Addendum 7.pdf

PDF 8 MB Posted

Attached to
RFB-228-23 - CJT - New Indoor Firing Range
Solicitation number
RFB-785-2300000633-8
Issued by
Lewis County, Kentucky

About this file

This document is an Addendum for an Invitation to Bid (ITB) issued by the Commonwealth of Kentucky Department for Facilities and Support Services Division of Engineering and Contract Administration for the construction of a New Indoor Firing Range for the Department of Criminal Justice Training in Richmond, Kentucky. The Addendum provides updates to the construction documents, including changes to the civil, architectural, mechanical, plumbing, and electrical specifications and drawings. Key changes include the addition of a sanitary sewer plan, revisions to the wood carpentry regional material requirements, the addition of sliding metal door specifications, and updates to trap primer and plumbing fixture details. The bid date has been extended to May 2, 2023.

The Addendum also addresses several bidder questions, including clarification that the 3/8" AR500 steel plates cannot be omitted and that a gypsum ceiling is required. The project is not a LEED registered project, but it still retains many LEED requirements. The Addendum provides further details on the existing DOCJT Avigilon H6 mini dome camera that is to be matched.

View the file

Other files

Show all 15

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

COMMONWEALTH OF KENTUCKY

DEPARTMENT FOR FACILITIES AND SUPPORT SERVICES

DIVISION OF ENGINEERING AND CONTRACT ADMINISTRATION

INVITATION TO BID NO: RFB-228-23

FOR: New Indoor Firing Range Department Of Criminal Justice Training Richmond, Kentucky

DATE: April 21, 2023

RFB-785-2300000633

ADDENDUM NO. Seven (7)

BIDDER SHALL CONFORM TO THE FOLLOWING CHANGES AS SAME SHALL BECOME BINDING

UPON THE CONTRACT TO BE ISSUED IN RESPONSE TO THIS INVITATION TO BID.

Item 1: Refer to the addendum below distributed by Lynn Imaging for all additions, deletions, and/or changes to specifications and/or drawings.

Item 2: Bid Date has been extended to May 2, 2023 at 2:00 P.M., Eastern Time

END OF ADDENDUM

Invitation to Bid No. RFB-228-23 For: New Indoor Firing Range Department Of Criminal Justice Training Richmond, Kentucky

Kyla Satterly, Statewide Procurement Analyst II Division of Engineering and Contract Administration

Addendum 7 Page 1 of 3

201 W. Short Street • Suite 700 • Lexington, KY 40507 • 859.231.7538 • fax 859.255.4380 • www.eopa.com

Addendum No. 7

For the new DOCJT Indoor Firing Range Richmond, Kentucky

Invitation to Bid NO: RFB-228-23 April 21, 2023

The following addendum items officially modify the construction documents and become binding to the contract for construction (Contractor is to note receipt of all addendums on their bid form of proposal):

1. CIVIL:

Drawings:

1.1. Add sheet C3.3 Sanitary Sewer Plan. This plan sheet shall supplement MEP Sheet U100.

Specification Section 22-1313 shall apply to the pipe materials and installation.

2. ARCHITECTURAL:

Specifications

2.1. Specification 061000 ROUGH CARPENTRY_Part 2_2.1 Wood Product General_A. Regional Materials. Revise distance to be within 500 miles.

2.2. Add Specification 081180 SLIDING METAL DOORS

3. MECHANICAL:

Drawings:

3.1. See revised drawings M902 and M903 showing missing control flow diagrams.

4. PLUMBING:

Specifications

4.1. Refer to Division 22 Section, add Piping Material Section:

• Install force-main, pressure piping according to the following:

Addendum 7 Page 2 of 3

201 W. Short Street • Suite 700 • Lexington, KY 40507 • 859.231.7538 • fax 859.255.4380 • www.eopa.com o Install piping with restrained joints at tee fitting and at horizontal and vertical changes in direction. Use corrosion-resistant rods, pipe or fitting manufacturer’s proprietary restraint system, or cast-in-place-concrete supports or anchors.

o Install piping with 36” minimum cover.

o Install ductile-iron pressure piping according to AWWA C600 or AWWA M41.

o Install ductile-iron special fittings according to AWWA C600.

o Install PVC pressure piping according to AWWA M23 or to ASTM D 2774 and ASTM F 1668.

Drawings:

4.2. Refer to sheet P410:

a. Coded note 10, installation of trap primer, revised to read as follows:

i. TRAP PRIMER UNIT (TP-1) – PRECISION PRODUCTS, INC. ELECTRONIC SURFACE

MOUNTED TRAP PRIMER MODEL PTS-4. INSTALL IN ACCORDANCE WITH

MANUFACTURER’S RECOMMENDATIONS. EXTEND ½” TRAP PRIMER LINES DOWN

ON WALL THROUGH FLOOR AND EXTEND BELOW SLAB TO FLOOR DRAINS. MOUNT

BOTTOM OF BOX 30” A.F.F. PROVIDE ANGLE IRON FRAME SUPPORT AS REQUIRED

FOR TRAP PRIMER AND PIPING. CAP ANY UNUSED OUTLETS.

b. Coded note 11, installation of trap primer, revised to read as follows:

i. TRAP PRIMER UNIT (TP-2) – PRECISION PRODUCTS, INC. MINI-PRIME ELECTRONIC

SURFACE MOUNTED TRAP PRIMER MODEL MPB-500-115V WITH AIR GAP AND BOX.

INSTALL IN ACCORDANCE WITH MANUFACTURER’S RECOMMENDATIONS. EXTEND

½” TRAP PRIMER LINE DOWN ON WALL THROUGH FLOOR AND EXTEND BELOW

SLAB TO FLOOR DRAIN. MOUNT BOTTOM OF BOX 30” A.F.F. PROVIDE ANGLE IRON

FRAME SUPPORT AS REQUIRED FOR TRAP PRIMER AND PIPING.

4.3. Refer to sheet P420:

a. Coded note 3, installation of trap primer, revised to read as follows:

i. TRAP PRIMER UNIT (TP-1) – PRECISION PRODUCTS, INC. ELECTRONIC SURFACE

MOUNTED TRAP PRIMER MODEL PTS-4. INSTALL IN ACCORDANCE WITH

MANUFACTURER’S RECOMMENDATIONS. EXTEND ½” TRAP PRIMER LINES DOWN

ON WALL THROUGH FLOOR AND EXTEND BELOW SLAB TO FLOOR DRAINS. MOUNT

BOTTOM OF BOX 30” A.F.F. PROVIDE ANGLE IRON FRAME SUPPORT AS REQUIRED

FOR TRAP PRIMER AND PIPING. CAP ANY UNUSED OUTLETS.

b. Coded note 4, installation of trap primer, revised to read as follows:

i. TRAP PRIMER UNIT (TP-2) – PRECISION PRODUCTS, INC. MINI-PRIME ELECTRONIC

SURFACE MOUNTED TRAP PRIMER MODEL MPB-500-115V WITH AIR GAP AND BOX.

INSTALL IN ACCORDANCE WITH MANUFACTURER’S RECOMMENDATIONS. EXTEND

½” TRAP PRIMER LINE DOWN ON WALL THROUGH FLOOR AND EXTEND BELOW

SLAB TO FLOOR DRAIN. MOUNT BOTTOM OF BOX 30” A.F.F. PROVIDE ANGLE IRON

FRAME SUPPORT AS REQUIRED FOR TRAP PRIMER AND PIPING.

4.4. Refer to sheet P800:

a. “DUPLEX SEWAGE EJECTOR DETAIL” - Rust-resistant steel is acceptable for sewage ejector basin lid.

b. “DUPLEX SEWAGE EJECTOR DETAIL” revised to specify 30 GPM at 12 FT head.

5. ELECTRICAL:

Drawings:

Addendum 7 Page 3 of 3

201 W. Short Street • Suite 700 • Lexington, KY 40507 • 859.231.7538 • fax 859.255.4380 • www.eopa.com

5.1. Refer to drawing sheet E410 coded note 12: delete the word Motorola.

6. BIDDERS QUESTIONS:

6.1. Question: The response to question 5.10 in Addendum 5 states that the 3/8” AR500 plates on the walls is required for ballistic containment. However, the solid grouted CMU wall section already provides the required ballistic containment, therefore the 3/8” AR500 plate is an expensive redundancy. May it be omitted?

Answer: No, the steel plate may not be omitted.

6.2. Question: The drawings show a hard ceiling above the baffles to contain the ventilation system air flow. Would it be acceptable to provide 18 ga flashing between the heel & toe of adjacent baffles to keep the laminar air flow below the baffles, eliminating the need for the costly GWB ceiling? This is the common design for walk down / tactical ranges.

Answer: No, Gypsum ceiling is to remain. Light fixtures are placed above the baffles and this also has heating and cooling load implications.

6.3. Question: I am getting quite a few folks asking about the regional materials and addenda #5 has verbiage in it for the brick to be sourced within 500 miles, which will likely not be an issue but the wood could pose a problem. Are LEEDS requirements mandated for this project?

Answer: Refer to specification clarification, revising rough carpentry to be within 500 miles. This project is not going to be a LEED Registered project, but still retains many LEED requirements.

6.4. Question: Reviewing Addendum 5, Division 28 Specs there were not specifications listed however the updates were made on the plans. RFI 1: Add 5, E410 Coded note 12 – The note states to provide Motorola Camera to match existing DOCJT Avigilon H6 mini dome. What is the existing model of the H6 Camera and what megapixel is desired?

Answer: Refer to drawing sheet E410 coded note 12: delete the word Motorola.

END OF ADDENDUM

DOCJT Indoor Firing Range

Commonwealth of Kentucky

Construction Documents - March 2023

Account Number 525CAL3CJ3600

SLIDING METAL DOORS 081180 - 1

SECTION 081180 - SLIDING METAL DOORS

PART 1 - GENERAL

1.1 RELATED DOCUMENTS

A. Drawings and general provisions of the Contract, including General and Supplementary

Conditions and Division 01 Specification Sections, apply to this Section.

1.2 SUMMARY

A. Section Includes:

1. Single-leaf, sliding door; manually operated.

B. Related Requirements:

1. Section 099113 "Exterior Painting" for on-site finish painting of factory prime-coated sliding metal doors.

1.3 ACTION SUBMITTALS

A. Product Data: For each type of product.

1. Include construction details, material descriptions, dimensions of individual components, and finishes.

B. Shop Drawings:

1. Include plans, elevations, sections, and mounting details.

2. Include details of equipment assemblies. Indicate dimensions, required clearances, method of field assembly, components, and location and size of each field connection.

3. Include points of attachment and their corresponding static and dynamic loads imposed on structure.

1.4 INFORMATIONAL SUBMITTALS

A. Qualification Data: For Installer .

SLIDING METAL DOORS 081180 - 2

1.5 CLOSEOUT SUBMITTALS

A. Operation and Maintenance Data: For sliding metal doors to include in operation, and maintenance manuals.

1.6 FIELD CONDITIONS

A. Field Measurements: Indicate measurements on Shop Drawings.

PART 2 - PRODUCTS

2.1 SLIDING METAL DOOR WITH BALLISTIC STEEL PLATE

A. Door Type: Overhead supported from wall-mounted track , with hidden reinforcements for mounting- and hardware-attachment locations, and with attached armor edges and astragals.

1. Configuration: Single-leaf .

2. Tubular-Frame Construction: Facing material welded to both sides of steel-tube perimeter frame and internal stiffeners, with mitered corner joints in frame and welded frame and stiffener joints; joints in face sheets located over stiffeners. Splice panel sections of wide leaves with a manufacturer's continuous, surface-applied, through-bolt splice plate or otherwise reinforce panels at connecting joints to provide a solid one-piece door. Weld and fill joints and grind exposed welds smooth and flush. Frame shall be heavy duty construction suitable for the weight of the door.

B. Operating System: Manual .

C. Facing Material:

1. Ballistic Steel Sheet at Interior Face: Factory prime finish 3/8 inch AR 500 steel plate at interior surface of sliding door.

2. Steel Sheet at Exterior Face: Factory prime finish steel sheet at exterior surface of sliding door.

D. Operating Hardware: Manufacturer's standard, heavy duty type (suitable for the weight of the door), sliding door hardware complete with track, roller assemblies, adjustable roller guides, binders, floor stops, as required. Furnish necessary hangers, fittings, and fasteners required for attaching hardware to door and for door sliding operation, including latch or handle for manual operation.

E. Crush Plates: Continuous 3/16-inch-thick by 6-inch-wide steel-bearing plates on hollow concrete masonry walls to bridge wall cavities and prevent through-wall bolts from crushing the masonry units.

SLIDING METAL DOORS 081180 - 3

2.2 MATERIALS

A. Steel Plate, Shapes, and Bars: ASTM A 36/A 36M.

B. Ballistic Steel Sheets: 3/8" AR 500 steel plate.

C. Steel Sheets: ASTM A 1008/A 1008M, cold rolled or ASTM A 1011/A 1011M, hot rolled

Commercial Steel (CS) or Drawing Steel (DS).

D. Metallic-Coated Steel Sheet: ASTM A 653/A 653M, Commercial Steel (CS), with G60 zinc coating; restricted flatness.

E. Hardware and Fastener Finish: Hot-dip galvanize according to ASTM A 153/A 153M where units are used on galvanized-steel exterior doors .

2.3 FABRICATION

A. Fabricate sliding metal door assemblies to be rigid and free of defects, warp, or buckle. Where practical, fit and assemble units in manufacturer's plant. To ensure proper assembly at Project site, clearly identify work that cannot be permanently factory assembled before shipment.

B. Factory prepare sliding metal door assemblies and frames to receive hardware and accessories including cutouts, reinforcements, mortising, drilling, and tapping.

2.4 METALLIC-COATED STEEL SHEET FINISHES

A. Surface Preparation: Clean surfaces of oil and other contaminants. Use cleaning methods that do not leave residue. After cleaning, apply a conversion coating compatible with the organic coating to be applied over it. Clean welds, mechanical connections, and abraded areas and apply galvanizing repair paint, complying with SSPC-Paint 20, to comply with

ASTM A 780/A 780M.

B. Factory Prime Finish: After cleaning and pretreating, apply an air-dried primer compatible with the organic coating to be applied over it.

2.5 STEEL FINISHES

A. Surface Preparation: Remove mill scale and rust, if present, from uncoated steel, complying with SSPC-SP 6/NACE No. 3, "Commercial Blast Cleaning" or SSPC-SP 7/NACE No. 4, "Brush-off

Blast Cleaning" . After cleaning, apply a conversion coating compatible with the organic coating to be applied over it.

B. Factory Prime Finish: After surface preparation and pretreatment, apply manufacturer's standard, fast-curing, lead- and chromate-free, universal primer.

SLIDING METAL DOORS 081180 - 4

PART 3 - EXECUTION

3.1 EXAMINATION

A. Examine substrates, areas, and conditions, with Installer present, for compliance with requirements for installation tolerances and other conditions affecting performance of the

Work.

1. Examine floor under door to confirm that floor is level for the full travel of door.

2. Examine wall where track assembly mounts and area behind door to confirm that wall is smooth and in same plane for the full travel of door.

B. Proceed with installation only after unsatisfactory conditions have been corrected.

3.2 INSTALLATION

A. Install sliding metal doors according to manufacturer's written instructions for type of door operation indicated.

B. Masonry: Install continuous crush plates between concrete masonry walls and tracks and operating mechanisms mounted to the walls.

C. Drill necessary holes for anchors in concrete and masonry cleanly, with no broken areas or spalls. Remove and replace or repair damaged concrete and masonry as directed.

3.3 ADJUSTING

A. Adjust hardware and moving parts to function smoothly, and lubricate as recommended by manufacturer.

END OF SECTION 081180

FP

FP

REVISION HISTORY OF THIS DRAWING

DECA LOG #

DRAWN BY

AS BULT DATE

COMMONWEALTH OF KENTUCKY

FINANCE AND ADMINISTRATION CABINET

DEPARTMENT FOR FACILITIES AND SUPPORT SERVICES

DIVISION OF ENGINEERING AND CONTRACT ADMINISTRATION

FRANKFORT, KENTUCKY

DESCRIPTION OF REVISIONS DATE DESCRIPTION OF REVISIONS DATE

CHECKED BY

PHASE

RTA DATE

DRAWING DATE

A & E FILE NO.

DRAWING INFORMATION

DRAWING NO.

ENGR. FILE NO.

RECORD DWG. DATE

DOCJT FIRING RANGE

HANCOCK TAYLOR LN.1956.01

CARMAN

LANDSCAPE ARCHITECTURE

URBAN PLANNING

CIVIL ENGINEERING

525CAL3CJ3600

CARMAN- 22.138

2023|03|14

JC

TD

D 2023|03|14

SANITARY SEWER PLAN

A7.0

NORTH

SCALE:

feet30 60 90

1" = 30'

GRAPHIC KEY

UTILITY NOTE

Kentucky 811

SPECIAL NOTES

REFER TO MEP SHEET U100 FOR LOCATION

TO CONNECT TO SANITARY SEWER PRESSURE

PIPE EXTENDED FROM BUILDING.

PRESSURE PIPE SHALL TIE INTO

EXISTING SAN SEWER MANHOLE

PVC FORCE-MAIN INSTALLATION

2023|04|20

CONTRACTOR SHALL LOCATE A PATH

FOR SEWER PIPE HAVING MINIMAL

OBSTRUCTIONS, AVOIDING EXISTING

TREES, SITE DRAINAGE STRUCTURES, ETC.

COORDINATE WITH GAS UTILTY

PRIOR TO PERFORMING WORK

NEAR GAS LINE CROSSINGS

EXISTING TREES TO REMAIN, TYP

1 Addendum #7

C3.3

H AI - Zone Humidity

P AI - Average Differential PressureM M M M

CHWS

CHWR

AO - Cooling Valve (x2)

CHWCHW

HWS

HWR

AO - Heating Valve (x2)

HWHW

BI - Smoke DetectorBI - Freezestat

T

T

T

AI - Discharge Air Temp

T

AI - CW Coil Air Temp

M

VFD

CT

BI - Exhaust Fan Status

BO - Exhaust Fan Start/Stop

Fan Array wired to single power point connection

M

VFD

CT

BI - Supply Fan Status

BO - Supply Fan Start/Stop

Fan Array wired to single power point connection

M M

BI - Zone Override

AI - Zone Setpoint Adjust

AI - Run-Around Loop Coil Discharge Air Temp

AI - Return Air Temp

AI - Outside Air Temp

AI - Exhaust Air Temp

AI - Run-Around Loop Temp

AO - Run-Around Loop Bypass Valve

BO - Run-Around Loop Pump Start/Stop (x2)

BI - Run-Around Loop Pump Status (x2)

T

T

EA RA

T

MCT

M

T

T

CT

BO - Coil Pump Start/Stop (x2)

BI - Coil Pump Status (x2)

CT

BO - Coil Pump Start/Stop (x2)

BI - Coil Pump Status (x2)

BI - Auto-reset Freezestat

H L

AI - Filter Differential Pressure

H L

AI - HEPA Filter Differential Pressure

H L

AI - Filter Differential Pressure

S

BO - Outside Air Damper

BI - Outside Air Damper Status

N.C.

OA

T

AI - Zone Temp

DA

NOTE:

IT IS NOT INTENDED THAT THE PLANS SHOW ALL OFFSETS IN PIPES, CONDUITS, AND DUCTS REQUIRED FOR INSTALLATION OF THE WORK. DETAILS AND SECTIONS ARE INCLUDED FOR SOME AREAS TO SHOW INTENDED RELATIONSHIP OF THE WORK OF VARIOUS TRADES. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR AND SUB-CONTRACTORS TO COORDINATE INSTALLATION OF THE

WORK AND TO PROVIDE THE NECESSARY OFFSETS, TRANSFORMATIONS, AND FITTINGS REQUIRED. NO ADDITIONAL COMPENSATION WILL BE ALLOWED FOR CORRECTION CONFLICTS BETWEEN THE WORK OF VARIOUS TRADES. DETAILS AND SECTIONS ARE SHOWN FOR THE CONTRACTORS CONVENIENCE AND SHALL NOT BE CONSIDERED COMPLETE IN EVERY DETAIL.

E

SE

R P

OF

S T

TA

E

NENIS O LA

E L

I C N S

IG

N

EE

D R

MATTHEW A.

N

36023

JUMP

OF KE

Y

CK

UT

REVISION HISTORY OF THIS DRAWING

DECA LOG #

DRAWN BY

AS BULT DATE

COMMONWEALTH OF KENTUCKY

FINANCE AND ADMINISTRATION CABINET

DEPARTMENT FOR FACILITIES AND SUPPORT SERVICES

DIVISION OF ENGINEERING AND CONTRACT ADMINISTRATION

FRANKFORT, KENTUCKY

DESCRIPTION OF REVISIONS DATE DESCRIPTION OF REVISIONS DATE

CHECKED BY

PHASE

RTA DATE

DRAWING DATE

A & E FILE NO.

DRAWING INFORMATION

DRAWING NO.

ENGR. FILE NO.

/2

/2

:2

:5

A

M

M902

MECHANICAL CONTROLS

525CAL3CJ3600

RECORD DWG. DATE

DOCJT FIRING RANGE

HANCOCK TAYLOR LN.

2023|03|14

1956.01

DHB

MAJ

2023|03|14

D

1. 100% Outside Air Range Unit (typical of 1) Run Conditions – Manual Start:

The unit shall run when commanded to via control signal or the local override momentary switch is activated:

• Occupied Mode: The unit shall maintain

• A 75°F (adj.) cooling setpoint and 60% (adj.) RH

• A 70°F (adj.) heating setpoint.

• Unoccupied Mode (night setback): The unit shall maintain

• A 85°F (adj.) cooling setpoint.

• A 55°F (adj.) heating setpoint.

The unit shall shut down if the exhaust air unit is shut down on failure or alarm.

Alarms shall be provided as follows:

• High Zone Temp: If the zone temperature is greater than the cooling setpoint by a user definable amount (adj.).

• Low Zone Temp: If the zone temperature is less than the heating setpoint by a user definable amount (adj.).

• High Relative Humidity: If the zone relative humidity is higher than the humidity setpoint by a user definable amount (adj.).

Status Lights Provide two lights in range area to indicate status of this unit. Red light shall indicate unit is not running at occupied. Green light shall indicate unit is running at full, occupied speed.

Zone Setpoint Adjust:

The occupant shall be able to adjust the zone temperature heating and cooling setpoints at the zone sensor.

Emergency Shutdown:

The unit shall shut down and generate an alarm upon receiving an emergency shutdown signal.

Freeze Protection:

The unit shall shut down and generate an alarm upon receiving a freezestat status.

Fire Alarm Shutdown:

The unit shall shut down and generate an alarm upon receiving a signal from the fire alarm system.

Outside Air Damper:

The outside air damper shall open anytime the unit runs and shall close anytime the unit stops. The supply fan shall start only after the damper status has proven the damper is open. The outside air damper shall close 4sec (adj.) after the supply fan stops.

Alarms shall be provided as follows:

• Outside Air Damper Failure: Commanded open, but the status is closed.

• Outside Air Damper in Hand: Commanded closed, but the status is open.

Heat Recovery - Run-Around Loop Coils:

The controller shall run the run-around loop pump and modulate the run-around loop mixing valve for energy recovery as follows.

Cooling Recovery Mode:

The run-around loop pump shall run continuously and the three-way valve shall be open to both air handlers. The run-around loop shall run for cool recovery whenever:

• Return air temperature is 8°F (adj.) or more below the outside air temperature.

• AND the zone temperature is above cooling setpoint.

• AND the supply fan is on.

Heating Recovery Mode:

The run-around loop pump shall run continuously. The run-around loop shall run for heat recovery whenever:

• Return air temperature is 8°F (adj.) or more above the outside air temperature.

• AND the zone temperature is below heating setpoint.

• AND the supply fan is on.

Frost Protection:

The run-around loop pump shall run and the run-around loop mixing valve shall close to 0% (adj.) in order to circulate water through the exhaust air coil only whenever:

• Run-around loop temperature drops below 33°F (adj.)

• OR the exhaust air temperature drops below 30°F (adj.).

• OR the exhaust air freezestat senses freezing condition in any 1' section (this freezestat shall not require a manual reset)

Alarms shall be provided as follows:

• Run-Around Loop Pump Failure: Commanded on, but the status is off.

• Run-Around Loop Pump in Hand: Commanded off, but the status is on.

• Run-Around Loop Pump Runtime Exceeded: Status runtime exceeds a user definable limit (adj.).

The two pump shall operate in a lead/standby manner and the controller shall alternate the lead run-around pump on a weekly (adj.) basis.

Supply Fan Array:

The supply fan array shall run anytime the unit is commanded to run. To prevent short cycling, the supply fan shall have a user definable (adj.)

minimum runtime, unless shutdown on safeties. The array shall run at maximum speed (as determined by the balancer) to provide 112,500 CFM when enabled for range use. The array shall run at 20% speed anytime it is commanded on to maintain unoccupied temperature setpoints.

Alarms shall be provided as follows:

• Supply Fan Failure: Commanded on, but the status is off.

• Supply Fan in Hand: Commanded off, but the status is on.

• Supply Fan Runtime Exceeded: Status runtime exceeds a user definable limit (adj.).

Cooling Coil Valves:

The controller shall measure the zone temperature and modulate the cooling coil valves to maintain its cooling setpoint.

The cooling shall be enabled whenever:

• Outside air temperature is greater than 60°F (adj.).

• AND the zone temperature is above cooling setpoint.

• AND the fan status is on.

The cooling coil valves shall open to 50% (adj.) whenever the freezestat is on.

Cooling Coil Pumps:

The controller shall monitor the cooling coil control valves. The coil pumps shall start when the flow is below 50% and stop when the flow is above 50% or fully closed. The pumps shall also run anytime the freeze stat is tripped.

Heating Coil Valves:

The controller shall measure the zone temperature and modulate the heating coil valves to maintain its heating setpoint.

The heating shall be enabled whenever:

• Outside air temperature is less than 65°F (adj.).

• AND the zone temperature is below heating setpoint.

• AND the fan status is on.

The heating coil valve shall open to 100% (adj.) whenever the freezestat is on.

Heating Coil Pumps:

The controller shall monitor the heating coil control valves. The coil pumps shall start when the flow is below 50% and stop when the flow is above 50% or fully closed.

Dehumidification:

The controller shall monitor space relative humidity. When the space relative humidity rises above 60% (adj.) RH, the unit shall go into dehumidificaiton mode. In this mode, the cooling coil valves shall modulate to maintain 55°F (adj.) cooling coil leaving temperature. The heating coil valves shall modulate to maintain space temperature setpoint.

Filter Differential Pressure Monitor:

The controller shall monitor the differential pressure across the filter.

Alarms shall be provided as follows:

• Filter Change Required: Filter differential pressure exceeds a user definable limit (adj.).

Discharge Air Temperature:

The controller shall monitor the discharge air temperature.

Alarms shall be provided as follows:

• High Discharge Air Temp: If the discharge air temperature is greater than 120°F (adj.).

• Low Discharge Air Temp: If the discharge air temperature is less than 40°F (adj.).

Alarms shall be provided as follows:

• High Zone Humidity: If the zone humidity is greater than 70% (adj.).

• Low Zone Humidity: If the zone humidity is less than 35% (adj.).

1. 100% Exhaust Air Range Unit

Run Conditions – Manual Start:

The unit shall run whenever the 100% Outside Air Range Unit is commanded to run. The unit shall be disabled anytime the 100% Outside Air Range Unit is commanded off or is disabled via failure or alarm.

Exhaust Air Dampers:

The exhaust air dampers shall open anytime the unit runs and shall close anytime the unit stops. The exhaust fan shall start only after the damper status has proven the damper is open. The exhaust air damper shall close 4sec (adj.) after the exhaust fan stops.

Alarms shall be provided as follows:

• Exhaust Air Damper Failure: Commanded open, but the status is closed.

• Exhaust Air Damper in Hand: Commanded closed, but the status is open.

Exhaust Fan Array:

The exhaust fan array shall run anytime the unit is commanded to run. To prevent short cycling, the exhaust fan shall have a user definable (adj.)

minimum runtime, unless shutdown on safeties. The controller shall measure the average differential pressure between the range and the office space by reading the three differential pressure sensors shown on the plans. The controller shall modulate the two exhaust fan array variable frequency drives to maintain a 0.05” (adj.) differential between the two buildings.

Alarms shall be provided as follows:

• Exhaust Fan Failure: Commanded on, but the status is off.

• Exhaust Fan in Hand: Commanded off, but the status is on.

• Exhaust Fan Runtime Exceeded: Status runtime exceeds a user definable limit (adj.).

Filter Differential Pressure Monitor:

The controller shall monitor the differential pressure across the pre-filter and final HEPA filter.

Alarms shall be provided as follows:

• Filter Change Required: Filter differential pressure exceeds a user definable limit (adj.).

3 Addendum #7 4/20/2023

RF

N.C.

M

M

CT

VFD

BO - Supply Fan Start/Stop

BI - Supply Fan Status

AO - Supply Fan VFD Speed

BI - Supply Fan VFD Fault

Locate ¾ distance down longest duct

H

L

AI - Supply Air Static Pressure

SA

BI - High Static Shutdown

H L

HWS

HWR

AO - Heating Valve M

HW

AO - Cooling Valve

CHWS

CHWR

M

CHW

M

BO - Return Fan Start/Stop

BI - Return Fan Status

AO - Return Fan VFD Speed

BI - Return Fan VFD Fault

CT

VFD

EA

BI - Return Air Smoke Detector

H L

AI - Prefilter Differential Pressure

AI - Mixed Air Temp

T

AI - HW Coil Air Temp

TT

AI - CW Coil Air Temp

M

M AO - Mixed Air Dampers

N.O.

N.C.

BI - Freezestat

T

H

AI - Return Air Humidity

T

AI - Return Air Temp

OA

RA

T

AI - Supply Air Temp

SF

NOTE:

IT IS NOT INTENDED THAT THE PLANS SHOW ALL OFFSETS IN PIPES, CONDUITS, AND DUCTS REQUIRED FOR INSTALLATION OF THE WORK. DETAILS AND SECTIONS ARE INCLUDED FOR SOME AREAS TO SHOW INTENDED RELATIONSHIP OF THE WORK OF VARIOUS TRADES. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR AND SUB-CONTRACTORS TO COORDINATE INSTALLATION OF THE

WORK AND TO PROVIDE THE NECESSARY OFFSETS, TRANSFORMATIONS, AND FITTINGS REQUIRED. NO ADDITIONAL COMPENSATION WILL BE ALLOWED FOR CORRECTION CONFLICTS BETWEEN THE WORK OF VARIOUS TRADES. DETAILS AND SECTIONS ARE SHOWN FOR THE CONTRACTORS CONVENIENCE AND SHALL NOT BE CONSIDERED COMPLETE IN EVERY DETAIL.

E

SE

R P

OF

S T

TA

E

NENIS O LA

E L

I C N S

IG

N

EE

D R

MATTHEW A.

N

36023

JUMP

OF KE

Y

CK

UT

REVISION HISTORY OF THIS DRAWING

DECA LOG #

DRAWN BY

AS BULT DATE

COMMONWEALTH OF KENTUCKY

FINANCE AND ADMINISTRATION CABINET

DEPARTMENT FOR FACILITIES AND SUPPORT SERVICES

DIVISION OF ENGINEERING AND CONTRACT ADMINISTRATION

FRANKFORT, KENTUCKY

DESCRIPTION OF REVISIONS DATE DESCRIPTION OF REVISIONS DATE

CHECKED BY

PHASE

RTA DATE

DRAWING DATE

A & E FILE NO.

DRAWING INFORMATION

DRAWING NO.

ENGR. FILE NO.

/2

/2

:2

:5

A

M

M903

MECHANICAL CONTROLS

525CAL3CJ3600

RECORD DWG. DATE

DOCJT FIRING RANGE

HANCOCK TAYLOR LN.

2023|03|14

1956.01

DHB

MAJ

2023|03|14

D

1. Variable Air Volume - AHU (typical of 1)

Run Conditions - Scheduled:

The unit shall run based upon an operator adjustable schedule.

Freeze Protection:

The unit shall shut down and generate an alarm upon receiving a freezestat status.

High Static Shutdown:

The unit shall shut down and generate an alarm upon receiving an high static shutdown signal.

Fire Alarm Shutdown:

The unit shall shut down and generate an alarm upon receiving a signal from the fire alarm system.

Supply Fan:

The supply fan shall run anytime the unit is commanded to run, unless shutdown on safeties. To prevent short cycling, the supply fan shall have a user definable (adj.) minimum runtime.

Alarms shall be provided as follows:

• Supply Fan Failure: Commanded on, but the status is off.

• Supply Fan in Hand: Commanded off, but the status is on.

Supply Air Duct Static Pressure Control:

The controller shall measure duct static pressure and shall modulate the supply fan VFD speed to maintain a duct static pressure setpoint of 1.5in H2O (adj.).

Alarms shall be provided as follows:

• High Supply Air Static Pressure: If the supply air static pressure is 25% (adj.) greater than setpoint.

• Low Supply Air Static Pressure: If the supply air static pressure is 25% (adj.) less than setpoint.

• Supply Fan VFD Fault.

Return Fan:

The return fan shall run whenever the supply fan runs.

Alarms shall be provided as follows:

• Return Fan Failure: Commanded on, but the status is off.

• Return Fan in Hand: Commanded off, but the status is on.

• Return Fan VFD Fault.

Return Fan Tracking:

The return fan VFD shall modulate in unison with the supply fan VFD. The return fan VFD shall track the supply fan VFD at 80% (adj.) of the supply fan VFD speed. The return fan VFD speed shall not drop below 20% (adj.).

Supply Air Temperature Setpoint - Fixed:

The controller shall monitor the supply air temperature and shall maintain fixed supply air temperature setpoints as follows:

• Cooling: The setpoint shall be 55°F (adj.).

• Heating: The setpoint shall be 55°F (adj.)

Cooling Coil Valve:

The controller shall measure the supply air temperature and modulate the cooling coil valve to maintain its cooling setpoint.

The cooling shall be enabled whenever:

• The supply fan status is on.

• AND the heating (if present) is not active.

The cooling coil valve shall open to 50% (adj.) whenever the freezestat (if present) is on.

Alarms shall be provided as follows:

• High Supply Air Temp: If the supply air temperature is 5°F (adj.) greater than setpoint.

Heating Coil Valve:

The controller shall measure the supply air temperature and modulate the heating coil valve to maintain its heating setpoint.

The heating shall be enabled whenever:

• The supply fan status is on.

• AND the cooling (if present) is not active.

Whenever the freeze stat trips, the heating coils shall modulate to maintain heating coil leaving temperature of 55°F (adj.).

Alarms shall be provided as follows:

• Low Supply Air Temp: If the supply air temperature is 5°F (adj.) less than setpoint.

Economizer:

The controller shall measure the mixed air temperature and modulate the economizer dampers in sequence to maintain discharge air temperature. The outside air dampers shall maintain a minimum adjustable position of 24% (adj.) open whenever occupied. Economizer is to maintain a minimum of 45°F (adj.).

The economizer shall be enabled whenever:

• Outside air temperature is less than 65°F (adj.).

• AND the outside air temperature is less than the return air temperature.

• AND the supply fan status is on.

The economizer shall close whenever:

• Mixed air temperature drops from 40°F to 35°F (adj.).

• OR the freezestat (if present) is on.

• OR on loss of supply fan status.

The outside and exhaust air dampers shall close and the return air damper shall open when the unit is off. If Optimal Start Up is available the mixed air damper shall operate as described in the occupied mode except that the outside air damper shall modulate to fully closed.

Minimum Outside Air Ventilation - Fixed Percentage:

The outside air dampers shall maintain a minimum adjustable position during building occupied hours and be closed during unoccupied hours.

Prefilter Differential Pressure Monitor:

The controller shall monitor the differential pressure across the prefilter.

Alarms shall be provided as follows:

• Prefilter Change Required: Prefilter differential pressure exceeds a user definable limit (adj.).

Mixed Air Temperature:

The controller shall monitor the mixed air temperature and use as required for economizer control (if present) or preheating control (if present).

Alarms shall be provided as follows:

• High Mixed Air Temp: If the mixed air temperature is greater than 90°F (adj.).

• Low Mixed Air Temp: If the mixed air temperature is less than 45°F (adj.).

Return Air Humidity:

The controller shall monitor the return air humidity and use as required for economizer control (if present) or humidity control (if present).

Alarms shall be provided as follows:

• High Return Air Humidity: If the return air humidity is greater than 70% (adj.).

• Low Return Air Humidity: If the return air humidity is less than 35% (adj.).

Return Air Temperature:

The controller shall monitor the return air temperature and use as required for setpoint control or economizer control (if present).

Alarms shall be provided as follows:

• High Return Air Temp: If the return air temperature is greater than 90°F (adj.).

• Low Return Air Temp: If the return air temperature is less than 45°F (adj.).

Supply Air Temperature:

The controller shall monitor the supply air temperature.

CW Coil Temperature:

The controller shall monitor the CW Coil discharge air temperature.

Alarms shall be provided as follows:

• High Supply Air Temp: If the supply air temperature is greater than 120°F (adj.).

• Low Supply Air Temp: If the supply air temperature is less than 45°F (adj.).

116V 116U

100B

130C

130E

130D

130B130A

124A

124C

124B

122C

122B

122A

120 111 112

L-1 L-1

WC-1 WC-1A SH-1A SH-1

SH-1A SH-1 SH-1WC-1AUR-1

L-1 L-1

MB-1

WC-1A

WC-1A

UR-1

L-2 L-2

EWC-1

S-1

S-1

A

FFD-2-TP

FFD-2-TP

FFD-2-TP

FD-1

FD-1

FD-1

FD-1

FFD-2-TP

FFD-2-TP

A D

B E FC

H

I

J

K

L

M N O P Q RB.1

3.9

IM-1

HB-1

HB-1

HB-1

WH-1

3/4" DCW UP

IN WALL TO

HOSE BIBB.

3 3

FD-3 FD-3 FD-3

FD-3FD-3

HB-1

D H

W

D C

W

/4

D

H W

R

D H

W

D C

W

/2

D C

W

/2

D H

W

1 1/2" DHW

2 1/2" DCW

3/4" DCW

3/4" DHW

/2

G

G

G

WH-1

WH-1

3/4" DCW

3/4" A 3/4" A 3/4" A 3/4" A

3/4" A

D C

W

G-01

P610

3/4" DCW

WHA-200

HCR-01

P610

HCR-02

P610

HCR-03

P610

HCR-04

P610

HCR-05

P610

/4

A

/4

A

/4

A

/4

A

/4

A

NOTE:

IT IS NOT INTENDED THAT THE PLANS SHOW ALL OFFSETS IN PIPES, CONDUITS, AND DUCTS REQUIRED FOR INSTALLATION OF THE WORK. DETAILS AND SECTIONS ARE INCLUDED FOR SOME AREAS TO SHOW INTENDED RELATIONSHIP OF THE WORK OF VARIOUS TRADES. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR AND SUB-CONTRACTORS TO COORDINATE INSTALLATION OF THE

WORK AND TO PROVIDE THE NECESSARY OFFSETS, TRANSFORMATIONS, AND FITTINGS REQUIRED. NO ADDITIONAL COMPENSATION WILL BE ALLOWED FOR CORRECTION CONFLICTS BETWEEN THE WORK OF VARIOUS TRADES. DETAILS AND SECTIONS ARE SHOWN FOR THE CONTRACTORS CONVENIENCE AND SHALL NOT BE CONSIDERED COMPLETE IN EVERY DETAIL.

E

SE

R P

OF

S T

TA

E

NENIS O LA

E L

I C N S

IG

N

EE

D R

MATTHEW A.

N

36023

JUMP

OF KE

Y

CK

UT

REVISION HISTORY OF THIS DRAWING

DECA LOG #

DRAWN BY

AS BULT DATE

COMMONWEALTH OF KENTUCKY

FINANCE AND ADMINISTRATION CABINET

DEPARTMENT FOR FACILITIES AND SUPPORT SERVICES

DIVISION OF ENGINEERING AND CONTRACT ADMINISTRATION

FRANKFORT, KENTUCKY

DESCRIPTION OF REVISIONS DATE DESCRIPTION OF REVISIONS DATE

CHECKED BY

PHASE

RTA DATE

DRAWING DATE

A & E FILE NO.

DRAWING INFORMATION

DRAWING NO.

ENGR. FILE NO.

/2

/2

:5

:3

A

M

P410

DOMESTIC WATER PLUMBING PLAN - FIRST FLOOR

525CAL3CJ3600

RECORD DWG. DATE

DOCJT FIRING RANGE

HANCOCK TAYLOR LN.

2023|03|14

1956.01

MAJ

DWH

2023|03|14

D

ROOM SCHEDULE

ROOM NUMBER ROOM NAME

100 VEST.

100B CORRIDOR

110 CLASSROOM

111 WOMENS

112 MENS

113 OBSERVATION

114 STAIR A

115 RANGE CONTROL

116 FIRING LANES

116U BACKSTOP

116V SHOOTING LINE

117 MECH

119 MDF

120 COPY

121 OFFICE

122A STAFF MENS

122B MENS SHOWER

122C MENS LOCKER

123 JANITOR

124A STAFF WOMENS

124B WOMENS SHOWER

124C WOMENS LOCKER

125 OFFICE

126 OFFICE

127 OFFICE

128 STAFF BREAK

130A ARMORY

130B WEAPONS CLEANING

130C STORAGE/GARAGE

130D WEAPONS STORAGE

130E AMMO STORAGE

140 MECH

201 MECH. PENTHOUSE

SCALE: 1/8" = 1'-0"P410

1 DOMESTIC WATER PLUMBING PLAN - FIRST FLOOR

CODED NOTES:

1 GAS WATER HEATER WITH EXPANSION TANK, RECIRCULATING PUMP,

AND DIGITAL MIXING VALVE. SEE PLUMBING DETAILS, SHEET P800, FOR

WATER HEATER PIPING DIAGRAM.

2 AIR COMPRESSOR. SEE PLUMBING DETAILS.

3 PROVIDE AND INSTALL AIR HOSE REEL BELOW CEILING AT COMPRESSED

AIR TERMINATION. SEE DETAILS.

4 4" GAS LINE DOWN TO BOILER B-1 (6,000 MBH) OR B-2 (6,000 MBH).

PROVIDE GAS COCK AND DRIP LEG ON VERTICAL. SEE HVAC DRAWINGS.

5 1-1/2" GAS LINE DOWN TO WATER HEATER WH-1 (150 MBH). PROVIDE GAS

COCK AND DRIP LEG ON VERTICAL.

6 SEE SITE UTILITIES PLAN, SHEET U100, FOR CONTINUATION.

7 PROVIDE 2.0 GPM BALANCING ASSEMBLY. SEE SHEET P800 FOR DETAIL.

CODED NOTES:

8 REDUCED PRESSURE BACKFLOW PREVENTER MOUNTED VERTICALLY.

SEE PLUMBING DETAILS. SEE SITE UTILITY PLAN FOR CONTINUATION.

9 PROVIDE 1" MAKEUP WATER TO HOT WATER FILL STATION.

10 TRAP PRIMER UNIT (TP-1) -- PRECISION PRODUCTS, INC. ELECTRONIC

SURFACE MOUNTED TRAP PRIMER MODEL PTS-4. INSTALL IN

ACCORDANCE WITH MANUFACTURER'S RECOMMENDATIONS. EXTEND

1/2" TRAP PRIMER LINES DOWN ON WALL THROUGH FLOOR AND EXTEND

BELOW SLAB TO FLOOR DRAINS. MOUNT BOTTOM OF BOX 30" A.F.F.

PROVIDE ANGLE IRON FRAME SUPPORT AS REQUIRED FOR TRAP

PRIMER AND PIPING. CAP ANY UNUSED OUTLETS.

11 TRAP PRIMER UNIT (TP-2) -- PRECISION PRODUCTS, INC. MINI-PRIME

ELECTRONIC SURFACE MOUNTED TRAP PRIMER MODEL MPB-500-115V

WITH AIR GAP AND BOX. INSTALL IN ACCORDANCE WITH

MANUFACTURER'S RECOMMENDATIONS. EXTEND 1/2" TRAP PRIMER LINE

DOWN ON WALL THROUGH FLOOR AND EXTEND BELOW SLAB TO FLOOR

DRAIN. MOUNT BOTTOM OF BOX 30" A.F.F. PROVIDE ANGLE IRON FRAME

SUPPORT AS REQUIRED FOR TRAP PRIMER AND PIPING.

12 SEE WATER HEATER PIPING DETAIL, SHEET 800, FOR CONTINUATION.

13 3/4" DOMESTIC COLD WATER LINE UP.

14 WALL HYDRANT WH-1: WOODFORD MODEL B67, CONCEALED TYPE,

AUTOMATIC DRAINING, VACUUM BREAKER, 3/4" SIZE, FREEZEPROOF

WITH LOOSE KEY, POLISHED BRASS FINISH. MOUNT 36" ABOVE FINISHED

GRADE.

15 HOSE BIBB HB-1: WOODFORD MODEL B24P-3/4", ANTI-SIPHON, CHROME

FINISH, 3/4" THREADED HOSE CONNECTION, METAL WHEEL HANDLE AND

ASSE 1011 VACUUM BREAKER, FLUSH MOUNTED WALL BOX, WITH LOOSE

KEY LOCK. MOUNT BOTTOM OF BOX 18" A.F.F.

CODED NOTES:

16 ICE MAKER BOX IM-1: GUY GRAY, SSBI1 STAINLESS STEEL,

FREEZEPROOF WITH QUARTER TURN VALVE, BOX RECESSED IN WALL.

MOUNT WITH BOTTOM OF BOX 42" A.F.F.

17 PIPING ABOVE TILE CEILING WHERE APPLICABLE, OR IN CEILING SPACE.

18 PIPING IN CHASE.

FFD-2-TP

FFD-2-TP

FFD-2-TP

FFD-2-TP

FFD-2-TP

A D

B E FC

H

I

J

K

L

M N O P Q RB.1

3.9

HB-1

HB-1

/4

D

C W

3/4" DCW

NOTE:

IT IS NOT INTENDED THAT THE PLANS SHOW ALL OFFSETS IN PIPES, CONDUITS, AND DUCTS REQUIRED FOR INSTALLATION OF THE WORK. DETAILS AND SECTIONS ARE INCLUDED FOR SOME AREAS TO SHOW INTENDED RELATIONSHIP OF THE WORK OF VARIOUS TRADES. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR AND SUB-CONTRACTORS TO COORDINATE INSTALLATION OF THE

WORK AND TO PROVIDE THE NECESSARY OFFSETS, TRANSFORMATIONS, AND FITTINGS REQUIRED. NO ADDITIONAL COMPENSATION WILL BE ALLOWED FOR CORRECTION CONFLICTS BETWEEN THE WORK OF VARIOUS TRADES. DETAILS AND SECTIONS ARE SHOWN FOR THE CONTRACTORS CONVENIENCE AND SHALL NOT BE CONSIDERED COMPLETE IN EVERY DETAIL.

E

SE

R P

OF

S T

TA

E

NENIS O LA

E L

I C N S

IG

N

EE

D R

MATTHEW A.

N

36023

JUMP

OF KE

Y

CK

UT

REVISION HISTORY OF THIS DRAWING

DECA LOG #

DRAWN BY

AS BULT DATE

COMMONWEALTH OF KENTUCKY

FINANCE AND ADMINISTRATION CABINET

DEPARTMENT FOR FACILITIES AND SUPPORT SERVICES

DIVISION OF ENGINEERING AND CONTRACT ADMINISTRATION

FRANKFORT, KENTUCKY

DESCRIPTION OF REVISIONS DATE DESCRIPTION OF REVISIONS DATE

CHECKED BY

PHASE

RTA DATE

DRAWING DATE

A & E FILE NO.

DRAWING INFORMATION

DRAWING NO.

ENGR. FILE NO.

/2

/2

:0

:5

P

M

P420

DOMESTIC WATER PLUMBING PLAN - SECOND FLOOR

525CAL3CJ3600

RECORD DWG. DATE

DOCJT FIRING RANGE

HANCOCK TAYLOR LN.

2023|03|14

1956.01

MAJ

DWH

2023|03|14

D

ROOM SCHEDULE

ROOM NUMBER ROOM NAME

100 VEST.

100B CORRIDOR

110 CLASSROOM

111 WOMENS

112 MENS

113 OBSERVATION

114 STAIR A

115 RANGE CONTROL

116 FIRING LANES

116U BACKSTOP

116V SHOOTING LINE

117 MECH

119 MDF

120 COPY

121 OFFICE

122A STAFF MENS

122B MENS SHOWER

122C MENS LOCKER

123 JANITOR

124A STAFF WOMENS

124B WOMENS SHOWER

124C WOMENS LOCKER

125 OFFICE

126 OFFICE

127 OFFICE

128 STAFF BREAK

130A ARMORY

130B WEAPONS CLEANING

130C STORAGE/GARAGE

130D WEAPONS STORAGE

130E AMMO STORAGE

140 MECH

201 MECH. PENTHOUSE

SCALE: 1/8" = 1'-0"P420

1 DOMESTIC WATER PLUMBING PLAN - SECOND FLOOR

CODED NOTES:

1 PROVIDE HOSE BIB ADJACENT TO GLYCOL FILL SYSTEM FOR CHILLED

WATER SYSTEM.

2 PROVIDE HOSE BIB ADJACENT TO GLYCOL FILL SYSTEM FOR ENERGY

RECOVERY WATER SYSTEM.

3 TRAP PRIMER UNIT (TP-1) -- PRECISION PRODUCTS, INC. ELECTRONIC

SURFACE MOUNTED TRAP PRIMER MODEL PTS-4. INSTALL IN

ACCORDANCE WITH MANUFACTURER'S RECOMMENDATIONS. EXTEND

1/2" TRAP PRIMER LINES DOWN ON WALL THROUGH FLOOR AND EXTEND

BELOW SLAB TO FLOOR DRAINS. MOUNT BOTTOM OF BOX 30" A.F.F.

PROVIDE ANGLE IRON FRAME SUPPORT AS REQUIRED FOR TRAP

PRIMER AND PIPING. CAP ANY UNUSED OUTLETS.

4 TRAP PRIMER UNIT (TP-2) -- PRECISION PRODUCTS, INC. MINI-PRIME

ELECTRONIC SURFACE MOUNTED TRAP PRIMER MODEL MPB-500-115V

WITH AIR GAP AND BOX. INSTALL IN ACCORDANCE WITH

MANUFACTURER'S RECOMMENDATIONS. EXTEND 1/2" TRAP PRIMER LINE

DOWN ON WALL THROUGH FLOOR AND EXTEND BELOW SLAB TO FLOOR

DRAIN. MOUNT BOTTOM OF BOX 30" A.F.F. PROVIDE ANGLE IRON FRAME

SUPPORT AS REQUIRED FOR TRAP PRIMER AND PIPING.

E

SE

R P

OF

S T

TA

E

NENIS O LA

E L

I C N S

IG

N

EE

D R

MATTHEW A.

N

36023

JUMP

OF KE

Y

CK

UT

REVISION HISTORY OF THIS DRAWING

DECA LOG #

DRAWN BY

AS BULT DATE

COMMONWEALTH OF KENTUCKY

FINANCE AND ADMINISTRATION CABINET

DEPARTMENT FOR FACILITIES AND SUPPORT SERVICES

DIVISION OF ENGINEERING AND CONTRACT ADMINISTRATION

FRANKFORT, KENTUCKY

DESCRIPTION OF REVISIONS DATE DESCRIPTION OF REVISIONS DATE

CHECKED BY

PHASE

RTA DATE

DRAWING DATE

A & E FILE NO.

DRAWING INFORMATION

DRAWING NO.

ENGR. FILE NO.

/2

/2

:5

:5

A

M

P800

PLUMBING SCHEDULES & DETAILS

525CAL3CJ3600

RECORD DWG. DATE

DOCJT FIRING RANGE

HANCOCK TAYLOR LN.

2023|03|14

1956.01

MAJ

MAJ

2023|03|14

D

FIXTURE SCHEDULE AND ROUGHING-IN REQUIREMENTS

WALL HUNG,

FLOOR MOUNTED,

COUNTERTOP

FIXTURE

NUMBER

REMARKS

MOUNTING

HEIGHT

MOUNTINGFIXTURE HOT COLD WASTE

(MIN.)

VENT

(MIN.)

ACCESSORIESMANUFACTURER AND MODEL NO. FLUSH VALVE, FAUCET

RIM 34" AFF.

SEE REMARKS

L-1 1/2" 1/2" 1-1/2"LAVATORY

AMERICAN STANDARD DECORUM,

9024.001EC, CENTER HOLE ONLY,

VITREOUS CHINA, WHITE.

GRID STRAINER, P-TRAP,

STOPS & SUPPLIES,

CHROME PLATED.

1-1/4"

P-TRAP

FROM FLOOR TO TOP EDGE OF BASIN.

AMERICAN STANDARD

PARADIGM SELECTRONIC

7025.303, AUTOMATIC

FAUCET, VANDAL-

RESISTANT, 0.35 GPM,

MOUNTED TO COUNTERTOP.

1/2" 1/2" 1-1/4"

P-TRAP

1-1/2"LAVATORYL-2

SEE ARCH.

DWGS.

LAVATORY UNDERMOUNTED IN

COUNTERTOP. SEE ARCHITECTURAL

DRAWINGS.

1/2" 1/2" 1-1/2"

P-TRAP

1-1/2"SINK - SINGLE

COMPARTMENT

LK99 CRUMB CUP

STRAINER, P-TRAP

W/CLEANOUT, STOPS &

SUPPLIES.

S-1 ELKAY ECTRU21179T, 18-GAUGE

STAINLESS STEEL, 22-1/2" X 18-1/2"

X 9" DEEP BOWL.

UNDERMOUNT --- SINK MOUNTED IN COUNTERTOP. SEE

ARCHITECTURAL DRAWINGS.

SEE ARCH.

DWGS.

1/2" 1/2" 3" 1-1/2"FLOOR MOUNTED

SHOWER FLOOR/WALL 1/2" 1/2"ADA 2" W/ TPSH-1 SEE REMARKS 1-1/2"

KOHLER K-2882-0, VITREOUS CHINA,

WHITE, UNDERMOUNT.

UNDERMOUNT SEE REMARKS

DELTA 9159-LS-DST, SINGLE

HANDLE DECK MOUNT

FAUCET, 1.8GPM AT 60PSI, 2-

FUNCTION PULL-DOWN

SPRAYER, 15-INCH

GOOSENECK FAUCET.

ADA WALL HUNG

MB-1 MOP BASIN STERN-WILLIAMS HL-1910,

32"X32" PRECAST TERRAZZO,

6" DROP FRONT, STAINLESS

STEEL CAP ALL SIDES AND

SPLASH CATCHER PANELS.

S-W TB-15-VB SERVICE SINK

FAUCET WITH INTEGRAL

STOPS, LEVER HANDLES,

SPRING CHECKS, VACUUM

BREAKER, BUCKET HOOK

AND HOSE THREAD ON

SPOUT WITH WALL BRACE,

CHROME FINISH.

EACH BASIN SHALL BE

PROVIDED WITH A 832-

AA, 30" LONG RUBBER

HOSE AND 302

STAINLESS STEEL

BRACKET WITH RUBBER

GRIP.

--- 30". SEE

REMARKS

SEE DETAIL FOR MOUNTING HEIGHTS.

PROVIDE WITH VACUUM BREAKER, IN-LINE

BACK FLOW PREVENTER, QUICK

DISCONNECT FOR FLEXIBLE HOSE.

PROVIDE WITH ZURN 1023 TRAP PRIMER

CONNECTION ADAPTOR OR EQUAL.

FROM FLOOR TO CENTERLINE OF SUPPLIES.

--- --- ---1/2"

SEE

REMARKS

DW-1 DISHWASHER PROVIDED BY OWNER. --- ------ --- SEE

REMARKS

PROVIDE VALVED 1/2" DHW CONNECTION IN

SINK BASE CABINET AND AN AIR GAP

FITTING FOR WASTE CONNECTION.

WALL HUNG FLUSH VALVE HANDLE ON WIDE SIDE. INSTALL

WITH A ZURN ZN1209-N4B NARROW WALL

SUPPORT SYSTEM. SEE NOTE BELOW.

WATER CLOSETWC-1 --- 1" 4" 2"AMERICAN STANDARD AFWALL,

3351.101, VITREOUS CHINA,

WHITE.

ELONGATED SEAT, WHITE

OPEN FRONT.

ADA 18" FROM

FLOOR TO TOP

OF SEAT.

UR-1 --- 3/4" 1-1/2"URINAL ------SLOAN G2 8111-1.28,

AUTOMATIC, 1.28 GPF

SEE ARCH.

DWGS.

SEE ARCHITECTURAL DETAILS FOR

MOUNTING HEIGHTS.

KOHLER

K-4991-ET, VITREOUS CHINA

WALL HUNG SEE REMARKS

SHOWER FLOOR/WALL 1/2" 1/2"ADASH-1A SEE REMARKS 1-1/2"---

PRESSURE BALANCING

VALVE, FIXED HEAD &

HAND HELD SHOWER &

DIVERTER W/ 24" SLIDE

BAR & 5' FLEXIBLE METAL

HOSE

BRADLEY 1C-HD-DV-E1-

B24, 1.5 GPM

BRADLEY 1C-HD-DV-E1-

B24, 1.5 GPM

PRESSURE BALANCING

VALVE, FIXED HEAD &

HAND HELD SHOWER &

DIVERTER W/ 24" SLIDE

BAR & 5' FLEXIBLE METAL

HOSE

2" W/ TP SEE DETAIL FOR MOUNTING HEIGHTS.

PROVIDE WITH VACUUM BREAKER, IN-LINE

BACK FLOW PREVENTER, QUICK

DISCONNECT FOR FLEXIBLE HOSE.

PROVIDE WITH ZURN 1023 TRAP PRIMER

CONNECTION ADAPTOR OR EQUAL.

2"

ELECTRIC

WATER

COOLER WITH

BOTTLE FILLER

EWC-1 ELKAY LZSTL8WSLK, ELECTRONIC

BI-LEVEL ADA, LIGHT GRAY

GRANITE, FILTERED,

REFRIGERATED.

1/2" MOUNT ADA BUBBLER WITH SPOUT 36"

FROM FLOOR.

WALL HUNG--- BI-LEVEL --- 1-1/2"P-TRAP, SHUT-OFF

VALVE

--- 1-1/2"

GRID STRAINER, P-TRAP,

STOPS & SUPPLIES,

CHROME PLATED.

AMERICAN STANDARD

PARADIGM SELECTRONIC

7025.303, AUTOMATIC

FAUCET, VANDAL-

RESISTANT, 0.35 GPM,

MOUNTED TO COUNTERTOP.

SLOAN G2 8111-1.28,

AUTOMATIC, 1.28 GPF

FLOOR DRAIN SCHEDULE

REMARKS:

1 8"X8" SQUARE TOP, HEEL PROOF STRAINER.

2 9" DIAMETER STRAINER.

3 DRAINS INDICATED ON THE DRAWINGS WITH A PREFIX "F" SHALL BE PROVIDED WITH A

Z-329-9 OVAL FUNNEL, 4" HIGH WITH NICKEL BRONZE FINISH FOR NICKEL BRONZE

DRAINS AND DURA-COATED FOR CAST IRON DRAINS.

2 3 4

REMARKSTOPBODYMODEL NO.MANUFACTURERTYPE

STAINLESS STEELSTAINLESS STEELCARMENSIGNATURE

HARDWARE

FD-3

BRONZE(DURA-COATED)

NICKELCAST IRONZ415SZURNFD-1

(DURA-COATED)(DURA-COATED)

CAST IRONCAST IRONFROET 100CZURNRD-1

BRONZE(DURA-COATED)

NICKELCAST IRONZ415SZURNFD-2

5 2" DRAIN, 3-3/8" X 36" LINEAR REMOVABLE GRATE. REMOVABLE HAIR STRAINER BASKET.

4 DRAINS INDICATED ON THE DRAWINGS WITH A SUFFIX "TP" SHALL BE PROVIDED WITH A

ZURN Z1023 OR EQUAL TRAP PRIMER CONNECTION ADAPTER.

6 4" DUAL FUNCTION DRAIN, CAST IRON DOME AND INTEGRAL OVERFLOW RISER WITH STRAINER. SEE DETAIL THIS SHEET.

7 5" DUAL FUNCTION DRAIN, CAST IRON DOME AND INTEGRAL OVERFLOW RISER WITH STRAINER. SEE DETAIL THIS SHEET.

(DURA-COATED)(DURA-COATED)

CAST IRONCAST IRONFROET 100CZURNRD-2

1-1/2"

GAS-FIRED WATER HEATER SCHEMATIC PIPING DETAIL

NO SCALE

PAD

CONCRETE

4" HIGH

THERMOMETER

CODED NOTES:

T

DCW

D C

W

DHW (140)

D H

W

D C

W

DHW

D H

W

D H

W R

T

DIELECTRIC

UNION

(TYPICAL)

FINISHED

FLOOR

HEAT TRAP IF

REQUIRED. 27"

DROP MIN.

CHECK

VALVE

(TYP.)

TEST CONNECTION

FOR SETUP

1 GAS-FIRED WATER HEATER (GWH-1) -- STATE MODEL NO. SUF100 150NEA,

100 GALLON STORAGE, 150,000 BTU/HR NATURAL GAS INPUT, 96 PERCENT

EFFICIENT, 178 GALLONS RECOVERY @ 100 DEG. RISE (ASME). SET OUTLET

TEMPERATURE AT 140 DEG. F. PROVIDE CPVC SIDEWALL EXHAUST AND INTAKE

TO WATER HEATER.

2 EXPANSION TANK, AMTROL ST-C THERM-X-TROL MODEL NO.

ST-12C-DD, 6.4 TANK VOLUME, 3.2 GALLON ACCEPTANCE VOLUME,

PRECHARGED AT 55 PSIG, ASME TANK.

3 TEMPERATURE-PRESSURE RELIEF VALVE -- PIPE DISCHARGE

LINE FULL SIZE DOWN TO NEAREST FLOOR DRAIN.

4 DOMESTIC HOT WATER RECIRCULATING PUMP -- B&G LEAD-FREE ALL BRONZE

SERIES PR FOR POTABLE WATER, 3/4", 5 GPM AT 15 FT. HEAD, 1750 RPM, 1/6 H.P., 115

VOLT, 1-PHASE.

5 MIXING VALVE -- POWERS INTELLISTATION JR. DIGITAL PRE-PIPED

MIXING VALVE MODEL NO. LFIS150VL, 0.5 GPM MINIMUM FLOW, 39

GPM AT 5 PSIG PRESSURE DROP, 1-1/4" INLETS, 1-1/2" OUTLET

(NO CABINET). PROVIDE 120 VOLT HARDWIRED ELECTRICAL FEED,

TEMPERATURE GAUGES ON HOT WATER INLET AND OUTLET

CONNECTIONS AND REDUCERS/INCREASERS AS REQUIRED.

BACNET COMPATBLE. MOUNT WITH CENTERLINE OF VALVE 60"

ABOVE FINISHED FLOOR. SET OUTLET TEMPERATURE AT 120 DEG. F.

DHWR

1-1/2"

1-1/2"

1-1/2"

1-1/2"

1-1/2"

DHWR

3/4"

3/4"

3/4"

D H

W R

AQUASTAT

BALANCING

VALVE

A

3/4"

FROM BUILDING DOMESTIC

COLD WATER MAIN

FROM

BUILDING

SYSTEM

TO

BUILDING

STSTEM

G

1-1/2"

PACKAGED AIR COMPRESSOR,

INGERSOLL RAND MODEL

P1.5IU-A9 VERTICAL, 20 GALLON

ASME TANK, 5.2 CFM AT 90PSI,

115V/15 AMP.

AUTOMATIC WATER

DRAIN TRAP

1"

TO COMPRESSED

AIR SYSTEM

CONCRETE PAD

VIBRATION ISOLATORS

FLEXIBLE

CONNECTION

A

VERTICAL AIR COMPRESSOR - SCHEMATIC PIPING DETAIL

SCALE: NONE

BALL VALVE

TAKE-OFF ON TOP

MAIN

SPLIT RING

CLAMP

ROD

WALL PLATE

3/4"

DIRT LEG

BRACKET PIPING TO WALL

WHERE REQUIRED FOR RIGID

INSTALLATION.

COMPRESSED AIR OUTLET DETAIL

SCALE: NONE

AIR HOSE REEL

(TYPICAL)

P

GRADEFINISHED FLOOR

CODED NOTES: DOMESTIC WATER ENTRANCE

1. 3" DOMESTIC COLD WATER MAIN FROM METER. SEE

SITE PLANS FOR CONTINUATION.

2. 3" REDUCED PRESSURE PRINCIPLE BACKFLOW LF009-

OSY 3 VERTICAL INSTALLATION. INSTALL AND

PROVIDE SUPPORTS AS RECOMMENDED PER

MANUFACTURER. VERIFY MINIMUM AND MAXIMUM

CLEARANCES WITH LOCAL WATER COMPANY.

3. AIR GAP FITTING. PIPE DRAIN LINE FULL SIZE TO OPEN

RECEPTACLE.

4. MAIN SHUT-OFF VALVE.

5. TO BUILDING SYSTEM. SEE FLOOR PLANS FOR

CONTINUATION.

6. 3/4" DRAIN VALVE.

W

DOMESTIC WATER ENTRANCE DTEAIL

SCALE: NONE

40" A.F.F.

CONTROL

VALVE

EXTEND

SHROUD TO

CEILING

MOUNT BOTTOM

OF FIXED

SHOWER HEAD

AT 80" A.F.F.

FIXED

SHOWER

HEAD

EQUAL SPACING.

SEE ARCHITECTURAL.

EQUAL SPACING.

SEE ARCHITECTURAL.

INLINE VACUUM

BREAKER

HAND HELD

SHOWER

60" LONG

HOSE

DIVERTER

NOTE:

LENGTHS WITHIN SHROUD TO

MEET SHOWER HEAD HEIGHT

REQUIREMENTS.

HANDICAPPED SHOWER MOUNTING DETAIL

SCALE: NONE

GATE

VALVE

UNION (TYPICAL)

IN-LINE PUMP

GATE VALVE

CHECK VALVE

PRESSURE

GUAGE

GUAGE

COCK

(TYPICAL)

IN-LINE PUMP DETAIL

SCALE: NONE

42" A.F.F.

CONTROL

VALVE

EXTEND

SHROUD TO

CEILINGMOUNT BOTTOM

OF SHOWER HEAD

AT 80" A.F.F.

SHOWER

HEAD

EQUAL SPACING, SEE

ARCHITECTURAL

EQUAL SPACING, SEE

ARCHITECTURAL

NOTE:

CUSTOM PIPE LENGTHS WITHIN

SHROUD TO MEET SHOWER

HEAD HEIGHT REQUIREMENTS.

SHOWER MOUNTING DETAIL

SCALE: NONE

SLEEVE AND LEG

FIRE CAULK UNDER

TO SLEEVE.

THICK LEG, WELDED

1/2" x 1/2" x 1/8"

PIPE SLEEVE 1"

ABOVE FINISHED

FLOOR FOR WATER

STOP. SCHEDULE

EXISTING CONCRETE

FLOOR SLAB

FOR SIZE (TYPICAL)

PIPE - SEE PLANS

BETWEEN PIPE AND

WATER SEAL

1"

REQUIRED

TO FLOOR AS

ANCHOR LEG

10 STEEL PIPE

NOTES:

1. COORDINATE WITH FIRE STOPPING MANUFACTURER TO

INSURE U.L. LISTED ASSEMBLY.

2. FIRE CAULK ALL AROUND UNDER PIPE SLEEVE AND LEGS.

SLEEVE

CAULK

FIRE

SCALE: NONE

SLEEVE DETIAL FOR PIPING PASSING

THRU EXISTING CONCRETE FLOOR SLAB

RIGID INSULATION

9" M

IN

IM

UM

CLEVIS HANGER

PIPE INSULATION

INSULATION PROTECTOR

SHIELD

PROVIDE SECTION OF RIGID INSULATION

BETWEEN PROTECTOR SHIELD AND PIPE TO

PREVENT CRUSHING OF INSULATION. SECTION

OF RIGID INSULATION SHALL BE FULL SIZE

(MINIMUM) OF BEARING SURFACE OF SHIELD.

CONTRACTOR'S OPTION - USE SECTION OF

RIGID INSULATION WITH FULL CIRCUMFERENCE

OF PIPE AT EACH PROTECTOR SHIELD.

TYPICAL PIPE SUPPORT DETAIL WITH SHIELD

SCALE: NONE

CODED NOTES: AIR PIPING CONNECTION DETAIL

1 FROM SUPPLY LINE. SEE DRAWINGS FOR PIPE SIZE

AND CONTINUATION.

3 BALL VALVE.

4 PRESSURE REGULATING VALVE. SET OUTLET PRESSURE

5 PRESSURE GAUGE.

2 TO EQUIPMENT. SEE DRAWINGS FOR SIZE AND

CONTINUATION.

TYPICAL EQUIPMENT AIR PIPING CONNECTION DETAIL

NO SCALE

AS REQUIRED BY EQUIPMENT MANUFACTURER.

24 3

P

FITTINGS -- ALL FITTINGS SHALL BE FINISHED

WITH CANVAS CLOTH APPLIED OVER.

CONTRACTOR HAS THE OPTION OF FINISHING

FITTINGS WITH P.V.C. FIRE TESTED AND

RATED FITTING COVERS. SEE SPECS.

CANVAS COVERED OR P.V.C FITTING

COVER - SEE SPECS

VAPOR BARRIER TAPE WITH P.V.C

FITTING COVERS

PIPE INSULATION

SEE SPECS.

FLARE-DOOR

STAPLES

TYPICAL DETAIL OF INSULATION AT PIPE FITTING

SCALE: NONE

P

CODED NOTES: PIPING…

This is the start of the file's text. The full file is on GovTribe.

File details come from the government source that posted it. Updated .