This document is an installation and programming manual for the Linear AK-11 Digital Keyless Entry System, a robust access control device designed for various applications. The keypad features a cast aluminum enclosure with a tactile keypad, capable of storing up to 480 entry codes between 1-6 digits long, and can activate two relay outputs with different capacities (Relay #1 at 5 Amps and Relay #2 at 1 Amp).

The system offers extensive programmability, including options to configure door sense/inhibit inputs, forced entry and door ajar outputs, keypad lockout, and anti-passback functionality. It operates on 12-24 Volt AC or DC power, has two LED indicators for system status, an internal sounder, and can be mounted on pedestals or walls. Additional features include solid state outputs for signaling various conditions, a courtesy light, and the ability to program different activation modes for entry codes such as timed or toggled relay responses.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

AK-11

Digital Keyless Entry System

Installation and Programming Instructions

(760) 438-7000 USA & Canada (800) 421-1587 & (800) 392-0123

Toll Free FAX (800) 468-1340 www.linearcorp.com

PRINTERS INSTRUCTIONS:

INSTR,INSTL,AK-11,ACCESS - LINEAR P/N: 227975 A - INK: BLACK - MATERIAL: 20 LB. MEAD BOND - SIZE: 8.500” X 11.000” - SCALE: 1-1 - FOLDING: ALBUM-FOLD - BINDING: SADDLE-STITCH

CONTENTS

INTRODUCTION

Linear’s AK-11 is a digital keyless entry system designed for access control applications. The keypad is housed in a rugged cast aluminum enclosure that can be mounted to a pedestal or bolted directly to a wall. The die-cast keys have bright, easy-to-read yellow graphics.

Up to 480 entry codes, from 1 to 6 digits in length, can be programmed. They can activate either, or both, of the relay outputs. Relay #1 has a 5 Amp capacity. Relay #2 has a 1 Amp capacity.

Two LED indicators show the status of the entry system. The left LED lights red to indicate power, then turns green when access is granted. The right LED lights yellow when the keypad is in “lockout” condition (from too many incorrect code entries). The keypad’s courtesy light can be always off, always on or be programmed to illuminate from 1-4 minutes after any keypress (default 2 minutes). An internal sounder beeps when each key is pressed.

The DOOR SENSE/INHIBIT input can be used two ways. If programmed for “door sense”, a switch on the door detects forced entry or door ajar situations. If programmed for “inhibit”, the input can be wired to a “service” switch or automatic timer that will disable the Relay #1 when required.

The REQUEST-TO-ENTER input can be wired to a pushbutton or fire access keyswitch to provide codeless entry for authorized personnel. The “anti-passback” feature prevents using the same code twice before the programmed time elapses.

The ALARM SHUNT output activates when access is granted.

This output can be wired to shunt alarm contacts on the access door/gate to prevent triggering of an alarm when authorized access occurs.

Two solid state outputs, capable of switching 100 mA to common, are programmable to signal forced entry, door ajar, lockout, alarm circuit shunting, request-to-enter, and keypad active conditions.

The AK-11 is powered from a 12-24 Volt AC or DC source. Power can be obtained from the access device or a separate power supply. The EEPROM memory retains all entry codes and programming, even without power.

SPECIFICATIONS

MECHANICAL

Case dimensions: 4.00" W x 5.50" H x 3.00" D

ELECTRICAL

Voltage: 12-24 Volts AC or DC

Current: 10 mA typical, 150 mA maximum

Outputs: Relay #1 Form “C” 5 Amps @ 24 Volts maximum

Relay #2 Form “C” 1 Amp @ 24 Volts maximum

Solid state outputs (Outputs #3 & #4) Short-to-common 100 mA @ 24 VDC maximum

ENVIRONMENTAL

Temperature: -22°F to 149°F (-30°C to 65°C)

Humidity: 5% to 95% non-condensing

FEATURES

� KEYPAD PROGRAMMABLE

� 480 ENTRY CODE CAPACITY

� 1-6 DIGIT ENTRY CODE LENGTH

� 4 INDEPENDENT OUTPUTS (TIMED/TOGGLED)

� 4 INDEPENDENT TIMERS

� EACH ENTRY CODE CAN BE PROGRAMMED TO

ACTIVATE EITHER OR BOTH RELAYS

� RELAY CONTACTS ARE FORM “C” (N.O. & N.C)

� SOLID STATE OUTPUTS ARE OPEN COLLECTOR

(SWITCH-TO-COMMON)

� TWO LED INDICATORS

� COURTESY LAMP

� PIEZO SOUNDER

� TIMED ANTI-PASSBACK (LAST 3 VALID ENTRIES)

� KEYPAD LOCKOUT

� TACTILE KEY FEEL

� DOOR SENSE INPUT

� INHIBIT INPUT

� REQUEST-TO-ENTER INPUT

INTRODUCTION

SPECIFICATIONS

FEATURES

COMPONENT LOCATIONS

WIRING DIAGRAM

INSTALLATION

FACTORY DEFAULTS

BASIC PROGRAMMING

PROGRAMMING OPTIONS

AK-11 OPERATION

MANAGER’S ENTRY CODE LOG

LINEAR LIMITED WARRANTY

FCC NOTICE

COMPONENT LOCATIONS

WIRING DIAGRAM

TACTILE

KEYPAD

YELLOW

"LOCKOUT"

INDICATOR

RED/GREEN

POWER/ACCESS

INDICATOR

NIGHT

LIGHT

TERMINAL BLOCK J4

POWER AND INPUTS

KEYLOCK

TERMINAL

BLOCK J3

OUTPUTS

JUMPER JP1

REMOVE TO

REDUCE

BEEPER SOUND

JUMPER JP2

RESETS

MASTER CODE

Figure 1. Component Locations

J4

J3

POWER

INHIBIT

COMMON

REQUEST-TO-ENTER

EARTH GROUND

N.O.

COMMON

N.C.

OUTPUT #3

OUTPUT #4

N.O.

COMMON

N.C.

COMMON

GROUND

AK-11

GATE OPERATOR

INHIBIT

TIMER

AUXILIARY

POWER

OPEN

J4

J3

DOOR SENSE

COMMON

REQUEST-TO-ENTER

EARTH GROUND

N.O.

COMMON

N.C.

OUTPUT #3

OUTPUT #4

N.O.

COMMON

N.C.

COMMON

GROUND

AK-11

FIRE

ACCESS

ELECTRIC

DOOR

STRIKE

OPEN

DOOR SWITCH

ALARM CONTACT

OPTIONAL WIRING

REQUIRED WIRING

POWER

SUPPLY

RELAY #1

TO ALARM

SYSTEM

TO ALARM

SYSTEM

POWER

RELAY #2

RELAY #1

RELAY #2

TYPICAL DOOR INSTALLATION WIRINGTYPICAL GATE INSTALLATION WIRING

Figure 2. Wiring Diagram

INSTALLATION

To avoid damage to the unit from static discharges, connect the EARTH GROUND terminal to a good earth grounding point.

Suggested wiring size is 18 AWG for earth ground and power (up to 500 feet of 18 AWG wire can be run for power, use larger wire for longer runs). Use 22 AWG or larger (depending on the load) for all other connections.

� CAUTION: If the unit is AC powered, and one side of the power transformer secondary is connected to earth ground, connect the grounded side to the “-” power terminal of the unit.

Select a location for the keypad. For door access control installations, mount the keypad near the controlled door. For gate control installations, mount the keypad in clear view of the gate, but far enough from the gate so the user cannot touch the gate from the keypad.

� WARNING: TO AVOID SERIOUS INJURY OR DEATH, MAKE

SURE THAT THE UNIT IS FAR ENOUGH FROM THE GATE

SO THAT THE USER CANNOT TOUCH THE GATE WHILE

OPERATING THE KEYPAD. HOWEVER, THE GATE MUST

BE FULLY VISIBLE FROM THE KEYPAD.

Pedestal Mounting The AK-11 keypad can be mounted on a standard pedestal.

Use four security bolts and locking nuts to secure the keypad’s backplate to the pedestal (see Figure 3).

Wall Mounting The AK-11 keypad can be mounted directly to a wall or flat surface.

Use the appropriate fasteners to secure the keypad’s backplate to the mounting surface.

When mounting the keypad to a concrete wall, use concrete wedge anchors or molly anchors (see Figure 4).

PEDESTAL

MOUNT BACKPLATE WITH

SECURITY BOLTS AND LOCKNUTS

Figure 3. Pedestal Mounting Keypad Backplate

USE CONCRETE

WEDGE ANCHORS

OR MOLLY ANCHORS

WALL MOUNTING

Figure 4. Wall Mounting Keypad Backplate

Gate Control Route four wires between the gate and the keypad (two for power, two for control).

Connect the gate operator’s auxiliary or radio power output terminals to the keypads POWER input terminals (observe wiring polarity).

Connect the gate operator’s OPEN terminals to the keypad’s Relay #1 COMMON & N.O. terminals.

�NOTE: For operator wiring specifics, refer to the gate operator’s wiring diagram.

If a request-to-enter pushbutton or fire access keyswitch is going to be used, route two wires from the keypad to the normally open switch. Connect the wires to the normally open switch and to the keypad’s REQUEST-TO-ENTER and COMMON terminals.

If an inhibit switch or timer is going to be used, route two wires from the keypad to the inhibit switch or timer relay.

Connect the inhibit switch/timer terminals to the keypad’s INHIBIT and COMMON terminals.

�NOTE: If the INHIBIT input is going to be used, it must be programmed to select that input type. See the Programming Options section of this manual.

Door Control Install a low voltage electric door strike for unlocking the door.

Choose a location for the power supply or transformer.

Route two wires between the power supply and the keypad. Connect the power supply’s output terminals to the keypad’s POWER input terminals (observe wiring polarity).

Route two wires between the door strike and the keypad.

Connect one of the door strike wires to the keypad’s Relay #1 N.O. terminal. Connect the other door strike wire to the keypad’s POWER + terminal. Connect a wire between the keypad’s POWER - terminal and the Relay #1 COMMON terminal.

If a request-to-enter pushbutton or fire access keyswitch is going to be used, route two wires from the keypad to the normally open switch. Connect the wires to the normally open switch and to the keypad’s REQUEST-TO-ENTER and COMMON terminals.

To use the door sense feature to detect forced entry or door ajar conditions, install a normally closed door switch on the door and route two wires from the switch to the keypad. Connect the door switch to the keypad’s DOOR SENSE and COMMON terminals.

If an inhibit switch or timer is going to be used, route two wires from the switch or timer to the keypad. Connect the inhibit switch/timer terminals to the keypad’s INHIBIT and COMMON terminals.

�NOTE: Either door sense or inhibit can be used. Both features cannot be used at the same time.

AK-11

KEYPAD

FIRE

ACCESS

KEYSWITCH

2 WIRES FROM OPERATOR

FOR AK-11 POWER

GATE

OPERATOR

(BEHIND GATE)

2 WIRES FROM AK-11

TO TRIGGER GATE OPEN

2 WIRES FOR

REQUEST-TO-ENTER

Figure 5. Gate Installation

FROM

POWER

SUPPLY

DOOR

SENSE

SWITCH

ELECTRIC

DOOR

STRIKE

AK-11

KEYPAD

2 WIRES

FOR DOOR

STRIKE

2 WIRES

FOR DOOR

SENSE

2 WIRES

FOR

POWER

Figure 6. Door Installation

FACTORY DEFAULTS

MASTER PROGRAMMING CODE

ENTRY CODE LENGTH . . . . . . . . . . . . . . . . . . . . . . . . . . 4 DIGITS

REQUEST-TO-ENTER OUTPUT . . . . . . . . . . . . . . . . . . RELAY #1

ALARM SHUNT OUTPUT . . . . . . . . . . . . . . . . . . . . . . . . DISABLED

FORCED ENTRY OUTPUT . . . . . . . . . . . . . . . . . . . . . OUTPUT #3

DOOR AJAR OUTPUT . . . . . . . . . . . . . . . . . . . . . . . . . OUTPUT #4

RELAY #1 ON TIME . . . . . . . . . . . . . . . . . . . . . . . . . . 2 SECONDS

RELAY #2 ON TIME . . . . . . . . . . . . . . . . . . . . . . . . . . 2 SECONDS

SOLID STATE OUTPUT #3 ON TIME . . . . . . . . . . . . 2 SECONDS

SOLID STATE OUTPUT #4 ON TIME . . . . . . . . . . . . 2 SECONDS

DOOR SENSE/INHIBIT INPUT. . . . . . . . . . . . . . . . DOOR SENSE

KEYPAD LOCKOUT OUTPUT . . . . . . . . . . . . . . . . . . . . DISABLED

KEYPAD ACTIVE OUTPUT . . . . . . . . . . . . . . . . . . . . . . DISABLED

DOWNLIGHT ON-TIME. . . . . . . . . . . . . . . . . . . . . . . . . 2 MINUTES

BEEPER SOUNDS WHEN KEY PRESSED . . . . . . . . . . . . . . YES

BEEPER SOUNDS DURING RELAY #1 . . . . . . . . . . . . . . . . . . NO

BEEPER SOUNDS DURING RELAY #2 . . . . . . . . . . . . . . . . . . NO

BEEPER SOUNDS DURING OUTPUT #3. . . . . . . . . . . . . . . . . NO

BEEPER SOUNDS DURING OUTPUT #4. . . . . . . . . . . . . . . . . NO

KEYPAD LOCKOUT COUNT . . . . . 3 TRIES BEFORE LOCKOUT

ANTI-PASSBACK TIME . . . . . . . . . . . . . . . . NO ANTI-PASSBACK

BASIC PROGRAMMING

When the AK-11 is in programming mode, both LEDs will turn off until programming begins. After a programming option number is entered the yellow LED will blink. This indicates that the AK-11 is ready to accept the new programming data. After the new data entry is complete, the green LED will light while the data is being stored. The red LED will light if any programming data is entered incorrectly, and the command will have to be fully re-entered.

Entering Programming Mode The 6-digit Master Programming Code (default = 123456) is used to enter Programming Mode.

Press: # 9 # Master Code Master Code = the current 6-digit Master Programming Code

Exiting Programming Mode

Press: * * # The red LED will light when Programming Mode is exited.

�NOTE: The AK-11 will automatically exit Programming Mode after two minutes of inactivity.

Re-entering a Command After a Mistake If the red LED lights, indicating an incorrect entry, or a wrong key is pressed during programming, to clear the keypad and re-enter the command:

Press: * 9 #

Setting Entry Code Length Default: 4 digits

Press: 0 3 # Length # Length = 1 - 6 for entry code length

�NOTE: If the Entry Code Length is going to be changed from the factory default of four digits, make this change first, before programming any entry codes.

Adding a New Entry Code

Press: 0 1 # Code # Code # Action # Code = The new entry code: 1-999999, depending on code length Action = Relay output entry code will activate as follows:

1 = Relay #1, timed open 2 = Relay #2, timed open 3 = Both Relays, timed open 10 = Relay #1, toggled 20 = Relay #2, toggled 30 = Both Relays, toggled 12 = Relay #1 toggled; Relay #2, timed open 21 = Relay #1, timed open; Relay #2 toggled

The yellow LED will flash quickly while the AK-11 searches its memory for available space and duplicate entries. The green LED will light when the new code is stored.

If the new entry code chosen is already being used for another entry code, the red LED will light. A new unique code needs to be entered.

�NOTE: Leading zeros (zeros before the code number, i.e.

0001) do not need to be entered when programming a new entry code. The AK-11 will internally add any zeros to fill all digits determined by the entry code length setting. Leading zeros will have to be entered by the user when entering their code to gain access.

Erasing a Single Entry Code

Press: 0 2 # Code # Code # Code = The entry code to delete.

The yellow LED will flash quickly while the AK-11 searches its memory for the code to erase. The green LED will light when the code is erased.

Erasing All Entry Codes � WARNING: Performing this command will remove all entry codes from the memory.

Press: 9 7 # 0 0 0 0 0 0 # 0 0 0 0 0 0 # �NOTE: The green LED will light while the memory is being erased. This may take up to 15 seconds.

Changing the 6-Digit Master Programming Code

Press: 9 8 # Master Code # Master Code # Master Code = The new 6-digit Master Programming Code

New master code: _____________________

PROGRAMMING OPTIONS

Select Door Sense or Inhibit Input Default: Door Sense

The input on terminal block J4, terminal #3 can be programmed for DOOR SENSE or INHIBIT.

Press: 1 0 # Input# Input = 1 for Inhibit, = 0 for Door Sense

When programmed for DOOR SENSE, if an open condition on the input occurs before access is granted (with an entry code or with the request-to-enter input) a FORCED ENTRY output will occur. If an open condition remains 60 seconds after a relay activation for access, a DOOR AJAR output will occur.

When programmed for INHIBIT, a closed condition on the input will prevent relay #1 from activating when access is requested (with an entry code). This mode is typically used with an external timer to disable the access device at certain times.

Select Forced Entry Output Default: Output #3 Sets which output activates if the Door Sense input opens before access is granted. This output is not timed.

Press: 1 1 # Output # Output = Output to Activate (0-4)

1 = Relay #1 2 = Relay #2 3 = Output #3 4 = Output #4 0 = No Output

Select Door Ajar Output Default: Output #4 Sets which output activates if the Door Sense input stays open after access is granted. This output is not timed.

Press: 1 2 # Output # Output = Output to Activate (0-4)

1 = Relay #1 2 = Relay #2 3 = Output #3 4 = Output #4 0 = No Output

Select Keypad Lockout Output Default: No Output Sets which output activates when the keypad is “locked out” after too many incorrect entry code attempts. The lockout time is 60 seconds.

Press: 1 3 # Output # Output = Output to Activate (0-4)

1 = Relay #1 2 = Relay #2 3 = Output #3 4 = Output #4 0 = No Output

Select Keypad Active Output Default: No Output Sets which output activates when any keys are pressed. This output is timed.

Press: 1 4 # Output # Output = Output to Activate (0-4)

1 = Relay #1 2 = Relay #2 3 = Output #3 4 = Output #4 0 = No Output

Select Alarm Shunt Output Default: No Output Sets which output activates during the time access is granted. (Use this output to shunt alarm contacts attached to the access door.) This output may be timed or latched.

Press: 1 5 # Output # Output = Output to Activate (0-4)

1 = Relay #1 2 = Relay #2 3 = Output #3, 4 = Output #4 0 = No Output

Select Request-to-Enter Output Default: Relay #1 Sets which output activates when the Request-to-Enter input is grounded. This output remains activated for at least the length of time specif ied by the On-times for the relays or outputs. If the Request-to-Enter input continues to be grounded beyond the time specified by the On-times for the relays or outputs, the output will remain activated as long as the Request-to-Enter input remains grounded.

Press: 1 6 # Output # Output = Output to Activate (0-4)

1 = Relay #1 2 = Relay #2 3 = Output #3 4 = Output #4 0 = No Output

Relay #1 On-time Default: 2 Seconds Sets the length of time Relay #1 activates when triggered.

Press: 2 1 # Seconds # Seconds = Output time in seconds (0-60)

Relay #2 On-time Default: 2 Seconds Sets the length of time Relay #2 activates when triggered.

Press: 2 2 # Seconds # Seconds = Output time in seconds (0-60)

Solid-state Output #3 On-time Default: 2 Seconds Sets the length of time Output #3 activates when triggered.

Press: 2 3 # Seconds # Seconds = Output time in seconds (0-60) 99 = Toggle mode

Solid-state Output #4 On-time Default: 2 Seconds Sets the length of time Output #4 activates when triggered.

Press: 2 4 # Seconds # Seconds = Output time in seconds (0-60)

99 = Toggle mode

Set Downlight On-Time Default: 2 Minutes Sets the time duration that the downlight remains on after a key press.

Press: 2 5 # Duration # 0 = Always off 1 = 1 minute 2 = 2 minutes 3 = 3 minutes

4 = 4 minutes 99 = Always on

Beep Sounds on Keystrokes Default: Yes Selects whether or not the keypad beeps as each key is pressed.

Press: 4 0 # Sound # Sound = 1 for Yes = 0 for No

Beep Sounds During Relay #1 Default: No Selects whether or not the keypad beeps during Relay #1 activation.

Press: 4 1 # Sound # Sound = 1 for Yes = 0 for No

Beep Sounds During Relay #2 Default: No Selects whether or not the keypad beeps during Relay #2 activation.

Press: 4 2 # Sound # Sound = 1 for Yes = 0 for No

Beep Sounds During Output #3 Default: No Selects whether or not the keypad beeps during Output #3 activation.

Press: 4 3 # Sound # Sound = 1 for Yes

= 0 for No

Beep Sounds During Output #4 Default: No Selects whether or not the keypad beeps during Output #4 activation.

Press: 4 4 # Sound # Sound = 1 for Yes

= 0 for No

Keypad Lockout Count Default: 3 Tries Sets the number of incorrect entry code attempts allowed before the keypad “locks out”.

Press: 5 0 # Attempts # Attempts = Number of attempts before lockout (2-7)

Anti-passback Time Default: No Anti-passback Sets the length of time an entry code will not function after it is used.

Press: 5 1 # Minutes # Minutes = Time in Minutes (1-4)

0 = No Anti-passback

Master Reset � CAUTION: Performing a master reset will clear the entire memory of the AK-11 and return all programmable options to the factory default values. ALL ENTRY CODES WILL BE

ERASED.

STEP 1 Disconnect power from the keypad.

STEP 2 Press and hold down the * and # keys.

STEP 3 Apply power to the keypad, continue holding the keys down until the red LED starts flashing.

STEP 4 Release the keys. The red and yellow LEDs will remain lit until the process is complete, then the yellow LED will go out.

Resetting the Master Code STEP 1 Open the AK-11 case.

STEP 2 Locate jumper JP2. This jumper is used to reset the master code.

STEP 3 With power applied to the keypad, remove jumper JP2. The keypad will begin to beep, signaling that the code has been reset.

STEP 4 Replace jumper JP2.

THE MASTER PROGRAMMING CODE IS NOW 123456.

Solid State Outputs The two solid state outputs (Output #3 & Output #4) can be programmed to activate during various conditions. These outputs can be used to activate indicators or sounders. See Figure 7 for wiring examples using the solid state outputs.

Beeper Sound Level The keypad’s beeper can be set to low or high level.

If the keypad’s beeper is too loud for the keypad’s location, remove jumper JP1 (see Figure 8).

Locking Keypad After the installation is complete. Lock the keypad using the keylock (see Figure 9).

REMOVE JUMPER JP1 TO REDUCE

THE SOUND LEVEL OF THE BEEPER

Figure 8. Removing Beeper Jumper

HOOK KEYPAD

ONTO BACKPLATE

USE KEY TO

LOCK KEYPAD

Figure 9. Locking the Keypad Case

OUTPUT #3

OUTPUT #4

COMMON

GROUND

DC

POWER

SOURCE

LED LED

ELECTRONIC

BEEPER

EXAMPLE 1: OUTPUT #3 LIGHTS AN LED,

OUTPUT #4 LIGHTS AN LED AND SOUNDS A BEEPER

EXAMPLE 2: OUTPUT #3 LIGHTS A LAMP POWERED FROM AN EXTERNAL

SOURCE, OUTPUT #4 TRIGGERS A NORMALLY OPEN ALARM PANEL ZONE

OUTPUT #3

OUTPUT #4

EACH

OUTPUT

100 mA

MAXIMUM

ALARM PANEL

N.O. ZONE

COMMON

END-OF-LINE

RESISTOR

POWER

SOURCE

LOW VOLTAGE

LAMP

EACH

OUTPUT

100 mA

MAXIMUM

1K Ω @ 12 volts 2K Ω @ 24 volts

Figure 7. Using the Solid State Outputs

AK-11 OPERATION

� Users of the AK-11 have up to 40 seconds to key in their entry code.

� Up to eight seconds are allowed between each keystroke.

� All digits of the entry code must be entered. Example:

If the code is 0042, the user must enter “0 0 4 2”.

� If the wrong key is pressed, pressing the * key will reset the keypad. The correct code can then be re-entered.

� After a correct code is entered, the red LED will turn green and the programmed relay will activate for the programmed time.

� If the number of incorrect codes entered exceeds the keypad lockout count, the yellow LED will light, indicating that the keypad is locked out. The lockout will remain for one minute.

� After a valid code has been entered, it will be unusable until the anti-passback time expires.

USERS HAVE UP TO

40 SECONDS TO ENTER

THEIR COMPLETE CODE

PRESS STAR KEY TO

RESET KEYPAD IF THE

WRONG KEY IS PRESSED

RED LED TURNS

GREEN WHEN

ACCESS IS GRANTED

YELLOW LED WILL LIGHT

DURING KEYPAD LOCKOUT IF

TOO MANY INCORRECT CODES

ARE ENTERED

Figure 10. Operating AK-11

MANAGER’S ENTRY CODE LOG

NAME ADDRESS OR APARTMENT NUMBER ENTRY CODE RELAY NUMBER

◊ 1 Timed ◊ 2 Timed ◊ 1 Toggled ◊ 2 Toggled

◊ 1 Timed ◊ 2 Timed ◊ 1 Toggled ◊ 2 Toggled

◊ 1 Timed ◊ 2 Timed ◊ 1 Toggled ◊ 2 Toggled

◊ 1 Timed ◊ 2 Timed ◊ 1 Toggled ◊ 2 Toggled

◊ 1 Timed ◊ 2 Timed ◊ 1 Toggled ◊ 2 Toggled

◊ 1 Timed ◊ 2 Timed ◊ 1 Toggled ◊ 2 Toggled

◊ 1 Timed ◊ 2 Timed ◊ 1 Toggled ◊ 2 Toggled

◊ 1 Timed ◊ 2 Timed ◊ 1 Toggled ◊ 2 Toggled

◊ 1 Timed ◊ 2 Timed ◊ 1 Toggled ◊ 2 Toggled

◊ 1 Timed ◊ 2 Timed ◊ 1 Toggled ◊ 2 Toggled

◊ 1 Timed ◊ 2 Timed ◊ 1 Toggled ◊ 2 Toggled

◊ 1 Timed ◊ 2 Timed ◊ 1 Toggled ◊ 2 Toggled

◊ 1 Timed ◊ 2 Timed ◊ 1 Toggled ◊ 2 Toggled

◊ 1 Timed ◊ 2 Timed ◊ 1 Toggled ◊ 2 Toggled

◊ 1 Timed ◊ 2 Timed ◊ 1 Toggled ◊ 2 Toggled

◊ 1 Timed ◊ 2 Timed ◊ 1 Toggled ◊ 2 Toggled

◊ 1 Timed ◊ 2 Timed ◊ 1 Toggled ◊ 2 Toggled

◊ 1 Timed ◊ 2 Timed ◊ 1 Toggled ◊ 2 Toggled

◊ 1 Timed ◊ 2 Timed ◊ 1 Toggled ◊ 2 Toggled

LINEAR LIMITED WARRANTY

This Linear product is warranted against defects in material and workmanship for twenty-four (24) months. The Warranty Expiration Date is labeled on the product. This warranty extends only to wholesale customers who buy direct from Linear or through Linear’s normal distribution channels. Linear does not warrant this product to consumers. Consumers should inquire from their selling dealer as to the nature of the dealer’s warranty, if any. There are no obligations or liabilities on the part of Linear LLC for consequential damages arising out of or in connection with use or performance of this product or other indirect damages with respect to loss of property, revenue, or profit, or cost of removal, installation, or reinstallation. All implied warranties, including implied warranties for merchantability and implied warranties for fitness, are valid only until Warranty Expiration Date as labeled on the product. This Linear LLC Warranty is in lieu of all other warranties express or implied.

All products returned for warranty service require a Return Product Authorization Number (RPA#). Contact Linear Technical Services at 1-800-421-1587 for an RPA# and other important details.

FCC NOTICE

Changes or modifications not expressly described in this manual or approved by the manufacturer could void the user’s authority to operate the equipment.

This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures:

° Reorient or relocate the receiving antenna.

° Increase the separation between the equipment and receiver.

° Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.

° Consult the dealer or an experienced radio/TV technician for help.

Copyright © 2007 Linear LLC 227975 A