This addendum to a project specification file pertains to the Royal Oak Schools' UVC Air Purification project and provides detailed technical requirements for ultraviolet-C (UVC) air cleaning devices and HVAC system enhancements across multiple school buildings. The project involves the installation of UVC air purification systems in nine school facilities: Adams, Keller, Northwood, Oakland, Oakridge, Upton, Royal Oak Middle School, Royal Oak High School, and Churchill, with additional installations at MTC. The bid due date, revised in Addendum #2, is Monday, June 21, 2021 at 11:00 AM local time. Prospective bidders must contact Michelle Kerns at michelle.kerns@royaloakschools.org or (248) 921-3929 to schedule required building visits, as unscheduled visits are prohibited. The project specification details two categories of UVC installations: wall-mounted units for upper air room disinfection and applied units for existing HVAC equipment coil cleaning, with specific equipment schedules and performance requirements documented for each school location.

The specification establishes comprehensive technical requirements for UVC equipment, including approval of specific manufacturers such as American Ultraviolet Company, Sailon-GUVC, CureUV, UV Resources, and Steril-Aire, Inc. All UVC units must be warranted for a minimum of one year from installation, with ballasts warranted for five years. Equipment specifications require high-output UVC lamps containing 8 milligrams of mercury, capable of producing minimum 11.7 microwatts/cm² per linear inch of lamp arc length, with wall-mounted units delivering a minimum of 600 cubic feet per minute airflow and sound levels not exceeding 62 decibels at one meter. Applied units must achieve a minimum airstream irradiance of 5000 microwatts/cm² dosage rate at 45 degrees Fahrenheit airflow velocity of 500 feet per minute to ensure minimum 4-log reduction of airstream pathogens. The specification includes requirements for safety interlocks on HVAC equipment access doors, airflow switches to disable UV lights when fans are not running, warning placards, surge-protected extension cords, and factory-trained technician support for installation and final inspection.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

ADDENDUM 3

Project: UVC Air Purification

Bid Due date: Monday, June 21, 2021 at 11:00 AM Local Time (REVISED IN ADDENDUM #2)

I. General Information

1. For questions contact Michelle Kerns at michelle.kerns@royaloakschools.org or (248) 921-

3929.

2. Any bidder wanting to visit any building, contact Michelle Kerns at michelle.kerns@royalschools.org or (248) 921-3929 to schedule a time. Bidders are not allowed to visit the building without an appointment.

3. Addendum #3 dated June 11, 2021 as prepared by Strategic Energy Solutions.

END

Addendum 3

21 0566 01 Royal Oak Schools UVC Implementation 23 4000 - 1 HVAC AIR CLEANING

DEVICES

SECTION 23 4000

HVAC AIR CLEANING DEVICES

PART 1 GENERAL

1.01 SECTION INCLUDES

A. Ultraviolet lights.

B. Air cleaning systems.

1.02 REFERENCE STANDARDS

A. ACGIH - Ultraviolet Radiation, TLV Physical Agents 2010, 7th edition.

1.03 SUBMITTALS

A. Product Data:

1. Published Literature: Indicate dimensions, weights, capacities, ratings, gauges and finishes of materials, and electrical characteristics and connection requirements.

2. Sound Power Level Data: Fan outlet and casing radiation at rated capacity.

3. Electrical Requirements: Power supply wiring including wiring diagrams for interlock and control wiring, clearly indicating factory-installed and field-installed wiring.

1.04 WARRANTY

A. All UVC Units shall be warranted for no less than one (1) year from date of installation.

PART 2 PRODUCTS

2.01 MANUFACTURERS

A. American Ultraviolet Company .

B. Sailon-GUVC .

C. CureUV.

D. UV Resources ; RLM Xtreme : www.uvresources.com/#sle.

E. Steril-Aire, Inc ; Rapid Install Kit : www.steril-aire.com/#sle.

2.02 APPLICATIONS

A. Unit A: Use CureUV GermAwayUV High Occupancy or approved equal.

B. Unit B: Unit Ventilators.

C. Unit C : Use CureUV Centurion or approved equal .

2.03 COMPONENTS

A. UVC Emitters:

1. UVC Emitters shall be ”High Output” “HO-style” and manufactured utilizing ≤ 8 mg.

Mercury in the lamp, also known as “Green Tubes”.

2. The “High-Output” UVC fixtures shall be designed specifically for HVAC.

3. Wall mount applications designed for upper air room mounting for fly-thru air disinfection of pathogens and complete dilution of room air with disinfected air.

4. For HVAC equipment coil cleaning applications UVC output shall be as specified in paragraph C to guarantee continuous destruction of all known molds, bacteria and viruses and shall produce the specified UVC energy to prevent coil biological fouling and eliminate the need for coil cleaning and drain pan biocides.

5. Fixtures shall be designed for “Moisture-Proof” applications with UVC lamps designed to incorporate built in inner pure silica quartz tube with non-wavelength degradation safety tube sleeve with protective boot on power end for sealing purposes. Units shall have power connecting cords to one end of the lamp end that incorporate a sure seal type connector that fits securely for moisture sealing purposes.

6. All UVC lamps downstream of the cooling coil shall have their ballasts located in a NEMA 1 type housing, suitable for mounting in the HVAC equipment adjacent to the cooling coil section.

7. UVC emitters must include EPA and FCC certifications for ≤ 8 mg. Mercury and wavelength.

8. Wall mount fixtures must include two (2) programmable universal remote controls per unit, time-of-day and week scheduling capability, Wi-Fi capability and a minimum 10’ UL rated 3-prong power cord.

UVC Implementation 23 4000 - 2 HVAC AIR CLEANING

DEVICES

9. Wall mounted units must provide a minimum of 600 CFM.

10. Wall mounted units sound level shall not exceed 62 db at 1m.

B. Fixture Ballasts:

1. Fixtures shall be “moisture proof” construction. Sizes shall be from 12” in total length to no more than 66” in total length .

2. Ballasts shall be of the solid-state electronic design and be a Class P rapid start with a power factor minimum of .95. Ballasts shall be available as a 120/208/230/277 VAC 50/60 Hz and be designed to maximize photon production in air temperatures of 35 to 175 degrees F. Minimum ballast start temperature shall be minus 20 degrees F.

Ballasts shall have a RFI EMI rating as defined by FCC part 18A for industrial / commercial applications in regards to suppression. Ballasts are to be UL listed.

Ballasts shall be of the type to incorporate “Green UVC Tubes” as specified in paragraph 1.0. Ballast shall be warranted for five (5) years.

3. Each fixture shall be factory assembled and tested prior to shipment. Each assembly consists of a housing, reflector, electronic ballast(s), lamp bracketry, power connectors and high output lamp(s). Reflectors shall be fabricated from the highest-grade polished aluminum lighting sheet material, which has a reflectivity rate of 88% when exposed to short-wave UVC in the range of 254 nm.

4. All fixtures and ballasts must carry at least one of the following certifications; UL, ETL, CE.

C. UVC “Green Tubes”:

1. Each UVC “Green Tube” shall contain no greater than 8 mg of mercury content .

2. Each UVC “Green Tube” shall be guaranteed to produce no ozone .

3. Lamps shall be rated for 11.7 µw output per linear inch of tube length and have a (1) year (10,000 hours) continuous operational life with no greater than a 20% drop in UVC output at end of lamp life of 1 year.

4. Each UVC “Green Tube” shall have a minimum intensity of 11.7 microwatts/cm² per linear inch of lamp arc length at a distance of one meter as per IES Test Standards.

Output shall be independently tested in airstreams of 400 feet per minute velocities at temperatures of 45 degrees F. Successful supplier shall submit independent documentation of specified performance with their submittals.

5. UVC lamps shall be high-output (HO) variety, T5 interior tube diameter, and are to be constructed from hard pure quartz glass tubing for superior UVC transmittance and minimal internal etching. Electrodes shall be designed to maximize plasma convection and stability for high output lamp performance. Lamps shall be rated to produce 11.7 microwatts/cm² per linear inch of lamp arc length at a distance of one meter. Output shall be independently tested in airstreams of 400 feet per minute velocities at temperatures of 45 degrees F.

6. The engineered selection of the UVC lamp system array shall be based upon a minimum airstream irradiance of 5000 µw/cm² dosage rate at 45°F airstream temperature, compensated for wind-chill effect at an airflow velocity of 500 FPM or 8.8 fps, and measurable at any air- to-lamp intersect point for minimum 4-log reduction of airstream pathogens.

2.04 ACCESSORIES

A. Vendor will provide 14"W x 5"H white placard with black letters on each wall-mounted unit indicating the purpose of the wall-mounted unit. Placard shall read:

UVC air disinfection device Do not touch or turn-off

B. Vendor will provide 6"W x 3"H red placard with white letter on each applied unit indicating:

CAUTION - DANGER

Do NOT service this unit unless UVC lights and FAN are locked out in the OFF position.

C. In locations where wall mounted UVC equipment is provided with a cord connection, provide a surge protected extension cord for each location to the nearest available receptacle. Cord provided shall meet the following requirements:

1. 25 feet in length (or less if receptacle is located closer).

2. Internal surge protection.

3. Neutral color (i.e.- gray, tan, white). Yellow, orange and black are not acceptable.

UVC Implementation 23 4000 - 3 HVAC AIR CLEANING

DEVICES

4. Provide support/strain relief of cord and connection.

5. If extension cord has multi-outlet assembly- mount assembly to wall.

6. Coordinate with owner for mounting locations and cord routing prior to installation.

PART 3 EXECUTION

3.01 EXAMINATION

A. Verification of Conditions: Field verify that products will fit and work with all existing equipment.

3.02 INSTALLATION

A. Install in accordance with manufacturer's written instructions.

B. A factory-trained technician shall assist at the project site for instructions on correct installation of the UVC Systems, both wall mount and applied systems in existing HVAC equipment.

C. A factory-designated technician shall inspect all final installations and submit in writing to the Engineer that the UVC System installation is of correct application and effectiveness.

D. Treat view port and other windows to assure the UV-C energy emitted is below the threshold limit specified by American Conference of Governmental Industrial Hygienists

(ACGIH).

E. Contractor to field coordinate with owner exact location of wall mounted UVC devices prior to installation.

F. Contractor shall coordinate with owner when programming run schedule.

G. Systems Integration:

1. All UVC devices installed as an enhancement to existing HVAC equipment shall have the access door interlocked to an electric interlock switch in order to shut off the UVC lights upon the opening of the door .

2. Wire airflow switch into control circuit to disable UV lights when the HVAC equipment fan is not running.

3. Vendor to provide and install electrical contact switch to kill power upon entry of any wall mounted unit, to provide immediate deactivation of the UVC energy upon opening access panel on any portion of the wall-mounted unit.

4. Each remote control shall be programmed to control any of the wall mount fixtures.

3.03 SCHEDULES

A. 000120 : List of Schedules .

3.04 ATTACHMENTS

A. Refer to List of Drawing Sheets .

B. Basis of Design Equipment Cutsheets.

END OF SECTION

APPENDIX B:

SCHEDULES

Applied Units Listing (by school)

ADDAMS Min. airstream dose 5000µW/cm² - Fly-by TOTAL INTENSITY at 18" from coil face

WATTAGE must meet or exceed values shown below AHU-1 2 CUV-JW150W 62" 145W 120/277v 290 1641

AHU-2 2 CUV-JW80w 34" 80W 120V 160 1327

AHU-3 2 CUV-JW80w 34" 80W 120V 160 1734

AHU-4 4 CUV-JW150W 62" 145W 120/277v 580 1824

AHU-5 2 CUV-JW80w 34" 80W 120V 160 1566

Unit Ventilators 0

KELLER

TOTAL UVC

WATTAGE INTENSITY

AHU-1 4 CUV-JW150W 62" 145W 120/277v 580 2235

AHU-2 4 CUV-JW150W 62" 145W 120/277v 580 2235

AHU-3 4 CUV-JW150W 62" 145W 120/277v 580 2235

Unit Ventilators 0

NORTHWOOD

TOTAL UVC

WATTAGE INTENSITY

AHU-1302 2 CUV-JW80W 34" 80W 120/277V 160 1327

AHU-1301 3 CUV-JW80W 34" 80W 120/277V 240 1450

AHU-1201 2 CUV-JW80W 34" 80W 120/277V 160 1824

Unit Ventilators 0

OAKLAND

TOTAL UVC

WATTAGE INTENSITY

AHU-1 4 CUV-JW40W 18" 48W 120/277V 160 1125

HV-1 4 CUV-JW120W 46" 120W 120/277V 480 2372

4 CUV-JW40W 18" 48W 120/277V

4 CUV-JW150W 62" 145W 120/277V

2 CUV-JW40W 18" 48W 120/277V

2 CUV-JW150W 62" 145W 120/277V

ERV-1 4 CUV-JW120W 46" 120W 120/277V 480 2145

RTU-1 2 CUV-JW80W 34" 80W 120/277V 160 2190

Unit Ventilator 1 CUV-JW40W 18" 48W 120/277v 48 256 per

OAKRIDGE

TOTAL UVC

WATTAGE INTENSITY

RTU-1 2 CUV-JW80w 34" 80W 120V 160 1451

AHU-1 2 CUV-JW80w 34" 80W 120V 160 1566

AHU-2 2 CUV-JW80w 34" 80W 120V 160 1451

AHU-3 4 CUV-JW150W 62" 145W 120/277v 580 2235

Unit Ventilators 9 CUV-JW40W 18" 48W 120/277v 48 per 256 per

TAG QTY

GRIFFIN IAQ

SYSTEMS PART#

DESCRIPTION

GRIFFIN IAQ

SYSTEMS PART#

TAG QTY

GRIFFIN IAQ

SYSTEMS PART#

DESCRIPTION

MZ-1 1142

TAG QTY DESCRIPTION

TAG QTY

GRIFFIN IAQ

SYSTEMS PART#

DESCRIPTION

TAG QTY

GRIFFIN IAQ

SYSTEMS PART#

DESCRIPTION

UPTON

TOTAL UVC

WATTAGE INTENSITY

AHU-1 2 CUV-JW80W 34" 80W 120/277V 160 1566

AHU-2 2 CUV-JW80W 34" 80W 120/277V 160 1566

AHU-3 3 CUV-JW80W 34" 80W 120/277V 240 1824

ERU-1 3 CUV-JW120W 46" 120W 120/277V 360 2090

RTU-1 3 CUV-JW80W 34" 80W 120/277V 240 2618

Unit Ventilators 2 CUV-JW40W 18" 48W 120/277v 48 256 per

ROYAL OAK MIDDLE SCHOOL

TOTAL UVC

WATTAGE INTENSITY

RTU-1 3 CUV-JW80w 34" 80W 120/277v 240 1451

RTU-2 4 CUV-JW120W 46" 120W 120/277V 480 2372

RTU-3 4 CUV-JW120W 46" 120W 120/277V 480 2372

HV-1 5 CUV-JW150W 62" 145W 120/277V 725 2050

HV-3 3 CUV-JW80w 34" 80W 120/277v 240 2069

HV-5 3 CUV-JW80w 34" 80W 120/277v 240 2069

HV-7 8 CUV-JW80w 34" 80W 120/277v 640 2049

HV-8 8 CUV-JW80w 34" 80W 120/277v 640 2049

9 CUV-JW150W 62" 145W 120/277V

9 CUV-JW120W 46" 120W 120/277V

AHU-1 2 CUV-JW80w 34" 80W 120/277v 160 1566

AHU-2 2 CUV-JW80w 34" 80W 120/277v 160 1566

AHU-3 5 CUV-JW150W 62" 145W 120/277V 725 1934

AHU-6 3 CUV-JW80w 34" 80W 120/277v 240 1824

HRU-4 4 CUV-JW120W 46" 120W 120/277V 480 2843

Unit Ventilators 6 CUV-JW40W 18" 48W 120/277v 48 per 256 per

ROYAL OAK HIGH SCHOOL

TOTAL UVC

WATTAGE INTENSITY

RTU-1A 4 CUV-JW80W 34" 80W 120/277V 320 2069

RTU-2A 4 CUV-JW80W 34" 80W 120/277V 320 2069

RTU-102 4 CUV-JW120W 46" 120W 120/277V 480 2372

RTU-103 4 CUV-JW80W 34" 80W 120/277V 320 2069

4 CUV-JW80W 34" 80W 120/277V

4 CUV-JW150W 62" 145W 120/277V

AHU-13 2 CUV-JW80W 34" 80W 120/277V 160 1451

AHU-14 2 CUV-JW80W 34" 80W 120/277V 160 1451

AHU-15 4 CUV-JW80W 34" 80W 120/277V 320 2069

AHU-2 4 CUV-JW80W 34" 80W 120/277V 320 1824

AHU-3 4 CUV-JW150W 62" 145W 120/277V 580 1899

AHU-4 8 CUV-JW120W 46" 120W 120/277V 960 2928

AHU-5 4 CUV-JW80W 34" 80W 120/277V 320 1824

AHU-9 2 CUV-JW80W 34" 80W 120/277V 160 1451

4 CUV-JW80W 34" 80W 120/277V

4 CUV-JW120W 46" 120W 120/277V

4 CUV-JW80W 34" 80W 120/277V

4 CUV-JW150W 62" 145W 120/277V

HRU-7 2 CUV-JW120W 46" 120W 120/277V 240 1944

HRU-8 2 CUV-JW120W 46" 120W 120/277V 240 1944

HRU-9 2 CUV-JW120W 46" 120W 120/277V 240 1451

Unit Ventilators 0 0 0 0 0

ERU-103 800

DHU-1 900

TAG QTY

GRIFFIN IAQ

SYSTEMS PART#

DESCRIPTION

AHU-12 900

2385AC-1

TAG QTY

GRIFFIN IAQ

SYSTEMS PART#

DESCRIPTION

TAG QTY

GRIFFIN IAQ

SYSTEMS PART#

DESCRIPTION

CHURCHILL

TOTAL UVC

WATTAGE INTENSITY

RTU-2 1 CUV-JW80w 34" 80W 120V 80 1451

RTU-3 3 CUV-JW120W 46" 120W 120/277V 360 2843

RTU-4 2 CUV-JW150W 62" 145W 120/277V 290 1934

AHU-1 2 CUV-JW80w 34" 80W 120V 160 1451

AHU-2 2 CUV-JW150W 62" 145W 120/277V 290 2235

AHU-4 2 CUV-JW150W 62" 145W 120/277V 290 1814

AHU-5 2 CUV-JW150W 62" 145W 120/277V 290 2235

RTU-4 3 CUV-JW80w 34" 80W 120V 240 1451

AHU-6 1 CUV-JW80w 34" 80W 120V 80 796

AHU-7 4 CUV-JW120W 46" 120W 120/277V 480 2372

AHU-13 2 CUV-JW120W 46" 120W 120/277V 240 1681

AHU-14 2 CUV-JW120W 46" 120W 120/277V 240 1681

AHU-8 2 CUV-JW80w 34" 80W 120V 160 1451

AHU-9 2 CUV-JW80w 34" 80W 120V 160 1451

Unit Ventilators 15 CUV-JW40W 18" 48W 120/277v 48 per 256 per

RTU-1 5 CUV-JW150W 62" 145W 120/277V 725 1934

MTC

TOTAL UVC

WATTAGE INTENSITY

4 CUV-JW80W 34" 80W 120/277V

4 CUV-JW150W 62" 145W 120/277V

HV-1 1 CUV-JW40W 18" 48W 120V/277 48 256

FCU-5 1 CUV-JW40W 18" 48W 120/277v 48 256

900 3788

TAG QTY

GRIFFIN IAQ

SYSTEMS PART#

DESCRIPTION

AHU-1

TAG QTY

GRIFFIN IAQ

SYSTEMS PART#

DESCRIPTION

APPENDIX C:

BASIS OF DESIGN EQUIPMENT CUTSHEETS

GermAwayUV High Occupancy Wall Mountable Air Puriöer and Sanitizer

Great for eliminating viruses, bacteria, and pathogens of all types.

• 150 Watts of UV-C germicidal irradiation sanitize and disinfect the air as it is pushed through the unit.

•• Powerful 600 cfm (cubic feet per minute) crossøow blower changes the air in small rooms dozens of times per hour.

• Carefully sealed to avoid any UV-C light leakage that would otherwise be harmful to eyes and skin.

• Eliminates odors and improves air quality.

KEY FEATURES

· Photocatalytic ölter breaks down Volatile Organic Compunds (VOC)

· Remote control can be used to control 1 or many of these systems in large of these systems in large installations for your convenience.

· Programmable functions for high occupancy scheduling.

Deactivate and eliminate harmful airborne bacteria and viruses in heavily occupied rooms by leveraging the power of UV-C disinfection without any risk to yourself or your clients.

SKU: 201076

TECHNICAL

SPECIFICATIONS

SYSTEM

ARCHITECTURE

DIMESNSIONS: 39.8” X 12.8” X 8.5

WEIGHT: 38 LBS

COVERAGE AREA: 500 SQUARE FEET WITH 8 FT CEILINGS

UV BULB LIFESPAN: 10,000 HOURS

UVC WATTAGE: 150 WATTS

CLEAN AIR DELIVERY RATECADR: 60 CUBIC FEET PER MINUTE CFM

DECONTAMINATION RATE: DECONTAMINATION RATE:

AMPS: 4.8

LOWERS COLONY FORMING UNIT COUNT

TO LESS THAN 200 CFU/M3 LESS THAN 200 CFU/M3DECONTAMINATION RATE:

AMPS: 4.8

DECONTAMINATION RATE:

AMPS: 4.8

INFO

ADDITIONAL

INFORMATION

For more information of any of our products or services please visit us on the Web at:

cureuv.com/wallmountapcureuv.com/wallmountap

RELATED

PRODUCTS

Our services offer enterprises the ability to have a clean and a safe enivorment to maintain a to maintain a healthy work place.

Phone: (800) 977-7292 Address: 2855 S. Congress Ave. Ste. C, Delray Beach, FL, 33445

Web store: www.cureUV.com

This document is copyright @ August 13, 2020 CureUV. All rights reserved. This document is provided for information purposes only. Contents are subject to change without notice. It is not warranted to be error-free. Nor subject to any other warrenties or conditions including implied warrenties and conditions of merchantability or ötness for a particular purpose

• 5 Bulb System

• Digital Display

• Primary medium efficiency ölter

• Activated Carbon Filter

• Photocatalyst Filter

• Remote Control (2 x AAA)

• Power supply: 120 VAC

NOTE: This device was also tested in a 10 x 10 room for exactly one hour and no trace of ozone was detected. Utilizing ozone meter Model: FD-90

Cord Length: 12 foot environment

1.https://www.news-medical.net/news/20200608/Irradiation-with-UV-light-kills-SARS-CoV-2.aspx 2.https://www.ashrae.org/File%20Library/Professional%20Development/Learning%20Portal/Instructor-Led%20Training/ Online%20Instructor-Led/FINAL_ReOpening-Our-Schools_Aug13-2020.pdf

Phone: (800) 977-7292 Address: 2855 S. Congress Ave. Ste. C, Delray Beach, FL, 33445 Web store: www.cureUV.com

This document is copyright @ September 30, 2020 CureUV. All rights reserved. This document is provided for information purposes only. Contents are subject to change without notice. It is not warranted to be error-free. Nor subject to any other warrenties or conditions including implied warrenties and conditions of merchantability or ötness for a particular purpose.

Technical Data Sheet

Griffin UVC CUV SERIES

Includes: 254nm Lamp, 10’ whip from lamp to waterproof connector, 18”whip from connector to ballast, IP 64 rated ballast, 3’ leads to power, 2-25mm Terry Clips and 1st year replacement lamp.

WARNING: The radiation of these lamps is harmful to skin and eyes. Operate these lamps only with radiation protection!

Certifications:UL, CE, EPA, FCC, IP 64

SPECS CUV-30 15 CUV-40 18 CUV-80 34 CUV-120 46 CUV-150 62

H1 LAMP DISTANCE 382 mm (15”) 461 mm (18”) 868 mm (34”) 1173 mm (46”) 1579mm (62”)

LAMP CURRENT 800mA 800mA 800mA 800mA 800mA

LAMP VOLT 40V 70V 127V 166V 220V

LAMP WATTAGE 32W 48W 80W 120W 150W

MERCURY CONTENT <8mg <8mg <8mg <8mg <8mg

AMPS .27 @120V .40 @120V .67 @120V 1.0@120V 1.21 @ 120V

AMBIENT TEMP Max: 140°F Min 14°F Max: 140°F Min 14°F Max: 140°F Min 14°F Max: 140°F Min 14°F Max: 140°F Min 14°F

UV Intensity 95uW/cm/2 120uW/cm/2 260uW/cm/2 310uW/cm/2 400uW/cm/2

UVC OUTPUT WATTS 10W 13W 28W 30W 43W

STANDARD LIFE 10,000 HRS 10,000 HRS 10,000 HRS 10,000 HRS 10,000 HRS

BALLAST PL1-800-100A PL1-800-100A PL1-800-100A PH1-800-155U PH1-800-155U

AC Source 99V-132V 99V-132V 99V-132V 99V~264V 99V~264V

Mains Frequency 50/60Hz 50/60Hz 50/60Hz 50/60Hz 50/60Hz

Ballast Size 215*44*26mm 215*44*26mm 215*44*26mm 240.5*44*30mm 240.5*44*30mm

High Occupancy 240 Watt 600+ CFM UV Air Sanitizer and Disinfection System

Replacement UV Bulb

SKU: 191701

Replacement Filter

SKU: 201106

Leverage Internet of Things (loT) technology, UV-C 253.7nm irradiation, TRUE HEPA H13 öltration, and bleeding edge blower developments to turn your room or building into a safe, virus and contaminant free space to breathe.

Proudly Made in the USA

TECHNICAL

SPECIFICATIONS

FILTRATION LEVEL: TRUE HEPA H13

UVC WATTAGE: 240 WATTS

REPLAVEMENT UVC BULB: 60 WATTS PHILIPS UVC GERMICIDAL BULB

UV BULB LIFE: UP TO 10,000 HOURS

CLEAN AIR DELIVERY RATECADR: 600+ CUBIC FEET PER MINUTE CFM

WEIGHT: 35 LBS

DIMENSIONS: DIMENSIONS: 38.5” X 7.22” X 14,51”

SOUND LEVEL: 62DB AT 1M

OZONE LEVELS: OZONE FREE

CONNECTIVITY PLATFORM: BLYNK IOT

EPA ESTABLISHMENT NUMBER: 94850FL1

DIMENSIONS: 38.5” X 7.22” X 14,51”

SOUND LEVEL: 62DB AT 1M

OZONE LEVELS: OZONE FREE

CONNECTIVITY PLATFORM: BLYNK IOT

EPA ESTABLISHMENT NUMBER: 94850FL1

DIMENSIONS: 38.5” X 7.22” X 14,51”

SOUND LEVEL: 62DB AT 1M

OZONE LEVELS: OZONE FREE

CONNECTIVITY PLATFORM: BLYNK IOT

EPA ESTABLISHMENT NUMBER: 94850FL1

INFO

CONTACT US:

sales@cureuv.com 1-800-977-7292

694 CUBIC FEET PER MINUTE (CFM)

High Occupancy 240 Watt 694 CFM UV Air Sanitizer and

Disinfection System

REPLACEMENT UV-C BULB:

COMPONENTS PANEL

COVER

INSIDE

4 x 60-Watt Phillips shatterproof UVC lamps

Extended Life Ballasts *(not pictured)

Optimized Air Flow Channeling for maximum air disinfection

WiFi loT card enables off site support and free lifetime OTA örmware updates

4-line high contrast display

3 modes of operation (can be used in combination):

•Manual: Use IR remote or Web App to control unit immediately.

•Scheduled: Plan out your sanitation cycles on 7-day calendar based upon building hours, holidays, etc.

•Automatic: Allow the system’s sensors and algorithm to maintain a germ-free environment.

Ultra efficient TRUE HEPA H13 ölter (per CDC Guidelines)

Quick Access cover for easy lamp replacement

Occupancy detection:

Walk through the 135° öeld of motion detection and system automatically begins sanitizing the air. Auto shut down when room is unoccupied.unoccupied.

600+ CFM ultra quiet cross øow multi-speed balanced blower Mobile App enables full range of control at your öngertips over one or multiple Centurion Wall systems

Quick-Lock lamp socket for easy bulb replacement

Mobile Application

GermAway UV Smart Control

GermAw d

Login I

GermAwayUV Tools

f. Everyone

Tt- s app s compatJb e w :r your ce ce

I!) Add to w,shlist

�Quic.kview0 ---, f· uvc orr © E11110•

,---ouick Control-, .-------tJ-, APPLICATION FEATURES

(AVAILABLE ON GOOGLE PLAY AND APP STORE)

• Wifi enabled electronic hub allows control and scheduling of one or multiple units from your mobile app.

• In addition to the web app, each unit comes with an infrared (IR) remote for in room control.

• 7 day programmable run schedule.

• Free lifetime over-the-air (OTA) updates guarantee that the system is always running the latest and greatest set of features.

• Easily control multiple units at once.

1.https://www.news-medical.net/news/20200608/Irradiation-with-UV-light-kills-SARS-CoV-2.aspx 2.https://www.ashrae.org/File%20Library/Professional%20Development/Learning%20Portal/Instructor-Led%20Training/ Online%20Instructor-Led/FINAL_ReOpening-Our-Schools_Aug13-2020.pdf

· The key to risk mitigation in the era of airborne SARS-CoV-2 is to decontaminate and disinfect the air in the room as quickly as possible.

· Standard commercial HVAC systems replenish the air in an average 15’ x 15’ x 7.5’ room 2-4 times per hour when running full time in the summer. The air is not disinfected but it at least goes through a single layer of öltration.

· The GermAwayUV Centurion decontaminates, ölters, and disinfects the air in the same sized room 21+ times per hour or once every 2 minutes and 48 seconds year-round.

Phone: (800) 977-7292 Address: 2855 S. Congress Ave. Ste. C, Delray Beach, FL, 33445 Web store: www.cureUV.com

This document is copyright @ September 30, 2020 CureUV. All rights reserved. This document is provided for information purposes only. Contents are subject to change without notice. It is not warranted to be error-free. Nor subject to any other warrenties or conditions including implied warrenties and conditions of merchantability or ötness for a particular purpose.

TRUE HEPA 13 Filtration+ UV-C 253.7nm Irradiation

File details come from the government source that posted it. Updated .