NAKWASINA BARGE DRAWING ADDENDUMS

View the file

Other files

Show all 11

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

NAKWASINA BARGE

DRAWING ADDENDUMS

P1 – ADDING MISSING PRESSURE SWITCH

E1 – EDITED WORDING, ADDED SPARE PRESSURE SWITCH

E3 – EDITED HOW WORK ITEM “E10” TERMINATES

E4 – EDITED WORDING

ADDED 7 PAGES OF ELECTRICAL DRAWINGS FOR

BUILDING CONTROL PANEL

USDA FOREST SERVICE - TONGASS NATIONAL FOREST SH. ofR-10 -

DESIGNED: DATE:

DATE:DRAWN:

REVIEWED: DATE:

DATE: REVISION: BY:

PLOT ON 11"X17" PAPER

TONGASS

ENGINEERING & RECREATION TNFTYP:09/04

NAKWASINA BARGE IMPROVEMENTS ELECTRICAL NOTES AND DETAILS

TONGASS SUPERVISOR'S OFFICE

JJP DEC 2014

JJP DEC 2014 1/28/15 EDITED NOTES JJP

ACAD.DWG

E1 6

GENERAL NOTES

1. ALL WIRING SHALL BE MIL-SPEC M24643 SHIPBOARD CABLE

2.UNLESS NOTED ELSEWHERE, ALL CONDUCTORS SHALL BE MINIMUM SIZE OF 4OO0

CMILS/14 A.W.G.

3. ALL UNUSED SHIPBOARD CABLE CAN BE REUSED PROVIDING THEY ARE UNDAMAGED

AND MEET CAPACITY AND CONDUCTOR COUNT.

4. ALL UNUSED CABLES FROM EXISTING WATER SYSTEM SHALL BE REMOVED

5. ALL UNUSED OPENING IN TANKS, WATER TIGHT COMPARTMENTS, AND ELECTRICAL

ENCLOSURES SHALL BE SEALED BY APPROPRIATE WATER TIGHT PLUGS

6. ROUTE ALL NEW CABLE VIA EXISTING CABLE TRAYS AND HANGER. INSTALL NEW HANGERS

ONLY AS NEEDED

7. LOCATION OF WORK ITEMS ARE ON DRAWINGS ARE IN GENERAL ONLY. SITE

CONDITIONS DETERMINES EXACT LOCATION. COORDINATE WITH OTHER TRADED AS

NEEDED

8. WATER TREATMENT CONTROL PANEL CONNECTION SCHEMATIC WILL BE PROVIDED WITH

GOVT SUPPLIED CONTROL PANEL

9. GOVT SUPPLIED PANEL SHALL NOT BE LARGER THAN 24" X 24" . ALL CABLES SHALL

ENTER THROUGH THE BOTTOM OF PANEL ONLY THROUGH APPROVED CORD GRIPS. LEAVE

SUFFICIENT AMOUNT OF CABLE FOR TERMINATING. LABEL BOTH ENDS OF CABLES WITH

WORK ITEM NUMBER

10. WIRING WITHIN THE HOUSE ABOVE THE MAIN DECK SHALL MEET 2014 NATIONAL

ELECTRICAL CODE. ALL EXTERIOR WIRING AND WIRING IN HOLD SHALL MEET CURRENT

AMERICAN BUREAU OF SHIPPING (ABS) RULES FOR STEEL VESSELS TO 45 METERS

11. PROVIDE ONE SPARE MADISON 8700 FLOAT SWITCH AND ONE PROXIMITY SWITCH

DRAWING NOTES

1 WORK ITEMS ARE LOCATED IN UTILIDOR UNDER THE STAIRS. ACCESS IS LOCATED IN

SIDE HALLWAY

2 LEAVE ENOUGH SLACK IN CABLE TO CONNECT CONNECTOR BODY TO VALVE ASSEMBLY

PLUG

3 CABLE SHALL BE SHIELDED CABLE

4 SEE DETAIL BELOW

ABBREVIATIONS

DP - DISTRIBUTION PUMP

FP - FILTRATION PUMP

WTCP - WATER TREATMENT CONTROL PANEL

SYMBOL LEGEND

JUNCTION BOX

COMBINATION MOTOR STARTER DISCONNECT

WATER TREATMENT CONTROL PANEL

WATER TIGHT TWIST LOCK PLUG/RECEPTACLE

CABLE RUN - TICK MARKS = NUMBER OR CONDUCTORS

J

DP

WTCP

CRITICAL PARTS LIST

QUANT DESCRIPTION PART NUMBER WORK ITEM COMMENT

3 MADISON FLOAT SWITCH 8700 E2, E3,E5 UNIVERSAL MOUNT NO,NC

2 TELEMECANIQUE ULTRASONIC

PROXIMITY SWITCH SM952A166000 E6,E7 SEE DRAWING NOTE 4

4 HUBBELL CONNECTOR

BODY/WATERTIGHT BOOT HBL2353/HBL60CM32 E16

2 ASCO SOLENOID WATER VALVE EF8015B202 w/ 12 VDC

COIL SEE SHEETS NO. E5 AND E6 FOR INLET VALVE ASSEMBLY

1 ASCO SOLENOID WATER VALVE 8212A055L1100F1 E14 HP UNTREATED FEED TO

FILTRATION

FLOAT SWITCH ASSEMBLY

(EXPLODED VIEW)

SHIPBOARD CABLE

2" WATERTIGHT CORD GRIP

APPROPRIATE SIZE FOR CABLE

2" ELECTRICAL LB WITH COVER AND GASKET

FOR SPLICING WIRES

FLOAT SWITCH

MADISON 8700

E9

GEN CONTROL PANEL

E9

GEN CONTROL PANEL

E9

WORK ITEM E9 - GENERATOR CONTROL PANEL TERMINATION

DRILL 30MM MINIMUM DIAMETER

HOLE FOR PROX SENSOR

2 INCH WHITE PVC

THREADED (NPT) MALE PLUG

4 WORK ITEM E6 & E7

DRILL HOLE AND INSERT PROX SWITCH

SCREW INTO NEW HUB IN TANKS

BATH 1

COOKS QTS

LA

U N D

R Y

BATTERIES

PANTRY

KITCHEN LIVING/DINING

BDRM 1 MUD RM WORK

SHOP

STORE

USDA FOREST SERVICE - TONGASS NATIONAL FOREST SH. ofR-10 -

DESIGNED: DATE:

DATE:DRAWN:

REVIEWED: DATE:

DATE: REVISION: BY:

PLOT ON 11"X17" PAPER

TONGASS

ENGINEERING & RECREATION TNFTYP:09/04

NAKWASINA BARGE IMPROVEMENTS MAIN DECK ELECTRICAL WORK ITEMS

TONGASS SUPERVISOR'S OFFICE

JJP DEC 2014

JJP DEC 2014 1/28/15 EDITED NOTES JJP

ACAD.DWG

E3 6

E8

E9 E10

WORK ITEMS

E8 120V 20 AMP GROUNDED CIRCUIT TO WATER TREATMENT CONTROL PANEL FROM INVERTER PANEL

E9 TERMINATE TO TERMINAL BLOCKS LABELED "E9" LOCATED INSIDE OF EXISTING GENERATOR CONTROL PANEL. LOOK FOR FLAGGING

E10 10 FOOT COIL FROM J-BOX TO BE LABELED "E10". TERMINATION BY OTHERS TERMINATE TO TERMINAL BLOCKS LABELED "E10" LOCATED INSIDE

EXISTING GENERATOR CONTROL PANEL. LOOK FOR FLAGGING

E33 CUT IN A DEEP METALLIC 2 GANG SWITCH BOX AT 60" AFF FOR GOVT SUPPLIED REMOTE PANEL FOR WATER TREATMENT SYSTEM.FEED IT WITH 3

CONDUCTOR CABLE FROM THE "WTCP". SEE SHEET E4.

E33

SEWAGE

TANK

SEWAGE

TANK

FUEL TANK

FUEL TANK

POTABLE

WATER TANK

POTABLE

WATER TANK

GENERATOR

GENERATOR

WINCH

MOTOR

W A

TE

R T

A N K

WASTE

WATER TANK

USDA FOREST SERVICE - TONGASS NATIONAL FOREST SH. ofR-10 -

DESIGNED: DATE:

DATE:DRAWN:

REVIEWED: DATE:

DATE: REVISION: BY:

PLOT ON 11"X17" PAPER

TONGASS

ENGINEERING & RECREATION TNFTYP:09/04

NAKWASINA BARGE IMPROVEMENTS LOWER DECK ELECTRICAL WORK ITEMS

TONGASS SUPERVISOR'S OFFICE

JJP DEC 2014

JJP DEC 2014 1/28/15 EDITED NOTES JJP

ACAD.DWG

E4 6

E1

WTCP

E2

E3

E7

E5

E20

TO

WTCP

TO

WTCP

TO

WTCP

D P

DP TO

WTCPE11

E12

JJ

TO

E10

UPSTAIRS

TO

INVERTER

PANEL

UPSTAIRS

SEE

E8

WORK ITEMS

E1 MOUNT AND WIRE IN GOVT SUPPLIED WATER TREATMENT CONTROL PANEL (WTCP)

E2 REMOVE ALL EXISTING FLOAT SWITCHES AND INSTALL NEW FLOAT SWITCH ASSEMBLY NORMALLY CLOSED INTO TANK HIGHEST INLET

E3 INSTALL NEW FLOAT SWITCH ASSEMBLY NORMALLY OPENED INTO THE LOWEST EXISTING INLET

E4 WIRE IN NEW PRESSURE SWITCH BY FILTRATION PUMP. WIRE SHALL GO TO "WTCP" AND NOT TO PUMP. COORDINATE WITH PLUMBING

E5 REMOVE EXISTING PLUMBING AND INSTALL NEW FLOAT SWITCH ASSEMBLY NORMALLY OPEN IN THE TANK LOWEST EXISTING INLET

E6 REMOVE EXISTING FLOAT SWITCHES AND INSTALL NEW PROXIMITY SWITCH. SEE DRAWING NOTE 4 AND DETAIL ON PAGE E1

E7 REMOVE EXISTING FLOAT SWITCH AND INSTALL NEW PROXIMITY SWITCH. SEE DRAWING NOTE 4 AND DETAIL ON PAGE E1

E11 REWIRE EXISTING MOTOR STARTER FOR DISTRIBUTION PUMP. CONTROL CIRCUIT FOR STARTER SHALL BE LOOPED TO " WTCP"

E12 REMOVE EXISTING CONTROL PANEL AND ALL UNUSED CABLES

E15 REWIRE EXISTING MOTOR STARTER FOR FILTRATION PUMP. CONTROL CIRCUIT FOR STARTER SHALL BE LOOPED TO" WTCP"

E16 CONNECT TWIST LOCK CONNECTOR BODY HUBBELL HBL2353/HBL60CM32 TO SHIPBOARD CABLE FOR CONNECTION TO VALVE

ASSEMBLY

TO

E9

UPSTAIRS

E19 WIRE IN NEW SOLENOID VALVE TO "WTCP". COORDINATE WITH PLUMBING

E20 REMOVE AND STORE EXISTING SHORE POWER CORD IN FWD HOLD

E21 REMOVED UNUSED ELECTRICAL EQUIPMENT

E22 REMOVE ABANDON CABLE

E23 INSTALL SQUARE D QO LOAD CENTER pn QO24L70RB W/ 30 AMP 2POLE BREAKER FOR GENERATOR SERVICE DISCONNECT ON 4kW

GENSET. 1 POLE SHALL BE FOR THE NEUTRAL.

E24 INSTALL SQUARE D QB3100BNRB W/ 80 AMP 3 POLE BREAKER FOR GENERATOR SERVICE DISCONNECT ON 20 kW GENSET.

CENTER POLE SHALL BE FOR THE NEUTRAL

E25 DRILL HOLES IN HEAT DETECTOR BASES TO ALIGN THEM TO THE JUNCTION BOXES

E30 BUILD VALVE ASSEMBLIES. ONE EACH FOR UNTREATED AND TREATED WATER INLETS SEE SHEETS E5 AND E6 FOR DETAILS

E34 REMOVE OLD FLOAT SWITCHES AND PLUG HOLES

FP

TO

WTCP

E15

E16

E16

E16 E16

J

E21

E22

E25 E25

E23

E24 E25

E25

E4

E19TO

WTCP

JE6

E34

TO

E33

UPSTAIRS

BUILD AND MOUNT

NAKWASINA BARGE
Barge_DrinkingWaterSystem_Improvement
revised-E1_notes
revised-E3_main_deck_work_items
revised-E4_hold_work_items