Addendum No. 2 - Construct Western KY Regional Training Center

This Addendum No. 2 modifies the Invitation to Bid (RFB-138-26) issued by the Commonwealth of Kentucky Department for Facilities and Support Services, Division of Engineering and Contract Administration, for the construction of the Western Kentucky Regional Training Center for the Kentucky Department of Criminal Justice Training in Madisonville, Kentucky. The project encompasses two primary buildings: a Classroom-Admin Building (Bid Pack A) and a High Bay Building (Bid Pack B), with supporting site work (Bid Pack C). The addendum includes comprehensive revisions to architectural, structural, mechanical, electrical, plumbing, and fire protection drawings and specifications, addressing changes to water/fire line coordination with the City of Madisonville, revisions to material specifications (including bullet-resistant door and glazing systems, rubber wall base, and acoustic treatments), updates to structural details for the mat foundation system and steel framing, modifications to MEP systems including fire protection controls and electrical circuiting, and answers to fifty-two bidder questions regarding product specifications, installation procedures, and design intent clarifications. The controls allowance of $649,830.00 is to be included in Bid Pack A pricing.

Key modifications include confirmation that Davis Bacon and prevailing wage rates are not required; clarification that dynamic compaction will densify existing mine spoil to meet the 15-foot minimum engineered fill requirement with no coal slurry over-excavation; specification of allowable bearing capacity at 2500 PSF; material substitutions approved for products meeting performance requirements (including PLAM, wood ceiling panels, wood slat wall panels, and fiberglass insulation); confirmation of meter vault responsibility assigned to the general contractor to coordinate between installing contractors; domestic water line sizing at 2.5 inches for the classroom building and 2 inches for the high bay building with two separate meters within the vault; approval of alternative locker ventilation designs pending coordination with mechanical systems; and contact information for the City of Madisonville Water Distribution Superintendent. All changes are binding upon the contract to be issued and become effective upon bidder receipt acknowledgment on the bid form of proposal.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

COMMONWEALTH OF KENTUCKY

DEPARTMENT FOR FACILITIES AND SUPPORT SERVICES

DIVISION OF ENGINEERING AND CONTRACT ADMINISTRATION

INVITATION TO BID NO: RFB-138-26

FOR: Construct Western KY Regional Training Center Kentucky Department of Criminal Justice Training Madisonville, Kentucky

DATE: December 8, 2025

RFB-785-2600000236

ADDENDUM NO. Two (2)

BIDDER SHALL CONFORM TO THE FOLLOWING CHANGES AS SAME SHALL BECOME BINDING

UPON THE CONTRACT TO BE ISSUED IN RESPONSE TO THIS INVITATION TO BID.

Item 1: Refer to attached addendum for all additions, deletions, and/or changes to specifications and/or drawings.

END OF ADDENDUM

Invitation to Bid No. RFB-138-26 For: Construct Western KY Regional Training Center Kentucky Department of Criminal Justice Training

Kristi Sharp, Statewide Procurement Manager Division of Engineering and Contract Administration

Addendum 2 Page 1 of 13

201 W. Short Street • Suite 700 • Lexington, KY 40507 • 859.231.7538

Addendum No. 2

For the DOCJT Western KY Regional Training Center

Invitation to Bid NO: RFB-138-26 December 5th, 2025

The following addendum items officially modify the construction documents and become binding to the contract for construction (Contractor is to note receipt of all addendums on their bid form of proposal):

1. General:

1.1. Controls Allowance – to be included in Bid Pack A pricing.

2. Civil:

Drawing:

2.1. Revised C.C200 with the new tap location. Changes were made to the Domestic Water/Fire Line as per coordination & request of the City of Madisonville. Water vault is removed, water meters have been relocated to near the buildings, fire line is a loop. Inverts of Sewer manhole & Storm Water were adjusted per MEP changes.

2.2. Revised sheet C.C301 - Added additional profile section to Dumpster Enclosure Plan.

3. Architectural:

3.1. Sheet A1100:

3.1.1. Addition of “RB2” to Finish and Materials legend. Material to be Johnsonite Tarkett Baseworks Thermoset (TS), Color: 63 Burnt Umber, Height: 6 inches.

3.1.2. Addition to General Finish and Materials Notes reading: “H. ALL BASE AND TALL CABINETS

SHALL RECEIVE A 4" RUBBER WALL BASE, RB-1, AT ALL EXPOSED SIDES, UNLESS NOTED

OTHERWISE.”

3.2. Sheet A1102: Rubber wall base at Corridors 217A, 217B, 217C, 217D and Lounge 210 to be RB2

Specifications:

3.1. 061600 – SHEATHING: New Spec section.

3.2. 085659- BULLET RESISTANT OPENINGS Edit Sections as follows:

Addendum 2 Page 2 of 13

REPLACE: 2.1A Basis of Design: BulletBlock HP500 bullet-resistant door; BulletBlock HP600 non-thermally broken framing; BulletBlock TTH600 thermally broken framing.

TO READ: 2.1A Basis of Design: BulletBlock HP500 bullet-resistant door; BulletBlock HP600 non-thermally broken framing; ( Frame Type AI2)

REPLACE: 2.2A Ballistic Rating: Provide assemblies tested and listed to UL 752 at the level indicated on the Drawings; assemblies shall match tested make-up.

TO READ: Ballistic Rating: Provide assemblies tested and listed to UL 752 at the level bullet resistance level 5 per UL752; assemblies shall match tested make-up.

NOTE: This is an assembly rating so I believe that would include the glazing resistance rating.

3.3. 088853- SECURITY GLAZING Edit Sections as follows:

REPLACE: 2.6 LAMINATED GLASS SECURITY GLAZING

TO READ: 2.6 LAMINATED GLASS SECURITY GLAZING (B ULLET RESISTANT GLASS IG-3)

REPLACE: 2.6.B.3 Ballistic Resistance, UL 752: Level 7 in accordance with UL 75.

TO READ: 2.6.B.3 Ballistic Resistance, UL 752: Level 5 in accordance with UL 75

4. Structural:

4.1. Re-issued Sheet A.S101 with Addendum 2 dated 12/5/2025.

4.1.1. Add “Mat Foundation Commentary of Risks and Construction” section.

4.2. Sheet A.S102

4.2.1. Changed “form deck” to “floor deck” in Steel (And other Metal) Construction section.

4.2.2. Removed reference to “joists” in Concrete Construction Section.

4.3. Re-issued Sheet A.S201 with Addendum 2 dated 12/5/2025.

4.3.1. Foundation Plan Notes

4.3.1.1. Plan Note 8 – Corrected Allowable Bearing Capacity to 2500 PSF.

4.3.2. Foundation Legend

4.3.2.1. Changed RWF40 to RWF35 and added reference detail.

4.3.2.2. Removed Step Grade Beam.

4.3.2.3. Updated CMU Wall Reinforcing types.

4.3.3. Foundation Tag Notes

4.3.3.1. Updated Tag Note 4.

4.3.3.2. Added Tag Note 7.

4.3.4. Mat Foundation Notes

4.3.4.1. Updated Notes 2 and 6.

4.3.5. Removed Wall Footing Schedule.

4.3.6. Plan A/A.S201

4.3.6.1. Added additional steel post at Stair A.

4.3.6.2. Added call out for Stair Framing Plan.

4.3.6.3. Added Tag Note 7 and isolation block-out square to all steel columns.

4.3.6.4. Updated Grade Beams that occur only below steel posts and masonry partitions to be grade beam type GB12. Added dimensions to locate these grade beams.

4.3.6.5. Changed site wall foundation sizes from RWF40 to RWF35 and RWF60 to RWF50.

Addendum 2 Page 3 of 13

4.3.6.6. Added tooled joint pattern at exterior slab by dock.

4.4. Re-issued Sheet A.S202 with Addendum 2 dated 12/5/2025.

4.4.1. Framing Legend

4.4.1.1. Updated CMU Wall Reinforcing types.

4.4.1.2. Added Solar Panel hatch

4.4.2. Framing Tag Notes

4.4.2.1. Updated Tag Note 4.

4.4.3. Plan A/A.S202

4.4.3.1. Added Callouts for Stair Framing Plans.

4.4.3.2. Added callouts for details M/A.S402 and N/A.S402.

4.5. Re-issued Sheet A.S203 with Addendum 2 dated 12/5/2025.

4.5.1. Framing Legend

4.5.1.1. Updated CMU Wall Reinforcing types.

4.5.1.2. Added Solar Panel hatch

4.5.2. Framing Tag Notes

4.5.2.1. Updated Tag Note 4.

4.5.3. Plan A/A.S203

4.5.3.1. Added Solar Panel Hatch area to plan

4.5.3.2. Updated beam and joist sizes associated with solar panels and roof top units.

4.6. Re-issued Sheet A.S301 with Addendum 2 dated 12/5/2025.

4.6.1. Updated Detail A/A.S301 Grade Beam Details & Schedule

4.6.2. Updated Detail B/A.S301 Typical Mat Slab and Grade Beam Joint Detail

4.6.3. Updated Detail C/A.S301 Typical Mat Slab Reinforcing Detail

4.7. Re-issued Sheet A.S302 with Addendum 2 dated 12/5/2025.

4.7.1. Added Detail D/A.S302 Typical Site Retaining Wall and Foundation Detail

4.7.2. Moved Typical Concrete Wall Reinforcing Detail from D/A.S302 to F/A.S302.

4.7.3. Moved Typical Exterior Slab on Grade Joint Detail from F/A.S302 to G/A.S302.

4.7.4. Moved Typical Mechanical Housekeeping Pad Detail from G/A.S302 to H/A.S302.

4.8. Re-issued Sheet A.S303 with Addendum 2 dated 12/5/2025.

4.8.1. Added insulation on sections A/A.S303, B/A.S303, C/A.S303, D/A.S303, E/A.S303, F/A.S303, G/A.S303, H/A.S303 and J/A.S303.

4.8.2. Added reinforcing detail reference to site retaining wall and foundation in Sections G/A.S303, H/A.S303 and M/A.S303.

4.8.3. Correct bond beam location and reinforcing in details K/A.S303 and L/A.S303.

4.9. Re-issued Sheet A.S401 with Addendum 2 dated 12/5/2025.

4.9.1. Updated Detail G/A.S401 Typical Steel Lintel Schedule.

4.10. Re-issued Sheet A.S402 with Addendum 2 dated 12/5/2025.

4.10.1. Removed Typical Stair Stringer detail from sheet.

4.10.2. Added Detail L/A.S402 Typical Reinforcement at Congregated Penetrations Detail.

4.10.3. Added Detail M/A.S402.

4.10.4. Added Detail N/A.S402.

4.11. Re-issued Sheet A.S501 with Addendum 2 dated 12/5/2025.

4.11.1. Updated Detail C/A.S501.

4.12. Added Sheet A.S601

4.13. Re-issued Sheet A.S701 with Addendum 2 dated 12/5/2025.

4.13.1. Updated Detail A/A.S701.

4.14. Re-issued Sheet B.S202 with Addendum 2 dated 12/5/2025.

4.14.1. Changed steel joist sizes at area designated for future solar panel installation.

4.15. Re-issued Sheet B.S203 with Addendum 2 dated 12/5/2025.

4.15.1. 3.2.1. Revised location of diaphragm zone 2.

Addendum 2 Page 4 of 13

4.16. Re-issued Sheet B.S401 with Addendum 2 dated 12/5/2025.

4.16.1. Removed Detail P/B.S401 and updated Detail G/B.S401 Typical Joist Seat on Column Cap /

Face Detail.

5. MEP:

Specifications:

5.1. Revised 2.11A to read “Furnish and install where shown on project drawings a double, rough brass, flush-type fire department connection with two individual clapper valves, plugs, chains, and rectangular escutcheon lettered “AUTOSPKR.” Size 2½” x 2½” x 4”. Outlets to have 2½” female Madisonville Fire Department hose threads.

Mechanical Drawings:

5.2. Refer to Sheet C.M.03 –

a. Revised water and fire meter vault detail.

b. Added water utility contact information.

c. Added thrust block and water service connection details with information for domestic water meters and boxes.

Plumbing Drawings:

5.3. Refer to Sheet A-P0-01 – revised invert elevations for sanitary and storm systems. Reworked floor drain piping in mechanical room. Added fire protection line.

5.4. 3. Refer to Sheet A-P1-01 – revised sanitary vent location in mechanical room.

5.5. 4. Refer to Sheet A-P4-01 – revised floor drain piping in mechanical room.

5.6. 5. Refer to Sheet B-P0-01 – revised invert elevations for sanitary and storm systems. Added fire protection line.

Electrical Drawings:

5.7. Refer to Sheet C.M.04 – Added battery charger and jacket heater circuits for generator, Added

OLF-7 fixture, adjusted site lighting circuiting.

5.8. 2. Refer to Sheet A.E0.00 – Change symbol for fire alarm wall mounted speaker strobe and wall mounted strobe.

5.9. 3. Refer to Sheet A.E1.11 – Changed light fixtures in private offices, and conference rooms to LF-7, added exit signs

a. Light Fixture Mounting Height additional information:

i. OLF-1 room 159 over door is to be mounted at 9’-0” AFF.

ii. OLF-1 room 159 over rolling door is to be mounted at 11’-0” AFF.

iii. OLF-1 outside room 169 is to be mounted at 9’-0” AFF.

iv. OLF-1 outside room 173 is to be mounted at 8’-0” AFF.

5.10. Refer to Sheet A.E1.12 – Changed light fixture type in classrooms to LF-7, changed linear light fixtures in restrooms to type LF-4.

5.11. Refer to Sheet A.E5.00 – updated both interior and exterior lighting schedules.

5.12. Refer to Sheet A.E5.00 – update panel board “L1-2” and “H1-1”

5.13. Refer to Sheet B.E0.00 – Change symbol for fire alarm wall mounted speaker strobe and wall mounted strobe.

Addendum 2 Page 5 of 13

5.14. Refer to Sheet BE1.01 – added exit sign in room 104A, rooms 120 and 130 changed light fixture to LF-1A type.

a. Light Fixture Mounting Height additional information:

i. OLF-1 door 109B is to be mounted at 8’-0” AFF.

ii. OLF-1 door 119B is to be mounted at 8’-0” AFF.

iii. OLF-1 door 119A is to be mounted at 10’-0” AFF.

iv. OLF-1 door 118B is to be mounted at 8’-0” AFF.

v. OLF-1 door 100C is to be mounted at 8’-0” AFF.

vi. OLF-1 door 104D is to be mounted at 8’-0” AFF.

vii. OLF-1 door 101 is to be mounted at 14’-0” AFF.

viii. OLF-1 door 102A is to be mounted at 14’-0” AFF.

ix. OLF-1 door 102B is to be mounted at 14’-0” AFF.

Fire Protection Drawings:

5.15. Refer to sheet A.F1.11 – Changed Fire Department Connection to a flush, rough brass type.

5.16. Refer to sheet B.F1.10 – Changed Fire Department Connection to a flush, rough brass type.

6. Bidders Questions:

6.1. Question: On C301 is the footprint of the dumpster. What is the height? What are the reinforcement specs? What will the cap be? Metal? Brick? Stone?

Answer: Updated detail is provided per sheet C301.

6.2. Question: Can dry damp cast stone be used instead of architectural precast concrete?

Answer: No, Dry Cast can not be used as it is a more porous material and this product will be in direct contact with grade.

6.3. Question: Which brick is to be used on the High Bay building?

Answer: Per spec Basis of Design Light Brick - Modular No. 8530 23-30, Belden Brick Company (The).

6.4. Question: Architectural details call for self-adhering membrane thru-wall flashing. Are there any specs for this flashing?

Answer: Thru-Wall Flashing is per Unit Masonry specification 042000 2.10 Embedded Flashing.

Self- adhering membrane flashing with termination bar, is for the transition from the through flashing to the Fluid Applied Air barrier: Butyl Rubber Flashing: Composite, self-adhesive, flashing product consisting of a pliable, butyl rubber compound, bonded to a high-density polyethylene film, aluminum foil, or spunbonded polyolefin to produce an overall thickness of not less than 40 mil.

6.5. Question: Please verify if finish to be dark bronze anodized or black anodized for the aluminum entrances and storefronts. Specifications 084113 Aluminum Framed Entrances and Storefront and 084413 Glazed Aluminum Curtain Walls call out for Black anodized but sheet A.A1001 calls out for the finish to be dark bronze anodized.

Addendum 2 Page 6 of 13

Answer: All Curtain Wall and Storefront to have a black anodized finish.

6.6. Question: Please verify if aluminum storefront door 101A is to have an automatic operator. Door Schedule on sheet A.A1000 calls for a power door operator in the remarks column but is not listed in the hardware schedule to have one.

Answer: Yes, door 101A and 101B are to have a power operator.

6.7. Question: Please verify if aluminum door frames for wood doors need to use same Kawneer AA 425 framing for 2 ¼” doors or for standard 1 ¾” doors.

Answer: Where wood doors are called out for in a Storefront frame, Frame to accommodate standard 1 ¾” wood door.

6.8. Question: Drawing A.S201 shows a “Wall Footing Schedule”. The reinforcing comment says to check the cut sections on drawings A.S301, A.S302, & A.S303 for reinforcing details. These cut sections do not show the transverse, continuous, or dowel reinforcing details. Please advise. I noticed that this was the case in all the drawings, and that rebar details are not shown for footings anywhere.

Please advise. Please also reference Section M on Drawing A.S303 as an example of not having rebar details for the retaining wall footings.

Answer: See related Structural Addendum drawing revisions. These details were updated and a new detail has been added for site retaining wall foundations and reinforcing.

6.9. Question: In the Unit Masonry 42000 Submittals 1.6/A./ QUALITY ASSURANCE Qualifications: 1. 2.

Installers: All masonry flashing installers must complete the International Masonry Institute Flashing Upgrade training course. Will this be required of the masonry contractor?

Answer: This will not be required of the masonry contractor. Masonry superintendent shall have minimum 10 years of commercial masonry experience.

6.10. Question: Addendum #1- 1.2.1 Provide controls allowance of $649,830.00 for JCI System. Is this for both bid packs or is it per each. We have to bid each bid pack separately, so if it is for both we need it broken out per bid pack, or you guys can just list it supplied by the owner.

Answer: Controls allowance to be include Bid Pack A pricing.

6.11. Question: Is this a Davis bacon act job? If so, can we get the pay scale documents?

Answer: Davis Bacon and Pre-vailing wage rates are not required on this project.

6.12. Question: Coal slurry removal / replacement -The geotechnical report repeatedly states coal slurry is unsuitable for engineered fill. Can you confirm the project intent: are we to over-excavate all identified coal slurry zones and replace them with compacted engineered fill (per AEI recommendations)?

Answer: No coal slurry is intended to be over-excavated. The geotechnical report addendum dated November 3, 2025 states that Dynamic Compaction will be utilized to densify the underlying

Addendum 2 Page 7 of 13 mine spoil. The spoil section densified by Dynamic Compaction will be considered to meet the minimum 15’ engineered fill requirement. All fill placed above the areas densified by Dynamic Compaction shall also be engineered fill.

6.13. Question: Basis for “15 ft minimum engineered fill” and reference elevation

AEI’s report calls for a minimum of 15 ft of engineered fill below the finish floor elevation and references excavation down to elevation 394 ft (for an assumed finished floor of 411 ft). There is some ambiguity with these design elevations. Please clarify:

6.13.1. If using AEI’s example (FFE = 411.0), AEI’s excavation to elevation 394.0 corresponds to

411.00 − 394.00 = 17.00 ft of removal. If the requirement is 15.0 ft of engineered fill, that would imply excavation to 411.00 − 15.00 = 396.00 ft. Which of these targets (or another) is the intended design basis?

6.13.2. For the High Bay building (current FFE = 407.54 ft), please confirm the excavation elevation you want:

6.13.2.1. If we adopt AEI’s stated target elevation 394.0 ft, the removal depth relative to High

Bay FFE is 407.54 − 394.00 = 13.54 ft; OR

6.13.2.2. If you require the same absolute removal depth used in AEI’s example (17.0 ft below the assumed 411.0 FFE), then High Bay would need excavation to 407.54 − 17.00 =

390.54 ft; OR

6.13.2.3. If the EOR intends the AEI minimum of 15.0 ft of engineered fill, the High Bay excavation would target 407.54 − 15.00 = 392.54 ft. Please confirm which target

(reference elevation + required engineered-fill thickness) we should use for each building.

Answer: No over excavation of building pads will occur beyond clearing and grubbing. The geotechnical report addendum dated November 3, 2025 states that Dynamic Compaction will be utilized to densify the underlying mine spoil. The spoil section densified by Dynamic Compaction will be considered to meet the minimum 15’ engineered fill requirement. All fill placed above the areas densified by Dynamic Compaction shall also be engineered fill.

6.14. Question: Disposal / handling of excavated coal slurry. What are the EOR/owner’s expectations for management and disposal of excavated coal slurry? (on-site stockpile for later isolation, off-site disposal, or reuse restrictions). Any environmental testing/manifesting required?

Answer: No Coal Slurry will be excavated.

6.15. Question: Please confirm whether on-site mine spoil is acceptable for use as engineered fill, and identify any restrictions, testing requirements, or exclusions (e.g., coal slurry) we must follow.

Answer: This item is addressed clearly in item 7.4 of the Geotechnical Report.

6.16. Question: Is the “reclaimed topsoil / reclaimed soil” encountered and noted on the boring logs acceptable to reuse as planting topsoil for turf and landscape areas, or is imported topsoil required?

Addendum 2 Page 8 of 13

Answer: Soil present on site that is free of rock and coal fines may be utilized as growth medium when properly amened. It is the responsibility of the contractor to provide adequate topsoil either preserved from the site or imported.

6.17. Question: Who is responsible for topsoil testing and approval (owner’s consultant, EOR, or contractor)?

Answer: The contractor is responsible for testing topsoil and submitting results to the design team for approval prior to placement.

6.18. Question: The brick specification is a modular brick at 2.6 C, 1; but 2.6 C, 4 gives the size of a utility brick. Which should it be?

Answer: Brick Masonry is to be utility size

6.19. Question: I see the ballistic door & frame specification, but do not see those specifications on the door schedule. Should it be?

Answer: Doors 101A and 101B in the door schedule are noted in remarks as being Ballistic.

Interior storefront elevations A12-1& A12-1B on sheet A.A1001 are noted as IG-3 Ballistic Glass.

6.20. Question: I see in the specs it is calling for UL 752 level 7. It also calls out insulated, low e, tints, and reflective. What all is necessary for the (2) elevations listing glass type IG-3?

Answer: Originally we were bullet proofing the whole (interior and exterior walls) of the vestibule that is why we had the thermally broken system originally in the spec. Please see the updated specs above regarding 085659- BULLET RESISTANT OPENINGS and 088853- SECURITY GLAZING

6.21. Question: Are the combo racks, jungle gyms & other items in Room 101A of the High Bay

Building OFOI?

Answer: Yes, exercise equipment shown are owner furnished and installed items.

6.22. Question: Is the clearing station in Keyed Floor Plan Note 9 of the high bay building the

'clearing trap' set forth in spec 116723?

Answer: Yes.

6.23. Question: What are the Frisk Circles- Keyed Floor Plan Note 11, Sheet B.A101A?

Answer: Painted lines on the floor

6.24. Question: The Finish & Material Legend on Sheet B.A1100 references WSP1. I do not see it in the specs or drawings.

Answer: Refer to sheet B.A101A Key Floor plan note 3 for location of WSP1. WSP1 limits are also shown on sheet B.A1100 per note 3. WSP1 can be found in specification 116623 – Gymnasium Equipment.

6.25. Question: On the wall type 962A-SB- what is the SB?

Addendum 2 Page 9 of 13

Answer: It stands for sound barrier the SB wall type incudes a sound isolation membrane and sound attenuation batts.

6.26. Question: AWP2 is listed as Owner provided on B.A1100, but not on A.A1100. Is it owner supplied?

Answer: In the High bay building it is owner supplied, in the classroom building it is not.

6.27. Question: Rulon's blade thickness is 3/4" versus Armstrong BOD @ 1/2". Rulon will not manufacture a blade thickness less than 5/8" due to wood movement/failure. Rulon could quote this scope as a solid Poplar, using a 3/4" blade thickness. If quoted in this manner, it would alter the O.C. spacing between blades. Does the design team see an issue concerning lighting or other MEP specification conflicts with this approach?

Answer: If the Rulon product can meet all of the other requirements of the specifications and drawings, design intent, ease of access to above the grid, and accommodate specified light fixtures then difference in manufacturer and blade thickness would be acceptable.

6.28. Question: It appears that a voice system is desired. However, the fire alarm plans show different symbols than those that represent speakers and speaker/strobes in the device legend.

Please confirm if the intent is for a mass notification system instead of a horn system.

Answer: Speaker/Strobes is the intent, revised on sheets A-E0-00, B-E0-00

6.29. Question: Do the new panels need to be interconnected? If so, via what means? Network, dry-contact relays, BAS, etc?

Answer: Panels to be interconnected in a “true loop” with single mode fiber 9/125UM

6.30. Question: Do the remote annunciators need to have microphones with all voice control capabilities or will 2x40 lcd annunciators suffice?

Answer: Microphones are not needed

6.31. Question: 284600-12 B. 1. Indicates 4064 addressable points as a minimum. Is this required to be included or just capable?

Answer: 250 points are acceptable

6.32. Question: Do you have a specific RoofNav Number that you want to use for this project, or are we to install the roof system per FM 1-90 guidelines?

Answer: There is not a specific RoofNav Number as those are assigned to specific roof systems.

Contractor proposed roofing system shall carry a RoofNav number that meets the specification performance requirements. Roofing system shall also meet FM 1-90 guidelines.

6.33. Question: The specs/ plans call out R-25 with 5” of ISO (2 layers of 2.5 ISO= 28.8). Is two layers of 2.2” ISO (R-25.2) acceptable?

Addendum 2 Page 10 of 13

Answer: Roof insulation to have a minimum R-25 not including HD polyiso coverboard.

6.34. Question: I’m not seeing any information on light fixture OLF-5.

Answer: Revised on sheet: A-E5-00.

6.35. Question: In regard to the loading dock on Building A, the manufacturers we have spoke with indicate the integrated system you request wi1l only work if a trailer restraint is included.

Section 2.1, H, 1, a calls for “Master panel: Control panel with integral fused disconnecting means for operating dock leveler, dock door, and truck restrains. However, there is no information for trailer restraint. Will a trailer restrain be included, or will the integrated system not be required?

Answer: Trailer restraint is not included and integration with a truck restraint is not required.

6.36. Question: Section 075419 part 2.3B: JM sheet that you have listed as an approved alternate. It shows that the thickness over scrim is .027 on a 60 mil minimum sheet. The roofing spec calls for 30 mil (.030) min over scrim. Will this be acceptable?

Answer: As long as JM can meet all of the other performance requirements of the specification

0.27 over scrim on a 60 mil sheet will be acceptable

6.37. Question: REFERENCE SPEC SECTION 095113 – ACT CEILINGS: SPEC SECTION STATES BASIS

OF DESIGN FOR APC-1 AS ARMSTRONG ULTIMA HIGH NRC #1942 W/ 9/16” GRID DRAWING SHEET

A.A1100 FINISH & MATERIAL LEGEND STATES APC-1 AS ARMSTRONG OPTIMA W/ 9/16” GRID.

PLEASE CONFIRM WHETHER ULTIMA #1942 OR OPTIMA (IDENTIFY MODEL NUMBER) IS TO BE

FIGURED?

Answer: Please provide Optima 3152.

6.38. Question: REFERENCE SPEC SECTION 054000 – COLD FORMED METAL FRAMING: SPEC

SECTION 054000 STATES TO PRODUCE ENGINEERED SHOP DRAWINGS FOR EXTERIOR NON-LOAD

BEARING CURTAIN WALL FRAMING. SPEC SECTION 092216 (NON-STRUCTURAL METAL FRAMING)

DOES NOT SPECIFY ANY ENGINEERING/SHOP DRAWINGS TO BE REQUIRED. PLEASE CONFIRM

EXTERIOR CURTAIN WALL FRAMING IS THE EXTENT OF THIRD PARTY ENGINEERING THAT WILL BE

REQUIRED FOR TYPICAL LIGHT GAUGE METAL FRAMING?

Answer: The structural cold-formed steel curtain and parapet walls are fully designed, delegated engineered shops are not required.

6.39. Question: REFERENCE SPEC SECTION 072100 – THERMAL INSULATION: UN-FACED

FIBERGLASS BATT INSULATION AS WELL AS TWO TYPES OF MINERAL WOOL(UNFACED &

REINFORCED-FOIL FACED) INSULATION IS SPECIFIED WITHIN THIS SPEC SECTION THERE IS NO MENTION OF TYPICAL INTERIOR WALL INSULATION WITHIN THIS SPEC NOR IS IT LISTED WITHIN DIVISION 9 SPECS. PLEASE SPECIFY LOCATIONS FOR THERMAL INSULATION (UN-FACED FIBERGLASS

BATTS, UN-FACED MINERAL WOOL BOARD & REINFORCED-FOIL FACED MINERAL WOOL BOARD

INSULATION)?

Addendum 2 Page 11 of 13

PLEASE SPECIFY WHAT ACCEPTABLE UN-FACED FIBERGLASS BATT INSULATION CAN BE FIGURED AT

“SOUND ATTENUATION BATTS S.A.B.” LOCATIONS (SEE WALL TYPES A.A004)?

Answer: Specification Section 072100 THERMAL INSULATION:

2.2 A. Glass-Fiber Blanket insulation – can be used for interior sound batt insulation for non-rated walls and in accordance with listed STC rating. Can also be used in exterior stud cavity to meet minimum R-value indicated.

2.3 Extruded Polystyrene board for use at below grade applications.

2.4 A. Mineral-wool board – to be used in exterior cavity wall construction

2.4 B. Mineral-wool blanket foil-faced to be utilized behind spandrel glass.

6.40. Question: REFERENCE SPEC SECTION 092900 – GYPSUM BOARD: THERE ARE TWO TYPES OF

INTERIOR GYPSUM BOARD PRODUCTS LISTED IN THIS SPEC SECTION (TYPE ‘C’ & MOLD-RESISTANT GYPSUM BOARD) PLEASE CONFIRM TYPE ‘C’ DRYWALL IS TO BE FIGURED AT ALL LOCATIONS OR IF TYPE ‘X’ FIRE CODE DRYWALL CAN BE FIGURED AT NON-RATED WALLS & CEILINGS/SOFFITS (AS IT

TYPICALLY IS)?

Answer: Type X Mold & Moisture Resistant gyp is typical for most interior locations. Type C would only be used as required per a specific UL rated system.

6.41. Question: REFERENCE A.A004 WALL TYPES – EXTERIOR WALL TYPES X1,X2,X3: THESE 3

WALL TYPES SPECIFY 5/8” DENSGLASS SHEATHING, HOWEVER I CANNOT FIND DENSGLASS

SHEATHING IN ANY OF THE SPEC SECTIONS (MOST COMMONLY 061600-SHEATHING) ON SHEET

A.A450 ROOF DETAILS: DETAIL 4: 5/8” DENSGLASS IS SHOWN ON THE BACKSIDE OF METAL

FRAMING AT ROOF PARAPET. PLEASE PROVIDE EXTERIOR SHEATHING SPEC SECTION OR CLARIFY BASIS OF DESIGN FOR ALL EXTERIOR SHEATHING IS DENSGLASS AND IF JOINTS ARE TO BE TAPED

PRIOR TO RIGID BOARD/CONTINUOUS INSULATION COMPONENTS ARE INSTALLED?

PLEASE CONFIRM DENSGLASS SHEATHING IS ALSO TO BE USED ON BACKSIDE OF METAL FRAMED

PARAPETS AS SHOWN ON DETAIL 4/A.A450 (LOTS OF TIME THIS IS DENSDECK/PLYWOOD BY

ROOFING CONTRACTOR)?

Answer: Refer to added spec section 061600 Sheathing. Backside of all Parapet walls where roof membrane is attached to be ¾” Fire Treated Plywood.

6.42. Question: REFERENCE SHEET B.A003 WALL TYPES: WALL TYPE 408A SPECIFIES (2) LAYERS OF

ACOUSTIC GYPSUM BOARD. PLEASE PROVIDE PRODUCT SPEC FOR WHAT THE BASIS OF DESIGN IS

FOR THE ACOUSTIC GYPSUM BOARD?

Answer: Basis of Design Products:

National Gypsum Gold Bond SoundBreak XP 5/8”.

Certainteed SilentFX Type X 5/8”.

6.43. Question: REFERENCE WALL SECTIONS A.A701/SECTION 3 & A.A700/SECTION 1: WALL

SECTION 3/A.A701 SHOWS DRYWALL TERMINATING JUST ABOVE CEILING HEIGHT & ONLY

INSULATION EXTENDING TO DECK ABOVE. WALL SECTION 1/A.A700 SHOWS DRYWALL EXTENDING

FULL HEIGHT ABOVE CEILING TO THE DECK AS WELL AS THE INSULATION. PLEASE CONFIRM

WHETHER DRYWALL IS TO EXTEND FULL HEIGHT TO DECK ON BOTH 1ST/2ND FLOORS OR CAN

TERMINATE ABOVE CEILINGS?

Answer: At exterior walls drywall to extend to deck.

Addendum 2 Page 12 of 13

6.44. Question: REFERENCE SPEC SECTION 095113 – ACT CEILINGS: BASIS OF DESIGN FOR BOTH

TILE & GRID ARE LISTED AS ARMSTRONG. PLEASE CONFIRM WHETHER USG OR CERTAINTEED

MANUFACTURER EQUIVALENT MATERIAL CAN BE CONSIDERED IN OUR PRICING?

Answer: Armstrong is Basis of Design only. Other manufacturers and products are acceptable if they can meet the performance and aesthetic requirements of the specifications and drawings.

6.45. Question: REFERENCE SPEC SECTION 095426 – WOOD SLAT PANEL SYSTEMS. THIS SECTION

INCLUDES WOOD PANEL SYSTEMS FOR WALL AND CEILINGS AS WELL AS THE SUSPENSION

SYSTEMS FOR THE CEILING SYSTEMS AND DIRECTS SPECIFIC MODEL AS INDICATED ON FINISH AND

MATERIAL LEGENDS (PER SHEET A.A1100 – WCP1 WOOD CEILING PANEL IS ARMSTRONG

WOODWORKS GRILLE 15/16” TEGULAR 6723F51L4T5GGM/1713BL & LISTED UNDER MILLWORK

SECTION 064023 WWP2 – WOOD SLAT WALL PANEL IS ARMSTRONG WOODWORKS WALL SLATS

7263BOGGM. PLEASE CONFIRM WHETHER USG, CERTAINTEED, RULON, ETC. MANUFACTURER

EQUIVALENT MATERIAL CAN BE CONSIDERED IN OUR PRICING?

PLEASE CONFIRM BOTH THE WOOD CEILINGS/WALLS ARE TO BE PROVIDED & INSTALLED BY THE

SAME CONTRACTOR AND WILL NOT BE SEPARATE FOR 060423 MILLWORK AT CERTAIN AREAS?

Answer: If the product can meet all of the other requirements of the specifications and drawings, design intent, ease of access to above the grid, and accommodate specified light fixtures then difference in manufacturer and blade thickness would be acceptable. Ceiling WCP1 and wood slat wall WWP2 are to be of the same manufacturer, so that blade size, spacing and wood finish are the same. The intent of the materials is to have alignment between ceiling and wall .

6.46. Question: C.C200 who will be responsible for meter vault, Fire main people or plumbing contractor?

Answer: The meter vault will not be set by the city. The general contractor should determine which of the installing contractors will be responsible for the meter vault. Revised notation for this is on attached revised sheet C.C200.

6.47. Question: C.c200 What are the sizes of DW line outside of the vault and will they be one meter or two?

Answer: The DW line serving the classroom building shall be 2-1/2”. The DW line serving the high bay building shall be 2”. Each DW line shall have its own meter for a total of 2 DW meters inside the vault. Sizes will be indicated on the vault detail by addendum.

6.48. Question: Has local water company been aware of these plan and do we have a contact person to get costs?

Answer: es. Coordinate with Superintendent of Water Distribution (Keith Browning, kbrowning@madisonvillegov.com) and Assistant Superintendent of Water Distribution, phone number 270-824-2140.

6.49. Question: Benches in front of lockers are noted as paper based composite on steel tubular brackets/cmu base by others (A.A1300); - please advise if these are phenolic bench tops.

Answer: No- these are the paperstone product (or equal) specified in the millwork section mailto:kbrowning@madisonvillegov.com

Addendum 2 Page 13 of 13

6.50. Question: Current spec 105129 Phenolic Lockers - lists several different lock types. Please confirm which we should include.

Answer: Use the Digilock model ATS Series.

6.51. Question: Current spec 105129 Phenolic Lockers - lists ventilation in the doors. Our Lockers are already designed with Concealed/Perimeter Ventilation as cutting holes/vents in this material can reduce both the structural integrity and theft proof properties. Please see attached and let me know if our Concealed Ventilation would be acceptable.

Answer: We are providing an active exhaust duct along the top of all the lockers- we will need to coordinate the flow rate with mechanical and verify the clear opening of 21 inches as your product data indicates, is enough for the flow rate of the exhaust fans.

6.52. Question: Current spec 105129 Phenolic Lockers - states the material must meet Class A standard for Fire Rating. This will be significantly more expensive and is typically not needed unless mandated by local Fire Code. Please confirm if this is intended/required when you can.

Answer: Surface-Burning Characteristics: Comply with ASTM E84 or UL 723; testing by a qualified testing agency. Identify products with appropriate markings of applicable testing agency.

1. Flame-Spread Index: 25 or less.

2. Smoke-Developed Index: 450 or less.

6.53. Question: Current spec 105129 Phenolic Lockers - lists material thicknesses that are different than what we would recommend. Please see attached and let me know if our recommended thicknesses will be acceptable.

Answer: Columbia material thicknesses are acceptable.

END OF ADDENDUM

DOCJT Western KY Regional Training Center Commonwealth of Kentucky

Addendum #2 – December 2025 Account Number 525CBSCCJ5300

SHEATHING 061600 - 1

SECTION 061600 - SHEATHING

PART 1 - GENERAL

1.1 SUMMARY

A. Section Includes:

1. Wall sheathing.

B. Related Requirements:

1. Section 061000 "Rough Carpentry" for plywood backing panels.

2. Section 072726 "Fluid-Applied Membrane Air Barriers" for barrier applied over wall sheathing.

1.2 DEFINITIONS

A. ABAA: The Air Barrier Association of America.

1.3 PREINSTALLATION MEETINGS

A. Preinstallation Conference: Conduct conference at Project site.

1. Review air-barrier and water-resistant glass-mat gypsum sheathing requirements and installation, special details, transitions, mockups, air-leakage testing, protection, and work scheduling that covers air-barrier and water-resistant glass-mat gypsum sheathing.

1.4 ACTION SUBMITTALS

A. Product Data: For each type of product. Indicate component materials and dimensions and include construction and application details.

1. Include data for wood-preservative treatment from chemical treatment manufacturer and certification by treating plant that treated plywood complies with requirements.

Indicate type of preservative used and net amount of preservative retained.

2. Include data for fire-retardant treatment from chemical treatment manufacturer and certification by treating plant that treated plywood complies with requirements. Include physical properties of treated materials.

3. For fire-retardant treatments, include physical properties of treated plywood both before and after exposure to elevated temperatures, based on testing by a qualified independent testing agency in accordance with ASTM D5516.

4. For products receiving waterborne treatment, include statement that moisture content

SHEATHING 061600 - 2

of treated materials was reduced to levels specified before shipment to Project site.

5. For air-barrier and water-resistant glass-mat gypsum sheathing, include manufacturer's technical data and tested physical and performance properties of products.

B. Shop Drawings: For air-barrier and water-resistant glass-mat gypsum sheathing assemblies.

1. Show locations and extent of sheathing, accessories, and assemblies specific to Project conditions.

2. Include details for sheathing joints and cracks, counterflashing strips, penetrations, inside and outside corners, terminations, and tie-ins with adjoining construction.

3. Include details of interfaces with other materials that form part of air barrier.

C. Sustainable Design Submittals:

1. Laboratory Test Reports: For composite wood products, indicating compliance with the formaldehyde emissions evaluation.

2. Product Data: For installation adhesives, indicating VOC content.

3. Laboratory Test Reports: For installation adhesives, indicating compliance with requirements for low-emitting materials.

1.5 INFORMATIONAL SUBMITTALS

A. Product Certificates: From air-barrier and water-resistant glass-mat gypsum sheathing manufacturer, certifying compatibility of sheathing accessory materials with Project materials that connect to or that come in contact with the sheathing.

B. Product Test Reports: For each air-barrier and water-resistant glass-mat gypsum sheathing assembly, indicating compliance with specified requirements, for tests performed by a qualified testing agency.

C. Evaluation Reports: For the following, from ICC-ES:

1. Preservative-treated plywood.

2. Fire-retardant-treated plywood.

3. Foam-plastic sheathing.

4. Air-barrier and water-resistant glass-mat gypsum sheathing.

5. Power-driven fasteners.

D. Field Quality Control Reports: For specified tests and inspections.

1.6 QUALITY ASSURANCE

A. Installer Qualifications: An entity that employs installers and supervisors who are trained and approved by manufacturer of air-barrier and water-resistant glass-mat gypsum sheathing.

1. Installer is to be licensed by ABAA in accordance with ABAA's Quality Assurance Program and is to employ ABAA-certified installers and supervisors on Project.

SHEATHING 061600 - 3

B. Testing Agency Qualifications:

1. For testing agency providing classification marking for fire-retardant-treated material, an inspection agency acceptable to authorities having jurisdiction that periodically performs inspections to verify that the material bearing the classification marking is representative of the material tested.

2. For testing and inspecting agency providing tests and inspections related to air-barrier and water-resistant glass-mat gypsum sheathing meeting the requirements as follows:

a. Independent agency, qualified in accordance with ASTM E329 for testing indicated, and certified by ABAA.

C. Certified Wood: Provide an invoice, including vendor's chain-of-custody number, product cost, and entity being invoiced.

D. Vendor Qualifications: Provide proof of use of vendors that are certified for chain of custody by an FSC-accredited certification body.

1.7 MOCKUPS

A. Build mockups to set quality standards for materials and execution and for preconstruction testing .

1. Build integrated mockups of exterior wall assembly, 150 sq. ft. , incorporating backup wall construction, window, storefront, door frame and sill, ties and other penetrations, and flashing to demonstrate crack and joint treatment and sealing of gaps, terminations, and penetrations of air-barrier sheathing assembly.

a. Coordinate construction of mockups to permit inspection and testing of sheathing before external insulation and cladding are installed.

b. Include junction with roofing membrane, building corner condition, and foundation wall intersection .

c. If Architect determines mockups do not comply with requirements, reconstruct mockups until mockups are approved.

2. Approval of mockups does not constitute approval of deviations from the Contract Documents contained in mockups unless Owner specifically approves such deviations by Change Order.

3. Subject to compliance with requirements, approved mockups may become part of the completed Work if undisturbed at time of Substantial Completion.

1.8 DELIVERY, STORAGE, AND HANDLING

A. Stack panels flat with spacers beneath and between each bundle to provide air circulation.

Protect sheathing from weather by covering with waterproof sheeting, securely anchored.

Provide for air circulation around stacks and under coverings.

SHEATHING 061600 - 4

PART 2 - PRODUCTS

2.1 PERFORMANCE REQUIREMENTS

A. Fire-Resistance Ratings: As tested in accordance with ASTM E119; testing by a qualified testing agency. Identify products with appropriate markings of applicable testing agency.

1. Fire-Resistance Ratings: Indicated by design designations from UL's "Fire Resistance Directory" or from the listings of another qualified testing agency.

B. Air-Barrier and Water-Resistant Glass-Mat Gypsum Sheathing Performance: Air-barrier and water-resistant glass-mat gypsum sheathing assembly, and seals with adjacent construction, are to be capable of performing as a continuous air barrier and as a liquid-water drainage plane flashed to discharge to the exterior incidental condensation or water penetration. Air-barrier assemblies are to be capable of accommodating substrate movement and of sealing substrate expansion and control joints, construction material changes, penetrations, tie-ins to installed waterproofing , tie-ins to other installed air barriers , and transitions at perimeter conditions without deterioration and air leakage exceeding specified limits.

2.2 WOOD STRUCTURAL PANEL PRODUCTS

A. General: Wood structural panels include plywood, mat-formed (nonveneer) panels such as oriented strand board, and composite panels, which are veneer-faced panels with mat-formed cores.

B. Emissions: Products are to meet the testing and product requirements of the California Department of Public Health's "Standard Method for the Testing and Evaluation of Volatile Organic Chemical Emissions from Indoor Sources Using Environmental Chambers."

C. Thickness: As needed to comply with requirements specified, but not less than thickness indicated on Drawings.

D. Factory mark panels to indicate compliance with applicable standard.

2.3 PRESERVATIVE-TREATED PLYWOOD

A. Preservative-Treated Plywood by Pressure Process: AWPA U1, use categories as follows:

1. UC2, Interior/Damp: For interior construction not in contact with ground but may be subject to moisture.

2. UC3B, Above Ground, Exposed: For exterior construction not in contact with ground, exposed to all weather cycles including prolonged wetting.

3. UC4A, Ground Contact: For wood panels in contact with ground and exposed to all weather cycles, normal exposure conditions.

4. Preservative Chemicals: Acceptable to authorities having jurisdiction and containing no

SHEATHING 061600 - 5

arsenic or chromium.

B. Mark plywood with appropriate classification marking of an inspection agency acceptable to authorities having jurisdiction.

C. Application: Treat all plywood unless otherwise indicated and plywood in contact with masonry or concrete or used with roofing, flashing, vapor barriers, and waterproofing .

2.4 FIRE-RETARDANT-TREATED PLYWOOD

A. General: Where fire-retardant-treated materials are indicated, use materials complying with requirements in this article that are acceptable to authorities having jurisdiction and with fire-test-response characteristics specified as determined by testing identical products per test method indicated by a qualified testing agency.

B. Fire-Retardant-Treated Plywood by Pressure Process: Products with a flame-spread index of 25 or less when tested in accordance with ASTM E84, and with no evidence of significant progressive combustion when the test is extended an additional 20 minutes, and with the flame front not extending more than 10.5 ft. beyond the centerline of the burners at any time during the test.

1. Treatment must not promote corrosion of metal fasteners.

2. Exterior Type: Treated materials are to comply with requirements specified above for fire-retardant-treated plywood by pressure process after being subjected to accelerated weathering in accordance with ASTM D2898. Use for exterior locations and where indicated on Drawings.

3. Interior Type A: Treated materials are to have a moisture content of 28 percent or less when tested in accordance with ASTM D3201/D3201M at 92 percent relative humidity.

Use where exterior type is not indicated.

4. Design Value Adjustment Factors: Treated lumber plywood is to be tested in accordance with ASTM D5516 and design value adjustment factors are to be calculated in accordance with ASTM D6305. Span ratings after treatment are to be not less than span ratings specified. For roof sheathing and where high-temperature fire-retardant treatment is indicated, span ratings for temperatures up to 170 deg F are to be not less than span ratings specified.

C. Kiln-dry material after treatment to a maximum moisture content of 15 percent. Do not use material that is warped or does not comply with requirements for untreated material.

D. Identify fire-retardant-treated plywood with appropriate classification marking of qualified testing agency.

E. Application: Treat all plywood unless otherwise indicated.

1. Roof sheathing.

2.5 WALL SHEATHING

A. Glass-Mat Gypsum Sheathing, Walls: ASTM C1177/C1177M.

SHEATHING 061600 - 6

1. Manufacturers: Subject to compliance with requirements, available manufacturers offering products that may be incorporated into the Work include, but are not limited to, the following :

a. CertainTeed; SAINT-GOBAIN

b. Continental Building Products Inc.

c. Georgia-Pacific Gypsum LLC

d. Gold Bond Building Products, LLC provided by National Gypsum Company

e. USG Corporation

2. Type and Thickness: Type X, 5/8 inch thick.

2.6 ROOF SHEATHING

A. Plywood Sheathing, Roofs :

1. Classification: Either DOC PS 1 or DOC PS 2 , Exterior, Structural I [ sheathing.

2. Nominal Thickness: Not less than ¾ inch

2.7 MISCELLANEOUS MATERIALS

A. General: Provide fasteners of size and type indicated that comply with requirements specified in this article for material and manufacturer.

1. For parapet and wall sheathing, provide fasteners with hot-dip zinc coating complying with ASTM A153/A153M or of Type 304 stainless steel .

B. Power-Driven Fasteners: Fastener systems with an evaluation report acceptable to authorities having jurisdiction, based on ICC-ES AC70.

C. Screws for Fastening Sheathing to Wood Framing: ASTM C1002.

D. Screws for Fastening Wood Structural Panels to Cold-Formed Metal Framing: ASTM C954, except with wafer heads and reamer wings, length as recommended in writing by screw manufacturer for material being fastened.

E. Screws for Fastening Gypsum Sheathing to Cold-Formed Metal Framing: Steel drill screws, in length recommended in writing by sheathing manufacturer for thickness of sheathing to be attached.

1. For steel framing less than 0.0329 inch thick, use screws that comply with ASTM C1002.

2. For steel framing from 0.033 to 0.112 inch thick, use screws that comply with ASTM

C954.

F. Sealant for Paper-Surfaced and Glass-Mat Gypsum Sheathing: Elastomeric, medium-modulus, neutral-curing silicone joint sealant compatible with joint substrates formed by gypsum sheathing and other materials, recommended in writing by sheathing manufacturer for application indicated and complying with requirements for elastomeric sealants specified in Section 079200 "Joint Sealants."

G. Sealant for Glass-Mat Gypsum Sheathing: Silicone emulsion sealant complying with ASTM

SHEATHING 061600 - 7

C834, compatible with sheathing tape and sheathing and recommended in writing by tape and sheathing manufacturers for use with glass-fiber sheathing tape and for covering exposed fasteners.

1. Sheathing Tape: Self-adhering glass-fiber tape, minimum 2 inches wide, 10 by 10 or 10 by 20 threads/inch, of type recommended in writing by sheathing and tape manufacturers for use with silicone emulsion sealant in sealing joints in glass-mat gypsum sheathing and with a history of successful in-service use.

H. Sheathing Tape for Foam-Plastic Sheathing: Pressure-sensitive plastic tape recommended in writing by sheathing manufacturer for sealing joints and penetrations in sheathing.

I. Adhesives for Field Gluing Panels to Wood Framing: Formulation complying with APA AFG-01 ASTM D3498 that is approved for use with type of construction panel indicated by manufacturers of both adhesives and panels.

1. Verify adhesive has a VOC content of 70 g/L or less.

2. Verify adhesive complies with testing and product requirements of the California

Department of Public Health's "Standard Method for the Testing and Evaluation of Volatile Organic Chemical Emissions from Indoor Sources Using Environmental Chambers."

PART 3 - EXECUTION

3.1 INSTALLATION, GENERAL

A. Do not use materials with defects that impair quality of sheathing or pieces that are too small to use with minimum number of joints or optimum joint arrangement. Arrange joints so that pieces do not span between fewer than three support members.

B. Cut panels at penetrations, edges, and other obstructions of work; fit tightly against abutting construction unless otherwise indicated.

C. Securely attach to substrate by fastening as indicated, complying with the following:

1. Table 2304.10.1, "Fastening Schedule," in the ICC's "International Building Code."

2. Table R602.3(1), "Fastener Schedule for Structural Members," and Table R602.3(2), "Alternate Attachments," in the ICC's "International Residential Code for One- and Two- Family Dwellings."

3. ICC-ES evaluation report for fastener.

D. Use common wire nails unless otherwise indicated. Select fasteners of size that will not fully penetrate members where opposite side will be exposed to view or will receive finish materials. Make tight connections. Install fasteners without splitting wood.

E. Coordinate wall parapet and roof sheathing installation with flashing and joint-sealant installation so these materials are installed in sequence and manner that prevent exterior moisture from passing through completed assembly.

SHEATHING 061600 - 8

F. Do not bridge building expansion joints; cut and space edges of panels to match spacing of structural support elements.

G. Coordinate sheathing installation with installation of materials installed over sheathing so sheathing is not exposed to precipitation or left exposed at end of the workday when rain is forecast.

3.2 INSTALLATION OF GYPSUM SHEATHING

A. Comply with GA-253 and with manufacturer's written instructions.

1. Fasten gypsum sheathing to cold-formed metal framing with screws.

2. Install panels with a 3/8-inch gap where non-load-bearing construction abuts structural elements.

3. Install panels with a 1/4-inch gap where they abut masonry or similar materials that might retain moisture, to prevent wicking.

B. Apply fasteners so heads bear tightly against face of sheathing, but do not cut into facing.

C. Horizontal Installation: Install sheathing with V-grooved edge down and tongue edge up.

Interlock tongue with groove to bring long edges in contact with edges of adjacent panels without forcing. Abut ends over centers of studs, and stagger end joints of adjacent panels not less than one stud spacing. Attach at perimeter and within field of panel to each stud.

1. Space fasteners approximately 8 inches o.c. and set back a minimum of 3/8 inch from edges and ends of panels.

2. For sheathing under stucco cladding, panels may be initially tacked in place with screws if overlying self-furring metal lath is screw-attached through sheathing to studs immediately after sheathing…