Addendum #4 - UVC Air Purification.pdf
PDF 355 KB Posted
- Attached to
- UVC Air Purification Project
- Solicitation number
- RFP ROY 210000002070 5
- Issued by
- Macomb County, Michigan
About this file
This is Addendum #4 to a UVC Air Purification procurement issued by Royal Oak Schools with engineering support from Strategic Energy Solutions, Inc. The addendum modifies the original procurement documents dated June 3, 2021 and addresses clarifications to HVAC air cleaning devices specifications in Section 23 4000. The project involves the installation of UVC air purification systems, with in-duct fixtures and upper air devices utilizing Philips TUV PL-L germicidal lamps. Bids are based on quantities, lengths, and intensity specifications indicated in Appendix B. The bid due date is Monday, June 21, 2021 at 11:00 AM local time. Prospective bidders may schedule building visits by contacting Michelle Kerns at michelle.kerns@royaloakschools.org or (248) 921-3929; visits without prior appointment are not permitted. Bidders must acknowledge receipt of this addendum in the bid form to avoid disqualification.
The addendum provides technical clarifications regarding ballast housing requirements, fixture placement in HVAC equipment adjacent to cooling coil sections, and lamp specifications. Ballasts must be suitable for mounting in HVAC equipment and may utilize rubber-sealed potted electronic ballasts designed for UV fixtures in moist HVAC environments when mounted internally in fixtures. The specifications clarify that Section 23 4000 Part 2.03C applies only to HVAC equipment coil cleaning applications and in-duct fixture installations. Prospective bidders should reference the complete specification section 23 4000 and Appendix B for detailed requirements and bid parameters.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
ADDENDUM 4
Project: UVC Air Purification
Bid Due date: Monday, June 21, 2021 at 11:00 AM Local Time (REVISED IN ADDENDUM #2)
I. General Information
1. For questions contact Michelle Kerns at michelle.kerns@royaloakschools.org or (248) 921-
3929.
2. Any bidder wanting to visit any building, contact Michelle Kerns at michelle.kerns@royalschools.org or (248) 921-3929 to schedule a time. Bidders are not allowed to visit the building without an appointment.
3. Addendum #4 dated June 16, 2021 as prepared by Strategic Energy Solutions.
END
Addendum 4
21 0566 01 Royal Oak Schools UVC Implementation 00 9111 - 1 Addendum Number 4
SECTION 00 9111
ADDENDUM NUMBER 4
PARTICULARS
1.01 DATE: JUNE 16, 2021
1.02 OWNER : ROYAL OAK SCHOOLS
1.03 ENGINEER: STRATEGIC ENERGY SOLUTIONS, INC.
TO: PROSPECTIVE BIDDERS:
2.01 THIS ADDENDUM FORMS A PART OF THE CONTRACT DOCUMENTS AND MODIFIES
THE ORIGINALPROCUREMENT DOCUMENTS DATED JUNE 3, 2021, WITH
AMENDMENTS AND ADDITIONS NOTED BELOW.
2.02 ACKNOWLEDGE RECEIPT OF THIS ADDENDUM IN THE SPACE PROVIDED IN THE BID
FORM. FAILURE TO DO SO MAY DISQUALIFY THE BIDDER.
CLARIFICATIONS TO THE PROJECT MANUAL - SPECIFICATIONS:
3.01 SECTION 23 4000-HVAC AIR CLEANING DEVICES
Q: Per 2.03 A.6, ballasts must be in a NEMA housing. Our fixtures use only rubber-sealed "potted" electronic ballasts designed for UV fixtures installed in moist HVAC environments.
They are mounted internally in the UV fixtures and don't need separate NEMA box protection.
A: Provide ballasts suitable for mounting in HVAC equipment adjacent to the cooling coil section in accordance with spec section 23 4000 part 2.03A.6.
Q: 2.03 C. Is this strictly for in-duct fixtures?
A: Spec section 23 4000 part 2.03C only applies to HVAC equipment coil cleaning applications as indicated in spec section 23 4000 part 2.03A.4.
Q: The upper air devices in the spec use the same Philips TUV PL-L lamps. We will propose the same Philips UVC lamps for in-duct use.
A: The new UVC lamps in existing HVAC equipment shall meet the requirements of spec section 23 4000 part 2.03C.
Q: Do you have any additional info? ie, coil sizes of each unit and possibly even dimensions we can base the bid off of?
A: Bids shall be based on quantities, lengths and intensity indicated in Appendix B.
Q: 2.03 C. If a modification is required at all, I propose to keep your numbers but replace the proprietary "Green Tube" terminology with "Germicidal lamp."
A: Refer to spec section 23 4000 part 2.03A.1 which defines the terminology.
END OF SECTION