Appendix 3 Craig Flex Housing - Sprinkler Inspection 2022.pdf
PDF 388 KB Posted
- Attached to
- TNF Fire Sprinkler and Backflow Prevention Certification Federal contract opportunity
- Solicitation number
- 1240BF24Q0026
- Issued by
- Department of Agriculture Forest Service
About this file
This document is an Appendix 3 - Sprinkler Inspection Form for the Craig Flex Housing location for the USDA Forest Service Alaska Regional Office. The form details the results of an annual sprinkler system inspection conducted on September 29, 2022. The inspection identified several deficiencies, including a non-functional alarm water flow bell, a non-functional alarm dialer, lack of sprinkler coverage for outdoor areas and the fire escape stairs, and the system being improperly configured as a glycol system instead of a wet system. The document includes photographs and a list of the identified deficiencies that require corrective action to maintain compliance with state and local code requirements.
The related federal contract opportunity is for Fire Sprinkler and Backflow Prevention Certification on Forest Service Buildings/systems in Southeast Alaska, with a solicitation number of 1240BF24Q0026. The opportunity is being issued by the Department of Agriculture Forest Service.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Amend 4 1240BF24Q0026 extend quote due.pdf | ||
| Amend 3 1240BF24Q0026 craig flex photos.pdf | ||
| Amend 2 1240BF24Q0026 TNF Fire Sprinklers.pdf | ||
| amend 1 1240BF24Q0026.pdf | ||
| Attachment 3 Schedule of Items Amend1.xlsx | XLSX spreadsheet | |
| 1240BF24Q0026 TNF Fire Sprinkler Backflow.pdf | ||
| Attachment 1 PWS TNF Fire Sprinklers and Backflow Certification.pdf | ||
| Appendix 1 Facilities and Equipment - TNF Fire Sprinkler and Backflow Preventer Certification.xlsx | XLSX spreadsheet | |
| Attachment 3 Schedule of Items.xlsx | XLSX spreadsheet | |
| Appendix 2 Craig Flex Housing - Floor Plan.pdf | ||
| Attachment 2 WD SCA 2015-5685 R23 2024.07.22 TNF.pdf | ||
| Appendix 4 Craig Flex Housing - Sprinkler System Photos.pdf |
Show all 12
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Sprinkler Inspection Form
Sprinkler Inspection Form
System Status
1 2 3 4
Customer Name:
USDA Forest Service Alaska Regional Office Address 709 West 9th St. (Craig Bunkhouse) City St Zip Phone Juneau Ak 99802-1628 907-586-8806
Bldg Insp/ Bldg Rep:
Name & Phone #
Type of Service:
Craig Bunkhouse Annual Inspected By: Inspection Date:
Gregory Stevenson 09/29/2022 SOA Permit #: Monitoring Entity:
99-036
1 General-A. (To be answered by the Owner or Owner's representative) Yes No N/A
1. Have there been any changes in the occupancy classification since the last inspection ?
2. Have there been any repairs to the fire protection systems since the last inspection ?
3. If a fire has occurred since the last inspection, have all damaged sprinkler components been replaced ?
4. Have fire pumps been tested to their full capacity through use of hose streams or flow meters within the past 12 months?
5. Are gravity surface or pressure tanks protected from freezing?
6. Are any of the sprinklers 50 years old or older? (testing and/or replacement is recommended for such sprinklers)
7. Are any extra high temperature solder sprinklers regularly exposed to temperatures near 300°F?
Has the piping in all dry systems been checked for proper pitch within the past five years ?
Yes No N/A Unknown
Date piping in all dry systems checked for proper pitch
Has the piping in all systems been checked for obstructive materials?
Yes No N/A Unknown https://mydoforms.appspot.com/
Date piping in all systems checked for obstructive materials 09/29/2022
1 General-B. (To be answered by the inspector) Yes No N/A
1. Have the sprinkler systems been extended to all visible areas of the building?
2. Does there appear to be proper clearance between the top of all storage and the sprinkler deflector?
3. Are the building areas protected by a wet system, heated, including its blind attics and perimeter areas, where accessible?
4. Are all visible exterior openings protected against the entrance of cold air?
2. Control Valves Yes No
a. Are all sprinkler system main control valves and all other valves in the appropriate open or closed position?
b. Are all control valves sealed or supervised in the open position?
Control Valve
# of Valves Type Easily
Accessible Signs Valve Open Secured
(Sealed?)
(Locked?)
(Supvd.?)
Supervision Operational
Alarm Line
City Conn.
Pre Action
Pump Sectional System Dry
System Wet
2 OS&Y Yes Yes Yes No Sealed No
Tank
3. Water Supplies
a. Water Supply source?
City Gravity Tank Craig N/A
Pressure Fire Pump & Tank Pressure Fire Pump & City Pressure Fire Pump & Pond N/A Waterflow Test Results Made During This Inspection Pressure Fire Pump & Pond Na
Test Pipe Located Size Test Pipe
Static Press.
Before
Flow Pressure
Static Press.
After
Main Drain (wet) 1.0 70 65 70
4. Tanks, Pumps, Fire Dept. Connections
Yes No N/A
a. Do fire pumps, gravity, surface or pressure tanks appear in good external condition?
b. Are gravity, surface and pressure tanks at the proper pressure and/or levels?
c. Are fire dept. connections in satisfactory condition, couplings free, caps, or plugs in place and check valves tight?
d. Are fire dept. connections visible and accessible?
5. Wet Systems
a. No. of systems Make and Model 1 2” riser with flow switch
b. Have all antifreeze systems been tested and date tested?
d. The antifreeze test indicates protection to:
N/A
System # Location Temperature Farenheit
2 Na
Yes N/A No
e. Did alarm valves, waterflow alarm indicators and retards test satisfactorily?
6. DRY SYSTEMS
a. No of systems Make & Model Date last trip tested
Yes N/ A No
b. Is the air pressure and priming water levels normal?
c. Did the air compressor operate satisfactorily?
d. Were all low points drained during this inspection?
e. Did all quick opening devices operate satisfactorily?
f. Did all dry valves operate satisfactorily during this inspection?
g. Do dry valves appear to be protected from freezing?
h. Is the dry valve house heated?
7. SPECIAL SYSTEMS
a. No of special systems Make & Model Type Na
Yes No N/A
b. Were valves tested as required?
c. Did all heat responsive systems operate satisfactorily?
d. Did supervisory features operate during testing?
Heat response devices:
Type Type of Test Na
Auxiliary equipment:
No. Type Na
Location
Test results
8. ALARMS
Yes No N/A
a. Did the water motors and gong operate during testing?
b. Did the electric alarms operate during testing?
c. Did the supervisory alarms operate during testing?
9. SPRINKLERS - PIPING
Yes No N/A
a. Do sprinklers generally appear to be in good external condition?
b. Do sprinklers generally appear to be free of corrosion, paint, or loading and visible obstructions?
c. Are extra sprinklers available on the premises?
d. Does the exterior condition of piping, drain valves, check valves, hangers, pressure gauges, open sprinklers and and strainers appear to be satisfactory?
e. Does the hand hose on the sprinkler system appear to be in satisfactory condition?
10. EXPLANATION OF "NO" ANSWERS (for sections 1b thru 9)
SEE DEFICIENCIES LIST BELOW
11. ADJUSTMENTS OR CORRECTIONS MADE:
12. LIST CHANGES IN THE OCCUPANCY HAZARD OR FIRE PROTECTION EQUIPMENT, AS
ADVISED BY THE OWNER IN SECTION 1A:
13. INSPECTION AND SUGGESTED IMPROVEMENTS WERE DISCUSSED WITH THE
UNDERSIGNED OWNER OR OWNER'S REPRESENTATIVE?
14. SYSTEM LOCATIONS
Sprinkler riser is in boiler room
15. INSPECTORS TEST LOCATIONS
At riser
DEFICIENCIES
The following items need corrective action to maintain this system to be in compliance with state and local code requirement:
Alarm water flow bell did not function when tested, just vibrated Alarm dialer is non functional disconnected at panel No sprinkler coverage for the outside areas and fire escape stairs System is supposed to be a glycol system, no glycol is present, it should be just a wet system and glycol outside when piped in.
2020- bell rang when tested but very low Db.
2023- no bell no vibration
Photos
Image 1 Image 2 Image 3
Image 4 Image 5 Image 6
Sign Here Technician
Print Name Date Logan wild 09/29/2022
Powered by www.doForms.com https://mydoforms.appspot.com/imageViewer?blobKey=ag9zfm15ZG9mb3Jtcy1ocmRyFwsSCmJsb2Jfc3RvcmUYgICMoLH71QgM&blobName=9a856g853r3oft0$$05042018173344$$Published$$282$$P1$$P1.jpg https://mydoforms.appspot.com/imageViewer?blobKey=ag9zfm15ZG9mb3Jtcy1ocmRyFwsSCmJsb2Jfc3RvcmUYgID034GamQsM&blobName=9a856g853r3oft0$$05042018173344$$Published$$282$$S1$$S1.jpg https://www.doForms.com