RFI for Solicitation # AG-1484-S-16-003 WMNF Backup Generator

Questions and Answers – 12/16/15

1. The plans show other work along with furnishing and installing the generator on a concrete pad and hook ups. Is that other work part of the contract?

Contract is to install an operational generator with all required equipment in accordance to specifications.

2. Is the walkway in front of the Chip Boiler concrete or asphalt?

Area shown on the plans has a concrete walkway.

3. Plan E-631 project 0602 note 7 (circled), is the noted conduit for this project, and is it in the proper location where the proposed pad will be?

There is no existing conduit in the ground for this contract and will need to be installed.

During pre-bid meeting contractors present seemed to agree that the opposite side of the building where the NHEC pad-mount transformer is installed is a better location to site generator and transfer switch. From that side tie into the existing conduits that run to the main switch gear. I agreed to this suggestion.