP OF INSTRUMENTS OF
SERVICE
All Drawings, Reports, Plans, Specifications, Computer Files (including CAD files), field information, notes, sketches, and other design materials prepared by the Engineer and his/her consultants as instruments of service shall remain the property of the Engineer. The Engineer shall retain all common law, statutory and other reserved rights, including the Copyright thereto.
SHEET
FO
R
T
LY
O N
E M
ER
G
EN
C
Y G
EN
ER
AT
O
R R
EP
LA
C
EM
EN
T
C
O R
D
5, L
AS
A
N
IM
AS
C O
PROJECT #: 23-6865
DRAWN BY: JL
CHECKED BY: MRM
FULL SET ISSUE HISTORY:
REVIEW SET 06.26.20241
CLIENT:
SHEET REVISION:
cShea 4445 Northpark Dr. Suite 200 Colorado Springs, CO 80907 mcsheaconsulting.com Project #: 23-6865 onsulting, LLC
MECHANICAL + ELECTRICAL + PLUMBING
E0.1
ARCHITECT:
11/11/2024
90% REVIEW SET 09.25.20242
BID SET 10.11.20243
AutoCAD SHX Text S
AutoCAD SHX Text S
AutoCAD SHX Text S
AutoCAD SHX Text S
AutoCAD SHX Text S
AutoCAD SHX Text S
AutoCAD SHX Text S
AutoCAD SHX Text S
OWNERSHIP OF INSTRUMENTS OF
SERVICE
All Drawings, Reports, Plans, Specifications, Computer Files (including CAD files), field information, notes, sketches, and other design materials prepared by the Engineer and his/her consultants as instruments of service shall remain the property of the Engineer. The Engineer shall retain all common law, statutory and other reserved rights, including the Copyright thereto.
SHEET
FO
R
T
LY
O N
E M
ER
G
EN
C
Y G
EN
ER
AT
O
R R
EP
LA
C
EM
EN
T
C
O R
D
5, L
AS
A
N
IM
AS
C O
PROJECT #: 23-6865
DRAWN BY: JL
CHECKED BY: MRM
FULL SET ISSUE HISTORY:
REVIEW SET 06.26.20241
CLIENT:
SHEET REVISION:
cShea 4445 Northpark Dr. Suite 200 Colorado Springs, CO 80907 mcsheaconsulting.com Project #: 23-6865 onsulting, LLC
MECHANICAL + ELECTRICAL + PLUMBING
E4-0.1
ARCHITECT:
11/11/2024
90% REVIEW SET 09.25.20242
BID SET 10.11.20243
500KVA
UTILITY
TRANSFORMER
1200A SERVICE
RATED AUTOMATIC
3-POLE TRANSFER
SWITCH
750 KVA
GENERATOR
480/277V, 3Ø
300kVA
NEMA
3R
XFMR
XFMR
(E)
PANEL
'DP3'
600A
480/277V 3Ø(E)
600A (E)
600A
(E) 600A, 480/277V, 2 SECTION
PANEL
'D3'
(E) 1600A, 208/120V
'MSB-4L'
OUTSIDE INSIDE
600A
600A 480V
NEMA 3R
DISCONNECT
600A
DISCONNECT
#2/0 AL
GND. IN
"3C
X
ISC = 42,958A
X
ISC = 18,798A
X
ISC = 9,983A
X
ISC = 9,941A
X
ISC = 16,556A
XISC = 9,966A
600A
DISCONNECT
DP3
1200A
MAIN
C .W
. P
IP
E
SE
R
VI
C E
G R
O U
N D
R O
D
BU
IL
D
IN
G S
TE
EL
#3 /0
#3 /0
#4 C
U
#3 /0
#3 /0
TE
LE
PH
O
N E
BO
AR
D
#6
GROUND BUS
20' MIN. CONCRETE
ENCASED ELECTRODE
EXOTHERMIC WELDED
CONNECTION
1600A
EXISTING
SERVICE
TRANSFORMER
480V,3Ø
(2 OF 2)
(E)
XFMR
(E)
PANEL
'DP3'
600A
480/277V 3Ø(E)
600A
EXISTING
SERVICE
TRANSFORMER
208V,3Ø
(1 OF 2)
(E)
XFMR
(E) 600A
(E) 600A, 480/277V, 2 SECTION
PANEL
'D3'
(E) 1600A, 208/120V
'MSB-4L'
OUTSIDE INSIDE
1600A
ELEVATORELEVATOR
J (E)
'EM4'(E)
'DP-4A'(E)
'EM4'(E)
SERVICE
DISCONNECT (E)
DEMO
EXISTING SERVICE
TRANSFORMER (2 OF 2)
DEMO
EXISTING SERVICE
TRANSFORMER (1 OF 2)
"MSB-4L"
XFMR (E)
ATS ABOVE (E)
"DP3" (E)
ELEVATOR
DISCONNECT (E)
ELEVATOR
DISCONNECT (E)
ELEV TRANSFER
ELEVATORELEVATOR
500KVA, 480V, 3Ø,
UTILITY TRANSFORMER
(REUSE EXISTING PAD)
600A, 480V
NEMA 3R
DISCONNECT (2 OF 2)
1200A, 480V, SERVICE
RATED AUTOMATIC
3-POLE TRANSFER
SWITCH
300KVA, 3Ø, NEMA 3R
TRANSFORMER
(REUSE EXISTING PAD)
750KVA
EMERGENCY
GENERATOR
ENCLOSURE
J (E)
'EM4'(E)
'DP-4A'(E)
'EM4'(E)
SERVICE
DISCONNECT (E)
"MSB-4L"
XFMR (E)
ATS ABOVE (E)
"DP" (E)
ELEVATOR
DISCONNECT (E)
ELEVATOR
DISCONNECT (E)
ELEV TRANSFER
OWNERSHIP OF INSTRUMENTS OF
SERVICE
All Drawings, Reports, Plans, Specifications, Computer Files (including CAD files), field information, notes, sketches, and other design materials prepared by the Engineer and his/her consultants as instruments of service shall remain the property of the Engineer. The Engineer shall retain all common law, statutory and other reserved rights, including the Copyright thereto.
SHEET
FO
R
T
LY
O N
E M
ER
G
EN
C
Y G
EN
ER
AT
O
R R
EP
LA
C
EM
EN
T
C
O R
D
5, L
AS
A
N
IM
AS
C O
PROJECT #: 23-6865
DRAWN BY: JL
CHECKED BY: MRM
FULL SET ISSUE HISTORY:
REVIEW SET 06.26.20241
CLIENT:
SHEET REVISION:
cShea 4445 Northpark Dr. Suite 200 Colorado Springs, CO 80907 mcsheaconsulting.com Project #: 23-6865 onsulting, LLC
MECHANICAL + ELECTRICAL + PLUMBING
E4-1.1
ARCHITECT:
11/11/2024
90% REVIEW SET 09.25.20242
BID SET 10.11.20243
SCALE:
PROPOSED ONE-LINE DIAGRAM - BUILDING 4
E4-1.1 NONESCALE:
EXISTING ONE-LINE DIAGRAM - BUILDING 41
E4-1.1 NONE
SCALE:
EXISTING BUILDING 4 ELECTRICAL PLAN
1/8"=1'-0"E4-1.1
SCALE:
PROPOSED BUILDING 4 ELECTRICAL PLAN
1/8"=1'-0"E4-1.1
CONCRETE FOOTER
All Drawings, Reports, Plans, Specifications, Computer Files (including CAD files), field information, notes, sketches, and other design materials prepared by the Engineer and his/her consultants as instruments of service shall remain the property of the Engineer. The Engineer shall retain all common law, statutory and other reserved rights, including the Copyright thereto.
SHEET
FO
R
T
LY
O N
E M
ER
G
EN
C
Y G
EN
ER
AT
O
R R
EP
LA
C
EM
EN
T
C
O R
D
5, L
AS
A
N
IM
AS
C O
PROJECT #: 23-6865
DRAWN BY: JL
CHECKED BY: MRM
FULL SET ISSUE HISTORY:
REVIEW SET 06.26.20241
CLIENT:
SHEET REVISION:
cShea 4445 Northpark Dr. Suite 200 Colorado Springs, CO 80907 mcsheaconsulting.com Project #: 23-6865 onsulting, LLC
MECHANICAL + ELECTRICAL + PLUMBING
E6-0.1
ARCHITECT:
11/11/2024
(E)
TRANSFORMER
1200A 480V SERVICE
RATED AUTOMATIC
3-POLE TRANSFER
SWITCH
XFMR
(E)
400 KVA
GENERATOR
480/277V, 3Ø
OUTSIDE INSIDE
(E)
PANEL 'MSB-6H'
1200A, 480/277V, 3Ø
1200A
MCB
(E)
PANEL
'EMD-6'
300A 480/277V
3Ø
NEW FEEDER
ISC = 42,958A
ISC = 42,958A
X
ISC = 22,247A
1200A
MAIN
300A
C .W
. P
IP
E
SE
R
VI
C E
G R
O U
N D
R O
D
BU
IL
D
IN
G S
TE
EL
#3 /0
#3 /0
#4 C
U
#3 /0
#3 /0
TE
LE
PH
O
N E
BO
AR
D
#6
GROUND BUS
20' MIN. CONCRETE
ENCASED ELECTRODE
EXOTHERMIC WELDED
CONNECTION
X X
STAIR
UP
'EMD6'(E)
'FL6'(E)
'F'(E)
'MSB-6H'(E)
LIGHTING
CONTACTOR(E)
'EM6'(E)
'UC'(E)
'D'(E)
'E'(E)
'G'(E)
J
(E)
EXISTING SERVICE
TRANSFORMER
EXISTING
EMERGENCY
GENERATOR
ENCLOSURE
ATS (D)
480V
TRANSFORMER
XFMR
(E)
PANEL 'MCB-6'
1200A, 480/277V, 3Ø
OUTSIDE INSIDE
(E)
PANEL
'EMD-6'
300A 480/277V
3Ø
400A, 480V AUTOMATIC
3-POLE TRANSFER
SWITCH
400 KVA
GENERATOR
600A, 480/277V, 3Ø
DEMO EXISTING ATS(E)
PANEL 'MSB-6H'
1200A, 480/277V, 3Ø
1200A
MCB 300A
STAIR
UP
'EMD6'(E)
'FL6'(E)
'F'(E)
'MSB-6H'(E)
LIGHTING
CONTACTOR(E)
'EM6'(E)
'UC'(E)
'D'(E)
'E'(E)
'G'(E)
EXISTING SERVICE
TRANSFORMER
REUSE
EXISTING
EMERGENCY
GENERATOR
ENCLOSURE
1200A, 480V, SERVICE
RATED AUTOMATIC
3-POLE TRANSFER
SWITCH
OWNERSHIP OF INSTRUMENTS OF
SERVICE
All Drawings, Reports, Plans, Specifications, Computer Files (including CAD files), field information, notes, sketches, and other design materials prepared by the Engineer and his/her consultants as instruments of service shall remain the property of the Engineer. The Engineer shall retain all common law, statutory and other reserved rights, including the Copyright thereto.
SHEET
FO
R
T
LY
O N
E M
ER
G
EN
C
Y G
EN
ER
AT
O
R R
EP
LA
C
EM
EN
T
C
O R
D
5, L
AS
A
N
IM
AS
C O
PROJECT #: 23-6865
DRAWN BY: JL
CHECKED BY: MRM
FULL SET ISSUE HISTORY:
REVIEW SET 06.26.20241
CLIENT:
SHEET REVISION:
cShea 4445 Northpark Dr. Suite 200 Colorado Springs, CO 80907 mcsheaconsulting.com Project #: 23-6865 onsulting, LLC
MECHANICAL + ELECTRICAL + PLUMBING
E6-1.1
ARCHITECT:
11/11/2024
90% REVIEW SET 09.25.20242
BID SET 10.11.20243
SCALE:
PROPOSED ONE-LINE DIAGRAM - BUILDING 6
E6-1.1 NONESCALE:
EXISTING ONE-LINE DIAGRAM - BUILDING 61
E6-1.1 NONE
SCALE:
EXISTING BUILDING 6 ELECTRICAL PLAN
1/8"=1'-0"E6-1.1
SCALE:
PROPOSED BUILDING 6 ELECTRICAL PLAN
1/8"=1'-0"E6-1.1
All Drawings, Reports, Plans, Specifications, Computer Files (including CAD files), field information, notes, sketches, and other design materials prepared by the Engineer and his/her consultants as instruments of service shall remain the property of the Engineer. The Engineer shall retain all common law, statutory and other reserved rights, including the Copyright thereto.
SHEET
FO
R
T
LY
O N
E M
ER
G
EN
C
Y G
EN
ER
AT
O
R R
EP
LA
C
EM
EN
T
C
O R
D
5, L
AS
A
N
IM
AS
C O
PROJECT #: 23-6865
DRAWN BY: JL
CHECKED BY: MRM
FULL SET ISSUE HISTORY:
REVIEW SET 06.26.20241
CLIENT:
SHEET REVISION:
cShea 4445 Northpark Dr. Suite 200 Colorado Springs, CO 80907 mcsheaconsulting.com Project #: 23-6865 onsulting, LLC
MECHANICAL + ELECTRICAL + PLUMBING
E8-0.1
ARCHITECT:
11/11/2024
TRANSFORMER
1200A SERVICE
RATED AUTOMATIC
3-POLE TRANSFER
SWITCH
750 KVA
GENERATOR
480/277V, 3Ø
300kVA
XFMR
XFMR
OUTSIDE INSIDE
400A
400A 480V
NEMA 3R
DISCONNECT
X
ISC = 7,484A
ISC = 42,958A
ISC = 18,798A
X X
X
ISC = 7,461A
X
ISC = 13,352A
X
ISC = 21,970A
3 3
#3/0 AL
GND. IN
"3C
REPLACE W/
LIKE FOR LIKE
1200A
MAIN
(A)
PANEL 'MDB-8L'
800A, 208/120V, 3Ø
800A
MCB
(A)
PANEL 'MDB-8H'
800A, 480/277V, 3Ø
800A
MCB
C .W
. P
IP
E
SE
R
VI
C E
G R
O U
N D
R O
D
BU
IL
D
IN
G S
TE
EL
#3 /0
#3 /0
#4 C
U
#3 /0
#3 /0
TE
LE
PH
O
N E
BO
AR
D
#6
GROUND BUS
20' MIN. CONCRETE
ENCASED ELECTRODE
EXOTHERMIC WELDED
CONNECTION
TO BLDG. No.7
ELEVATOR
'MDP'(E)
J
(E)
'FL8'(E)
ATS #2(E)'EM8'(E)
ATS #1(E)
EXISTING EMERGENCY GENERATOR
ENCLOSURE LOCATED WEST OF THIS
AREA
500KVA, 480V, 3Ø,
UTILITY
TRANSFORMER
300KVA, 3Ø, NEMA
3R TRANSFORMER
750KVA
EMERGENCY
GENERATOR
ENCLOSURE
400A, 480V
NEMA 3R
DISCONNECT
1200A, 480V, SERVICE
RATED AUTOMATIC
3-POLE TRANSFER
SWITCH
'LIGHTS'(E)
800A, 480V 'MSB-8H' (B)
800A, 208V 'MSB-4L' (A)
OWNERSHIP OF INSTRUMENTS OF
SERVICE
All Drawings, Reports, Plans, Specifications, Computer Files (including CAD files), field information, notes, sketches, and other design materials prepared by the Engineer and his/her consultants as instruments of service shall remain the property of the Engineer. The Engineer shall retain all common law, statutory and other reserved rights, including the Copyright thereto.
SHEET
FO
R
T
LY
O N
E M
ER
G
EN
C
Y G
EN
ER
AT
O
R R
EP
LA
C
EM
EN
T
C
O R
D
5, L
AS
A
N
IM
AS
C O
PROJECT #: 23-6865
DRAWN BY: JL
CHECKED BY: MRM
FULL SET ISSUE HISTORY:
REVIEW SET 06.26.20241
CLIENT:
SHEET REVISION:
cShea 4445 Northpark Dr. Suite 200 Colorado Springs, CO 80907 mcsheaconsulting.com Project #: 23-6865 onsulting, LLC
MECHANICAL + ELECTRICAL + PLUMBING
E8-1.1
ARCHITECT:
11/11/2024
90% REVIEW SET 09.25.20242
BID SET 10.11.20243
SCALE:
PROPOSED ONE-LINE DIAGRAM - BUILDING 8
E8-1.1 NONE
SCALE:
PROPOSED BUILDING 8 ELECTRICAL PLAN
1/8"=1'-0"E8-1.1
File details come from the government source that posted it. Updated .