CHICKAMIN BARGE
DRAWING ADDENDUMS
P1 – ADDING MISSING PRESSURE SWITCH
E1 – EDITED WORDING, ADDED SPARE PRESSURE SWITCH
E3 – EDITED HOW WORK ITEM “E10” TERMINATES, ADD
BATTERY REPLACEMENT
E4 – EDITED WORDING
ADDED 7 PAGES OF ELECTRICAL DRAWINGS FOR
BUILDING CONTROL PANEL
USDA FOREST SERVICE - TONGASS NATIONAL FOREST SH. ofR-10 -
DESIGNED: DATE:
DATE:DRAWN:
REVIEWED: DATE:
DATE: REVISION: BY:
PLOT ON 11"X17" PAPER
TONGASS
ENGINEERING & RECREATION TNFTYP:09/04
CHICKAMIN BARGE IMPROVEMENTS ELECTRICAL NOTES AND DETAILS
TONGASS SUPERVISOR'S OFFICE
JJP DEC 2014
JJP DEC 2014 1/28/15 EDITED NOTES JJP
ACAD.DWG
E1 6
GENERAL NOTES
1. ALL WIRING SHALL BE MIL-SPEC M24643 SHIPBOARD CABLE
2.UNLESS NOTED ELSEWHERE, ALL CONDUCTORS SHALL BE MINIMUM SIZE OF 4OO0
CMILS/14 A.W.G.
3. ALL UNUSED SHIPBOARD CABLE CAN BE REUSED PROVIDING THEY ARE UNDAMAGED
AND MEET CAPACITY AND CONDUCTOR COUNT.
4. ALL UNUSED CABLES FROM EXISTING WATER SYSTEM SHALL BE REMOVED
5. ALL UNUSED OPENING IN TANKS, THROUGH HULL PENETRATIONS, AND ELECTRICAL
ENCLOSURES SHALL BE SEALED BY APPROPRIATE WATER TIGHT PLUGS
6. ROUTE ALL NEW CABLE VIA EXISTING CABLE TRAYS AND HANGER. INSTALL NEW HANGERS
ONLY AS NEEDED
7. LOCATION OF WORK ITEMS ARE ON DRAWINGS ARE IN GENERAL ONLY. SITE
CONDITIONS DETERMINES EXACT LOCATION. COORDINATE WITH OTHER TRADES AS
NEEDED
8. WATER TREATMENT CONTROL PANEL CONNECTION SCHEMATIC WILL BE PROVIDE WITH
GOVT SUPPLIED CONTROL PANEL
9. GOVT SUPPLIED PANEL SHALL NOT BE LARGER THAN 24" X 24". ALL CABLES SHALL
ENTER THROUGH THE BOTTOM OF PANEL ONLY THROUGH APPROVED CORD GRIPS. LEAVE
SUFFICIENT AMOUNT OF CABLE FOR TERMINATING. LABEL BOTH ENDS OF CABLES WITH
WORK ITEM NUMBER
10. WIRING WITHIN THE HOUSE ABOVE THE MAIN DECK SHALL MEET 2014 NATIONAL
ELECTRICAL CODE. ALL EXTERIOR WIRING AND WIRING IN HOLD SHALL MEET CURRENT
AMERICAN BUREAU OF SHIPPING (ABS) RULES FOR STEEL VESSELS TO 45 METERS
11. PROVIDE ONE ADDITIONAL SPARE MADISON 8700 FLOAT SWITCH AND ONE
PROXIMITY SWITCH
DRAWING NOTES
1 WORK ITEMS ARE LOCATED IN UTILIDOR UNDER THE STAIRS. ACCESS IS LOCATED IN
SIDE HALLWAY
2 LEAVE ENOUGH SLACK IN CABLE TO CONNECT CONNECTOR BODY TO VALVE ASSEMBLY
PLUG
3 CABLE SHALL BE SHIELDED CABLE
4 SEE DETAIL BELOW
ABBREVIATIONS
DP - DISTRIBUTION PUMP
FP - FILTRATION PUMP
WTCP - WATER TREATMENT CONTROL PANEL
SYMBOL LEGEND
JUNCTION BOX
COMBINATION MOTOR STARTER DISCONNECT
WATER TREATMENT CONTROL PANEL
WATER TIGHT TWIST LOCK PLUG/RECEPTACLE
CABLE RUN - TICK MARKS = NUMBER OR CONDUCTORS
J
DP
WTCP
CRITICAL PARTS LIST
QUANT DESCRIPTION PART NUMBER WORK ITEM COMMENT
3 MADISON FLOAT SWITCH 8700 E2, E3,E5 UNIVERSAL MOUNT NO,NC
2 TELEMECANIQUE ULTRASONIC
PROXIMITY SWITCH SM952A166000 E6,E7 SEE DRAWING NOTE 4
4 HUBBELL CONNECTOR
BODY/WATERTIGHT BOOT HBL2353/HBL60CM32 E16
2 ASCO SOLENOID WATER VALVE EF8015B202 w/ 12 VDC
COIL SEE SHEETS NO. E5 AND E6 FOR INLET VALVE ASSEMBLIES
1 ASCO SOLENOID WATER VALVE 8212A055L1100F1 E14 HP UNTREATED FEED TO
FILTRATION
FLOAT SWITCH ASSEMBLY WORK ITEMS E2-E5
(EXPLODED VIEW)
SHIPBOARD CABLE
2" WATERTIGHT CORD GRIP
APPROPRIATE SIZE FOR CABLE
2" ELECTRICAL LB WITH COVER AND GASKET
FOR SPLICING WIRES
FLOAT SWITCH
MADISON 8700DCCP TB2
WORK ITEM E9 - DCCP TERMINATION
TB2 IS BOTTOM HORIZONTAL TERMINAL BUS
DRILL 30MM MINIMUM DIAMETER
HOLE FOR PROX SENSOR
2 INCH WHITE PVC
THREADED (NPT) MALE PLUG
4 WORK ITEM E6 & E7
DRILL HOLE AND INSERT PROX SWITCH
SCREW INTO NEW HUB IN TANKS
PANTRY 1
PANTRY 2
KITCHEN LIVING/DINING
LINENS
OFFICE
MECH
BATH 1
CLOSET
LAUNDRY/
MUDRM WORK
SHOP
USDA FOREST SERVICE - TONGASS NATIONAL FOREST SH. ofR-10 -
DESIGNED: DATE:
DATE:DRAWN:
REVIEWED: DATE:
DATE: REVISION: BY:
PLOT ON 11"X17" PAPER
TONGASS
ENGINEERING & RECREATION TNFTYP:09/04
CHICKAMIN BARGE IMPROVEMENTS MAIN DECK ELECTRICAL WORK ITEMS
TONGASS SUPERVISOR'S OFFICE
JJP DEC 2014
JJP DEC 2014 1/28/15 EDITED WORDING, ADD E40 JJP
ACAD.DWG
E3 6
E8
E10
WORK ITEMS
E8 120V 20 AMP GROUNDED CIRCUIT TO WATER TREATMENT CONTROL PANEL FROM INVERTER PANEL
E10 LEAVE 10 FOOT COIL FROM NEW J-BOX IN MAIN HOLD TO BE LABELED "E10". TERMINATION BY OTHERS TERMINATE TO TERMINAL BLOCKS LABELED
"E10 INSIDE OF BIG JUNCTION BOX "BJB"
E32 CUT INTO NEW CEILING TILE EXISTING JUNCTION BOX FOR SMOKE DETECTOR
E33 CUT IN A DEEP METALLIC 2 GANG SWITCH BOX AT 60" AFF FOR GOVT SUPPLIED REMOTE PANEL FOR WATER TREATMENT SYSTEM.FEED IT WITH 3
CONDUCTOR CABLE FROM THE "WTCP". SEE SHEET E4.
E40 REPLACE ALL 16 WET CELL BATTERIES IN KIND. CLEAN OR REPLACE INTERCONNECTING CABLES IN KING. REPROGRAM INVERTER
E32
E33
E40
SEWAGE
TANK
SEWAGE
TANK
FUEL TANK
FUEL TANK
POTABLE
WATER TANK
POTABLE
WATER TANK
GENERATOR
W A
TE
R T
A N K
WASTE
WATER TANK
GENERATOR
GENERATOR
USDA FOREST SERVICE - TONGASS NATIONAL FOREST SH. ofR-10 -
DESIGNED: DATE:
DATE:DRAWN:
REVIEWED: DATE:
DATE: REVISION: BY:
PLOT ON 11"X17" PAPER
TONGASS
ENGINEERING & RECREATION TNFTYP:09/04
CHICKAMIN BARGE IMPROVEMENTS LOWER DECK ELECTRICAL WORK ITEMS
TONGASS SUPERVISOR'S OFFICE
JJP DEC 2014
JJP DEC 2014 1/28/15 EDITED NOTES JJP
ACAD.DWG
E4 6
E1
WTCP
E2
E3
E5
TO
WTCP
TO
WTCP TO
WTCP
D P
DP TO
WTCPE11
E17
JJ
TO
E10
UPSTAIRS
TO
INVERTER
PANEL
UPSTAIRS
SEE
E8
WORK ITEMS
E1 MOUNT AND WIRE IN GOVT SUPPLIED WATER TREATMENT CONTROL PANEL (WTCP)
E2 REMOVE EXISTING FLOAT SWITCHES AND INSTALL NEW FLOAT SWITCH ASSEMBLY NORMALLY CLOSED INTO TANK HIGHEST INLET.
E3 INSTALL NEW FLOAT SWITCH ASSEMBLY NORMALLY OPENED INTO THE LOWEST EXISTING INLET
E4 WIRE IN NEW PRESSURE SWITCH BY FILTRATION PUMP. WIRE SHALL GO TO "WTCP" AND NOT TO PUMP. COORDINATE WITH PLUMBING
E5 REMOVE EXISTING FLOAT SWITCHES AND INSTALL NEW FLOAT SWITCH ASSEMBLY NORMALLY OPEN IN THE TANK LOWEST EXISTING
INLET
E6 INSTALL NEW PROXIMITY SWITCH IN NEW 2 INCH THREADED HUB. SEE DRAWING NOTE 4 AND DETAIL ON PAGE E1
E7 INSTALL NEW PROXIMITY SWITCH IN NEW 2 INCH THREADED HUB. SEE DRAWING NOTE 4 AND DETAIL ON PAGE E1
E11 REWIRE EXISTING MOTOR STARTER FOR DISTRIBUTION PUMP. CONTROL CIRCUIT FOR STARTER SHALL BE LOOPED TO "WTCP"
E14 DISCONNECT OLD SOLENOID VALVE WIRING.
E15 REWIRE EXISTING MOTOR STARTER FOR FILTRATION PUMP. CONTROL CIRCUIT FOR STARTER SHALL BE LOOPED TO "WTCP"
TO
"DCCP"
IN
AFT
HOLD
FPE15
E16
E16
E16 E16
J
J
E6
E7
D C
C P
E16 CONNECT TWIST LOCK CONNECTOR BODY HUBBELL HBL2353/HBL60CM32 TO SHIPBOARD CABLE FOR CONNECTION TO VALVE
ASSEMBLY
E17 REMOVE OLD GRAY WATER PUMP, STARTER, AND ASSOCIATED EQUIPMENT
E18 TERMINATE CABLE FROM "WTCP" IN "DC CONTROL PANEL" (DCCP) IN AFT HOLD. SEE DETAIL ON SHEET E1
E19 WIRE IN NEW SOLENOID VALVE TO "WTCP". COORDINATE WITH PLUMBING
E143
E18
E19
E4
TO
E33
UPSTAIRS
BUILD AND MOUNT