ADDENDUM #4 ELECTRICAL REVISIONS 1 of 3 May 13.pdf
PDF 18 MB Posted
- Attached to
- RFP NORTH CAMPUS BID PKG #2
- Solicitation number
- RFP JCI 260000001841 6
- Issued by
- Kalamazoo County, Michigan
About this file
Summary
This is Addendum #4 Electrical Revisions for the JCISD Torrant Center Additions & Renovations project, a state and local contract opportunity in Michigan for North Campus Bid Package #2. The addendum provides comprehensive electrical demolition and installation plans across multiple areas (C, D, F, G, H, and M) of the facility. The work encompasses disconnection and removal of existing electrical equipment, conduit, wire, and lighting fixtures, with selective retention of certain conduit and wire for new equipment connections. New electrical installations include multiple panels (new panels A, B1, B2, C1, C2, D1, D2, E, F, J, MDP, and X), various power circuits ranging from 120V to 208V three-phase configurations, and specialized equipment including rooftop units, exhaust fans, pool equipment, and exterior lighting systems. The project includes detailed specifications for lighting fixtures (McGraw Edison models with LED technology), pole-mounted area lights with photocell and motion sensor controls, handhole installations, and communications infrastructure. Panel schedules show load modifications with removed and added electrical loads across multiple circuits, with breaker replacements specified throughout.
The addendum includes general electrical notes requiring contractors to provide and install new panels, modify existing conduit and wire for new connections, reuse existing infrastructure where applicable, and coordinate with owners regarding equipment locations prior to rough-in work. Key technical specifications address contractor responsibilities for timeclock control of exhaust fans with owner scheduling confirmation, removal and reconnection of pneumatic interlocks, transformer circuits for control valve power, and installation of four-11/16" deep square boxes with one-inch conduit and single-gang plaster rings for data devices. The document references load summaries showing net load changes (both increases and decreases) across different panel areas, with specific breaker sizing modifications detailed in the panel schedules. All work must comply with NEC standards and project specifications, with detailed drawings provided at 1/8" = 1'-0" scale across multiple sheets (E10-E58).
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
EXISTING EQUIPMENT TO REMAIN.
DISCONNECT AND REMOVE EXISTING EQUIPMENT. ASSOCIATED CONDUIT
AND WIRE TO REMAIN FOR CONNECTION TO NEW EQUIPMENT.
EXISTING LIGHTING CONTROL DEVICE TO REMAIN.
DISCONNECT AND REMOVE EXISTING LIGHT FIXTURES. REMOVE CONDUIT
AND WIRE BACK TO SOURCE.
REMOVE LIGHTING CONTROL DEVICE. REMOVE CONDUIT AND WIRE. PATCH
AND PAINT WALL TO MATCH EXISTING.
DISCONNECT AND REMOVE EXISTING EQUIPMENT. REMOVE CONDUIT AND
WIRE BACK TO SOURCE.
DISCONNECT AND REMOVE EXISTING EQUIPMENT. REMOVE ASSOCIATED
CONDUIT AND WIRE BACK TO SOURCE.
DISCONNECT AND REMOVE EXISTING EQUIPMENT. ASSOCIATED CONDUIT
AND WIRE TO REMAIN FOR CONNECTION TO NEW EQUIPMENT.
DISCONNECT AND REMOVE EXISTING LIGHT FIXTURE FOR CEILING
MODIFICATIONS. REINSTALL IN CEILING WHEN COMPLETE.
DEMOLITION NOTES
CU
CU
CU
UV
UV
UV
CU
CU
UV
UV
EXIST. PNL
"N"
EXIST. PNL
"A"
SCALE: 1/8" = 1'-0"
0 1 5 10 20
N PARTIAL FLOOR PLAN - POWER DEMOLITION - AREA "C"
J C
IS
D
T O
R R
A N
T C
E N
T E R
A D
D
IT
IO
N
S
R E N
O V A T
IO
N S
M A
T R
I X
E10
P A R
T
IA
L F
L O
O R
P L A N
P
O W
E R
D E M
O L
IT
IO
N
A
R E A C
N KEY PLAN
NOT TO SCALE
CU
UV
CONV
1 1
CONV
CONV
CONV
EXIST. PNL
"M"
EXIST. PNL
"L"
EXIST. PNL
"X"
EXIST. PNL
"K"
EXIST. PNL
"J"
EXIST. PNL
"MDP"
9 9
EXISTING EQUIPMENT TO REMAIN.
DISCONNECT AND REMOVE EXISTING EQUIPMENT. ASSOCIATED CONDUIT
AND WIRE TO REMAIN FOR CONNECTION TO NEW EQUIPMENT.
EXISTING LIGHTING CONTROL DEVICE TO REMAIN.
DISCONNECT AND REMOVE EXISTING LIGHT FIXTURES. REMOVE CONDUIT
AND WIRE BACK TO SOURCE.
REMOVE LIGHTING CONTROL DEVICE. REMOVE CONDUIT AND WIRE. PATCH
AND PAINT WALL TO MATCH EXISTING.
DISCONNECT AND REMOVE EXISTING EQUIPMENT. REMOVE CONDUIT AND
WIRE BACK TO SOURCE.
DISCONNECT AND REMOVE EXISTING EQUIPMENT. REMOVE ASSOCIATED
CONDUIT AND WIRE BACK TO SOURCE.
DISCONNECT AND REMOVE EXISTING EQUIPMENT. ASSOCIATED CONDUIT
AND WIRE TO REMAIN FOR CONNECTION TO NEW EQUIPMENT.
DISCONNECT AND REMOVE EXISTING LIGHT FIXTURE FOR CEILING
MODIFICATIONS. REINSTALL IN CEILING WHEN COMPLETE.
DEMOLITION NOTES
SCALE: 1/8" = 1'-0"
0 1 5 10 20
N PARTIAL FLOOR PLAN - POWER DEMOLITION - AREA "D"
J C
IS
D
T O
R R
A N
T C
E N
T E R
A D
D
IT
IO
N
S
R E N
O V A T
IO
N S
M A
T R
I X
E11
P A R
T
IA
L F
L O
O R
P L A N
P
O W
E R
D E M
O L
IT
IO
N
A
R E A D
CONVCONVCONVCONV
F F
CU CU CU CU
1 1 1 1
22 F F 22
22 2 2
EXIST. PNL
"B"
EXIST.
PNL
"DP1A"
EXIST. PNL
"B1"
EXIST. PNL
"B2"
EXIST. PNL
"DP1"
EXISTING EQUIPMENT TO REMAIN.
DISCONNECT AND REMOVE EXISTING EQUIPMENT. ASSOCIATED CONDUIT
AND WIRE TO REMAIN FOR CONNECTION TO NEW EQUIPMENT.
EXISTING LIGHTING CONTROL DEVICE TO REMAIN.
DISCONNECT AND REMOVE EXISTING LIGHT FIXTURES. REMOVE CONDUIT
AND WIRE BACK TO SOURCE.
REMOVE LIGHTING CONTROL DEVICE. REMOVE CONDUIT AND WIRE. PATCH
AND PAINT WALL TO MATCH EXISTING.
DISCONNECT AND REMOVE EXISTING EQUIPMENT. REMOVE CONDUIT AND
WIRE BACK TO SOURCE.
DISCONNECT AND REMOVE EXISTING EQUIPMENT. REMOVE ASSOCIATED
CONDUIT AND WIRE BACK TO SOURCE.
DISCONNECT AND REMOVE EXISTING EQUIPMENT. ASSOCIATED CONDUIT
AND WIRE TO REMAIN FOR CONNECTION TO NEW EQUIPMENT.
DISCONNECT AND REMOVE EXISTING LIGHT FIXTURE FOR CEILING
MODIFICATIONS. REINSTALL IN CEILING WHEN COMPLETE.
DEMOLITION NOTES
SCALE: 1/8" = 1'-0"
0 1 5 10 20
N PARTIAL FLOOR PLAN - POWER DEMOLITION - AREA "F"
J C
IS
D
T O
R R
A N
T C
E N
T E R
A D
D
IT
IO
N
S
R E N
O V A T
IO
N S
M A
T R
I X
E13
P A R
T
IA
L F
L O
O R
P L A N
P
O W
E R
D E M
O L
IT
IO
N
A
R E A F
CU
CU
CONV
F F
F F
CONV
CONV
CONV
CU
EXIST. PNL
"C1"
EXIST. PNL
"C2"
EXIST. PNL
"C"
CU
CU
CU
CU
CONV
F
CONV
CONV
CONV
F
F
F
EXIST. PNL
"D"
EXIST. PNL
"D1"
EXIST. PNL
"D2"
EXISTING EQUIPMENT TO REMAIN.
DISCONNECT AND REMOVE EXISTING EQUIPMENT. ASSOCIATED CONDUIT
AND WIRE TO REMAIN FOR CONNECTION TO NEW EQUIPMENT.
EXISTING LIGHTING CONTROL DEVICE TO REMAIN.
DISCONNECT AND REMOVE EXISTING LIGHT FIXTURES. REMOVE CONDUIT
AND WIRE BACK TO SOURCE.
REMOVE LIGHTING CONTROL DEVICE. REMOVE CONDUIT AND WIRE. PATCH
AND PAINT WALL TO MATCH EXISTING.
DISCONNECT AND REMOVE EXISTING EQUIPMENT. REMOVE CONDUIT AND
WIRE BACK TO SOURCE.
DISCONNECT AND REMOVE EXISTING EQUIPMENT. REMOVE ASSOCIATED
CONDUIT AND WIRE BACK TO SOURCE.
DISCONNECT AND REMOVE EXISTING EQUIPMENT. ASSOCIATED CONDUIT
AND WIRE TO REMAIN FOR CONNECTION TO NEW EQUIPMENT.
DISCONNECT AND REMOVE EXISTING LIGHT FIXTURE FOR CEILING
MODIFICATIONS. REINSTALL IN CEILING WHEN COMPLETE.
DEMOLITION NOTES
SCALE: 1/8" = 1'-0"
0 1 5 10 20
N PARTIAL FLOOR PLAN - POWER DEMOLITION - AREA "G"
J C
IS
D
T O
R R
A N
T C
E N
T E R
A D
D
IT
IO
N
S
R E N
O V A T
IO
N S
M A
T R
I X
E14
P A R
T
IA
L F
L O
O R
P L A N
P
O W
E R
D E M
O L
IT
IO
N
A
R E A G
AHU
AHU
BLR
CUH
EF
CONV CONV CONV CONV CONV CONV
CONVCONV
1 1 1 1 1 1
CONV
EXIST. PNL
"F"
EXIST. PNL
"E"
EXISTING EQUIPMENT TO REMAIN.
DISCONNECT AND REMOVE EXISTING EQUIPMENT. ASSOCIATED CONDUIT
AND WIRE TO REMAIN FOR CONNECTION TO NEW EQUIPMENT.
EXISTING LIGHTING CONTROL DEVICE TO REMAIN.
DISCONNECT AND REMOVE EXISTING LIGHT FIXTURES. REMOVE CONDUIT
AND WIRE BACK TO SOURCE.
REMOVE LIGHTING CONTROL DEVICE. REMOVE CONDUIT AND WIRE. PATCH
AND PAINT WALL TO MATCH EXISTING.
DISCONNECT AND REMOVE EXISTING EQUIPMENT. REMOVE CONDUIT AND
WIRE BACK TO SOURCE.
DISCONNECT AND REMOVE EXISTING EQUIPMENT. REMOVE ASSOCIATED
CONDUIT AND WIRE BACK TO SOURCE.
DISCONNECT AND REMOVE EXISTING EQUIPMENT. ASSOCIATED CONDUIT
AND WIRE TO REMAIN FOR CONNECTION TO NEW EQUIPMENT.
DISCONNECT AND REMOVE EXISTING LIGHT FIXTURE FOR CEILING
MODIFICATIONS. REINSTALL IN CEILING WHEN COMPLETE.
DEMOLITION NOTES
SCALE: 1/8" = 1'-0"
0 1 5 10 20
N
PARTIAL FLOOR PLAN - POWER DEMOLITION - AREA "H" (ALTERNATE)
J C
IS
D
T O
R R
A N
T C
E N
T E R
A D
D
IT
IO
N
S
R E N
O V A T
IO
N S
M A
T R
I X
E15
P A R
T
IA
L F
L O
O R
P L A N
P
O W
E R
D E M
O L
IT
IO
N
A
R E A H
FC-1
208V-1Ø, 1.0A
N-39,41
FED FROM HP-1
CU-5B
208V-1Ø, 15.1MCA
CU-4B
208V-1Ø, 17.5MCA
CU-3B
208V-1Ø, 17.5MCA
UV-3
120V-1Ø, 6.3MCA
UV-4
120V-1Ø, 6.3MCA
UV-5
120V-1Ø, 6.3MCA
UV-6
120V-1Ø, 6.3MCA
UV-7
120V-1Ø, 6.3MCA
CU-7B
208V-1Ø, 15.1MCA
CU-6B
208V-1Ø, 15.1MCA
HP-1
208V-1Ø, 12.0A
N-12
N-14
N-16
WP
WP
WP
N-31,33
WP
N-32,34
WP
A-8
A-16
A-38,40
A-32,34
EXIST. PNL
"DP3"
EXIST. PNL
"N"
NEW PNL
"A"
WP
WP
GFI
N-35
WP
GFI
WP
GFI
WP
GFI
N-42
N-42
WP
GFI
N-36
WP
GFI
A-42
A-36
ELECTRICAL KEY NOTES
CONTRACTOR SHALL PROVIDE AND INSTALL NEW PANEL. MODIFY EXISTING
CONDUIT AND WIRE FOR NEW CONNECTION.
CONTRACTOR SHALL PROVIDE AND INSTALL POWER FOR OWNER PROVIDED
SIGNAGE. VERIFY LOCATION WITH OWNER, PRIOR TO ROUGH-IN.
CONTRACTOR SHALL REUSE EXISTING CONDUIT AND WIRE FOR NEW
EQUIPMENT.
CONTRACTOR SHALL REUSE EXISTING CONDUIT AND WIRE FOR NEW
EQUIPMENT. CONTRACTOR SHALL REMOVE PHASE WIRE FROM PANEL
CONNECTION, FOR USE ON 2-POLE UNIT.
CONTRACTOR SHALL PROVIDE AND INSTALL NEW CONDUIT AND WIRE FOR
NEW EQUIPMENT.
EXHAUST FAN SHALL BE CONTROLLED BY NEW TIMECLOCK. CONFIRM TIME
SCHEDULING WITH OWNER.
REMOVE EXISTING PNEUMATIC INTERLOCK WITHIN STARTER, AND CONNECT
TO NEW CONTROL PANEL FOR CONTROLS.
CONTRACTOR SHALL PROVIDE CIRCUIT TO TRANSFORMER, FOR CONTROL
VALVE POWER.
1. CONTRACTOR SHALL PROVIDE AND INSTALL 4-11/16" DEEP SQUARE BOX WITH 1" CND
AND SINGLE GANG PLASTER RING, STUBBED TO NEAREST CIRCULATION CEILING OR
CABLE TRAY FOR ALL DATA DEVICES.
GENERAL ELECTRICAL NOTES
SCALE: 1/8" = 1'-0"
0 1 5 10 20
N PARTIAL FLOOR PLAN - NEW POWER - AREA "C"
J C
IS
D
T O
R R
A N
T C
E N
T E R
A D
D
IT
IO
N
S
R E N
O V A T
IO
N S
M A
T R
I X
E29
P A R
T
IA
L F
L O
O R
N KEY PLAN
NOT TO SCALE
P L A N
N
E W
P O
W E R
A
R E A C
CONV
CONV
RTU-6
208V-1Ø, 17.0A
J
DOOR OPERATOR
(TYP.)
J-15
J-17
CU-5B
208V-1Ø, 15.1MCA
UV-5
120V-1Ø, 6.3MCA
WP
A-8
A-32,34
J
J-15
WP
EXIST. PNL
"M"
EXIST. PNL
"L"
NEW PNL
"X"
EXIST. PNL
"K"
NEW PNL "J"
NEW PNL
"MDP"
WP
GFI
A-36
WP
EWC
J-16
ELECTRICAL KEY NOTES
CONTRACTOR SHALL PROVIDE AND INSTALL NEW PANEL. MODIFY EXISTING
CONDUIT AND WIRE FOR NEW CONNECTION.
CONTRACTOR SHALL PROVIDE AND INSTALL POWER FOR OWNER PROVIDED
SIGNAGE. VERIFY LOCATION WITH OWNER, PRIOR TO ROUGH-IN.
CONTRACTOR SHALL REUSE EXISTING CONDUIT AND WIRE FOR NEW
EQUIPMENT.
CONTRACTOR SHALL REUSE EXISTING CONDUIT AND WIRE FOR NEW
EQUIPMENT. CONTRACTOR SHALL REMOVE PHASE WIRE FROM PANEL
CONNECTION, FOR USE ON 2-POLE UNIT.
CONTRACTOR SHALL PROVIDE AND INSTALL NEW CONDUIT AND WIRE FOR
NEW EQUIPMENT.
EXHAUST FAN SHALL BE CONTROLLED BY NEW TIMECLOCK. CONFIRM TIME
SCHEDULING WITH OWNER.
REMOVE EXISTING PNEUMATIC INTERLOCK WITHIN STARTER, AND CONNECT
TO NEW CONTROL PANEL FOR CONTROLS.
CONTRACTOR SHALL PROVIDE CIRCUIT TO TRANSFORMER, FOR CONTROL
VALVE POWER.
1. CONTRACTOR SHALL PROVIDE AND INSTALL 4-11/16" DEEP SQUARE BOX WITH 1" CND
AND SINGLE GANG PLASTER RING, STUBBED TO NEAREST CIRCULATION CEILING OR
CABLE TRAY FOR ALL DATA DEVICES.
GENERAL ELECTRICAL NOTES
SCALE: 1/8" = 1'-0"
0 1 5 10 20
N PARTIAL FLOOR PLAN - NEW POWER - AREA "D"
J C
IS
D
T O
R R
A N
T C
E N
T E R
A D
D
IT
IO
N
S
R E N
O V A T
IO
N S
M A
T R
I X
E30
P A R
T
IA
L F
L O
O R
N KEY PLAN
NOT TO SCALE
P L A N
N
E W
P O
W E R
A
R E A D
CONVCONVCONVCONV
CU-3A
208V-1Ø, 13.6A
CU-2A
208V-1Ø, 16.5ACU-1A
208V-1Ø, 16.5A
F-1 120V-1Ø, 11.0A
F-2 120V-1Ø, 11.0A
F-3 120V-1Ø, 8.2A
B2-8,10
B2-2
B1-7,9 B1-8,10
B1-4B1-2
WPWPWP
EXIST. PNL
"B"
EXIST.
PNL
"DP1A"
NEW PNL
"B1"
NEW PNL
"B2"
EXIST. PNL
"DP1"
3 3
WP
GFI
B1-11
J
W-35
1 1
ELECTRICAL KEY NOTES
CONTRACTOR SHALL PROVIDE AND INSTALL NEW PANEL. MODIFY EXISTING
CONDUIT AND WIRE FOR NEW CONNECTION.
CONTRACTOR SHALL PROVIDE AND INSTALL POWER FOR OWNER PROVIDED
SIGNAGE. VERIFY LOCATION WITH OWNER, PRIOR TO ROUGH-IN.
CONTRACTOR SHALL REUSE EXISTING CONDUIT AND WIRE FOR NEW
EQUIPMENT.
CONTRACTOR SHALL REUSE EXISTING CONDUIT AND WIRE FOR NEW
EQUIPMENT. CONTRACTOR SHALL REMOVE PHASE WIRE FROM PANEL
CONNECTION, FOR USE ON 2-POLE UNIT.
CONTRACTOR SHALL PROVIDE AND INSTALL NEW CONDUIT AND WIRE FOR
NEW EQUIPMENT.
EXHAUST FAN SHALL BE CONTROLLED BY NEW TIMECLOCK. CONFIRM TIME
SCHEDULING WITH OWNER.
REMOVE EXISTING PNEUMATIC INTERLOCK WITHIN STARTER, AND CONNECT
TO NEW CONTROL PANEL FOR CONTROLS.
CONTRACTOR SHALL PROVIDE CIRCUIT TO TRANSFORMER, FOR CONTROL
VALVE POWER.
1. CONTRACTOR SHALL PROVIDE AND INSTALL 4-11/16" DEEP SQUARE BOX WITH 1" CND
AND SINGLE GANG PLASTER RING, STUBBED TO NEAREST CIRCULATION CEILING OR
CABLE TRAY FOR ALL DATA DEVICES.
GENERAL ELECTRICAL NOTES
SCALE: 1/8" = 1'-0"
0 1 5 10 20
N PARTIAL FLOOR PLAN - NEW POWER - AREA "F"
J C
IS
D
T O
R R
A N
T C
E N
T E R
A D
D
IT
IO
N
S
R E N
O V A T
IO
N S
M A
T R
I X
E32
P A R
T
IA
L F
L O
O R
N KEY PLAN
NOT TO SCALE
P L A N
N
E W
P O
W E R
A
R E A F
CONV
CONV
CU-5A
208V-1Ø, 17.6A
CU-4A
208V-1Ø, 17.6A
F-5 120V-1Ø, 11.0A
F-4 120V-1Ø, 11.0A
C1-8,10
C1-2
C2-8,10
C2-2
CU-11B
208V-1Ø, 15.1MCA
WP
WP
W-38,40
NEW PNL
"C1"
NEW PNL
"C2"
EXIST. PNL
"C"
WP
GFI
C2-4
CONV
CONV
CONV
CONV
F-7 120V-1Ø, 11.0A
F-6 120V-1Ø, 11.0A
CU-7A
208V-1Ø, 17.6A
CU-6A
208V-1Ø, 17.6A
D1-2
D2-2 D2-8,10
D1-8,10
WP
WP
EXIST. PNL
"D"
NEW PNL
"D1"
NEW PNL
"D2"
WP
GFI
WP
GFI
D2-4
D1-4
ELECTRICAL KEY NOTES
CONTRACTOR SHALL PROVIDE AND INSTALL NEW PANEL. MODIFY EXISTING
CONDUIT AND WIRE FOR NEW CONNECTION.
CONTRACTOR SHALL PROVIDE AND INSTALL POWER FOR OWNER PROVIDED
SIGNAGE. VERIFY LOCATION WITH OWNER, PRIOR TO ROUGH-IN.
CONTRACTOR SHALL REUSE EXISTING CONDUIT AND WIRE FOR NEW
EQUIPMENT.
CONTRACTOR SHALL REUSE EXISTING CONDUIT AND WIRE FOR NEW
EQUIPMENT. CONTRACTOR SHALL REMOVE PHASE WIRE FROM PANEL
CONNECTION, FOR USE ON 2-POLE UNIT.
CONTRACTOR SHALL PROVIDE AND INSTALL NEW CONDUIT AND WIRE FOR
NEW EQUIPMENT.
EXHAUST FAN SHALL BE CONTROLLED BY NEW TIMECLOCK. CONFIRM TIME
SCHEDULING WITH OWNER.
REMOVE EXISTING PNEUMATIC INTERLOCK WITHIN STARTER, AND CONNECT
TO NEW CONTROL PANEL FOR CONTROLS.
CONTRACTOR SHALL PROVIDE CIRCUIT TO TRANSFORMER, FOR CONTROL
VALVE POWER.
1. CONTRACTOR SHALL PROVIDE AND INSTALL 4-11/16" DEEP SQUARE BOX WITH 1" CND
AND SINGLE GANG PLASTER RING, STUBBED TO NEAREST CIRCULATION CEILING OR
CABLE TRAY FOR ALL DATA DEVICES.
GENERAL ELECTRICAL NOTES
SCALE: 1/8" = 1'-0"
0 1 5 10 20
N PARTIAL FLOOR PLAN - NEW POWER - AREA "G"
J C
IS
D
T O
R R
A N
T C
E N
T E R
A D
D
IT
IO
N
S
R E N
O V A T
IO
N S
M A
T R
I X
E33
P A R
T
IA
L F
L O
O R
N KEY PLAN
NOT TO SCALE
P L A N
N
E W
P O
W E R
A
R E A G
CUH
CONV CONV CONV CONV CONV CONV
CONVCONV
CONV
RTU-7
208V-3Ø, 43.0A
ECH-4
208V-1Ø, 1.5KW
ECH-3
208V-1Ø, 3.0KW
ECH-1
208V-1Ø, 3.0KW
ECH-2
208V-1Ø, 1.5KW
DP2-20,22,24
F-24,26
F-28,30
E-30,32
E-38,40
WP
NEW PNL
"F"
NEW PNL
"E"
WP
GFIE-5
1 1
ELECTRICAL KEY NOTES
CONTRACTOR SHALL PROVIDE AND INSTALL NEW PANEL. MODIFY EXISTING
CONDUIT AND WIRE FOR NEW CONNECTION.
1. CONTRACTOR SHALL PROVIDE AND INSTALL 4-11/16" DEEP SQUARE BOX WITH 1" CND
AND SINGLE GANG PLASTER RING, STUBBED TO NEAREST CIRCULATION CEILING OR
CABLE TRAY FOR ALL DATA DEVICES.
GENERAL ELECTRICAL NOTES
SCALE: 1/8" = 1'-0"
0 1 5 10 20
N
PARTIAL FLOOR PLAN - NEW POWER - AREA "H" (ALTERNATE)
J C
IS
D
T O
R R
A N
T C
E N
T E R
A D
D
IT
IO
N
S
R E N
O V A T
IO
N S
M A
T R
I X
E34
P A R
T
IA
L F
L O
O R
N KEY PLAN
NOT TO SCALE
P L A N
N
E W
P O
W E R
A
R E A H
120V-1Ø, 1/15HP
120V-1Ø, 1/15HP
CONTROL PANEL (TYP.)
POOL-7
POOL-9
POOL-8
POOL-10
CU-14B
208V-1Ø, 17.5MCAUV-14
120V-1Ø, 6.3MCA
CH-2
120V-1Ø, 17.5MCA
R-37
WP
V-8
B-2 120V-1Ø, 12.0A
B-1 120V-1Ø, 12.0A
P-1
208V-3Ø, 1.5HP
P-2
208V-3Ø, 1.5HP
J J
J J
T-14,16,18
T-19,21,23
T-33
T-35
P-3 120V-1Ø, 3.0A
P-4 120V-1Ø, 3.0A
EPO
EXIST. PNL
"S"
EXIST. PNL
"T"
EXIST.
POOL "PNL
#1"
EX
EX
J
S-15
J
S-15
J
S-15J
S-15
J
S-15
ELECTRICAL KEY NOTES
CONTRACTOR SHALL PROVIDE AND INSTALL NEW PANEL. MODIFY EXISTING
CONDUIT AND WIRE FOR NEW CONNECTION.
CONTRACTOR SHALL PROVIDE AND INSTALL POWER FOR OWNER PROVIDED
SIGNAGE. VERIFY LOCATION WITH OWNER, PRIOR TO ROUGH-IN.
CONTRACTOR SHALL REUSE EXISTING CONDUIT AND WIRE FOR NEW
EQUIPMENT.
CONTRACTOR SHALL REUSE EXISTING CONDUIT AND WIRE FOR NEW
EQUIPMENT. CONTRACTOR SHALL REMOVE PHASE WIRE FROM PANEL
CONNECTION, FOR USE ON 2-POLE UNIT.
CONTRACTOR SHALL PROVIDE AND INSTALL NEW CONDUIT AND WIRE FOR
NEW EQUIPMENT.
EXHAUST FAN SHALL BE CONTROLLED BY NEW TIMECLOCK. CONFIRM TIME
SCHEDULING WITH OWNER.
REMOVE EXISTING PNEUMATIC INTERLOCK WITHIN STARTER, AND CONNECT
TO NEW CONTROL PANEL FOR CONTROLS.
CONTRACTOR SHALL PROVIDE CIRCUIT TO TRANSFORMER, FOR CONTROL
VALVE POWER.
1. CONTRACTOR SHALL PROVIDE AND INSTALL 4-11/16" DEEP SQUARE BOX WITH 1" CND
AND SINGLE GANG PLASTER RING, STUBBED TO NEAREST CIRCULATION CEILING OR
CABLE TRAY FOR ALL DATA DEVICES.
GENERAL ELECTRICAL NOTES
SCALE: 1/8" = 1'-0"
0 1 5 10 20
N PARTIAL FLOOR PLAN - NEW POWER - AREA "M"
J C
IS
D
T O
R R
A N
T C
E N
T E R
A D
D
IT
IO
N
S
R E N
O V A T
IO
N S
M A
T R
I X
E39
P A R
T
IA
L F
L O
O R
N KEY PLAN
NOT TO SCALE
P L A N
N
E W
P O
W E R
A
R E A M
PHOTO CONTROL,
INTERMATIC
NOTE:
-MOUNT PHOTO EYE FACING NORTH ON NORTH SIDE OF BUILDING.
WITH CLOCK MOTOR, 7-DAY
TIME SWITCH CONTROL
INTERMATIC #T7402BC
CONTROL AND 40 AMP 4 POLE CONTACTS,
N
AREA LIGHTS
2 EXTERIOR LIGHTING CONTROL DETAIL
SCALE: N.T.S.
BUILDING LIGHTSLINE
NEUTRAL
PLAN
ELECTRICAL
COMPOSITE GASKETED BOX,
QUAZITE OR EQUAL
HEAVY DUTY, SKID-RESISTANT COVER,
BOLT-DOWN TYPE, TAMPER RESISTANT
HARDWARE
3" MIN. SAND OR
GRANULAR BACKFILL
1 ELECTRICAL HANDHOLE DETAIL
SCALE:NTS
LIFTING EYE
FINISHED GRADE
UNDISTURBED EARTH
CONDUIT
SECTION
24"
13"
OPEN BOTTOM
BOX EXTENSION
DIVIDER
24" DIAMETER
SONOTUBE
6 LIGHT POLE DETAIL
SCALE: N.T.S.
24"60"
36"
CURB & ROADWAY
SEAL TIGHT HOLE
LIGHT POLE:
ULS POLES #RPSQ-20-5-11-AB-MODBASE/MODAB-DD1-XHH
(20' POLE WITH 2 HH 1-3/8" HOLE) WITH ANCHOR BOLTS
· STEEL POLE: 20' POLE x 5" SQ x 11 GAUGE
· MODBASE/MODAB: 10.5"-11.5" BOLT CIRCLE WITH 3/4"
O.D. ANCHOR BOLTS
· XHH: 15' ABOVE BASE AT 90°
HAND HOLE ON SIDE
OPPOSITE OF ROADWAY
216"
48"
12"
18"
24" DIAMETER GRAY
"CEMETUBE" HDPE WITH BELLED
END
1.75'
(TYP. U.N.O.)
1" CONDUIT OUT OF BOX
INTO POLE BASE
2" CONDUIT IN
12"x12" QUAZITE BOX
(COMMUNICATION)
2" CONDUIT
2" CONDUIT
LIGHT POLE
1.75'
(TYP. U.N.O.)
CURB & GUTTER
PLAN VIEW
24" DIAMETER BASE
1" CONDUIT
FOR COMMUNICATIONS
1" CONDUIT
FOR ELECTRIC
1" SEAL TIGHT WITH 90°
FITTING AT TOP
FOR COMMUNICATIONS
HAND HOLE: QUAZITE #PC1212BA12, 12"x12", 12" DEEP OPEN BOTTOM. PROVIDE
#PC1212CA0012 "COMMUNICATIONS" COVER. INSTALL ENCLOSURE ON 6" GRAVEL BASE.
INSTALL 1" PVC CONDUIT FROM HAND HOLE THROUGH CONCRETE POLE BASE AND
INTO POLE. COMMUNICATION CONDUIT SHALL EXTEND UNINTERRUPTED FROM PVC
CONDUIT TO 90° FITTING AT 17' ABOVE POLE BASE BY MEANS OF SEAL TIGHT FLEXIBLE
CONDUIT. ELECTRICIAN SHALL DRILL HOLE IN 11 GAUGE STEEL FOR FITTING. PAINT
METAL TO PREVENT RUSTING.
HAND HOLE: QUAZITE #PC1212BA12, 12"x12", 12" DEEP OPEN
BOTTOM. PROVIDE #PC1212CA0017 "ELECTRIC" COVER.
INSTALL ENCLOSURE ON 6" GRAVEL BASE. INSTALL POWER IN
1" PVC CONDUIT FROM HAND HOLE THROUGH CONCRETE POLE
BASE AND INTO POLE.
FIXTURE(S) PER SCHEDULE
BASE COVER
GROUND LUG
#6 TW GREEN GRD. WIRE
GROUND ROD/CADWELD
8'-0" x 5/8" GROUND ROD.
PROVIDE IN-LINE WATERPROOF FUSES AS
RECOMMENDED BY LUMINAR MANUFACTURER.
INSTALL NEAR HANDHOLE.
ANCHOR BOLTS FURNISHED
BY MANUFACTURER
RIGID STEEL CONDUIT
STUB-OUT MIN. DEPTH PER
N.E.C. OR SPECS.
PROVIDE DOUBLE NUTS FOR LEVELING OF UNIT (ONE ABOVE,
ONE BELOW BASE FLANGE) GROUT BETWEEN BASE AND
FLANGE. SLOPE TOP TO PREVENT WATER ACCUMULATION.
2'-0"
5' -0
3'
-0
'-0
4 AREA LIGHT - POLE BASE DETAIL
SCALE: N.T.S.
PROVIDE IN-LINE WATER
BY MANUFACTURER
CONNECT GRD. TO POLE
BASE WITH BURNDY #GB4C
HANDHOLE
SIZE AS RECOMMENDED
PROOF FUSES IN CIRCUIT
POLE MANUFACTURER
REBAR (TYP.)
BASE BY E.C.
GRD. ROD CLAMP
8'-0" x 5/8" DIA.
#6 TW GREEN GRD. WIRE
RIGID CONDUIT
GROUND ROD
COPPER CLAD
BASE COVER
LEVELING OF UNIT (ONE ABV. & ONE
TO PREVENT WATER ACCUMULATION.
ANCHOR BOLTS FURNISHED BY
ANCHOR BOLTS TO PROJECT ABOVE TOP
OF BASE. PROVIDE DOUBLE NUTS FOR
BELOW BASE FLANGE). GROUT BETWEEN
CONCRETE BASE & FLANGE. SLOPE TOP
CONDUIT & WIRE AS SPECIFIED
2'-0" 3'
-0
'-0
INSTALL NEAR HANDHOLE
5 PEDESTRIAN LIGHT - POLE BASE DETAIL
SCALE: N.T.S.
CONCRETE SLAB
3" MIN. BELOW SLAB
OR AS REQUIRED FOR
SWEEPS
SCHEDULE 40 PVC CONDUIT
REFER TO SPECS FOR CONDUIT REQUIREMENTS
PVC TO RIGID ADAPTOR
TO TRANSITION FROM UNDERFLOOR
PROVIDE RGC WITH SWEEP
PVC CONDUIT.
COMPACTED
UNDERFLOOR CONDUITS IN
SLAB ON GRADE INSTALLATION
SCALE: N.T.S.
FIXTURE
MOUNTING
HEIGHT
LIGHT ENGINEDESCRIPTION AND COMMENTSTYPE MANUFACTURER CATALOG NO.
LIGHTING FIXTURE SCHEDULE
T5W
2T4W
T4W
T4FT
T2-HSS
T2
SL2
DIMMING INFO
1. ALTERNATE LIGHTING NOT ALLOWED FOR THE FIXTURES LISTED.
FIXTURE SCHEDULE NOTES
GALN-SA2C-740-U-T2-BZ-MS/DIM-L40MCGRAW EDISON AS SHOWN ON
DRAWINGS
EXTERIOR SITE LIGHT WITH 2 LIGHT SQUARES, TYPE 2 OPTICS, INTEGRAL
PHOTOCELL AND MOTION SENSOR, AND BRONZE FINISH. 0-10V
14219 LUMENS
108W, 4000K
LED
GPC-SA1C-740-U-SL2-BZ-MS/DIM-L20MCGRAW EDISON AS SHOWN ON
DRAWINGS
EXTERIOR SITE LIGHT WITH 1 LIGHT SQUARE, TYPE 2 SPILL-CONTROL OPTICS,
INTEGRAL PHOTOCELL AND MOTION SENSOR, AND BRONZE FINISH. 0-10V
7399 LUMENS
59W, 4000K
LED
GALN-SA2C-740-U-T2-BZ-HSS-MS/DIM-L40MCGRAW EDISON AS SHOWN ON
DRAWINGS
EXTERIOR SITE LIGHT WITH 2 LIGHT SQUARES, TYPE 2 OPTICS, HOUSE SIDE
SHIELD, INTEGRAL PHOTOCELL AND MOTION SENSOR, AND BRONZE FINISH. 0-10V
14219 LUMENS
108W, 4000K
LED
GALN-SA6C-740-U-T4FT-BZ-MS/DIM-L40MCGRAW EDISON AS SHOWN ON
DRAWINGS
EXTERIOR SITE LIGHT WITH 6 LIGHT SQUARES, TYPE 4 FORWARD OPTICS,
INTEGRAL PHOTOCELL AND MOTION SENSOR, AND BRONZE FINISH. 0-10V
42558 LUMENS
321W, 4000K
LED
GALN-SA6C-740-U-5WQ-BZ-MS/DIM-L40MCGRAW EDISON AS SHOWN ON
DRAWINGS
EXTERIOR SITE LIGHT WITH 6 LIGHT SQUARES, TYPE 5 WIDE OPTICS, INTEGRAL
PHOTOCELL AND MOTION SENSOR, AND BRONZE FINISH. 0-10V
44560 LUMENS
321W, 4000K
LED
GALN-SA4C-740-U-T4W-BZ-MS/DIM-L40MCGRAW EDISON AS SHOWN ON
DRAWINGS
EXTERIOR SITE LIGHT WITH 4 LIGHT SQUARES, TYPE 4 WIDE OPTICS, INTEGRAL
PHOTOCELL AND MOTION SENSOR, AND BRONZE FINISH. 0-10V
28333 LUMENS
213W, 4000K
LED
(2): GALN-SA6C-740-U-T4FT-BZ-MS/DIM-L40MCGRAW EDISON AS SHOWN ON
DRAWINGS
DOUBLE HEAD EXTERIOR SITE LIGHT WITH 6 LIGHT SQUARES, TYPE 4 FORWARD
OPTICS, INTEGRAL PHOTOCELL AND MOTION SENSOR, AND BRONZE FINISH. 0-10V
85116 LUMENS
642W, 4000K
LED
-PROVIDE ADEQUATE COMPONENTS FOR CIRCUITING SHOWN ON SITE PLAN
J C
IS
D
T O
R R
A N
T C
E N
T E R
A D
D
IT
IO
N
S
R E N
O V A T
IO
N S
M A
T R
I X
E42
E L E C
T R
IC
A L
S
IT
E D
E T A
IL
S
ELECTRICAL KEY NOTES
CONTRACTOR SHALL REPLACE EXISTING 30A 3P BREAKER WITH NEW 50A 3P
BREAKER TO SERVE NEW ROOFTOP UNIT.
CONTRACTOR SHALL REPLACE EXISTING 50A 3P BREAKER WITH NEW 40A 3P
BREAKER TO SERVE NEW ROOFTOP UNIT.
LOAD SUMMARY
REMOVED LOAD: 14411W
ADDED LOAD: 6778W
NET LOAD: (7633)W
LOAD SUMMARY
REMOVED LOAD: 62623W
ADDED LOAD: 63342W
NET LOAD: 719W
J C
IS
D
T O
R R
A N
T C
E N
T E R
A D
D
IT
IO
N
S
R E N
O V A T
IO
N S
M A
T R
I X
E45
P A N
E L S
C H
E D
U L E S
E L E C
T R
IC
A L
CONTRACTOR SHALL REPLACE EXISTING 20A 1P BREAKER WITH NEW 15A 1P
BREAKER TO SERVE NEW FURNACE.
CONTRACTOR SHALL REPLACE EXISTING 30A 3P BREAKER WITH (1) NEW 25A
2P BREAKER AND (1) NEW 20A 1P BREAKER TO SERVE NEW CONDENSING
UNIT.
2 2
LOAD SUMMARY
REMOVED LOAD: 21133W
ADDED LOAD: 7604W
NET LOAD: (135293)W
J C
IS
D
T O
R R
A N
T C
E N
T E R
A D
D
IT
IO
N
S
R E N
O V A T
IO
N S
M A
T R
I X
E46
P A N
E L S
C H
E D
U L E S
E L E C
T R
IC
BREAKER TO SERVE NEW FURNACE.
CONTRACTOR SHALL REPLACE EXISTING 30A 2P BREAKER WITH NEW 20A 2P
BREAKER TO SERVE NEW CONDENSING UNIT.
LOAD SUMMARY
REMOVED LOAD: 10566W
ADDED LOAD: 3052W
NET LOAD: (7514)W
J C
IS
D
T O
R R
A N
T C
E N
T E R
A D
D
IT
IO
N
S
R E N
O V A T
IO
N S
M A
T R
I X
E47
P A N
E L S
C H
E D
U L E S
E L E C
T R
IC
BREAKER TO SERVE NEW FURNACE.
LOAD SUMMARY
REMOVED LOAD: 6912W
ADDED LOAD: 3986W
NET LOAD: (2926)W
LOAD SUMMARY
REMOVED LOAD: 6912W
ADDED LOAD: 3986W
NET LOAD: (2926)W
J C
IS
D
T O
R R
A N
T C
E N
T E R
A D
D
IT
IO
N
S
R E N
O V A T
IO
N S
M A
T R
I X
E48
P A N
E L S
C H
E D
U L E S
E L E C
T R
IC
BREAKER TO SERVE NEW FURNACE.
LOAD SUMMARY
REMOVED LOAD: 6912W
ADDED LOAD: 3986W
NET LOAD: (2926)W
LOAD SUMMARY
REMOVED LOAD: 6912W
ADDED LOAD: 3986W
NET LOAD: (2926)W
J C
IS
D
T O
R R
A N
T C
E N
T E R
A D
D
IT
IO
N
S
R E N
O V A T
IO
N S
M A
T R
I X
E49
P A N
E L S
C H
E D
U L E S
E L E C
T R
IC
CONTRACTOR SHALL REPLACE EXISTING 30A 2P BREAKER WITH NEW 20A 2P
BREAKER TO SERVE NEW ELECTRIC CABINET UNIT HEATER.
CONTRACTOR SHALL INSTALL WITH NEW 20A 2P BREAKER TO SERVE NEW
ELECTRIC CABINET UNIT HEATER.
J C
IS
D
T O
R R
A N
T C
E N
T E R
A D
D
IT
IO
N
S
R E N
O V A T
IO
N S
M A
T R
I X
E52
P A N
E L S
C H
E D
U L E S
E L E C
T R
IC
CONTRACTOR TO VERIFY EXISTING BREAKER SIZE. SERVE NEW ROOFTOP
UNIT WITH 25A 2P BREAKER.
J C
IS
D
T O
R R
A N
T C
E N
T E R
A D
D
IT
IO
N
S
R E N
O V A T
IO
N S
M A
T R
I X
E53
P A N
E L S
C H
E D
U L E S
E L E C
T R
IC
J C
IS
D
T O
R R
A N
T C
E N
T E R
A D
D
IT
IO
N
S
R E N
O V A T
IO
N S
M A
T R
I X
E58
P A N
E L S
C H
E D
U L E S
E L E C
T R
IC
| Sheets and Views |
| E10-25072200-E300C-24x36 |
| E11-25072200-E300D-24x36 |
| E13-25072200-E300F-24x36 |
| E14-25072200-E300G-24x36 |
| E15-25072200-E300H-24x36 |
| E29-25072200-E500C-24x36 |
| E30-25072200-E500D-24x36 |
| E32-25072200-E500F-24x36 |
| E33-25072200-E500G-24x36 |
| E34-25072200-E500H-24x36 |
| 250722.00 - Bulletin 2 - Electrical2 |
| E39-25072200-E500M-24x36 |
| E45-25072200-E900-24x36 |
| E46-25072200-E901-24x36 |
| E47-25072200-E902-24x36 |
| E48-25072200-E903-24x36 |
| E49-25072200-E904-24x36 |
| E52-25072200-E907-24x36 |
| E53-25072200-E908-24x36 |
| E58-25072200-E913-24x36 |
E42-25072200-E800-24x36
File details come from the government source that posted it. Updated .