NAKWASINA BARGE
DRAWING ADDENDUMS
P1 – ADDING MISSING PRESSURE SWITCH
E1 – EDITED WORDING, ADDED SPARE PRESSURE SWITCH
E3 – EDITED HOW WORK ITEM “E10” TERMINATES
E4 – EDITED WORDING
ADDED 7 PAGES OF ELECTRICAL DRAWINGS FOR
BUILDING CONTROL PANEL
USDA FOREST SERVICE - TONGASS NATIONAL FOREST SH. ofR-10 -
DESIGNED: DATE:
DATE:DRAWN:
REVIEWED: DATE:
DATE: REVISION: BY:
PLOT ON 11"X17" PAPER
TONGASS
ENGINEERING & RECREATION TNFTYP:09/04
NAKWASINA BARGE IMPROVEMENTS ELECTRICAL NOTES AND DETAILS
TONGASS SUPERVISOR'S OFFICE
JJP DEC 2014
JJP DEC 2014 1/28/15 EDITED NOTES JJP
ACAD.DWG
E1 6
GENERAL NOTES
1. ALL WIRING SHALL BE MIL-SPEC M24643 SHIPBOARD CABLE
2.UNLESS NOTED ELSEWHERE, ALL CONDUCTORS SHALL BE MINIMUM SIZE OF 4OO0
CMILS/14 A.W.G.
3. ALL UNUSED SHIPBOARD CABLE CAN BE REUSED PROVIDING THEY ARE UNDAMAGED
AND MEET CAPACITY AND CONDUCTOR COUNT.
4. ALL UNUSED CABLES FROM EXISTING WATER SYSTEM SHALL BE REMOVED
5. ALL UNUSED OPENING IN TANKS, WATER TIGHT COMPARTMENTS, AND ELECTRICAL
ENCLOSURES SHALL BE SEALED BY APPROPRIATE WATER TIGHT PLUGS
6. ROUTE ALL NEW CABLE VIA EXISTING CABLE TRAYS AND HANGER. INSTALL NEW HANGERS
ONLY AS NEEDED
7. LOCATION OF WORK ITEMS ARE ON DRAWINGS ARE IN GENERAL ONLY. SITE
CONDITIONS DETERMINES EXACT LOCATION. COORDINATE WITH OTHER TRADED AS
NEEDED
8. WATER TREATMENT CONTROL PANEL CONNECTION SCHEMATIC WILL BE PROVIDED WITH
GOVT SUPPLIED CONTROL PANEL
9. GOVT SUPPLIED PANEL SHALL NOT BE LARGER THAN 24" X 24" . ALL CABLES SHALL
ENTER THROUGH THE BOTTOM OF PANEL ONLY THROUGH APPROVED CORD GRIPS. LEAVE
SUFFICIENT AMOUNT OF CABLE FOR TERMINATING. LABEL BOTH ENDS OF CABLES WITH
WORK ITEM NUMBER
10. WIRING WITHIN THE HOUSE ABOVE THE MAIN DECK SHALL MEET 2014 NATIONAL
ELECTRICAL CODE. ALL EXTERIOR WIRING AND WIRING IN HOLD SHALL MEET CURRENT
AMERICAN BUREAU OF SHIPPING (ABS) RULES FOR STEEL VESSELS TO 45 METERS
11. PROVIDE ONE SPARE MADISON 8700 FLOAT SWITCH AND ONE PROXIMITY SWITCH
DRAWING NOTES
1 WORK ITEMS ARE LOCATED IN UTILIDOR UNDER THE STAIRS. ACCESS IS LOCATED IN
SIDE HALLWAY
2 LEAVE ENOUGH SLACK IN CABLE TO CONNECT CONNECTOR BODY TO VALVE ASSEMBLY
PLUG
3 CABLE SHALL BE SHIELDED CABLE
4 SEE DETAIL BELOW
ABBREVIATIONS
DP - DISTRIBUTION PUMP
FP - FILTRATION PUMP
WTCP - WATER TREATMENT CONTROL PANEL
SYMBOL LEGEND
JUNCTION BOX
COMBINATION MOTOR STARTER DISCONNECT
WATER TREATMENT CONTROL PANEL
WATER TIGHT TWIST LOCK PLUG/RECEPTACLE
CABLE RUN - TICK MARKS = NUMBER OR CONDUCTORS
J
DP
WTCP
CRITICAL PARTS LIST
QUANT DESCRIPTION PART NUMBER WORK ITEM COMMENT
3 MADISON FLOAT SWITCH 8700 E2, E3,E5 UNIVERSAL MOUNT NO,NC
2 TELEMECANIQUE ULTRASONIC
PROXIMITY SWITCH SM952A166000 E6,E7 SEE DRAWING NOTE 4
4 HUBBELL CONNECTOR
BODY/WATERTIGHT BOOT HBL2353/HBL60CM32 E16
2 ASCO SOLENOID WATER VALVE EF8015B202 w/ 12 VDC
COIL SEE SHEETS NO. E5 AND E6 FOR INLET VALVE ASSEMBLY
1 ASCO SOLENOID WATER VALVE 8212A055L1100F1 E14 HP UNTREATED FEED TO
FILTRATION
FLOAT SWITCH ASSEMBLY
(EXPLODED VIEW)
SHIPBOARD CABLE
2" WATERTIGHT CORD GRIP
APPROPRIATE SIZE FOR CABLE
2" ELECTRICAL LB WITH COVER AND GASKET
FOR SPLICING WIRES
FLOAT SWITCH
MADISON 8700
E9
GEN CONTROL PANEL
E9
GEN CONTROL PANEL
E9
WORK ITEM E9 - GENERATOR CONTROL PANEL TERMINATION
DRILL 30MM MINIMUM DIAMETER
HOLE FOR PROX SENSOR
2 INCH WHITE PVC
THREADED (NPT) MALE PLUG
4 WORK ITEM E6 & E7
DRILL HOLE AND INSERT PROX SWITCH
SCREW INTO NEW HUB IN TANKS
BATH 1
COOKS QTS
LA
U N D
R Y
BATTERIES
PANTRY
KITCHEN LIVING/DINING
BDRM 1 MUD RM WORK
SHOP
STORE
USDA FOREST SERVICE - TONGASS NATIONAL FOREST SH. ofR-10 -
DESIGNED: DATE:
DATE:DRAWN:
REVIEWED: DATE:
DATE: REVISION: BY:
PLOT ON 11"X17" PAPER
TONGASS
ENGINEERING & RECREATION TNFTYP:09/04
NAKWASINA BARGE IMPROVEMENTS MAIN DECK ELECTRICAL WORK ITEMS
TONGASS SUPERVISOR'S OFFICE
JJP DEC 2014
JJP DEC 2014 1/28/15 EDITED NOTES JJP
ACAD.DWG
E3 6
E8
E9 E10
WORK ITEMS
E8 120V 20 AMP GROUNDED CIRCUIT TO WATER TREATMENT CONTROL PANEL FROM INVERTER PANEL
E9 TERMINATE TO TERMINAL BLOCKS LABELED "E9" LOCATED INSIDE OF EXISTING GENERATOR CONTROL PANEL. LOOK FOR FLAGGING
E10 10 FOOT COIL FROM J-BOX TO BE LABELED "E10". TERMINATION BY OTHERS TERMINATE TO TERMINAL BLOCKS LABELED "E10" LOCATED INSIDE
EXISTING GENERATOR CONTROL PANEL. LOOK FOR FLAGGING
E33 CUT IN A DEEP METALLIC 2 GANG SWITCH BOX AT 60" AFF FOR GOVT SUPPLIED REMOTE PANEL FOR WATER TREATMENT SYSTEM.FEED IT WITH 3
CONDUCTOR CABLE FROM THE "WTCP". SEE SHEET E4.
E33
SEWAGE
TANK
SEWAGE
TANK
FUEL TANK
FUEL TANK
POTABLE
WATER TANK
POTABLE
WATER TANK
GENERATOR
GENERATOR
WINCH
MOTOR
W A
TE
R T
A N K
WASTE
WATER TANK
USDA FOREST SERVICE - TONGASS NATIONAL FOREST SH. ofR-10 -
DESIGNED: DATE:
DATE:DRAWN:
REVIEWED: DATE:
DATE: REVISION: BY:
PLOT ON 11"X17" PAPER
TONGASS
ENGINEERING & RECREATION TNFTYP:09/04
NAKWASINA BARGE IMPROVEMENTS LOWER DECK ELECTRICAL WORK ITEMS
TONGASS SUPERVISOR'S OFFICE
JJP DEC 2014
JJP DEC 2014 1/28/15 EDITED NOTES JJP
ACAD.DWG
E4 6
E1
WTCP
E2
E3
E7
E5
E20
TO
WTCP
TO
WTCP
TO
WTCP
D P
DP TO
WTCPE11
E12
JJ
TO
E10
UPSTAIRS
TO
INVERTER
PANEL
UPSTAIRS
SEE
E8
WORK ITEMS
E1 MOUNT AND WIRE IN GOVT SUPPLIED WATER TREATMENT CONTROL PANEL (WTCP)
E2 REMOVE ALL EXISTING FLOAT SWITCHES AND INSTALL NEW FLOAT SWITCH ASSEMBLY NORMALLY CLOSED INTO TANK HIGHEST INLET
E3 INSTALL NEW FLOAT SWITCH ASSEMBLY NORMALLY OPENED INTO THE LOWEST EXISTING INLET
E4 WIRE IN NEW PRESSURE SWITCH BY FILTRATION PUMP. WIRE SHALL GO TO "WTCP" AND NOT TO PUMP. COORDINATE WITH PLUMBING
E5 REMOVE EXISTING PLUMBING AND INSTALL NEW FLOAT SWITCH ASSEMBLY NORMALLY OPEN IN THE TANK LOWEST EXISTING INLET
E6 REMOVE EXISTING FLOAT SWITCHES AND INSTALL NEW PROXIMITY SWITCH. SEE DRAWING NOTE 4 AND DETAIL ON PAGE E1
E7 REMOVE EXISTING FLOAT SWITCH AND INSTALL NEW PROXIMITY SWITCH. SEE DRAWING NOTE 4 AND DETAIL ON PAGE E1
E11 REWIRE EXISTING MOTOR STARTER FOR DISTRIBUTION PUMP. CONTROL CIRCUIT FOR STARTER SHALL BE LOOPED TO " WTCP"
E12 REMOVE EXISTING CONTROL PANEL AND ALL UNUSED CABLES
E15 REWIRE EXISTING MOTOR STARTER FOR FILTRATION PUMP. CONTROL CIRCUIT FOR STARTER SHALL BE LOOPED TO" WTCP"
E16 CONNECT TWIST LOCK CONNECTOR BODY HUBBELL HBL2353/HBL60CM32 TO SHIPBOARD CABLE FOR CONNECTION TO VALVE
ASSEMBLY
TO
E9
UPSTAIRS
E19 WIRE IN NEW SOLENOID VALVE TO "WTCP". COORDINATE WITH PLUMBING
E20 REMOVE AND STORE EXISTING SHORE POWER CORD IN FWD HOLD
E21 REMOVED UNUSED ELECTRICAL EQUIPMENT
E22 REMOVE ABANDON CABLE
E23 INSTALL SQUARE D QO LOAD CENTER pn QO24L70RB W/ 30 AMP 2POLE BREAKER FOR GENERATOR SERVICE DISCONNECT ON 4kW
GENSET. 1 POLE SHALL BE FOR THE NEUTRAL.
E24 INSTALL SQUARE D QB3100BNRB W/ 80 AMP 3 POLE BREAKER FOR GENERATOR SERVICE DISCONNECT ON 20 kW GENSET.
CENTER POLE SHALL BE FOR THE NEUTRAL
E25 DRILL HOLES IN HEAT DETECTOR BASES TO ALIGN THEM TO THE JUNCTION BOXES
E30 BUILD VALVE ASSEMBLIES. ONE EACH FOR UNTREATED AND TREATED WATER INLETS SEE SHEETS E5 AND E6 FOR DETAILS
E34 REMOVE OLD FLOAT SWITCHES AND PLUG HOLES
FP
TO
WTCP
E15
E16
E16
E16 E16
J
E21
E22
E25 E25
E23
E24 E25
E25
E4
E19TO
WTCP
JE6
E34
TO
E33
UPSTAIRS
BUILD AND MOUNT
| NAKWASINA BARGE |
| Barge_DrinkingWaterSystem_Improvement |
| revised-E1_notes |
| revised-E3_main_deck_work_items |
| revised-E4_hold_work_items |
File details come from the government source that posted it. Updated .