RFI_-122815_AG-1484-S-16-0003_WMNF_Backup_Generator.docx
DOCX document 18 KB Posted
- Attached to
- Backup Generator Installation WMNF
- Solicitation number
- AG-1484-S-16-0003
View the file
Other files
| File | Type | Posted |
|---|---|---|
| RFI_-121615_AG-1484-S-16-0003_WMNF_Backup_Generator.docx | DOCX document | |
| RFI_-121515_AG-1484-S-16-0003_WMNF_Backup_Generator.docx | DOCX document | |
| Attendees.pdf | ||
| WMAC-E-713.pdf | ||
| Site_Visit_-120115_AG-1484-S-16-003_WMNF_Backup_Generator.docx | DOCX document | |
| RFI_-112415_AG-1484-S-16-003_WMNF_Backup_Generator.pdf | ||
| Attach_1_HQ_Generator_Spec.docx | DOCX document | |
| Attach_4_GovtProvidedTechnicalProposalForms.docx | DOCX document | |
| AG-1484-S-16-0003.pdf | ||
| Attach_3_DBWD_NH140009_Building_Grafton_Co.docx | DOCX document | |
| Attach_2_NECC_Gen_and_ATS_Plans.pdf |
Show all 11
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
RFI for Solicitation # AG-1484-S-16-003 WMNF Backup Generator
Questions and Answers – 12/28/15
1. Drawing E-721, Electrical Line Diagram. A note on this drawing states : "crosshatched areas are) not in contract." There is equipment (MSB, several panels) that are NOT in the crosshatched areas. Since the drawing is dated 3-05-07, we assume that this equipment was installed, is existing to remain, and is not in the SOW. Is this correct?
Main Switch is to remain in place and drawing E-721 is provided for reference of what generator/transfer switch in the statement of work is to power.
2. Drawing E-713. Same comment applies. Are these ductbanks/excavations existing to remain?
E713 is provided to show existing conduit from NHEC pad-mount transformer to Main Switch Gear, there are two spare existing conduits that could be utilized. Some contractors at the pre-bid viewing wanted to install generator and transfer switch next to the incoming power pad-mount transformer, this alternate location was approved.
3. Drawing E-631. What equipment, components, conduit and wire on this sheet are part of the SOW? In addition to the new generator and ATS switch, what other equipment/hardware are in the SOW?
E-613 is a reference of existing equipment.
File details come from the government source that posted it. Updated .