13100 - 1

PolyPhase Job #C03053 - Questa Ranger Station - November 4, 2003

SECTION 13100

LIGHTNING PROTECTION

PART 1 GENERAL

1.01SECTION INCLUDES
A.Air terminals and interconnecting conductors.
B.Grounding and bonding for lightning protection.
1.02REFERENCES
A.NFPA 780 - Standard for the Installation of Lightning Protection Systems; National Fire Protection Association; 2000.
B.UL 96 - Lightning Protection Components; Underwriters Laboratories Inc.; 1994.
C.UL 96A - Installation Requirements for Lightning Protection Systems; Underwriters Laboratories Inc.; 2001.
D.29 CFR 1910 and 29 CFR 1926
1.03SYSTEM DESCRIPTION
A.Lightning Protection System: Conductor system protecting the Office and Office/Shop Buildings consisting of air terminals on roofs; bonding of structure and other metal objects; grounding electrodes; and interconnecting conductors.
1.04SUBMITTALS
A.See Section 01300 - Administrative Requirements, for submittal procedures.
B.Shop Drawings: Indicate layout of air terminals, grounding electrodes, and bonding connections to structure and other metal objects. Include terminal, electrode, and conductor sizes, and connection and termination details.
C.Product Data: Provide dimensions and materials of each component, and include indication of testing agency listing.
D.Manufacturer's Certificate: Certify that products meet or exceed specified requirements.
E.Project Record Documents: Record actual locations of air terminals, grounding electrodes, bonding connections, and routing of system conductors in project record documents.
1.05QUALITY ASSURANCE
A.Perform Work in accordance with NFPA 780 and UL 96A and provide UL Master Label.
B.Maintain one copy of each document on site.
C.Products: Furnish products listed and classified by testing agency acceptable to authority having jurisdiction as complying with UL 96.
D.Manufacturer Qualifications: Company specializing in lightning protection equipment with minimum three years documented experience.
E.Installer Qualifications: Authorized installer of manufacturer with minimum three years documented experience.
1.06PRE-INSTALLATION MEETING
A.Convene one week after notification to proceed.
1.Coordinate this work with building foundation and roof work to insure preparations necessary for thru-roof penetrations, concealed down conductors, and the counterpoise loop are completed.

PART 2 PRODUCTS

2.01MANUFACTURERS
A.Lightning Protection:
1.Harger Lightning and Grounding: www.harger.com.
2.National Lightning Protection Corporation: www.theprotectionsource.com.
3.East Coast Lightning Products.
4.Substitutions: See Section 01600 - Product Requirements.
2.02COMPONENTS
A.Air Terminals: Copper, solid, thru-roof type, impalement protected..
B.Ground Plate: Copper, sized as indicated on the drawings.
C.Conductors: Copper cable.
1.Size:
a.Loop Conductors, Underground Counterpoise: #1/0 minimum, Class I type, constructed as required by NFPA 780, Table 3.1.1(a).
b.Loop conductors, Roof mains: #1/0 minimum, Class I type, constructed as required by NFPA 780, Table 3.1.1(a).
c.Down conductors: #1/0 minimum, Class I type, constructed as required by NFPA 780, Table 3.1.1(a).
d.Bonding conductors: #4 AWG minimum, Class I type, constructed as required by NFPA 780, Table 3.1.1(a).
D.Connectors and Splicers: Bronze.
E.Verify the materials which will come into contact with the lightning protection system to insure deterioration of the system will not occur due to galvanic reaction.

PART 3 EXECUTION

3.01EXAMINATION
A.Verify that field measurements are as indicated on shop drawings.
B.Coordinate work with roofing and exterior and interior finish installations.
C.Coordinate installation of the counterpoise loop with other underground structures around the building footings.
D.Coordinate the installation of the system with the roofing contractor to insure the lightning protection system installation methods will not void the roof warranty.
3.02INSTALLATION
A.Install in accordance with NFPA 780, UL 96A, and LPI-175.
B.Connect conductors using mechanical connectors. Protect adjacent construction elements and finishes from damage.
C.Bond exterior metal bodies on building to lightning protection system and provide intermediate level interconnection loops 60 feet (18 m) on center.
D.Securely fasten conductors to the structure at intervals not exceeding 36".
3.03FIELD QUALITY CONTROL
A.Perform field inspection in accordance with Section 01400.
B.Obtain the services of Underwriters Laboratories, Inc. to provide inspection and labeling of the lightning protection system.

END OF SECTION

Other files

File Type Posted
SF 30.pdf PDF
resp pkg 20 TP warehouse roof.docx DOCX document
A-1 Model —
A-5 Model —
T-1_TITLESHT T1.pdf PDF
01330-submittal_procedure.rtf RTF text file
A-4 Model —
01300-mobilization.rtf RTF text file
20 TP warehouse roof.docx DOCX document
A-3 Model —
01732_02.doc DOC document
A-6 Model —
07900_-_joint_sealers.docx DOCX document
07130_-_underlaymentr.rtf RTF text file
A-2 Model —
Wage Det NM100001 6-4-10 NM1.docx DOCX document
07410-metal_roofing.rtf RTF text file
Show all 17

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

File details come from the government source that posted it. Updated .