Addenda 3.pdf

PDF 7 MB Posted

Attached to
RFB-228-23 - CJT - New Indoor Firing Range
Solicitation number
RFB-785-2300000633-8
Issued by
Lewis County, Kentucky

About this file

This document is an Addendum No. 3 issued by the Commonwealth of Kentucky Department for Facilities and Support Services Division of Engineering and Contract Administration for Invitation to Bid No. RFB-228-23 for the construction of a New Indoor Firing Range for the Department of Criminal Justice Training in Richmond, Kentucky. The addendum includes changes to the architectural specifications and drawings, such as revised requirements for the EPDM roofing installer, additions to the electrical drawings for the targeting system and new panelboard, and modifications to the wall section details. The bid opening date is not provided.

The addendum indicates that the contractor is to note receipt of all addendums on their bid form of proposal. No other pricing terms, set asides, incumbents, funding requirements, or other salient information is included in this document.

View the file

Other files

Show all 15

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

COMMONWEALTH OF KENTUCKY

DEPARTMENT FOR FACILITIES AND SUPPORT SERVICES

DIVISION OF ENGINEERING AND CONTRACT ADMINISTRATION

INVITATION TO BID NO: RFB-228-23

FOR: New Indoor Firing Range Department Of Criminal Justice Training Richmond, Kentucky

DATE: April 10, 2023

RFB-785-2300000633

ADDENDUM NO. Three (3)

BIDDER SHALL CONFORM TO THE FOLLOWING CHANGES AS SAME SHALL BECOME BINDING

UPON THE CONTRACT TO BE ISSUED IN RESPONSE TO THIS INVITATION TO BID.

Item 1: Refer to addendum below distributed by Lynn Imaging for all additions, deletions, and/or changes to specifications and/or drawings.

END OF ADDENDUM

Invitation to Bid No. RFB-228-23 For: New Indoor Firing Range Department Of Criminal Justice Training Richmond, Kentucky

Kyla Satterly, Statewide Procurement Analyst II Division of Engineering and Contract Administration

Addendum 1 Page 1 of 2

201 W. Short Street • Suite 700 • Lexington, KY 40507 • 859.231.7538 • fax 859.255.4380 • www.eopa.com

Addendum No. 3

For the new DOCJT Indoor Firing Range Richmond, Kentucky

Invitation to Bid NO: RFB-228-23 April 10th, 2023

The following addendum items officially modify the construction documents and become binding to the contract for construction (Contractor is to note receipt of all addendums on their bid form of proposal):

1. ARCHITECTURAL:

Specifications

1.1. 075323 ETHYLEN-PROPYLENE-DIENE-MONOMER (EPDM) ROOFING, section 1.7 Quality Assurance_ B. – Installers to have minimum 5 years experience installation on projects of similar size and scale within the last five years using the submitted products.

Drawings

1.2. General were indicated in drawings 3/8” steel plate to be grade AR-500 Ballistic Steel.

1.3. Drawing Sheet A452 – Revised Wall Section Detail 10.

2. ELECTRICAL:

Drawings

2.1. Refer to sheet E310:

2.1.1. Add outlets for targeting system.

2.1.2. Add new panelboard “1L3”.

2.2. Refer to sheet E410:

2.2.1. Add data outlet above target run individual 1” conduits with Cat6 data cable to control room.

2.3. Refer to sheet E601:

2.3.1. Add new 120/208-volt panelboard “1L3”.

2.4. Refer to sheet E602:

Addendum 1 Page 2 of 2

201 W. Short Street • Suite 700 • Lexington, KY 40507 • 859.231.7538 • fax 859.255.4380 • www.eopa.com

2.4.1. Replace lighting control riser.

2.5. Refer to sheet E801:

2.5.1. Added new panelboard schedule “1L3”.

2.5.2. Added new 60 amp. 3-pole breaker in panelboard “1L1” to feed new panelboard “1L3”.

2.6. Refer to sheet U100:

2.6.1. Replace coded note #7.

END OF ADDENDUM

7"

Level 1

0' - 0"

12' - 0"

GWB

13' - 6 1/2"

6"18' - 3"

/4

5' - 0"

1' - 6"

20' - 0"

PRE-FORMED METAL COPING

CAP, W/ HEMMED EDGE &

CONT. CLEAT

FLUID APPLIED MEMBRANE

AIR BARRIER

8" NOMINAL CMU WALL

IN RUNNING BOND

2" SEMI-RIGID MINERAL WOOL

INSULATION, CONTINUOUS,

TYP. (R7.5 MIN)

BALLISTIC BACKSTOP (DELEGATED DESIGN) -

REFER TO SPECIFICATIONS

V A

R

IE

S

S L O

P

IN

G P

A R

A P

E T

PROVIDE ADDITIONAL

BALLISTIC PANELS ABOVE

BALLISTIC BACKSTOP

SUSPENDED INDOOR OVERHEAD BAFFLE SYSTEM:

- BALLISTIC RUBBER PANEL

- 1/2" PLYWOOD BACK PANEL

- 2x FURRING

- 3/8" AR-500 STEEL PLATE

- SUSPENSION ASSEMBLY W/ TURNBUCKLES

LONG SPAN ROOF JOISTS @ 10' O.C.

-REFER TO STRUCTURAL

ROOF ASSEMBLY:

- EPDM MEMBRANE (60 MIL), ROOFING ASSEMBLY

- 1/2" HD POLYISO COVERBOARD

- 5" POLYISOCYANURATE RIGID ROOF

INSULATION - (2) LAYERS @ 2 1/2" EA.

METAL JOIST CEILING SUPPORT

FRAMING - REFER TO STRUCTURAL

5/8" GYPSUM BOARD

CEILING (ABOVE BAFFLES)

TARGETING SYSTEM -

REFER TO SPECIFICATIONS

A.2

A104

FIRING LANES

BACKSTOP

116U

2' - 0" (HOLD)

°2

MOUNT 3/8" AR-500 STEEL PLATE TO

BACK WALL FROM TOP OF BULLET

TRAP FRAME TO BOTTOM OF HOPPER

BAFFLE

GRANULAR RUBBER

ABOVE BULLET TRAP IN

HOPPER BAFFLE

LOWER THE (3) LEADING ROWS OF BAFFLES,

IN FRONT OF TARGET, & ANGLE @ 27 DEGREES

(DIFFERENT THAN THE TYPICAL BAFFLES)

(1) - OUT OF VIEW (2) (3)

LOWER THE (2) BACK ROWS OF BAFFLES,

BEHIND TARGET, & ANGLE @ 27 DEGREES

(DIFFERENT THAN THE TYPICAL BAFFLES)

(2)

(1)

MOUNT 3/8" AR-500 STEEL PLATE TO

CEILING TO PROTECT ANY ERRANT

FROM GOING THRU CEILING

2' - 0"

2' (MIN) GRANULAR RUBBER

/2

1 1/2" DEEP KEY NOTCHED IN THE

CONRETE SLAB TO CONTAIN

RUBBER FROM SPILLING OUT ON

MAIN FLOOR

NOTE:

ALL BAFFLES, BULLET TRAP, & WALL

STEEL MUST BE FIELD VERIFIED

PRIOR TO CONSTRUCTION

Level 1

0' - 0"

Level 2

14' - 0"

PARAPET

32' - 8"

A500

SIM

A.2

408B1

PRE-FORMED METAL COPING

CAP, W/ HEMMED EDGE &

CONT. CLEAT

FLUID APPLIED MEMBRANE

AIR BARRIER

8" NOMINAL CMU WALL

IN RUNNING BOND

2" SEMI-RIGID MINERAL WOOL

INSULATION, CONTINUOUS,

TYP. (R7.5 MIN)

ROOF ASSEMBLY:

- EPDM MEMBRANE (60 MIL), ROOFING ASSEMBLY

- 1/2" HD POLYISO COVERBOARD

- 5" POLYISOCYANURATE RIGID ROOF INSULATION -

(2) LAYERS @ 2 1/2" EA.

PRE-FINISHED, HEAVY GAUGE THRU-

WALL FLASHING W/ HEMMED EDGE DRIP

GALVANIZED STL MASONRY SUPPORT

ABOVE ROOF - REFER TO STRUCTURAL

SELF ADHERING MEMBRANE FLASHING

2-PART THRU WALL FLASHING @ ROOF

MECHANICAL DUCT WORK

- REFER TO MEP &

COORDINATE PENETRATIONS

W/ STRUCTURAL AS REQUIRED

12' - 0"

GWB

BLEACHERS (N.I.C.)

113B

SUSPENDED INDOOR OVERHEAD BAFFLE SYSTEM:

- BALLISTIC RUBBER PANEL

- 1/2" PLYWOOD BACK PANEL

- 3/8" STEEL PLATE

- STL ANGLE SUPPORT FRAMING

- SUSPENSION ASSEMBLY W/ TURNBUCKLES

A104

HOLD OFF

2' - 0"

9' - 4"

ACT

OBSERVATION

SHOOTING LINE

116V

Level 1

0' - 0"

Level 2

14' - 0"

PARAPET

32' - 8"

9' - 6"

ACT

1215 SF

CLASSROOM

3015 SF

MECH. PENTHOUSE

FLUID APPLIED AIR / VAPOR BARRIER,

APPLY UP AND OVER SILL BLOCKING

8" NOMINAL

CMU WALL IN

RUNNING BOND

2" SEMI-RIGID MINERAL WOOL

INSULATION, CONTINUOUS,

TYP. (R7.5 MIN)

BRICK VENEER (TYPE 1)

1/2" SOLID

SURFACE SILL,

EASED EDGE

PRE-FINISHED, HEAVY GAUGE SILL

COPING W/ HEMMED EDGE DRIP -

PROVIDE CONT. CLEAT (ATTACH @

VERT. MORTAR JOINTS)

BRICK VENEER (TYPE 2) TURNS

BACK @ JAMB (BEYOND)

BRICK VENEER (TYPE 2)

FLUID APPLIED MEMBRANE

AIR BARRIER

8" NOMINAL CMU

WALL IN RUNNING

BOND

THRU WALL FLASHING W/ DRIP

SELF-ADHERING

MEMBRANE FLASHING

4 1/2" EXTERIOR STOREFRONT

SYSTEM W/ INSULATED GLAZING FINISH CEILING

- REFER TO RCP'S

STRUCTURAL LINTEL ASSEMBLY

@ WALL OPENING - REFER TO

STRUCTURAL FOR TYPES AND

LOCATIONS, TYP.

ROOF DECKING

PRE-FORMED METAL COPING

CAP, W/ HEMMED EDGE &

CONT. CLEAT

FLUID APPLIED MEMBRANE

AIR BARRIER

8" NOMINAL CMU WALL

IN RUNNING BOND

2" SEMI-RIGID MINERAL WOOL

INSULATION, CONTINUOUS,

TYP. (R7.5 MIN)

PRESSURE TREATED 2X BLOCKING

@ TOP OF WALL ASSEMBLY

STRUCTURAL LINTEL @

CMU WALL OPENING

- REFER TO STRUCTURAL

BLANK OUT PANELS BEHIND

LOUVER ASSEMBLY, AS

REQUIRED TO SEAL DUCTS TO

OPENINGS, TYP.

PRE-FINISHED EXTERIOR

METAL WALL LOUVER

ASSEMBLY - REFER TO MEP

PROVIDE INTERMEDIATE

RELIEF SUPPORT @

STACKED LOUVER

ASSEMBLY

ROOF ASSEMBLY:

- EPDM MEMBRANE (60 MIL), ROOFING ASSEMBLY

- 1/2" HD POLYISO COVERBOARD

- 5" POLYISOCYANURATE RIGID ROOF

INSULATION - (2) LAYERS @ 2 1/2" EA.

3/4" F.T. PLYWOOD SHEATHING,

OVER 2" CONT. PARAPET INSULATION

PRE-FINISHED EXTERIOR

METAL WALL LOUVER

ASSEMBLY - REFER TO MEP

BLANK OUT PANELS BEHIND

LOUVER ASSEMBLY, AS

REQUIRED TO SEAL DUCTS TO

OPENINGS, TYP.

A.2

C.1

DECORATIVE GRAVEL

PERIMETER EDGE -

REFER TO CIVIL

FOUNDATION

DRAIN W/

GEOFABRIC

SLEEVE

CONCRETE FOUNDATION

- REFER TO STRUCTURAL

CONCRETE STEM WALL

W/ FORMED BRICK LEDGE2" RIGID INSULATION

@ PERIMETER

VAPOR BARRIER

BELOW SLAB

CONCRETE SLAB

ON GRADE

CONCRETE FLOOR SLAB

OVER METAL DECK

- REFER TO STRUCTURAL

MECHANICAL DUCT WORK

- REFER TO MEP

SF 1

C

COMMONWEALTH

T

H A

R

A

HC

I

N

KE

UT

OF

R

C

I

2 9 3 2

I

R

EG

No.

TS E

R D J.

L

C E

YK T

K

D

ER

OP

REVISION HISTORY OF THIS DRAWING

DECA LOG #

DRAWN BY

AS BULT DATE

COMMONWEALTH OF KENTUCKY

FINANCE AND ADMINISTRATION CABINET

DEPARTMENT FOR FACILITIES AND SUPPORT SERVICES

DIVISION OF ENGINEERING AND CONTRACT ADMINISTRATION

FRANKFORT, KENTUCKY

DESCRIPTION OF REVISIONS DATE DESCRIPTION OF REVISIONS DATE

CHECKED BY

PHASE

RTA DATE

DRAWING DATE

A & E FILE NO.

DRAWING INFORMATION

DRAWING NO.

ENGR. FILE NO.

/6

/2

:5

:4

P M

A452

WALL SECTIONS

525CAL3CJ3600

RECORD DWG. DATE

DOCJT FIRING RANGE

HANCOCK TAYLOR LN.

2023|03|14

1956.01

Checker

Author

2023|03|14

D

SCALE: 3/4" = 1'-0"A452

WALL SECTION 10

SCALE: 3/4" = 1'-0"A452

WALL SECTION 9

SCALE: 3/4" = 1'-0"A452

WALL SECTION 8 1 ADDENDUM #1 23/04/063

P

P P

P

J

116V

116U

B

130C

130E

130D

130B130A

124A 124C124B

122C

122B 122A

111 112

1L1

1L2

1H1

A T

S

L S

1T1

SWBD

WP

WP

WP

WP

WP

AHU-ER

WP

B-1

HWP-2

HWP-1

WH-1

FACP

F A

A P

CH-1

CH-2

26 24 31 29

1L2 - 23,25

25 23

23 25

20 22

1L2 - 20,22

1L2 - 19,21

16 1L2 - 16,18

16 18

34 32

33 35

35 33

1L2 - 33,35

41 39 41

4139413941

1L2 - 36,38

18 20

18 20 18

16 14

2ESL1 - 18,20

1L2 - 43,45

131715

17151715

1L2 - 13,15,17

1L2 - 12,14

SWBD

SWBD - 2

SWBD - 1

1L1 - 7

7 7 7

9 9 9

11 11 11

8 8 8

10 10 10

1L2 - 27,29,311L2 - 24,26,28

1L2 - 37,39,41

1L2 - 2,4,6

1L2 - 7,9,11

1L2 - 8,10

1L2 - 3

WP

1L2 - 40,42

1L1 - 1,10

SWBD - 3

CH-3

2ESL1 - 3,14,16

L

,3

,3

1L1 - 5

4848 4848

SSOU-1

E

S L

E

S L

E

S L

E

S L

E

S L

E

S L

4 4

A D

B E FC

H

I

J

K

L

M N

O P Q

RB.1

3.9

1L2 - 1

B-2

HP-OU

HP-IU

1L1 - 8

E320

1L1 - 12,14

1L1 - 21,23

SWBD - 5

1L1 - 40,42,44

WP

1L2 - 5

2ESL1 - 4

2ESL1 - 8

2ESL1 - 8

2ESL1 - 7

2ESL1 - 13,15,17

2ESL1 - 8

2ESL1 - 2

2ESL1 - 2

1L1 - 34,36,38

1L1 - 35,37,39

1L1 - 25,27

1L3

1L3 - 1,3

4 1L3 - 2,4

1L3 - 5,7

1L3 - 6,8

NOTE:

IT IS NOT INTENDED THAT THE PLANS SHOW ALL OFFSETS IN PIPES, CONDUITS, AND DUCTS REQUIRED FOR INSTALLATION OF THE WORK. DETAILS AND SECTIONS ARE INCLUDED FOR SOME AREAS TO SHOW INTENDED RELATIONSHIP OF THE WORK OF VARIOUS TRADES. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR AND SUB-CONTRACTORS TO COORDINATE INSTALLATION OF THE

WORK AND TO PROVIDE THE NECESSARY OFFSETS, TRANSFORMATIONS, AND FITTINGS REQUIRED. NO ADDITIONAL COMPENSATION WILL BE ALLOWED FOR CORRECTION CONFLICTS BETWEEN THE WORK OF VARIOUS TRADES. DETAILS AND SECTIONS ARE SHOWN FOR THE CONTRACTORS CONVENIENCE AND SHALL NOT BE CONSIDERED COMPLETE IN EVERY DETAIL.

C E N ENFO

SE

ENOIS

AL

GN

I

E

AT

P R

S

T K

E

CARTER

GREGORY G.

14715

L I S

D RE

Y

EFO K

C

TN

U

REVISION HISTORY OF THIS DRAWING

DECA LOG #

DRAWN BY

AS BULT DATE

COMMONWEALTH OF KENTUCKY

FINANCE AND ADMINISTRATION CABINET

DEPARTMENT FOR FACILITIES AND SUPPORT SERVICES

DIVISION OF ENGINEERING AND CONTRACT ADMINISTRATION

FRANKFORT, KENTUCKY

DESCRIPTION OF REVISIONS DATE DESCRIPTION OF REVISIONS DATE

CHECKED BY

PHASE

RTA DATE

DRAWING DATE

A & E FILE NO.

DRAWING INFORMATION

DRAWING NO.

ENGR. FILE NO.

/6

/2

:5

:0

A M

E310

POWER PLAN - FIRST FLOOR

525CAL3CJ3600

RECORD DWG. DATE

DOCJT FIRING RANGE

HANCOCK TAYLOR LN.

2023|03|14

1956.01

GGC

WTG / NPD

2023|03|14

D

SCALE: 1/8" = 1'-0"E310

1 POWER PLAN - FIRST FLOOR

ROOM SCHEDULE

ROOM NUMBER ROOM NAME

100 VEST.

100B CORRIDOR

110 CLASSROOM

111 WOMENS

112 MENS

113 OBSERVATION

114 STAIR A

115 RANGE CONTROL

116 FIRING LANES

116U BACKSTOP

116V SHOOTING LINE

117 MECH

119 MDF

120 COPY

121 OFFICE

122A STAFF MENS

122B MENS SHOWER

122C MENS LOCKER

123 JANITOR

124A STAFF WOMENS

124B WOMENS SHOWER

124C WOMENS LOCKER

125 OFFICE

126 OFFICE

127 OFFICE

128 STAFF BREAK

130A ARMORY

130B WEAPONS CLEANING

130C STORAGE/GARAGE

130D WEAPONS STORAGE

130E AMMO STORAGE

140 MECH

201 MECH. PENTHOUSE

ROOM SCHEDULE

ROOM NUMBER ROOM NAME

100 VEST.

100B CORRIDOR

110 CLASSROOM

111 WOMENS

112 MENS

113 OBSERVATION

114 STAIR A

115 RANGE CONTROL

116 FIRING LANES

116U BACKSTOP

116V SHOOTING LINE

117 MECH

119 MDF

120 COPY

121 OFFICE

122A STAFF MENS

122B MENS SHOWER

122C MENS LOCKER

123 JANITOR

124A STAFF WOMENS

124B WOMENS SHOWER

124C WOMENS LOCKER

125 OFFICE

126 OFFICE

127 OFFICE

128 STAFF BREAK

130A ARMORY

130B WEAPONS CLEANING

130C STORAGE/GARAGE

130D WEAPONS STORAGE

130E AMMO STORAGE

140 MECH

201 MECH. PENTHOUSE

CODED NOTES:

1 PROVIDE ELECTRICAL CONNECTION TO AIR HANDLING UNIT (AHU-ER) IN ACCORDANCE WITH MANUFACTURES RECOMMENDATIONS. -- 480V., 3-PHASE

2 PROVIDE ELECTRICAL CONNECTION TO CHILLERS (CH-1 AND CH-2) SUPPLY AIR SECTION IN ACCORDANCE WITH MANUFACTURES RECOMMENDATIONS. -- 480V., 3-PHASE

3 PROVIDE ELECTRICAL CONNECTION TO CHILLER (CH-3) SUPPLY AIR SECTION IN ACCORDANCE WITH MANUFACTURES RECOMMENDATIONS. -- 480V., 3-PHASE

4 PROVIDE ELECTRICAL CONNECTION TO HEAT TRACE CABLE IN ACCORDANCE WITH MANUFACTURES RECOMMENDATIONS.

5 PROVIDE ELECTRICAL CONNECTION TO AIR HANDLING UNIT LIGHTS ACCORDANCE WITH MANUFACTURES RECOMMENDATIONS.

6 PROVIDE ELECTRICAL CONNECTION TO AIR HANDLING UNIT RECEPTACLES ACCORDANCE WITH MANUFACTURES RECOMMENDATIONS.

7 UP TO EXHAUST FAN (EF-2) LOCATED ON ROOF.

8 PROVIDE ELECTRICAL CONNECTION TO UNIT HEATER (UH-1) IN ACCORDANCE WITH MANUFACTURES RECOMMENDATIONS. -- 120V., SINGLE-PHASE.

9 PROVIDE ELECTRICAL CONNECTION TO TRAP PRIMER IN ACCORDANCE WITH THE MAUFACTURES RECOMMENDATIONS. --120V., SINGLE-PHASE.

10 VARIABLE FREQUENCY DRIVE TO FEED AIR HANDLING UNIT (AHU-ER) IN ACCORDANCE WITH MANUFACTURES RECOMMENDATIONS. -- 480V., 3-PHASE.

11 PROVIDE ELECTRICAL CONNECTION TO POWER WINDOW SHADES IN ACCORDANCE WITH MANUFACTUERS RECEOMMENDATIONS.

12 PROVIDE ROUGH IN FOR WINDOW SHADE CONTROLLER IN ACCORDANCE WITH MANUFACTUERS RECOMMENDATIONS.

13 PROVIDE ELECTRICAL CONNECTION TO THE DOOR POWER SUPPLIES IN ACCORDANCE WITH MANUFACTURES RECOMMENDATIONS.

14 PROVIDE ELECTRICAL CONNECTION TO OVERHEAD COILING DOOR MOTOR IN ACCORDANCE WITH MANUFACTURES RECOMMENDATIONS. --208V., 3-PHASE.

15 PROVIDE ELECTRICAL CONNECTION TO DOCK LEVELER IN ACCORDANCE WITH MANUFACTURES RECOMMENDATIONS.--208V, 1-PHASE.

16 MOUNT OUTLET ON CEILING ADJACENT TO DATA OUTLET (TYPICAL).

1 Addendum #3 4/5/2023

CR

CR

CR

CR

CR

CR

CR

CR CR

CR

CR

CR

CR

CR

F

F

F

F

F F

F

F

F

F

F

F

F

F

SD

F

F

F F

F

F

F F

F

F

F

F

F

F

F

F

F

F

F F

F

I

FSTS

CR CRCR

SD

116V 116U

100B

130C

130E

130D

130B

130A

124A

124C

124B

122C

122B 122A

120 111 112

2D

2D

2D

2D

2D 2D

2D 2D

2D

2D

2D

2D

2D 2D

2D 2D

E410

FAAP

2D 2D

2D

2D

2D

2D

2D

2D

2D 2D

2D 2D

1L1

1T1

1H1

SWBD

ATS - LS

2D 2D

2D

3D 3D 3D

3D3D3D

3D 3D 3D

3D 3D 3D

3D3D3D

2D 2D

2D 2D 2D

7 7

48 48 48

2D

2D

2D

2D

2D

2D

2D

2D

4D

A D

B E FC

H

I

J

K

L

M N O P Q RB.1

3.9 w

1D

1D

1D

1D

1D

1D

1D

1D

1D

1D

1D

1D

1D

1D

1D

1D

1D

1D

1D

1D

1D

1D

1D

1D

1D

1D

1D

1D

1D

1D

F A

C P

1V

F

3.9

NOTE:

IT IS NOT INTENDED THAT THE PLANS SHOW ALL OFFSETS IN PIPES, CONDUITS, AND DUCTS REQUIRED FOR INSTALLATION OF THE WORK. DETAILS AND SECTIONS ARE INCLUDED FOR SOME AREAS TO SHOW INTENDED RELATIONSHIP OF THE WORK OF VARIOUS TRADES. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR AND SUB-CONTRACTORS TO COORDINATE INSTALLATION OF THE

WORK AND TO PROVIDE THE NECESSARY OFFSETS, TRANSFORMATIONS, AND FITTINGS REQUIRED. NO ADDITIONAL COMPENSATION WILL BE ALLOWED FOR CORRECTION CONFLICTS BETWEEN THE WORK OF VARIOUS TRADES. DETAILS AND SECTIONS ARE SHOWN FOR THE CONTRACTORS CONVENIENCE AND SHALL NOT BE CONSIDERED COMPLETE IN EVERY DETAIL.

C E N ENFO

SE

ENOIS

AL

GN

I

E

AT

P R

S

T K

E

CARTER

GREGORY G.

14715

L I S

D RE

Y

EFO K

C

TN

U

REVISION HISTORY OF THIS DRAWING

DECA LOG #

DRAWN BY

AS BULT DATE

COMMONWEALTH OF KENTUCKY

FINANCE AND ADMINISTRATION CABINET

DEPARTMENT FOR FACILITIES AND SUPPORT SERVICES

DIVISION OF ENGINEERING AND CONTRACT ADMINISTRATION

FRANKFORT, KENTUCKY

DESCRIPTION OF REVISIONS DATE DESCRIPTION OF REVISIONS DATE

CHECKED BY

PHASE

RTA DATE

DRAWING DATE

A & E FILE NO.

DRAWING INFORMATION

DRAWING NO.

ENGR. FILE NO.

/6

/2

:5

:1

A M

E410

TECHNOLOGY PLAN - FIRST FLOOR

525CAL3CJ3600

RECORD DWG. DATE

DOCJT FIRING RANGE

HANCOCK TAYLOR LN.

2023|03|14

1956.01

GGC

WTG / NPD

2023|03|14

D

SCALE: 1/8" = 1'-0"E410

1 TECHNOLOGY PLAN - FIRST FLOOR

ROOM SCHEDULE

ROOM NUMBER ROOM NAME

100 VEST.

100B CORRIDOR

110 CLASSROOM

111 WOMENS

112 MENS

113 OBSERVATION

114 STAIR A

115 RANGE CONTROL

116 FIRING LANES

116U BACKSTOP

116V SHOOTING LINE

117 MECH

119 MDF

120 COPY

121 OFFICE

122A STAFF MENS

122B MENS SHOWER

122C MENS LOCKER

123 JANITOR

124A STAFF WOMENS

124B WOMENS SHOWER

124C WOMENS LOCKER

125 OFFICE

126 OFFICE

127 OFFICE

128 STAFF BREAK

130A ARMORY

130B WEAPONS CLEANING

130C STORAGE/GARAGE

130D WEAPONS STORAGE

130E AMMO STORAGE

140 MECH

201 MECH. PENTHOUSE

SCALE: 1/4" = 1'-0"E410

2 ENLARGED LOW-VOLTAGE PLAN

CODED NOTES:

1 PROVIDE AND INSTALL FIRE RETARDANT 3/4” THICK PLYWOOD ALONG WALLS AS INDICATED

FOR MOUNTING OF LOW-VOLTAGE SYSTEMS EQUIPMENT. PLYWOOD TO BE MOUNTED

STARTING AT 4” AFF AND CONTINUOUS UP TO 8’-4” OR TO THE CEILING DECK WHICHEVER

COMES FIRST.

2 PROVIDE AND INSTALL A TELECOMMUNICATIONS GROUNDING BUSS BAR AT 24” AFF. SEE

DETAIL FOR ADDITIONAL INFORMATION. CONNECT THE GROUND BAR TO THE MAIN ELECTRICAL

SERVICE GROUND SYSTEM WITH A #6 AWG WIRE.

3 ROUTE ONE 1” CONDUIT FROM FIRE ALARM PANEL TO CABLE TRAY. RUN ONE FOUR STRAND

MULIT MODE 62.5 FIBER CABLE FROM FIRE ALARM PANEL TO FIBER TERMINATION POINT IN THE

MAIN TELECOMMUNICATIONS ROOM AND TERMINATE PER SPECIFICATIONS.

4 12” X 6” CABLE TRAY TO BE 4” – 6” ABOVE ACCESSIBLE CEILINGS.

5 12” X 6” CABLE TRAY TO BE 8’-0” AFF.

6 12” X 6” LADDER RUNAWAY ON TOP OF RACKS.

7 INSTALL DATA OUTLET 2" ABOVE BACKSPLASH/COUNTER. REFER TO ARCHITECTURAL

DRAWINGS AND APPROVED CASEWORK SHOP DRAWINGS.

8 DATA OUTLET MOUNTED ABOVE CEILING FOR CEILING MOUNTED PROJECTOR. REFER TO

ARCHITECTURAL REFLECTED CEILING PLAN FOR CEILING HEIGHT.

9 PROVIDE CONNECTION TO WATER FLOW ALARM AS REQUIRED.

10 MOUNT DATA OUTLET ON CEILING RUN CONDUIT TO CONTROL ROOM REFER TO TARGETING

SYSTEM SHOP DRAWINGS FOR LOCATION TYIPICAL.

C E N ENFO

SE

ENOIS

AL

GN

I

E

AT

P R

S

T K

E

CARTER

GREGORY G.

14715

L I S

D RE

Y

EFO K

C

TN

U

REVISION HISTORY OF THIS DRAWING

DECA LOG #

DRAWN BY

AS BULT DATE

COMMONWEALTH OF KENTUCKY

FINANCE AND ADMINISTRATION CABINET

DEPARTMENT FOR FACILITIES AND SUPPORT SERVICES

DIVISION OF ENGINEERING AND CONTRACT ADMINISTRATION

FRANKFORT, KENTUCKY

DESCRIPTION OF REVISIONS DATE DESCRIPTION OF REVISIONS DATE

CHECKED BY

PHASE

RTA DATE

DRAWING DATE

A & E FILE NO.

DRAWING INFORMATION

DRAWING NO.

ENGR. FILE NO.

/6

/2

:5

:1

A M

E601

ELECTRICAL DISTRIBUTION SYSTEM RISER DIAGRAM

525CAL3CJ3600

RECORD DWG. DATE

DOCJT FIRING RANGE

HANCOCK TAYLOR LN.

2023|03|14

1956.01

GGC

WTG / NPD

2023|03|14

D

N

DESIGNATES THAT THE NEUTRAL CONDUCTOR IS NOT REQUIRED.

4#6 & 1#10 GND. IN 1" CONDUIT.

4#2 & 1#8 GND. IN 1-1/4" CONDUIT.

4#1 & 1#6 GND. IN 1-1/2" CONDUIT.

4#1 & 1#6 GND. IN 1-1/2" CONDUIT.

4#2/0 & 1#6 GND. IN 2" CONDUIT.

4#3/0 & 1#6 GND. IN 2" CONDUIT.

4#4/0 & 1#4 GND. IN 2-1/2" CONDUIT.

4-250MCM & 1#4 GND. IN 3" CONDUIT.

4-350MCM & 1#3 GND. IN 3" CONDUIT.

4-500MCM & 1#2 GND. IN 3-1/2" CONDUIT.

4#3 & 1#8 GND. IN 1-1/4" CONDUIT.

4#12 & 1#12 GND. IN 3/4" CONDUIT.

4#10 & 1#10 GND. IN 3/4" CONDUIT.

4#8 & 1#10 GND. IN 1" CONDUIT.

4#4 & 1#8 GND. IN 1-1/4"" CONDUIT.

4#1/0 & 1#6 GND. IN 2" CONDUIT.

4#4 & 1#8 GND. IN 1-1/4" CONDUIT.

4-250MCM & 1#2 GND. IN EACH OF TWO (2) 2-1/2" CONDUITS.

4-350MCM & 1#1 GND. IN EACH OF TWO (2) 3" CONDUITS.

4-500MCM & 1#1/0 GND. IN EACH OF TWO (2) 3 1/2" CONDUITS.

4-500MCM & 1#4/0 GND. IN EACH OF FIVE (5) 3-1/2" CONDUITS.

4-500MCM & 1-250MCM GND. IN EACH OF SIX (6) 3-1/2" CONDUITS.

4-350MCM & 1#2/0 GND. IN EACH OF THREE (3) 3" CONDUITS.

4-400MCM & 1#3/0 GND. IN EACH OF THREE (3) 3-1/2" CONDUITS.

4-350MCM & 1#3/0 GND. IN EACH OF FOUR (4) 3" CONDUITS.

4-500MCM & 1-350MCM GND. IN EACH OF SEVEN (7) 3-1/2" CONDUITS.

1800 4-500MCM & 1-250MCM GND. IN EACH OF FIVE (5) 3-1/2" CONDUITS.

1400 4-500MCM & 1#4/0 GND. IN EACH OF FOUR (4) 3-1/2" CONDUITS.

4-500MCM & 1#1/0 GND. IN EACH OF TWO (2) 3-1/2" CONDUITS.

4-500MCM & 1-500MCM GND. IN EACH OF ELEVEN (11) 3-1/2" CONDUITS.

45 4#6 & 1#10 GND. IN 1" CONDUIT.

4#1 & 1#6 GND. IN 1-1/2" CONDUIT.110

4-500MCM & 1#3 GND. IN 3-1/2" CONDUIT.

FEEDER AND BRANCH CIRCUIT SCHEDULE

NO. CONDUCTORS THWN/THHN COPPER

ADJUST QUANTITY OF WIRES FOR BRANCH CIRCUITS IN ACCORDANCE WITH

CIRCUIT BREAKER SIZE SHOWN IN PANEL SCHEDULES.

INCREASE WIRE SIZE TO THE NEXT WIRE SIZE FOR BRANCH CIRCUITS OVER 150

FEET.

INCREASE WIRE SIZE TO NEXT WIRE SIZE FOR EVERY ADDITIONAL 150 FEET.

TRANSFORMER GROUNDING DETAIL

SCALE: NONE

DRY TYPE

TRANSFORMER

SYSTEM

BONDING JUMPER

NEAREST

GROUNDING

ELECTRODE

GROUNDING

ELECTRODE

CONDUCTOR

NEUTRAL

208Y/120V

PANEL OR

DISCONNECT

SUPPLY SIDE

BONDING JUMPERSISOLATED NETURAL

TERMINAL

NOTE:

THE SUPPLY SIDE BONDING JUMPERS AND THE GROUNDING ELECTRODE CONDUCTOR SHALL

BE SIZED PER NEC TABLE 250.66.

N G

A B C

EQUIPMENT GROUNDING

CONDUCTOR480V

ELECTRICAL DISTRIBUTION SYSTEM RISER DIAGRAM

TRANSFER

SWITCH

ATS-LS

200 AMPS

NEW EXTERIOR PAD

MOUNTED TRANSFORMER

PRI. - 12470 DELTA

SEC. - 277/480V/3P/4W

EMERGENCY

GENERATOR

200 KW

FUEL TYPE: NATIONAL GAS

GROUND PER NEC.

4" CONCRETE

HOUSEKEEPING PAD

METER

INTERIOR EXTERIOR

PANELBOARD

1L2

120/208V

3PH/4W

PANELBOARD

1H1

277/480V

3PH/4WEXISTING PRIMARY SWITCH

GROUND PER NEC.

TRANSFORMER

1T1

75 KVA

PRI. - 277/480V/3PH

SEC. - 120/208V/3PH

SWBD

GROUND PER NEC THIS

GROUND IS SIZED PER

TABLE 250.66

4" CONCRETE

HOUSEKEEPING PAD

PANELBOARD

2ESL1

120/208V

3PH/4W

PANELBOARD

2ESH1

277/480V

3PH/4W

TRANSFORMER

2T1

30 KVA

PRI. - 277/480V/3PH

SEC. - 120/208V/3PH

GROUND PER NEC.

PANELBOARD

1L1

120/208V

3PH/4W

250 250250

125 AMP.

ENCLOSED

BREAKER

15 KV

WIREWAY

(2) 5"C.

1 Addendum #3 4/5/2023

M

PANELBOARD

1L3

120/208V

3PH/4W

BLACK

RED

W H

IT

E

B L K

/O R

G

N H

FCS PS10

BLK/ORG-

120V/ 277V

BLUE

EN

W H

IT

E

/R E

D

GRN

EN EH

N

H BLK- 120/277V

VI

GY

WHITE

Y E

L /R

| Y

R E

D

0-10V DIM

EMERGENCY

YEL-

120V/

R|Y=RED|YEL-

277V

BLUE

EN

W H

IT

E

/R E

D

GRN

EN EH

N

H BLK- 120/277V

VI

GY

WHITE

Y E

L /R

| Y

R E

D

0-10V DIM

EMERGENCY

YEL-

120V/

R|Y=RED|YEL-

277V

BLUE

EN

W H

IT

E

/R E

D

GRN

EN EH

N

H BLK- 120/277V

VI

GY

WHITE

Y E

L /R

| Y

R E

D

0-10V DIM

EMERGENCY

YEL-

120V/

R|Y=RED|YEL-

277V

BLUE

EN

W H

IT

E

/R E

D

GRN

EN EH

N

H BLK- 120/277V

VI

GY

WHITE

Y E

L /R

| Y

R E

D

0-10V DIM

EMERGENCY

YEL-

120V/

R|Y=RED|YEL-

277V

BLUE

EN

W H

IT

E

/R E

D

GRN

EN EH

N

H BLK- 120/277V

VI

GY

WHITE

Y E

L /R

| Y

R E

D

0-10V DIM

EMERGENCY

YEL-

120V/

R|Y=RED|YEL-

277V

VI

GY

BLUE

N

W H

IT

E

B L K

/O R

G

N H

GRN

0-10V DIM

BLK- 120V/

ORG 277V

R E

D

VI

GY

BLUE

N

W H

IT

E

B L K

/O R

G

N H

GRN

0-10V DIM

BLK- 120V/

ORG 277V

R E

D

VI

GY

BLUE

N

W H

IT

E

B L K

/O R

G

N H

GRN

0-10V DIM

BLK- 120V/

ORG 277V

R E

D

VI

GY

BLUE

N

W H

IT

E

B L K

/O R

G

N H

GRN

0-10V DIM

BLK- 120V/

ORG 277V

R E

D

VI

GY

BLUE

N

W H

IT

E

B L K

/O R

G

N H

GRN

0-10V DIM

BLK- 120V/

ORG 277V

R E

D

VI

GY

BLUE

N

W H

IT

E

B L K

/O R

G

N H

GRN

0-10V DIM

BLK- 120V/

ORG 277V

R E

D

POWER SUPPLY

H

N

SEE PANEL SCHEDULE FOR

INTERNAL RELAY/DIMMING

DETAILS

SEE WIRING DIAGRAM FOR

INTERNAL AND EXTERNAL

WIRING DETAILS

NLIGHT

BLUE

EN

W H

IT

E

/R E

D

GRN

EN EH

N

H BLK- 120/277V

WHITE

Y E

L /R

| Y

R E

D

EMERGENCY

YEL-

120V/

R|Y=RED|YEL-

277V

SPLITTER

CAT5e nLight

CAT5e nLightCAT5e nLightCAT5e nLight

CAT5e nLight

CAT5e nLight CAT5e nLightCAT5e nLight

CAT5e nLight

CAT5e nLight

CAT5e nLight CAT5e nLight

CAT5e nLight

CAT5e nLight CAT5e nLightCAT5e nLight CAT5e nLight CAT5e nLightCAT5e nLight CAT5e nLightCAT5e nLight

CAT5e nLight nLight - Room 1 Design 1

MASTER CTRL RM115

FCS 7TSN X XX

[TS1]

NPODMA DX XX

[SW2]

FIRING RANGE

NPODMA DX XX

[SW2]

FIRING RANGE

NPODMA DX XX

[SW2]

NPODMA DX XX

[SW2]

VEST 100

NPODMA DX XX

[SW2]

OBSERVATION

NPODMA DX XX

[SW2]

NPODMA DX XX

[SW2]

ZONE A EM

LOAD

NPP16 D ER EFP

[DE1]

VESTIBULE

LOAD

NPP16 D ER EFP

[DE1]

ZONE C EM

LOAD

NPP16 D ER EFP

[DE1]

VEST 100

LOAD

NPP16 D ER EFP

[DE1]

OBSERVATION

LOAD

NPP16 D ER EFP

[DE1]

ZONE B

LOAD

NPP16 D EFP

[DP1]

ZONE D

LOAD

NPP16 D EFP

[DP1]

LOAD

NPP16 D EFP

[DP1]

ZONE F

LOAD

NPP16 D EFP

[DP1]

ZONE G

LOAD

NPP16 D EFP

[DP1]

OBSERVATION

LOAD

NPP16 D EFP

[DP1]

SITE

ARP INTENC08 NLT 4FCR MVOLT SC SM

[PL1]

EXT BLDG MOUNT

SITE

NPP16 ER EFP

[PE1]

VESTIBULE

NPODMA XX

[SW1] NCM PDT 9 RJB

[OS1]

C E N ENFO

SE

ENOIS

AL

GN

I

E

AT

P R

S

T K

E

CARTER

GREGORY G.

14715

L I S

D RE

Y

EFO K

C

TN

U

REVISION HISTORY OF THIS DRAWING

DECA LOG #

DRAWN BY

AS BULT DATE

COMMONWEALTH OF KENTUCKY

FINANCE AND ADMINISTRATION CABINET

DEPARTMENT FOR FACILITIES AND SUPPORT SERVICES

DIVISION OF ENGINEERING AND CONTRACT ADMINISTRATION

FRANKFORT, KENTUCKY

DESCRIPTION OF REVISIONS DATE DESCRIPTION OF REVISIONS DATE

CHECKED BY

PHASE

RTA DATE

DRAWING DATE

A & E FILE NO.

DRAWING INFORMATION

DRAWING NO.

ENGR. FILE NO.

/6

/2

:5

:1

A M

E602

LIGHTING RISERS

525CAL3CJ3600

RECORD DWG. DATE

DOCJT FIRING RANGE

HANCOCK TAYLOR LN.

2023|03|14

1956.01

GGC

WTG

2023|03|14

D

C E N ENFO

SE

ENOIS

AL

GN

I

E

AT

P R

S

T K

E

CARTER

GREGORY G.

14715

L I S

D RE

Y

EFO K

C

TN

U

REVISION HISTORY OF THIS DRAWING

DECA LOG #

DRAWN BY

AS BULT DATE

COMMONWEALTH OF KENTUCKY

FINANCE AND ADMINISTRATION CABINET

DEPARTMENT FOR FACILITIES AND SUPPORT SERVICES

DIVISION OF ENGINEERING AND CONTRACT ADMINISTRATION

FRANKFORT, KENTUCKY

DESCRIPTION OF REVISIONS DATE DESCRIPTION OF REVISIONS DATE

CHECKED BY

PHASE

RTA DATE

DRAWING DATE

A & E FILE NO.

DRAWING INFORMATION

DRAWING NO.

ENGR. FILE NO.

/6

/2

:5

:1

A M

E801

ELECTRICAL PANEL SCHEDULES

525CAL3CJ3600

RECORD DWG. DATE

DOCJT FIRING RANGE

HANCOCK TAYLOR LN.

2023|03|14

1956.01

GGC

WTG / NPD

2023|03|14

D

Notes:

2776 A

2307560 VA

23 MECH. PENTHOUSE 201 - HOT WATER CONDENSATE PUMP (HWCP-2) 3 20 A 1330 VA

22 MECH. PENTHOUSE 201 - HOT WATER CONDENSATE PUMP (HWCP-1) 3 20 A 1330 VA

21 MECH. PENTHOUSE 201 - CHILLED WATER CONDENSATE PUMP (CWCP-2) 3 20 A 3991 VA

20 MECH. PENTHOUSE 201 - CHILLED WATER CONDENSATE PUMP (CWCP-1) 3 20 A 3991 VA

19 SEWER EJECTOR PUMP - MECH 117 3 20 A 9141 VA

18 MECH 117 - BOILER (B-2) 3 20 A 5817 VA

17 MECH 117 - BOILER (B-1) 3 20 A 5817 VA

16 MECH PENTHOUSE 201 - AIR HANDLING UNIT RETURN AIR (AHU-2) 3 20 A 7479 VA

15 MECH PENTHOUSE 201 - AIR HANDLING UNIT SUPPLY AIR (AHU-2) 3 40 A 13296 VA

14 MECH 117 - HOT WATER PUMP (HWP-2) 3 40 A 17459 VA

13 MECH 117 - HOT WATER PUMP (HWP-1) 3 40 A 17459 VA

12 MECH PENTHOUSE 201 - ENERGY RECOVERY PUMP (ERP-2) 3 60 A 22447 VA

11 MECH PENTHOUSE 201 - ENERGY RECOVERY PUMP (ERP-1) 3 60 A 22447 VA

10 MECH PENTHOUSE 201 - CHILLED WATER PUMP (CWP-2) 3 80 A 33255 VA

9 MECH PENTHOUSE 201 - CHILLED WATER PUMP (CWP-1) 3 80 A 33255 VA

8 MECH 117 - PANEL 2ESH1 via AUTOMATIC TRANSFER SWITCH -- ATS-LS 3 200 A 34129 VA

7 MECH 117 - PANEL 1H1 3 125 A 18999 VA

6 MECH 117 - TRANSFORMER 1T1 3 125 A 85361 VA

5 MECH 140 - ENERGY RECOVERY UNIT (AHU-ER) 3 250 A 151242 VA

4 PENTHOUSE 201 - AIR HANDLING UNIT (AHU-1) 3 250 A 151242 VA

3 EXTERIOR - CHILLER (CH-3) 3 175 A 128805 VA

2 EXTERIOR - CHILLER (CH-2) 3 1200 A 771168 VA

1 EXTERIOR - CHILLER (CH-1) 3 1200 A 771168 VA

CKT Circuit Description # of Poles Trip Rating Load Remarks

Notes:

Enclosure: NEMA 1

Mounting: CONCRETE PAD Wires: 4 MCB/MLO Rating: 2000

Supply From: Phases: 3 Mains Type: MCB

Location: MECH 117 Volts: 480/277 Wye A.I.C. Rating: 65,000

Switchboard: SWBD

Total Amps: 20 A 24 A 26 A

Total Load: 5590 VA 6422 VA 6988 VA

29 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 30

27 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 28

25 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 26

23 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 24

21 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 22

19 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 20

17 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 18

15 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 16

13 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 14

11 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 12

9 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 10

7 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 8

5 LTG - FIRING LANES 116 20 A 1 2795 VA 4193 VA 1 20 A LTG - FIRING LANES 116 6

3 LTG - OFFICE 121 20 A 1 2229 VA 4193 VA 1 20 A LTG - FIRING LANES 116 4

1 LTG - BACKSTOP 116U 20 A 1 1398 VA 4193 VA 1 20 A LTG - FIRING LANES 116 2

CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT

Notes:

Enclosure: TYPE 1

Mounting: SURFACE Wires: 4 MCB/MLO Rating: 125

Supply From: SWBD Phases: 3 Mains Type: MLO

Location: MECH 117 Volts: 480/277 Wye A.I.C. Rating: 42,000

Branch Panel: 1H1

Total Amps: 121 A 150 A 138 A

Total Load: 14464 VA 17723 VA 16255 VA

53 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 54

51 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 52

49 SPARE 20 A 1 0 VA 1260 VA 50

47 SPARE 20 A 1 0 VA 1440 VA 48

45 SPARE 20 A 1 0 VA 2700 VA

3 60 A PANELBOARD "1L3"

43 SPARE 20 A 1 0 VA 3333 VA 44

41 SPARE 20 A 1 0 VA 3333 VA 42

39 937 VA 3333 VA

3 40 A HVAC - MECH 140 (HP-1U HEAT STRIPS)

37 937 VA 937 VA 38

COILING DOOR - STORAGE/GARAGE 130C 15 A 3

937 VA 937 VA 36

33 TRAP PRMER - MECH 117 20 A 1 500 VA 937 VA

3 15 A COILING DOOR - SHOOTING LINE 116V

31 RECS - MECH 117 (AIR COMPRESSOR) 20 A 1 1200 VA 150 VA 1 20 A UNIT HEATER - STAIR A 114 32

29 RECS - MECH 117 & EXTERIOR 20 A 1 1080 VA 150 VA 1 20 A UNIT HEATER MECH. PENTHOUSE 201 30

27 1040 VA 1200 VA 28

DOCK LEVELER - STORAGE/GARAGE 130C 20 A 2

1040 VA 1200 VA

2 15 A HVAC OUTDOOR UNIT (SSOU-1)

23 3016 VA 1500 VA 1 20 A MECH 117 WATER HEATER (WH-1) 24

HVAC - EXTERIOR (HP-OU) 35 A 2

3016 VA 1200 VA 1 20 A RECIRC PUMP - MECH 117 22

19 726 VA 728 VA 20

MECH 117 BOILER RECIRC PUMP (B-2) 20 A 2

726 VA 728 VA

2 20 A MECH 117 BOILER RECIRC PUMP (B-1)

15 UNIT HEATER MECH. PENTHOUSE 201 20 A 1 150 VA 0 VA 1 20 A SPARE 16

13 RECS - MECH. PENTHOUSE 201 20 A 1 1260 VA 520 VA 14

11 EXHAUST FAN (EF-1) 20 A 1 1176 VA 520 VA

2 15 A HVAC - MECH 140 (HP-IU)

9 TRAP PRIMERS - MECH. PENTHOUSE 201 20 A 1 1000 VA 1080 VA 1 20 A RECS - MECH 140 10

7 EXHAUST FAN (EF-2) 20 A 1 500 VA 1000 VA 1 20 A DOOR POWER SUPPLIES - VEST 100 8

5 AHU-ER (LIGHTS AND RECEPTACLES) 20 A 1 280 VA 700 VA 1 20 A AHU-1 (LIGHTS AND RECEPTACLES) 6

3 AHU-2 (LIGHTS AND RECEPTACLES) 20 A 1 270 VA 608 VA 1 20 A LTG - FIRING LANES 116 (STROBES) 4

1 TRAP PRIMER - MECH 140 20 A 1 0 VA 180 VA 1 20 A RECS - MECH 117 (MIXING VALVE) 2

CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT

Notes:

Enclosure: TYPE 1

Mounting: SURFACE Wires: 4 MCB/MLO Rating: 225

Supply From: 1T1 Phases: 3 Mains Type: MCB

Location: MECH 117 Volts: 120/208 Wye A.I.C. Rating: 42,000

Branch Panel: 1L1

GENERAL NOTES:

1. PROVIDE A COPY OF ALL COMPLETED PANEL SCHEDULES IN THE O & M MANUAL.

1 Addendum #3 4/5/2023

Total Amps: 99 A 104 A 107 A

Total Load: 11870 VA 12440 VA 12700 VA

53 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 54

51 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 52

49 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 50

47 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 48

45 RECS - VEST. 100 (DRINKING FOUNTAIN) GFCI 20 A 1 180 VA 0 VA 1 20 A SPARE 46

43 RECS - WOMENS 111 & MENS 11 20 A 1 360 VA 0 VA 1 20 A SPARE 44

41 RECS - WEAPONS CLEANING 130B 20 A 1 900 VA 900 VA 1 20 A RECS - SHOOTING LINE 116V & EXTERIOR 42

39 RECS - WEAPONS CLEANING 130B 20 A 1 720 VA 900 VA 1 20 A RECS - SHOOTING LINE 116V & EXTERIOR 40

37 RECS - WEAPONS CLEANING 130B 20 A 1 360 VA 900 VA 1 20 A RECS - ARMORY 130A 38

35 RECS - WEAPONS STR 130D & AMMO STR 130E 20 A 1 900 VA 900 VA 1 20 A RECS - ARMORY 130A 36

33 RECS - WEAPONS STR 130D & AMMO STR 130E 20 A 1 720 VA 1080 VA 1 20 A RECS - CORRIDOR 100B & STORAGE/GARAGE 130C 34

31 RECS - STAFF BREAK 128 (DISHWASHER) GFCI 20 A 1 1000 VA 1080 VA 1 20 A RECS - ROOMS 100B, 128, 130C 32

29 RECS - STAFF BREAK 128 (COFFEE MAKER) 20 A 1 1000 VA 540 VA 1 20 A RECS - CORR. 100B & JAN. 123 30

27 RECS - STAFF BREAK 128 20 A 1 1000 VA 1000 VA 1 20 A RECS - STAFF BREAK 128 (REFRIGERATOR) GFI 28

25 RECS - OFFICE 126 20 A 1 1080 VA 1000 VA 1 20 A RECS - STAFF BREAK 128 (MICROWAVE) 26

23 RECS - OFFICE 126 20 A 1 1080 VA 1000 VA 1 20 A RECS - STAFF BREAK 128 24

21 RECS - OFFICE 125 20 A 1 1080 VA 900 VA 1 20 A RECS - OFFICE 127 22

19 RECS - OFFICE 125 20 A 1 1080 VA 900 VA 1 20 A RECS - OFFICE 127 20

17 RECS - COPY 120 20 A 1 720 VA 900 VA 1 20 A RECS - OFFICE 121 18

15 RECS - COPY 120 20 A 1 720 VA 900 VA 1 20 A RECS - OFFICE 121 16

13 RECS - COPY 120 (COPIER) 20 A 1 180 VA 900 VA 1 20 A RECS - VEST. 100 & EXTERIOR 14

11 FLOORBOXES - CLASSROOM 110 20 A 1 1080 VA 900 VA 1 20 A RECS - VEST. 100 12

9 FLOORBOXES - CLASSROOM 110 20 A 1 1080 VA 1080 VA 1 20 A FLOORBOXES - CLASSROOM 110 10

7 FLOORBOXES - CLASSROOM 110 20 A 1 1080 VA 1080 VA 1 20 A FLOORBOXES - CLASSROOM 110 8

5 WINDOW SHADES - CLASSROOM 110 20 A 1 800 VA 1080 VA 1 20 A RECS - CLASSROOM 110 6

3 RECS - CLASSROOM 110 (PROJECTOR) 20 A 1 180 VA 900 VA 1 20 A RECS - CLASSROOM 110 4

1 UNIT HEATER - STORAGE/GARAGE 130C (UH-1) 20 A 1 150 VA 720 VA 1 20 A RECS - CLASSROOM 110 2

CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT

THIS PANEL CONTAINS GFI BREAKERS

Notes:

Enclosure: TYPE 1

Mounting: SURFACE Wires: 4 MCB/MLO Rating: 125

Supply From: 1T1 Phases: 3 Mains Type: MLO

Location: JANITOR 123 Volts: 120/208 Wye A.I.C. Rating: 22,000

Branch Panel: 1L2

Total Amps: 41 A 41 A 41 A

Total Load: 11417 VA 11346 VA 11369 VA

29 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 30

27 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 28

25 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 26

23 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 24

21 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 22

19 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 20

17 SPARE 20 A 1 0 VA 8680 VA 18

15 SPARE 20 A 1 0 VA 7700 VA 16

13 LTG - RMS 100, 123, 100B, 124A, 122A, 124B, 124C,... 20 A 1 2351 VA 7260 VA

3 100 A TRANSFORMER - 2T1 - MECH. PENTHOUSE 201

11 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 12

9 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 10

7 LTG - MECH 140 20 A 1 429 VA 1170 VA 1 20 A LTG - EXTERIOR POLE LIGHTS 8

5 LTG - FIRING LANES 116 20 A 1 2795 VA 0 VA 1 20 A SPARE 6

3 LTG - MECH. PENTHOUSE 201 20 A 1 977 VA 2796 VA 1 20 A LTG - SHOOTING LINE 116V 4

1 LTG - STAIR A 114 20 A 1 120 VA 200 VA 1 20 A LTG - EXTERIOR 2

CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT

Notes:

Enclosure: TYPE 1

Mounting: SURFACE Wires: 4 MCB/MLO Rating: 200

Supply From: ATS - LS Phases: 3 Mains Type: MCB

Location: MECH. PENTHOUSE 201 Volts: 480/277 Wye A.I.C. Rating: 22,000

Branch Panel: 2ESH1

Total Amps: 61 A 65 A 73 A

Total Load: 7260 VA 7700 VA 8680 VA

41 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 42

39 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 40

37 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 38

35 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 36

33 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 34

31 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 32

29 SPARE 20 A 1 0 VA 180 VA 1 20 A RECS - MDF 119 30

27 SPARE 20 A 1 0 VA 180 VA 1 20 A RECS - MDF 119 28

25 HEAT TRACE TO CH-3 30 A 1 2400 VA 180 VA 1 20 A RECS - MDF 119 26

23 HEAT TRACE TO CH-3 30 A 1 2400 VA 2400 VA 1 30 A HEAT TRACE TO CH-2 24

21 HEAT TRACE TO CH-2 30 A 1 2400 VA 2400 VA 1 30 A HEAT TRACE TO CH-2 22

19 HEAT TRACE TO CH-2 30 A 1 2400 VA 360 VA 1 20 A RECS - STAFF WOMENS 124A 20

17 RECS - RANGE CONTROL 115 20 A 1 360 VA 540 VA 1 20 A RECS - STAFF WOMENS 124A 18

15 RECS - RANGE CONTROL 115 20 A 1 180 VA 360 VA 1 20 A RECS - STAFF MENS 122A 16

13 RECS - RANGE CONTROL 115 20 A 1 180 VA 540 VA 1 20 A RECS - STAFF MENS 122A 14

11 RECS - MDF 119 20 A 1 1000 VA 800 VA 1 20 A FIRE ALARM CONTROL PANEL (FACP) - MDF 119 12

9 RECS - MDF 119 20 A 1 1000 VA 180 VA 1 20 A RECS - MDF 119 10

7 DOOR POWER SUPPLY - RM 130D 20 A 1 400 VA 400 VA 1 20 A DOOR POWER SUPPLY - RMS 116V, 128 & 130D 8

5 RECS - MDF 119 (UPS) 30 A 1 1000 VA 0 VA 1 20 A SPARE 6

3 DOOR POWER SUPPLY - ROOMS 122A & 124A 20 A 1 400 VA 600 VA 1 20 A DOOR POWER SUPPLY - RMS 130A & 130B 4

1 DOOR POWER SUPPLY - RMS 116V & 117 20 A 1 0 VA 400 VA 1 20 A DOOR POWER SUPPLY - MECH. 140 2

CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT

Notes:

Enclosure: TYPE 1

Mounting: UNISTRUT Wires: 4 MCB/MLO Rating: 100

Supply From: 2T1 Phases: 3 Mains Type: MLO

Location: MECH. PENTHOUSE 201 Volts: 120/208 Wye A.I.C. Rating: 22,000

Branch Panel: 2ESL1

Total Amps: 23 A 12 A 11 A

Total Load: 2700 VA 1440 VA 1260 VA

23 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 24

21 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 22

19 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 20

17 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 18

15 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 16

13 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 14

11 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 12

9 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 10

7 TARGET LINE 21-24 20 A 1 720 VA 540 VA 1 20 A TARGET LINE 28-30 8

5 TARGET LINE 17-20 20 A 1 720 VA 540 VA 1 20 A TARGET LINE 25-27 6

3 TARGET LINE 5-8 20 A 1 720 VA 720 VA 1 20 A TARGET LINE 13-16 4

1 TARGET LINE 1-4 20 A 1 720 VA 720 VA 1 20 A TARGET LINE 9-12 2

CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT

Notes:

Enclosure: TYPE 1

Mounting: SURFACE Wires: 4 MCB/MLO Rating: 100

Supply From: 1L1 Phases: 3 Mains Type: MLO

Location: RANGE CONTROL 115 Volts: 120/208 Wye A.I.C. Rating: 42,000

Branch Panel: 1L3

TS FS

C W

S

C

W R

MDF

EXISTING TELECOMMUNICATIONS

MANHOLE MH-34C

U G

T

U G

T

U G

E

UGE

UGT

UGT UGT

UGT

U G

E

U G

E

U G

E

UGEUGEUGEUGE

U G

E

U G

E

EXISITNG

15KV SWITCH

NEW PAD MOUNTED

TRANSFORMER

SWITCHGEAR

MECHANICAL ROOM

CH-1 CH-2

CH-3

NEW PAD MOUNTED

GENERATOR

C W

R

C W

S

C W

R

C W

S

C W

R

C

W S

S

2ESH1 - 8

OLF-3

OLF-3

OLF-3A

OLF-3A

OLF-3

OLF-3B

3" G

NOTE:

IT IS NOT INTENDED THAT THE PLANS SHOW ALL OFFSETS IN PIPES, CONDUITS, AND DUCTS REQUIRED FOR INSTALLATION OF THE WORK. DETAILS AND SECTIONS ARE INCLUDED FOR SOME AREAS TO SHOW INTENDED RELATIONSHIP OF THE WORK OF VARIOUS TRADES. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR AND SUB-CONTRACTORS TO COORDINATE INSTALLATION OF THE

WORK AND TO PROVIDE THE NECESSARY OFFSETS, TRANSFORMATIONS, AND FITTINGS REQUIRED. NO ADDITIONAL COMPENSATION WILL BE ALLOWED FOR CORRECTION CONFLICTS BETWEEN THE WORK OF VARIOUS TRADES. DETAILS AND SECTIONS ARE SHOWN FOR THE CONTRACTORS CONVENIENCE AND SHALL NOT BE CONSIDERED COMPLETE IN EVERY DETAIL.

C E N ENFO

SE

ENOIS

AL

GN

I

E

AT

P R

S

T K

E

CARTER

GREGORY G.

14715

L I S

D RE

Y

EFO K

C

TN

U

REVISION HISTORY OF THIS DRAWING

DECA LOG #

DRAWN BY

AS BULT DATE

COMMONWEALTH OF KENTUCKY

FINANCE AND ADMINISTRATION CABINET

DEPARTMENT FOR FACILITIES AND SUPPORT SERVICES

DIVISION OF ENGINEERING AND CONTRACT ADMINISTRATION

FRANKFORT, KENTUCKY

DESCRIPTION OF REVISIONS DATE DESCRIPTION OF REVISIONS DATE

CHECKED BY

PHASE

RTA DATE

DRAWING DATE

A & E FILE NO.

DRAWING INFORMATION

DRAWING NO.

ENGR. FILE NO.

/6

/2

:5

:1

A M

U100

SITE UTILITIES PLAN

525CAL3CJ3600

RECORD DWG. DATE

DOCJT FIRING RANGE

HANCOCK TAYLOR LN.

2023|03|14

1956.01

Checker

Author

2023|03|14

D

SCALE: 1" = 30'-0"U100

1 SITE UTILITIES PLAN

GENERAL NOTES:

1. CONTRACTOR IS RESPONSIBLE TO COORDINATE WITH ALL UTILITY COMPANIES AND PAY ALL

ASSOCIATED TAP FEES AND PROVIDE INSTALLATION PER ALL LOCAL UTILITY REQUIREMENTS.

2. LOCATION OF UTILITIES ARE APPROXIMATE AND SUBJECT TO MINOR CHANGES IN THE FIELD. DO NOT

SCALE THE DRAWINGS.

3. THE CONTRACT DOCUMENTS SHOW THE APPROXIMATE LOCATION OF THE EXISTING AND NEW

SUBSURFACE UTILITY LINES. THESE LINES HAVE BEEN IDENTIFIED AND LOCATED AS ACCURATELY AS POSSIBLE USING AVAILABLE INFORMATION. THE CONTRACTOR IS RESPONSIBLE FOR VERIFYING ALL ACTUAL LOCATIONS. IF ANY CHARTED, UNCHARTED, OR MIS-LOCATED UTILITY SERVICE IS INTERRUPTED

FOR ANY REASON, THE CONTRACTOR WILL WORK CONTINUOUSLY TO RESTORE SERVICE TO

SATISFACTION OF THE OWNER.

4. SHOULD EXISTING UTILITIES REQUIRE RELOCATION OR REROUTING NOT SHOWN OR INDICATED TO BE

RELOCATED OR REROUTED, CONTACT AND COOPERATE WITH THE OWNER TO MAKE THE REQUIRED

ADJUSTMENTS AT AN EQUITABLE CHANGE IN THE CONTRACT PRICE.

5. EXISTING UTILITIES SHOWN MAY ACTUALLY BE IN DIFFERENT LOCATIONS AND ADDITIONAL UTILITIES NOT SHOWN MAY EXIST AND MAY BE IN USE. IT IS THE CONTRACTOR’S RESPONSIBILITY TO PROTECT

ALL UTILITIES DURING CONSTRUCTION.

6. THE CONTRACTOR IS RESPONSIBLE FOR LOCATING ALL EXISTING UNDERGROUND UTILITIES PRIOR TO EXCAVATING. THE OWNER WILL NOT LOCATE THE UTILITIES FOR THE CONTRACTOR. IF AN OUTSIDE SERVICE OR COMPANY IS REQUIRED TO ACCURATELY LOCATE BURIED UTILITIES THE CONTRACTOR IS RESPONSIBLE FOR SCHEDULING THIS WORK AND IS RESPONSIBLE FOR THE COSTS. THE CONTRACTOR

SHOULD CONTACT APPROPRIATE UTILITY COMPANIES BEFORE DOING ANY EXCAVATING.

7. TOP ELEVATIONS OF NEW UNDERGROUND STRUCTURE ARE APPROXIMATE AND ARE FOR ESTIMATING PURPOSES ONLY. ACTUAL TOP ELEVATIONS MUST BE THE SAME AS FINISHED GRADE IN THE SAME

AREA. SEE ARCHITECTURAL PLANS FOR FINISHED GRADES.

8. INSTALL DOMESTIC WATER PIPING WITH 3’-6” MINIMUM COVER.

9. INSTALL FIRE PROTECTION WITH 4'-0" MINIMUM COVER.

10. INSTALL NATURAL GAS PIPING WITH 2’-0” MINIMUM COVER.

11. INSTALL UNDERGROUND FEEDERS WITH 2’-0” MINIMUM COVER.

12. EXCAVATION: MATERIALS TO BE EXCAVATED SHALL INCLUDE EARTH AND ANY OTHER MATERIAL, INCLUDING ROCK ENCOUNTERED IN TRENCH EXCAVATION.

13. SITE LIGHTING CIRCUITS SHALL BE #6 CONDUCTORS IN 1-1/4” CONDUITS.

14. TESTING OF EXTERIOR SEWER MANHOLES SHALL BE AS FOLLOWS:

A. EXTERIOR SANITARY SEWER SHALL BE PLUGGED BETWEEN MANHOLES AND SUBJECTED TO

AN AIR PRESSURE TEST WITH ALL OPENINGS TIGHTLY CLOSED. AIR SHALL BE PUMPED IN UNTIL

THE PRESSURE IS NOT LESS THAN 5 POUNDS PER SQUARE INCH. THE AIR PRESSURE GAGE

SHALL REMAIN CONSTANT WITHOUT PUMPING ADDITIONAL AIR INTO THE SYSTEM.

B. MANHOLE SHALL BE PLUGGED AND FILLED WITH WATER AND A VISUAL INSPECTION MADE FOR

LEAKS. ALL LEAKS SHALL BE CORRECTED.

C. ALL TESTS SHALL BE DONE PRIOR TO BACKFILLING.

CODED NOTES:

1 INSULATE ABOVE-GROUND CHILLED WATER PIPING WITH ARMAFLEX INSULATION AND ALUMINUM

JACKET.

2 TO 4" FIRE DEPARTMENT CONNECTION (FDC). SEE SITE CIVIL PLANS FOR CONTINUATION.

3 6" FIRE PROTECTION FROM COMBINATION VAULT. SEE SITE CIVIL PLANS FOR CONTINUATION.

4 2" PUMPED SANITARY/WASTE LINE. SEE SITE CIVIL PLANS FOR CONTINUATION.

5 3" DOMESTIC COLD WATER LINE FROM COMBINATION VAULT. SEE SITE CIVIL PLANS FOR

CONTINUATION.

6 GAS SERVICE LINE FROM MAIN AND METER BY RICHMOND UTILITIES. COORDINATE WITH RICHMOND UTILITIES PRIOR TO CONSTRUCTION. PROVIDE REGULATOR AND EXTEND NEW SERVICE LINE AS

REQUIRED. SEE GAS METER DETAIL.

7 (2) 4"CONDUITS FROM MDF IN NEW FIRING RANGE TO EXISTING COMMUNICATONS MANHOLE.

8 STUB CONDUITS UP THROUGH FLOOR SLAB IN MDF, SEAL CONDUITS WITH REMOVABLE SEALENT TO

PREVENT WATER INTRUSION INTO BUILDING.

9 NEW UNDERGROUND PRIMARY DUCTBANK, SEE ELECTRICAL DISTRIBUTION SYSTEM RISER DIAGAM

AND ELECTRICAL DUCTBANK DETAIL.

10 PROVIDE CONCRETE EQUIPMENT PAD FOR SITE MECHANICAL EQUIPMENT. SEE DETAIL.

11 8" STORM PIPING. SEE SITE CIVIL PLANS FOR CONTINUATION.

12 EXTEND NEW GAS SERVICE LINE AS REQUIRED TO AVOID COMBINATION VAULT AND SERVICE

CONNECTIONS. COORDINATE WITH SITE CIVIL PLANS.

13 TAMPER AND FLOW SWITCH FOR PIV. COORDINATE LOCATION WITH CIVIL DRAWINGS.

Addenda 3
1956.01_Addendum 03 (1)

File details come from the government source that posted it. Updated .