This is a flexible sheet roofing submittal letter from Pickens Roofing & Sheet Metals, Inc. dated June 16, 1994, addressing roofing materials for the Greer Weather Forecast Nexrad Office Building project managed by Norungolo-Davis, Inc.
The submittal details four primary components per Item 69, Section 07530: (A) installation of 0.5 permethylene vapor retarder sheeting laid loose under 1/2" type "X" fire-resistant gypsum board by Georgia Pacific; (B) installation of Manville UltraGard Isocyanurate roof insulation, 4" thick, screw-to-deck with fasteners per manufacturer recommendations; (C) installation of white 60 mils adhered EPDM roof membrane by Manville; and (D) provision of a 10-year Manville guarantee and 20-year membrane material guarantee upon job completion. The letter requests architect approval of these submittals to proceed with material ordering, with a separate letter to follow regarding Item 67 flashing and sheet metal. The submittal includes supporting documentation: roof system specifications, sample of Manville roofing system, and warranty specimens for both 10-year and 20-year guarantees. The document is marked as received by Fluor Daniel, Inc. on June 23, 1994.