AE Drawings Perimeter Fence.pdf
PDF 7 MB Posted
- Solicitation number
- 36C10D23R0006
- Issued by
-
Department of Veterans Affairs
About this file
This statement of work outlines requirements for the installation of a perimeter fence at the St. Petersburg VA Regional Office. Key requirements include removing approximately 500 linear feet of existing vinyl fencing and fixtures; submitting shop drawings and as-built documentation; complying with safety standards in 29 CFR 1926 and EM 385-1-1; providing a site-specific safety plan and activity hazard analyses; disposing of waste in accordance with environmental regulations; and completing work between 6:00 pm and 6:00 am Monday through Friday except federal holidays. The contractor must enter and exit through the front entrance and pass security screening, and coordinate with the COR on scheduling, risk assessments for additional trades, and mishap reporting procedures. The government will provide parking, loading dock access, and a waste receptacle location, while the contractor must supply all tools and PPE. Work must adhere to directives in EM 385-1-1, 29 CFR 1926.20, and the AHA template from ORS.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 323119DecoMetalFencesGates.docx | DOCX document | |
| Detail.docx | DOCX document | |
| 36C10D23R0006 0005.docx | DOCX document | |
| SOW.pdf | ||
| Fence Layout 0005.pdf | ||
| 36C10D23R0006 0004.docx | DOCX document | |
| Fence Layout.pdf | ||
| 36C10D23R0006 0003.docx | DOCX document | |
| Revised RFIs 36C10D23R0006 0002.pdf | ||
| Statement of Work SOW.pdf | ||
| 36C10D23R0006 0002.docx | DOCX document | |
| S04 Sign in Roster 36D10D23R006.pdf | ||
| 36C10D23R0006 0001.docx | DOCX document | |
| AMIGUARD 5000 Brochure.pdf | ||
| SOW Perimeter Fence 3-24-23 Final.docx | DOCX document | |
| S02 P07 WD FL20230222 SAM.pdf | ||
| AMIGUARD 6000 _ 7000 Meshes.pdf | ||
| 36C10D23R0006_1.docx | DOCX document | |
| zS02 St Pete Perimeter Fence - PAST OR PRESENT PERFORMANCE SURVEY.pdf | ||
| Specs AE Perimeter Fence.pdf |
Show all 20
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
DRAWING LIST
X
1i
0 GRID / COLUMN LINE
DESIGNATOR
EQUIPMENT NUMBER
DOOR TAG
Ga5xFB1
WALL TYPE
WINDOW TYPE
ROOM NAME
101 ROOM NAME /
NUMBER
REVISION TAG
PLAN NORTH
NORTH ARROW WITH
TRUE NORTH INDICATION
EGRESS ROUTE ID
AND SECTION
LENGTH
ROOM
ROOM OCCUPANCY
150 SF
EGRESS : EGRESS ID
Egress Length
ROOM OCCUPANCY &
AREA
ELEVATION NUMBER
SECTION
INTERIOR ELEVATION
ENLARGEMENT,
DETAIL
SPOT ELEVATION
Name Elevation FLOOR LEVEL &
NAME
PLATE NUMBER WHERE
SECTION/DETAIL IS
DRAWN
PLATE NUMBER WHERE
SECTION/DETAIL IS
DRAWN
PLATE NUMBER WHERE
SECTION/DETAIL IS
DRAWN
SHEET KEYNOTE
A101
SIM
EXTERIOR ELEVATION
A-101
PLATE NUMBER WHERE
SECTION/DETAIL IS
DRAWN
INDEX OF DRAWINGS
DISCIPLINE:
G - GENERAL
C - CIVIL
L - LANDSCAPE
S - STRUCTURAL
A - ARCHITECTURE
P - PLUMBING
M - MECHANICAL
E - ELECTRICAL
T - TELECOM
Q - FOOD SERVICE
SHEET TYPE
DESIGNATOR
VICINITY MAP
PROJECT TEAMBUILDING SUMMARY
PROJECT INFORMATION
ANNOTATION DRAWING SYMBOLSGENERAL NOTES
PROJECT NAME: A&E DESIGN FOR SECURITY FENCE AT THE ST PETERSBURG VARO
PROJECT NUMBER: VB3237
PROJECT LOCATION: ST. PETERSBURG REGIONAL OFFICES
9500 BAY PINES BOULEVARD
ST. PETERSBURG, FL 33708
PROJECT PURPOSE/USE: DESIGN FOR SECURITY FENCE
1. THESE DRAWINGS SHALL BE USED ONLY FOR THIS SPECIFIC PROJECT/SITE LOCATION. THESE DRAWINGS ARE A COMPOSITE SET OF CONTRACT DOCUMENTS AND SHALL NOT BE SEPARATED FOR DISTRIBUTION. THE GC SHALL REVIEW ALL DRAWINGS AND PROVIDE/DISTRIBUTE THE ENTIRE SET TO EACH SUBCONTRACTOR.
2. THE GC SHALL VISIT THE SITE TO INSPECT EXISTING CONDITIONS AND VERIFY WORK BEING PERFORMED
BEFORE SUBMITTING COST QUOTATIONS FOR WORK.
3. NOTIFY THE ARCHITECT PROMPTLY OF ANY ERRORS, OMISSIONS, INCONSISTENCIES, DISCREPANCIES AND CONFLICTS WITHIN THE CONTRACT DOCUMENTS AND ITS ASSOCIATED FIELD/PROJECT CONDITIONS SO THAT
A RESOLUTION CAN BE PROVIDED PRIOR TO CONTINUING WITH WORK.
4. DO NOT SCALE THE DRAWINGS. REQUEST ANY MISSING DIMENSIONS FROM THE ARCHITECT
5. ALL WORK PERFORMED SHALL BE IN STRICT COMPLIANCE WITH GOVERNING FEDERAL, STATE AND LOCAL BUILDING CODE REQUIREMENTS, SHALL BE EXECUTED IN ACCORDANCE WITH ACCEPTED INDUSTRY STANDARDS, AND SHALL CONFORM TO SPECIFIC REGULATIONS AS MANDATED BY THE OWNER, THE ARCHITECT, AND THE AUTHORITIES HAVING JURISDICTION. THE GENERAL CONTRACTOR IS RESPONSIBLE FOR ANY FEES ASSOCIATED WITH PROCURING SUCH PERMITS AND CERTIFICATES AND SHALL FURNISH COPIES OF
PERMITS, INSPECTIONS, AND CERTIFICATES TO THE OWNER.
6. THE GENERAL CONTRACTOR SHALL COORDINATE ALL WORK TO MINIMIZE DISRUPTION OF OF ANY EXISTING TENANTS OR BUILDING OPERATIONS. THE GENERAL CONTRACTOR SHALL TAKE ADEQUATE PRECAUTIONS TO PROTECT BUILDING OCCUPANTS, MATERIALS, AND EXISTING CONSTRUCTION THROUGHOUT ALL PHASES OF CONSTRUCTION. DAMAGE TO EXISTING-TO-REMAIN CONSTRUCTION OR EQUIPMENT SHALL BE RESTORED TO
ORIGINAL CONDITION AT THE CONTRACTOR'S EXPENSE.
7. THE GENERAL CONTRACTOR SHALL REMOVE ALL TRASH AND DEBRIS FROM THE JOB SITE ON A DAILY BASIS.
8. ANY REQUESTS FOR SUBSTITUTIONS OF ANY SPECIFIED ITEM ARE TO BE SUBMITTED TO THE ARCHITECT IN WRITING AND WILL BE CONSIDERED ONLY IF THE ALTERNATE PROPOSED IS PROVEN TO BE ADVANTAGEOUS
TO THE OWNER WITH RESPECT TO DELIVERY DATE, QUALITY, OR COST.
9. THE MEANS AND METHODS OF CONSTRUCTION, AND TEMPORARY STRUCTURES AND FACILITIES, ARE THE RESPONSIBILITY OF THE GENERAL CONTRACTOR. THE ARCHITECT DOES NOT ASSUME ANY RESPONSIBILITY
FOR THE CONTRACTOR'S MEANS AND METHODS OR FOR TEMPORARY STRUCTURES.
10. DEMOLITION OF EXISTING STRUCTURES IS THE RESPONSIBILITY OF THE GENERAL CONTRACTOR. THE
CONTRACTOR SHALL EMPLOY ENGINEERING EXPERTISE AS NEEDED TO ASSIST IN DEMOLITION.
11. JOB SITE SAFETY AND SECURITY ARE THE SOLE RESPONSIBILITY OF THE GENERAL CONTRACTOR. THE GENERAL CONTRACTOR SHALL CONSULT WITH LOCAL FIRE AUTHORITIES TO ASCERTAIN REQUIREMENTS FOR FIRE SUPPRESSION AND SAFETY DURING CONSTRUCTION. THE GENERAL CONTRACTOR IS SOLELY
RESPONSIBLE FOR MEETING OSHA REGULATIONS DURING CONSTRUCTION.
12. THE GENERAL CONTRACTOR IS SOLELY RESPONSIBLE FOR STORAGE AND PROTECTION OF BUILDING MATERIALS, AND INSTALLED CONSTRUCTION, FROM INCLEMENT WEATHER, THEFT, AND OTHER HAZARDS. THE GC SHALL FOLLOW ALL MANUFACTURER'S RECOMMENDATIONS FOR STORAGE OF MATERIALS. PARTIALLY COMPLETED WALLS SHALL BE COVERED TO PROTECT FROM WATER INTRUSION. DAMAGE, INCLUDING BUT NOT LIMITED TO MOLD, RESULTING FROM WATER INTRUSION DURING CONSTRUCTION SHALL BE REPAIRED AT
THE GENERAL CONTRACTOR'S EXPENSE.
A101
A101
SHEET NUMBER
WITHIN SERIES
AE101
PURPOSE
NOT USED
NUMBER
Romanyk Consulting Focusing on what matters
0' 1'
6" 3"
1'
Gr ap hi c S ca le
: 1 /2"
1'-
0"
0' 4"
8" 1'
2'
Gr ap hi c S ca le
: 3 /32
1'
-0
0'
8' Gr ap hi c S ca le : 1
/16
1' -0
0' 8'
4' Gr ap hi c S ca le
: 1 /8"
1'-
0"
0' 2'
1' 4'
Gr ap hi c S ca le
: 1 /4"
1'-
0"
0' 2'
1' 4'
Gr ap hi c S ca le
: 3 /8"
1'-
0"
0' 2'
4' 1' Gr ap hi c S ca le : 1
/2"
1'- 0"
0' 1'
2' 6"
Gr ap hi c S ca le
: 3 /4"
1'-
0"
0' 1'
2' 6"
Gr ap hi c S ca le
: 1
1' -0
VA FORM 08 - 6231
F
E
D
C
B
A
F
E
D
C
B
A
910 7 6 5 4 3 2 1
8910 7 6 5 4 3 2 1
U.S. Department of Veterans Affairs
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
U.S. Department of Veterans Affairs
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093
Spinklered
Office of Construction and Facilities Management FULLY SPRINKLERED
BI
M
VB
A
- S t.
Pe te rs bu rg
S ec ur ity
F en ce /S t P et er sb ur g
Se cu rit y
Fe nc e
- V
.rv t 4/
6/
:5 4:
A
M
PROJECT NUMBER - VB3237
RCC OBLIGATION NUMBER - 36C10E18D019
RCC TASK ORDER NUMBER - 36C10E20N0198
A&E Design for Security Fence at the St. Petersburg VARO
100% CD
APRIL 09, 2021
BW TG
VB3237
46, 47
GI100ST. PETERSBURG, FL
APRIL 09, 2021
SHEET INDEX & GENERAL INFORMATION 100% CD A&E Design for Security Fence at the St. Petersburg VARO
STRUCTURAL ENGINEER:
IMEG - St. Louis Branch 15 Sunnen Drive, Suite 104 St. Louis, MO 63143
Kurtis Minton kurtis.w.minton@imegcorp.com
314-279-9917
OWNER:
Department of Veterans Affairs St. Petersburg Regional Office 9500 Bay Pines Boulevard St. Petersburg, FL 33708
Danny Wert, VBASPT Danny.Wert@va.gov
727-319-7988
SHEET # SHEET TITLE
GENERAL
GI100 SHEET INDEX & GENERAL INFORMATION
GI101 LIFE SAFETY PLAN
STRUCTURAL
S-100 GENERAL NOTES AND DETAILS
S-101 SITE PLAN AND TYPICAL DETAILS
S-102 DETAILS
S-103 DETAILS
ARCHITECTURAL
AS100 SITE ORIENTATION PLAN
AD100 DEMOLITION PLAN - SECTION A
AD101 DEMOLITION PLAN - SECTION B
AD102 DEMOLITION PLAN - SECTION C
AD103 DEMOLITION PLAN - SECTION D
AE100 SECURITY FENCE PLANS - SECTION A
AE101 SECURITY FENCE PLANS - SECTION B
AE102 SECURITY FENCE PLANS - SECTION C
AE103 SECURITY FENCE PLANS - SECTION D
AE200 SECURITY FENCE ELEVATIONS
AE201 SECURITY FENCE ELEVATIONS
AE400 GATE DETAILS
AE401 GATE DETAILS
AE402 GATE DETAILS
AE403 SECURITY FENCE DETAILS
ELECTRICAL
E100 ELECTRICAL SYMBOLS AND ABBREVIATIONS
ED100 LIGHTING & POWER DEMOLITION - SECTION A
ED101 LIGHTING & POWER DEMOLITION - SECTION C
ED102 LIGHTING & POWER DEMOLITION - SECTION D
ES100 ELECTRICAL SITE PLAN -DEMO
ES101 ELECTRICAL SITE PLAN
EL100 LIGHTING PLAN - SECTION A
EL101 LIGHTING PLAN - SECTION B
EL102 LIGHTING PLAN - SECTION C
EL103 LIGHTING PLAN - SECTION D
EP100 POWER AND SYSTEMS PLAN - SECTION A
EP101 POWER AND SYSTEMS PLAN - SECTION B
EP102 POWER AND SYSTEMS PLAN - SECTION C
EP103 POWER AND SYSTEMS PLAN - SECTION D
E-401 ENLARGED ELECTRICAL POWER PLANS
E-402 ENLARGED ELECTRICAL POWER PLANS
E-403 ENLARGED ELECTRICAL POWER PLANS
E-601 ELECTRICAL DETAILS AND SCHEDULES
Grand total: 39
ARCHITECT:
Romanyk Consulting Corp.
3308 Preston Road, Suite 350-164 Plano, Texas
Barrett Webb barrett.webb@romanykconsulting.com
855-424-3838 ext 318
ELECTRICAL ENGINEER:
Romanyk Consulting Corp.
3308 Preston Road, Suite 350-164 Plano, Texas 75093
Jonathan Foster jonathan.foster@romanykconsulting.com
855-424-3838 ext 307
15 SUNNEN DR SUITE 104
SAINT LOUIS, MO 63143
314.645.1132 FAX: 314.645.1173
www.imegcorp.com # 17002665.02Revisions: Date:
EA
ST
G
AT
E
UP
LEGEND
EAST GATE DRIVE
EXISTING
EXISTIN
G
EXISTING
EXISTING
EXISTIN
G
EX
IS
TI
N
G
EX
IS
TI
N
G
TRAVEL DISTANCE= 145'-9"
TRAVEL
DISTANCE= 80
'-6
TRAVEL DISTANCE= 207'-5"
TRAVEL D
ISTANCE= 1
'-5
TRAVEL DISTANCE= 153'-6"
TRAVEL DISTANCE= 115'-0"
TRAVEL DISTANCE= 125'- 6"
TRAVEL D
ISTANCE= 1
'- 6"
MAXIMUM TRAVEL DISTANCEX'-X"
EGRESS DIRECTIONAL ARROW
TRAVEL DISTANCE START CIRCLE
TRAVEL PATH
ILLUMINATED EXIT SIGN
0' 1'
6" 3"
1'
Gr ap hi c S ca le
: 1 /2"
1'-
0"
0' 4"
8" 1'
2'
Gr ap hi c S ca le
: 3 /32
1'
-0
0'
8' Gr ap hi c S ca le : 1
/16
1' -0
0' 8'
4' Gr ap hi c S ca le
: 1 /8"
1'-
0"
0' 2'
1' 4'
Gr ap hi c S ca le
: 1 /4"
1'-
0"
0' 2'
1' 4'
Gr ap hi c S ca le
: 3 /8"
1'-
0"
0' 2'
4' 1' Gr ap hi c S ca le : 1
/2"
1'- 0"
0' 1'
2' 6"
Gr ap hi c S ca le
: 3 /4"
1'-
0"
0' 1'
2' 6"
Gr ap hi c S ca le
: 1
1' -0
Romanyk Consulting Focusing on what matters
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
F
U.S. Department of Veterans Affairs
E
D
C
B
A
F
E
D
C
B
A
910 7 6 5 4 3 2 1
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
8910 7 6 5 4 3 2 1
Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093
Spinklered
Office of Construction and Facilities Management
NORTH
FULLY SPRINKLERED
BI
M
VB
A
- S t.
Pe te rs bu rg
S ec ur ity
F en ce /S t P et er sb ur g
Se cu rit y
Fe nc e
- V
.rv t 4/
6/
:5 4:
A
M
BW TG
VB3237
46, 47
GI101ST. PETERSBURG, FL
APRIL 09, 2021
LIFE SAFETY PLAN 100% CD A&E Design for Security Fence at the St. Petersburg VARO
1" = 30'-0"1 LIFE SAFETY PLAN
15 SUNNEN DR SUITE 104
SAINT LOUIS, MO 63143
314.645.1132 FAX: 314.645.1173
www.imegcorp.com # 17002665.02
0' 15' 30' 60'
Graphic Scale : 1" = 30'-0"
Revisions: Date:
1. NEITHER THE PROFESSIONAL ACTIVITIES OF THE ENGINEER, NOR THE PRESENCE OF THE
ENGINEER OR THEIR EMPLOYEES AND SUBCONSULTANTS AT THE CONSTRUCTION SITE,
SHALL RELIEVE THE CONTRACTOR AND ANY OTHER ENTITY OF THEIR OBLIGATIONS,
DUTIES AND RESPONSIBILITIES INCLUDING BUT NOT LIMITED TO, CONSTRUCTION MEANS,
METHODS, SEQUENCE, TECHNIQUES OR PROCEDURES NECESSARY FOR PERFORMING,
SUPERINTENDING OR COORDINATING ALL PORTIONS OF THE CONSTRUCTION WORK IN
ACCORDANCE WITH THE CONTRACT DOCUMENTS AND ANY HEALTH OR SAFETY
PRECAUTIONS REQUIRED BY ANY REGULATORY AGENCIES. THE ENGINEER AND THEIR
PERSONNEL HAVE NO AUTHORITY TO EXERCISE ANY CONTROL OVER ANY
CONSTRUCTION CONTRACTOR OR OTHER ENTITY OR THEIR EMPLOYEES IN CONNECTION
WITH THEIR WORK OR ANY HEALTH OR SAFETY PRECAUTIONS. THE CONTRACTOR IS
SOLELY RESPONSIBLE FOR THE JOBSITE SAFETY. THE ENGINEER AND THE ENGINEER’S
CONSULTANTS SHALL BE MADE ADDITIONAL INSUREDS UNDER THE CONTRACTOR’S
GENERAL LIABILITY INSURANCE POLICY.
2. ALL DRAWINGS ARE CONSIDERED TO BE A PART OF THE CONTRACT DOCUMENTS. THE
GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR THE REVIEW AND COORDINATION
OF ALL DRAWINGS PRIOR TO THE START OF CONSTRUCTION. ANY DISCREPANCIES SHALL
BE BROUGHT TO THE ATTENTION OF THE ARCHITECT PRIOR TO THE START OF
CONSTRUCTION SO A CLARIFICATION CAN BE ISSUED. ANY WORK PERFORMED IN
CONFLICT WITH THE CONTRACT DOCUMENTS OR ANY CODE REQUIREMENTS SHALL BE
CORRECTED BY THE CONTRACTOR AT THEIR OWN EXPENSE AND AT NO EXPENSE TO THE
OWNER OR ARCHITECT.
3. ALL DIMENSIONS AND SITE CONDITIONS SHALL BE VERIFIED BY THE CONTRACTOR AT THE
JOBSITE PRIOR TO CONSTRUCTION, START OF SHOP DRAWINGS, START OF
CONSTRUCTION, AND/OR FABRICATION OF MATERIALS. IF DISCREPANCIES ARE
ENCOUNTERED, OR CONDITIONS DEVELOP THAT ARE NOT COVERED BY THE CONTRACT
DOCUMENTS, THE ARCHITECT SHALL BE NOTIFIED FOR CLARIFICATION.
4. CONTRACTOR SHALL PROVIDE AND BE RESPONSIBLE FOR THE PROTECTION AND REPAIR
OF ADJACENT EXISTING SURFACES AND AREAS WHICH MAY BE DAMAGED AS A RESULT
OF NEW WORK.
5. STRUCTURAL DRAWINGS INCLUDE DESIGN REQUIREMENTS AND DIMENSIONS FOR
STRUCTURAL INTEGRITY BUT DO NOT SHOW ALL DETAIL DIMENSIONS TO FIT INTRICATE
ARCHITECTURAL AND MECHANICAL DETAILS. CONTRACTOR SHALL SO CONSTRUCT THE
WORK SO IT WILL CONFORM TO THE CLEARANCES REQUIRED BY ARCHITECTURAL,
MECHANICAL AND ELECTRICAL DESIGN.
6. ALL SYMBOLS AND ABBREVIATIONS USED ON THE DRAWINGS ARE CONSIDERED TO BE
CONSTRUCTION STANDARDS. IF CLARIFICATION IS REQUIRED, THE CONTRACTOR SHALL
NOTIFY THE ARCHITECT PRIOR TO PROCEEDING WITH THE WORK.
7. DO NOT SCALE DRAWINGS. PRINTED DIMENSIONS HAVE PRECEDENCE OVER SCALED
DRAWINGS AND LARGE-SCALE OVER SMALL-SCALE DRAWINGS. CONTRACTOR TO
DETERMINE FINAL DIMENSION WITH ARCHITECT.
8. TYPICAL DETAILS SHALL APPLY TO SITUATIONS OCCURRING ON THE PROJECT THAT ARE
THE SAME OR SIMILAR TO THOSE SPECIFICALLY REFERENCED. WHERE NO DETAILS ARE
GIVEN, CONSTRUCTION SHALL BE AS SHOWN FOR SIMILAR WORK.
9. THE CONTRACT DOCUMENTS REPRESENT THE FINISHED STRUCTURE. THEY DO NOT
INDICATE THE METHOD OF CONSTRUCTION. THE CONTRACTOR SHALL PROVIDE ALL
MEASURES NECESSARY TO PROTECT THE STRUCTURE AND SAFETY OF WORKMEN
DURING CONSTRUCTION. SUCH MEASURES SHALL INCLUDE, BUT NOT BE LIMITED TO,
BRACING AND SHORING FOR LOADS DUE TO CONSTRUCTION EQUIPMENT, ETC.
OBSERVATION VISITS TO THE SITE BY THE ARCHITECT OR STRUCTURAL ENGINEER SHALL
NOT INCLUDE INSPECTION OR APPROVAL OF THE ABOVE ITEMS AND DOES NOT IN ANY
WAY RELIEVE THE CONTRACTOR OF THEIR RESPONSIBILITIES FOR THE ABOVE.
10. SEE ARCHITECTURAL, ELECTRICAL AND MECHANICAL DRAWINGS FOR DETAILS,
CONDITIONS, PITS, TRENCHES, PADS, DEPRESSIONS, ROOF/FLOOR OPENINGS, STAIRS,
SLEEVES, ITEMS TO BE EMBEDDED OR ATTACHED TO STRUCTURAL ELEMENTS, ETC., NOT
SHOWN ON THE STRUCTURAL DRAWINGS.
11. ESTABLISH AND VERIFY ALL OPENINGS AND INSERTS FOR MECHANICAL, ELECTRICAL AND
PLUMBING WITH APPROPRIATE TRADE CONTRACTORS. OPENING SIZES AND LOCATIONS
SHOWN FOR DUCTS, PIPE, INSERTS AND OTHER PENETRATIONS WHEN SHOWN ARE FOR
GENERAL INFORMATION ONLY AND SHALL BE VERIFIED PRIOR TO FORMING.
12. NO HOLES, NOTCHES, BLOCKOUTS, ETC. ARE ALLOWED IN STRUCTURAL ELEMENTS
UNLESS SPECIFICALLY DETAILED ON THE STRUCTURAL DRAWINGS OR APPROVED BY THE
STRUCTURAL ENGINEER.
13. BEFORE SUBMITTING A PROPOSAL FOR THIS WORK, EACH BIDDER SHALL VISIT THE
PREMISES AND BECOME FULLY ACQUAINTED WITH THE EXISTING CONDITIONS,
TEMPORARY CONSTRUCTION REQUIRED, QUANTITIES AND TYPE OF EQUIPMENT, ETC. THE
BID SHALL INCLUDE ALL SUMS REQUIRED TO DO THE WORK WITHIN THE EXISTING
CONDITIONS.
14. SHOP DRAWINGS SHALL BE REVIEWED AND COORDINATED PRIOR TO SUBMITTING TO THE
ARCHITECT. EACH SHOP DRAWING SUBMITTED SHALL BE STAMPED INDICATING REVIEW
BY THE CONSTRUCTION MANAGER/GENERAL CONTRACTOR AND REVIEW BY THE
ARCHITECT SHALL NOT BEGIN UNTIL THIS IS COMPLETE. WORK SHALL NOT BEGIN
WITHOUT REVIEW BY THE ARCHITECT/STRUCTURAL ENGINEER.
15. SHOP DRAWINGS SHALL BE REVIEWED BY THE ARCHITECT/STRUCTURAL ENGINEER FOR
GENERAL CONFORMANCE WITH DESIGN CONCEPT ONLY. NOTATIONS MADE BY THE
ARCHITECT/STRUCTURAL ENGINEER ON THE SHOP DRAWINGS DO NOT RELIEVE THE
CONTRACTOR FROM COMPLYING WITH THE REQUIREMENTS OF THE DRAWINGS.
16. ELEVATIONS ARE BASED ON THE TOP OF SLAB ON GRADE ELEVATION OF (+0' - 0").
17. EXISTING CONDITIONS:
A. EXISTING STRUCTURAL INFORMATION SHOWN WAS OBTAINED FROM EXISTING
BUILDING 46 DRAWINGS DATED SEPTEMBER 15, 1994 BY TILDEN, LOBNITZ, & COOPER,
INC. EXISTING BUILDING 47 DRAWINGS DATED MAY 19, 2006 BY MASTER CONSULTING
ENGINEERS, INC.
B. EXISTING STRUCTURAL INFORMATION SHOWN WAS OBTAINED FROM FIELD TAKE-OFF
BY IMEG AS PERMITTED BY ACCESS RESTRICTIONS DURING DESIGN.
C. ALL INFORMATION SHOWN ON THE DRAWINGS RELATIVE TO EXISTING CONDITIONS IS
GIVEN AS THE BEST PRESENT KNOWLEDGE. CONTRACTOR TO VERIFY EXISTING
INFORMATION, DIMENSIONS AND SIZES AS REQUIRED TO COMPLETE THEIR WORK.
WHERE ACTUAL CONDITIONS CONFLICT WITH THE DRAWINGS, THEY SHALL BE
REPORTED TO THE ARCHITECT OR STRUCTURAL ENGINEER SO PROPER
CLARIFICATION MAY BE MADE. MODIFICATION OF CONSTRUCTION DETAILS SHALL NOT
BE MADE WITHOUT WRITTEN APPROVAL OF THE ARCHITECT OR STRUCTURAL
ENGINEER.
GENERAL
DEMOLITION
1. ALL DEMOLITION SHALL BE CARRIED OUT IN SUCH A WAY AS TO NOT DAMAGE
EXISTING ELEMENTS WHICH ARE TO REMAIN.
2. ALL ELEMENTS WHICH ARE TO REMAIN AND WHICH ARE DAMAGED DURING
DEMOLITION WORK SHALL BE REPLACED AT NO ADDED COST. EXISTING
ELEMENTS ARE TO BE PROTECTED TO THE FULLEST EXTENT POSSIBLE TO
REDUCE SUCH DAMAGE TO A MINIMUM.
1. STRUCTURE HAS BEEN DESIGNED TO COMPLY WITH:
FLORIDA BUILDING CODE 2020
ASCE/SEI 7- 16
ACI 318- 14
AWS D1.1
2. WIND:
RISK CATEGORY III (BUILDING 46 & 47 ARE "LIFE SAFETY")
BASIC WIND SPEED 154 MPH
IMPORTANCE FACTOR 1.0
EXPOSURE CLASS C
DESIGN WIND PRESSURE 55 PSF
(CH. 29 - SOLID FREESTANDING
WALL PROCEDURE)
DESIGN CRITERIA AND LOADS
1. FOUNDATION DESIGN IS BASED ON THE GEOTECHNICAL REPORT DATED NOVEMBER 6, 2020 BY TERRACON
CONSULTANTS, INC. REPORT IS ON FILE WITH THE ARCHITECT.
2. SOIL PROPERTIES PER THE GEOTECHNICAL REPORT:
ALLOWABLE NET SOIL BEARING PRESSURE:
FOOTINGS 2000 PSF
DEPTH TO ALLOWABLE
SOIL BEARING 1'-6" FT BELOW EXISTING GRADE
EQUIVALENT FLUID PRESSURE 50 PCF
LATERAL BEARING PRESSURE 150 PSF/FT, SEE FLORIDA BUILDING CODE 1806.2
COEFFICIENT OF FRICTION 0.4
3. ALL EXCAVATIONS SHALL BE PROPERLY AND SAFELY BACKFILLED. DO NOT PLACE BACKFILL BEHIND RETAINING/BASEMENT WALLS BEFORE CONCRETE HAS ATTAINED SPECIFIED COMPRESSIVE STRENGTH.
CONTRACTOR SHALL BRACE OR PROTECT ALL WALLS BELOW GRADE FROM LATERAL LOADS UNTIL
SUPPORTING FLOORS ARE COMPLETELY IN PLACE AND HAVE ATTAINED 7-DAY STRENGTH MINIMUM.
BACKFILLING IS NOT PERMITTED FOR FOUNDATION WALLS UNTIL SUPPORTED SLAB TOP AND BOTTOM IS IN PLACE OR THE WALL IS ADEQUATELY BRACED TO RESIST LATERAL LOADS. CONTRACTOR SHALL PROVIDE
FOR DESIGN, PERMITS, AND INSTALLATION OR SHORING AND/OR SHEETING.
4. CONTRACTOR SHALL PROVIDE FOR DE-WATERING OF EXCAVATIONS FROM SURFACE WATER, GROUND WATER OR SEEPAGE. FREE GROUND WATER WAS NOT ENCOUNTERED IN THE BORINGS. DETAILS OF GROUND WATER INFORMATION CAN BE OBTAINED FROM THE ABOVE MENTIONED GEOTECHNICAL REPORT.
IF GROUND WATER SHOULD OCCUR DURING EXCAVATION, SPECIAL PROCEDURES SHALL BE IMPLEMENTED
AS RECOMMENDED BY THE GEOTECHNICAL ENGINEER OF RECORD.
5. CONTRACTOR SHALL INVESTIGATE SITE DURING CLEARING AND EARTHWORK OPERATIONS FOR FILL MATERIAL OR BURIED STRUCTURES SUCH AS CESSPOOLS, CISTERNS AND FOUNDATIONS. IF ANY SUCH MATERIAL OR STRUCTURES ARE FOUND, ARCHITECT SHALL BE NOTIFIED IMMEDIATELY. ALL ABANDONED FOOTINGS, UTILITIES AND OTHER STRUCTURES THAT INTERFERE WITH NEW CONSTRUCTION SHALL BE
REMOVED.
6. EXTREME CARE SHALL BE EXERCISED WHEN EXCAVATING OR GRADING ADJACENT TO EXISTING
STRUCTURES OR IMPROVEMENTS TO NOT DAMAGE OR UNDERMINE FOUNDATIONS, WALLS, SLABS,
UTILITIES, ETC.
7. ALL FOOTINGS SHALL BE PLACED ONTO FIRM UNDISTURBED SOIL OR CONTROLLED COMPACTED FILL, REMOVING ANY EXISTING FILL OR UNSUITABLE SOILS, AS RECOMMENDED BY THE GEOTECHNICAL REPORT.
EXCAVATIONS FOR FOOTINGS SHALL BE INSPECTED AND APPROVED BY THE INSPECTION AGENCY PRIOR TO PLACING CONCRETE. CONTRACTOR SHALL NOTIFY INSPECTION AGENCY WHEN EXCAVATION IS READY
FOR TESTING. INSPECTION AGENCY TO SUBMIT LETTER OF COMPLIANCE TO THE OWNER.
8. FOOTING ELEVATIONS SHOWN DESIGNATE A MINIMUM DEPTH WHERE AN ADEQUATE SOIL BEARING PRESSURE IS EXPECTED. FOOTINGS, PIERS AND/OR WALLS SHALL BE LOWERED OR EXTENDED AS
REQUIRED TO REACH SOIL MEETING THE DESIGN BEARING PRESSURE.
9. THE MOISTURE CONTENT OF ONSITE CLAYEY SOILS AT THE TIME OF COMPACTION SHALL BE BETWEEN 2-3%
ABOVE OPTIMUM MOISTURE CONTENT.
10. ANY IMPORT FILL SOIL REQUIRED SHALL HAVE A LOW POTENTIAL FOR EXPANSION AND SHALL BE
APPROVED BY THE GEOTECHNICAL ENGINEER OF RECORD PRIOR TO IMPORTING.
11. ALL UNACCEPTABLE MATERIAL AND ORGANIC MATERIAL SHALL BE REMOVED FROM BELOW ALL PROPOSED SLABS-ON-GRADE. THE EXPOSED NATURAL SOIL SHALL BE PROOF-ROLLED AND THE COMPACTION VERIFIED BY AN INSPECTION AGENCY PRIOR TO PLACING FILL. AREAS EXHIBITING WEAKNESS SHALL BE
REMOVED AND REPLACED BY ACCEPTABLE COMPACTED FILL.
12. ALL SITE WORK SHALL BE PERFORMED UNDER THE INSPECTION OF THE SPECIAL INSPECTION AGENCY.
VARIATIONS IN SITE CONDITIONS AND THE GEOTECHNICAL REPORT SHALL BE REPORTED TO THE
ARCHITECT/STRUCTURAL ENGINEER FOR CLARIFICATIONS PRIOR TO PROCEEDING.
EARTHWORK
REINFORCING STEEL
1. ALL REINFORCING STEEL SHALL BE DETAILED AND PLACED IN CONFORMANCE WITH THE AMERICAN CONCRETE INSTITUTE “ACI DETAILING MANUAL” (SP-066) EXCEPT AS OTHERWISE SHOWN, NOTED OR
SPECIFIED.
2. CONCRETE REINFORCING STEEL SHALL BE HIGH STRENGTH NEW BILLET STEEL CONFORMING TO THE
FOLLOWING STANDARDS:
DEFORMED BARS ASTM A615, GR60 Fy = 60 KSI EPOXY-COATED BARS ASTM A775 Fy = 60 KSI
3. MINIMUM CONCRETE COVER SHALL BE PROVIDED AS FOLLOWS TO THE OUTERMOST REINFORCING BARS:
CAST AGAINST AND PERMANENTLY IN CONTACT WITH GROUND 3"
EXPOSED TO WEATHER OR IN CONTACT WITH GROUND
#6 BARS OR LARGER 2"
#5 BARS OR SMALLER 1 1/2"
4. BAR SPLICES SHALL BE PROVIDED WHERE INDICATED ON THE DRAWINGS. ALL SPLICES SHALL BE CLASS 'B' AS DEFINED IN ACI 318. IF SPLICE LENGTH IS NOT GIVEN ON THE DRAWINGS, PROVIDE LAP LENGTH (IN
INCHES) AS FOLLOWS:
LAP LENGTHS ASSUME CLEAR SPACING BETWEEN BARS OF 2 BAR DIAMETERS, AND A MINIMUM COVER OF 1 BAR DIAMETER. FOR DEVELOPMENT LENGTHS, DIVIDE BY 1.3. TOP BARS ARE DEFINED AS HORIZONTAL BARS
WITH MORE THAN 1'-0" OF FRESH CONCRETE BELOW.
5. PROVIDE ADEQUATE TIES FOR ALL REINFORCING BARS AND STIRRUPS IN CONCRETE SLABS AND BEAMS.
ANCHOR BOLTS, DOWELS, REINFORCING STEEL, INSERTS, ETC., SHALL BE SECURELY TIED IN PLACE PRIOR TO POURING CONCRETE. CONCRETE BLOCKS SHALL ONLY BE USED TO SUPPORT REINFORCING OFF
GRADE.
6. SUPPORTS FOR REINFORCEMENT SHALL HAVE CLASS 2 PROTECTION AS DEFINED IN THE CRSI MANUAL OF
STANDARD PRACTICE, UNO.
7. CONTINUOUS REINFORCING SHALL BE LAPPED AT MIDSPAN FOR TOP BARS AND DIRECTLY OVER THE
SUPPORT FOR BOTTOM BARS.
8. DOWELS BETWEEN FOOTINGS AND WALLS OR COLUMNS SHALL BE THE SAME GRADE, SIZE AND SPACING
OR NUMBER AS THE VERTICAL REINFORCING, RESPECTIVELY, UNO.
9. REINFORCING IN CONTINUOUS FOOTINGS BETWEEN FENCE POSTS SHALL EXTEND INTO POST
FOUNDATIONS A MINIMUM OF 2 FEET.
10. REINFORCING IN FOOTINGS SHALL BE ACCURATELY PLACED, SPACED, SUPPORTED AND SECURED BEFORE
PLACING CONCRETE.
11. CUTTING OF REINFORCING WHICH CONFLICTS WITH EMBEDDED OBJECTS IS NOT ACCEPTABLE.
12. REINFORCING BARS SHALL BE BENT COLD, AND NO METHOD OF FABRICATION SHALL BE USED WHICH WOULD BE INJURIOUS TO THE MATERIAL. HEATING OF BARS FOR BENDING IS NOT PERMITTED.
13. FIELD WELDING OR BENDING OF REINFORCING IS NOT PERMITTED EXCEPT AS INDICATED ON THE
DRAWINGS OR AS APPROVED BY THE STRUCTURAL ENGINEER.
14. SUBMIT SHOP DRAWINGS FOR FABRICATION AND PLACEMENT OF REINFORCING STEEL. INCLUDE SCHEDULES AND DIAGRAMS OF BENT BARS AND SHOW ARRANGEMENT OF REINFORCEMENT. STRUCTURAL ENGINEER’S REVIEW WILL BE FOR COMPLIANCE WITH DESIGN REQUIREMENTS. THE CONTRACTOR SHALL
BE RESPONSIBLE FOR VERIFYING DIMENSIONS AND QUANTITIES.
CAST-IN-PLACE CONCRETE
1. ALL CONCRETE WORK SHALL CONFORM TO THE AMERICAN CONCRETE INSTITUTE
PUBLICATIONS: ACI 117, ACI 301, ACI 305.1, ACI 306.1, ACI 308.1, ACI 318 AND SP-066, UNO.
2. CONCRETE MATERIALS SHALL CONFORM TO:
CEMENT ASTM C150, TYPE I OR II
FLY ASH ASTM C618, TYPE C OR F
FINE AND COARSE AGGREGATE ASTM C33
WATER POTABLE
AIR-ENTRAINING ADMIXTURE ASTM C260
WATER-REDUCING ADMIXTURE ASTM C494
3. CONCRETE STRENGTHS SHALL CONFORM TO, UNO:
4. DRYPACK SHALL BE 1:3-1/2 PORTLAND CEMENT TO SAND WITH A MINIMUM 28-DAY STRENGTH OF
7000 PSI.
5. GROUT SHALL BE 1:3:2 PORTLAND CEMENT TO SAND TO PEA GRAVEL WITH A MINIMUM 28-DAY
STRENGTH OF 7000 PSI.
6. CROSS REFERENCE ARCHITECTURAL AND STRUCTURAL DRAWINGS TO ASSURE PROPER
DIMENSIONS AND PLACEMENT OF ALL ANCHOR BOLTS, INSERTS, NOTCHES, EDGES OF
WALLS/GRADE BEAMS AND PIERS.
7. UNO, ALL FOOTINGS SHALL BE CENTERED UNDER WALLS, PIERS OR COLUMNS.
8. SANDBLAST ALL EXISTING CONCRETE SURFACES OLDER THAN 28 DAYS AGAINST WHICH
CONCRETE IS TO BE PLACED, UNLESS DIRECTED OTHERWISE IN WRITING BY THE STRUCTURAL
ENGINEER.
9. PROVIDE SLEEVES FOR PLUMBING AND ELECTRICAL PENETRATIONS THROUGH CONCRETE
BEFORE PLACING. SECURE SUCH SLEEVES TO PREVENT MOVEMENT DURING PLACING
OPERATIONS. REFER TO MECHANICAL AND ELECTRICAL DRAWINGS FOR LOCATIONS OF
PENETRATIONS.
10. CORE DRILLING CONCRETE IS NOT PERMITTED UNLESS NOTED OTHERWISE OR APPROVED IN WRITING BY THE ARCHITECT. NOTIFY THE ARCHITECT IN ADVANCE OF CONDITIONS NOT SHOWN
ON THE DRAWINGS.
11. CONFIRM WITH ARCHITECT THAT MATERIALS TO BE EMBEDDED ARE SUITABLE FOR EMBEDMENT
IN CONCRETE.
12. THE OUTSIDE DIAMETER OF EMBEDDED CONDUIT OR PIPE SHALL NOT EXCEED 1/3 OF THE
STRUCTURAL SLAB THICKNESS, INCLUDING AT CROSS-OVERS, AND SHALL BE PLACED BETWEEN
THE TOP AND BOTTOM REINFORCING WITH A MINIMUM 3” CLEAR COVER. CONDUIT OR PIPE
RUNNING PARALLEL TO EACH OTHER SHALL BE SPACED AT LEAST 8” APART AND NO MORE THAN 2 RUNS STACKED VERTICALLY IN THE SLAB. CONDUIT OR PIPE SHALL NOT BE EMBEDDED IN SLAB
THICKNESSES LESS THAN 6 INCHES.
13. DO NOT PLACE PIPES, DUCTS, REGLETS OR CHASES IN STRUCTURAL CONCRETE WITHOUT
APPROVAL OF THE STRUCTURAL ENGINEER THROUGH THE ARCHITECT.
14. PROJECTING CORNERS OF BEAMS, WALLS, COLUMNS, ETC., SHALL BE FORMED WITH A 3/4 INCH
CHAMFER, UNLESS NOTED OTHERWISE ON ARCHITECTURAL DRAWINGS.
15. SLOPE SLABS TO DRAINS OR FOR POSITIVE DRAINAGE IF NO DRAINS ARE PRESENT, AND
PROVIDE DEPRESSIONS WHERE SHOWN ON THE STRUCTURAL AND/OR ARCHITECTURAL
DRAWINGS, WITHOUT REDUCING THE THICKNESS OF SLAB INDICATED. FOR SLAB-ON-GRADE
DEPRESSIONS GREATER THAN 1 INCH, REFER TO DETAILS FOR ADDITIONAL REINFORCING.
16. CONCRETE SHALL NOT BE PERMITTED TO DROP MORE THAN 5 FEET.
17. CONCRETE SLABS SHALL BE CURED BY KEEPING CONTINUOUSLY WET FOR 7 DAYS. FORMS FOR
CONCRETE WALLS SHALL BE LEFT IN PLACE FOR 7 DAYS OR MAY BE STRIPPED AFTER 3 DAYS
AND COATED WITH AN APPROVED CURING COMPOUND.
18. NOTIFY THE ARCHITECT/STRUCTURAL ENGINEER 48 HOURS MINIMUM PRIOR TO ALL POURS.
19. THE DESIGN AND ENGINEERING OF FORMWORK, AS WELL AS ITS CONSTRUCTION, SHALL BE THE
RESPONSIBILITY OF THE CONTRACTOR. FORMS SHALL BE DESIGNED TO HAVE SUFFICIENT
STRENGTH TO SAFELY WITHSTAND THE LOADS RESULTING FROM PLACEMENT AND VIBRATION
OF THE CONCRETE, AND SHALL ALSO BE DESIGNED FOR SUFFICIENT RIGIDITY TO MAINTAIN
SPECIFIED TOLERANCES. CONTRACTOR SHALL SUBMIT DETAILED FORMWORK SHOP DRAWINGS
TO THE ARCHITECT TO BE REVIEWED FOR GENERAL COMPLIANCE WITH THE DESIGN CONCEPT
ONLY.
20. NO CONCRETE SHALL BE PLACED ONTO OR AGAINST SUBGRADES CONTAINING FREE WATER,
FROST, ICE OR SNOW.
21. THE CONCRETE CONTRACTOR SHALL FURNISH MIX DESIGN SHOP DRAWINGS FOR REVIEW.
BAR
SIZE
OTHER TOP
3000 PSI CONCRETE
OTHER TOP
4000 PSI CONCRETE
#4 29 38 25 33
#5 36 47 31 41
#6 43 56 37 49
INTENDED USE
28-DAY
STRENGTH (PSI)
MAX W/C
RATIO
A/E SLUMP
FOUNDATIONS
SLAB-ON-GRADE
UNLESS NOTED OTHERWISE
0.5
0.45
0.45
5-8%
N/A
5-8%
4"-6"
1"-4"
1"-4"
STRUCTURAL TESTS AND INSPECTION
1. UNLESS NOTED, MATERIALS SHALL CONFORM AND TESTS AND INSPECTIONS SHALL BE
PERFORMED BY THE INSPECTION AGENCY WHO IS APPROVED THE ARCHITECT AND THE
STRUCTURAL ENGINEER. CONTINUOUS AND PERIODIC TESTING AND INSPECTION SHALL
CONFORM TO IBC CHAPTER 17, AND AS FOLLOWS:
A. CONCRETE CONSTRUCTION 1704.4 1705.3
B. SOILS 1704.7 1705.6
C. WIND RESISTANCE 1705.10 1705.11
2. REFER TO ARCHITECTURAL, CIVIL, AND ELECTRICAL DRAWINGS OR SPECIFICATIONS FOR
TESTING AND INSPECTION REQUIREMENTS OF NON-STRUCTURAL COMPONENTS.
3. DUTIES OF THE INSPECTION AGENCY PER IBC CHAPTER 17:
A. SUBMIT A PROPOSED TESTING AND INSPECTION PROGRAM TO THE OWNER, THE
ARCHITECT AND THE STRUCTURAL ENGINEER FOR REVIEW AND APPROVAL AT LEAST TWO
WEEKS PRIOR TO COMMENCEMENT OF WORK.
B. PERFORM ALL TESTING AND INSPECTION REQUIRED PER APPROVED TESTING AND
INSPECTION PROGRAM.
C. FURNISH INSPECTION REPORT TO THE BUILDING OFFICIAL, THE OWNER, THE ARCHITECT,
STRUCTURAL ENGINEER AND THE GENERAL CONTRACTOR. THE REPORTS SHALL BE
COMPLETED AND FURNISHED WITHIN 48 HOURS OF INSPECTED WORK.
D. SUBMIT A FINAL SIGNED REPORT STATING WHETHER THE WORK REQUIRING SPECIAL
INSPECTION WAS, TO THE BEST OF THE SPECIAL INSPECTION AGENCY’S KNOWLEDGE, IN
CONFORMANCE WITH THE APPROVED PLANS AND SPECIFICATIONS.
STEEL
1. STRUCTURAL STEEL SHALL BE DETAILED IN ACCORDANCE WITH THE AMERICAN
INSTITUTE OF STEEL CONSTRUCTION (AISC) “DETAILING FOR STEEL
CONSTRUCTION” AND FABRICATED AND ERECTED IN ACCORDANCE WITH THE
“SPECIFICATION FOR STRUCTURAL STEEL BUILDINGS”.
2. STRUCTURAL STEEL SHALL CONFORM TO ASTM STANDARDS AS NOTED BELOW:
BASE AND CONNECTION PLATES ASTM A36 Fy = 36 KSI
ELECTRODES FOR ARC WELDING AWS 5.1, E70XX
3. STANDARD BOLT HOLES IN STEEL SHALL BE 1/16 INCH LARGER IN DIAMETER THAN
NOMINAL SIZE OF BOLT USED, UNO.
4. ALL WELDS SHALL CONFORM TO THE AMERICAN WELDING SOCIETY “STRUCTURAL
WELDING CODE - STEEL” (AWS D1.1), “STRUCTURAL WELDING CODE - SEISMIC
SUPPLEMENT” (AWS D1.8), AND BE MADE WITH APPROVED ELECTRODES.
5. WELD LENGTHS INDICATED ON THE DRAWINGS ARE THE NET EFFECTIVE LENGTH
REQUIRED. WHERE FILLET WELD SYMBOL IS GIVEN WITHOUT INDICATION OF SIZE,
USE MINIMUM SIZE WELDS AS SPECIFIED IN AISC 360, SECTION J2.4.
6. ALL WELDING OF STRUCTURAL STEEL SHALL BE PERFORMED BY CERTIFIED
WELDERS WITH EXPERIENCE AND CERTIFICATION IN THE TYPES OF WELDING
CALLED FOR. WELDERS SHALL HAVE BEEN RECENTLY QUALIFIED AS PRESCRIBED
IN “QUALIFICATION PROCEDURES” OF THE AMERICAN WELDING SOCIETY (AWS).
7. ALL STEEL EXPOSED TO WEATHER SHALL BE HOT-DIP GALVANIZED AFTER
FABRICATION. ABRADED AREAS TO BE TOUCHED UP WITH GALVALOY. ALL
HOLLOW SECTIONS SHALL HAVE WELDED CAP PLATES TO SEAL EXPOSED ENDS.
8. PAINT STEEL PER ARCHITECTS SPECIFICATIONS.
POST-INSTALLED ANCHORS
1. ANCHORS SERVING AS THE BASIS OF DESIGN ARE SHOWN ON THE DRAWINGS. ACCEPTABLE
ALTERNATIVE ANCHORS MAY BE SUPPLIED PROVIDED THE QUANTITY AND CONFIGURATION
MATCH THE CAPACITY OF THE DESIGN ANCHOR QUANTITY AND CONFIGURATION. ANY
ALTERNATES ARE TO BE SUBMITTED TO THE STRUCTURAL ENGINEER FOR REVIEW. INSTALL IN
ACCORDANCE WITH MANUFACTURER’S WRITTEN INSTRUCTIONS. BELOW SUMMARIZES EACH
ANCHOR TYPE USED ON THE PROJECT.
2. MECHANICAL ANCHORS:
EXPANSION ANCHORS
THREADED SCREW ANCHORS
ANCHORED
INTO
BASIS OF DESIGN ACCEPTABLE ALTERNATES
UNCRACKED
CONCRETE
HILTI KWIK BOLT 3 [ESR-2302]
DEWALT POWER STUD+ SD2 [ESR-2502]
RED HEAD TRUBOLT+ [ESR-2427]
SIMPSON STRONG BOLT 2 [ESR-3037]
CRACKED
CONCRETE
HILTI KWIK BOLT TZ [ESR-1917]
DEWALT POWER STUD+ SD2 [ESR-2502]
RED HEAD TRUBOLT+ [ESR-2427]
SIMPSON STRONG BOLT 2 [ESR-3037]
ANCHORED
INTO
BASIS OF DESIGN ACCEPTABLE ALTERNATES
UNCRACKED
CONCRETE
HILTI KWIK HUS-EZ [ESR-3027]
DEWALT POWER SCREW-BOLT+ [ESR-3889]
SIMPSON TITEN HD [ESR-2713]
CRACKED
CONCRETE
DEWALT POWER SCREW-BOLT+ [ESR-3889]
SIMPSON TITEN HD [ESR-2713]
HILTI KWIK HUS-EZ [ESR-3027]
STRUCTURAL ABBREVIATION KEY
LONG SIDE HORIZONTAL
LONG SIDE VERTICAL
LOW
LONGITUDINAL
LIGHTWEIGHT
MACHINE BOLT
MAXIMUM
MANUFACTURER
MINIMUM
METAL
NORTH
NEW
NOT IN CONTRACT
NOT TO SCALE
ON CENTER
OPPOSITE HAND
OPENING
PIECE
POUNDS PER CUBIC FOOT
PLATE
POUNDS PER LINEAR FOOT
PARTIAL JOINT PENETRATION WELD
POUNDS PER SQUARE FOOT
POUNDS PER SQUARE INCH
RADIUS
REINFORCING, -MENT, -ED
REQUIRED
TC WITH CLASS A FAYING SURFACE
SCHEDULE
SEPARATION
SIMILAR
SLAB ON GRADE
SPACE(S)
SPECIFICATION(S)
SQUARE
STIFFENER
STEEL
SUPPORT
SYMMETRICAL
TOP AND BOTTOM
TOP OF
TOP OF WALL
PRE-TENSIONED BOLT
TEMPERATURE
THICK
TRANSVERSE
TYPICAL
UNLESS NOTED OTHERWISE
VERTICAL
VERIFY IN FIELD
VERIFY WITH ARCHITECTURAL DRAWINGS
WITH
WORK POINT
WEIGHT
WELDED WIRE REINFORCING
ABBR: DESCRIPTION: ABBR: DESCRIPTION:
LSH
LSV
LO
LONG
LT WT
M.B.
MAX
MANUF
MIN
MTL
N (N)
NIC
NTS
OC
OH
OPNG
PC
PCF
PL
PLF
P.P.
PSF
PSI
R
REINF
REQD
SC
SCHED
SEP'N
SIM
SOG
SP
SPEC
SQ
STIFF
STL
SUPPT
SYM
T&B T.O.
T.O.W.
TC
TEMP
THK
TRANS
TYP
UNO
VERT
VIF
VWA
W/
WP
WT
WWR
NUMBER OR POUNDS
AT
DEGREE
DIAMETER
SLAB DEPRESSION
ANCHOR BOLT
ARCHITECT, -URE, -URAL
BOTTOM OF
BEAM
BOTTOM OF FOOTING
BOTTOM
BASE PLATE
BETWEEN
CLEAR
CENTERLINE
COLUMN
CONCRETE
CONTINUOUS
COMPLETE JOINT PENETRATION WELD
DIAMETER
DIMENSION
DEAD LOAD
DETAIL
DRAWING
DOWEL
EACH
EACH FACE
ELEVATION
EQUAL
EACH WAY
EXISTING
EXPANSION
EXTERIOR
CONCRETE COMPRESSIVE STRENGTH
FOUNDATION
FINISH, -ED
FLOOR
FACE OF WALL
FOOT
FOOTING
YIELD STRESS
GAGE OR GAUGE
GALVANIZED
GRADE BEAM
HIGH
HORIZONTAL
HIGH STRENGTH BOLT
INCH
JOINT
KILOPOUND (1,000 POUNDS)
KIPS PER SQUARE FOOT
POUND
LIVE LOAD
LONG LEG HORIZONTAL
LONG LEG VERTICAL
Ø -3" A.B.
ARCH
B.O.
BM
B.O.F.
BOTT
BP
BTWN
CLR
CL
COL
CONC
CONT
C.P.
DIA
DIM
DL
DET
DWG
DWL
EA
EF
EL
EQ
EW
(E)
EXP
EXT
f 'c
FDN
FIN
FLR
F.O.W.
FT
FTG
Fy
GA
GALV
GB
HI
HORIZ
HSB
IN
JT
K, KIP
KSP
LB
LL
LLH
LLV
PLAN OR DETAIL NUMBER
PLAN OR DETAIL NAME
PLAN OR DETAIL SCALE
DETAIL REFERRED TO BY SECTION CUT
SHEET DETAIL IS LOCATED ON
NAME
VIEW NAME
1/8" = 1'-0"
S300
SIM
INDICATES SIMILAR DETAIL REFERENCED
IN MULTIPLE LOCATIONS
LEVEL NAME
10' - 0" HEIGHT ABOVE
PROJECT 0' - 0"
INDICATES NOTE USED TO DESCRIBE
ADDITIONAL INFORMATION ABOUT
WORK REQUIRED, SPECIFIC TO THE
SHEET AND/OR DETAIL
INDICATES DIRECTION OF TRUE NORTH
VIEW KEY
LINE TYPE KEY:
NEW WORK
(DARK SOLID LINE)
NEW WORK UNDERGROUND OR UNDER OTHER FRAMING AND EXISTING TO BE
REMOVED
(DARK DASHED LINE)
EXISTING TO REMAIN
(LIGHT SOLID LINE)
GRID OR CENTERLINE
MATERIAL LEGEND:
CONCRETE - CAST-IN-PLACE
CONCRETE - EXISTING
EARTH
GRAVEL OR GRANULAR FILL
MASONRY
STEEL
GROUT OR DRYPACK OR SAND
N O R
HT
G ra p h ic S ca le
/2
0"
G ra p h ic S ca le
/3 2"
0"
' G ra p h ic S ca le
/1 6"
0"
' G ra p h ic
S ca le
/8
0"
G ra p h ic S ca le
/4
0"
G ra p h ic S ca le
/8
0"
' G ra p h ic
S ca le
/2
0"
G ra p h ic S ca le
/4
0"
G ra p h ic S ca le
0"
Romanyk Consulting Focusing on what matters
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
F
U.S. Department of Veterans Affairs
E
D
C
B
A
F
E
D
C
B
A
910 7 6 5 4 3 2 1
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
8910 7 6 5 4 3 2 1
Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093
NOT FOR
PERMITTING OR
CONSTRUCTION
Spinklered
PLAN NORTH
ST. PETERSBURG, FL
Office of Construction and Facilities Management
46, 47
FULLY SPRINKLERED
C
R e v it
L o c a l F il e s \S
.0
V
B A
R O
S E
C U
R
IT
Y F
E N
C E
C
K u rt is .W
.M in to n
.r v t
/6
/2
:0 :2
A
M
GENERAL NOTES AND ABBREVIATIONS
KATGOL ELITRE
100% CD VB3237
S-100
A&E Design for Security Fence at the
St. Petersburg VARO
APRIL 9, 2021
15 SUNNEN DR SUITE 104
SAINT LOUIS, MO 63143
314.645.1132 FAX: 314.645.1173
www.imegcorp.com # 18004378.01Revisions: Date:
This item has been electronically signed and sealed by Heather Heidenreich using a Digital Signature and date. Printed copies of this document are not considered signed and sealed and all signatures must be verified on any electronic copies.
EXP 02/28/23
EXISTING
CHILLING
TOWER
EXISTING
BUILDING
46 "A"
EXISTING
BUILDING
46 "B"
EXISTING
BUILDING
46 "D"
EXISTING
BUILDING
46 "C"
EXISTING
BUILDING
EXISTING
OUTDOOR
MECHANICAL
EQUIPMENT
UP
A
SECTION A
8' - 0" MAX
24"Ø SONOTUBE
FOUNDATION, TYP
UNO
M
IN
SECURITY FENCE
BY OTHERS - SEE ARCH
FOR BASIS OF DESIGN
C L
R(6) #5 VERTICAL, TYP
#4 TIES @ 12" OC, TYP
1 1/2" CLR
12" x 12" CONTINUOUS
FOOTING - SEE SECTION B
FOR REINFORCING
M
IN
P O
S T
E M
B E
D
EL (SEE ARCH)
T.O. FOOTING
#5 DOWELS AT EACH
CONTINUOUS FOOTING
BAR - CONTINUOUS BAR
NOT SHOWN FOR CLARITY
EL (SEE ARCH)
T.O. FENCE
B
C L
R T
Y P
1' - 6"
24"Ø TYP, UNO
90 DEGREE HOOK
12"
1/2" TOOLED
RADIUS
(2) #5 CONT.
T&B
3" CLR
C L R
SECTION B
#4 TIES 16" OC
8' - 0" MAX
M
IN
SEE
FOR FOUNDATION
REINFORCING
M
IN
P O
S T
E M
B E
D
EL (SEE ARCH)
T.O. FOOTING
EL (SEE ARCH)
T.O. FENCE
6"
1/S-101
#5 BENT DOWELS AT
EACH CONTINUOUS
FOOTING BAR12" x 12"
CONTINUOUS
FOOTING - SEE
1/S-101
1' - 6" 8
1' - 0"
#5 BAR
8"
LAP SPLICE
CLASS B
#4 TIES @
12" OC
M
A X
R
IS
E
S -1
S -102
S-1
S-102
S-102
4'
6"
4' - 6"
G B1
G B1
G B1
G B1G
B13' - 0"
DP3.5
DP3.5
4'
6"
4' - 6"
P3
P7
W F4
W F4
W F4
P7
W F3
P3
P7
P3
P7
P9
PLANTER
P9 P9
S-102
P39
S-103
S-102
S-102
P39
S-103
P3
S-102
3' - 0"
3' - 0"
DP3.5
DP3.5
DP3.5
S-102
S-102
TYP @ CONT
FOOTINGS
W F4
(E) PAVEMENT
S-102
P9
S-102TYP @ PILE
CAPS
S-102
S-102
P39
S-103
S-103
DP3.5
EXISTING FOUNDATION SCHEDULE
MARK
5' - 8" (3 SIDES) x 36"
SIZE ( L x W x T )
( -3' - 2" )
T.O. FOUNDATION EL (UNO)
3/S-102
DETAIL
P3
P7
P9
WF3
WF4
GB1
9' - 8" x 8' - 8" x 41"
9' - 8" x 9' - 8" x 51"
CONT x 3' - 0" x 24"
CONT x 4' - 0" x 16"
CONT x 4' - 0" x 48"
REMARKS
PLINTH ON DRILLED CONCRETE PIER
TRIANGULAR PILE CAP
SQUARE PILE CAP
SQUARE PILE CAP
CONTINUOUS FOOTING
CONTINUOUS FOOTING
GRADE BEAM
3' - 6"Ø
( -2' - 0" )
( -2' - 0" )
( -2' - 0" )
( -2' - 0" )
( -2' - 0" )
( -3' - 2" )
( -2' - 0" )P39 58' - 0" x 16' - 0" x 48" MAT FOUNDATION
3/S-102
3/S-102
3/S-102
4/S-102
4/S-102
4/S-102
3/S-102
NOTES:
1. SEE 4/S103 FOR TYPICAL LIGHT POLE FOUNDATION DETAIL.
2. SEE THIS SHEET FOR TYPICAL FENCE POST DETAILS.
3. TYPICAL SLAB ON GRADE IS 5" THICK REINFORCED WITH WWR. TOP OF SLAB ELEVATION (+0' - 0").
4. DENOTES PATH OF NEW SECURITY FENCE. SEE ARCH.
5. ALL EXISTING DIMENSIONS AND ELEVATIONS TO BE FIELD VERIFIED. COORDINATE ALL NEW
DIMENSIONS AND ELEVATIONS WITH ARCH DRAWINGS.
KEYNOTES:
1. (E) 4" SLAB ON GRADE WITH WWR.
G ra p h ic S ca le
/2
0"
G ra p h ic S ca le
/3 2"
0"
' G ra p h ic S ca le
/1 6"
0"
' G ra p h ic
S ca le
/8
0"
G ra p h ic S ca le
/4
0"
G ra p h ic S ca le
/8
0"
' G ra p h ic
S ca le
/2
0"
G ra p h ic S ca le
/4
0"
G ra p h ic S ca le
0"
Romanyk Consulting Focusing on what matters
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
F
U.S. Department of Veterans Affairs
E
D
C
B
A
F
E
D
C
B
A
910 7 6 5 4 3 2 1
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
8910 7 6 5 4 3 2 1
Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093
NOT FOR
PERMITTING OR
CONSTRUCTION
Spinklered
PLAN NORTH
ST. PETERSBURG, FL
Office of Construction and Facilities Management
46, 47
FULLY SPRINKLERED
C
R e v it
L o c a l F il e s \S
.0
V
B A
R O
S E
C U
R
IT
Y F
E N
C E
C
K u rt is .W
.M in to n
.r v t
/6
/2
:0 :2
A
M
SITE PLAN AND TYPICAL DETAILS
KATGOL ELITRE
100% CD VB3237
S-101
A&E Design for Security Fence at the
St. Petersburg VARO
APRIL 9, 2021
15 SUNNEN DR SUITE 104
SAINT LOUIS, MO 63143
314.645.1132 FAX: 314.645.1173
www.imegcorp.com # 18004378.01Revisions: Date:
3/4" = 1'-0"
TYPICAL FENCE POST FOUNDATION DETAIL
3/4" = 1'-0"
TYPICAL FOUNDATION STEP DETAIL
1" = 30'-0"
SITE PLAN
This item has been electronically signed and sealed by Heather Heidenreich using a Digital Signature and date. Printed copies of this document are not considered signed and sealed and all
18"Ø CONCRETE PIER
PAPER JOINT
(E) SLAB ON GRADE - SEE NOTE 1,
(E) GRADE WHERE OCCURS
ROUND OFF TOP OF
CONCRETE INFILL
PIPE 6 STD WITH
CONCRETE INFILL
M A
T C
H E
X
IS
T
IN
G
M
IN
M A
X
EQ EQ
BOLLARD FINISH TO
MATCH EXISTING
1/2" EXPANSION JOINT
MATERIAL
NOTES:
1. DEMO EXISTING SLAB AS NECESSARY FOR
INSTALLATION OF PIPE BOLLARD AND FOUNDATION.
2. SEE ARCH FOR NEW BOLLARD LOCATIONS.
PIPE BOLLARD AND
FOUNDATION - SEE
1/S-102
1/2" EXPANSION
JOINT MATERIAL
REPLACE ROLLED
CURB IN LIKE KIND OR
PER VA STANDARD
(E) PAVEMENT GRADE
NOTE:
1. SEE ARCH FOR NEW BOLLARD AND CURB LOCATIONS.
SEE 1/S-101 FOR
FOUNDATION
REINFORCING. DO NOT
INCLUDE #5 DOWELS.
24"Ø
NOTES:
1. DEMO EXISTING SLAB AS NECESSARY FOR INSTALLATION OF
FENCE POST AND FOUNDATION.
2. DEMO EXISTING CURB AS NECESSARY FOR INSTALLATION OF
FENCE POST AND FOUNDATION. REPLACE EXISTING CURB TO
MATCH EXISTING.
SECURITY FENCE BY
OTHERS - SEE ARCH
FOR BASIS OF DESIGN
(E) SLAB ON GRADE
SEE NOTE 1
1/2" EXPANSION
JOINT MATERIAL
(V
IF
(E) CURB BEYOND
WHERE OCCURS
SEE NOTE 2
CENTER POST IN
FOUNDATION
M
IN
(V
A R
IE
S
(E) CONCRETE PILES
4" W-SHAPE SECURITY
FENCE POST BY
OTHERS - SEE ARCH
(E) PILE CAP -
SEE SCHEDULE
ON S-101
(E) COLUMN FACADE
(E) STEEL COLUMN WITH
BASEPLATE AND ANCHOR
BOLTS
CORE DRILL (E) SLAB ON
GRADE AND (E)
CONCRETE PILE CAP.
SET POST AND FILL
WITH GROUT.
EL ( 0' - 0" )
T.O. SLAB
EL ( -2' - 0" ), (VIF)
T.O. PILE CAP
ROUGHEN EDGES
M
IN
P O
S T
E M
B E
D
M
IN
8" Ø
NOTE 1
NOTE:
1. PLACE SECURITY FENCE POST AS CLOSE TO EXISTING FACADE AS
POSSIBLE.
EL ( 0' - 0" )
T.O. SLAB
EL ( SEE SCHED ), (VIF)
OR GRADE BEAM
T.O. FOOTING
(E) CONTINUOUS
FOOTING, GRADE BEAM
WHERE OCCURS
(E) CONCRETE SLAB
SEE NOTE 1
(E) CMU WALL,
CONCRETE WHERE
OCCURS
(E) CONCRETE PILE
WHERE OCCURS
M
IN
V A
R
IE
S
CORE DRILL (E) CONCRETE PILE CAP AS
NECESSARY. SET POST AND FILL WITH
GROUT TO TOP OF PILE CAP. PLACE
REINFORCING AND POUR CONCRETE
FOUNDATION TO TOP OF (E) SLAB.
18"Ø POST FOUNDATION - SEE 1/S-101
FOR REINFORCING. DOWEL AND EPOXY
VERTICAL BARS INTO CONTINUOUS
FOOTING OR GRADE BEAM 6" EMBED MIN.
4" W-SHAPE SECURITY
FENCE POST BY
OTHERS - SEE ARCH
NOTE:
1. DEMO EXISTING SLAB AS NECESSARY FOR INSTALLATION OF FENCE
POST AND FOUNDATION.
2. PLACE SECURITY FENCE POST AS CLOSE TO EXISTING WALL WHERE
OCCURS AS POSSIBLE.
OFFSET POST FROM
CENTERLINE OF FOOTING
AS NECESSARY. POST
MUST REMAIN CONFINED
IN REBAR TIES.
8" Ø
M
IN
P O
S T
E M
B E
D
M
IN
NOTE 2
12"x12" CONTINUOUS
FOOTING - SEE 1/S-101,
REINFORCEMENT NOT
SHOWN FOR CLARITY
SEE 1/S-101, FOR
REINFORCING SIZE AND
DIMENSIONS
M
IN
S T
A N
D A
R D
H E
IG
H
T
HINGE CLEARANCE
SEE ARCH
LATCH
SEE ARCH
SEE 1/S-101, FOR
REINFORCING SIZE AND
DIMENSIONS
(E) PAVEMENT
HINGE CLEARANCE
VARIES (FIELD VARIFY)
12' - 0"
(E) DEMO EXISTING CURB AND
SIDEWALK AS NECESSARY FOR
INSTALLATION OF SWING GATE
FOUNDATION. REPLACE PER
SIDEWALK AND CURB DETAILS
ON SHEET S-103. POUR CURB
AND SIDEWALK OVER FENCE
POST FOUNDATION.
M
IN
VARIES (FIELD VARIFY)
12' - 0"
LATCH CLEARANCE
SET POST IN LINE WITH CURB.
SEE 1/S103 FOR CURB DETAIL.
NEW GUARD RAIL
SEE ARCH
(E) CONC CURB
EL ( 0' - 0" )
T.O. SLAB
(E) PAVEMENT
GALVANIZED A36 STEEL
PL1/4" x 3" x 0' - 7" WITH (2) 5/8"
HILT KWIK HUS-EZ (GALV)
ANCHORS, 3 1/2" NOMINAL
EMBEDMENT. 1" ANCHOR
EDGE DISTANCE FROM EDGE
OF STEEL PLATE. PAINT
STEEL PER ARCH.
3/16
(E) 5" THICK SLAB ON GRADE
MIN
3"
SEE 1/S-101, FOR
REINFORCING SIZE AND
DIMENSIONS
M
IN
3' - 0"
12"x12" CONTINUOUS
FOOTING. SEE 1/S-100
FOR REINFORCING. (E)
SLAB OR (E) PAVEMENT
TO REMAIN WHERE
OCCURS.
NOTE:
1. WHERE DOOR OCCURS AT EXISTING FOUNDATIONS,
CROSS REFERENCE DETAILS 3 & 4 THIS SHEET FOR
FOUNDATION DETAILING.
G ra p h ic S ca le
/2
0"
G ra p h ic S ca le
/3 2"
0"
' G ra p h ic S ca le
/1 6"
0"
' G ra p h ic
S ca le
/8
0"
G ra p h ic S ca le
/4
0"
G ra p h ic S ca le
/8
0"
' G ra p h ic
S ca le
/2
0"
G ra p h ic S ca le
/4
0"
G ra p h ic S ca le
0"
Romanyk Consulting Focusing on what matters
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
F
U.S. Department of Veterans Affairs
E
D
C
B
A
F
E
D
C
B
A
910 7 6 5 4 3 2 1
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
8910 7 6 5 4 3 2 1
Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093
NOT FOR
PERMITTING OR
CONSTRUCTION
Spinklered
PLAN NORTH
ST. PETERSBURG, FL
Office of Construction and Facilities Management
46, 47
FULLY SPRINKLERED
C
R e v it
L o c a l F il e s \S
.0
V
B A
R O
S E
C U
R
IT
Y F
E N
C E
C
K u rt is .W
.M in to n
.r v t
/6
/2
:0 :2
A
M
DETAILS
KATGOL ELITRE
100% CD VB3237
S-102
A&E Design for Security Fence at the
St. Petersburg VARO
APRIL 9, 2021
15 SUNNEN DR SUITE 104
SAINT LOUIS, MO 63143
314.645.1132 FAX: 314.645.1173
www.imegcorp.com # 18004378.01
1/2" = 1'-0"
PIPE BOLLARD
1 1/2" = 1'-0"
PIPE BOLLARD WITH CURB
2 1/2" = 1'-0"
FENCE POST FOUNDATION
AT EXISTING SLAB
3 3/4" = 1'-0"
FENCE POST FOUNDATION
AT EXISTING PILE CAP
4 3/4" = 1'-0"
FENCE POST FOUNDATION AT EXISTING
CONTINUOUS FOOTING OR GRADE BEAM
1/2" = 1'-0"
DOUBLE GATE POST FOUNDATION
6 1/2" = 1'-0"
SWING GATE POST FOUNDATION
7 1" = 1'-0"
NEW GUARDRAIL DETAIL
Revisions: Date:
1/2" = 1'-0"
SWING GATEPOST
FOUNDATION
This item has been electronically signed and sealed by Heather Heidenreich using a Digital Signature and date. Printed copies of this document are not considered signed and sealed and all
LEVEL AREA
5' - 0" MIN 35' - 0" MAX AT 1:20
LEVEL AREA
5' - 0" MIN
1' - 0"
HANDRAIL - SEE ARCH
B
A
SECTION A
SECTION B
HANDRAIL, TYP
6"x6" - MW19xMW19 WWR
COMPACTED SUBGRADE
4" MIN WITH RAIL, TYP
8" MIN WITH RAIL 4' - 0"
1/2" BEVEL, TYP
/2
" 2% MAX
SLOPE
NOTES:
1. RAMP IS REQUIRED WHERE THE WALK EXCEEDS 3%.
2. IF A RAMP RUN HAS A RISE GREATER THAN 6" OR A HORIZONTAL PROJECTION GREATER THAN 72", THEN IT SHALL HAVE HANDRAILS ON BOTH SIDES.
3. MAXIMUM SLOPE OF RAMP SHALL NOT EXCEED 8.33%.
4. SEE ARCHITECTURAL STANDARDS FOR HANDRAIL DETAILS.
5. PROVIDE AN AGGREGATE BASE WHERE SUBSURFACE CONDITIONS WARRANT IT.
6. COORDINATE DETAIL WITH ARCHITECTURAL RAMP DETAIL.
1/2" R
EL ( 0' - 0" )
T.O. (E) SLAB
EL ( -2' - 0" )
T.O. (E) FOUNDATION
EL ( 8' - 0" ) - VIF
T.O. (E) OPENING
(E) OPENING IN SHEAR WALL
Px30096P GATE POST - SEE ARCH
(E) 12" THICK CAST-IN-PLACE
CONCRETE SHEAR WALL
S-103
S-103
SIM
3" x 12 GA ANTI-CLIMB STEEL PLATED SQUARE POST (Px30096P). 6" SQUARE, 1/4" THICK BASE PLATE
PROVIDED BY FENCE MANUFACTURER. ANCHOR TO
WALL WITH (4) 1/2" HILTI KWIK HUS-EZ ANCHORS. 3
1/2" NOMINAL EMBEDMENT. 1 1/4" EDGE DISTANCE
FROM ANCHOR TO EDGE OF PLATE.
NOTE:
1. AT SIM, DETAIL OCCURS AT TOP OF FENCE POST.
HAVE FENCE MANUFACTURER PROVIDE A STEEL
CAP PLATE AT TOP END OF POST AND ANCHOR
TO CONCRETE AT TOP OF WALL OPENING PER
THIS DETAIL.
12" THICK CAST-IN-PLACE
CONCRETE WALL
EL ( 0' - 0" )
WALL OPENING
T.O. (E) SLAB / B.O.
EL ( -0' - 5" )
B.O. (E) SLAB
SECTION VIEW
PLAN VIEW
REFER TO SECTION BELOW
CONTRACTOR SHALL USE TEMPLATE
FURNISHED WITH POLE TO SET ANCHOR
BOLTS. CENTER POLE ON CONCRETE BASE.
ANCHOR BOLTS FOR POLE AS
REQUIRED BY POLE MANUFACTURER
5/8" CHAMFER
FINISHED GRADE
CONCRETE BASE (3000 PSI)
MINIMUM 28 DAY STRENGTH
6% AIR ENTRAINED +/- 1%
(8) #5 WITH #3 TIES, TOP (3) @ 2" OC
AND REMAINDER @ 12" OC. PROVIDE
MINIMUM CONCRETE COVER FOR
REINFORCING STEEL OF 2" ON SIDES
AND 3" AT BOTTOM
ANCHOR BOLT COVER
NON-SHRINK GROUT BETWEEN POLE AND BASE, AFTER POLE IN
PLUMBED. PROVIDE A CHANNEL THROUGH THE GROUT FOR POLE
INTERIOR DRAINAGE.
EXPOSED SURFACES TROWELLED SMOOTH
2 3/4" OR AS REQUIRED BY POLE MANUFACTURER.
PROVIDE ROUND HEAVY DUTY SEAMLESS
HDPE PLASTIC FORM. ABOVE GRADE FORM
SHALL BE REFLECTIVE YELLOW COLOR. LIGHT
POLE CEME-TUBE, OR APPROVED EQUAL.
EXTEND TO FIRM CLEAN
UNDISTURBED SOIL
2'-0" DIA
M
IN
IM
U
M
3'-0" TO CURB
OR CENTER IN ISLAND
NOTE:
1. COORDINATE DETAIL WITH ELECTRICAL POLE BASE DETAIL.
G ra p h ic S ca le
/2
0"
G ra p h ic S ca le
/3 2"
0"
' G ra p h ic S ca le
/1 6"
0"
' G ra p h ic
S ca le
/8
0"
G ra p h ic S ca le
/4
0"
G ra p h ic S ca le
/8
0"
' G ra p h ic
S ca le
/2
0"
G ra p h ic S ca le
/4
0"
G ra p h ic S ca le
0"
Romanyk Consulting Focusing on what matters
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
F
U.S. Department of Veterans Affairs
E
D
C
B
A
F
E
D
C
B
A
910 7 6 5 4 3 2 1
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
8910 7 6 5 4 3 2 1
Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093
NOT FOR
PERMITTING OR
CONSTRUCTION
Spinklered
PLAN NORTH
ST. PETERSBURG, FL
Office of Construction and Facilities Management
46, 47
FULLY SPRINKLERED
C
R e v it
L o c a l F il e s \S
.0
V
B A
R O
S E
C U
R
IT
Y F
E N
C E
C
K u rt is .W
.M in to n
.r v t
/6
/2
:0 :2
A
M
DETAILS
KATGOL ELITRE
100% CD VB3237
S-103
A&E Design for Security Fence at the
St. Petersburg VARO
APRIL 9, 2021
15 SUNNEN DR SUITE 104
SAINT LOUIS, MO 63143
314.645.1132 FAX: 314.645.1173
www.imegcorp.com # 18004378.01Revisions: Date:
NO SCALE
RAMP SECTION
2 NO SCALE
SECURITY DOOR
INSET IN SHEAR WALL
NO SCALE
SECURITY DOOR
INSET IN SHEAR WALL
12" = 1'-0"
EXTENDED POLE BASE DETAIL
This item has been electronically signed and sealed by Heather Heidenreich using a Digital Signature and date. Printed copies of this document are not considered signed and sealed and all
EA
ST
G
AT
E
DR
IV
E
EA
ST
G
AT
E
DR
IV
E
EA
ST
G
AT
E
DR
IV
E
STATE ROAD NO. 595 (U. S. ALT. BAY PINES BL. VD.
WET DETENTION
POND
WET DETENTION POND
VA ST. PETERSBURG
REGIONAL OFFICE
BUILDING 46
BUILDING 47
0' 1'
6" 3"
1'
Gr ap hi c S ca le
: 1 /2"
1'-
0"
0' 4"
8" 1'
2'
Gr ap hi c S ca le
: 3 /32
1'
-0
0'
8' Gr ap hi c S ca le : 1
/16
1' -0
0' 8'
4' Gr ap hi c S ca le
: 1 /8"
1'-
0"
0' 2'
1' 4'
Gr ap hi c S ca le
: 1 /4"
1'-
0"
0' 2'
1' 4'
Gr ap hi c S ca le
: 3 /8"
1'-
0"
0' 2'
4' 1' Gr ap hi c S ca le : 1
/2"
1'- 0"
0' 1'
2' 6"
Gr ap hi c S ca le
: 3 /4"
1'-
0"
0' 1'
2' 6"
Gr ap hi c S ca le
: 1
1' -0
Romanyk Consulting Focusing on what matters
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
F
U.S. Department of Veterans Affairs
E
D
C
B
A
F
E
D
C
B
A
910 7 6 5 4 3 2 1
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
8910 7 6 5 4 3 2 1
Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093
Spinklered
Office of Construction and Facilities Management
NORTH
FULLY SPRINKLERED
BI
M
VB
A
- S t.
Pe te rs bu rg
S ec ur ity
F en ce /S t P et er sb ur g
Se cu rit y
Fe nc e
- V
.rv t 4/
6/
:5 3:
A
M
BW TG
VB3237
46, 47
AS100ST. PETERSBURG, FL
APRIL 09, 2021
SITE ORIENTATION PLAN 100% CD A&E Design for Security Fence at the St. Petersburg VARO
1" = 60'-0"1 SITE ORIENTATION PLAN
15 SUNNEN DR SUITE 104
SAINT LOUIS, MO 63143
314.645.1132 FAX: 314.645.1173
www.imegcorp.com # 17002665.02
0' 60'30' 120'
Graphic Scale : 1" = 60'-0"
GENERAL NOTES
LEGEND
KEY NOTES
1. REMOVE ALL LANDSCAPING AND TREES WITHIN 8'-0" OF
PROPOSED FENCELINE AND REGRADE LEVEL WITH
ADJACENT. RESEED / RESOD WITH MATCHING SPECIES
GRASS OR MULCH TO MATCH ADJACENT CONDITIONS.
EXISTING LANDSCAPING TO BE ALTERED
OR REMOVED BASED ON NEW FENCING
LOCATIONS
EXISTING LOW HEIGHT VINYL FENCING
EXISTING STORM DRAINOR
/1 AD102
AD
1 1
DEMOLISH EXISTING CONCRETE SIDEWALK
BETWEEN BUILDING AND PARKING LOT
SIDEWALK
5 EXISTING
BUILDING
46 "A"
0' 40'20'10'
Graphic Scale : 1" = 20'-0"
0' 1'
6" 3"
1'
Gr ap hi c S ca le
: 1 /2"
1'-
0"
0' 4"
8" 1'
2'
Gr ap hi c S ca le
: 3 /32
1'
-0
0'
8' Gr ap hi c S ca le : 1
/16
1' -0
0' 8'
4' Gr ap hi c S ca le
: 1 /8"
1'-
0"
0' 2'
1' 4'
Gr ap hi c S ca le
: 1 /4"
1'-
0"
0' 2'
1' 4'
Gr ap hi c S ca le
: 3 /8"
1'-
0"
0' 2'
4' 1' Gr ap hi c S ca le : 1
/2"
1'- 0"
0' 1'
2' 6"
Gr ap hi c S ca le
: 3 /4"
1'-
0"
0' 1'
2' 6"
Gr ap hi c S ca le
: 1
1' -0
Romanyk Consulting Focusing on what matters
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
F
U.S. Department of Veterans Affairs
E
D
C
B
A
F
E
D
C
B
A
910 7 6 5 4 3 2 1
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
8910 7 6 5 4 3 2 1
Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093
Spinklered
Office of Construction and Facilities Management
NORTH
FULLY SPRINKLERED
DC
BA
KEY PLAN
BI
M
VB
A
- S t.
Pe te rs bu rg
S ec ur ity
F en ce /S t P et er sb ur g
Se cu rit y
Fe nc e
- V
.rv t 4/
6/
:5 1:
A
M
BW TG
VB3237
46, 47
AD100ST. PETERSBURG, FL
APRIL 09, 2021
DEMOLITION PLAN - SECTION A 100% CD A&E Design for Security Fence at the St. Petersburg VARO
1" = 20'-0"1 SECURITY FENCE DEMOLITION PLAN - SECTION A
Note Number Note
1 REMOVE TREES AND LANDSCAPE WITHIN 8’ OF FENCE LOCATION, GO TO
COORDINATE LANDSCAPE HARVESTING, DISPOSAL AND/OR REPLANTING WITH
THE VA/VBA IN ADVANCE OF REMOVAL.
2 DEMOLISH EXISTING LOW HEIGHT VINYL FENCING AND REMOVE BASE
PLATES/ANCHOR BOLTS.
3 DEMOLISH EXISTING LOW HEIGHT VINYL FENCING AND REMOVE AND REPAIR
ANCHORING PER STRUCTURAL.
4 DEMOLISH EXISTING LOW HEIGHT VINYL FENCING AND REPAIR/REPLACE
CURBING SLAB AT MOUNTING LOCATIONS.
5 EXISTING SECURITY GATES AND ISLAND TO BE REMOVED IN FULL.
6 VA TO REMOVE AND RELOCATE EXISTING ACCESSIBLE PARKING AND SIGNAGE.
7 EXISTING SECURITY GATES AND ISLAND TO BE REMAIN. NOT IN PROJECT SCOPE.
8 REMOVE EXISTING SPEED BUMP PADS (TYP 2) AND ASSOCIATED MOUNTING
HARDWARE. VERIFY WITH COR IF THEY WANT TO KEEP THEM FOR FUTURE USE
OR DISCARD. PATCH HOLES FROM MOUNTING TO MATCH EXISTING CONDITIONS.
15 SUNNEN DR SUITE 104
SAINT LOUIS, MO 63143
314.645.1132 FAX: 314.645.1173
www.imegcorp.com # 17002665.02
(APPLY TO SHEETS AD100-AD103)
Revision 1 Date 1
KEY NOTES
1. REMOVE ALL LANDSCAPING AND TREES WITHIN 8'-0" OF
PROPOSED FENCELINE AND REGRADE LEVEL WITH
ADJACENT. RESEED / RESOD WITH MATCHING SPECIES
GRASS OR MULCH TO MATCH ADJACENT…
This is the start of the file's text. The full file is on GovTribe.
File details come from the government source that posted it. Updated .