Sheet2_PUL6438s.pdf

PDF 415 KB Posted

Attached to
Idaho Panhandle NF, Fernan Office HVAC Renovation
Solicitation number
AG-02RC-S-11-0062
Issued by

About this file

Amend2-Sheet 2

View the file

Other files

File Type Posted
Amend_3.docx DOCX document
Sheet5_PACE_ AHU.pdf PDF
Amend_2.docx DOCX document
Sheet4_FanCoil.pdf PDF
Sheet6_YaskawaVFD.pdf PDF
Sheet3_WebsAX.pdf PDF
Sheet1_Web600.pdf PDF
Amend_1_WageDeterm.docx DOCX document
Amend_1.docx DOCX document
SPS.pdf PDF
Sol_Pkg_AG-02RC-S-11-0062.docx DOCX document
DB_Wage_Determination.docx DOCX document
DrawingsHVAC.pdf PDF
OwnerPastPerformanceSurvey.docx DOCX document
SF24BidBondFillForm.pdf PDF
IdahoWCI.doc DOC document
Show all 16

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

SPECIFICATION DATA

74-4040

PVL6436A, PVL6438N, PUL6438

Programmable, VAV/Unitary Controllers

GENERAL

The PVL6436A, PVL6438N, and PUL6438 controllers are part of the Excel 10 product line family. The three controllers are Free Topology Transceiver (FTT) LONMARK®-compliant devices designed to control HVAC equipment. These controllers provide many options and advanced system features that allow state-of-the-art commercial building control. Each controller is programmable and configurable using the NIAGARA FRAMEWORK® software.

The controllers are for use in VAV (Variable Air Volume) and Unitary HVAC control applications. Each controller contains a host microcontroller to run the main HVAC application and a second microcontroller for LONWORKS® network communications. Each controller provides flexible, universal inputs for external sensors, digital inputs, and a combination of analog outputs and digital Triac outputs.

The photo to the left is the PVL6436A, which includes the Series 60 floating actuator.

FEATURES

• Uses the Echelon® LONWORKS® network protocol.

• Free Topology Transceiver (FTT) high-speed 78 kilobit communications network.

• Capable of stand-alone operation, but can also use

LONWORKS® Bus network communications.

• 120 controllers per Excel 10 Q7751A,B Router when configured as a repeater.

• Field configurable and programmable for control, input, and output functions using the NIAGARA FRAMEWORK® software.

• User-defined network variables.

• Function Block engine, which allows the application designer to program the controller to perform a wide variety of HVAC applications.

• Significant Event Notification, Periodic Update capability, and Failure Detect (FD) when network inputs fail to be detected within their configurable time frame.

• Built-in Zone Control functions include a remote wall module interface and a scheduler.

• Pressure-independent or pressure-dependent single or dual duct Variable Air Volume (VAV) control as well as Unitary equipment control.

• Microbridge air flow sensor with dual integral restrictor design (PVL6436A and PVL6438N only).

• Easy user access to air flow sensor inputs.

• Actuator (PVL6436A only) mounts directly onto VAV box damper shaft and has up to 44 lb-in. (5 Nm) torque, 90-degree stroke, and 90 second timing at 60 Hz.

• All wiring connections are made to removable terminal blocks to simplify controller installation and replacement.

• Both controller housing and actuator are UL plenum rated.

PVL6436A, PVL6438N, PUL6438 PROGRAMMABLE, VAV/UNITARY CONTROLLERS

74-4040 2

DESCRIPTION

The programmable VAV/Unitary controllers are available in three models, as described in Table 1.

Each controller is programmable because the user chooses which function blocks to use and how to connect them. It is configurable because each Function Block has user-defined behavior.

The PVL6436A and PVL6438N models are Variable Air Volume (VAV) controllers, and the PUL6438 model is a Unitary controller.

VAV Equipment Control (Models PVL6436A and PVL6438N) The VAV controllers provide pressure-independent air flow control and pressure-dependent damper control. VAV systems generally provide cool air only to zones. However, each controller has additional programmable inputs and outputs that may be used to control devices, such as a fan or VAV box reheat coils. Heaters can be staged electric or modulating hot water. Supply and exhaust pressurization control are provided on a zone basis.

Unitary Equipment Control (Model PUL6438) Unitary equipment includes natural convection units, radiant panels, unit heaters, unit ventilators, fan coil units, and heat pumps. Unitary equipment does not require a central fan.

Depending on design, unitary equipment may perform one or all of the functions of HVAC—ventilation, filtration, heating, cooling, humidification and distribution. Unitary equipment frequently requires a distribution system for steam or hot and or chilled water.

SPECIFICATIONS

Electrical Rated Voltage: 20-30 Vac; 50/60 Hz Power Consumption:

100 VA for controller and all connected loads (including the actuator on model PVL6436A)

Controller only Load: 20 VA maximum; models PVL6438N and PUL6438

Controller and Actuator Load: 21 VA maximum; model

PVL6436A

External Sensors Power Output: 20 Vdc ±10% @ 75 mA maximum

Environmental VAV Operating & Storage Temperature Ambient Rating

(models PVL6436A and PVL6438N):

Minimum 32° F (0° C); Maximum 122° F (50° C)

Unitary Operating & Storage Temperature Ambient Rating (model PUL6438):

Minimum -40° F (-40° C); Maximum 150° F (65.5° C)

Relative Humidity: 5% to 95% non-condensing

Dimensions (H/W/D) See Fig. 1 and Fig. 2 beginning on page 6, for dimensioned drawings.

PVL6436A (including Actuator): 6.27 x 10.316 x 2.26 in.

(15.92 x 26.20 x 5.74 cm)

PVL6438N: 5.76 x 6.85 x 2.26 in. (14.62 x 17.40 x 5.74 cm)

PUL6438: 5.45 x 6.85 x 2.26 in. (13.84 x 17.40 x 5.74 cm)

Approval Bodies UL/cUL (E87741) listed under UL916 (Standard for Open Energy Management Equipment) with plenum rating.

CSA (LR95329-3) listed.

Meets FCC Part 15, Subpart B, Class B (radiated emissions) requirements.

Meets Canadian standard C108.8 (radiated emissions).

Conforms to the following requirements per European Consortium standards:

— EN 61000-6-1; 2001 (EU Immunity).

— EN 61000-6-3; 2001 (EU Emissions)

Real Time Clock Operating Range: 24 hour, 365 day, multi-year calendar including day of week and configuration for automatic day-light savings time adjustment to occur at 2:00 a.m. local time on configured start and stop dates

Power Failure Backup: 24 hours at 32 to 122° F (0 to 50° C) Accuracy: ±1 minute per month at 77° F (25° C)

Table 1. Controller Configurations.

Controller Model

Programmable Type

Universal Inputs

(UI)

Digital Inputs

(DI)

Analog Outputs

(AO)

Digital Outputs

(DO)

Velocity Pressure Sensor

(Microbridge)

Series 60 Floating Actuator

PVL6436A VAV 6 4 3 6 YES YES

PVL6438N VAV 6 4 3 8 YES NO

PUL6438 Unitary 6 4 3 8 NO NO

3 74-4040

Velocity Pressure Sensor (models PVL6436A and PVL6438N only) Operating Range: 0 to 1.5 in. H2O (0 to 374 Pa) Accuracy: ±2% of full scale at 32 to 122° F (0 to 50° C); ±1% of full scale at null pressure

Series 60 Floating Actuator (model PVL6436A only) Rotation Stroke: 95° ± 3° for CW or CCW opening dampers Torque Rating: 44 lb-in. (5 Nm) Run Time for 90° rotation: 90 seconds at 60 Hz

Inputs and Outputs Each controller has four digital inputs (DI), six or eight digital Triac outputs (DO), three analog outputs (AO), and six universal input (UI) circuits.

The PVL6436A has only 6 digital Triac outputs available, and the PVL6438N and PUL6438 each have eight digital Triac outputs available.

Digital Input (DI) Circuits Voltage Rating: 0 to 30 Vdc open circuit Input Type: Dry contact to detect open and closed circuit Operating Range: Open circuit = False; Closed circuit = True Resistance: Open circuit > 3,000 Ohms; Closed circuit < 500

Ohms

Digital Triac Output (DO) Circuits Voltage Rating: 20 to 30 Vac @ 50-60Hz Current Rating: 25 mA to 500 mA continuous, 800 mA

(AC rms) for 60 milliseconds

Analog Output (AO) Circuits All three analog outputs must be configured for either current or voltage. Configuring analog outputs individually for current or voltage is not possible.

ANALOG CURRENT OUTPUTS:

Current Output Range: 4.0 to 20.0 mA Output Load Resistance: 550 Ohms maximum

ANALOG VOLTAGE OUTPUTS:

Voltage Output Range: 2.0 to 10.0 Vdc Maximum Output Current: 10.0 mA

Analog outputs may be configured as digital outputs and operate as follows:

– False (0%) produces 0 Vdc, (0 mA)

– True (100%) produces the maximum 11 Vdc, (22 mA)

Universal Input (UI) Circuits See Table 2 for the UI specifications:

Hardware

CPU

Each controller uses a Texas Instruments MSP430 family microprocessor. The processor contains on-chip FLASH program memory, FLASH information memory, and RAM.

Memory Capacity Flash Memory: 60 kilobytes with 8 kilobytes available for user program. The controller is able to retain Flash memory settings for up to ten (10) years.

RAM: 2 kilobytes

Table 2. Universal Input Circuit Specifications.

Input Type

Sensor Type

Operating Range

Room/Zone Discharge Air Outdoor Air Temperature

20K Ohm

NTC

-40° F to 199° F (-40° C to 93° C)

Outdoor Air Temperature

C7031G a a C7031G and C7041F are recommended for use with these controllers, due to improved resolution and accuracy when compared to the PT1000.

-40° to 120°F (-40° to 49°C)

C7041F a -40° to 250°F (-40° to 121°C)

PT1000

(IEC751

3850)

-40° F to 199° F (-40° C to 93° C)

T7770 Setpoint Potentiometer

500 Ohm to

10,500 Ohm

-4° DDC to 4° DDC (-8° DDF to 7° DDF) or 50° F to 90° F

(10° C to 32° C)

Resistive Input

Generic 100 Ohms to

100K Ohms

Voltage Input

Transducer, Controller

0 - 10 Vdc

Discrete Input Dry Contact closure

OpenCircuit 3000Ohms≥ ClosedCircuit 3000< Ohms

74-4040 4

Status Information The LED on the front of the controller provides a visual indication of the status of the device. When the controller receives power, the LED appears in one of the following allowable states, as described in Table 3.

Communications Each controller uses an FTT transformer-coupled communications port. The controller’s Manchester encoded data is presented to other controllers and devices on the LONWORKS® Bus at 78 kilobits per second (kbs) via Echelon® communication protocol. The transformer-coupled communications interface offers a much higher degree of common mode-noise rejection while assuring dc isolation.

The LONWORKS® Bus is polarity insensitive, eliminating installation errors due to miswiring.

The maximum LONWORKS® Bus network length is 4,600 ft.

(1,400 m). For LONWORKS® Bus network lengths greater than the above, see “LONWORKS® Bus Wiring Guidelines,” form 74-2865.

The theoretical limit for each LONWORKS® Bus segment is 60 controllers. Up to 120 controllers can be configured when the Excel 10 Q7751A,B Router (configured as a repeater) is used, and the bus must be either singly or doubly terminated. Actual installations may have a lower limit, depending on the devices connected.

Honeywell-provided cable types for LONWORKS® Bus communications wiring are Level IV 22 AWG (0.34 sq. mm) plenum or non-plenum rated unshielded, twisted pair, stranded conductor wire.

• For non-plenum areas, U.S. part AK3798 (single-pair stranded) can be used.

• For plenum areas, U.S. part AK3797 (single-pair stranded) or U.S. part AK3799 (two-pair stranded) can be used.

Contact Echelon Corp. Technical Support for the recommended vendors of Echelon approved cables.

Refer to the “LONWORKS® Bus Wiring Guidelines,” form 74- 2865, for a complete description of LONWORKS® Bus network topology rules and approved cable types.

If a longer LONWORKS® Bus network is required, the Excel 10 Q7751A,B Router (configured as a repeater) can be added to extend the length of the LONWORKS® Bus. Each network segment can have a maximum of one repeater.

NOTE: Connection for operator access to the LONWORKS® Bus is provided by plugging the Serial LONTALK® Adapter (SLTA) connector into the LONWORKS® Bus jack on the controller.

Network Variables Profile Network variables, as described in Table 4 on page 5, are communicated over the LONWORKS® Bus. User-defined variables provide for customized configurations. The controller’s built-in functions provide for the selection of variables, which are available from/to the network. Each network variable is named and configured using the NIAGARA FRAMEWORK® software.

Each controller supports a range of network variables, depending on the byte count (storage requirements) of each variable. In most typical installations, a maximum of 30-37 variables are configured.

NOTE: The maximum number of variables that a controller supports is 62, and the maximum byte count per variable is 31.

The controller is capable of supporting up to 1,922 separate data values.

In Table 4 on page 5, the network variable prefixes have the following meaning:

• nvi — Network Variable Input

• nvo — Network Variable Output

• nci — Configuration Property Network Variable Input stored in Non-Volatile Memory

• nro — Network Variable Output stored in Non-Volatile memory

Table 3. Status LED States.

LED State Blink Rate Status or Condition

OFF not applicable No power to processor, LED damaged, low voltage to board, or controller damaged.

ON ON steady;

not blinking

Processor and/or controller is not operating.

Very Slow Blink (continuous)

1 second ON, 1 second OFF

Controller is operating normally.

Slow Blink (continuous)

0.5 second ON,

0.5 second OFF

Controller alarm is active, controller in process of download, or controller lost its configuration.

Medium Blink (continuous)

0.25 second ON,

0.25 second OFF

Controller firmware is loading.

Fast Blink (continuous)

0.10 second ON,

0.10 second OFF

Controller is in manual mode under control of the PC-based software tool.

5 74-4040

Accessories

— 201052A,B,C Auxiliary Switches (one, two or three switches)

— 205979 Excel 10 Connector Cable from the Excel 10

Q7752A Serial Interface Adapter to Excel 10 Controller or Wall Module

— 209541B Excel 10 Termination Module

— Excel 10 C7041B,C,D,P,R Air Temperature Sensor (indoor)

— Excel 10 C7770A Air Temperature Sensor (indoor/plenum)

— Excel 10 C7031G Air Temperature Sensor (outdoor)

— Excel 10 C7041F Air Temperature Sensor (outdoor)

— Excel 10 Q7751A,B Router (configured as a repeater)

— Excel 10 Q7752A,B Serial Interface Adapter

— Excel 10 T7770 Wall Module

— C7400A Enthalpy Sensor

— P7640 Pressure Transducer Family

— C7232 CO2 Sensor Family

— C7600 Humidity Sensor Family

— H7625, H7635, and H7655 Humidity and Temperature

Sensors

Refer to the “Sensors Product Overview,” form 63-9285, for additional accessories.

Mounting The controller enclosure is constructed of a plastic base plate and a plastic factory-snap-on cover. The cover does not need to be removed from the base plate for either mounting or wiring. Removable terminal blocks are used for all wiring connections, which allow the controller to be wired before or after mounting.

The controller can be mounted in any orientation. Ventilation openings are designed into the cover to allow proper heat dissipation, regardless of the mounting orientation.

NOTE: The controller must be mounted in a position that allows clearance for wiring, servicing, removal, con-nection of the LONWORKS® Bus Jack, and access to the NEURON® Service Pin.

NOTE: For complete mounting information, refer to the “PVL6436A, PVL6438N, PUL6438 Programmable, VAV/Unitary Controllers - Installation Instructions,” form 95-7732).

PVL6436A Mounting The PVL6436A controller includes the direct-coupled actuator with Declutch mechanism, which is shipped hard-wired to the controller (using digital outputs 7 and 8).

The actuator mounts directly onto the VAV box damper shaft and has up to 44 lb-in. (5 Nm) torque, 90-degree stroke, and 90 second timing at 60 Hz. The actuator is suitable for

Table 4. Network Object Variables List.

Network Object Variables

→ Input Mandatory Output → nviNodeRequest * a nvoNodeStatus *

→ Input Optional Output → nviTimeSet * nvoFileStatus * nviFileRequest nviFilePos *

→ Input Manufacturer Defined Output → nviDebugIndx * nvoTime * nviInUse * nvoConfigError * nviManVal * nvoDebug1 * nvoDebug2 * nvoAlarmH * nvoAlarmStatus * nvoError * nvoIO1 * nvoIO2 * nvoIO3 *

→ Input Configuration Output → (Manufacturer Defined) nciApplVerNew * nroPgmVer * nciDeviceName * nciSendHrtBt * nciRcvHrtBt * nciUICalOffset *

→ Input User-defined (Examples of) b Output → nviSpaceTemp nvoSpaceTemp nviSetPoint nvoEffectSetPt nviManOverride nvoUnitStatus nviEmergCmd nvoTerminalLoad nviEnergyHoldOff nvoEnergyHoldOff nviFanSpeed nvoBoxFlow a Network variables marked with an asterisk (*) are fixed. All network variables, other than those that are user-defined, are fixed and not configurable.

b User-defined network variables are created using the NIAGARA FRAMEWORK® software. The variables listed in the table are a few examples. A wide range of variables are user-definable.

74-4040 6 mounting onto a 3/8 to 1/2 in. (10 to 13 mm) square or round VAV box damper shaft. The minimum VAV box damper shaft length is 1-9/16 in. (40 mm).

After the actuator is mounted to the damper shaft, the controller mounts to a panel by using four No. 6 or No. 8 machine or sheet metal screws inserted through the corners of the base plate.

Fig. 1. Panel Mounting Model PVL6436A, Dimensions in inches (mm).

PVL6438N and PUL6438 Mounting The controller mounts to either a panel or DIN rail (standard EN50022; 7.5mmm x 35mm).

• For panel mounting, use four No. 6 or No. 8 machine or sheet metal screws inserted through the corners of the base plate.

• For DIN rail mounting, refer to the “Installation Instructions,” form 95-7732.

Fig. 2. Panel Mounting Models PVL6438N and PUL6438, Dimensions in inches (mm).

1 2 3 4 5 6 7 8 109 2 3 4 5 6 7 11 1 1 1 1 1 1

1 2 3 4 5 6 7 8 09 22 2 2 2 2 2 2 2 33

1 2 3 4 5 6 7 8 09 33 33 33 33 45-3/4

(146)

10-5/16 (262)

NOTE: CONTROLLER CAN BE MOUNTED IN ANY ORIENTATION.

PANEL MOUNTING HOLE

(4X) 29/64 IN. (12)

M23590

5-3/64 (128)

8-5/16 (211)

6-29/64 (164) 1-55/64

(47)

6-17/64 (159)

7/16 (11)

DEPTH IS

2-1/4 (57)

1 2 3 4 5 6 7 8 109 2 3 4 5 6 7 8 09 11 1 1 1 1 1 1 1 21

1 2 3 4 5 6 7 8 09 22 2 2 2 2 2 2 2 33

1 2 3 4 5 6 7 8 09 33 33 33 33 4

5-3/4 (146)

6-27/32 (174)

NOTE: CONTROLLER CAN BE MOUNTED IN ANY ORIENTATION.

PANEL MOUNTING HOLE

(4X) 29/64 IN. (12)

M23589

5-3/64 (128)

6-29/64 (164)

5-29/64 (139)

1 2 3 4 5 6 7 8 109 2 3 4 5 6 7 8 09 11 1 1 1 1 1 1 1 21

1 2 3 4 5 6 7 8 09 22 2 2 2 2 2 2 2 33

1 2 3 4 5 6 7 8 09 33 33 33 33 4

6-27/32 (174)

5-3/64 (128)

6-29/64 (164)

5-29/64 (139)

PVL6438N PUL6438

DEPTH IS

2-1/4 (57)

7 74-4040

Automation and Control Solutions Honeywell International Inc. Honeywell Limited-Honeywell Limitée 1985 Douglas Drive North 35 Dynamic Drive Golden Valley, MN 55422 Toronto, Ontario M1V 4Z9 customer.honeywell.com

® U.S. Registered Trademark © 2006 Honeywell International Inc.

74-4040 M.S. 09-06

LON®, LONTALK®, LONWORKS® and NEURON® are registered trademarks of Echelon® Corporation.

LONMARK® and the LonMark Logo are trademarks of the LonMark Association.

NIAGARA FRAMEWORK® and the Niagara framework logo are registered trademarks of Tridium, Inc.

General
Features
Description
VAV Equipment Control (Models PVL6436A and PVL6438N)
Unitary Equipment Control (Model PUL6438)
Specifications
Electrical
Environmental
Dimensions (H/W/D)
Approval Bodies
Real Time Clock
Velocity Pressure Sensor (models PVL6436A and PVL6438N only)
Series 60 Floating Actuator (model PVL6436A only)
Inputs and Outputs
Hardware
Status Information
Communications
Network Variables Profile
Accessories
Mounting

/ASCII85EncodePages false /AllowTransparency false /AutoPositionEPSFiles true /AutoRotatePages /All /Binding /Left /CalGrayProfile (Dot Gain 20%) /CalRGBProfile (sRGB IEC61966-2.1) /CalCMYKProfile (U.S. Web Coated \050SWOP\051 v2) /sRGBProfile (sRGB IEC61966-2.1) /CannotEmbedFontPolicy /Warning /CompatibilityLevel 1.3 /CompressObjects /Tags /CompressPages true /ConvertImagesToIndexed true /PassThroughJPEGImages true /CreateJDFFile false /CreateJobTicket false /DefaultRenderingIntent /Default /DetectBlends true /DetectCurves 0.0000 /ColorConversionStrategy /LeaveColorUnchanged /DoThumbnails false /EmbedAllFonts true /EmbedOpenType false /ParseICCProfilesInComments true /EmbedJobOptions true /DSCReportingLevel 0 /EmitDSCWarnings false /EndPage -1 /ImageMemory 1048576 /LockDistillerParams false /MaxSubsetPct 100 /Optimize true

/OPM 1

/ParseDSCComments true /ParseDSCCommentsForDocInfo true /PreserveCopyPage true /PreserveDICMYKValues true /PreserveEPSInfo true /PreserveFlatness false /PreserveHalftoneInfo false /PreserveOPIComments false /PreserveOverprintSettings true /StartPage 1 /SubsetFonts true /TransferFunctionInfo /Apply /UCRandBGInfo /Preserve /UsePrologue false /ColorSettingsFile () /AlwaysEmbed [ true /NeverEmbed [ true /AntiAliasColorImages false /CropColorImages false /ColorImageMinResolution 300 /ColorImageMinResolutionPolicy /OK /DownsampleColorImages true /ColorImageDownsampleType /Bicubic /ColorImageResolution 300 /ColorImageDepth -1 /ColorImageMinDownsampleDepth 1 /ColorImageDownsampleThreshold 1.50000 /EncodeColorImages true /ColorImageFilter /DCTEncode /AutoFilterColorImages true /ColorImageAutoFilterStrategy /JPEG /ColorACSImageDict << /QFactor 0.76 /HSamples [2 1 1 2] /VSamples [2 1 1 2] /ColorImageDict << /QFactor 0.15 /HSamples [1 1 1 1] /VSamples [1 1 1 1] /JPEG2000ColorACSImageDict << /TileWidth 256 /TileHeight 256 /Quality 30 /JPEG2000ColorImageDict << /TileWidth 256 /TileHeight 256 /Quality 30 /AntiAliasGrayImages false /CropGrayImages false /GrayImageMinResolution 300 /GrayImageMinResolutionPolicy /OK /DownsampleGrayImages true /GrayImageDownsampleType /Bicubic /GrayImageResolution 300 /GrayImageDepth -1 /GrayImageMinDownsampleDepth 2 /GrayImageDownsampleThreshold 1.50000 /EncodeGrayImages true /GrayImageFilter /DCTEncode /AutoFilterGrayImages true /GrayImageAutoFilterStrategy /JPEG /GrayACSImageDict << /QFactor 0.76 /HSamples [2 1 1 2] /VSamples [2 1 1 2] /GrayImageDict << /QFactor 0.15 /HSamples [1 1 1 1] /VSamples [1 1 1 1] /JPEG2000GrayACSImageDict << /TileWidth 256 /TileHeight 256 /Quality 30 /JPEG2000GrayImageDict << /TileWidth 256 /TileHeight 256 /Quality 30 /AntiAliasMonoImages false /CropMonoImages false /MonoImageMinResolution 1200 /MonoImageMinResolutionPolicy /OK /DownsampleMonoImages true /MonoImageDownsampleType /Bicubic /MonoImageResolution 300 /MonoImageDepth -1 /MonoImageDownsampleThreshold 1.50000 /EncodeMonoImages false /MonoImageFilter /CCITTFaxEncode /MonoImageDict << /K -1 /AllowPSXObjects false /CheckCompliance [ /None /PDFX1aCheck false /PDFX3Check false /PDFXCompliantPDFOnly false /PDFXNoTrimBoxError true /PDFXTrimBoxToMediaBoxOffset [ 0.00000 0.00000 0.00000 0.00000 /PDFXSetBleedBoxToMediaBox true /PDFXBleedBoxToTrimBoxOffset [ 0.00000 0.00000 0.00000 0.00000 /PDFXOutputIntentProfile () /PDFXOutputConditionIdentifier () /PDFXOutputCondition () /PDFXRegistryName () /PDFXTrapped /False

/Description << /ENU ([Based on 'TechLit-INDD'] An attempt at replicating the Tech Lit standards in InDesign.)

/Namespace [ (Adobe) (Common) (1.0) /OtherNamespaces [ /AsReaderSpreads false /CropImagesToFrames true /ErrorControl /WarnAndContinue /FlattenerIgnoreSpreadOverrides true /IncludeGuidesGrids false /IncludeNonPrinting false /IncludeSlug false /Namespace [ (Adobe) (InDesign) (4.0) /OmitPlacedBitmaps false /OmitPlacedEPS false /OmitPlacedPDF false /SimulateOverprint /Legacy /AddBleedMarks false /AddColorBars false /AddCropMarks false /AddPageInfo false /AddRegMarks false /BleedOffset [ /ConvertColors /NoConversion /DestinationProfileName () /DestinationProfileSelector /NA /Downsample16BitImages true /FlattenerPreset << /ClipComplexRegions true /ConvertStrokesToOutlines false /ConvertTextToOutlines false /GradientResolution 300 /LineArtTextResolution 1200 /PresetName ([High Resolution]) /PresetSelector /HighResolution /RasterVectorBalance 1 /FormElements false /GenerateStructure true /IncludeBookmarks false /IncludeHyperlinks false /IncludeInteractive false /IncludeLayers false /IncludeProfiles false /MarksOffset 6 /MarksWeight 0.250000 /MultimediaHandling /UseObjectSettings /Namespace [ (Adobe) (CreativeSuite) (2.0) /PDFXOutputIntentProfileSelector /NA /PageMarksFile /RomanDefault /PreserveEditing true /UntaggedCMYKHandling /LeaveUntagged /UntaggedRGBHandling /LeaveUntagged /UseDocumentBleed false /AllowImageBreaks true /AllowTableBreaks true /ExpandPage false /HonorBaseURL true /HonorRolloverEffect false /IgnoreHTMLPageBreaks false /IncludeHeaderFooter false /MarginOffset [ /MetadataAuthor () /MetadataKeywords () /MetadataSubject () /MetadataTitle () /MetricPageSize [ /MetricUnit /inch /MobileCompatible 0 /Namespace [ (Adobe) (GoLive) (8.0) /OpenZoomToHTMLFontSize false /PageOrientation /Portrait /RemoveBackground false /ShrinkContent true /TreatColorsAs /MainMonitorColors /UseEmbeddedProfiles false /UseHTMLTitleAsMetadata true >> setdistillerparams /HWResolution [2400 2400] /PageSize [612.000 792.000] >> setpagedevice

File details come from the government source that posted it. Updated .