Appendix E - Points of Demarcation.pdf

PDF 83 KB Posted

Attached to
Charleston Air Base Dormitory Maintenance Federal contract opportunity
Solicitation number
FA441823Q0018
Issued by
Department of the Air Force Air Mobility Command

About this file

This document outlines maintenance responsibilities for utilities at Charleston Air Base facilities. The contractor will be responsible for maintenance and repairs of potable water lines from the shutoff valve to buildings, sewage lines from cleanouts to buildings, electrical components downstream of main breakers including all exterior lighting, natural gas lines downstream of meters, and chilled water lines and systems downstream of isolation valves. The Base Civil Engineer will maintain utilities upstream of contractor responsibilities, including water mains, sewage mains, electrical lines and components upstream of main breakers, natural gas components upstream of meters, and chilled water lines from the plant to isolation valves. This document provides details to support the Charleston Air Base Dormitory Maintenance solicitation, which seeks maintenance of utilities and facilities at specified Charleston Air Base buildings.

View the file

Other files for this federal contract opportunity

Other files attached to Charleston Air Base Dormitory Maintenance, newest first.
File Type Posted
Questions and Answers - AB Dorm Mx - Part 2.pdf PDF
PWS Air Base Dormitory Facility Mx - Revision 2.docx DOCX document
Site Visit Attendence - AB Dorms Mx.pdf PDF
Questions and Answers - AB Dorm Mx.docx DOCX document
Appendix C - Service Call Historical Workload Data - Revision 1.xlsx XLSX spreadsheet
COMBO_ABDorms_FA441823Q0018_Amendment_2.docx DOCX document
PWS Air Base Dormitory Facility Mx - Revision 1.pdf PDF
AB Dormitory Facility Maintenance and Repair Services Price Schedule - Revision 1.xlsx XLSX spreadsheet
COMBO_ABDorms_FA441823Q0018_Amendment_1.pdf PDF
Appendix A - Real Property Installed Equipment Inventory.xlsx XLSX spreadsheet
Appendix C - Service Call Historical Workload Data.xlsx XLSX spreadsheet
Appendix G - Exterior Lighting.pdf PDF
Wage Determination 15-4427.pdf PDF
COMBO_ABDorms_FA441823Q0018.docx DOCX document
AB Dormitory Facility Maintenance and Repair Services Price Schedule.xlsx XLSX spreadsheet
PWS Air Base Dormitory Facility Mx.docx DOCX document
Appendix B - Facilities And Structures.xlsx XLSX spreadsheet
Appendix D - Contractor Base Security and Access.pdf PDF
Appendix F - Government Furnished Facilities and Structures.pdf PDF
Joint Base Charleston Base Access Worksheet - Form 111 (Aug 22).pdf PDF
Show all 20

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Appendix F – Points of Demarcation

FOR OFFICIAL USE ONLY

The contractor shall be responsible for maintenance and repairs of the utilities (excluding security and telecommunications lines) for Air Base buildings 460, 461, 464, 466, 468, 469, 473, and 479 as follows:

Exterior domestic (potable water) lines and system as follows:

Water supply lines from the shutoff valve to the building or five feet from the building if no valve exists, will be the responsibility of the Contractor.

Water supply from the shut off valve or five feet from the building to the source main will be the responsibility of the Base Civil Engineer (BCE).

If no shut off valve exists, the Base Civil Engineer (BCE) will assist with isolation and the five-foot rule will take effect.

Exterior sewage (CHT) lines and system as follows:

From the building clean-out to the building or five feet from the building if no clean-out exist, will be the responsibility of the contractor.

From the clean-out to the sewer main or five feet from the building if no clean-out exists, will the responsibility of the Base Civil Engineer (BCE).

Electric lines as follows:

The contractor shall be responsible for the main distribution breaker(s) and all components downstream in each facility.

The contractor shall be responsible for all exterior lighting from the base of the pole to the fixture or bulb.

All underground electrical lines, electrical components upstream from the main distribution breaker, and transformers shall be the responsibility of the Base Civil Engineer (BCE).

All underground electrical lines from the main distribution breaker panel to the base of the pole for exterior lighting shall be the responsibility of the Base Civil Engineer (BCE).

Natural gas lines and systems as follows:

Everything downstream from the meter and/or regulator shall be the responsibility of the contractor.

The meter, regulator, and everything upstream shall be the responsibility of the provisioning entity.

Chilled Water distribution lines and systems as follows:

The chilled water line from the primary shutoff valve in the Chilled Water Plant (CWP) to the isolation valve inside of each serviced facility shall be the responsibility of the Base Civil Engineer

(BCE).

The chilled water line and systems in the chilled water plant shall be the responsibility of the contractor for everything upstream of the primary shutoff valve.

Chilled water lines and systems downstream from the facility isolation valve shall be the responsibility of the contractor.

The entirety of chilled water systems for facilities not tied into the CWP shall be the responsibility of the Contractor, excluding all portions of chilled water lines that are underground, which shall be the responsibility of the Base Civil Engineer (BCE).