Addendum #4 Summary – Floyd County Law Enforcement Center Renovation RFP #26-003
Addendum #4 is a pre-bid clarification document issued by Floyd County, Georgia Purchasing Department on March 5, 2026, for RFP #26-003 concerning the Law Enforcement Center Renovation project. The project involves comprehensive renovation of an existing three-story office building located at 5 Government Plaza, Rome, Georgia, totaling approximately 59,000 gross square feet with 18,013 square feet designated for renovation work. The scope includes updating office spaces with new gypsum walls, light fixtures, and floor finishes; creating a new courtroom to replace existing assembly space; adding public restrooms to the second and third-floor lobbies; constructing a holding cell adjacent to the Sheriff's Office; installing a new stretcher-complaint elevator in the entry lobby; updating mechanical, lighting, and electrical systems; and installing a new storefront entry door on the north side of the first floor. The building remains classified as Type IIB construction with Business and Assembly (A-3) occupancies under the 2018 International Building Code.
Addendum #4 provides critical clarifications and updates to the construction documents, including revised architectural plans, partition type schedules, finish specifications, door and signage schedules, and HVAC renovation plans for the second and third floors. Key clarifications specify that contractors are not required to use listed subcontractors; that pages 611–619 of Section 28-2000 VIDEO SURVEILLANCE from the Project Manual should be omitted; that holding cell benches must be DDS Detention Bed 7504L/R-M5 powder coated units; and that holding cells must be entirely tamper-proof and ligature-free. The addendum includes detailed acoustic transfer grille specifications, revised wall partition modifiers for height changes, updated finish schedules with specific material selections (including Patcraft luxury vinyl tile and Tarkett carpet tile options), and comprehensive HVAC renovation details requiring coordination with existing controls through Control Concepts Inc. The addendum confirms the building will remain operational during construction, with the 911 call center and essential data lines requiring continuous maintenance throughout the project duration.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 26_003 LAW ENFORCEMENT CENTER RENOVATIONS _ F.pdf | ||
| ADDENDUM _3.pdf | ||
| ADDENDUM _1.pdf | ||
| Pre_Bid Sign_in Sheet _ Floyd County LEC Reno.pdf | ||
| ADDENDUM _2.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Twelve East Fourth Ave. Suite 106 ♦ ROME, GEORGIA 30161
PHONE (706) 291-5118
FLOYD COUNTY, GEORGIA
PURCHASING
TO: All Prospective Bidders: RFP #26-003 – “Law Enforcement Center Renovation”
FROM: Randy E. Self, Purchasing Director
SUBJECT: Clarification
DATE: March 5, 2026
RE: Addendum #2, Question #9
• The contractor is not required to use the subcontractors listed.
Please omit the last pages of section 28-2000 VIDEO SURVEILLANCE (pages 611-619, section 28 2000-10-18) from the Project Manual. See below for starting page (p.611) to be omitted.
RANDY E. SELF AMANDA JENKINS SHARON PASLEY
PURCHASING DIRECTOR PURCHASING AGENT PURCHASING AGENT
ADDENDUM #4
Twelve East Fourth Ave. Suite 106 ♦ ROME, GEORGIA 30161
PHONE (706) 291-5118
Additionally, please review the following updated information & drawings.
Thank you, Randy E. Self
Randy E. Self, Purchasing Director
Floyd County Board of Commissioners angelk Text Box
HOLDING CELL TOILET SPEC
Amanda Jenkins Highlight
Amanda Jenkins Highlight
Amanda Jenkins Highlight
Amanda Jenkins Highlight
Amanda Jenkins Highlight
Amanda Jenkins Highlight
01234 843 303 • sales@rcmproducts.co.uk • www.rcmproducts.co.uk
ACOUSTIC TRANSFER GRILLE - ATG
DESCRIPTION & FEATURES
Acoustic transfer grilles (ATG) are suitable for use in doors and partitions where ventilation and reduction in noise transfer or cross-talk from one area to another is required. The channel sections are internally lined with acoustic media.
ATG/F is complete with single mounting fl ange. ATG/BF complete with mounting fl ange plus loose telescopic rear fl ange to suit minimum 42mm to 110mm thickness door or partition.
Standard fi nish is RAL9010 or polyester powder coated to the customers colour requirement.
ATG ORDERING CODE
Series ATG
Core F - c/w Flange (one sided) BF - c/w Backing Flange (double sided)
Fixing F0 - No fi xings F1 - CSK Flange Fixing Holes
Finish
1 - (Mill Finish) 2 - RAL9006 (Silver/Grey) 3 - RAL9010 (White) 4 - RAL9005 (Black) 5 - RAL9003 (White) 6 - RAL9016 (White), 7 - Other RAL/BS Code (additional costs may apply)
8 - Chrome Finish - Powder Coated Example: ATG/BF/F1/3/Nominal Opening Size
Please refer to Performance Data for available standard sizes.
Other sizes/depths may be available upon request.
ATG PERFORMANCE DATA
Air Vol
(l/s) Size
(W x H) P.Drop
(Pa)
325 x 205
40 27 50 45
325 x 285
40 15 50 27 60 32 70 40 80 45
Air Vol (l/s)
Size (W x H)
P.Drop (Pa)
425 x 365
50 12 60 14 70 17 80 20 90 25
100 30 110 33 120 35 130 38 140 42 150 45
Air Vol (l/s)
Size (W x H)
P.Drop (Pa)
425 x 445
80 12 90 14
100 16 110 18 120 20 130 22 140 25 150 28 160 30 170 32 180 35 190 37 200 40 210 42 220 44 230 46
Frequency (Hz) 63 125 250 500 1000 2000 4000 8000 Transmission Loss (dB) 2 3 3 5 7 11 13 18
Overall Nom A+57
Opening Size
P 1.
8.
R
A
TG
A co us ti c
Tr an sf er
G ri lle
A
TG
angelk
TRANSFER GRILL SPEC
DN
DN
DN
1 1.9 2 3 4 5 5.5 6 6.2 6.4 7 7.5 7.9 8 8.3 8.5 8.8 9
A
AV
AX
AZZ
AZ
B
BX
C
CX
D
E
AW
SHERIFF
OFFICE
HOLDING
254A
COPY/PRINT/DOCUMENT
ASSEMBLY
LOBBY
STAIR
MEN'S RR
UP
DOWN
DOWN
HOLDING
254B
COURTROOM
SEATING
259B
ALIGN
ALIGN
A210
OFFICE
PUBLIC DEF.
STORAGE
CORRIDOR
ATTORNEY
MTG.
EQUIPMENT
STORAGE
PROBATION
CORRIDOR
RECEPTION
DEP. CLERK
DEP. CLERK
DEP. CLERK
CLERK
PROBATION
PROBATION
ATTORNEY
MTG
WOMEN'S
RR
WOMEN
MEN
JANITOR
OFFICE
ATTORNEY
MTG
COMMUNICATION
ROOM
BREAK
ROOM
SUPPLY
EQUIPMENT
SUPERVISOR
CONFERENCE
DIRECTORDIRECTOR
SECRETARY
CLOSET
CLOSET
TOILET
TOILET
OFFICE
LOBBY
OFFICE
OFFICE OFFICE OFFICE
ELECT.
TELEPHONE
/DATA
235A
BREAKROOM
STOR.
SHERIFF
BULLPEN
246A
STORAGE OFFICE
CORRIDOR
ELEVATOR
STAIR
BREAK
ROOM
CORRIDOR
CONFERENCE
ROOM
OFFICE
OFFICE
OFFICE
A400
A400
254A 254B
256A
256B
251B
251A
259A
E204
E263 E264
E272
E271
E265
E257
E282 E281 E280 E279 E278 E277 E276 E275 E274
E273
STORAGE
E258
SHERIFF
SUPERVISOR
246B
A510
0S478
0M758A
0M758A
0S478
0S478S
/2
A210
1M1034NOT IN SCOPE
NOT IN SCOPE
0M758A
17'-7"2" 2"
7'-6" 0F414S A402
ALIGN
A L
IG
N
0S478S
EQ EQ
13'-2"
259C
1X414A
2X434A
5'-3"
15'-6 1/2" 0 S
F
A
F
A
F
A
1F478A
S
A
F
A
S
0S478
0C658S
0S478
0S478S
0S478S
0S478S
8'-0"
0M1914
259B E205
34H
42H
NOTE: 911 CALL CENTER TO REMAIN OPERATIONAL
FOR DURATION OF DEMOLITION & CONSTRUCTION
NOTE: MAINTAIN ESSENTIAL DATA LINES &
CONNECTIONS FOR DURATION OF DEMOLITION &
CONSTRUCTION (TO BE COORDINATED W/ OWNER)
6' - 6 1/2"
G400
0S478S
F
S
A401
11' - 3 1/2"
/2 "9' - 6"
" 3' - 5"
A570
9"
INSTALL
ACCESS
DOOR
C R
C R
CR C
R
C R
CR
C R
CR
C R
C R
A210
COURTROOM
259A
C R
C R
C R
C R
CR
11' - 3"
4' - 8"
E232
E233
E267
5' - 3 1/2"
/2
A101
CR
CR
E261
0F414S
0F414S
0F414S
0F414S
0F414S
A210
1. CORRIDOR PARTITIONS, SMOKESTOP PARTITIONS, HORIZONTAL EXIT
PARTITIONS, EXIT ENCLOSURES, AND FIRE WALLS SHALL BE
EFFECTIVELY AND PERMANENTLY IDENTIFIED WITH SIGNS OR
STENCILING ABOVE ANY DECORATIVE CEILING AND / OR IN CONCEALED
SPACE WITH LETTERS "A" MINIMUM OF TWO INCHES HIGH ON A
CONTRASTING BACKGROUND SPACED A MAXIMUM OF TWELVE FEET ON
CENTER WITH A MINIMUM OF ONE PER WALL OR BARRIER. THE HOURLY
FIRE RATING SHALL BE INCLUDED ON ALL RATED BARRIER OR WALLS.
SUGGESTED WORDING ( ) HOUR -- FIRE AND SMOKE BARRIER-PROTECT
ALL OPENINGS.
2. ALL VERTICAL PIPING EXPOSED IN ROOMS SHALL BE FURRED WITH
SAME MATERIAL AS ADJACENT WALLS. EXCEPTIONS ARE: MECHANICAL
ROOMS, ELECTRICAL ROOMS, TELEPHONE ROOMS.
3. METAL STUD PARTITIONS BEHIND ALL PLUMBING AND OTHER FIXTURES
SHALL BE BRACED TO STRUCTURE WHERE REQUIRED TO SUPPORT THE
EQUIPMENT PROVIDED.
4. DO NOT SCALE DRAWINGS. ALL DIMENSIONS AND CONDITIONS
INDICATED IN THESE DOCUMENTS MUST BE FIELD VERIFIED PRIOR TO
CONSTRUCTION. FOR DIMENSIONS NOT SHOWN OR IN QUESTION,
CONTRACTOR SHALL REQUEST CLARIFICATION FROM ARCHITECT
BEFORE PROCEEDING.
5. ANY DAMAGE INCURRED DURING CONSTRUCTION SHALL BE FULLY
REPLACED.
6. NEW GYPSUM BOARD CONSTRUCTION MEETING EXISTING GYPSUM
BOARD CONSTRUCTION IN THE SAME SHALL BE FLUSH WITH NO
VISIBLE JOINTS SHOWING.
7. PROVIDE COAT HOOK BEHIND DOORS IN ALL PRIVATE OFFICES, SINGLE
HOOK TYPE.
8. DO NOT SCALE DRAWINGS - USE DIMENSIONS ONLY.
9. UNLESS OTHERWISE NOTED, INTERIOR PARTITION DIMENSIONS ARE
GIVEN FACE OF FINISH SURFACE TO FACE OF FINISH SURFACE.
10. ELECTRIC PANELS, ALARM BOXES, FIRE EQUIPMENT CABINETS AND
OTHER RECESSED BOXES GREATER THAN 16 SQUARE INCHES THAT
ARE LOCATED IN RATED WALLS SHALL BE BACKED BY GYPSUM
WALLBOARD LAYERS SUFFICIENT TO MAINTAIN THE DESIGNATED
RATING.
11. ALL EXISTING WORK, FURNISHINGS, EQUIPMENT OR MATERIAL TO
REMAIN THAT ARE DAMAGED BY CONTRACTOR'S OPERATION UNDER
THIS CONTRACT SHALL BE RECTIFIED OR REPAIRED AT NO
ADDITIONAL COST TO OWNER.
12. ALL PARTITIONS SHOWN AS 3 5/8" METAL STUDS U.N.O.. GENERAL
CONTRACTOR SHALL COORDINATE ACTUAL SIZE, GAUGE AND
SPACING OF METAL STUDS FOR ALL CONDITIONS.
13. CEILING ACCESS PANELS SHALL BE PROVIDED IN NON-ACCESSABLE
CEILING BELOW THE FOLLOWING MECHANICAL AND PLUMBING
DEVICES:
A. VALVES
B. FLOW MEASURING DEVICES
C. MIXING BOXES
D. POWER OPERATED DAMPERS
E. ACCESS PANELS IN DUCTWORK
F. VOLUME AND BALANCING DEVICES
G. WATER FLOW SWITCHES
H. SPRINKLER SYSTEM DRAINS AND TEST CONNECTIONS
I. PRESSURE SWITCHES
14. ALL FURNITURE BY OTHERS; NOT IN CONTRACT (N.I.C.) U.N.O.
15. ALL GYPSUM BOARD SHALL BE 5/8" THICK; PROVIDE CORNER
REINFORCEMENT AT ALL EXPOSED OUTSIDE CORNERS. EXCEPTION -
GYPSUM BOARD MAY BE ALTERNATE THICKNESS AT CONDITIONS
REQUIRING NEW CONSTRUCTION TO BE FLUSH WITH EXISTING.
16. PROVIDE SOLID WOOD BLOCKING INSIDE PARTITIONS FOR SECURING
WALL HUNG CABINETS/MILLWORK, SHELVING AND WALL HUNG
ACCESSORIES.
17. ALL DRYWALL FINISH WORK TO BE FINISH LEVEL 4, U.N.O.
18. ALL INTERIOR PARTITIONS TO BE TYPE 0S478, U.N.O.
19. ALL ANGLES ARE 90 DEGREES, U.N.O.
20. WHEN DIFFERENT PARTITION TYPES ARE LOCATED ADJACENT TO ONE
ANOTHER, THE FINISHED FACES OF THE PARTITIONS SHALL BE ALIGNED
AND FLUSH, U.N.O.
21. LOCATE EDGE OF DOOR OPENINGS 6" FROM INSIDE FACE OF ADJACENT
PARTITION, U.N.O.
22. CONTRACTOR TO PATCH ALL HOLES, SAND AND PAINT ALL WALLS
WITHIN SCOPE.
EXISTING CONSTRUCTION TO REMAIN
NEW PARTITION
NEW PARTITION (MASONRY)
A210
A402
A402
/2
10"
3' - 4"3' - 4"
5' - 1 1/2"
25' - 9"
4' - 8 1/2"
/2
/2
9' - 2" 5' - 7"8' - 7"
/2
/2
5' - 2 1/2"6
9' - 6" 1' - 4 1/2"
/2
/2
4' - 7 1/2"
6' - 11"
9' - 1 1/2"
A210
SCALE
DATE:
DRAWN BY:
CHECKED BY:
PROJECT #
THIS DRAWING IS AN INSTRUMENT OF
SERVICE AND SHALL REMAIN THE
PROPERTY OF THE ARCHITECT. NO
PART OF THIS DOCUMENT SHALL BE
REPRODUCED OR TRANSMITTED IN
ANY FORM, ELECTRONICALLY OR
MECHANICALLY, FOR ANY PURPOSE,
WITHOUT THE EXPRESS WRITTEN
PERMISSION OF THE ARCHITECT.
M A
R
IE
T T
A S
T R
E E
T
N W
U
N
IT
A
T L
A N
T A
G
E O
R G
IA
T
F w w w .s iz e m o re g ro u p
.c o m
S
IZ
E M
O R
E G
R O
U P
12/12/25
As indicated
12/15/2025 4:08:56 PMAutodesk Docs://24260FLOLEC_Floyd_County_Law_Enforcement_Center/24260SLOYLEC_Floyd_County_LEC.rvt
A101
OVERALL
PROPOSED
FLOOR PLANS –
2ND FLOOR
SMG
IDV
12/12/25
24260FLOLEC
F L
O Y
D C
O U
N T
Y L
E C
R E
N O
V A
T
IO
N
G O
V E
R N
M E
N T
P L
A Z
A R
O M
E
G A
100% CONSTRUCTION DOCUMENTS
1/8" = 1'-0"A101
1 PROPOSED FLOOR PLANS - 2ND FLOOR
N
0 40' 60' 80'20'
Graphic Scale: 1 inch = 20 feet
GENERAL NOTES
LEGEND
3/16" = 1'-0"A101
2 COURTROOM - ENLARGED PLAN
N o
D
E S
C R
IP
T
IO
N
D A
T E wproudfo Rectangle wproudfo Rectangle wproudfo Line wproudfo Line wproudfo PolyLine wproudfo Rectangle wproudfo Rectangle wproudfo Rectangle wproudfo Line wproudfo PolyLine wproudfo Line angelk
FOR REFERENCE: WALLS HIGHLIGHTED IN RED TO GO TO DECK (REFER TO DRAWING REVISIONS)
UP
1 1.9 2 3 4 5 5.5 6 6.2 6.4 7 7.5 7.9 8 8.3 8.5 8.8 9
A
AV
AX
AZZ
AZ
B
BX
C
CX
D
E
AW
MEN'S RR
STAIRS
UP
DOWN
DOWN
5"
FILE ROOM
SUPPLY
NOT IN SCOPE
NOT IN SCOPE
A211
FILE/VAULT
SUPPLY/STORAGE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
ELECTRICAL
373A
JANITOR
303A
WOMEN'S
RR
OFFICE
WORKSPACE
/ COUNTER
MEN
WOMEN
CHASE
JANITOR
WORKSPACE/COUNTER
OFFICE
OFFICE OFFICE OFFICE OFFICE
OFFICE
CONFERENCE
OFFICE
OFFICE
CONFERENCE OFFICE
A2112
A211
A211
WORKSPACE
A211
A210
E304
367A
E306
353 354 355 356
373A
E373C
373B
E360 E361 E362
CORRIDOR
A510
A21110
3' - 6" 24' - 9"
4'
6" 1'
1'
"4'
7"
0S478
0F414
0F414
F
0F414
0S478
A211
A211 11
1M758A 1M1034
1M758A
A211
A211 8
13' - 5 1/2"
2' - 3"
14' - 3"
14' - 9"
A400
S
S
/2
.0
A L
IG
N
ALIGN
2' - 4"
A500
3A500
INFILL WALL OPENINGS
9'-3"
5'-0"
2'-8 1/2"
0S478
0S478
0S478
S
0S478S
S
S
S
S
0S478S
0S478S
26' - 9"
/2
S
A500
MIN.
1' - 6"
OFFICE
STORAGE
3' - 0"
ALIGN
ALIGN
367B
E375
E376
E377
ALIGN
A500
F
A500
A500
A500
A211
0M758SW 0M758SW
(1'-6'' MIN.)
1' - 8"
34H
42H
5' - 4 1/2"
W01
W02
W03
W02
W04
0S478S
0C658S
S
S
0S478S
0C658S
NOTE: MAINTAIN ESSENTIAL DATA LINES &
CONNECTIONS FOR DURATION OF DEMOLITION &
CONSTRUCTION (TO BE COORDINATED W/ OWNER)
/2
/2
S
C R
CR
CR
C R
CR
C R
C R
C R
ELEC.
TELEPHONE
DATA
329A
BREAKROOM
OFFICESTORAGE
STORAGE
STORAGE OFFICE BREAKROOM STORAGE
WOMEN'S
LOCKERS EVIDENCE
STAIRS
4' - 6" 4' - 4 1/2"
W02
3' - 1"
/2
/2
1' - 1"
/2
C R
CR
E326
301301
FEC
1. CORRIDOR PARTITIONS, SMOKESTOP PARTITIONS, HORIZONTAL EXIT
PARTITIONS, EXIT ENCLOSURES, AND FIRE WALLS SHALL BE
EFFECTIVELY AND PERMANENTLY IDENTIFIED WITH SIGNS OR
STENCILING ABOVE ANY DECORATIVE CEILING AND / OR IN CONCEALED
SPACE WITH LETTERS "A" MINIMUM OF TWO INCHES HIGH ON A
CONTRASTING BACKGROUND SPACED A MAXIMUM OF TWELVE FEET ON
CENTER WITH A MINIMUM OF ONE PER WALL OR BARRIER. THE HOURLY
FIRE RATING SHALL BE INCLUDED ON ALL RATED BARRIER OR WALLS.
SUGGESTED WORDING ( ) HOUR -- FIRE AND SMOKE BARRIER-PROTECT
ALL OPENINGS.
2. ALL VERTICAL PIPING EXPOSED IN ROOMS SHALL BE FURRED WITH
SAME MATERIAL AS ADJACENT WALLS. EXCEPTIONS ARE: MECHANICAL
ROOMS, ELECTRICAL ROOMS, TELEPHONE ROOMS.
3. METAL STUD PARTITIONS BEHIND ALL PLUMBING AND OTHER FIXTURES
SHALL BE BRACED TO STRUCTURE WHERE REQUIRED TO SUPPORT THE
EQUIPMENT PROVIDED.
4. DO NOT SCALE DRAWINGS. ALL DIMENSIONS AND CONDITIONS
INDICATED IN THESE DOCUMENTS MUST BE FIELD VERIFIED PRIOR TO
CONSTRUCTION. FOR DIMENSIONS NOT SHOWN OR IN QUESTION,
6. NEW GYPSUM BOARD CONSTRUCTION MEETING EXISTING GYPSUM
BOARD CONSTRUCTION IN THE SAME SHALL BE FLUSH WITH NO
VISIBLE JOINTS SHOWING.
7. PROVIDE COAT HOOK BEHIND DOORS IN ALL PRIVATE OFFICES, SINGLE
HOOK TYPE.
8. DO NOT SCALE DRAWINGS - USE DIMENSIONS ONLY.
9. UNLESS OTHERWISE NOTED, INTERIOR PARTITION DIMENSIONS ARE
GIVEN FACE OF FINISH SURFACE TO FACE OF FINISH SURFACE.
10. ELECTRIC PANELS, ALARM BOXES, FIRE EQUIPMENT CABINETS AND
OTHER RECESSED BOXES GREATER THAN 16 SQUARE INCHES THAT
ARE LOCATED IN RATED WALLS SHALL BE BACKED BY GYPSUM
WALLBOARD LAYERS SUFFICIENT TO MAINTAIN THE DESIGNATED
RATING.
11. ALL EXISTING WORK, FURNISHINGS, EQUIPMENT OR MATERIAL TO
REMAIN THAT ARE DAMAGED BY CONTRACTOR'S OPERATION UNDER
SPACING OF METAL STUDS FOR ALL CONDITIONS.
13. CEILING ACCESS PANELS SHALL BE PROVIDED IN NON-ACCESSABLE
C. MIXING BOXES
D. POWER OPERATED DAMPERS
E. ACCESS PANELS IN DUCTWORK
F. VOLUME AND BALANCING DEVICES
G. WATER FLOW SWITCHES
H. SPRINKLER SYSTEM DRAINS AND TEST CONNECTIONS
I. PRESSURE SWITCHES
14. ALL FURNITURE BY OTHERS; NOT IN CONTRACT (N.I.C.) U.N.O.
15. ALL GYPSUM BOARD SHALL BE 5/8" THICK; PROVIDE CORNER
REINFORCEMENT AT ALL EXPOSED OUTSIDE CORNERS. EXCEPTION -
GYPSUM BOARD MAY BE ALTERNATE THICKNESS AT CONDITIONS
REQUIRING NEW CONSTRUCTION TO BE FLUSH WITH EXISTING.
16. PROVIDE SOLID WOOD BLOCKING INSIDE PARTITIONS FOR SECURING
WALL HUNG CABINETS/MILLWORK, SHELVING AND WALL HUNG
ACCESSORIES.
17. ALL DRYWALL FINISH WORK TO BE FINISH LEVEL 4, U.N.O.
18. ALL INTERIOR PARTITIONS TO BE TYPE 0S478, U.N.O.
19. ALL ANGLES ARE 90 DEGREES, U.N.O.
20. WHEN DIFFERENT PARTITION TYPES ARE LOCATED ADJACENT TO ONE
ANOTHER, THE FINISHED FACES OF THE PARTITIONS SHALL BE ALIGNED
AND FLUSH, U.N.O.
21. LOCATE EDGE OF DOOR OPENINGS 6" FROM INSIDE FACE OF ADJACENT
PARTITION, U.N.O.
22. CONTRACTOR TO PATCH ALL HOLES, SAND AND PAINT ALL WALLS
WITHIN SCOPE.
EXISTING CONSTRUCTION TO REMAIN
NEW PARTITION
NEW PARTITION (MASONRY)
SCALE
DATE:
DRAWN BY:
CHECKED BY:
PROJECT #
THIS DRAWING IS AN INSTRUMENT OF
SERVICE AND SHALL REMAIN THE
PROPERTY OF THE ARCHITECT. NO
PART OF THIS DOCUMENT SHALL BE
REPRODUCED OR TRANSMITTED IN
ANY FORM, ELECTRONICALLY OR
MECHANICALLY, FOR ANY PURPOSE,
WITHOUT THE EXPRESS WRITTEN
PERMISSION OF THE ARCHITECT.
M A
R
IE
T T
A S
T R
E E
T
N W
U
N
IT
A
T L
A N
T A
G
E O
R G
IA
T
F w w w .s iz e m o re g ro u p
.c o m
S
IZ
E M
O R
E G
R O
U P
12/12/25
1/8" = 1'-0"
12/15/2025 4:08:58 PMAutodesk Docs://24260FLOLEC_Floyd_County_Law_Enforcement_Center/24260SLOYLEC_Floyd_County_LEC.rvt
A102
OVERALL
PROPOSED
FLOOR PLANS –
3RD FLOOR
SMG
IDV
12/12/25
24260FLOLEC
F L
O Y
D C
O U
N T
Y L
E C
R E
N O
V A
T
IO
N
G O
V E
R N
M E
N T
P L
A Z
A R
O M
E
G A
100% CONSTRUCTION DOCUMENTS
1/8" = 1'-0"A102
1 PROPOSED FLOOR PLANS - 3RD FLOOR
N
0 40' 60' 80'20'
Graphic Scale: 1 inch = 20 feet
GENERAL NOTES
CR
CR
LEGEND
N o
D
E S
C R
IP
T
IO
N
D A
T E wproudfo PolyLine wproudfo PolyLine angelk
FOR REFERENCE: WALLS HIGHLIGHTED IN RED TO GO TO DECK (REFER TO DRAWING REVISIONS)
Revision Narrative
SIZEMORE GROUP
5 GOVERNMENT PLAZA 342 Marietta St. NW, Unit 3 ROME, GA 30161 Atlanta, GA 30313
SHEET NUMBER SHEET NAME DESCRIPTION
G000 COVER SHEET ADDED ADD ALTERNATE: "ACOUSTICAL WALL PANELS IN COURTROOM" PREVIOUSLY LISTED ON FINISH SHEETS G400 PARTITION TYPES UPDATED WALL PARTITION MODIFIERS AND SCHEDULES FOR WALL HEIGHT CHANGES
A100 OVERALL PROPOSED FLOOR PLANS 1ST FLOOR ADDED GENERAL NOTE FOR CLARIFICATION
A101 OVERALL PROPOSED FLOOR PLANS 2ND FLOOR UPDATED WALL TAGS TO LABEL WALLS THAT ARE TO GO TO UNDERSIDE OF DECK
ADDED ELEVATION TAG FOR 267 RECEPTION DESK (ELEVATION PREVIOUSLY SHOWN ON ELEVATION SHEET)
ADDED GENERAL NOTES FOR CLARIFICATION
A102 OVERALL PROPOSED FLOOR PLANS 3RD FLOOR UPDATED WALL TAGS TO LABEL WALLS THAT ARE TO GO TO UNDERSIDE OF DECK
ADDED SERVICE WINDOW ELEVATION TAG AT OFFICE 368 FOR CLARIFICATION
ADDED GENERAL NOTES FOR CLARIFICATION
A171 FINISH PLAN - 1ST FLOOR UPDATED LVT-1 IN FINISH SCHEDULE TO PREFERRED SUBSTITUTION
UPDATED FINISH NOTES FOR CLARIFICATION
A172 FINISH PLAN - 2ND FLOOR UPDATED FINISH NOTES FOR CLARIFICATION
A173 FINISH PLAN - 3RD FLOOR UPDATED FINISH NOTES FOR CLARIFICATION
A210 INTERIOR ELEVATIONS CORRECTED RM NUMBER IN ELEVATION NAME
ADDED SERVICE WINDOW ELEVATION AT OFFICE 368 FOR CLARIFICATION
A211 INTERIOR ELEVATIONS ADDED PL REGION AND WOOD TRIM LOCATIONS IN THE TRANSACTION WINDOW ELEVATIONS
A400 ENLARGED RESTROOM PLANS UPDATED FIXTURE SCHEDULE TO INCLUDE CELL FIXTURES
REMOVED TOILET ROOM GENERAL NOTE
A600 DOOR SCHEDULE AND DETAILS ADDED COURTROOM GATE ELEVATION FOR CLARIFICATION
A900 SIGNAGE TYPES AND ELEVATIONS UPDATED SIGNAGE SCHEDULE TO INCLUDE "SIGNAGE TEXT" COLUMN
A904 SIGNAGE PLAN - 3RD FLOOR UPDATED AND CLARIFIED SIGNAGE LOCATIONS
M201 HVAC RENOVATION PLAN - SECOND FLOOR UPDATED KEYNOTES FOR CLARIFICATION
UPDATED GENERAL NOTES FOR CLARIFICATION
M301 HVAC RENOVATION PLAN - THRID FLOOR UPDATED GENERAL NOTES FOR CLARIFICATION
24260FLOLEC - FLOYD COUNTY LEC RENOVATION
NFPA 101, 2018 EDITION
4.6.10 CONSTRUCTION, REPAIR, AND IMPROVEMENT OPERATIONS
BUILDINGS, OR PORTIONS OF BUILDINGS, SHALL BE PERMITTED TO BE OCCUPIED DURING CONSTRUCTION, REPAIR, ALTERATIONS, OR ADDITIONS ONLY WHERE REQUIRED MEANS OF EGRESS AND REQUIRED FIRE PROTECTION FEATURES ARE IN PLACE AND CONTINUOUSLY MAINTAINED FOR THE PORTION OCCUPIED OR WHERE ALTERNATIVE LIFE SAFETY MEASURES ACCEPTABLE TO THE AUTHORITY HAVING JURISDICTION ARE IN
PLACE.
FIRE PROTECTION:
PLANS FOR FIRE PROTECTION SPRINKLER PIPING INCLUDING COMPLETE SEISMIC SUPPORT DETAILS SHALL BE REVIEWED AND APPROVED BY THE COA FIRE MARSHAL'S OFFICE PRIOR TO INSTALLATION FOR COMPLIANCE
WITH ASCE/ SEI 7-10 SECTIONS 13.3.1, 13.3.2, ABD NFPA 13.
GENERAL PROJECT NOTES:
A. ALL INTERIOR FINISH CLASSIFICATIONS SHALL COMPLY WITH 2018 NFPA 101: 38.3.3.1, “INTERIOR FINISH
SHALL BE IN ACCORDANCE WITH SECTION 10.2.” .
B. GENERAL: SAFETY GLAZING SHALL BE PERMANENTLY IDENTIFIED PER 2018 IBC: 2406.3.
C. ALL DEMOLITION WORK SHALL COMPLY WITH THE REQUIREMENTS OF 2019 NFPA 241, STANDARD FOR SAFEGUARDING ANY REQUIREMENTS FOR AIR FILTERING OR SYSTEMS THAT MUST REMAIN IN OPERATION
DURING CONSTRUCTION, ALTERATION, AND DEMOLITION OPERATIONS.
D. GENERAL: ALL FIRE AND/OR SMOKE BARRIERS OR WALLS SHALL BE EFFECTIVELY AND PERMANENTLY IDENTIFIED WITH SIGNS OR STENCILING ABOVE A DECORATIVE CEILING AND / OR IN CONCEALED SPACES WITH LETTERS A MINIMUM OF TWO (2) INCHES HIGH ON A CONTRASTING BACKGROUND SPACED A MAXIMUM OF
TWELVE (12) FEET ON CENTER WITH A MINIMUM OF ONE PER WALL OR BARRIER IN
1. CONTRACTORS SHALL VISIT THE SITE PRIOR TO BIDDING THE PROJECT TO VERIFY EXISTING FIELD
CONDITIONS. BID SUBMISSION SHALL AFFIRM CONTRACTOR MADE ALLOWANCES FOR SAID
CONDITIONS AND RELATED PROJECT COSTS.
2. WORK IS TO BE PERFORMED IN AN EXISTING FACILITY. CONTRACTOR SHALL COORDINATE ALL WORK, INCLUDING INTERRUPTION OF UTILITIES AND BUILDING SERVICE WITH THE OWNER OR BUILDING
MANAGEMENT. PHASING OF WORK IS TO BE PERFORMED AND COORDINATED TO ACCOMMODATE
EXISTING FACILITY OPERATIONS.
3. CONTRACTOR SHALL BE RESPONSIBLE FOR COST AND WORK ASSOCIATED WITH CUTTING AND
PATCHING OF EXISTING FACILITY AS REQUIRED TO COMPLETE THIS PROJECT. AFFECTED AREAS
SHALL BE RESTORED OR REPAIRED TO LEAVE IN "LIKE-NEW" CONDITION AND MATCHING
SURROUNDING SURFACES.
4. CONTRACTOR SHALL BE RESPONSIBLE FOR COSTS ASSOCIATED WITH BUILDING UTILITY EQUIPMENT
SHUTDOWNS AND FIRE WATCHES.
5. SHOULD STOPPAGE OF WORK OCCUR THE CONTRACTOR SHALL LEAVE THE FACILITY IN A WEATHER TIGHT CONDITION OCCUPIED FACILITIES SYSTEMS SHALL BE LEFT IN AN OPERATIONAL STATE TO
ALLOW CONTINUED NORMAL FACILITIES OPERATIONS.
6. ALL RENOVATION WORK IS TO BE PERFORMED IN COMPLIANCE WITH IFC 2012, SECTION 3304.2 WASTE DISPOSAL. COMBUSTIBLE DEBRIS AND WASTE MATERIAL SHALL BE REMOVED FROM THE BUILDING AT
THE END OF EACH SHIFT OF WORK.
7. ALL DEMOLITION WORK SHALL COMPLY WITH THE REQUIREMENTS OF NFPA 241, 2013 EDITION, STANDARD FOR SAFEGUARDING CONSTRUCTION, ALTERATION, AND DEMOLITION OPERATIONS.
8. CONTRACTOR SHALL BE RESPONSIBLE FOR THE PROTECTION OF THE ELEVATORS THROUGHOUT
CONSTRUCTION.
9. NO MUSIC OR LOUD CONSTRUCTION DURING DAY HOURS, PROVIDE ACOUSTIC INSULATION AT
CONSTRUCTION BARRIER.
SCOPE OF WORK: RENOVATION OF AN EXISTING OFFICE BUILDING
WILL INVOLVE UPDATING OFFICE SPACES WITH NEW GYPSUM
WALLS, LIGHT FIXTURES, AND FLOOR FINISHES. A NEW
COURTROOM WILL REPLACE THE EXISITNG ASSEMBLY SPACE.
ADDITIONAL PUBLIC RESTROOMS WILL BE ADDED TO THE 2ND AND
3RD FLOOR LOBBIES. A HOLDING CELL WILL BE LOCATED
ADJACENT TO THE SHERIFF'S OFFICE. A NEW STRETCHER-
COMPLAINT ELEVATOR WILL BE ADDED TO THE EXISITNIG ENTRY
LOBBY. VARIOUS FINISH UPDATES WILL BE MADE ON THE 2ND AND
3RD FLOORS. A NEW STOREFRONT ENRTY DOOR WILL BE
INSTALLED ON THE NORTH SIDE OF THE FIRST FLOOR. MECHANICAL
UNITS, NEW LIGHTING AND ELECTRICAL UPDATES WILL ALSO BE
INCLUDED IN THE RENOVATION. THERE WILL BE NO CHANGE TO
THE BUILDING'S USE GROUP (BUSINESS).
PERMITTING AGENCY
ROME, GA
ROME-FLOYD COUNTY BUILDING INSPECTION DEPARTMENT
607 BROAD ST.
ROME, GA 30162
TEL: 706-236-4480
CONSTRUCTION TYPE (PER CHAPTER 6 - 2018 IBC)
BLDG.: TYPE IIB SPRINKLERED
OCCUPANCY TYPE
BLDG.: B, A-3
AREA
FIRST FLOOR 19,220 GSF
SECOND FLOOR 19,890 GSF
THIRD FLOOR 19,890 GSF
TOTAL 59,000 GSF
AREA OF RENOVATION
FIRST FLOOR 1,547 GSF
SECOND FLOOR 7,843 GSF
THIRD FLOOR 8,623 GSF
TOTAL 18,013 GSF
BUILDING HEIGHT
BLDG.: 47'-6 1/4"
OWNER
FLOYD COUNTY
12 EAST 4TH AVENUE
ROME, GA 30161
RYAN DAVIS
FACILITIES MANAGER
ARCHITECT
SIZEMORE GROUP, LLC
342 MARIETTA STREET, NW | UNIT 3 |
ATLANTA, GA 30313
TEL: 404-605-0690
FAX: 404-605-0890
KATHRYN SCOTT
PRINCIPAL IN CHARGE, SIZEMORE GROUP
ANGEL KAUFFMANN
PROJECT MANAGER
STRUCTURAL
PALMER ENGINEERING COMPANY
3585 HABERSHAM, BUILDING N
TUCKER, GA 30084
TEL: 770-908-9908
BRIAN NANNIS
VICE PRESIDENT
MECHANICAL, PLUMBING, AND FIRE PROTECTION
DRINKARD ENGINEERING GROUP
300 JOHN DAVENPORT DR.
ROME, GA 30162
TEL: 888-687-3589
JEFF DRINKARD
PROJECT ENGINEER
ELECTRICAL
LUNDY ENGINEERING GROUP
229 LAND ROAD
WALESKA, GA 30183
TEL: 678-634-6941
ANDREW LUNDY
PROJECT ENGINEER
LOW VOLTAGE
NEWCOMB & BOYD
303 PEACHTREE CENTER, NE | SUITE 525 |
ATLANTA, GA 30303
TEL: 404-730-8400
MILES HOLCOMBE
SECURITY CONSULTANT
GLADYS MARROQUIN
AV CONSULTANT
NICK SCHNEIDER
COMMUNICATIONS CONSULTANT
NOT TO SCALE
SCALE
DATE:
DRAWN BY:
CHECKED BY:
PROJECT #
THIS DRAWING IS AN INSTRUMENT OF
SERVICE AND SHALL REMAIN THE
PROPERTY OF THE ARCHITECT. NO
PART OF THIS DOCUMENT SHALL BE
REPRODUCED OR TRANSMITTED IN
ANY FORM, ELECTRONICALLY OR
MECHANICALLY, FOR ANY PURPOSE,
WITHOUT THE EXPRESS WRITTEN
PERMISSION OF THE ARCHITECT.
M
A R
IE
T
T A
S T
R E
E T
N
W U
N
IT
A
T L A
N T
A
G E
O R
G
IA
T
F w w w .s iz e m o re g ro u p
.c o m
S
IZ
E
M O
R E
G R
O U
P
12/12/25
As indicated
3/5/2026 11:41:26 AMAutodesk Docs://24260FLOLEC_Floyd_County_Law_Enforcement_Center/24260SLOYLEC_Floyd_County_LEC.rvt
G000
COVER SHEET
ANGEL
WYATT
12/12/25
24260FLOLEC
F L O
Y D
C O
U N
T Y
L E
C R
E N
O V
A T
IO
N
G
O V
E R
N M
E N
T P
L A
Z A
R O
M E
G
A
100% CONSTRUCTION DOCUMENTS
PROJECT DIRECTORYVICINITY MAP
BUILDING CODES & CONSTRUCTION INFORMATIONBUILDING INFORMATION
N
FLOYD COUNTY
LAW ENFORCEMENT CENTER RENOVATION
5 GOVERNMENT PLAZA
ROME, GA 30161
ADD OR DEDUCT ALTERNATES
OWNER PROVIDED ITEMS AND COMPONENTS
GENERAL NOTES
SHEET # SHEET NAME
ISSUE
DATE
CURRENT
REV.
GENERAL
G000 COVER SHEET 12/12/25 3
G002 ABBREVIATIONS AND LEGENDS 12/12/25
G100 SITE ACCESS PLAN 12/12/25
G200 CODE REVIEW 12/12/25
G300 LIFE SAFETY PLAN - LEVEL 01 12/12/25
G301 LIFE SAFETY PLAN - LEVEL 02 12/12/25
G302 LIFE SAFETY PLAN - LEVEL 03 12/12/25
G400 PARTITION TYPES 12/12/25 3
G500 ACCESS PLAN - LEVEL 01 12/12/25
G501 ACCESS PLAN - LEVEL 02 12/12/25
G900 UL Details 12/12/25
G901 UL Details 12/12/25
G902 UL Details 12/12/25
ARCHITECTURE
AD000 DEMOLITION PLAN - 1ST FLOOR 12/12/25
AD001 DEMOLITION PLAN - 2ND FLOOR 12/12/25
AD002 DEMOLITION PLAN - 3RD FLOOR 12/12/25
AD150 DEMOLITION RCP - 1ST FLOOR 12/12/25
AD151 DEMOLITION RCP - 2ND FLOOR 12/12/25
AD152 DEMOLITION RCP - 3RD FLOOR 12/12/25
A100 OVERALL PROPOSED FLOOR PLANS – 1ST FLOOR 12/12/25 3
A101 OVERALL PROPOSED FLOOR PLANS – 2ND FLOOR 12/12/25 3
A102 OVERALL PROPOSED FLOOR PLANS – 3RD FLOOR 12/12/25 3
A153 OVERALL PROPOSED RCP – 1ST FLOOR 12/12/25
A154 OVERALL PROPOSED RCP – 2ND FLOOR 12/12/25
A155 OVERALL PROPOSED RCP – 3RD FLOOR 12/12/25
A171 FINISH PLAN - 1ST FLOOR 12/12/25 3
A172 FINISH PLAN - 2ND FLOOR 12/12/25 3
A173 FINISH PLAN - 3RD FLOOR 12/12/25 3
A190 FURNITURE PLAN - 2ND FLOOR 12/12/25
A191 FURNITURE PLAN - 3RD FLOOR 12/12/25
A200 EXTERIOR ELEVATIONS 12/12/25
A210 INTERIOR ELEVATIONS 12/12/25 3
A211 INTERIOR ELEVATIONS 12/12/25 3
A400 ENLARGED RESTROOM PLANS 12/12/25 3
A401 ENLARGED HOLDING CELL PLANS 12/12/25 3
A402 ENLARGED JUDGES BENCH PLAN 12/12/25
A500 DETAIL VIEW 12/12/25
A510 VERTICAL CIRCULATION 12/12/25
A570 MILLWORK DETAILS 12/12/25
A600 DOOR SCHEDULE AND DETAILS 12/12/25 3
A601 WINDOW SCHEDULE AND DETAILS 12/12/25
A900 SIGNAGE TYPES AND ELEVATIONS 12/12/25 3
A901 SIGNAGE TYPES AND ELEVATIONS 12/12/25
A902 SIGNAGE PLAN - 1ST FLOOR 12/12/25
A903 SIGNAGE PLAN - 2ND FLOOR 12/12/25
A904 SIGNAGE PLAN - 3RD FLOOR 12/12/25 3
STRUCTURAL
S001 GENERAL NOTES AND TYPICAL DETAILS 12/12/25
S002 STATEMENT OF SPECIAL INSPECTIONS 12/12/25
S101 FOUNDATION PLAN 12/12/25
S102 SECOND FLOOR FRAMING PLAN 12/12/25
S103 THIRD FLOOR FRAMING PLAN 12/12/25
S104 ROOF FRAMING PLAN 12/12/25
S301 SECTIONS & DETAILS 12/12/25
S401 SECTIONS & DETAILS 12/12/25
MECHANICAL
M001 HVAC NOTES, LEGENDS & SCHEDULES 12/12/25
M002 HVAC NOTES, LEGENDS & SCHEDULES 12/12/25
M101 HVAC RENOVATION PLAN - FIRST FLOOR 12/12/25
M201 HVAC RENOVATION PLAN - SECOND FLOOR 12/12/25
M301 HVAC RENOVATION PLAN - THIRD FLOOR 12/12/25
M401 HVAC SPECIFICATIONS 12/12/25
M402 HVAC SPECIFICATIONS 12/12/25
ELECTRICAL
E001 ELECTRICAL NOTES, LEGEND, AND SPECIFICATIONS 12/12/25
E002 ELECTRICALDETAILS & SCHEDULES 12/12/25
E003 ELECTRICAL SCHEDULES 12/12/25
E004 ELECTRICAL SCHEDULES 12/12/25
ED101 ELECTRICAL CEILING DEMOLITION PLAN 1ST FLOOR 12/12/25
ED102 ELECTRICAL CEILING DEMOLITION PLAN 2ND FLOOR 12/12/25
ED103 ELECTRICAL CEILING DEMOLITION PLAN 3RD FLOOR 12/12/25
E101 ELECTRICAL CEILING PLAN 1ST FLOOR 12/12/25
E102 ELECTRICAL CEILING PLAN 2ND FLOOR 12/12/25
E103 ELECTRICAL CEILING PLAN 3RD FLOOR 12/12/25
ED201 ELECTRICAL FLOOR DEMOLITION PLAN 1ST FLOOR 12/12/25
ED202 ELECTRICAL FLOOR DEMOLITION PLAN 2ND FLOOR 12/12/25
ED203 ELECTRICAL FLOOR DEMOLITION PLAN 3RD FLOOR 12/12/25
E201 ELECTRICAL FLOOR PLAN 1ST FLOOR 12/12/25
E202 ELECTRICAL FLOOR PLAN 2ND FLOOR 12/12/25
E203 ELECTRICAL FLOOR PLAN 3RD FLOOR 12/12/25
PROJECT SCOPE OF WORK
ADD ALTERNATES:
1. REPLACE ALL STOREFRONT WINDOWS AT ENTRANCE TOWER AND INCLUDE 3M FILM.
2. INCLUDE 3M FILM ON EXISTING STOREFRONT WINDOWS AT ENTRANCE TOWER.
3. BAFFLE TRANSACTION WINDOWS IN LIEU OF SPEAKER TRANSACTION WINDOWS.
4. REPLACE/INSTALL NEW BLINDS
5. ACOUSTICAL WALL PANELS IN COURTROOM
DEDUCT ALTERNATES:
1. VCT IN LIEU OF LVT IN CORRIDORS AND BREAKROOMS.
2. REMOVE 2ND & 3RD FLOOR BREAKROOMS FROM SCOPE.
3. REMOVER TOWER STAIRWELL FROM SCOPE.
SHEET # SHEET NAME
ISSUE
DATE
CURRENT
REV.
AUDIO / VISUAL
AV000 AV SYSTEMS LEGEND 12/12/25
AV002 AV SYSTEMS - JUVENILE COURT 259A 12/12/25
AV003 AV SYSTEMS - DIGITAL SIGNAGE & CONFERENCE
ROOM
12/12/25
AV100 AV SYSTEMS WALL PLATE 12/12/25
AV INFRASTRUCTURE
AVI000 AV INFRASTRUCTURE LEGEND 12/12/25
AVI100 AV INFRASTRUCTURE FLOOR PLANS - 1ST FLOOR 12/12/25
AVI101 AV INFRASTRUCTURE FLOOR PLANS - 2ND FLOOR 12/12/25
AVI102 AV INFRASTRUCTURE FLOOR PLANS - 3RD FLOOR 12/12/25
AVI200 AV INFRASTRUCTURE RCP - 1ST FLOOR 12/12/25
AVI201 AV INFRASTRUCTURE RCP - 2ND FLOOR 12/12/25
AVI202 AV INFRASTRUCTURE RCP - 3RD FLOOR 12/12/25
AVI300 AV INFRASTRUCTURE ELEVATIONS 12/12/25
AVI400 AV INFRASTRUCTURE DETAILS 12/12/25
TELECOM
T001 TELECOM LEGEND 12/12/25
T100 TELECOM PROPOSED FLOOR PLANS - 1ST FLOOR 12/12/25
T101 TELECOM PROPOSED FLOOR PLANS - 2ND FLOOR 12/12/25
T102 TELECOM PROPOSED FLOOR PLANS - 3RD FLOOR 12/12/25
T400 TELECOM DETAILS 12/12/25
T401 TELECOM DETAILS 12/12/25
T601 TELECOM RISER DIAGRAMS 12/12/25
TD000 TELECOM DEMOLITION PLAN - 1ST FLOOR 12/12/25
TD001 TELECOM DEMOLITION PLAN - 2ND FLOOR 12/12/25
TD002 TELECOM DEMOLITION PLAN - 3RD FLOOR 12/12/25
SECURITY
SC001 SECURITY LEGEND AND NOTES 12/12/25
SC100 SECURITY PROPOSED FLOOR PLANS - 1ST FLOOR 12/12/25
SC101 SECURITY PROPOSED FLOOR PLANS - 2ND FLOOR 12/12/25
SC102 SECURITY PROPOSED FLOOR PLANS - 3RD FLOOR 12/12/25
SC400 SECURITY DOOR DETAILS 12/12/25
SC401 SECURITY CAMERA DETAILS 12/12/25
PLUMBING
P001 PLUMBING - NOTES, LEGENDS & SCHEDULES 12/12/25
P002 TYP. PLUMBING DETAILS 12/12/25
P101 PLUMBING PLAN - FIRST FLOOR 12/12/25
P201 PLUMBING PLAN - SECOND FLOOR 12/12/25
P301 PLUMBING PLAN - THIRD FLOOR 12/12/25
P401 PLUMBING SPECIFICATIONS 12/12/25
N o
D
E S
C R
IP
T
IO
N
D A
T E
P
R E
-B
ID
A D
D E
N D
U M
/0
/2
A. LIMITING HEIGHT, STUD GAUGE AND SPACING INFORMATION PROVIDED IN PARTITION SCHEDULES ARE ABBREVIATED AND MAY NOT ADDRESS ALL CONDITIONS OF THE PROJECT. THIS INFORMATION IS
PROVIDED FOR USE AS A GUIDE AND DOES NOT ALLEVIATE THE CONTRACTOR FROM PROVIDING
WALL ASSEMBLIES THAT MEET THE DESIGN CRITERIA FOR EACH CONDITION. CONTRACTOR SHALL
COORDINATE WITH PROJECT CONDITIONS AND PROVIDE WALL ASSEMBLIES BASED ON
MANUFACTURER'S STANDARD SPAN TABLES THAT MEET DESIGN CRITERIA INCLUDING: LOADS,
DEFLECTION LIMITS, FIRE TEST RATINGS AND SOUND TEST CLASSIFICATIONS.
B. SOUND TRANSMISSION CLASS (STC) INDICATED IS BASED ON MATERIALS AND CONSTRUCTION IDENTICAL TO THOSE IN SOUND TEST ASSEMBLY SCHEDULED. IF CHANGES IN THE ASSEMBLY ARE
NECESSARY DUE TO CONTRACTOR'S SELECTION OF PRODUCTS/MANUFACTURER OR DUE TO
REQUIRED PARTITION HEIGHT, DEFLECTION CRITERIA OR DESIGN PRESSURE, CONTRACTOR SHALL SUBMIT FOR APPROVAL AND PROVIDE ALTERNATE PARTITION ASSEMBLIES THAT MEET SPECIFIED DESIGN CRITERIA. FIELD SOUND TRANSMISSION (FSTC) IS PERMITTED TO BE 5 POINTS LOWER THAN
SPECIFIED STC.
C. IF THE SELECTED STEEL STUD MANUFACTURER'S THICKNESS OF STEEL COMPONENT VARIES FROM THE BASIS OF DESIGN (AS DEFINED BELOW) OR HAS OTHER ATTRIBUTES THAT VARY FROM THE BASIS OF DESIGN, PROVIDE MANUFACTURER'S STANDARD THICKNESS WITH LIMITING HEIGHT SPAN TABLES
THAT MEETS OR EXCEEDS THE SPECIFIED DESIGN CRITERIA.
D. PARTITIONS SHALL EXTEND 6" PAST FINISHED CEILING, U.N.O
E. RATED PARTITIONS SHALL BE PERMANENTLY IDENTIFIED IN CONCEALED SPACES EITHER AS
REQUIRED BY CODE OR WITH 2" HIGH LETTERING IN A COLOR/VALUE CONTRASTING WITH THE
BACKGROUND AND SPACE NO MORE THAN 12 FEET ON CENTER. TEXT SHALL READ AS REQUIRED BY CODE OFFICIAL OR AS"_____ HOUR FIRE & SMOKE BARRIER - PROTECT ALL OPENINGS." (FILL IN
APPROPRIATE HOURLY RATING)
F. GYPSUM WALL BOARD IS TO BE TYPE 'X' FIRE RESISTANT BOARD UNLESS OTHERWISE NOTED.
G. DOOR OPENING FRAMING (WHETHER RATED OR NON - RATED) SHALL BE MINIMUM 20 GAGE STUDS
WITH SINGLE STUD JAMB FOR STANDARD WEIGHT DOORS AND DOUBLE STUD JAMB FOR HEAVY
WEIGHT DOORS IN ACCORDANCE WITH GYPSUM ASSOCIATION STANDARD GA-219.
H. ALL FIRE AND/OR SMOKE BARRIERS OR WALLS SHALL BE EFFECTIVELY ANDPERMANENTLY IDENTIFIED WITH SIGNS OR STENCILING ABOVE A DECORATIVE CEILING AND/OR IN CONCEALED SPACES WITH LETTERS A MINIMUM OF 2" HIGH ON A CONTRASTING BACKGROUND SPACED A MAXIMUM OF 12'-0" ON CENTER WITH A MINIMUM OF ONE PER WALL OR BARRIER. THE HOURLY RATING SHALL BE INCLUDED ON ALL RATED BARRIERS OR WALLS. SUGGESTED WORDING ‘(__) HOUR FIRE AND SMOKE BARRIER-
PROTECT ALL OPENINGS.
a. EXCEPTION: EXISTING STENCILING ACCEPTABLE TO THE AUTHORITY HAVING JURISDICTION.” AS
STATED IN THE RULES AND REGULATIONS OF THE SAFETY FIRE COMMISSIONER CHAPTER 120-3-3
RULES AND REGULATIONS FOR THE STATE MINIMUM FIRE SAFETY STANDARDS.
b. APPLY LETTERING TO BOTH SIDES OF WALLS.
I. ALL FIRE RATED PARTITIONS ARE REQUIRED TO GO TO THE BOTTOM OF STRUCTURAL DECK, U.N.O
J. IN ALL WET AREAS USE 5/8" MOLD AND MOSISTURE RESISTANT DRYWALL PANELS. SUBSTITUTE
SCHEDULED GYPSUM BOARD WITH WATER RESISTANT BACKING PANEL GYPSUM BOARD OF EQUAL
THICKNESS & EQUAL FIRE RATING IN AREAS TO RECEIVE TILE.
GENERAL NOTES:
CONSTRUCTION AND LOCATION MAXIMUM SINGLE DIMENSION MAXIMUM SINGLE AREA
PARTITION - INTERIOR
CEILING - INTERIOR
WITH PERIMETER RELIEF
WITHOUT PERIMETER RELIEF
30' - 0"
50' - 0"
30' - 0"
2,500 S.F.
900 S.F.
NOTE: ANY REQUIRED CONTROL JOINTS NOT SHOWN OR LOCATED IN THE DRAWINGS SHALL BE
FIELD COORDINATED WITH THE ARCHITECT PRIOR TO FINAL INSTALLATION
STRUCTURE ABOVE
FINISHED CEILING
CONTROL JOINTS REFERENCE CONTROL
JOINTS DETAILS FOR INFORMATION
SCHEDULED WALL BASE
SCHEDULED FINISH FLOOR
MAXIMUM SPACING - CONTROL JOINTS
GYPSUM BOARD CONTROL JOINTS
GYPSUM BOARD CONTROL JOINTS - PLACEMENT DIAGRAMS
2S438SW
HOURLY RATING
CORE STRUCTURE
OVERALL PARTITION THICKNESS
MODIFICATION CODE(S)
HOURLY RATING CODE STRUCTURE
S
S
W
M
F
X
C
0 HOUR
1 HOUR
2 HOUR
3 HOUR
4 HOUR
SMOKE
STEEL STUD
WOOD STUD
CONCRETE MASONARY UNIT
FURRING
SHAFT WALL - STEEL STUD
CHASE WALL
MODIFICATION CODES
WALL TAG
S SOUND ATTENUATION REQUIRED TO CONTINUE THE FULL HEIGHT OF THE WALL –
COMPLY WITH SCHEDULED STC RATING & TESTING ASSEMBLY REQUIREMENTS.
A EXTEND PARTITION TO UNDERSIDE OF DECK ABOVE
C EXTEND PARTITION TO UNDERSIDE OF FINISH CEILING, ADD SOUND ATTENUATION
ABOVE CEILING - REFER TO "C" MODIFIER DETAIL FOR ADDITIONAL INFORMATION
U NOT USED
P NOT USED
M NOT USED
K NOT USED
CIP CAST IN PLACE CONCRETE WALL, REFER TO TABLE IBC CH 721.1(2) FOR RATING
TYPICAL WALL TYPE BEGINS AT THE EXISTING SLAB AND EXTENDS 6" PAST FINISHED
CEILING, U.N.O. BELOW. - REFER TO "A" MODIFIER DETAIL FOR ADDITIONAL INFORMATION
B NOT USED
STRUCTURE ABOVE
SCHEDULED PARTITION
"A" MODIFIER - PARTIAL HEIGHT FINISH
SCHEDULED CEILINGS
EXTEND METAL STUDS TO
STRUCTURE ABOVE
EXTEND GYPSUM WALLBOARD
6" ABOVE FINISHED CEILING
.0
BRACING TO STRUCTURE ABOVE
EXTEND FRAMING AND GYPSUM
WALLBOARD 6" ABOVE FINISHED
CEILING
SCHEDULED CEILING
SCHEDULED PARTITION
"Y" MODIFIER - PARTIAL HEIGHT PARTITION
BRACE TO STRUCTURE
STRUCTURE ABOVE
WHERE USED WITH "S" MODIFIER,
PROVIDE 3" SOUND ATTENUATION
BLANKET, EXTENDED 4' - 0"
MINIMUM EACH SIDE OF WALL
SCHEDULED CEILING
WHERE USED WITH "S" MODIFIER,
COMPLY WITH REFERENCE STC
TESTED ASSEMBLY REQUIREMENTS
IN SCHEDULED PARTITION TYPE
SCHEDULED PARTITION
"C" MODIFIER - PARTITION TO FINISH CEILING
FIRESTOP SEALANT EACH SIDE
2" WIDE 16 GA. GALV. STEEL
STRAPS AT 24" O.C. MAX
FIRE SAFING INSULATION FILL
T.O. GYP. BD. EACH SIDE
FIRE SAFING INSULATION FILL
METAL DECK FLUTES
EXISTING FLOOR DECK
W/CONCRETE FILL
CUT STUDS SHORT AS
REQD. BY U.L DESIGN
1 LAYER TYPE X GYP. BD.
FOR 1 HR, 2LAYERS TYPE X
GYP. BD. FOR 2 HR; REFER TO
SCHEDULED PARTITION FOR
ADDITIONAL INFORMATION
BASIS OF DESIGN: U.L. NO. HW - D - 0360
FIRESTOP SEALANT BEYOND
FIRE SAFING INSULATION FILL
T.O. GYP. BD. EACH SIDE
FIRE SAFING INSULATION AT
DECK FLUTE BEYOND
STEEL FLOOR DECK
W/CONCRETE FILL
CUT STUDS SHORT AS
REQD. BY U.L DESIGN
1 LAYER TYPE X GYP. BD.
FOR 1 HR, 2 LAYERS TYPE X
GYP. BD. FOR 2 HR; REFER TO
SCHEDULED PARTITION FOR
ADDITIONAL INFORMATION
BASIS OF DESIGN: U.L. NO. HW - D - 0091
FIRESTOP SEALANT EACH SIDE
PLAN
BASE
HEAD
CONT TRACK WITH (2) PAF AT 16" O.C. MAX. WITHIN
1" OF ENDS.
SLIP-TYPE CONNECTION BETWEEN TOP TRACK
AND STUDS; ALLOW FOR 1/2" MIN. CLEARANCE
CONT. FIRESTOPPING; REFER TO TYPES BELOW
FOR EXACT DESCRIPTION
1 LAYER 5/8" GYP. BD. ON EACH SIDE; REFER TO
TYPES BELOW FOR EXACT DESCRIPTION
METAL STUD FRAMING AS SPECIFIED
CONT. FIRE STOPPING; REFER TO TYPES
BELOW FOR EXACT DESCRIPTION
TOP OF FLOOR LEVEL TO RECEIVE FINISH
UNLESS INDICATED OTHERWISE
CONT. METAL STUD RUNNER WITH FASTENERS AT
2'-0" O.C. MAX. AND WITHIN 1" OF ENDS
COORDINATE SOUND ATTENUATION BLANKET
(SAB) WITH PARTITION TYPE BELOW
PLAN
BASE
HEAD
CONT. 20 GA MIN. WITH (2) PAF AT 16" O.C. MAX.
WITHIN 1" OF ENDS.
SLIP-TYPE CONNECTION BETWEEN TOP TRACK
AND STUDS; ALLOW FOR 1/2" MIN. CLEARANCE
CONT. FIRESTOPPING; REFER TO TYPES BELOW
FOR EXACT DESCRIPTION
1 LAYER 5/8" GYP. BD. ON ONE SIDE; REFER TO
TYPES BELOW FOR EXACT DESCRIPTION
METAL SHAFT STUD STUD AT 16" O.C. CONT. ROW
OF BLOCKING AT 4'-0" O.C.
CONT. SEALANT; REFER TO TYPES BELOW
FOR EXACT DESCRIPTION
TOP OF FLOOR LEVEL TO RECEIVE FINISH
UNLESS INDICATED OTHERWISE
CONT. METAL STUD RUNNER WITH FASTENERS AT
2'-0" O.C. MAX. AND WITHIN 1" OF ENDS
COORDINATE SOUND ATTENUATION BLANKET
(SAB) WITH PARTITION TYPE BELOW
PLAN
BASE
HEAD SLIP-TYPE CONNECTION BETWEEN TOP TRACK
AND STUDS; ALLOW FOR 1/2" MIN. CLEARANCE
CONT. SEALANT OR FIRESTOPPING; REFER TO
TYPES BELOW FOR EXACT DESCRIPTION
1 LAYER 5/8" GYP. BD. ON EACH EXTERIOR SIDE;
REFER TO TYPES BELOW FOR EXACT DESCRIPTION
METAL STUD FRAMING AS SPECIFIED
CONT. SEALANT; REFER TO TYPES BELOW
FOR EXACT DESCRIPTION
TOP OF FLOOR LEVEL TO RECEIVE FINISH
UNLESS INDICATED OTHERWISE
CONT. METAL STUD RUNNER WITH FASTENERS
WITHIN 1" OF ENDS
COORDINATE SOUND ATTENUATION BLANKET
(SAB) WITH PARTITION TYPE BELOW
PROVIDE 1" CLEAR GAP BETWEEN PLUMBING AND
ONE WALL. DO NOT BRACE BETWEEN STUDS
PLAN
BASE
HEAD
LINE OF SUBSTRATE
CONT. SEALANT OR
FIRESTOPPING; REFER
TO TYPES BELOW FOR
EXACT DESCRIPTION
1 LAYER FINISH MATERIAL
ON ONE SIDE; REFER TO
TYPES BELOW FOR EXACT
DESCRIPTION
METAL FURRING
STRIPS, REFER TO
TYPES BELOW
CONT. SEALANT;
REFER TO TYPES
BELOW FOR EXACT
DESCRIPTION
TOP OF FLOOR LEVEL TO RECEIVE
FINISH UNLESS INDICATED OTHERWISE
PLAN
BASE
HEAD LINE OF SUBSTRATE
CONT. SEALANT OR FIRESTOPPING
1 LAYER 5/8" GYP. BD. ON ONE SIDE
METAL STUD FRAMING AS SPECIFIED
CONT. SEALANT; REFER TO TYPES BELOW
FOR EXACT DESCRIPTION
TOP OF FLOOR LEVEL TO RECEIVE FINISH
UNLESS INDICATED OTHERWISE
COORDINATE SOUND ATTENUATION BLANKET
(SAB)
PLAN
BASE
HEAD
CONT. FIRESTOPPING; REFER TO TYPES BELOW
FOR EXACT DESCRIPTION
CONT. FIRE STOPPING; REFER TO TYPES
BELOW FOR EXACT DESCRIPTION
TOP OF FLOOR LEVEL TO RECEIVE FINISH
UNLESS INDICATED OTHERWISE
8" NOMINAL CMU
UNDERSIDE OF DECK/STRUCTURE
1 LAYER 1" GYP. BD. ON SHAFT SIDE; REFER TO
TYPES BELOW FOR EXACT DESCRIPTION
PLAN
BASE
HEAD LINE OF SUBSTRATE
CONT. SEALANT OR FIRESTOPPING; REFER TO
TYPES BELOW FOR EXACT DESCRIPTION
2 LAYERS 5/8" GYP. BD. ON ONE SIDE
METAL STUD FRAMING AS SPECIFIED
CONT. SEALANT; REFER TO TYPES BELOW
FOR EXACT DESCRIPTION
TOP OF FLOOR LEVEL TO RECEIVE FINISH
UNLESS INDICATED OTHERWISE
COORDINATE SOUND ATTENUATION BLANKET
(SAB) WITH PARTITION TYPE BELOW
PLAN
BASE
HEAD
Z-FURRING CHANNELSHAT-FURRING CHANNELS
PAINT CMU AS SCHEDULED REFER TO FINISH
SCHEDULE
RESILIENT SOUND ISOLATION CLIP SPACED @ 24" O.C.
DRYWALL FURRING CHANNEL @ 24" O.C.
2 LAYERS 5/8" GYP. BD. ON ONE EXTERIOR SIDE;
REFER TO TYPES BELOW FOR EXACT DESCRIPTION
1 LAYER 5/8" GYP. BD. ON ONE SIDE; REFER TO TYPES
BELOW FOR EXACT DESCRIPTION. USED WITH UL U429
PLAN
BASE
HEAD CONT. FIRESTOPPING; REFER TO TYPES BELOW
FOR EXACT DESCRIPTION
CONT. FIRE STOPPING; REFER TO TYPES
BELOW FOR EXACT DESCRIPTION
TOP OF SLAB
8" NOMINAL CMU
UNDERSIDE OF DECK/STRUCTURE
2-1/2" 20 GA METASL STUD STUDS AT 16" O.C.
11"
1" AIR SPACES BETWEEN CMU AND STUD WALL
1 LAYER 5/8" GYP. BD. ON ONE SIDE; REFER TO
TYPES BELOW FOR EXACT DESCRIPTION
NOTE: WALL TYPE TO BE COORDINATED WITH SLAB REMOVAL.
PLAN
BASE
HEAD
CONT. FIRESTOPPING; REFER TO TYPES BELOW
FOR EXACT DESCRIPTION
CONT. FIRE STOPPING; REFER TO TYPES
BELOW FOR EXACT DESCRIPTION
TOP OF FLOOR LEVEL TO RECEIVE FINISH
UNLESS INDICATED OTHERWISE
4" NOMINAL CMU
UNDERSIDE OF DECK/STRUCTURE
PAINT CMU AS SCHEDULED REFER TO FINISH
SCHEDULE
PROVIDE 1" CLEAR GAP BETWEEN PLUMBING AND
ONE WALL. DO NOT BRACE BETWEEN STUDS
NOTE: WALL TYPE TO BE COORDINATED WITH SLAB REMOVAL.
ADDITIONAL LAYER 5/8" GYP. BD. ON EACH SIDE
FOR 2 HR PARTITIONS; REFER TO TYPES BELOW
FOR EXACT DESCRIPTION
NOTE: SEE STRUCT. DWGS FOR WALL-TO-FLOOR CONNECTION.
NOTE: SEE STRUCT. DWGS FOR WALL-TO-FLOOR CONNECTION.
ADDITIONAL LAYER 5/8" GYP. BD. FOR 1 HR
PARTITIONS, SECURE WITH A LAYER OF SETTING-
TYPE JOINT COMPOUND; REFER TO TYPES
BELOW FOR EXACT DESCRIPTION
HINGE
FRAME
METAL STUD
DOOR
FIRE RESISTANT MATERIAL
DOUBLE WALL CONSTRUCTION
TYPE X GYPSUM
SCALE
DATE:
DRAWN BY:
CHECKED BY:
PROJECT #
THIS DRAWING IS AN INSTRUMENT OF
SERVICE AND SHALL REMAIN THE
PROPERTY OF THE ARCHITECT. NO
PART OF THIS DOCUMENT SHALL BE
REPRODUCED OR TRANSMITTED IN
ANY FORM, ELECTRONICALLY OR
MECHANICALLY, FOR ANY PURPOSE,
WITHOUT THE EXPRESS WRITTEN
PERMISSION OF THE ARCHITECT.
M
A R
IE
T
T A
S T
R E
E T
N
W U
N
IT
A
T L A
N T
A
G E
O R
G
IA
T
F w w w .s iz e m o re g ro u p
.c o m
S
IZ
E
M O
R E
G R
O U
P
12/12/25
As indicated
3/5/2026 11:41:29 AMAutodesk Docs://24260FLOLEC_Floyd_County_Law_Enforcement_Center/24260SLOYLEC_Floyd_County_LEC.rvt
G400
PARTITION
TYPES
Checker
Author
12/12/25
24260FLOLEC
F L O
Y D
C O
U N
T Y
L E
C R
E N
O V
A T
IO
N
G
O V
E R
N M
E N
T P
L A
Z A
R O
M E
G
A
100% CONSTRUCTION DOCUMENTS
3" = 1'-0"G400
2 HEAD WALL DETAILS AT STEEL DECK A - 1 & 2 HR
3" = 1'-0"G400
3 HEAD WALL DETAILS AT STEEL DECK B - 1 & 2 HR
WALL TYPE - CONCRETE MASONRY UNIT CHASE PARTITION
TAG
WIDTH FIRE SOUND MODIFIER
TTL CORE RATING TEST STC TEST SAB
0M1914A 1'-7 1/4" 8"
WALL TYPE - METAL FRAMED FURRING PARTITION - (1) LAYER GYPSUM
BOARD, ONE SIDE ONLY
TAG
WIDTH FIRE SOUND MODIFIER
TTL CORE RATING TEST STC TEST SAB
0F414 4 1/4" 3 5/8"
0F414AS 4 1/4" 3 5/8"
1F478AS 4 7/8" 3 5/8" 1-HR V497
WALL TYPE - METAL FRAMED FURRING CHANNEL PARTITION - (1) LAYER
GYPSUM BOARD, ONE SIDE ONLY
TAG
WIDTH FIRE SOUND MODIFIER
TTL CORE RATING TEST STC TEST SAB
WALL TYPE - METAL FRAMED PARTITION - (1) LAYER GYPSUM BOARD, EACH
SIDE
TAG
WIDTH FIRE SOUND MODIFIER
TTL CORE RATING TEST STC TEST SAB
0S478 4 7/8" 3 5/8" U419 40 USG-860808 0"
0S478AS 4 7/8" 3 5/8" U419 50 CK 654-40 3 5/8"
0S478S 4 7/8" 3 5/8" U419 50 CK 654-40 3 5/8"
1S478AS 4 7/8" 3 5/8" 1-HR U419 50 CK 654-40 3 5/8"
2S618A 6 1/8" 3 5/8" 2-HR U419
WALL TYPE - METAL FRAMED CHASE PARTITION - (1) LAYER GYPSUM
BOARD, BOTH SIDES
TAG
WIDTH FIRE SOUND MODIFIER
TTL CORE RATING TEST STC TEST SAB
0C658AS 1'-4 1/2" 8" 60 TL-93-309 3 5/8"
WALL TYPE - METAL FRAMED SHAFT PARTITION - (1) LAYER SHAFT LINER ON
SHAFT SIDE WITH (1) LAYER GYPSUM BOARD ON THE OTHER SIDE
TAG
WIDTH FIRE SOUND MODIFIER
TTL CORE RATING TEST STC TEST SAB
1X414A 4 1/8" 4" 1-HR U336, V473
2X434A 4 3/4" 4" 2-HR U415
WALL TYPE - CONCRETE MASONRY UNIT
TAG
WIDTH FIRE SOUND MODIFIER
TTL CORE RATING TEST STC TEST SAB
0M758A 7 5/8" 7 5/8"
1M758A 7 5/8" 7 5/8" 2-HR U905
WALL TYPE - CONCRETE MASONRY UNIT - (1) LAYER GYPSUM BOARD, ONE
SIDE ONLY
TAG
WIDTH FIRE SOUND MODIFIER
TTL CORE RATING TEST STC TEST SAB
1M1034 10 3/4" 2-HR U905
3" = 1'-0"G400
1 FEC RATING @ COURTROOM
WALL TYPE - CONCRETE MASONRY UNIT CHASE PARTITION
TAG
WIDTH FIRE SOUND MODIFIER
TTL CORE RATING TEST STC TEST SAB
0M1914A 1'-7 1/4" 8"
N o
D
E S
C R
IP
T
IO
N
D A
T E
P
R E
-B
ID
A D
D E
N D
U M
/0
/2
A
AV
AX
AZZ
AZ
B
BX
C
CX
D
AW
UP
DOWN
NOT IN SCOPE
NOT IN SCOPE
NOT IN SCOPE
DETENTION
VESTIBULE
STOR
VESTIBULE
FILES
VESTIBULE
MUNCIPAL
COURTROOM
MEN LEDGE
VESTWOMEN'S
LOCKERS
MENS
LOCKERS
OFFICE
TASK
FORCE
ELECTRICAL
ELECTRONICS
CORRIDOR
ELEVATOR
EQUIPMENT
ELEVATOR
TELEPHONE
DATA
JANITOR INTOXILYZER CORRIDOR SERGEANT
DARK ROOM
LABORATORY
EVIDENCE
COURT
CLERK
CORRIDOR
SERGEANT
PUBLIC
WOMEN
VESTIBULE
CORRIDOR
PUBLIC MEN
ID/
PASSPORT
RECORDS
TECH
FILES FILES/
COUNTRY
RECORDS
FILE
SERVER
LOBBY
STAIRS
ELEVATOR
EQUIPMENT
CORRIDOR
FITNESS
RECORD
FITNESS
ROOM
CORRIDORCORRIDOR
VEST
WOMEN
CORRIDOR
PROBATION
STAIR
CITY
RECORDS
A510
RELOCATED PLANTER BOX
S01
S02
1M1034
8'-8"
6' -1
1" E104
E101
1X414A
2X434A
NOTE: MAINTAIN ESSENTIAL DATA LINES &
CONNECTIONS FOR DURATION OF DEMOLITION &
CONSTRUCTION (TO BE COORDINATED W/ OWNER)
11' - 10"
DEMO CONCRETE AS NEEDED
FOR INSTALLATION OF HELICAL
PIERS. REPAIR AND INFILL TO
MATCH EXISTING SLOPE,
PATTERN AND THICKNESS
AFTER INSTALLATION. STRUCT.
DWGS.
PROVIDE FIREMAN'S
EMERGENCY KEY BOX.
(KNOXBOX 3200)
ALIGN
NOTE: DEMO AS NEEDED TO INSTALL NEW STRUCTURE
UNDERNEATH PROPOSED HOLDING CELLS ON 2ND LEVEL.
SALVAGE FIXTURES, PARTITIONS, CEILING GRID, LIGHT
FIXTURES, AND FLOORING TO BE REINSTALLED AFTER
INSTALLATION OF STRUCTURE.
HELICAL PIER LOCATIONS. SEE
STRUCT. DWGS.
C R
C R
2S618A
KEY PAD AT ELEVATOR DOOR - SEE AV DRAWINGS
1. CORRIDOR PARTITIONS, SMOKESTOP PARTITIONS, HORIZONTAL EXIT
PARTITIONS, EXIT ENCLOSURES, AND FIRE WALLS SHALL BE
EFFECTIVELY AND PERMANENTLY IDENTIFIED WITH SIGNS OR
STENCILING ABOVE ANY DECORATIVE CEILING AND / OR IN CONCEALED
SPACE WITH LETTERS "A" MINIMUM OF TWO INCHES HIGH ON A
CONTRASTING BACKGROUND SPACED A MAXIMUM OF TWELVE FEET ON
CENTER WITH A MINIMUM OF ONE PER WALL OR BARRIER. THE HOURLY
FIRE RATING SHALL BE INCLUDED ON ALL RATED BARRIER OR WALLS.
SUGGESTED WORDING ( ) HOUR -- FIRE AND SMOKE BARRIER-PROTECT
ALL OPENINGS.
2. ALL VERTICAL PIPING EXPOSED IN ROOMS SHALL BE FURRED WITH
SAME MATERIAL AS ADJACENT WALLS. EXCEPTIONS ARE: MECHANICAL
ROOMS, ELECTRICAL ROOMS, TELEPHONE ROOMS.
3. METAL STUD PARTITIONS BEHIND ALL PLUMBING AND OTHER FIXTURES
SHALL BE BRACED TO STRUCTURE WHERE REQUIRED TO SUPPORT THE
EQUIPMENT PROVIDED.
4. DO NOT SCALE DRAWINGS. ALL DIMENSIONS AND CONDITIONS
INDICATED IN THESE DOCUMENTS MUST BE FIELD VERIFIED PRIOR TO
CONSTRUCTION. FOR DIMENSIONS NOT SHOWN OR IN QUESTION,
6. NEW GYPSUM BOARD CONSTRUCTION MEETING EXISTING GYPSUM
BOARD CONSTRUCTION IN THE SAME SHALL BE FLUSH WITH NO
VISIBLE JOINTS SHOWING.
7. PROVIDE COAT HOOK BEHIND DOORS IN ALL PRIVATE OFFICES, SINGLE
HOOK TYPE.
8. DO NOT SCALE DRAWINGS - USE DIMENSIONS ONLY.
9. UNLESS OTHERWISE NOTED, INTERIOR PARTITION DIMENSIONS ARE
GIVEN FACE OF FINISH SURFACE TO FACE OF FINISH SURFACE.
10. ELECTRIC PANELS, ALARM BOXES, FIRE EQUIPMENT CABINETS AND
OTHER RECESSED BOXES GREATER THAN 16 SQUARE INCHES THAT
ARE LOCATED IN RATED WALLS SHALL BE BACKED BY GYPSUM
WALLBOARD LAYERS SUFFICIENT TO MAINTAIN THE DESIGNATED
RATING.
11. ALL EXISTING WORK, FURNISHINGS, EQUIPMENT OR MATERIAL TO
REMAIN THAT ARE DAMAGED BY CONTRACTOR'S OPERATION UNDER
SPACING OF METAL STUDS FOR ALL CONDITIONS.
13. CEILING ACCESS PANELS SHALL BE PROVIDED IN NON-ACCESSABLE
C. MIXING BOXES
D. POWER OPERATED DAMPERS
E. ACCESS PANELS IN DUCTWORK
F. VOLUME AND BALANCING DEVICES
G. WATER FLOW SWITCHES
H. SPRINKLER SYSTEM DRAINS AND TEST CONNECTIONS
I. PRESSURE SWITCHES
14. ALL FURNITURE BY OTHERS; NOT IN CONTRACT (N.I.C.) U.N.O.
15. ALL GYPSUM BOARD SHALL BE 5/8" THICK; PROVIDE CORNER
REINFORCEMENT AT ALL EXPOSED OUTSIDE CORNERS. EXCEPTION -
GYPSUM BOARD MAY BE ALTERNATE THICKNESS AT CONDITIONS
REQUIRING NEW CONSTRUCTION TO BE FLUSH WITH EXISTING.
16. PROVIDE SOLID WOOD BLOCKING INSIDE PARTITIONS FOR SECURING
WALL HUNG CABINETS/MILLWORK, SHELVING AND WALL HUNG
ACCESSORIES.
17. ALL DRYWALL FINISH WORK TO BE FINISH LEVEL 4, U.N.O.
18. ALL INTERIOR PARTITIONS TO BE TYPE 0S478, U.N.O.
19. ALL ANGLES ARE 90 DEGREES, U.N.O.
20. WHEN DIFFERENT PARTITION TYPES ARE LOCATED ADJACENT TO ONE
ANOTHER, THE FINISHED FACES OF THE PARTITIONS SHALL BE ALIGNED
AND FLUSH, U.N.O.
21. LOCATE EDGE OF DOOR OPENINGS 6" FROM INSIDE FACE OF ADJACENT
PARTITION, U.N.O.
22. CONTRACTOR TO PATCH ALL HOLES, SAND AND PAINT ALL WALLS
WITHIN SCOPE.
23. HOLDINGS CELLS TO BE ENTIRELY TAMPER PROOF AND LIGATURE FREE.
24. HOLDING CELL BENCHES TO BE:
DDS DETENTION BED 7504L/R-M5
POWDER COATED
EXISTING CONSTRUCTION TO REMAIN
NEW PARTITION
NEW PARTITION (MASONRY)
SCALE
DATE:
DRAWN BY:
CHECKED BY:
PROJECT #
THIS DRAWING IS AN INSTRUMENT OF
SERVICE AND SHALL REMAIN THE
PROPERTY OF THE ARCHITECT. NO
PART OF THIS DOCUMENT SHALL BE
REPRODUCED OR TRANSMITTED IN
ANY FORM, ELECTRONICALLY OR
MECHANICALLY, FOR ANY PURPOSE,
WITHOUT THE EXPRESS WRITTEN
PERMISSION OF THE ARCHITECT.
M
A R
IE
T
T A
S T
R E
E T
N
W U
N
IT
A
T L A
N T
A
G E
O R
G
IA
T
F w w w .s iz e m o re g ro u p
.c o m
S
IZ
E
M O
R E
G R
O U
P
12/12/25
1/8" = 1'-0"
3/5/2026 11:41:06 AMAutodesk Docs://24260FLOLEC_Floyd_County_Law_Enforcement_Center/24260SLOYLEC_Floyd_County_LEC.rvt
A100
OVERALL
PROPOSED
FLOOR PLANS –
1ST FLOOR
SMG
IDV
12/12/25
24260FLOLEC
F L O
Y D
C O
U N
T Y
L E
C R
E N
O V
A T
IO
N
G
O V
E R
N M
E N
T P
L A
Z A
R O
M E
G
A
100% CONSTRUCTION DOCUMENTS
1/8" = 1'-0"A100
1 PROPOSED FLOOR PLANS - 1ST FLOOR
N
0 40' 60' 80'20'
Graphic Scale: 1 inch = 20 feet
GENERAL NOTES
LEGEND
N o
D
E S
C R
IP
T
IO
N
D A
T E
P
R E
-B
ID
A D
D E
N D
U M
/0
/2
DN
DN
1 1.9 2 3 4 5 5.5 6 6.2 6.4 7 7.5 7.9 8 8.3 8.5 8.8 9
A
AV
AX
AZZ
AZ
B
BX
C
CX
D
E
AW
SHERIFF
OFFICE
HOLDING
254A
COPY/PRINT/DOCUMENT
ASSEMBLY
LOBBY
STAIR
MEN'S RR
UP
DOWN
DOWN
HOLDING
254B
COURTROOM
SEATING
259B
ALIGN
ALIGN
A210
OFFICE
PUBLIC DEF.
STORAGE
CORRIDOR
ATTORNEY
MTG.
EQUIPMENT
STORAGE
PROBATION
CORRIDOR
RECEPTION
DEP. CLERK
DEP. CLERK
DEP. CLERK
CLERK
PROBATION
PROBATION
ATTORNEY
MTG
WOMEN'S
RR
WOMEN
MEN
JANITOR
OFFICE
ATTORNEY
MTG
COMMUNICATION
ROOM
BREAK
ROOM
SUPPLY
EQUIPMENT
SUPERVISOR
CONFERENCE
DIRECTORDIRECTOR
SECRETARY
CLOSET
CLOSET
TOILET
TOILET
OFFICE
LOBBY
OFFICE
OFFICE OFFICE OFFICE
ELECT.
TELEPHONE
/DATA
235A
BREAKROOM
STOR.
SHERIFF
BULLPEN
246A
STORAGE OFFICE
CORRIDOR
ELEVATOR
STAIR
BREAK
ROOM
CORRIDOR
CONFERENCE
ROOM
OFFICE
OFFICE
OFFICE
A400
A400
254A 254B
256A
256B
251B
251A
259A
E204
E263 E264
E272
E271
E265
E257
E282 E281 E280 E279 E278 E277 E276 E275 E274
E273
STORAGE
E258
SHERIFF
SUPERVISOR
246B
A510
0S478
0M758A
0M758A
0S478
0S478AS
/2
A210
1M1034NOT IN SCOPE
NOT IN SCOPE
0M758A
17'-7"2" 2"
7'-4"
0F414AS A402
ALIGN
A L
IG
N
0S478S
EQ EQ
13'-2"
259C
1X414A
2X434A
5'-3"
15'-6 1/2" 0 S
F
A
S
F
A
S
F
A
S
1F478AS
S
A
S
F
A
S
S
0S478
0C658AS
0S478
0S478S
0S478S
0S478S
8'-0"
0M1914A
259B E205
34H
42H
NOTE: 911 CALL CENTER TO REMAIN OPERATIONAL
FOR DURATION OF DEMOLITION & CONSTRUCTION
NOTE: MAINTAIN ESSENTIAL DATA LINES &
CONNECTIONS FOR DURATION OF DEMOLITION &
CONSTRUCTION (TO BE COORDINATED W/ OWNER)
6' - 6 1/2"
G400
A210
0S478S
F
S
A401
11' - 3 1/2"
/2 "9' - 6"
" 3' - 5"
A570
9"
INSTALL
ACCESS
DOOR
C R
C R
CR C
R
C R
CR
C R
CR
C R
C R
A210
COURTROOM
259A
C R
C R
C R
C R
CR
11' - 3"
4' - 8"
E232
E233
E267
5' - 3 1/2"
/2
A101
CR
CR
E261
0F414AS
0F414AS
0F414AS
0F414AS
0F414AS
A210
0F414AS
0F414AS
0S478AS
CELL BENCHES
3' - 4" 3' - 4"
1. CORRIDOR PARTITIONS, SMOKESTOP PARTITIONS, HORIZONTAL EXIT
PARTITIONS, EXIT ENCLOSURES, AND FIRE WALLS SHALL BE
EFFECTIVELY AND PERMANENTLY IDENTIFIED WITH SIGNS OR
STENCILING ABOVE ANY DECORATIVE CEILING AND / OR IN CONCEALED
SPACE WITH LETTERS "A" MINIMUM OF TWO INCHES HIGH ON A
CONTRASTING BACKGROUND SPACED A MAXIMUM OF TWELVE FEET ON
CENTER WITH A MINIMUM OF ONE PER WALL OR BARRIER. THE HOURLY
FIRE RATING SHALL BE INCLUDED ON ALL RATED BARRIER OR WALLS.
SUGGESTED WORDING ( ) HOUR -- FIRE AND SMOKE BARRIER-PROTECT
ALL OPENINGS.
2. ALL VERTICAL PIPING EXPOSED IN ROOMS SHALL BE FURRED WITH
SAME MATERIAL AS ADJACENT WALLS. EXCEPTIONS ARE: MECHANICAL
ROOMS, ELECTRICAL ROOMS, TELEPHONE ROOMS.
3. METAL STUD PARTITIONS BEHIND ALL PLUMBING AND OTHER FIXTURES
SHALL BE BRACED TO STRUCTURE WHERE REQUIRED TO SUPPORT THE
EQUIPMENT PROVIDED.
4. DO NOT SCALE DRAWINGS. ALL DIMENSIONS AND CONDITIONS
INDICATED IN THESE DOCUMENTS MUST BE FIELD VERIFIED PRIOR TO
CONSTRUCTION. FOR DIMENSIONS NOT SHOWN OR IN QUESTION,
6. NEW GYPSUM BOARD CONSTRUCTION MEETING EXISTING GYPSUM
BOARD CONSTRUCTION IN THE SAME SHALL BE FLUSH WITH NO
VISIBLE JOINTS SHOWING.
7. PROVIDE COAT HOOK BEHIND DOORS IN ALL PRIVATE OFFICES, SINGLE
HOOK TYPE.
8. DO NOT SCALE DRAWINGS - USE DIMENSIONS ONLY.
9. UNLESS OTHERWISE NOTED, INTERIOR PARTITION DIMENSIONS ARE
GIVEN FACE OF FINISH SURFACE TO FACE OF FINISH SURFACE.
10. ELECTRIC PANELS, ALARM BOXES, FIRE EQUIPMENT CABINETS AND
OTHER RECESSED BOXES GREATER THAN 16 SQUARE INCHES THAT
ARE LOCATED IN RATED WALLS SHALL BE BACKED BY GYPSUM
WALLBOARD LAYERS SUFFICIENT TO MAINTAIN THE DESIGNATED
RATING.
11. ALL EXISTING WORK, FURNISHINGS, EQUIPMENT OR MATERIAL TO
REMAIN THAT ARE DAMAGED BY CONTRACTOR'S OPERATION UNDER
SPACING OF METAL STUDS FOR ALL CONDITIONS.
13. CEILING ACCESS PANELS SHALL BE PROVIDED IN NON-ACCESSABLE
C. MIXING BOXES
D. POWER OPERATED DAMPERS
E. ACCESS PANELS IN DUCTWORK
F. VOLUME AND BALANCING DEVICES
G. WATER FLOW SWITCHES
H. SPRINKLER SYSTEM DRAINS AND TEST CONNECTIONS
I. PRESSURE SWITCHES
14. ALL FURNITURE BY OTHERS; NOT IN CONTRACT (N.I.C.) U.N.O.
15. ALL GYPSUM BOARD SHALL BE 5/8" THICK; PROVIDE CORNER
REINFORCEMENT AT ALL EXPOSED OUTSIDE CORNERS. EXCEPTION -
GYPSUM BOARD MAY BE ALTERNATE THICKNESS AT CONDITIONS
REQUIRING NEW CONSTRUCTION TO BE FLUSH WITH EXISTING.
16. PROVIDE SOLID WOOD BLOCKING INSIDE PARTITIONS FOR SECURING
WALL HUNG CABINETS/MILLWORK, SHELVING AND WALL HUNG
ACCESSORIES.
17. ALL DRYWALL FINISH WORK TO BE FINISH LEVEL 4, U.N.O.
18. ALL INTERIOR PARTITIONS TO BE TYPE 0S478, U.N.O.