Appendix A - Inspection Forms and Checklists.pdf
PDF 703 KB Posted
- Solicitation number
- 36C25025Q0470
About this file
The file is a comprehensive set of inspection checklists for underground storage tank (UST) systems, following the Petroleum Equipment Institute's Recommended Practice 900 (PEI RP 900) standard. The checklists cover multiple critical areas of UST system inspection, including:
The detailed forms provide thorough annual and quarterly inspection guidance for various UST system components such as submersible turbine pumps, fill areas, leak detection devices, dispenser systems, ATG (Automatic Tank Gauge) manholes, overfill prevention mechanisms, and corrosion protection systems. Each checklist includes specific technical inspection points with reference numbers, test date fields, and sections for documenting deficiencies across up to four tanks. The forms are designed to ensure comprehensive assessment of underground storage tank infrastructure, helping facilities maintain regulatory compliance and detect potential issues before they become critical problems.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| UST 5.pdf | ||
| Technical Questions.pdf | ||
| UST 1.pdf | ||
| UST 6.pdf | ||
| 36C25025Q0470 0001.pdf | ||
| Appendix A - Inspection Forms and Checklists 2.pdf | ||
| UST 3.pdf | ||
| UST 2.pdf | ||
| Statement of Work UST Inspection FINAL.docx | DOCX document | |
| UST 4.pdf | ||
| Appendix C - As-Built Documents for UST Tanks.pdf | ||
| Appendix B - Veeder Root Verify Test Guide.pdf | ||
| Appendix D - Tank Charts.pdf | ||
| Service Contract Act WD 2015-4839 REV 26 EFF 12.23.2024 WAYNE.pdf | ||
| 36C25025Q0470.docx | DOCX document |
Show all 15
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Department of Licensing and Regulatory Affairs, Bureau of Fire Services, Storage Tank Division P.O. Box 30033, Lansing, MI 48909 Phone 517-241-8847
UNDERGROUND STORAGE TANK OPERATIONAL FACILITY INSPECTION FORM
This information is required under Part 211, Underground Storage Tank Regulations, of the Natural Resources and Environmental Protection Act, Act 451 of the Public Acts of 1994.
Any owner who knowingly fails to notify or submits false information shall be subject to a misdemeanor punishable by imprisonment for not more than 6 months or fines of not more than $500.00 or both and/or a civil fine not to exceed $5,000.00 for each underground storage tank system for each day of violation.
INITIAL BESIDE EACH STATEMENT THAT APPLIES:
__________ Verification of proper tank registration including proper certificate posting.
__________ Verification of functional status of corrosion protection equipment if required and present, including proper cathodic protection system readings in the case of impressed current corrosion protection systems.
__________ Verification of functional status of release detection equipment including reviewing the alarm history report for the previous month, and checking that each alarm condition was documented and responded to appropriately. A copy of the alarm history report or log, along with documentation describing action taken in response to any alarm(s), shall be attached to the monthly report.
__________ Results of inspection for the presence of product, water, or debris in the spill containers and verifying the functional status of leak prevention equipment, such as spill and overflow.
__________ Results of inspection for the presence of product, water, or debris in under dispenser containment areas or containment sumps, and checking that the monitoring equipment in these containment areas is located in the proper position to detect a leak at the earliest possible opportunity.
__________ Verification that any required testing, monitoring, or periodic inspections of the UST systems have been completed, including documentation of the dates those activities occurred. (i.e.: Impact/fire safety valve, mechanical leak detector, annual piping testing, etc.)
__________ Verification of the presence of all required records necessary to substantiate operational compliance.
__________ Notice to the Class A operator of any deficiencies or noncompliance with any of the above items and any recommendations made to remedy any deficiencies or noncompliance discovered during the site visit, including any prior recommendations that have not been addressed within 60 days or another time frame determined by the department.
Provide an explanation for any of the above statements left incomplete._____________________________________________
I attest that this inspection was done in accordance with Section 280.13(c)(1) & (2) of the Michigan Underground Storage Tank Rules (MUSTR). As a certified Class B operator, I am familiar with the information submitted in this report and all attached documents. Based upon my reasonable inquiry of those individuals responsible for obtaining the information, I believe the information in this report is, to the best of my knowledge, true, accurate and complete.
Print name & official title of Designated Class B Operator Signature of Designated Class B Operator Date
BFS-4027 (Rev 9/15)
FACILITY NAME
FACILITY ID NUMBER
FACILITY STREET ADDRESS (P.O. BOX NOT ACCEPTABLE) CONTACT PERSON AREA CODE & TELEPHONE NUMBER
CITY COUNTY STATE
MI
ZIP CODE
OWNER NAME OWNER ADDRESS AREA CODE & TELEPHONE NUMBER
CITY STATE ZIP CODE
INSTRUCTIONS: Section 280.13(c)(1) & (2) of the Michigan Underground Storage Tank Rules (MUSTR) requires owners and operators of underground storage tanks (UST) to perform required checks of their UST systems and to attest to their findings. This form, a form acceptable to the department or an electronic form must be completed by the Class B operator and then provided to the Class A operator. The Class B operator shall alert the Class A operator of any conditions discovered during the inspection that may require follow-up actions. The completed form must be maintained (kept) by the Class A operator for at least 3 years. The form is NOT submitted to the Bureau of Fire Services, Storage Tank Division. Please direct questions to the Storage Tank Division, at 517-241-8847.
N/A Tank 1 Tank 2 Tank 3 Tank 4 Tank 5 Tank 6
If any problem is found, contact: Contact Information:
Tank Vents Vent cap present, vent pipe solidly supported and vertical Stage I Vapor Recovery
Manual Interstitial Monitoring for Piping (MIMPT) Tank-top sump inspected & no liquid found
Manual Interstitial Monitoring for Tanks
(MIMT)
Steel tank: interstitial space checked & found dry
Tank Gauge Stick Tank gauge stick can be clearly read, is not warped or broken Check for Water
Fiberglass tank: Interstitial space checked & found dry
No water present in the tank
Drop Tube Standard drop tube smooth, no ragged edges, in good condition Top edge of coaxial drop tube smooth, round, slightly below the top edge of the fill pipe
All Tanks
Spill-Containment Manhole Drain valve in spill-containment manhole in good condition
All covers present, in good condition, seated firmly on the correct tank
Grade-Level Covers
N/A
Instructions: Mark each tank where no problem is observed with a "Yes" - If certain equipment is not required and/or not present, mark checklist in the N/A column - If a defect is found, mark the checklist with an "No", describe the problem in the DEFICIENCIES section, and notify the Class B person.
If spill-containment manhole is present, no cracks, bulges, or holes
If spill-containment manhole is present, no dirty, no trash, water, or product
Record volt & amp readings, readings consistent with previous months
N/A
DESCRIBE ANY DEFICIENCIES HERE:
Observation and Monitoring Wells Observation well cover is properly identified and secured
Corrosion Protection
Impressed-Current Cathodic Protection Record hour meter reading (if present). Reading increases by about 700 hours each month
Two-Point (Dual-Point) Vapor Recovery
Cover present, colored orange, seated firmly at grade, not broken, cracked or chipped
Vapor recovery cap present, seals tightly Poppet of vapor recovery adaptor seals tightly
Fiberglass tank: level of monitoring fluid within normal range For steel & fiberglass tanks, vacuum level is within tolerances
Manual Groundwater (GWM) Or Soil Vapor Monitoring (SVM)
Wells sampled and results pass
Inventory reconciled & within the company or regulatory standard
Inventory Control (IC)
Monthly Piping Leak Test (MPLT) Passing tank test report printed & properly filed
Statistical Inventory Reconciliation (SIR) This month's inventory analyzed; last month's results passed and available for inspection
Automatic Tank Gauge (ATG) Passing tank test report printed & properly filed Continuous Interstitial Monitoring (CIM) Sensor status report printed and properly filed
Daily Inspections Complete daily checklist & Compare to previously completed daily checklists
Leak Detection Recordkeeping
Circle method of tank leak detection: ATG, CIM, SIR, IC, GWM, SVM, MIMT Circle method of piping leak detection: CIM, CMPT, SIR, GWM, SVM, MIMP
Category Description Product Type:
QUARTERLY UNDERGROUND STORAGE SYSTEM INSPECTION CHECKLIST
Facility ID Facility Name/ Address Class A/B Operator Date
PEI/RP900
-21 pei.org cepsnI resnepsiD launnA 009 PR IEP __ fo ___ egaP tsilkcehC noit _
ID#: ANNUAL DISPENSER INSPECTION CHECKLIST Date:
Category Description PEI/RP900 N/A Disp 1 Disp 2 Disp 3 Disp 4
Initial Fuel Dispenser Inspection 7.5
All Dispensers
1.5.7 yrd dna naelc era stnenopmoc resnepsid llA
2.5.7 yrd si pmus ,tneserp si pmus resnepsid fI
Fuel Dispenser Inspection 7.6
All Dispensers
1.6.7 gnikael fo sngis on wohs sgnittif dna gnipip elbisiV
Piping in good condition 7.6.2
Dispenser containment sump fr 5.6.7 sirbed dna hsart fo ee
Junction box(es) have covers, not corroded; conduit and intrinsically safe wiring in good condition 7.6.8
Flexible connectors not frayed, twisted, kinked or bent beyond manufacturer specifications 7.6.9
Shear valves operate freely and close completely TEST DATE: 7.6.15 Stage II piping functional or else capped and sealed at an elevation lower than the fuel dispenser island 7.6.16
Dispensers Without Sumps
Flex connectors and other metallic product piping are not in contact with soil or water or are cathodically protected 7.6.17
Dispensers With Sumps
4.6.7 ylreporp fo desopsid dna devomer tcudorp ro retaw ynA
6.6.7 stcefed rehto ro ,seglub ,seloh ,skcarc fo eerf pmuS
7.6.7 deruces dna tcatni sgnittif noitarteneP Piping interstitial space open to the dispenser sump or dispenser pan (open double-walled piping system only) 7.6.21
Piping interstitial space closed to the dispenser sump (closed double-walled piping system only) 7.6.22 Dispensers With
Single-Walled Sumps
Single-walled sump tested for integrity every 3 years TEST DATE: 7.6.18
Dispensers With Double-Walled
Sumps
If not continuously monitored or inspected annually, double-walled sump tightness tested every 3 years 91.6.7 :ETAD TSET
DESCRIBE ANY DEFICIENCIES HERE:
APPENDIX A-2: SAMPLE FORM FOR ANNUAL DISPENSER INSPECTION CHECKLIST
Go to www.pei.org/RP900 for an electronic version of this form.
cepsnI pmuS lliF launnA 009 PR IEP __ fo ___ egaP tsilkcehC noit _
ID#: ANNUAL FILL CONTAINMENT SUMP INSPECTION CHECKLIST Date:
Category Description PEI/RP900 N/A Tank 1 Tank 2 Tank 3 Tank 4
Fill Sump 7.6
Fill Containment Sump
4.6.7 ylreporp fo desopsid dna devomer tcudorp ro retaw ynA
1.6.7 gnikael fo sngis on wohs sgnittif dna gnipip elbisiV
Piping in good condition 7.6.2
3.6.7 tneserp ton noisorroc evissecxE
5.6.7 sirbed dna hsart fo eerf pmuS
Sump is free of cracks, holes, bul 6.6.7 stcefed rehto ro seg
7.6.7 deruces dna tcatni sgnittif noitarteneP Junction box(es) have covers, not corroded; conduit and intrinsically safe wiring in good condition 7.6.8
Flexible connectors not frayed, twisted, kinked or bent beyond manufacturer specifications 7.6.9
Piping interstitial space open to the fill sump (open double-walled piping system only) 7.6.20
Piping interstitial space closed to the fill sump (closed double-walled piping system only) 7.6.22
Sump lid, gasket and seals pres 32.6.7 noitidnoc doog ni dna tne
Manhole cover at grade in good condition, does not touch sump cover, all bolts present, handles and lift mechanism in good condition (as applicable) 7.6.24
Single-Walled Fill Sump Single-walled sump tested for integrity every 3 years TEST DATE: 7.6.18
Double-Walled Fill Sump
If not continuously monitored or inspected annually, double-walled sump tightness tested every 3 years TEST DATE: 7.6.19
APPENDIX A-2: SAMPLE FORM FOR ANNUAL FILL CONTAINMENT SUMP INSPECTION CHECKLIST
Recom m ended Practices for the Inspection and M aintenance of UST System s aP tsilkcehC noitcepsnI eciveD noitceteD kaeL launnA 009 PR IEP ge ___ of ___
ID#: ANNUAL LEAK DETECTION DEVICE INSPECTION CHECKLIST Date:
Category Description PEI/RP900 N/A Tank 1 Tank 2 Tank 3 Tank 4
Leak Detection Device. Describe location (e.g., interstitial, STP, fill, dispenser) on this row: 7.7
Liquid Sensor
Sensor tested and functio 1.7.7 :ETAD TSET lan Sensor properly mounted at the bottom of the containment sump or pan (containment sump or pan sensor only) 7.7.3
Sensor properly mounted at the bottom of double-walled tank (double-walled tank sensor only) 7.7.4
Discriminating Sensor
Sensor tested and functio 1.7.7 :ETAD TSET lan Sensor properly mounted at the bottom of the containment sump or pan (containment sump or pan sensor only) 7.7.3
Sensor properly mounted at the bottom of double-walled tank (double-walled tank sensor only) 7.7.4
Hydrostatic Sensor
Sensor tested and functio 1.7.7 :ETAD TSET lan
5.7.7 denoitisop ylreporp rosnes citatsordyH
Vacuum/Pressure Sensor
Sensor tested and functio 1.7.7 :ETAD TSET lan
Alarm sounds when pressure or vacuum is released TEST DATE: 7.7.2 Entire interstitial space under pressure or vacuum (closed double-walled piping system only) TEST DATE: 7.7.7
Visually Monitored
Double-Walled Sump
Leak detection device is withi 6.7.7 stimil dednemmocer n
Dispenser Pan Float Mechanism
Sensor tested and functio 1.7.7 :ETAD TSET lan Dispenser pan float mechanism free to move and properly adjusted TEST DATE: 7.7.8
APPENDIX A-2: SAMPLE FORM FOR ANNUAL LEAK DEVICE INSPECTION CHECKLIST
___ fo ___ egaP tsilkcehC noitcepsnI PTS launnA 009 PR IEP
ID#: ANNUAL STP INSPECTION CHECKLIST Date:
Category Description PEI/RP900 N/A Tank 1 Tank 2 Tank 3 Tank 4
Submersible Turbine Pump (STP)
All STP
1.6.7 gnikael fo sngis on wohs sgnittif dna gnipip elbisiV
Piping in good condition 7.6.2
3.6.7 tneserp ton noisorroc evissecxE
5.6.7 sirbed dna hsart fo eerf pmuS
Junction box(es) have covers, not corroded; conduit and intrinsically safe wiring in good condition 7.6.8
Flexible connectors not frayed, twisted, kinked or bent beyond manufacturer specifications 7.6.9 Mechanical line leak detector properly vented, vent tube not kinked or twisted, vent tube fittings intact and tightened 7.6.10
Mechanical line leak detector passes 3.0 gallons per hour (gph) test TEST DATE: 7.6.11
Electronic line leak detector (ELLD) passes 3.0 gph test TEST DATE: 7.6.12
ELLD passes 0.2 gph test TEST DATE: 7.6.13
ELLD passes 0.1 gph test TEST DATE: 7.6.14 Manhole cover at grade in good condition, does not touch sump cover, all bolts present, handles and lift mechanism in good condition (as applicable) 7.6.24
STP: No Containment
Sump
Submersible pump head, flex connector(s) and other metallic product piping are not in contact with soil or water or are cathodically protected 7.6.17
STP: In Containment
Sump
4.6.7 ylreporp fo desopsid dna devomer tcudorp ro retaw ynA
Sump is free of cracks, holes, bul 6.6.7 stcefed rehto ro seg
7.6.7 deruces dna tcatni sgnittif noitarteneP
Piping interstitial space open to the STP sump (open double-walled piping system only) 7.6.20
Piping interstitial space closed to the STP sump (closed double-walled piping system only) 7.6.22
Sump lid, gasket and seals pres 32.6.7 noitidnoc doog ni dna tne STP: In
Single-Walled Containment
Sump
Single-walled sump tested for integrity every 3 years TEST DATE: 7.6.18
APPENDIX A-2: SAMPLE FORM FOR ANNUAL STP INSPECTION CHECKLIST – Page 1
Recom m ended Practices for the Inspection and M aintenance of UST System s
___ fo ___ egaP tsilkcehC noitcepsnI PTS launnA 009 PR IEP
Category Description PEI/RP900 N/A Tank 1 Tank 2 Tank 3 Tank 4
STP: In Double-Walled
Containment Sump
If not continuously monitored or inspected annually, double-walled sump tightness tested every 3 years TEST DATE: 7.6.19
APPENDIX A-2: SAMPLE FORM FOR ANNUAL STP INSPECTION CHECKLIST – Page 2
Recom m ended Practices for the Inspection and M aintenance of UST System s ___ fo ___ egaP tsilkcehC noitcepsnI launnA 009 PR IEP
ANNUAL UST SYSTEM INSPECTION CHECKLIST
Facility ID# Facility Name/Addre utangiS naicinhceT deifilauQ ss re Date
If any problem is found, contact: Contact information:
Category Description PEI/RP900 N/A Tank 1 Tank 2 Tank 3 Tank 4
Monthly Inspections
Complete monthly checklist and compare to previously completed monthly checklists 7.4.1
2.4.7 etauqeda dnuof dna deweiver snoitcepsni ylhtnoM
ATG Manhole 7.8
ATG Manhole
Cap in good condition, seals tightly, hole sealed where probe wire goes through 7.8.1
2.8.7 noitidnoc doog ni eriw dna delaes secilps eriW
Junction box has cover, not corroded; intrinsically safe wiring in good condition 7.8.3
No exposed wires 7.8.4 Probe and floats in good condition, both floats present and move freely (mag probe) TEST DATE: 7.8.5
Verify functionality of ATG p 6.8.7 :ETAD TSET ebor
7.8.7 noitidnoc doog ni revoc elohnaM
Adequate clearance between ATG grade-level cover and below-grade components 7.8.8
Fill Area 7.9
Drop Tube Drop tube extends to within 6 inches of the tank bottom (if no flow diffuser present) 7.9.1 Vapor Recovery
Adaptor Poppet of Stage I vapor recovery adaptor (also known as a “dry break”) moves freely, seals tightly 7.9.2
Single-Walled Spill Containment
Manhole
Single-walled spill containment manhole tightness tested within last 3 years TEST DATE: 7.9.3
Double-Walled Spill Containment
Manhole
Double-walled spill containment manhole tightness tested within last 3 years OR inspected monthly TEST DATE: 7.9.4
Overfill Prevention 7.10 Drop Tube
Shutoff (Flapper Valve)
Drop tube shutoff valve passes inspection EVALUATION DATE: 7.10.1.1
For drop tube shutoff valves in diesel tanks, excessive corrosion not present 7.10.1.2
APPENDIX A-2: SAMPLE FORM FOR ANNUAL UNDERGROUND STORAGE SYSTEM INSPECTION CHECKLIST – Page 1
___ fo ___ egaP tsilkcehC noitcepsnI launnA 009 PR IEP
Category Description PEI/RP900 N/A Tank 1 Tank 2 Tank 3 Tank 4
Ball Float Valve
1.2.01.7 detcepsni dna devomer eb nac taolf llaB
2.2.01.7 :ETAD NOITAULAVE noitcepsni sessap evlav taolf llaB
For ball float valves in diesel tanks, excessive corrosion not 3.2.01.7 tneserp
Overfill Alarm Overfill alarm pas ETAD NOITAULAVE noitcepsni ses : 7.10.3.1
Leak Detection 7.11
ATG Console
LAVE noitcepsni launna sessap GTA UATION DATE: 7.11.1.1
Console has no active warni 2.1.11.7 smrala ro sgn
Alarm history shows no recurri 3.1.11.7 smrala kael gn
Verify in-tank leak detection tests are being completed (if used for leak detection) 7.11.1.4 Verify correct set-up parameters for electronic line leak detector (if present) VERIFICATION DATE: 7.11.1.5
Verify piping leak detection tests are being completed (if used for leak detection) 7.11.1.6
Electronic Leak Detection Monitor Leak monitoring console is operational and has no active warnings or alarms 7.11.2.1
Line Tightness Testing
If pressurized piping has been tested in the last year, review the results and verify that the test passed TEST DATE: 7.11.3.1
If suction piping has been tested within the last 3 years, review the results and verify that the test passed TEST DATE: 7.11.3.2
ELLD has conducted a 0.1 gph test in the last year TEST DATE: 7.11.3.3
Under Pump Check Valve
(Suction Pump)
Below-grade piping operates at les 7 erusserp cirehpsomta naht s .11.4.1
Below-grade piping slopes contin .4.11.7 knat eht ot kcab ylsuou 2
There is only one check valve, and it is located as close as practicable to the suction pump 7.11.4.3
Tank Tightness Testing
1.5.11.7 ssel ro dlo sraey 01 si knaT If a tank test has been conducted within the last 5 years, review the results and verify that the test passed TEST DATE: 7.11.5.2
Statistical Inventory
Reconciliation
(SIR)
SIR results for the previous 1.6.11.7 "ssap" era shtnom 21
APPENDIX A-2: SAMPLE FORM FOR ANNUAL UNDERGROUND STORAGE SYSTEM INSPECTION CHECKLIST – Page 2
Recom m ended Practices for the Inspection and M aintenance of UST System s ___ fo ___ egaP tsilkcehC noitcepsnI launnA 009 PR IEP
Category Description PEI/RP900 N/A Tank 1 Tank 2 Tank 3 Tank 4
Continuous Soil Vapor Monitoring 1.7.11.7 :ETAD TSET detset ecived gnisneS
Continuous Ground-water Monitoring 1.8.11.7 :ETAD TSET detset ecived gnisneS
Corrosion Protection 7.12 Galvanic Cathodic
Protection
Verify that cathodic protection testing of all metallic components in contact with soil or water has been conducted within the past 3 years and the test passed
TEST DATE: 7.12.1.1
Impressed Current Cathodic
Protection
Verify that cathodic protection testing has been conducted within the past 3 years and the test passed TEST DATE: 7.12.2.1
No exposed wires 7.12.2.2
Tank Lining Lining inspected as required and in good condition TEST DATE: 7.12.3.1
Miscellaneous Inspection Items 7.13 Tank Pad &
Pavement Concrete or asphalt over or near tanks is level, no significant 1.1.31.7 skcarc
Stage II Liquid Collection Points Cap in good condition, fits tightly, little or no liquid in bot 1.2.31.7 mot
Stage I Testing Verify that Stage I testing has been conducted and test results are passing TEST DATE: 7.13.3.1
Stage II Testing Verify that Stage II testing has been conducted and test results are passing TEST DATE: 7.13.4.1
Site Diagram Site diagram accurately reflects the site conditio 1.5.31.7 sn
Instructions: Mark each tank where no problem is observed with a checkmark: √ If certain equipment is not required and / or not present, mark checklist in the N/A column. If a defect is found, mark the checklist with an “X,” describe the problem in the “DEFICIENCIES” section, and notify the appropriate person. Refer to the section listed in the “PEI/RP900” column for additional information. Refer to PEI RP500, Recommended Practices for Inspection and Maintenance of Motor Fuel Dispensing Equipment, for inspection procedures that apply to fuel dispensing equipment.
APPENDIX A-2 SAMPLE FORM FOR ANNUAL UNDERGROUND STORAGE SYSTEM INSPECTION CHECKLIST – Page 3
| Appendix A bfs4027 Form |
| appendix_a-1_Quarterly_ust_inspection_checklist rev1 |
| appendix_a-2_annual_dispenser_inspection_checklist |
| appendix_a-2_annual_fill_containment_sump_inspection_checklist |
| appendix_a-2_annual_leak_device_inspection_checklist |
| appendix_a-2_annual_stp_inspection_checklist |
| appendix_a-2_annual_ust_inspection_checklist |
File details come from the government source that posted it. Updated .