This document outlines the requirements for a fire alarm system maintenance service solicitation. Key details include maintenance of fire alarm systems at Aviano and Ghedi Air Bases in Italy. Services required include maintenance of automatic fire detection systems, water-based suppression systems, commercial kitchen systems, chemical systems, clean agent systems, and smoke venting. The solicitation number is FA568220Q0004 and was issued on 27 February 2020 by the Department of the Air Force for United States Air Forces in Europe - Air Forces Africa. The attached performance work statement provides general requirements for the maintenance services.

View the file

Other files

Show all 21

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

APPENDIX A

FOR FIRE SYSTEMS

AT THE AVIANO & GHEDI (BRESCIA) AIR BASE, ITALY

2 Dec 2019

CONTENTS

SECTION TITLE

1 Automatic Fire Detection Systems, including Manual Stations, Monaco Transceivers, and Public Annunciators as Warning System

2 Water Based Fire Suppression Systems 3 Commercial Kitchen: Dry &Wet Suppression Systems on Hoods 4 Chemical Dry &Wet Suppression Systems 5 Clean Agent Extinguishing Systems 6 Smoke and Heat Venting 7 Ghedi Air Base Fire Systems

SECTION 1

Automatic Fire Detection Systems, Manual Stations, and Monaco Transceivers

Aviano Air Base

AREA “A-1”

1. Bldg. # 106 System consists of a NOTIFIER CFP 12-24 conventional FACP,1 additional power supply, 2 smoke detectors on ceiling, 20 smoke detectors above ceiling, 10 duct detectors above ceiling, total of 31 detectors placed over 3 meters, 20 repeaters, 1 switch, 11 manual stations,11 acoustic/optic warning devices and 4 alarm bells. MONACO BT-X transmitter

2. Bldg. # 110 System consists of a BENTEL J-424 conventional FACP, 42 heat detectors, 5 heat detectors water-proof, 3 smoke detectors on ceiling, 45 smoke detector above ceiling, total of 45 detectors placed over 3 meters, 1 switch, 6 manual stations and 9 siren/strobe lights. MONACO BT-X transmitter.

3. Bldg. # 113 System consists of NOTIFIER AM-1000 addressable FACP, 3 heat detectors place over 6 meters, 2 manual pull stations, 2 optic/acoustic warning panels, and 1 output module to shut gas solenoid valve in case of ALR activation; sprinkler system is connected to FACP with 6 input modules for 2 tamper switches, 1 flow switch, 1 pressure switch, and 2 temperature supervisor. MONACO BT-X transmitter.

4. Bldg. # 116 System consists of a NOTIFIER AFP-200 addressable FACP, 1 remote panel LCD80, 2 additional power supply, 8 smoke detectors, 34 smoke detectors above ceiling, 4 duct smoke detectors, total of 31 detectors placed over 3 meters, 31 repeaters, 5 input modules, 10 output modules, 5 magnetic door holders, 19 manual stations, 50 siren/strobe lights, 4 acoustic/optic water-proof warning devices. MONACO BT-X transmitter.

5. Bldg. # 147 System consists of a NOTIFIER AM-2000 addressable FACP, 2 auxiliary power supply units, 1 remote panel, 29 smoke detectors on ceiling, 73 smoke detector above ceiling, 2 duct smoke detectors, 46 repeaters, 6 input modules, 9 output modules, 2 isolating modules, 4 manual stations and 8 siren/strobe lights.

Warning system throughout facility rely also on recorded warning messages from speakers controlled by P.A.

system (see description at end of Section). MONACO BT-X transmitter.

6. Bldg. # 149 System consists of a Notifier AM2000N addressable FACP, 1 auxiliary power supply unit FireClass

BXM24U50, 1 remote panel LCD6000N, 38 smoke detectors on ceiling, 32 smoke detectors above false ceiling, 1 duct smoke detector above false ceiling, 33 repeaters, total of 33 detectors placed over 3 meters, 11 manual station, 30 alarm strobe lights controlled by 1 output module, 1 input module monitoring 1 CO detector, 3 output modules controlling 3 door holders, 2 output modules controlling the elevator, 1 output module controlling the ventilation, 2 output modules activating 2 fire dampers, 2 input and 1 output modules controlling the MNS, 2 output and 9 input modules controlling the sprinkler system, 1 output module connected to the transmitter.

Warning system throughout facility rely also on recorded warning messages from speakers controlled by P.A.

system (see description at end of Section). MONACO BT-X transmitter

7. Bldg. # 170 System consists of a THERMOSTICK MAR-1 conventional FACP, 50 smoke detectors on ceiling, 7 duct smoke detectors above ceiling, total of 7 detectors placed over 3 meters, total of 6 detectors placed over 4 meters, 5 repeater, 7 switches, 20 manual stations, 20 siren/strobe lights, 6 acoustic/optic water-proof warning devices. MONACO BT-X transmitter. UNDER RENOVATION

8. Bldg. # 172 System consists of a THERMOSTICK MAR-1 conventional FACP, 43 heat detectors, 10 smoke detectors on ceiling, 30 smoke detectors above ceiling, 7 duct detectors above ceiling, total of 40 detectors placed over 3 meters, total of 6 detectors placed over 4 meters, total of 6 detectors placed over 6 meters, 30 repeaters, 11 switches, 20 manual stations and 15 siren/strobe lights and 1 alarm bell. MONACO BT-X transmitter.

UNDER RENOVATION

9. Bldg. # 175 System consists of a Notifier S-5000 conventional FACP, 20 heat detectors, 1 duct smoke detector, total of 4 detectors placed over 3 meters, total of 11 detectors placed over 4 meters, 3 switches, 4 manual stations,6 optic lights. MONACO BT-X transmitter.

10. Bldg. # 176 System consists of a Notifier AM2000N addressable FACP, 1 additional power supply, 30 heat detectors, 7 heat & smoke detectors (dual technology), 3 smoke detector on ceiling, 74 smoke detectors above ceiling, 3 duct smoke detectors, total of 11 detectors placed over 3 meters, total of 64 detectors placed over 4 meters, 77 repeaters, 3 input modules, 12 output modules, 8 manual stations, 10 switches, 1 optic warning device, and 14 optic/acoustic warning panels. MONACO BT-X transmitter.

11. Bldg. # 176-B System consists of Notifier AM2000N addressable FACP, 12 smoke detectors on ceiling, 11 heat/smoke detectors above ceiling, 11 led repeaters, 1 heat detector on ceiling, total of 12 devices placed over 3 meters, 3 manual pull stations, 1 switch, and 3 audio/visual warning panels. MONACO BT-X transmitter.

12. Bldg. # 178-11 System consists of Notifier conventional FACP, 8 smoke detectors, 5 manual stations and 6 optic/acoustic warning panels. MONACO BT-X transmitter.

13. Bldg. # 179 System consists of a Notifier AFP-400 addressable FACP, 1 remote panel LCD80, 1 additional power supply, 6 smoke detectors, 36 smoke detector above ceiling, 7 duct smoke detectors, total of 36 detectors placed over 4 meters, 36 repeaters, 5 input modules, 5 output modules, 17 manual stations, 4 optical warning devices, and 49 acoustic/optical warning devices. MONACO BT-X transmitter.

AREA “A-2”

14. Bldg. # 264 System consists of a NOTIFIER FireStar conventional FACP, 1 smoke detector on ceiling, 7 smoke detectors above ceiling, 7 repeaters, 1 switch, 3 manual stations and 5 bells. MONACO BT-X transmitter.

AREA “C”

15. Bldg. # 407 System consists of a Notifier AM2000N addressable FACP, 1 additional power supply, 24 heat detectors, 81 smoke detectors on ceiling, 64 smoke detectors above ceiling, 1 duct smoke detector, total of 64 detectors placed over 3 meters, total of 20 detectors placed over 6 meters, 64 repeaters, 30 modules, 1 damper, 20 manual stations and 28 optic/acoustic warning devices. MONACO BT-X transmitter.

16. Bldg. # 410 System consists of a THERMOSTICK MAR-1 conventional FACP, 42 heat detectors, 4 heat detectors waterproof, 2 smoke detectors on ceiling, 19 smoke detectors above ceiling, total of 5 detectors placed over 3 meters, total of 13 detectors placed over 4 meters, 19 repeaters, 11 switches, 15 manual stations and 13 sirens/strobe lights. MONACO BT-X transmitter.

17. Bldg. # 411 System consists of a NOTIFIER AM-2020 addressable FACP, 1 heat detector, 2 smoke detectors on ceiling, total 3 detectors placed over 4 meters, 3 output modules, 2 manual stations and 1 bell water-proof.

MONACO BT-X transmitter.

18. Bldg. # 416 System consists of a THERMOSTICK MAR-1 conventional FACP, 13 heat detectors, 5 smoke detectors on ceiling, 11 smoke detectors above ceiling, total of 18 detectors placed over 3 meters, total of 11 detectors placed over 4 meters, 11 repeaters, 8 manual station and 8 sirens/strobe lights. MONACO BT-X transmitter.

19. Bldg. # 421 System consists of a THERMOSTICK MAR-1 conventional FACP, 9 heat detectors, 1 heat detector waterproof, 3 smoke detectors above ceiling, total of 7 detectors placed over 3 meters, total of 2 detectors placed over 4 meters, 3 repeaters, 3 manual stations and 3 alarm bells. MONACO BT-X transmitter.

20. Bldg. # 422 System consists of a THERMOSTICK MAR-1A conventional FACP, 16 heat detectors, 1 smoke detector on ceiling, total of 16 detectors placed over 4 meters, 3 switches, 5 manual stations and 2 siren/strobe lights, 1 alarm bell. MONACO BT-X transmitter.

21. Bldg. # 424 System consists of a BENTEL J-408 conventional FACP, 10 heat detectors, 1 heat detectors waterproof, 8 smoke detectors above ceiling, 2 duct smoke detectors, total of 8 detectors placed over 4 meters, 9 repeaters, 2 air dampers, 1 switch, 3 manual stations and 3 alarm bells. MONACO BT-X transmitter

22. Bldg. # 428 System consist of a Notifier NFS4-2PLUS conventional FACP, 6 smoke detectors, 2 smoke detectors above ceiling, total of 2 detectors placed over 3 meters, 2 repeaters, 2 manual stations and 2 siren/strobe lights. MONACO BT-X transmitter.

23. Bldg. # 430-1 (Bay # 1) System consists of a NOTIFIER AM1000 addressable FACP, 1 auxiliary power supply unit, 24 heat detectors, 1 smoke detector, 2 smoke detectors under floating floor, 14 smoke detectors above false ceiling, 6 manual stations, 6 optic/acoustic warning devices controlled by 6 modules, 1 input module monitoring the auxiliary power supply unit, 1 switch controlled by 1 module. FACP is connected to MONACO BT-X transmitter in Bldg. # 430 fire system mechanical room West side of facility.

24. Bldg. # 430 (Bay # 2, # 3, # 4, & # 5) System consists of a THERMOSTICK MAR-1 conventional FACP, 6 heat detectors, 5 heat detectors waterproof, 19 smoke detectors on ceiling, 18 smoke detectors above ceiling, total of 18 detectors placed over 3 meters, total of 6 detectors placed over 4 meters, total of 4 detectors placed over 6 meters, 18 repeaters, 10 switches, 15 manual stations and 16 siren/strobe lights. MONACO BT-X

AREA “D”

25. Bldg. # 554 System consists of a BENTEL J424-8 conventional FACP, 16 heat detectors, 1 heat detector waterproof, 4 smoke detectors on ceiling, 11 smoke detectors above ceiling, 1 duct smoke detector, total of 20 detectors placed over 3 meters, total of 11 detectors placed over 4 meters, 11 repeaters, 4 manual stations, 1 manual station waterproof, 5 siren/strobe lights, 1 bell and 1 bell waterproof. MONACO BT-X transmitter.

AREA “E”

26. Bldg. # 600 System consists of a NOTIFIER S-500 conventional FACP, 114 heat detectors, 7 heat detectors waterproof, 16 smoke detectors on ceiling, 109 smoke detectors above ceiling, total of 103 detectors placed over 3 meters, 103 repeaters, 17 manual stations and 25 alarm bells. MONACO BT-X transmitter.

27. Bldg. # 604 System consists of a THERMOSTICK MAR-1 conventional FACP, 13 heat detectors, 2 heat detectors waterproof, 3 smoke detectors on ceiling, 11 smoke detectors above ceiling, total of 21 detectors placed over 3 meters, total of 8 detectors placed over 4 meters, 4 manual stations, 1 manual station waterproof, 3 siren/strobe lights, 1 bell and 1 bell waterproof. MONACO BT-X transmitter.

28. Bldg. # 606 System consists of a THERMOSTICK MAR-1/A conventional FACP, 25 heat detectors, 6 smoke detectors on ceiling, 19 smoke detectors above ceiling, total of 12 detectors placed over 3 meters, total of 5 detectors placed over 4 meters, 17 repeaters, 1 switch, 8 manual stations and 4 alarm bells. MONACO BT-X

29. Bldg. # 620 System consist of a Bentel J408 conventional FACP, 12 heat detectors, 1 smoke detector on ceiling, 6 smoke detectors above ceiling, total of 6 detectors placed over 3 meters, 6 repeaters, 1 switch, 5 manual stations and 2 alarm bells. MONACO BT-X transmitter.

30. Bldg. # 623 System consists of NOTIFIER AM-2000 addressable FACP, 1 auxiliary power supply unit Bentel BXM24U50, 14 heat detectors, 2 smoke detectors on ceiling, 4 smoke detectors above ceiling, 4 repeaters, 1 duct smoke detector, total of 4 detectors placed over 3 meters, 8 manual pull stations, and 8 optic/acoustic warning panels controlled by 8 modules, 1 input module monitoring the auxiliary power supply unit, 1 output module to send the signal to the Fire suppression control panel to actuate the extinguishing sequence. MONACO BT-X transmitter.

31. Bldg. # 624 System consists of a COE CLERICI conventional FACP, 4 heat detectors, 1 smoke detector on ceiling, 2 manual stations and 2 alarm bells. MONACO BT-X transmitter.

32. Bldg. # 627 System consists of a CERBERUS CZ-16 conventional FACP, 14 heat detectors, 7 smoke detectors above ceiling, 1 duct smoke detectors above ceiling, total of 8 detectors placed over 3 meters, 8 repeaters, 3 manual stations and 4 alarm bells. MONACO BT-X transmitter.

AREA “F”

33. Bldg. # 898 System consists of a NOTIFIER NFS4-2PLUS conventional FACP, 1 heat detector, 6 smoke detectors on ceiling, 3 smoke detectors above ceiling, total of 3 detectors placed over 3 meters, 3 repeaters, 3 manual stations and 2 optic/acoustic warning panels. MONACO BT-X transmitter.

34. Bldg. # 904 System consists of a THERMOSTICK MAR-1 conventional FACP, 101 heat detectors, 11 heat detectors waterproof, 1 smoke detector on ceiling, 68 smoke detectors above ceiling, total of 68 detectors placed over 3 meters, 68 repeaters, 18 manual stations and 18 alarm bells. MONACO BT-X transmitter.

35. Bldg. # 904-1 System consists of a THERMOSTICK MAR-1A conventional FACP, 16 heat detectors, 1 smoke detector on ceiling, total of 1 detector over 3 meters, total of 16 detectors placed over 4 meters, 3 switches, 5 manual stations and 5 siren/strobe lights. MONACO BT-X transmitter.

36. Bldg. # 904-2 System consists of a NOTIFIER AFP-200 addressable FACP, 20 heat detectors, 2 smoke detectors on ceiling, 11 smoke detectors above ceiling, 2 duct smoke detectors above ceiling, total of 13 detectors placed over 4 meters, 1 output module, 1 input module, 11 repeaters, 4 manual stations, 1 bell and 6 siren/strobe

37. Bldg. # 907 System consists of a THERMOSTICK MAR-1 conventional FACP, 34 heat detectors, 26 smoke detectors above ceiling, 3 duct smoke detectors, total of 26 detectors placed over 3 meters, 26 repeaters, 1 switch, 8 manual station, 11 siren/strobe lights and 2 alarm bells. MONACO BT-X transmitter.

38. Bldg. # 909 System consists of a NOTIFIER S-5000 conventional FACP, 2 smoke detectors on ceiling, 3 smoke detectors above ceiling, total of 3 detectors placed over 3 meters, 1 switch, 3 repeaters, 1 manual station and 2 siren/strobe lights. MONACO BT-X transmitter.

39. Bldg. # 910-9 System consists of a NOTIFIER AM4000 addressable FACP, 1 NOTIFIER LCD-6000 repeater, 1 NOTIFIER LCD-6000T, 1 NOTIFIER ALI-25EN auxiliary power supply device, 2 NOTIFIER UDS-3 controlling foam suppression systems, 4 heat detectors, 46 heat detectors explosion-proof, 59 smoke detectors, 18 smoke duct detectors, 9 smoke detectors above false ceiling, 9 repeaters, 2 methane gas detectors, 1 CO detector, 8 flame detectors explosion-proof, total of 16 detectors placed over 4 meters, total of 40 detectors installed over 6 meters, total of 44 detectors placed in the bays’ attics, 6 manual stations, 2 manual stations water-proof, 19 manual stations explosion-proof, 19 input modules monitoring the suppression system components, 1 input module monitoring the auxiliary power supply device, 6 releasing devices, 1 shut-off gas solenoid valve, 4 sirens water-proof with strobe lights, 4 sirens explosion-proof, and 4 strobe lights explosion-proof. MONACO BT-X transmitter. UNDER MAIN RENOVATION AND EXPANSION

40. Bldg. # 914 System consists of a NOTIFIER AM1000 addressable FACP, 3 heat detectors with water-protection, 6 heat detectors, 1 smoke detector on ceiling, 4 smoke detectors above ceiling, total of 6 detectors placed over 3 meters, total of 4 detectors placed over 4 meters, 4 repeaters, 4 manual stations and 4 siren/strobe

41. Bldg. # 916 System consists of a NOTIFIER SFP-400 conventional FACP, 4 heat detectors waterproof, 1 switch, 4 manual stations, 1 trouble bell and 7 siren/strobe lights. MONACO BT-X transmitter.

42. Bldg. # 916-01 System consists of Notifier AM1000 addressable FACP, 12 input modules monitoring fire pumps supervised valves, 1 optic/acoustic warning device water-proof. MONACO BT-X transmitter.

43. Bldg. # 919 System consists of a THERMOSTICK MAR-1 conventional FACP, 3 heat detectors, 12 smoke detectors on ceiling, 3 manual stations and 3 siren/strobe lights. MONACO BT-X transmitter.

44. Bldg. # 920 System consists of a THERMOSTICK MAR-1 conventional FACP, 3 heat detectors, 2 heat detectors water-proof, 3 smoke detectors above ceiling, total of 3 detectors placed over 3 meters, 3 repeaters, 2 manual stations and 2 alarm bells. MONACO BT-X transmitter.

45. Bldg. # 921 System consists of NOTIFIER AM2000N addressable FACP, 1 NOTIFIER UDS-3 fire suppression panel (managing DELUGE suppression systems), 1 NOTIFIER ALI-25EN auxiliary power supply device, 1 BENTER BXM24U50 power supply device, 56 heat detectors, 1 heat detector explosion-proof monitored by a module, 63 smoke detectors on ceiling in aircrafts servicing area, 18 smoke detectors above false ceiling, 9 duct smoke detectors, 18 repeaters, 3 linear (beam) smoke detectors, total of 27 detectors installed over 3 meters, total of 3 detectors installed over 6 meters, total of 63 detectors installed over 10 meters, 37 monitor modules, 22 output control modules (21 for warning devices, 1 for gas shut off valve, 2 for AHU shut down), 3 relay modules, 29 manual stations (7 for foam discharge), 30 door holders, 23 sirens with strobe lights, 7 optic/acoustic panels.

46. Bldg. # 925 System consists of NOTIFIER AM-2000 addressable FACP, 1 NOTIFIER UDS-3 fire suppression panel (managing DELUGE suppression systems), 3 BENTEL BXM24U50 auxiliary power supply devices, 90 heat detectors, 5 heat detectors explosion-proof, 27 smoke detectors, 5 duct smoke detectors, 21 smoke detectors above ceiling, 21 repeaters, total of 21 detectors installed over 3 meters, 90 detectors installed over 10 meters, 1 shut-off gas solenoid valve, 15 monitor modules, 2 relay modules for the sprinkler system, 3 relay modules controlling warning devices, 35 manual pull stations, (9 for foam discharge), 28 sirens with strobe light, 7 optic/acoustic panels, and 2 bells explosion-proof. MONACO BT-X transmitter.

47. Bldg. # 933 System consists of NOTIFIER AM4000 addressable FACP, 1 NOTIFIER UDS-3 fire suppression panel (managing DELUGE suppression systems), 3 BTE auxiliary power supply devices, 72 heat detectors, 6 smoke detectors, 3 duct smoke detectors, 56 smoke detectors above false ceiling, 59 repeaters, total of 59 detectors placed over 3 meters, total of 72 detectors placed over 10 meters, 1 module controlling the shut-off gas solenoid valve, 25 modules controlling the water based suppression system, 2 modules controlling the temperature probes, 4 modules controlling the warning devices, 1 module controlling the auxiliary power supply devices, 36 manual station (10 for foam discharge), 3 sirens23 sirens with strobe light, and 9 optic/acoustic panels. MONACO BT-X transmitter.

48. Bldg. # 933-A All devices are connected to the FACP of Bldg# 933. System consists of 20 heat detectors, 16 smoke detectors, total of 20 detectors installed over 4 meters, 4 manual stations and 4 optic/acoustic warning devices.

49. Bldg. # 933-B All devices are connected to the FACP of Bldg# 933. System consists of 35 smoke detectors, 19 smoke detectors above false ceiling, total of 11 detectors installed over 4 meters, total of 8 detectors installed over 4 meters, 19 repeaters, 6 manual stations and 8 optic/acoustic warning devices.

50. Bldg. # 933-C All devices are connected to the FACP of Bldg# 933. System consists of 7 smoke detectors, 3 manual stations and 3 optic/acoustic warning devices

51. Bldg. # 936 System consists of a THERMOSTICK MAR-1 conventional FACP, 11 heat detectors, 3 heat detectors waterproof, 7 smoke detectors above ceiling, 1 duct smoke detector, total of 8 detectors placed over 3 meters, 8 repeaters, 3 manual stations and 3 alarm bells. MONACO BT-X transmitter.

52. Bldg. # 939 System consists of a NOTIFIER AM-1000 addressable FACP, 26 heat detectors, 16 smoke detectors above ceiling, 1 duct smoke detector, total of 17 detectors placed over 3 meters, 17 repeaters, 3 control modules (2 for warning devices, 1 for MDP power tripping coil), 5 monitor modules (low battery on APSD, 3 air dampers position, extinguishing system on hood), 5 manual stations and 6 optic/acoustic warning devices.

MONACO BT-X transmitter. UNDER MAIN RENOVATION AND EXPANSION

53. Bldg. # 940 System consists of a NOTIFIER AM-2000 addressable FACP, 1 auxiliary power supply unit, 66 heat detectors, 2 smoke detector, 39 smoke detectors above ceiling, 39 repeaters, 8 manual stations, 12 acoustic/optic warning devices, 8 input modules, 1 output module, and total of 39 detectors placed over 3 meters.

54. Bldg. # 940-A System consists of a NOTIFIER AM-1000 addressable FACP, 1 auxiliary power supply unit, 27 heat detectors, 17 smoke detectors on ceiling, 2 duct smoke detectors above ceiling, total of 19 detectors placed over 3 meters, 19 repeaters, 1 input module, 4 output modules, 1 isolating module, 3 manual station, and 3 acoustic/optic warning devices. MONACO BT-X transmitter.

55. Bldg. # 940-03 System consists of a NOTIFIER S-5000 conventional FACP, 6 heat detectors, 6 smoke detectors, total of 12 detectors placed over 4 meters, 1 switch, 2 manual stations and 2 siren/strobe lights.

56. Bldg. # 941 ARMY Offices. System consists of a Bentel J-424 conventional FACP, 31 heat detectors, 3 heat detectors waterproof, 31 smoke detectors above ceiling, 2 duct smoke detectors above ceiling, total of 33 detectors placed over 3 meters, 31 repeaters, 1 switch, 6 manual stations and 7 alarm bells. MONACO BT-X

57. Bldg. # 944 System consists of a BENTEL J-408 conventional FACP, 5 heat detectors, 5 smoke detectors above ceiling, 1 duct smoke detector above ceiling, total of 3 detectors placed over 3 meters, total of 6 detectors placed over 4 meters, 6 repeaters, 1 switch, 2 manual stations and 2 bells. MONACO BT-X transmitter.

58. Bldg. # 945-04 Radio Station. System consists of Notifier AM-2000N addressable FACP, 3 heat detectors, 3 smoke detectors, 10 relay modules, 2 control modules (shutdown ventilation in EG shelter & mezzanine), 1 output module for warning devices, 4 manual pull stations, and 3 optic/acoustic warning devices. MONACO

59. Bldg. # 946 System consists of Notifier AM-2000N addressable FACP, 1 Notifier ALI-25EN auxiliary power supply device, 20 heat detectors, 9 smoke detectors on ceiling, 24 smoke detectors above ceiling, 4 duct smoke detectors, 1 linear (beam) smoke detector, total of 34 devices placed over 3 meters, total of 1 device placed over 4 meters, 25 led repeaters, 9 output modules controlling the warning devices, 1 input and 2 output modules for beam smoke detector functioning, 4 input modules for sprinkler system, 1 output module for release device, 14 manual pull stations, and 22 siren/strobe lights. MONACO BT-X transceiver.

60. Bldg. # 1000 System consists of NOTIFIER AM1000 addressable FACP, 1 auxiliary power supply unit, 12 heat detectors explosion-proof, 2 heat detectors, 1 smoke detector on ceiling, 1 heat & smoke detector, total of 12 detectors placed over 4 meters, 3 output control modules, 22 input modules, 3 manual stations explosion-proof, 2 manual stations, 3 explosion-proof bells, and 2 optic/acoustic warning panels. MONACO BT-X transceiver.

61. Bldg. # 1004 System consists of NOTIFIER AM1000 addressable FACP, 1 heat detector, 15 smoke detectors, 11 smoke detectors above ceiling, total of 9 detectors placed over 3 meters, 11 repeaters, 4 output modules controlling the warning devices, 2 spare input modules, 2 relay modules to transmit signals to Monaco unit, 8 manual stations and 5 optic/acoustic warning panels. MONACO BT-X transmitter.

62. Bldg. # 1010 System consists of a NOTIFIER CFP 12-24 conventional FACP, 25 smoke detectors, 2 smoke detectors above ceiling, 6 duct smoke detectors above ceiling, 8 repeaters, 25 manual stations, 7 bells, 14 acoustic/optical warning devices, 1 switch stops HVAC equipment, total of 8 detectors placed over 3 meters.

63. Bldg. # 1013 System consists of a FireClass J-408 conventional FACP, 4 heat detectors, 1 heat detectors waterproof, 4 smoke detectors above ceiling, total of 4 detectors placed over 3 meters, 1 repeater, 1 switch, 1 manual station and 1 alarm bell. MONACO BT-X transmitter.

64. Bldg. # 1014 System consist of a THERMOSTICK MAR-1 conventional FACP, 13 heat detectors, 1 heat detector waterproof, 15 smoke detectors above ceiling, total of 15 detectors placed over 3 meters, 15 repeaters, 3 switches, 5 manual stations 3 audio/visual warning devices and 1 alarm bells. MONACO BT-X transmitter.

65. Bldg. # 1015 System consists of a THERMOSTICK MAR-1 conventional FACP, 5 heat detectors, 1 manual station and 1 siren/strobe light. MONACO BT-X transmitter.

66. Bldg. # 1016-1 System consists of a BENTEL J-408 conventional FACP, 5 smoke detectors, 4 manual stations, 3 siren/strobe lights, 1 siren/strobe light water-proof, 1 switch leading warm air generator, closes motorized air dampers and stops ventilation, total of 5 detectors placed over 6 meters. MONACO BT-X transmitter.

67. Bldg. # 1023 System consists of a NOTIFIER AM2000N addressable FACP, 2 VENITEM TUL375 EN auxiliary power supply devices, 1 heat detector, 54 smoke detectors, 48 smoke detectors above false ceiling, 5 duct smoke detectors, total of 53 detectors placed over 3 meters, 48 repeaters, 13 manual stations, and 16 optic/acoustic warning devices. MONACO BT-X transmitter.

68. Bldg. # 1029 System consists of a NOTIFIER S-500 conventional FACP, 1 fire rated door, 7 manual stations and 8 alarm bells. Inside 1029 warehouse there are 8 groups of prefab offices. System activating devices are connected to main fire alarm panel and consist of 13 heat detectors, 2 smoke detectors, 12 manual stations and 12 alarm bells. MONACO BT-X transmitter.

69. Bldg. # 1029-3 System consists of BENTEL J-408-8 conventional FACP, 4 smoke detectors on ceiling, 1 manual station, and 1 audio/visual warning device. MONACO BT-X transmitter.

70. Bldg. # 1029-5 System consists of a THERMOSTICK MAR-1 conventional FACP, 14 heat detectors, 14 smoke detectors above ceiling, 1 duct smoke detector, total of 15 detectors placed over 3 meters, 15 repeaters, 2 switches, 4 manual stations and 2 alarm bells. MONACO BT-X transmitter.

71. Bldg. # 1029-6 System consists of a THERMOSTICK MAR-1A conventional FACP, 16 heat detectors, 1 smoke detector on ceiling, total of 1 detector over 3 meters, total of 16 detectors placed over 4 meters, 3 switches, 5 manual stations and 5 siren/strobe lights. MONACO BT-X transmitter.

72. Bldg. # 1032 System consists of a THERMOSTICK MAR-1 conventional FACP with 3 GDU modules for gas detectors (for irritant vapors), 7 heat detectors, 1 heat detector waterproof, 8 heat detectors explosion proof, 7 smoke detectors above ceiling, 1 duct smoke detectors explosion proof, total of 7 detectors placed over 3 meters, total of 14 detectors placed over 4 meters, 7 repeaters, 3 gas detectors (for irritant vapors), 3 fire doors in bay, 1 switch, 1 manual station, 3 manual stations explosion proof, 1 alarm bell, 2 siren/strobe lights, 3 visual advisors explosion proof and 3 sirens explosion proof. MONACO BT-X transmitter.

73. Bldg. # 1035 System consists of NOTIFIER AM2000N addressable FACP, 11 smoke detectors explosion proof, 7 manual stations explosion proof, one control module (fan shut down), 4 control modules for 4 optic/acoustic warning devices explosion proof and 1 external warning bell. MONACO BT-X transmitter.

74. Bldg. # 1036 Grounds Maintenance Warehouse. System consists of a NOTIFIER AM-1000 addressable FACP, 40 heat detectors, 11 smoke detectors, total of 40 detectors placed over 6 meters, 6 manual stations and 6 optic/acoustic warning panels. MONACO BT-X transmitter.

75. Bldg. # 1037 System consists of a Bentel J-408 conventional FACP, 18 heat detectors, 8 heat detectors waterproof, 2 smoke detectors on ceiling, 13 smoke detectors above ceiling, total of 9 detectors placed over 3 meters, total of 6 detectors placed over 4 meters, total of 6 detectors placed over 6 meters, 13 repeaters, 1 switch, 6 manual station, 2 alarm bells, and 6 siren/strobe lights. MONACO BT-X transmitter.

76. Bldg. # 1037-2 System consists of a THERMOSTICK MAR-1 conventional FACP, 9 heat detectors, 1 smoke detector, total of 9 detectors placed over 3 meters, 2 manual stations and 2 siren/strobe lights. MONACO BT- X transmitter.

77. Bldg. # 1046 System consists of a CERBERUS CZ-16 conventional FACP, 12 heat detectors, 3 smoke detectors on ceiling, 9 smoke detectors above ceiling, total of 9 detectors placed over 4 meters, total of 6 detectors placed over 6 meters, 9 repeaters, 1 switch, 6 manual stations and 5 alarm bells. MONACO BT-X transmitter.

78. Bldg. # 1046-1 System consists of a THERMOSTICK MAR-1 conventional FACP, 6 heat detectors, 1 heat detector waterproof, 3 heat detectors explosion-proof, 2 smoke detectors above ceiling, total of 2 detectors placed over 3 meters, total of 3 detectors placed over 6 meters, 2 repeaters, 6 switches, 3 manual stations, 3 manual stations explosion proof, 2 siren/strobe lights, and 1 alarm bell explosion proof. MONACO BT-X transmitter.

79. Bldg. # 1046-2 System consists of a FireClass J-408 conventional FACP, 9 smoke detectors on ceiling, 6 smoke detectors above ceiling, total of 6 detectors placed over 4 meters, 6 repeaters, 1 switch, 3 air dampers, 2 manual stations, 2 siren/strobe lights and 2 strobe lights. MONACO BT-X transmitter.

80. Bldg. # 1048 System consists of a NOTIFIER AM2000N addressable FACP, 1 heat detector, 1 heat detector explosion proof, 18 smoke detectors on ceiling, 16 smoke detectors above ceiling, total of 16 detectors placed over 3 meters, 16 repeaters, 1 gas detectors, 4 manual stations, 1 manual station explosion proof, 4 audio/visual warning devices, 1 audio/visual warning device explosion proof. MONACO BT-X transmitter.

81. Bldg. # 1053 System consists of a THERMOSTICK MAR-1 conventional FACP, 34 heat detectors, 2 heat detectors water proof, 6 smoke detectors on ceiling, total of 30 detectors placed over 8 meters, 7 manual stations, 3 optic/acoustic advisors and 1 alarm bell. MONACO BT-X transmitter.

82. Bldg. # 1063 System consists of a NOTIFIER AM1000 addressable FACP, 1 auxiliary power supply unit Bentel

BXM24U50, 14 input modules, 12 output modules, 1 external self-powered warning device, 1 yellow and 1 green light located outside the building reporting the system status. MONACO BT-X transmitter.

83. Bldg. # 1078 System consists of NOTIFIER AM-2000 addressable FACP, 2 panel repeaters NOTIFIER LCD-

6000, 3 NOTIFIER ALI-25A auxiliary power supply units, 3 smoke detectors on ceiling, 58 smoke detectors above ceiling, 4 duct smoke detectors, total of 65 detectors placed over 3 meters height, 60 repeaters, 21 control modules, 16 monitor modules, 24 manual pull stations, 5 horn/strobe light, and 53 strobe lights. Warning system throughout facility rely also on recorded warning messages from speakers controlled by P.A. system (see description at end of Section). MONACO BT-X transceiver.

84. Bldg. # 1078-1 System consists of NOTIFIER AM-2000 addressable FACP, 24 heat detectors placed over 6 meters height, 2 manual pull stations and 3 siren/strobe light. MONACO BT-X transceiver.

85. Bldg. # 1097 System consists of a THERMOSTICK MAR-1 conventional FACP, 12 heat detectors, 2 smoke detectors above ceiling, total of 2 detectors placed over 3 meters, total of 9 detectors placed over 6 meters, 2 repeaters, 3 switches, 3 manual stations, 1 alarm bell and 3 siren/strobe lights. MONACO BT-X transmitter.

86. Bldg. # 1099 System consists of one THERMOSTICK MAR-1 conventional FACP for the explosion-proof sensors and one COE CLERICI conventional FACP (4 zones), 6 heat detectors, 1 heat detectors waterproof, 13 heat detectors explosion proof, 1 smoke detector on ceiling, 2 smoke detectors above ceiling, 1 duct smoke detector, total of 2 detectors placed over 3 meters, total of 11 detectors placed over 4 meters, 2 repeaters, 2 flame detectors explosion proof, 1 switch, 2 manual stations, 2 manual stations explosion proof, 1 siren/strobe light, 2 alarm bells, 1 alarm bell explosion proof, 2 horns explosion proof, and 2 strobe lights explosion proof.

87. Bldg. # 1100 System consists of a NOTIFIER AM-2000 addressable FACP, 27 heat detectors, 2 smoke detectors on ceiling, 20 smoke detectors above ceiling, total of 20 detectors placed over 3 meters, 20 repeaters, 1 control module (tripping gas solenoid valve), 5 manual pull stations, and 4 control modules for 4 optic/acoustic warning devices. MONACO BT-X transmitter. .

88. Bldg. # 1121 System Consists of NOTIFIER AM-1000 addressable FACP, 4 heat detectors, 3 input modules

(from UDSs), 1 output module (shut-off AHU), 1 manual pull station, and 1 optic/acoustic warning panel.

System provided with MONACO BT-X transceiver.

89. Bldg. # 1122-5 System consists of NOTIFIER AM-4000 addressable FACP, 1 NOTIFIER AL24EN auxiliary power supply device, 1 heat detector, 56 smoke detectors on ceiling, 19 smoke detectors above ceiling, total of 12 detectors placed over 6 meters, total of 19 detectors placed over 3 meters, 19 repeaters, 8 input modules, 8 output modules, 12 magnetic door holders, 13 manual pull stations, 1 optic/acoustic warning device water-proof, and 17 optic/acoustic warning devices. MONACO BT-X transmitter.

90. Bldg. # 1131 System consists of a NOTIFIER AM-1000 addressable FACP, 9 heat detectors, 6 smoke detectors above ceiling, total of 6 detectors placed over 3 meters, 6 repeaters, 3 manual stations and 3 alarm bells.

91. Bldg. # 1133 Offices. System consists of a NOTIFIER AM-1000 addressable FACP, 32 heat detectors, 1 heat detector waterproof, 11 smoke detectors above ceiling, 7 smoke detectors water-proof above ceiling, 1 duct smoke detector, total of 19 detectors placed over 3 meters, 19 repeaters, 15 manual stations, and 8 alarm bells.

92. Bldg. # 1134-1 System consists of NOTIFIER S-5000 conventional FACP, 4 smoke detectors on ceiling, 1 manual station, and 1 audio/visual warning device. MONACO BT-X transceiver.

93. Bldg. # 1135 System consists of a NOTIFIER AM-2000 addressable FACP, 22 heat detectors, 16 smoke detectors above ceiling, total of 16 detectors placed over 3 meters, 16 repeaters, 1 control module (AHU shutdown), 9 manual stations, and 2 control modules for 9 optic/acoustic warning devices. MONACO BT-X

94. Bldg. # 1140 System consists of a THERMOSTICK MAR-1 conventional FACP, 4 heat detectors, 3 smoke detectors above ceiling, 1 duct smoke detector, total of 3 detectors placed over 3 meters, 3 repeaters, 2 switches, 2 manual stations and 2 bells. MONACO BT-X transmitter.

95. Bldg. # 1163 System consists of a NOTIFIER S-5000 conventional FACP, 2 smoke detectors on ceiling, 2 duct smoke detectors, total of 2 detectors placed over 6 meters, 10 manual stations and 14 siren/strobe lights.

96. Bldg. # 1173 System consists of NOTIFIER AM-2000 addressable FACP, 3 NOTIFIER mod. TUL375 auxiliary power supply unit, 1 NOTIFIER LCD-6000 panel repeater, 18 heat detectors, 32 smoke detectors on ceiling, 108 smoke detectors above ceiling, 2 duct smoke detectors, 3 duct smoke detectors above ceiling, total of 111 placed over 3 meters, 111 repeaters, 4 input modules, 10 output modules, 29 manual pull stations, and 29 siren/strobe lights. MONATO BT-X transceiver.

97. Bldg. # 1174 System consists of NOTIFIER AM-2000 addressable FACP, 2 heat detectors, 15 smoke detectors on ceiling, 13 smoke detectors above ceiling, 2 duct smoke detectors, total of 13 detectors placed over 3 meters, 13 repeaters, 11 input modules, 2 input modules not programmed, 10 output modules, 9 manual pull stations, 11 siren/strobe lights, and 8 strobe lights. Warning system throughout facility rely also on recorded warning messages from speakers controlled by P.A. system (see description at end of Section). MONACO BT-X transceiver.

98. Bldg. # 1175 System consists of NOTIFIER AM6000N addressable FACP, 1 remote annunciator LCD6000N, 3 auxiliary power supply units, 44 laser smoke detectors on ceiling, 32 smoke detectors on ceiling, 69 smoke detectors above false ceiling, 37 smoke detectors under floating floor, 1 duct smoke detector, 71 repeaters, 17 input modules monitoring the sprinkler system, 3 output modules managing the signals for hydrogen hazard7 output modules, 6 input modules, 6 manual stations, 53 strobe lights, 1 audio/visual warning device for hydrogen hazard. Warning system throughout facility rely also on recorded warning messages from speakers controlled by P.A. system (see description at end of Section). MONACO BT-X transmitter

99. Bldg. # 1204 System consists of NOTIFIER AM-2000N addressable FACP, 1 panel repeater LCXD-6000, 4 auxiliary power supply units, 1 heat detector, 5 smoke detectors above ceiling, total of 5 detectors place over 3 meters, 4 duct smoke detectors, 9 repeaters, 4 fire rated air dampers, 14 input modules, 6 output modules, 9 manual pull stations, and 16 siren/strobe lights. MONACO BT-X transceiver.

100. Bldg. # 1204-3 System consists of NOTIFIER AM-1000 addressable FACP, 6 smoke detector on ceiling, 3 manual pull station, 4 siren/strobe lights warning devices, and total of 22 modules (2 NC relay modules, 8 monitor modules, 12 input modules). MONACO BT-X transceiver.

101. Bldg. # 1226 System consists of a CERBERUS CZ-16 conventional FACP, 14 heat detectors, 2 heat detectors water-proof, 14 smoke detectors above ceiling, 1 duct smoke detector, total of 14 detectors placed over 3 meters, 14 repeaters, 3 air dampers, 2 switches, 5 manual stations and 4 alarm bells. MONACO BT-X transmitter.

102. Bldg. # 1227 System consists of a NOTIFIER AM-1000 addressable FACP, 18 heat detectors, 4 smoke detectors on ceiling, 2 smoke detectors above ceiling, 2 repeaters, 5 manual stations, 2 acoustic/optical warning devices, 2 input modules, 1 output module, total of 18 detectors placed over 4 meters. MONACO BT-X

103. Bldg. # 1229 System consists of NOTIFIER AM-2000N addressable FACP, 1 auxiliary power supply unit, 1

NOTIFIER LCD-6000T in boiler room used as “Gas Leak Control Panel”, 1 heat detector, 4 input modules, 3 output modules, 1 gas detector, 1 solenoid valve on gas line, 1 manual pull station, 9 siren/strobe light, 1 siren/strobe light water-proof, and 1 red colored siren/strobe lights water proof for gas leak system activation.

MONACO BT-X transceiver.

104. Bldg. # 1230 System consists of NOTIFIER AM-2000 addressable FACP, 42 heat detectors, 35 smoke detectors above ceiling, total of 35 detectors placed over 3 meters, 35 repeaters, 9 manual stations and 8 siren/strobe lights.

Fire detection system in Bldg. 1230 (old offices in North/West side) was not renovated and existing conventional fire alarm system has been connected to above mentioned panel using 4 input modules (old zones), 1 output module (old warning devices), and consists of 1 heat detector water-proof, 26 heat detectors, 26 smoke detectors above ceiling, total of 26 detectors placed over 3 meters, 26 repeaters, 8 manual stations, 1 siren/strobe light and 4 bells. MONACO BT-X transmitter.

105. Bldg. # 1234 System consists of a BENTEL J-408-8 conventional FACP, 1 heat detector water-proof, 3 heat detectors explosion-proof, 1 smoke detector on ceiling, total of 5 detectors placed over 3 meters, 1 manual station, 3 manual stations explosion-proof, 1 alarm bell and 3 alarm bells explosion-proof. MONACO BT-X transmitter.

106. Bldg. # 1235 System consists of NOTIFIER AM2000N addressable FACP, 1 conventional heat detector waterproof (IP-54), 4 smoke detectors on ceiling, 11 Omni (heat & smoke) detectors on ceiling, 8 smoke detectors above ceiling, 8 led and buzzer repeaters, 1 duct smoke detector, 3 isolating modules, 1 input module (OS&Y valve), 1 input module (conventional waterproof IP-54 heat detector), 3 output modules (warning devices circuits), 1 synchronization module (warning devices), total of 19 devices placed over 3 meters, 7 manual pull stations, 3 manual pull stations water-proof (IP-54), 9 audio/visual warning devices and 1 audio/visual warning devices waterproof (IP-54). MONACO BT-X transceiver.

107. Bldg. # 1236 All devices are connected to the FACP of Bldg# 1235. System consists of 1 heat detector, 1 manual station water-proof (IP-54) and one external audio/visual warning device waterproof (IP-54).

108. Bldg. # 1237 System consists of BENTEL mod. J-424 conventional FACP, 1 auxiliary power supply device, 2 heat detectors water-proof, 1 heat detector explosion-proof, 3 heat detectors, 12 smoke detectors on ceiling, 52 smoke detectors above ceiling, 52 repeaters, 3 duct smoke detectors, 4 duct smoke detectors above ceiling, total of 56 detectors placed over 3 meters, 2 switch for pre-action sprinkler system, 2 switches on MEP electric panel, 19 manual pull stations, 1 optic/acoustic warning panel water-proof, and 16 optic/acoustic warning panels.

109. Bldg. # 1243 System consists of a THERMOSTICK MAR-1 conventional FACP, 8 heat detectors, 4 smoke detectors on ceiling, total of 12 detectors placed over 3 meters, 4 manual stations and 4 bells. MONACO BT-

110. Bldg. # 1270 System consists of a NOTIFIER AM-1000 addressable FACP, 1 heat detector, 24 smoke detectors on ceiling, 16 smoke detectors above ceiling, total of 7 detectors placed over 4 meters, 5 control modules (for optic/acoustic warning devices), 2 rele’ modules (electric switches), 5 input modules (for tampers, flow & pressure switches), 13 manual stations, and 5 optic/acoustic warning devices. MONACO BT-X transmitter.

111. Bldg. # 1302 Automatic detection system consists of NOTIFIER AM-2000N addressable FACP, 1 auxiliary power supply unit, 26 smoke/heat detector on ceiling, 11 smoke/heat detectors in the tunnel, 20 smoke/heat detectors above ceiling, 20 repeaters, 12 input modules, 20 output modules, 23 manual stations, and 14 acoustic/optical warning devices. MONACO BT-X transmitter.

112. Bldg. # 1305 System consists of a THERMOSTICK MAR-1 conventional FACP, 17 heat detectors, 5 smoke detectors on ceiling, total of 22 detectors placed over 3 meters, 6 manual stations, 2 siren/strobe lights and 3 bells. MONACO BT-X transmitter.

113. Bldg. # 1307 System consists of a NOTIFIER S-5000 conventional FACP, 17 smoke detectors on ceiling, 27 smoke detector above ceiling, 15 smoke detectors under floor, 2 duct smoke detectors, total of 44 detectors placed over 3 meters, 47 repeaters, 7 manual station, 8 siren/strobe lights and 5 strobe light. MONACO BT-X

114. Bldg. # 1325 System consists of a NOTIFIER AM-1000 addressable FACP, 12 heat detectors, 1 duct smoke detector, 4 manual stations, and 5 optic/acoustic warning panels. MONACO BT-X transmitter.

115. Bldg. # 1333 System consists of a CERBERUS CZ-16 conventional FACP, 14 heat detectors, 3 smoke detectors above ceiling, 1 duct smoke detector, total of 3 detectors placed over 3 meters, total of 3 detectors placed over 4 meters, 4 repeaters, 3 flame detectors, 1 air damper, 1 switch, 6 manual stations and 5 alarm bells. MONACO

116. Bldg. # 1334 System is 220 V and it consists of 2 manual stations water-proof, 2 alarm bells, no back-up system in case of power failure, without remote notification device (MONACO transmitter).

117. Bldg. # 1335 System consists of a NOTIFIER S-5000 conventional FACP, 1 heat detector water-proof, 2 smoke detectors on ceiling, 36 smoke detectors above ceiling, 1 duct smoke detector, total of 40 detectors placed over 4 meters, 39 repeaters, 2 switches, 6 manual stations and 8 alarm bells. MONACO BT-X transmitter.

118. Bldg. # 1338 System consists of a THERMOSTICK MAR-1 conventional FACP, 6 heat detectors, total of 6 detectors placed over 4 meters, 2 manual stations and 2 alarm bells. MONACO BT-X transmitter.

119. Bldg. # 1342 System consists of a NOTIFIER S-5000 conventional FACP, 1 heat detector waterproof, 1 smoke detector on ceiling, 31 smoke detectors above ceiling, 1 duct smoke detector above ceiling, total of 32 detectors placed over 4 meters, 2 switches, 6 manual stations, and 7 alarm bells. MONACO BT-X transmitter.

120. Bldg. # 1360-HQ System consists of a NOTIFIER AM-2000 addressable FACP, 76 heat detectors, 47 smoke detectors above ceiling, 2 duct smoke detectors, total of 47 detectors placed over 4 meters, 47 repeaters, 9 manual stations, and 1 control module for 7 optic/acoustic warning devices. MONACO BT-X transmitter.

121. Bldg. # 1360-CP System consists of a NOTIFIER AM-1000 addressable FACP, 21 heat detectors, total of 27 assorted smoke detectors (above ceiling, duct detectors, and under floating floor), 27 repeaters, 2 control modules

(AHU shutdown), 9 manual pull stations, and 3 control modules for 10 optic/acoustic warning devices. System is connected to MONACO BT-X transmitter at Bldg. 1360-HQ.

122. Bldg. # 1360-WT System consists of a THERMOSTICK MAR-1A conventional FACP, 23 heat detectors, 2 smoke detectors on ceiling, 23 smoke detectors above ceiling, total of 25 detectors placed over 3 meters, 23 repeaters, 1 switch, 6 manual stations and 8 siren/strobe lights. MONACO BT-X transmitter.

123. Bldg. # 1362 System consists of NOTIFIER AM-2000N addressable FACP, 12 heat detectors, 4 smoke detectors above ceiling, 2 smoke detectors under floor, 3 output/control modules (2 air dampers and 1 mechanical system shut-off switch), 4 manual pull stations, and 2 siren/strobe lights. FACP controls also inert gas suppression system using 3 input modules (2 micro-switches on doors and 1 magnetic door holder), 2 output/control modules (operating solenoid valve controlling extinguishing discharge), and 1 evacuation warning panel. Old conventional system is connected to new panel using 8 input modules. Old system (6 zones) consists of 12 heat detectors, 4 heat detectors water-proof, 2 smoke detectors on ceiling, 8 smoke detectors above ceiling, 1 duct smoke detector, total of 9 detectors placed over 3 meters, 9 repeaters, 4 manual stations, and 4 warning bells. MONACO BT-X transceiver.

124. Bldg. # 1379 System consists of a NOTIFIER S-5000 conventional FACP, 1 heat detector water-proof, 1 smoke detector on ceiling, 28 smoke detectors above ceiling, 1 duct smoke detectors above ceiling, total of 1 detector placed over 3 meters, total of 28 detectors placed over 4 meters, 1 switch, 4 manual stations and 4 alarm bells.

125. Bldg. # 1380 System consists of NOTIFIER AM-2020 addressable FACP, 2 smoke detectors, 19 smoke detectors above ceiling, 2 input module, 4 output modules, 19 repeaters, 1 switch, 14 manual stations, and 14 siren/strobe lights; beside external system modules there are also 3 input and 1 output module for conventional components installed in Bldg. # 1381. MONACO BT-X transmitter.

126. Bldg. # 1381 System has following conventional components: 11 heat detectors on ceiling, 10 heat detectors above ceiling, 4 repeaters, 3 manual stations, and 1 siren/strobe light. Conventional components are connected to addressable FACP located in Bldg. # 1380 by 3 input modules (for on ceiling, above ceiling, and manual stations) and 1 output module (activating warning devices).

127. Bldg. # 1380-7 System consists of a NOTIFIER AM-1000 addressable FACP, 3 heat detectors, 2 smoke detectors above ceiling, total of 2 detectors placed over 4 meters, 2 repeaters, 1 manual station, 1 optic/acoustic warning panel, and 1 optic/acoustic warning device water-proof. MONACO BT-X transmitter.

128. Bldg. # 1390-9 System consists of a NOTIFIER AM-1000 addressable FACP, 12 heat detectors, 1 heat detector fixed temperature 88oC with water protection, 2 smoke detectors on ceiling, 4 smoke detectors above ceiling, total of 13 detectors placed over 4 meters, 4 repeaters, 7 manual stations, 1 manual station water-proof, 4 siren/strobe light and 2 siren/strobe light water-proof. MONACO BT-X transmitter.

129. Bldg. # 1391 System consists of 1 NOTIFIER S-5000 conventional FACP, 2 smoke detectors on ceiling, 15 smoke detectors above ceiling, total of 15 detectors placed over 4 meters, 15 repeaters, 5 manual stations, 9 siren/strobe lights, and 2 strobe/lights. MONACO BT-X transmitter.

130. Bldg. # 1396 System consists of a THERMOSTICK MAR-1 conventional FACP, 5 heat detectors waterproof, 1 smoke detector on ceiling, 3 manual station and 3 alarm bells. MONACO BT-X transmitter.

131. Bldg. # 1403 System consists of a NOTIFIER AFP-400 addressable FACP, 1 synoptic panel, 2 heat detectors, 3 smoke detectors on ceiling, 120 smoke detectors above ceiling, 4 duct smoke detector, total of 120 detectors placed over 6 meters, 5 switches, 13 manual stations, 22 optic/acoustic advisors, and 8 strobe lights. MONACO

132. Bldg. # 1404 System consists of a NOTIFIER AFP-200 addressable FACP and a synoptic NOTIFIER LCD-

80, 4 smoke detectors on ceiling, 32 smoke detector above ceiling, 14 duct smoke detectors above ceiling, total of 17 detectors placed over 3 meters, total of 37 detectors placed over 4 meters, total of 49 detectors placed over

6 meters, 34 repeaters, 4 isolating modules, 4 input modules, 18 output modules, 2 gas solenoid valves, 2 magnetic fire door holders, 3 switches, 14 manual station, 20 siren/strobe lights and 8 strobe light. MONACO

133. Bldg. # 1405 System consists of a NOTIFIER AM-2020 addressable FACP, 2 smoke detectors on ceiling, 4 duct smoke detectors above ceiling, total of 2 detectors placed over 4 meters, total of 4 detectors placed over 6 meters, 4 repeaters, 1 isolating module, 3 input modules, 5 output modules, 2 air-dampers, 11 manual station, 1 siren, 20 siren/strobe lights and 4 strobe lights. MONACO BT-X transmitter.

134. Bldg. # 1407 System consists of a NOTIFIER AM-2000 addressable FACP, 1 remote panel repeater LCD6000, 1 auxiliary power supply unit, 21 smoke detectors on ceiling, 6 smoke detectors above ceiling, 1 duct smoke detector on ceiling, 2 duct smoke detectors above ceiling, total of 9 detectors placed over 6 meters, 8 repeaters, 3 input module, 2 output modules, 2 fire doors, 2 magnetic door holders, 5 manual station, 10 siren/strobe lights and 5 strobe lights. MONACO BT-X transmitter.

135. Bldg. # 1407-1 System…