ADA_Access_Controls_at_FSU_Charter.pdf

PDF 3 MB Posted

Attached to
FSU Charter School ADA Access Controls
Solicitation number
PSPW-24-08
Issued by
Broward County, Florida

About this file

These electrical plan documents are for the Pembroke Shores Charter School Access Control project located at 501 SW 172nd Avenue in Pembroke Pines, Florida, prepared by INGEMEL S.A. engineering firm. The scope of work consists of installing five (5) new electrical outlets for door access control systems across Buildings A, B, and C on the first and second floors. The project involves integrating these new access control systems with the existing access control infrastructure of the school, with the electrical contractor responsible for coordinating all work with the City of Pembroke Pines Project Manager.

The electrical plans detail specific technical requirements including compliance with multiple building codes such as the Florida Building Code (8th Edition - 2023), Florida Fire Prevention Code, National Electrical Code (2020 Edition), and other relevant standards. The electrical specifications mandate that all new equipment be installed according to manufacturer recommendations, all conductors be copper with appropriate insulation, conduits meet specific material requirements, and all work be guaranteed free from defects for one year from final acceptance. The project drawings include detailed electrical symbols, panel schedules, key notes, and site plans showing the precise locations of the proposed access control system modifications.

View the file

Other files

Show all 13

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

BRANCH CIRCUIT HOMERUN TO PANEL BOARD

NUMBER INDICATE CIRCUIT DESIGNATIONP-XX

ELECTRICAL SYMBOLS

EXISTING ELECTRICAL PANEL

JUNTION BOX

ELECTRICAL KEY NOTES

1 ALL WORK SHALL BE COORDINATED WITH CITY OF PEMBOKE PINES

PROJECT MANAGER.

2 ALL WORK SHALL BE PERFORMED IN A CLEAN MANNER. ALL WORK

SHALL BE COORDINATED WITH OWNER'S PROJECT MANAGER TO

MINIMIZE ANY DISTURBANCE TO OTHER AREAS OF THE BUILDING

WHICH ARE TO REMAIN IN OPERATION.

3 THESE DRAWINGS ARE DIAGRAMMATICAL IN NATURE AND

REPRESENT EXISTING CONDITIONS BASED ON AVAILABLE

DRAWINGS AND SITE OBSERVATIONS. CONTRACTOR IS

RESPONSIBLE FOR FIELD VERIFICATION OF ALL ACTUAL

CONDITIONS, FOR EXACT LOCATIONS AND SIZES OF PIPING,

CONDUIT, WIRES, EQUIPMENT, ETC.

4 EXISTING WORK TO REMAIN SHALL BE PROTECTED FROM DAMAGE.

WORK DAMAGED BY THE CONTRACTOR SHALL BE REPAIRED TO

MATCH EXISTING WORK.

5 NEW JUNCTION BOX ON TOP OF THE DOOR FOR THE INSTALLATION

OF A NEW ACCES DOOR CONTROL SYSTEM. ELECTRICAL

CONTRACTOR SHALL COORINATE THE LOCATION WITH ACCES

CONTROL SYSTEM CONTRACTOR (TYPICAL).

SCOPE OF WORK

THE SCOPE OF WORK OF THIS PROJECT CONSISTS OF THE ADDITION OF

FIVE ELECTRICAL OUTLETS FOR THE INSTALLATION OF FIVE (5) NEW DOOR

ACCESS CONTROL.

THE INSTALLATION OF THE DOOR ACCESS CONTROL AND THE

INTEGRATION OF THEM TO THE EXISTING ACCES CONTROL SYSTEM OF THE

SCHOOL WILL BE THE CONTRACTOR'S RESPONSABILITY. THE DOOR

ACCESS CONTROL CONTRACTOR SHALL COORDINATE ALL WORK WITH

CITY OF PEMBROKE PINES PROJECT MANAGER.

J

BUILDING CODE: FLORIDA BUILDING CODE - 8TH EDITION - 2023

FIRE/LIFE SAFETY CODE: FLORIDA FIRE PREVENTION CODE - 8TH EDITION -

ENERGY CODE: FLORIDA ENERGY CONSERVATION CODE - 8TH

EDITION-2023

NFPA 70: NATIONAL ELECTRICAL CODE - 2020 EDITION

NFPA 72: NATIONAL FIRE ALARM CODE - 2019 EDITION

NFPA 101: LIFE SAFETY CODE - 2021 EDITION

CODE REQUIREMENTS SHALL BE INCLUSIVE OF ALL ADDENDUMS AND

CLARIFICATIONS ISSUED UP TO THE TIME WHEN THE BUILDING PERMIT IS

GRANTED. THE LISTED CODES AND PERMIT STANDARDS SHALL NOT BE

CONSTRUED TO BE THE ONLY APPLICABLE CODES AND STANDARDS

GOVERNING THIS PROJECT. THE GENERAL CONTRACTOR, ALL

SUB-CONTRACTORS AND SUPPLIERS SHALL VERIFY AND ADHERE TO THE

REQUIREMENTS OF ALL OF THE CODES AND STANDARDS THAT GOVERN

AND PERTAIN TO THEIR PRESCRIBED SCOPE OF WORK.

APPLICABLE CODES

ELECTRICAL NOTES

1. ALL NEW EQUIPMENT INSTALLED IN THIS PROJECT SHALL BE INSTALLED IN

ACCORDANCE WITH MANUFACTURER'S RECOMMENDED INSTALLATION INSTRUCTIONS.

2. CONTRACTOR TO ASSURE THAT PROPER CLEARANCE (AS PER MANUF.

RECOMMENDATIONS) IS PROVIDED AROUND ALL NEW EQUIPMENT FOR SERVICING

AND REPLACEMENT PURPOSES.

3. EQUIPMENT VOLTAGES SHALL BE VERIFIED PRIOR TO ANY INSTALLATION.

4. ANY CHANGES FROM DESIGN SHALL REQUIRE THE CONTRACTOR TO PREPARE A

WRITTEN REQUEST FOR SAID CHANGE WHICH WILL BE SENT TO OWNER'S

REPRESENTATIVE FOR REVIEW.

5. ALL MATERIALS SHALL BE NEW AND BEAR UNDERWRITERS' LABELS WHERE

APPLICABLE.

6. ALL CONDUCTORS SHALL BE COPPER WITH THW/THWN INSULATION. ALL

CONDUCTORS #10 AND SMALLER MAY BE SOLID. ALL CONDUCTORS #8 AND LARGER

SHALL BE STRANDED TYPE. ALL CONDUCTORS SHALL BE IN CONDUIT. OUTDOOR

UNDERGROUND CONDUITS SHALL BE IN PVC SCHEDULE-40., MINIMUM COVER SHALL

BE 18". OUTDOOR ABOVEGROUND CONDUITS SHALL BE RIGID. INTERIOR EXPOSED OR

CONCEALED CONDUIT SHALL BE EMT. STEEL SET-SCREW FITTINGS. ALL WIRING

INSTALLATION SHALL BE MADE AS REQUIRED BY NEC Art. 300.

7. THE WORK INCLUDED CONSISTS OF ALL SUPERVISION, LABOR, MATERIALS,

EQUIPMENT FACILITIES, AND INSTALLATION REQUIRED FOR THE COMPLETE

SATISFACTORY AND APPROVED ELECTRICAL SYSTEM AS INDICATED ON THE

DRAWINGS AND CALLED FOR IN THIS SPECIFICATION, OR AS MAY BE REASONABLY

IMPLIED BY EITHER.

8. LABEL ALL EQUIPMENT (DISCONNECT SWITCHES, CIRCUIT BREAKERS, CONTROLS

ETC.) WITH ENGRAVED LAMINATED PLASTIC.

9. CONTRACTOR SHALL PAY FOR ALL PERMITS, FEES, INSPECTIONS AND TESTING.

CONTRACTOR SHALL OBTAIN PERMITS AND APPROVED SUBMITTALS PRIOR TO

BEGINNING WORK OR ORDERING EQUIPMENT.

10. OUTLET BOXES SHALL BE PRESSED STEEL IN DRY LOCATIONS. CAST ALLOY WITH

THREADED HUBS IN WET OR DAMP LOCATIONS AND SPECIAL ENCLOSURES FOR

OTHER CLASSIFIED AREAS.

11. ELECTRICAL SYSTEM SHALL BE COMPLETE AND EFFECTIVELY GROUNDED AS PER

N.E.C ART. 250.

12. CONTRACTOR SHALL BE RESPONSIBLE FOR ALL CUTTING AND PATCHING REQUIRED

OF HIS WORK.

13. THE CONTRACTOR SHALL FIELD VERIFY ALL DIMENSIONS AND VERIFY WITH OTHER

TRADES PRIOR TO PROCEEDING WITH ANY WORK. WHERE DISCREPANCIES OCCUR

BETWEEN THESE DOCUMENTS AND ACTUAL CONDITIONS, THE DISCREPANCY SHALL

BE REPORTED TO OWNER'S REPRESENTATIVE FOR EXPEDITING AND RESOLUTION.

14. ALL ELECTRICAL CIRCUITS SHALL BE IDENTIFIED AND LABELED IN THE ELECTRICAL

PANEL.

15. THE CONTRACTOR IS REFERRED TO THE MECHANICAL PLANS AND SPECIFICATIONS.

SUCH PLANS AND SPECIFICATIONS ARE TO BE CONSIDERED PART OF THE ELECTRICAL

CONTRACT DOCUMENTS.COORDINATE WITH INTERIOR DESIGNER AND/OR ARCHITECT

FOR EXACT LOCATION AND HEIGHT OF ELECTRICAL OUTLETS.

16. ALL WORK SHALL BE GUARANTEED FREE FROM DEFECTS FOR A PERIOD OF ONE

YEAR FROM DATE OF FINAL ACCEPTANCE.

17. THE ELECTRICAL INSTALLATION SHALL MEET THE APPROVAL OF THE OWNER'S

REPRESENTATIVES BEFORE ACCEPTANCE.

18. LABEL ALL JUNCTION BOXES ABOVE CEILINGS AND IN WALLS WITH PANEL

DESIGNATION AND CIRCUIT NUMBER.

19. SUPPORT ALL BOXES AND CONDUIT ABOVE CEILING INDEPENDENTLY. DO NOT

SUPPORT ANY BOX OR CONDUIT FROM SUSPENDED CEILING SYSTEM.

20. INSTALL ALL EXPOSED CONDUIT AND WIREWAYS PARALLEL AND PERPENDICULAR TO

BUILDING SURFACES.

21. ELECTRICAL EQUIPMENT SHALL BE LISTED AND LABELED FOR THE QUALIFIED USE.

ELECTRICAL

ROOM

ELEV.

LOBBY

BREEZEWAY

WAITING

GR-2

CLASSROOM

MEDIA

RESOURCE

GR-2

CLASSROOM

MULTI

PURPOSE

BUILDING

A

BUILDING

B

J

EXISTING

PANEL LKB

LOCATION

J

J

LKB-12

LKB-12

LKB-14

D1

D3

D2 5

APPROVED:

DRAWN:

SCALE :

OF:

PROJECT NO.:

DWG FILE:

DATE:

DATEREV No. DESCRIPTION

This drawing and the information and design application herein contained is property of INGEMEL S.A. The information contained herein may not be used or reproduced in any manner without written permission of INGEMEL S.A.

LEGENDS:

SHEET:

SHEET No.:

CONTENTS:

PROJECT ADDRESS:

PROJECT:

P.E. SEAL

TO THE BEST OF OUR KNOWLEDGE THE

PLANS AND SPECIFICATIONS COMPLY WITH

THE APPLICABLE MINIMUM BUILDING CODE

20871 Johnson Street, Suite 115 Phone: (954) 318-2264 Fax: (954) 450-7216

Pembroke Pines, Florida 33029

State of Florida CA No. 9113

PEMBROKE SHORES

CHARTER SCHOOL

ACCESS CONTROL

501 SW 172nd Avenue

Pembroke Pines, FL 33029

INDICATED 08-15-24

24-108

09-24-24 ISSUED FOR PERMIT-

ELECTRICAL PLAN

BLDG A & BLDG B

1ST FLOOR

G. PACHECO 24-108E1

P. ARIAS

E -1

1 2

Pedro Arias, P.E.

Florida Registration. No. 63813

SCALE: 3/16" = 1'-0"

ELECTRICAL PLAN - BLDG A & BLDG B - 1ST FLOOR

N.T.S.

SITE PLAN

N.T.S.

KEY PLAN

BUILDING

B

BUILDING

A BUILDING

C

AutoCAD SHX Text

WH

AutoCAD SHX Text S7

ELECTRICAL KEY NOTES

1 ALL WORK SHALL BE COORDINATED WITH CITY OF PEMBOKE PINES

PROJECT MANAGER.

2 ALL WORK SHALL BE PERFORMED IN A CLEAN MANNER. ALL WORK

SHALL BE COORDINATED WITH OWNER'S PROJECT MANAGER TO

MINIMIZE ANY DISTURBANCE TO OTHER AREAS OF THE BUILDING

WHICH ARE TO REMAIN IN OPERATION.

3 THESE DRAWINGS ARE DIAGRAMMATICAL IN NATURE AND

REPRESENT EXISTING CONDITIONS BASED ON AVAILABLE

DRAWINGS AND SITE OBSERVATIONS. CONTRACTOR IS

RESPONSIBLE FOR FIELD VERIFICATION OF ALL ACTUAL

CONDITIONS, FOR EXACT LOCATIONS AND SIZES OF PIPING,

CONDUIT, WIRES, EQUIPMENT, ETC.

4 EXISTING WORK TO REMAIN SHALL BE PROTECTED FROM DAMAGE.

WORK DAMAGED BY THE CONTRACTOR SHALL BE REPAIRED TO

MATCH EXISTING WORK.

5 NEW JUNCTION BOX ON TOP OF THE DOOR FOR THE INSTALLATION

OF A NEW ACCES DOOR CONTROL SYSTEM. ELECTRICAL

CONTRACTOR SHALL COORINATE THE LOCATION WITH ACCES

CONTROL SYSTEM CONTRACTOR (TYPICAL).

ELECTRICAL

ROOM

116ELEV.

EQ.

CLASSROOM

BUILDING

C

EXISTING

PANEL LKC

LOCATION

J

CLASSROOM

CLASSROOM

SCIENCE

CLASSROOM

ENTRY

100 ENTRY

100 B

CLASSROOM

CLASSROOM

CLASSROOM

CLASSROOM

CORRIDOR

100A4321D5

LKC-39

BUILDING

C

CORRIDOR

200A

CLASSROOM

CLASSROOM

CLASSROOM

CLASSROOM

CLASSROOM

CLASSROOM

CLASSROOM

SCIENCE

CLASSROOM

ENTRY

200 ENTRY

200 B J

LKC-39

D4

APPROVED:

DRAWN:

SCALE :

OF:

PROJECT NO.:

DWG FILE:

DATE:

DATEREV No. DESCRIPTION

This drawing and the information and design application herein contained is property of INGEMEL S.A. The information contained herein may not be used or reproduced in any manner without written permission of INGEMEL S.A.

LEGENDS:

SHEET:

SHEET No.:

CONTENTS:

PROJECT ADDRESS:

PROJECT:

P.E. SEAL

TO THE BEST OF OUR KNOWLEDGE THE

PLANS AND SPECIFICATIONS COMPLY WITH

THE APPLICABLE MINIMUM BUILDING CODE

20871 Johnson Street, Suite 115 Phone: (954) 318-2264 Fax: (954) 450-7216

Pembroke Pines, Florida 33029

State of Florida CA No. 9113

PEMBROKE SHORES

CHARTER SCHOOL

ACCESS CONTROL

501 SW 172nd Avenue

Pembroke Pines, FL 33029

INDICATED 08-15-24

24-108

09-24-24 ISSUED FOR PERMIT-

ELECTRICAL PLAN

BLDG C

1ST & 2ND FLOOR

G. PACHECO 24-108E2

P. ARIAS

E -2

2 2

Pedro Arias, P.E.

Florida Registration. No. 63813

SCALE: 1/8" = 1'-0"

ELECTRICAL PLAN - BLDG C - 1ST FLOOR

SCALE: 1/8" = 1'-0"

ELECTRICAL PLAN - BLDG C - 2ND FLOOR

N.T.S.

KEY PLAN

BUILDING

B

BUILDING

A BUILDING

C

AutoCAD SHX Text

UP

AutoCAD SHX Text

UP

AutoCAD SHX Text

DN.

AutoCAD SHX Text

DN.

24-108 E-1-R0.pdf
Sheets and Views
E-1
24-108 E-2-R0.pdf
Sheets and Views
E-2

File details come from the government source that posted it. Updated .