A10_Atch 5_Drawings_signed.pdf
PDF 9 MB Posted
- Attached to
- Water Treatment Facility
- Solicitation number
- 1240LN26Q0003
- Issued by
-
Department of Agriculture Forest Service
About this file
These are construction drawings and specifications for the Monument Fire Center Water Treatment Improvement project, a federal contract for the U.S. Department of Agriculture Forest Service located in Monument, Colorado (Pikes Peak Ranger District, Rocky Mountain Region). The project involves demolishing an existing water treatment facility building and constructing a new prefabricated treatment building with relocated and new water treatment equipment.
The scope of work includes installation of a complete water treatment system designed for 10 gallons per minute capacity with multiple filtration stages (pre-filter, acid-washed carbon filter, KDF filter, and post-filter), corrosion control via phosphoric acid injection, disinfection via chlorine injection, caustic pH adjustment, and storage in a 6,000-gallon finished water tank. Key equipment includes three peristaltic metering pumps (Stenner S3001 models), three 55-gallon chemical storage tanks, Greensand filters with 12 filter rounds, and process instrumentation including pH analyzers, pressure transmitters, and flow meters. The project requires civil site work including grading, utilities relocation, concrete foundations and entrance pads, erosion control measures, and electrical infrastructure with a new 100-amp primary distribution panel and treatment facility control panel. Mechanical systems include a 3.3 kilowatt unit heater, exhaust fan with louver, and associated HVAC controls. The contract specifies compliance with NSF 61 certification for water contact components, Schedule 80 PVC piping throughout the interior system, and coordination with existing groundwater well and storage tank connections. Construction documents are dated September 10, 2025, and require contractor coordination with the Forest Service contracting officer for final dimensions, material verification, utility locations, and equipment submittals.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Water Treatment QA.pdf | ||
| Amd0002_Water_Treatment_Facility signed.pdf | ||
| A11 -Amd001_Water_Treatment_Facility_001signed.pdf | ||
| A11_Amd001_Atch_1_SOW_Water Treat_rev.pdf | ||
| A10_Atch_1_1240LN26Q0003_Water_Dmg.pdf | ||
| A10_Atch_6_WD_CO20260022.pdf | ||
| A10_Atch_3_ProjectManual_Specs.pdf | ||
| A10_Atch_1_1240LN26Q0003_Water_Dmg.docx | DOCX document | |
| A10_Atch_2_SOW_MFC Water Treatment.docx | DOCX document | |
| A02_Atch 4_Schedule of Items.xlsx | XLSX spreadsheet |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
DATE
RECOMMENDED BY:
FOREST ENGINEER
PROJECT MANAGER
REGIONAL ENGINEER
FOREST SUPERVISOR
ENGINEERING/REGIONAL SPECIALIST [FSP MANAGER]
I HAVE REVIEWED THE TECHNICAL ASPECTS OF THESE DRAWINGS:
APPROVED BY:
THESE DRAWINGS COMPLY WITH THE FOREST PLAN AND PROJECT
SPECIFIC NEPA DOCUMENTATION:
DATE
DATE
DATE
DATE
PROJECT LOCATION
PROJECT ADDRESS
MONUMENT, CO 80132
LATITUDE: 39°05'3.69" N
LONGITUDE: 104°54'19.73" W
INDEX
SHEET TITLE OF SHEET
9/
/2
:0
JC
D N
:\2
8.
EN
V
- U
SD
A
FS
M O
N U
M
EN
T
FI
R E
C
EN
TE
R
W
AT
ER
T R
EA
TM
EN
T
EV
AL
U
AT
IO
N
\D R
AW
IN
G S\
X2
8.
EN
V
- C O
VE
R
S H
EE
T.
D W
G
SHEET
OF
DESIGNER
STAMPS, LOGOS, AND SEALS
PROJECT NAME
DRAWING TITLE
CHECKED
ARCHIVE NO.
SUB SHEET NO.
DATENO.
REVISION / ISSUE
MONUMENT FIRE
CENTER
WATER TREATMENT
PIKE-SAN ISABEL
NATIONAL FORESTS &
CIMARRON AND COMANCHE
NATIONAL GRASSLANDS
PIKES PEAK RANGER DISTRICT
MONUMENT FIRE CENTER
R2
ROCKY MOUNTAIN REGION
9/10/2025 18
DATE
UNITED STATES
DEPARTMENT OF AGRICULTURE
FOREST SERVICE
WYE
KAT
PROJECT LOCATION MONUMENT, CO
TITLE AND INDEX
SHEET
PIKES PEAK RANGER DISTRICT
COLORADO
T1.0 TITLE AND INDEX SHEET
T1.1 LEGEND, NOTES AND ABBREVIATIONS
G1.2 EQUIPMENT RELOCATION
P1.0 TREATMENT BUILDING
P1.1 TREATMENT BUILDING SECTIONS
BID
MITCHELL AVE
MT HERMAN RD
SCHILLING AVE
PROJECT
LOCATION
PD1.0 PROCESS DETAILS
C1.0 CIVIL SITE PLANS
CD1.0 SITE DETAILS
M0.1 MECHANICAL COVER SHEET
M1.0 MECHANICAL FLOOR PLAN
M3.1 MECHANICAL SCHEDULES
E0.1 ELECTRICAL LEGEND
E1.0 ELECTRICAL SITE PLAN
E1.1 ELECTRICAL BUILDING PLAN
E1.2 ELECTRICAL ONE-LINE DIAGRAM
E1.3 ELECTRICAL DETAILS
G1.0 PROCESS AND INSTRUMENTATION LEGEND
G1.1 PROCESS AND INSTRUMENTATION DIAGRAM
N/A
28699 09/10/25
LANDON WIGTON Digitally signed by LANDON WIGTON Date: 2025.11.21 08:07:23 -07'00'
PHILLIP KRIEBLE Digitally signed by PHILLIP KRIEBLE Date: 2025.11.20 13:23:14 -07'00'
GERARDO CHAVARRIA Digitally signed by GERARDO CHAVARRIA Date: 2025.12.01 10:34:34 -07'00'
RYAN NEHL Digitally signed by RYAN NEHL Date: 2025.11.24 10:00:48 -07'00'
KEVIN KHUNG Digitally signed by KEVIN KHUNG Date: 2025.12.01 10:39:04 -07'00'
ABBREVIATIONS DESIGN LEGEND GENERAL NOTES
SURVEY LEGEND
DETAIL MARKER
DETAIL TITLE
DETAIL TITLE
SCALE
C1.0
DETAIL NUMBER IDENTIFICATION
REVISION CLOUD
REVISION NUMBER
DETAIL NUMBER IDENTIFICATION
A SECTION NUMBER IDENTIFICATION
SHEET WHERE THE SECTION IS DRAWN
- INDICATES SAME DRAWING
SECTION CALLOUT
BENCHMARK
MANHOLE
FLARED END SECTION W/ RIPRAP
TEE W/ THRUST BLOCK
BEND W/ THRUST BLOCK
END CAP W/ THRUST BLOCK
GATE VALVE
REDUCER/INCREASER
WATER METER
FIRE HYDRANT
FLOW LINE OF DITCH OR WASH
FENCE
CONCRETE PAVING
PROPOSED SPOT ELEVATION
SIGN W/ POST
EXIST SPOT ELEVATION
SPILL/CATCH CURB TRANSITION
AREA DRAIN
COMBINATION INLET
TYPE R INLET
TYPE 13 FIELD INLET
M
SLOPE ARROW
CURB AND GUTTER
SIDEWALK
HEAVY DUTY ASPHALT PAVING
5.0%
03.54
03.3
LIGHT DUTY ASPHALT PAVING
SIDEWALK CHASE
CURB RAMP
PROPOSED INDEX CONTOUR
PROPOSED INTERMEDIATE CONTOUR
EXIST INDEX CONTOUR
EXIST INTERMEDIATE CONTOUR
PROPERTY LINE
EASEMENT LINE
LIMITS OF WORK
BUILDING ACCESS
LIMITS OF SAWCUT
MATCHLINE
RETAINING WALL
BOULDER/ROCK WALL
PROPOSED BUILDING
ADJACENT PROPERTY LINE/ROW
GRAVEL
CONCRETE
EDGE OF ASPHALT
GRAVEL
FENCE
SIGN
WATER LINE
WATER VALVE
FIRE HYDRANT
SANITARY SEWER LINE
SANITARY SEWER MANHOLE
STORM DRAINAGE LINE
STORM DRAINAGE MANHOLE
CURB INLET
UNDERGROUND ELECTRICAL LINE
ELECTRICAL TRANSFORMER
LIGHT POLE
DECORATIVE LIGHT
FIBEROPTIC LINE
TELEPHONE LINE
TELEPHONE RISER
GAS LINE
INDICATION OF ACCESS
ELECTRICAL RISER
ELECTRIC VAULT
MAILBOX
WATER METER
OVERHEAD ELECTRICAL LINE
GUY WIRE
ELECTRICAL POLE
BOULDER
GUARDRAIL
BOLLARD
BUILDING
CONIFEROUS TREE (TRUNK
DIAMETER/DRIP LINE RADIUS)
DECIDUOUS TREE (TRUNK
DIAMETER/DRIP LINE RADIUS)
NOTE: SHADED ITEMS REPRESENT EXIST FEATURES
FOUND MONUMENT
BENCHMARK AS DESCRIBED
FOUND MONUMENT
AS MEASURED AT TIME OF SURVEY
PLAT
TEST CP
UTILITY LOCATED FROM MAP
CALCULATED FROM RECORD AND AS
MEASURED INFORMATION
RECORDED
HEAVY DUTY CONCRETE PAVING
FH FIRE HYDRANT
AC
ADDL
ADDM
ADJ
AL
ALT
AMT
ARCH
ASPH
ASSY
ASPHALTIC CONCRETE PAVING
ADDITIONAL
ADDENDUM
ADJUSTABLE
ALUMINUM
ALTERNATE
AMOUNT
ARCHITECT(URAL)
ASPHALT
ASSEMBLY
APPROXIMATEAPPROX
ASYM
BC
BFV
BLDG
BLK
BM
BS
BSMT
ASYMMETRICAL
BACK OF CURB
BUTTERFLY VALVE
BUILDING
BLOCK
BENCH MARK
BACKSIGHT
BASEMENT
CB
CCW
CIP
CJ
CL
CLR
CMP
CO
CONC
CONST
CONT
CR
DIA
DIP
DN
DR
CATCH BASIN
COUNTER CLOCKWISE
CAST IRON PIPE
CONSTRUCTION JOINT
CENTER LINE OR CHAIN LINK
CLEAR
CORRUGATED METAL PIPE
CLEANOUT
CONCRETE
CONSTRUCTION
CONTINUOUS(ATION)
CONCENTRIC REDUCER
DIAMETER
DUCTILE IRON PIPE
DOWN
DRAIN
DWG
DWL
EL
ELB
ELEC
ENGR
EQUIV
ESMT
EST
EW
EXP JT
EXIST
FND
DRAWING
DOWEL
ELEVATION
ELBOW
ELECTRICAL
ENGINEER
EQUIPMENT
EQUIVALENT
EASEMENT
ESTIMATE
EACH WAY
EXPANSION JOINT
EXISTING
FOUNDATION
EQUIP
FES
FG
FL
FN
FOC
FPM
FPS
FTG
G
GAL
GALV
GIP
GND
GPD
GPM
GV
FLARED END SECTION
FINISH GRADE
FLOW LINE
FENCE
FACE OF CONCRETE
FEET PER MINUTE
FEET PER SECOND
FOOTING OR FITTING
GAS
GALLON
GALVANIZED
GALVANIZED IRON PIPE
GROUND
GALLONS PER DAY
GALLONS PER MINUTE
GATE VALVE
HB
HDWL
HNDRL
HORIZ
HR
HVAC
HWL
HWY
HYD
ID
IN
INSUL
INV
HOSE BIB
HEADWALL
HAND RAIL
HORIZONTAL
HOUR
HEATING, VENTILATION,
HIGH WATER LINE
HIGHWAY
HYDRANT
INSIDE DIAMETER
INLET
INSULATION
INVERT
KNOCKOUTKO
KPL
KWY
L
LF
LP
LT
MAINT
MAN
MATL
MAX
MECH
MFR
KICK PLATE
KEYWAY
LEFT OR LITER
LINEAR FOOT
LOW POINT
LIGHT
MAINTENANCE
MANUAL
MATERIAL
MAXIMUM
MECHANICAL
MANUFACTURER
AIR CONDITIONING
MH
MIN
MISC
MJ
NA
NIC
NTS
OC
OD
OPP
OPT
MANHOLE
MINIMUM
MISCELLANEOUS
MECHANICAL JOINT
NOT APPLICABLE
NOT IN CONTRACT
NOT TO SCALE
ON CENTER
OUTSIDE DIAMETER
OPPOSITE
OPTIONAL
POINT OF CURVATURE
POINT OF INTERSECTION
POINT OF VERTICAL INTERSECTION
PROPERTY LINE
POLYETHYLENE
PC
PI
PVI
PL
PE
PREFAB
PRELIM
PREP
PROP
PRV
PSF
PSI
PT
PV
PVC
PVMT
PREFABRICATED
PRELIMINARY
PREPARATION
PROPOSED
PRESSURE REDUCING VALVE OR
PRESSURE RELIEF VALVE
POUNDS PER SQUARE FOOT
POUNDS PER SQUARE INCH
POINT OF TANGENCY
PLUG VALVE
POLYVINYL CHLORIDE OR
PAVEMENT
QUANTITY
RADIUS
REINFORCED CONCRETE PIPE
ROOF DRAIN
REFERENCE
RECTANGULAR
REINFORCE (D) (ING) (MENT)
REQUIRED
RIGHT OF WAY
QTY
RAD
RCP
RD
RE
RECT
REINF
REQD
ROW
SC
SD
SECT
SPEC
SQ
SQ FT
SQ YD
SS
SST
STA
STD
STL
STRUCT
SYM
SAWCUT
STORM DRAIN
SECTION
SPECIFICATION
SQUARE
SQUARE FOOT
SQUARE YARD
SANITARY SEWER
STAINLESS STEEL
STATION
STANDARD
STEEL
STRUCTURAL
SYMMETRICAL
TEMPORARY BENCH MARK
TOP OF CONCRETE OR TOP OF CURB
TEMPORARY
TOTAL
TOP OF WALL OR CAP OF WALL
TYPICAL
TBM
TOC
TEMP
TOT
TW
TYP
VERT
W/ W/O
WW
VERTICAL
WITH
WITHOUT
WASTEWATER
ABAN ABANDON
CMU CONCRETE MASONRY UNIT
DIAGONALDIAG
ECCENTRICECC
GAUGEGA
EJ EXPANSION JT
AUTOMATICAUTO
AVG AVERAGE
ARV AIR RELIEF VALVE
AMERICAN SOCIETY FOR TESTING AND MATERIALSASTM
BMP BEST MANAGEMENT PRACTICE
CDOT COLORADO DEPARTMENT OF TRANSPORTATION
CORNERCOR
CENTERCTR
CY CUBIC YARDS
DEMOLITIONDEMO
EA EACH
EQ EQUAL
EDGE OF PAVEMENTEOP
FEETFT
GRATINGGRTG
GALVANIZED STEEL PIPEGSP
HIGHH
INCL INCLUDED
JTS JOINTS
LOW WATER LEVELLWL
NORTHN
NATIONAL PIPE THREADNPT
POINT OF CURVE RETURNPCR
SWMP STORMWATER MANAGEMENT PLAN
THK THICK
TOB TOP OF BANK
PRESSURE CLEAN OUTPCO
UNDERGROUND ELECTRICUGE
UNIFORM BUILDING CODEUBC
WIDE OR WIDTHW
AASHTO AMERICAN ASSOC. OF STATE HIGHWAY AND
TRANSPORTATION OFFICIALS
AMERICAN WATER WORKS ASSOC.AWWA
E EAST
POINT OF VERTICAL CURVATURE
FF FINISH FLOOR
BVCE
BVCS
BEGIN VERTICAL CURVE ELEVATION
BEGIN VERTICAL CURVE STATION
EVCE
EVCS
END VERTICAL CURVE ELEVATION
END VERTICAL CURVE STATION
POINT OF VERTICAL CURVATUREVC
SQUARE INCHSQ IN
WSE WATER SURFACE ELEVATION
SPD STANDARD PROCTOR DENSITY
HE HORIZONTAL ELLIPTICAL
GCO GRADE CLEANOUT
BOTTOMBOT
UTILITYUTIL
LANDSCAPE(ING)LSCAPE
THRUST BLOCKTB
HIGH POINTHP
R RIGHT
TBC TOP BACK OF CURB
WATER QUALITY CONTROL ELEVATIONWQCE
IRR IRRIGATION
DOM DOMESTIC
VITRIFIED CLAY PIPEVCP
BW BOTTOM OF WALL
BOTTOM OF STEPBOS
TOP OF STEPTOS
ME MATCH EXISTING
GR GRATE
SERVICESVC
FINISHED GRADE ADJACENT TO BOTTOM OF WALL
TG FINISHED GRADE ADJACENT TO TOP OF WALL
X SECT
YH
CROSS SECTION
YARD HYDRANT
XFMR ELECTRONIC TRANSFORMER
1. ALL MATERIALS AND WORKMANSHIP SHALL BE IN CONFORMANCE WITH THE LATEST STANDARDS AND SPECIFICATIONS OF THE COLORADO DEPARTMENT OF TRANSPORTATION, FOREST SERVICE FIRE PROTECTION REQUIREMENTS, AND APPLICABLE STATE SPECIFICATIONS. THE CONTRACTOR SHALL HAVE IN POSSESSION AT THE JOB SITE AT ALL TIMES ONE (1) SIGNED COPY OF APPROVED PLANS, STANDARDS AND SPECIFICATIONS. CONTRACTOR SHALL CONSTRUCT AND MAINTAIN EMERGENCY ACCESS ROUTES TO THE SITE AND STRUCTURE AT ALL TIMES PER THE APPLICABLE FOREST SERVICE FIRE PROTECTION DISTRICT REQUIREMENTS. THE CONTRACTOR SHALL OBTAIN WRITTEN APPROVAL FOR ANY VARIANCE TO THE ABOVE DOCUMENTS. NOTIFY CONTRACTING OFFICER OF ANY CONFLICTING STANDARDS OR SPECIFICATIONS. IN THE EVENT OF ANY CONFLICTING STANDARD OR SPECIFICATION, THE MORE STRINGENT OR HIGHER QUALITY STANDARD, DETAIL OR SPECIFICATION SHALL APPLY.
2. THE CONTRACTOR SHALL OBTAIN, AT THEIR OWN EXPENSE, ALL APPLICABLE CODES, LICENSES, STANDARD SPECIFICATIONS, PERMITS, BONDS, ETC., WHICH ARE NECESSARY TO PERFORM THE PROPOSED WORK, INCLUDING, BUT NOT LIMITED TO STATE GROUNDWATER DISCHARGE AND COLORADO DEPARTMENT OF HEALTH AND ENVIRONMENT (CDPHE) STORMWATER DISCHARGE PERMIT ASSOCIATED WITH
CONSTRUCTION ACTIVITY.
3. THE CONTRACTOR SHALL BE RESPONSIBLE FOR NOTIFYING THE REQUIRED PARTY CONTRACTING OFFICER AT LEAST 48 HOURS PRIOR TO START OF ANY CONSTRUCTION, PRIOR TO BACKFILLING, AND AS REQUIRED BY PROJECT SPECIFICATIONS. THE CONTRACTOR SHALL CONTINUE WITH NOTIFICATIONS THROUGHOUT THE PROJECT AS REQUIRED BY THE STANDARDS AND SPECIFICATIONS.
4. THE LOCATIONS OF EXISTING UTILITIES ARE SHOWN IN THE APPROXIMATE LOCATION BASED ON INFORMATION BY OTHERS. NOT ALL UTILITIES MAY BE SHOWN. THE CONTRACTOR SHALL DETERMINE THE EXACT SIZE, LOCATION AND TYPE OF ALL EXISTING UTILITIES WHETHER SHOWN OR NOT BEFORE COMMENCING WORK. THE CONTRACTING OFFICER ASSUMES NO RESPONSIBILITY FOR THE ACCURACY OR COMPLETENESS SHOWN ON PLANS. THE CONTRACTOR SHALL BE FULLY AND SOLELY RESPONSIBLE FOR ANY AND ALL DAMAGES AND COSTS WHICH MIGHT OCCUR BY THE CONTRACTOR'S FAILURE TO EXACTLY LOCATE AND PRESERVE ANY AND ALL UTILITIES. THE CONTRACTOR SHALL NOTIFY ALL PUBLIC AND PRIVATE UTILITY COMPANIES AND DETERMINE THE LOCATION OF ALL EXISTING UTILITIES PRIOR TO PROCEEDING WITH GRADING AND CONSTRUCTION. ALL WORK PERFORMED IN THE AREA OF UTILITIES SHALL BE PERFORMED AND INSPECTED ACCORDING TO THE REQUIREMENTS OF THE UTILITY OWNER.
LIKEWISE, THE CONTRACTOR SHALL BE RESPONSIBLE FOR LOCATING AND MAPPING ANY EXISTING UTILITY (INCLUDING DEPTH) WHICH MAY CONFLICT WITH THE PROPOSED CONSTRUCTION, AND FOR RELOCATING ENCOUNTERED UTILITIES AS DIRECTED BY THE ENGINEER. CONTRACTOR SHALL CONTACT AND RECEIVE APPROVAL FROM GOVERNMENT BEFORE RELOCATING ANY ENCOUNTERED UTILITIES.
CONTRACTOR RESPONSIBLE FOR SERVICE CONNECTIONS, AND RELOCATING AND RECONNECTING AFFECTED UTILITIES AS COORDINATED WITH GOVERNMENT, INCLUDING NON-MUNICIPAL UTILITIES (TELEPHONE, GAS, CABLE, ETC., WHICH SHALL BE COORDINATED WITH THE UTILITY OWNER). THE CONTRACTOR SHALL IMMEDIATELY CONTACT CONTRACTING OFFICER UPON DISCOVERY OF A UTILITY DISCREPANCY OR CONFLICT. AT LEAST 48 HOURS PRIOR TO CONSTRUCTION, THE CONTRACTOR SHALL NOTIFY THE UTILITY NOTIFICATION CENTER OF COLORADO (1-800-922-1987, WWW.UNCC.ORG). SEE
SURVEY UTILITY LOCATION INFORMATION BELOW.
5. THE CONTRACTOR SHALL BE SOLELY AND COMPLETELY RESPONSIBLE FOR CONDITIONS AT AND ADJACENT TO THE JOB SITE, INCLUDING SAFETY OF ALL PERSONS AND PROPERTY DURING THE PERFORMANCE OF THE WORK. THE CONTRACTOR SHALL PREPARE A TRAFFIC CONTROL PLAN FOR OWNER AND/OR CITY APPROVAL AND PROVIDE ALL LIGHTS, SIGNS, BARRICADES, FENCING, FLAGMEN OR OTHER DEVICES NECESSARY TO PROVIDE FOR PUBLIC SAFETY. THIS REQUIREMENT SHALL APPLY CONTINUOUSLY AND NOT BE LIMITED TO NORMAL WORKING HOURS. THE CONTRACTOR AGREES TO COMPLY WITH THE PROVISIONS OF THE TRAFFIC CONTROL PLAN AND THE LATEST EDITION OF THE "MANUAL ON UNIFORM TRAFFIC CONTROL DEVICES," PART VI, FOR CONSTRUCTION SIGNAGE AND TRAFFIC CONTROL. ALL TEMPORARY AND PERMANENT TRAFFIC SIGNS SHALL COMPLY TO THE MANUAL ON UNIFORM TRAFFIC CONTROL DEVICES (MUTCD) WITH REGARD TO SIGN SHAPE, COLOR, SIZE, LETTERING, ETC. UNLESS OTHERWISE SPECIFIED. IF APPLICABLE, PART NUMBERS ON SIGNAGE DETAILS REFER TO MUTCD SIGN NUMBERS.
6. THE CONTRACTOR SHALL BE RESPONSIBLE FOR REMOVING ANY GROUNDWATER ENCOUNTERED DURING THE CONSTRUCTION OF ANY PORTION OF THIS PROJECT. GROUNDWATER SHALL BE PUMPED, PIPED, REMOVED AND DISPOSED OF IN A MANNER WHICH DOES NOT CAUSE FLOODING OF EXISTING STREETS NOR EROSION ON ABUTTING PROPERTIES IN ORDER TO CONSTRUCT THE IMPROVEMENTS SHOWN ON THESE PLANS. GROUNDWATER TO BE PUMPED SHALL BE TESTED, PERMITTED, AND PUMPED PER THE STATE OF COLORADO AND LOCAL GROUNDWATER DISCHARGING PERMIT REQUIREMENTS.
7. RIM AND GRATE ELEVATIONS SHOWN ON PLANS ARE APPROXIMATE ONLY AND ARE NOT TO BE TAKEN AS FINAL ELEVATIONS. THE CONTRACTOR SHALL ADJUST RIMS AND OTHER IMPROVEMENTS TO MATCH FINAL PAVEMENT AND FINISHED GRADE ELEVATIONS. ALL MANHOLES SHALL BE FINAL ADJUSTED AFTER PAVING SUCH THAT THE RIM IS ¼” TO ½” BELOW FINISHED ASPHALT. MANHOLES IN UNPAVED AREAS
SHALL BE SET SO THAT THE RIM IS 6” ABOVE FINISHED GRADE.
8. THE EXISTING AND PROPOSED ELEVATIONS OF FLATWORK, SIDEWALKS, CURBS, THRESHOLDS, PAVING, ETC. AS SHOWN HEREON ARE BASED ON EXTRAPOLATION OF FIELD SURVEY DATA, EXISTING CONDITIONS, AND DATA PROVIDED BY OTHERS. AT CRITICAL AREAS AND SITE FEATURES, CONTRACTOR SHALL HAVE FORMWORK INSPECTED AND APPROVED BY CONTRACTING OFFICER PRIOR TO PLACING CONCRETE.
MINOR ADJUSTMENTS, AS APPROVED, TO PROPOSED GRADES, INVERTS, ETC. MAY BE REQUIRED TO PREVENT PONDING OR SLOPE NOT IN CONFORMANCE WITH CDOT STANDARDS. ALL FLATWORK MUST PREVENT PONDING AND PROVIDE POSITIVE DRAINAGE AWAY FROM EXISTING AND PROPOSED BUILDINGS, WALLS, ROOF DRAIN OUTFALLS, ACROSS DRIVES AND WALKS, ETC., TOWARDS THE PROPOSED
INTENDED DRAINAGE FEATURES AND CONVEYANCES.
9. FINAL LIMITS OF REQUIRED ASPHALT SAWCUTTING AND PATCHING MAY VARY FROM LIMITS SHOWN ON PLANS. CONTRACTOR TO PROVIDE SAWCUT AND PATCH WORK TO ACHIEVE POSITIVE DRAINAGE AND A SMOOTH TRANSITION TO EXISTING ASPHALT WITHIN SLOPES ACCEPTABLE TO THE CONTRACTING OFFICER AND WITHIN CDOT STANDARDS. CONTRACTOR SHALL PROVIDE ADDITIONAL SAWCUTTING AND PATCHING AT UTILITY WORK, CONNECTION POINTS TO EXISTING PAVEMENT AND FEATURES, ETC. THAT MAY NOT BE DELINEATED ON PLANS.
10. ANY EXISTING MONITORING WELLS, CLEANOUTS, VALVE BOXES, ETC. TO BE PROTECTED AND TO REMAIN IN SERVICE. IF FEATURES EXIST, EXTEND OR LOWER TO FINAL SURFACE WITH LIKE KIND CAP WITH STANDARD CAST ACCESS LID WITH SAME MARKINGS. IN LANDSCAPED AREAS PROVIDE A CONCRETE COLLAR (18"x18"x6" THICK) AT ALL EXISTING AND PROPOSED MONITORING WELLS, CLEANOUTS, VALVE BOXES, ETC.
11. GOVERNMENT TO APPROVE ALL PRIVATE CONCRETE FINISHING, JOINT PATTERNS AND COLORING REQUIREMENTS PRIOR TO CONSTRUCTION. SUBMIT JOINT LAYOUT PLAN TO GOVERNMENT FOR APPROVAL
PRIOR TO CONSTRUCTION.
12. PIPE LENGTHS AND HORIZONTAL CONTROL POINTS SHOWN ARE FROM CENTER OF STRUCTURES, END OF FLARED END SECTIONS, ETC. SEE STRUCTURE DETAILS FOR EXACT HORIZONTAL CONTROL LOCATION.
CONTRACTOR IS RESPONSIBLE FOR ADJUSTING ACTUAL PIPE LENGTHS TO ACCOUNT FOR STRUCTURES AND LENGTH OF FLARED END SECTIONS.
13. ALL SURPLUS MATERIALS, TOOLS, AND TEMPORARY STRUCTURES, FURNISHED BY THE CONTRACTOR, SHALL BE REMOVED FROM THE PROJECT SITE BY THE CONTRACTOR. ALL DEBRIS AND RUBBISH CAUSED BY THE OPERATIONS OF THE CONTRACTOR SHALL BE REMOVED, AND THE AREA OCCUPIED DURING CONSTRUCTION ACTIVITIES SHALL BE RESTORED TO ITS ORIGINAL CONDITION, WITHIN 48 HOURS OF PROJECT
COMPLETION, UNLESS OTHERWISE DIRECTED BY THE GOVERNMENT.
14. THE CONTRACTOR IS REQUIRED TO PROVIDE AND MAINTAIN EROSION AND SEDIMENT CONTROL MEASURES IN ACCORDANCE WITH THE LOCAL JURISDICTION, THE STATE OF COLORADO, MILE HIGH FLOOD DISTRICT "URBAN STORM DRAINAGE CRITERIA MANUAL VOLUME 3", THE M-STANDARD PLANS OF THE COLORADO DEPARTMENT OF TRANSPORTATION, AND THE APPROVED EROSION CONTROL PLAN. THE CONTRACTOR IS RESPONSIBLE FOR PROHIBITING SILT AND DEBRIS LADEN RUNOFF FROM LEAVING THE SITE, AND FOR KEEPING ALL PUBLIC AREAS FREE OF MUD AND DEBRIS. THE CONTRACTOR IS RESPONSIBLE FOR RE-ESTABLISHING FINAL GRADES AND FOR REMOVING ACCUMULATED SEDIMENTATION FROM ALL AREAS INCLUDING SWALES AND DETENTION/WATER QUALITY AREAS. CONTRACTOR SHALL REMOVE TEMPORARY EROSION CONTROL MEASURES AND REPAIR AREAS AS REQUIRED AFTER VEGETATION IS ESTABLISHED AND ACCEPTED BY GOVERNMENT.
15. ADA COMPLIANCE: THE CROSS-SLOPE OF ALL WALKS MUST BE LESS THAN 1:48 (2.0%) PERPENDICULAR TO DIRECTION OF TRAVEL. RUNNING SLOPE OF ACCESSIBLE WALKS MUST BE NOT STEEPER THAN 1:20 (5.0%) IN DIRECTION OF TRAVEL. MAXIMUM GRADE OF ACCESSIBLE CURB RAMPS AND RAMPS IS 1:12 (8.3%). CURB RAMPS SHALL PROVIDE A LANDING AT THE TOP AND RAMP RUNS PROVIDE LANDINGS AT THE BOTTOM AND TOP OF EACH RAMP RUN AT A SLOPE NOT TO EXCEED 1:48. RAMPS RUNS EXCEEDING SIX INCHES SHALL INCLUDE HANDRAILS. ACCESSIBLE PARKING SPACES AND ACCESS AISLES SHALL NOT EXCEED 1:48 IN ALL DIRECTIONS. CONTRACTOR SHALL NOTIFY CONTRACTING OFFICER PRIOR TO PLACEMENT OF FLATWORK OF SITE CONDITIONS OR DISCREPANCIES WHICH PREVENT TYPICAL REQUIRED GRADES FROM BEING ACHIEVED. ALL RAMPS, STAIRS, EDGE PROTECTION, AND RAILINGS SHALL BE CONSTRUCTED IN ACCORDANCE WITH CURRENT ADA STANDARDS. ACCESSIBLE CURB RAMPS SHALL
CONFORM TO THE CDOT M-STANDARDS (SEE DETAIL M-608-1, ETC).
16. PROTECT ALL TREES AND VEGETATION. PLACE CONSTRUCTION FENCING AT DRIP LINE OF TREES AND PLANTS NEAR THE WORK ZONE. DEEP WATER TREES WEEKLY. HAND EXCAVATION REQUIRED AT ROOT
ZONES WHERE PROPOSED PAVING OR UTILITY WORK IS WITHIN DRIPLINE OF TREES.
17. LOCATIONS OF CLEANOUTS, LIGHTS, SIGNAGE, JUNCTION BOXES, AND OTHER SIGNIFICANT SITE FEATURES TO BE STAKED FOR CONTRACTING OFFICER AND OR GOVERNMENT APPROVAL PRIOR TO WORK.
CLEANOUTS, JUNCTION BOXES, AND ADJACENT GRADES TO BE RAISED ONE-HALF INCH AT ASPHALT/CONCRETE (OR 1" AT LANDSCAPING) TO PROVIDE POSITIVE DRAINAGE AWAY FROM FEATURES.
18. SURVEY INFORMATION:
18.1. BENCHMARK INFORMATION: TOPOGRAPHIC INFORMATION WAS PROVIDED BY USFS. SEE "MONUMENT FIRE CENTER" DATED AUGUST, 2001. PROJECT BENCHMARK ELEVATION:THE DATUM IS NAD27 PER
SURVEY. COORDINATE AND VERIFY ALL VERTICAL AND HORIZONTAL DATA SHOWN IN SURVEY AND REPORT ANY IRREGULARITIES OR DISCREPANCIES TO CONTRACTING OFFICER PRIOR TO CONSTRUCTION.
18.2. BASIS OF BEARINGS: SEE PLANS.
18.3. HORIZONTAL CONTROL INFORMATION: HORIZONTAL CONTROL COORDINATES ARE BASED ON THE REFERENCED SURVEY AND ARE PROVIDED BY THE FOLLOWING POINTS AS SHOWN ON THE PLANS:
CP-2 N456608.10 E2168799.33 ELEV7194.72 HV-2
CP-4 N458316.05 E2170918.29 ELEV7194.72 HV-4
CP-6 N454059.85 E2170908.70 ELEV7049.59 HV-6
18.4. SURVEY UTILITY LOCATION INFORMATION PER THE SURVEYOR: SUBSURFACE UTILITIES ARE SHOWN IN APPROXIMATE HORIZONTAL AND VERTICAL LOCATIONS CONSISTENT WITH ASCE 38-02 QUALITY LEVEL "B" (INFORMATION OBTAINED BY THE APPLICATION OF APPROPRIATE SURFACE GEOPHYSICAL METHODS TO DETERMINE THE EXISTENCE AND HORIZONTAL POSITION OF VIRTUALLY ALL UTILITIES WITHIN THE PROJECT LIMITS. THE INFORMATION OBTAINED IN THIS MANNER IS SURVEYED TO PROJECT CONTROL.) AND QUALITY LEVEL "C" (INFORMATION OBTAINED BY SURVEYING AND PLOTTING VISIBLE ABOVE-GROUND UTILITY FEATURES AND BY USING PROFESSIONAL JUDGMENT IN CORRELATING THIS INFORMATION TO QUALITY LEVEL D; INFORMATION DERIVED FROM EXISTING RECORDS OR ORAL RECOLLECTIONS), AND BASED ON FIELD MEASUREMENTS PROVIDED BY THE GOVERNMENT AND THE CONTRACTOR. SUBSURFACE UTILITIES ARE NOT DEPICTED TO THE EXTENT SET FORTH IN ASCE 38-02 QUALITY LEVELS "A" (INFORMATION OBTAINED THROUGH THE NONDESTRUCTIVE EXPOSURE OF UNDERGROUND UTILITIES, AND ALSO PROVIDES THE TYPE, SIZE, CONDITION, MATERIAL AND OTHER CHARACTERISTICS OF UNDERGROUND FEATURES.). TO THE EXTENT DEEMED NECESSARY FOR THE PROTECTION OF PERSONS AND PROPERTY, POTHOLING OR OTHER PRECISE MAPPING MAY BE COMPLETED TO CONFIRM THE EXACT LOCATION OF ANY SUBSURFACE UTILITIES. NOTIFY GOVERNMENT AND CONTRACTING OFFICER WITH ALL UTILITY INFORMATION PRIOR TO CONSTRUCTION.VISIT
HTTPS://WWW.FHWA.DOT.GOV/PROGRAMADMIN/SUEINDEX.CFM FOR MORE INFORMATION.
19. THE CONTRACTOR AT THE CONTRACTORS EXPENSE SHALL FURNISH THE GOVERNMENT AND CONTRACTING OFFICER OF RECORD A COMPLETE SET OF CONSTRUCTION RECORD DRAWINGS ("AS-BUILTS") FOR THE CONSTRUCTED IMPROVEMENTS. THE AS-BUILT SET SHALL SHOW SUFFICIENT DIMENSION TIES TO PERMANENT SURFACE FEATURES OR NORTHING/EASTING POINTS FOR ALL BURIED FACILITIES TO ALLOW FOR FUTURE LOCATING. THE AS-BUILT SET SHALL SHOW AS-BUILT CONTOURS AND ELEVATIONS OF ASPHALT AND CONCRETE FLATWORK, FLOWLINES, GRADE BREAKS, STAIRS, CROSS-SLOPES, HIGH AND LOW POINTS, AND ADDITIONAL ELEVATIONS TO DEMONSTRATE IMPROVEMENTS WERE CONSTRUCTED PER PLANS. THE AS-BUILT SET SHALL SHOW ELEVATIONS OF ALL DETENTION/WATER QUALITY FACILITIES, INCLUDING BUT NOT LIMITED TO BERMS, SPILLWAYS, BASIN BOTTOM, PIPE INVERTS, AND CONTROL STRUCTURE FEATURES (AS SURVEYED AND STAMPED BY A CERTIFIED P.L.S.). THE AS-BUILT SET SHALL ALSO INCLUDE ELEVATIONS OF MANHOLES, PIPES, INLETS, GRATES, AND SIZES OF ALL UTILITIES. THE AS-BUILT SET SHALL SHOW ANY AND ALL VARIATIONS FROM THE APPROVED PLAN. CONTRACTING OFFICER WILL
PRODUCE FINAL RECORD DRAWINGS.
OS OFFSET
SAN SANITARY
ROOF DRAIN
IRRIGATION - 12" AND SMALLER
UNDERDRAIN
TRENCH DRAIN
CABLE TV
DRAIN
FORCE MAIN
FUEL
GAS
TELEPHONE
UNDERGROUND ELECTRIC
OVERHEAD ELECTRIC
FIBER OPTIC
ELECTRIC
STORM - 12" AND SMALLER
STORM - LARGER THAN 12"
POTABLE WATER
NON POTABLE WATER
PVC PIPE (MISC)
IRRIGATION - LARGER THAN 12"
WATER - 12" AND SMALLER
WATER - LARGER THAN 12"
SANITARY SEWER - 12" AND SMALLER
SANITARY SEWER - LARGER THAN 12"
DETAILDET
MEP MECHANICAL, ELECTRICAL, PLUMBING (ARCH)
BUTTERFLY VALVE
GB GRADE BREAK
Know what's below.
before you dig.Call
R
SHEET WHERE THE DETAIL IS DRAWN
- INDICATES SAME DRAWING
SHEET WHERE THE OBJECT IS
DRAWN IN PLAN VIEW
- INDICATES SAME DRAWING
9/
/2
:0
JC
D N
:\2
8.
EN
V
- U
SD
A
FS
M O
N U
M
EN
T
FI
R E
C
EN
TE
R
W
AT
ER
T R
EA
TM
EN
T
EV
AL
U
AT
IO
N
\D R
AW
IN
G S\
X2
8.
EN
V
- C O
VE
R
S H
EE
T.
D W
G
SHEET
OF
DESIGNER
STAMPS, LOGOS, AND SEALS
PROJECT NAME
DRAWING TITLE
CHECKED
ARCHIVE NO.
SUB SHEET NO.
DATENO.
REVISION / ISSUE
MONUMENT FIRE
CENTER
WATER TREATMENT
PIKE-SAN ISABEL
NATIONAL FORESTS &
CIMARRON AND COMANCHE
NATIONAL GRASSLANDS
PIKES PEAK RANGER DISTRICT
MONUMENT FIRE CENTER
R2
ROCKY MOUNTAIN REGION
9/10/2025 18
FOREST SERV I CE
DEPA R TMENT OF AGR I CU LT
UR
E
DATE
UNITED STATES
DEPARTMENT OF AGRICULTURE
FOREST SERVICE
WYE
KAT
T1.1
N/A
LEGEND, NOTES
AND
ABBREVIATIONS
28699
KE
V IN A . TONE
PROFESS I ONA L ENG I NEER
CO
LORADO L I CENSED
09/10/25
USER'S CHOICE
GLASS, VIEWING DEVICE
SENSOR (PRIMARY
USER'S CHOICE
POINT (TEST)
MULTIFUNCTION
ORIFICE, RESTRICTION
INSTRUMENT IDENTIFICATION LETTERS
(INSTRUMENT SOCIETY OF AMERICA)
UNCLASSIFIED
TORQUEN
VIBRATION, MECHANICAL
POSITION, DIMENSION
V
Z
Y X W
EVENT, STATE OR
PRESENCE
UNCLASSIFIED
WEIGHT, FORCE
ANALYSIS
R S
U T
O P
Q
RADIATION
FAILURE
TEMPERATURE
SPEED, FREQUENCY
PRESSURE, VACUUM
USER'S CHOICE
QUANTITY
Z AXIS
X AXIS
Y AXIS
WELL
INTEGRATE, TOTALIZE
SAFETY
RECORD
CONNECTION
BURNER, COMBUSTION
TIME, TIME SCHEDULE
CURRENT (ELECTRICAL)
L M
K J I H
USER'S CHOICE
LEVEL
POWER
HAND
F G
E
B
D C
A
FLOW RATE
USER'S CHOICE
VOLTAGE
USER'S CHOICE
CONTROL
ANALYSIS
MOMENTARY
TIME RATE OF CHANGE
SCAN
LIGHT
INDICATE
RATIO (FRACTION)
DIFFERENTIAL
ELEMENT)
ALARM
FIRST - LETTER
USER'S CHOICEUSER'S CHOICE
UNCLASSIFIED
SWITCH
TRANSMIT
MULTIFUNCTION
UNCLASSIFIED
MULTIFUNCTION
OPEN
CONTROL STATION
CONTROL SWITCH
USER'S CHOICE
INTERMEDIATE
LOW
MIDDLE,
HIGH
USER'S CHOICE
CLOSED
SUCCEEDING - LETTERS
OUTPUT FUNCTION MODIFIER
COMMANDRELAY, COMPUTE,
CONVERT
DRIVER, ACTUATOR,
UNCLASSIFIED FINAL
CONTROL ELEMENT
MEASURED OR INITIATING
VARIABLE
READOUT OR PASSIVE
FUNCTION
VALVE, DAMPER,
LOUVER
P&ID INSTRUMENT SYMBOLS
MOTOR
EXIST SECONDARY PROCESS LINE
SECONDARY PROCESS LINE
EXIST MAIN PROCESS LINE
MAIN PROCESS LINE
EXIST CHANNEL
CHANNEL
FUTURE SECONDARY PROCESS LINE
FUTURE MAIN PROCESS LINE
PROCESS IDENTIFICATION NUMBER
NUMBER INDICATES SHEET OF
PROCESS OR CONTROL CONTINUATION
PROCESS LEGEND
BUILDING
HARDWIRED SIGNAL
VALVE SYMBOLS
CLOSED OPEN
GATE VALVE
PLUG VALVE
BALL VALVE
CHECK VALVE
NEEDLE VALVE
P&ID EQUIPMENT SYMBOLS
HOSE BIB
BLIND FLANGE/CAP
FLUSHING PORT
GENERAL NOTES:
1. THIS IS A STANDARD LEGEND, THEREFORE NOT ALL OF THIS INFORMATION MAY BE
USED ON THIS PROJECT.
2. P & ID INSTRUMENTATION DETAILS DO NOT REPRESENT INSTRUMENTS AND
CONTROLS INTEGRAL TO VENDOR SUPPLIED CONTROL PANELS OR EQUIPMENT.
SEE EQUIPMENT SPECIFICATIONS FOR THIS INFORMATION.
3. P & ID DOES NOT REPRESENT CONTROL STRATEGIES OR INTERACTIONS.
REFERENCE SECTION 16950, CONTROL NARRATIVES, FOR THIS INFORMATION.
4. P & ID DOES NOT REPRESENT EQUIPMENT HARDWIRED INTERLOCK AND ENABLE
CIRCUITRY, REFER TO SECTION 16950 FOR COMPLETE DESCRIPTION.
DATA LINK OR SOFTWARE SIGNAL
THROUGH
INSTRUMENTS PLC
SHARED
DISPLAYDISCRETE
AND CONTROL
(DCS)
LOCATION/ACCESSIBILITY
FIELD MOUNTED
1.
2.
FIELD OR LOCALLY MOUNTED.
1.
2.
3.
4.
MOUNTED.
VISIBLE ON VIDEO DISPLAY.
CENTRAL OR MAIN CONTROL ROOM.
DEVICE.
ACCESSIBLE TO AN OPERATOR AT
DEVICE OR CONSOLE.
FRONT OF MAIN PANEL OR CONSOLE
PRIMARY LOCATION NORMALLY
ACCESSIBLE TO AN OPERATOR
ACCESSIBLE TO AN OPERATOR AT
ARV
AIR RELEASE VALVE
SAMPLE PORT
DRAIN
ULTRASONIC LEVEL INDICATOR
CAM-LOCK FITTING/
QUICK CONNECT
--- ANALYZER
1 G1.2
M MOTOR
AERATOR
STATIC MIXER
PERISTALTIC PUMP
DIAPHRAGM PUMP
ORP SENSOR
PRESSURE ELEMENT
PRESSURE GAUGE
CALIBRATION COLUMN
BUTTERFLY VALVE
TAG DESIGNATION
COMMON INSTRUMENT DESIGNATIONS
YI EQUIPMENT RUNNING STATUS
YS EQUIPMENT IN AUTO OR REMOTE STATUS
YY EQUIPMENT RUN COMMAND
UA EQUIPMENT FAULT STATUS
HC HAND CONTROL
HS LOCAL HAND SWITCH; AUTO STATUS
SI SPEED INDICATION
SC SPEED COMMAND
PSL PRESSURE SWITCH LOW
PSH PRESSURE SWITCH HIGH
FE FLOW ELEMENT
FIT FLOW INDICATOR/TRANSMITTER
ZSO VALVE POSITION FULL OPEN
ZSC VALVE POSITION FULL CLOSE
ZSI VALVE POSITION INDICATOR
SP SET POINT
PID PROPORTIONAL-INTEGRAL-DERIVATIVE
HOA HAND-OFF-AUTO
OCA OPEN-CLOSE-AUTO
LCP LOCAL CONTROL PANEL
TSH TEMPERATURE SWITCH HIGH
YC EQUIPMENT RUN COMMAND
YA EQUIPMENT ALARM STATUS
LIT LEVEL INDICATOR/TRANSMITTER
AIT ANALYZER INDICATOR/TRANSMITTER
AE ANALYZER ELEMENT
FLOAT SWITCH
PRESSURE RELIEF VALVE
9/
/2
:0
JC
D N
:\2
8.
EN
V
- U
SD
A
FS
M O
N U
M
EN
T
FI
R E
C
EN
TE
R
W
AT
ER
T R
EA
TM
EN
T
EV
AL
U
AT
IO
N
\D R
AW
IN
G S\
.E
N V
- P &I
D .D
W G
SHEET
OF
DESIGNER
STAMPS, LOGOS, AND SEALS
PROJECT NAME
DRAWING TITLE
CHECKED
ARCHIVE NO.
SUB SHEET NO.
DATENO.
REVISION / ISSUE
MONUMENT FIRE
CENTER
WATER TREATMENT
PIKE-SAN ISABEL
NATIONAL FORESTS &
CIMARRON AND COMANCHE
NATIONAL GRASSLANDS
PIKES PEAK RANGER DISTRICT
MONUMENT FIRE CENTER
R2
ROCKY MOUNTAIN REGION
9/10/2025 18
FOREST SERV I CE
DEP A R TMENT OF AGR I CU LT
UR
E
DATE
UNITED STATES
DEPARTMENT OF AGRICULTURE
FOREST SERVICE
WYE
KAT
G1.0
N/A
PROCESS &
INSTRUMENTATION
LEGEND
28699
KE
V IN A . TONE
PROFESS I ONA L ENG I NEER
CO
FROM WELL
M
ARV
PRE-FILTER
GRAVER
5 ROUNDS
(PF-1)
ACID WASHED
CARBON
12 ROUNDS
(AWCF-1)
KDF
12 ROUNDS
(KDF-1)
POST-FILTER
GRAVER
5 ROUNDS
(FF-1)
BAFFLE
TANK NO. 1
CAUSTIC
INJECTION
PHOSPHORIC ACID
INJECTIONCHLORINE
INJECTION
BAFFLE
TANK NO. 2
pH ANALYZER
GENERAL NOTES
1. COMPONENTS SHALL MEET NSF 61 CERTIFICATION
2. ALL INTERIOR WTF PIPING AND FITTINGS SHALL BE SCH80 PVC,
ALL PIPING SHALL BE 1.5"
DESIGN CRITERA
DISINFECTION SYSTEM
CHLORINE PUMP
QUANTITY: 1
TYPE: PERISTALTIC
MODEL: STENNER S3001
TARGET DOSE: 5.5 mg/L
DESIGN FEED RATE: 0.08 GPH
MIN FEED RATE: 0.021 GPH
CHLORINE STORAGE
QUANTITY: 1
VOLUME: 55 GAL
CORROSION CONTROL
PHOSPHORIC ACID PUMP
QUANTITY: 1
TYPE: PERISTALTIC
MODEL: STENNER S3001
TARGET DOSE: 1-3 mg/L
DESIGN FEED RATE: 0.017 - 0.052 GPH
MIN FEED RATE: 0.0044 GPH
PHOSPHORIC ACID STORAGE
QUANTITY: 1
VOLUME: 55 GAL
CAUSTIC PUMP
QUANTITY: 1
TYPE: PERISTALTIC
MODEL: STENNER S3001
TARGET DOSE: 8-10 mg/L
DESIGN FEED RATE: 0.045 - 0.056
MIN FEED RATE: 0.0113 GPH
CAUSTIC STORAGE
QUANTITY: 1
VOLUME: 55 GAL
GREENSAND
12 ROUNDS
(GS-1)
DESIGN FLOWS
QDESIGN: 10 GPM
SYSTEM PRESSURE: 100 PSI
WATER TEMPERATURE: 5-15 DEGREES C
WATER PH: 6.6 TO 7.4
FILTRATION
PRE-FILTER
QUANTITY: 1
HOUSING: GRAVER
NUMBER OF ROUNDS: 5
ACID WASH CARBON
QUANTITY: 1
HOUSING: GRAVER
NUMBER OF ROUNDS: 12
KDF
QUANTITY: 1
HOUSING: GRAVER
NUMBER OF ROUNDS: 12
GREENSAND
QUANTITY: 1
HOUSING: GRAVER
MODEL: 12LPF30
NUMBER OF ROUNDS: 12
POST-FILTER
QUANTITY: 1
HOUSING: GRAVER
NUMBER OF ROUNDS: 5
ARV ARV ARV ARV ARV
TREATMENT BUILDING
AIT
AI
PT
PI
PT
PI
FE
FQI
FI
CP CP
CP
YI
CP
YC
SI
SC
TYP CMP-101,
CMP-102
CMP-102CMP-100
STORAGE TANK
(6,000 GALLONS)
LI
CP
LT
CMP-101
CALIBRATION COLUMN
PANEL
TO BUCKET
LSL
CP
TYP LSL-101,
LSL-102
LSL
LSL
LSL
CALIBRATION COLUMN
PANEL
9/
/2
:0
JC
D N
:\2
8.
EN
V
- U
SD
A
FS
M O
N U
M
EN
T
FI
R E
C
EN
TE
R
W
AT
ER
T R
EA
TM
EN
T
EV
AL
U
AT
IO
N
\D R
AW
IN
G S\
.E
N V
- P &I
D .D
W G
SHEET
OF
DESIGNER
STAMPS, LOGOS, AND SEALS
PROJECT NAME
DRAWING TITLE
CHECKED
ARCHIVE NO.
SUB SHEET NO.
DATENO.
REVISION / ISSUE
MONUMENT FIRE
CENTER
WATER TREATMENT
PIKE-SAN ISABEL
NATIONAL FORESTS &
CIMARRON AND COMANCHE
NATIONAL GRASSLANDS
PIKES PEAK RANGER DISTRICT
MONUMENT FIRE CENTER
R2
ROCKY MOUNTAIN REGION
9/10/2025 18
FOREST SERV I CE
DEPA R TMENT OF AGR I CU LT
UR
E
DATE
UNITED STATES
DEPARTMENT OF AGRICULTURE
FOREST SERVICE
WYE
KAT
G1.1
N/A
PROCESS &
INSTRUMENTATION
DIAGRAM
28699
KE
V IN A . TONE
PROFESS I ONA L ENG I NEER
CO
9/
/2
:0
JC
D N
:\2
8.
EN
V
- U
SD
A
FS
M O
N U
M
EN
T
FI
R E
C
EN
TE
R
W
AT
ER
T R
EA
TM
EN
T
EV
AL
U
AT
IO
N
\D R
AW
IN
G S\
.E
N V
- D
EM
O .D
W G
SHEET
OF
DESIGNER
STAMPS, LOGOS, AND SEALS
PROJECT NAME
DRAWING TITLE
CHECKED
ARCHIVE NO.
SUB SHEET NO.
DATENO.
REVISION / ISSUE
MONUMENT FIRE
CENTER
WATER TREATMENT
PIKE-SAN ISABEL
NATIONAL FORESTS &
CIMARRON AND COMANCHE
NATIONAL GRASSLANDS
PIKES PEAK RANGER DISTRICT
MONUMENT FIRE CENTER
R2
ROCKY MOUNTAIN REGION
9/10/2025 18
FOREST SERV I CE
DEPA R TMENT OF AGR I CU LT
UR
E
DATE
UNITED STATES
DEPARTMENT OF AGRICULTURE
FOREST SERVICE
WYE
KAT
G1.2
N/A
EQUIPMENT
RELOCATION
1. SALVAGE AND REINSTALL HATCHED ITEMS SHOWN IN THE ABOVE IMAGES
INCLUDING FILTER HOUSINGS, FLOW METER, AND BAFFLE TANKS.
2. ITEMS TO BE SALVAGED AND REINSTALLED INCLUDE FILTER CARTRIDGES,
FLOW METER, AND BAFFLE TANKS.
3. DEMO ALL OTHER ITEMS, NOT TO BE SALVAGED
NOTE:
28699
KE
V IN A . TONE
PROFESS I ONA L ENG I NEER
CO
VTC
CWA
SF
4.0 0'
CD1.0
CD1.0
CD1.0
CD1.0
CD1.0
EXIST
GROUNDWATER
WELL
EXIST WTF BUILDING TO BE DEMOLISHED AS PART OF THIS CONTRACT. CONTRACTOR TO COORDINATE WITH CONTRACTING OFFICER.
CONTRACTOR TO DEMO BUILDING AFTER RELOCATING EXIST EQUIPMENT. REMOVE BUILDING, SLAB, AND FOUNDATION TO 12" BELOW GRADE.
REMAINING FOUNDATION CAN BE BURIED.
APPROX SIZE OF PREFABRICATED WTF BUILDING SHOWN FOR REFERENCE. CONTRACTOR TO COORDINATE
WITH CONTRACTING OFFICER FOR FINAL BUILDING DIMENSIONS AND FFE.
FFE USED FOR GRADING:74.55
APPROX SIZE OF CONCRETE FOUNDATION SLAB SHOWN FOR REFERENCE: CONTRACTOR TO
COORDINATE WITH CONTRACTING OFFICER FOR FINAL SLAB DIMENSIONS
15.5 LF 1.5" PVC FINISHED WATER TO
POTABLE WATER TANK
CONNECT TO EXIST WATER MAIN. CONTRACTOR TO POTHOLE AND VERIFY LOCATION, MATERIAL, SIZE AND
DEPTH PRIOR TO CONSTRUCTION. CONTRACTOR TO COORDINATE WITH CONTRACTING OFFICER.
JUNCTION BOX RE:
ELECTRICAL
ABANDONED TELEPHONE
LINE PER SURVEY
CONNECT NEW WELL LINE TO EXIST PITLESS
ADAPTOR. CONTRACTOR TO POTHOLE AND VERIFY
LOCATION, MATERIAL, SIZE AND DEPTH PRIOR TO
CONSTRUCTION. CONTRACTOR TO COORDINATE
WITH CONTRACTING OFFICER
ELECTRICAL LINE
RE: ELECTRICAL
ELECTRICAL LINE
RE: ELECTRICAL
ELECTRICAL LINE
RE: ELECTRICAL
EXISTING STORAGE TANK LINE INTO EXISTING WTF BUILDING NOT SHOWN IN SURVEY.
CONTRACTOR TO VERIFY LOCATION. CUT AND CAP AT EXISTING WTF BUILDING.
DISCONNECT AND CAP EXISTING
ELECTRICAL AND CONTROL LINE
EXISTING WELL LINE NOT SHOWN IN SURVEY.
CONTRACTOR TO VERIFY LOCATION. DISCONNECT AND
CAP AT EXISTING WTP BUILDING
DISCONNECT AND CAP EXISTING
ELECTRICAL AND CONTROL LINE
CONCRETE
WASHOUT AREA
VEHICLE TRACKING
CONTROL
SEDIMENT CONTROL LOGS
41.5 LF 1.5" PVC RAW
WATER TO WTF
CONCRETE ENTRANCE PAD
CD1.0
SF
EXPANSION JOINT TO BE INSTALLED BETWEEN
ENTRANCE PAD AND BUILDING PAD
CD1.0
24" X 6" FLOOR PENETRATION FOR ELECTRICAL CONDUITS (OWNER TO
COORDINATE LOCATION WITH PREMANUFACTURED BUILDING SUPPLIER)
SCALE IN FEET
10 10 20
5/ 7/
1:
L
JF
N :\2
8.
EN
V
- U
SD
A
FS
M
O N
U M
EN
T
FI
R
E C
EN
TE
R
W
AT
ER
T
R
EA
TM
EN
T
EV
AL
U
AT
IO
N \D
R
AW
IN
G
S\
.E N
V
- 0
1- C
SI
TE
-0 0.
D W
G
SHEET
OF
DESIGNER
STAMPS, LOGOS, AND SEALS
PROJECT NAME
DRAWING TITLE
CHECKED
ARCHIVE NO.
SUB SHEET NO.
DATENO.
REVISION / ISSUE
MONUMENT FIRE
CENTER
WATER TREATMENT
PIKE-SAN ISABEL
NATIONAL FORESTS &
CIMARRON AND COMANCHE
NATIONAL GRASSLANDS
PIKES PEAK RANGER DISTRICT
MONUMENT FIRE CENTER
R2
ROCKY MOUNTAIN REGION
05/2025 18
FOREST SERV I CE
DEP A R TMENT OF AGR I CU LT
UR
E
DATE
UNITED STATES
DEPARTMENT OF AGRICULTURE
FOREST SERVICE
C:\Users\tcmichael\Box\CDI\RIOG\Bldgs\SupvOffice-School\2019-Remodel\AE IDIQ\Provided-Info\DWG\CDILogo-BW.jpg
CIVIL SITE PLANS
CAP
KAT
C1.0
1. CONTRACTOR IS RESPONSIBLE FOR RESTORING ALL DISTURBED AREAS TO
THEIR ORIGINAL CONDITIONS.
2. ALL SPOT ELEVATIONS ARE TO FINISHED GRADE OR FLOWLINE UNLESS
OTHERWISE SPECIFIED.
3. SPOT ELEVATIONS PROVIDED BY THE USFS HAVE BEEN PROJECTED INTO
THE EXISTING SURFACE FILE TO BETTER REFLECT ACTUAL SURFACE
GRADES. CONTRACTOR TO VERIFY ALL SPOT GRADES AND COORDINATE
WITH USFS WITH ANY DISCREPANCIES.
GRADING AND DRAINAGE NOTES:
1. CONTRACTOR IS RESPONSIBLE FOR INSTALLING AND MAINTAINING ALL
CONTROLS DURING INITIAL, INTERIM, AND FINAL CONDITIONS.
2. ALL CONTROLS SHALL BE INSTALLED WITHIN THE PROPERTY LINES UNLESS
OTHERWISE SPECIFIED. WHEN CONSTRUCTION ACTIVITIES DISTURB
ADJACENT AND/OR RIGHT-OF-WAY PROPERTIES, COORDINATION WITH
PROPERTY OWNERS IS REQUIRED PRIOR TO CONSTRUCTION.
3. VTC PAD TO BE COORDINATED WITH CONTRACTING OFFICER
EROSION AND SEDIMENTATION NOTES:
VEHICLE TRACKING CONTROL
SILT FENCE
EROSION CONTROL LEGEND
EXISTING INDEX CONTOUR
EXISTING INTERMEDIATE CONTOUR
PROPOSED INDEX CONTOUR
PROPOSED INTERMEDIATE CONTOUR
CONCRETE WASHOUT AREA
VTC
SF
CWA
1. CONTRACTOR TO FIELD VERIFY ALL EXISTING UNDERGROUND UTILITIES
PRIOR TO CONSTRUCTION. REFER TO GENERAL NOTES FOR UTILITY
LOCATION AND PROTECTION. COORDINATE WITH USFS.
2. CONTRACTOR TO POTHOLE EXISTING UTILITIES AT PROPOSED UTILITY
CROSSINGS PRIOR TO CONSTRUCTION. COORDINATE WITH USFS.
3. CONTRACTOR TO MARK ALL UTILITY STUBS WITH MARKERS.
4. CONTRACTOR TO MAINTAIN A MINIMUM BURIAL DEPTH OF 7.0' OR MATCH
EXISTING, WHICHEVER IS GREATER. COORDINATE WITH USFS.
UTILITY NOTES:
1. CONTRACTOR TO FIELD VERIFY ALL EXISTING UNDERGROUND UTILITIES
PRIOR TO CONSTRUCTION. REFER TO GENERAL NOTES FOR UTILITY
LOCATION AND PROTECTION.
2. ACTUAL LIMITS MAY VARY, CONTRACTOR IS RESPONSIBLE FOR ADJUSTING
LIMITS OF DEMOLITION AND CONSTRUCTION AS NECESSARY. COORDINATE
DEMOLITION REQUIREMENTS, LIMITS OF DEMOLITION, SALVAGE ITEMS,
PROTECTION OF ITEMS TO REMAIN, TREES, FENCING, ETC. WITH
CONTRACTING OFFICER.
3. ALL NECESSARY EROSION AND SEDIMENTATION CONTROLS MUST BE
INSTALLED PRIOR TO SITE DISTURBANCE.
4. CONTRACTOR TO COMPLY WITH ALL REGULATORY REQUIREMENTS FOR
HAZARDOUS MATERIAL REMOVAL AND DISPOSAL.
5. CONTRACTOR TO TAKE NECESSARY PRECAUTIONS TO PROTECT AND
MAINTAIN ALL UTILITIES DURING CONSTRUCTION.
6. CONTRACTOR TO REPAIR/REPLACE ALL DAMAGE TO EXISTING FLATWORK
OR SITE FEATURES NOT INTENDED FOR DEMOLITION.
7. IF SLAB DIMENSIONS AND FFE ARE DIFFERENT THAN SHOWN,
CONTRACTOR SHALL ADJUST GRADING ACCORDINGLY AND PROVIDE
POSITIVE DRAINAGE AWAY FROM THE BUILDING.
DEMOLITION NOTES:
DEMOLITION LEGEND
DEMO BUILDING
PROTECT EXISTING TREE
28699
KE
V IN A . TONE
PROFESS I ONA L ENG I NEER
CO
LORADO L I CENSED
STAMPS, LOGOS, AND SEALS
C1.0
VEHICLE TRACKING CONTROL DETAIL
NTS
WIDTH VARIES50'-0" MIN LENGTH
OR HARD SURFACE
(AS REQUIRED)
EXIST PAVED ROAD
3" TO 6" ROCK AT 6" TO 12" DEPTH INSTALLED
OVER LAYER OF NON-WOVEN GEOTEXTILE
NOTES:
1. VEHICLE TRACKING CONTROL PADS SHALL BE INSTALLED AT ALL INGRESS/EGRESS POINTS WHERE
VEHICULAR ACCESS TRANSITIONS FROM PAVED SURFACES TO DISTURBED SURFACES.
2. THE VTC PAD SHALL CONSIST OF HARD, ANGULAR, DENSE, AND DURABLE STONE. ROUNDED STONE, BOULDERS, RECYCLED ASPHALT, AND RECYCLED CONCRETE ARE NOT ACCEPTABLE.
3. ANY CRACKED OR DAMAGED CURB AND/OR GUTTER SHALL BE REPLACED BY THE CONTRACTOR.
4. PAD WILL BE REPAIRED AND REFRESHED AS NEEDED TO MAINTAIN FUNCTION AND INTEGRITY.
5. VTC PADS SHALL BE INSTALLED AT ALL CONCRETE WASHOUT AREAS AND AT STABILIZED
STAGING/STORAGE AREAS.
VTC
C1.0
CONCRETE WASHOUT FACILITY DETAIL
NTS
EXCAVATED
AREA
' M
IN
CONTAINMENT
AREA
VEHICLE TRACKING
CONTROL PAD
TOP OF PERIMETER
BERM
COMPACTED
EMBANKMENT
TOE OF FILL
5:1
COMPACTED
EMBANKMENT
(TYP)
EXCAVATED
AREA
PERIMETER
BERM
10' MIN
MI
N2'
MI
N
1 EXCAVATED
AREA
10' MIN
MI
N
VEHICLE TRACKING
CONTROL PAD
SECTION A-A
SECTION B-B
PLAN VIEW
A A
B
B "CONCRETE WASHOUT AREA"
IDENTIFIER SIGN
CWA
NOTE:
CONTRACTOR MAY USE PORTABLE
CONCRETE WASHOUT FACILITY AS
OPTION
C1.0
CONCRETE SECTION DETAIL
NTS
NOTES:
1. CONCRETE THICKNESS:4" FOR BUILDING ENTRANCE PAD
2. ALL CONCRETE SHALL HAVE FIBERMESH REINFORCEMENT.
2.1. FIBROUS REINFORCEMENT: COLLATED, FIBRILLATED,
POLYPROPYLENE FIBERS, TENSILE STRENGTH 70,000 PSI
i) ASTM C1116 AND ASTM D7508
ii) USE MINIMUM OF 1.5 POUNDS PER CUBIC YARD
iii) FIBERMESH OR ACCEPTED SUBSTITUTION
3. CONCRETE REQUIREMENTS: COMPLY WITH ASTM C94
3.1. MAXIMUM COARSE AGGREGATE SIZE: 1-INCH
3.2. PORTLAND CEMENT: ASTM C595, TYPE IL; 555 POUNDS
MINIMUM PER CUBIC YARD OF CONCRETE
3.3. WATER/CEMENTITIOUS MATERIAL (CEMENT AND FLY ASH)
RATIO: LESS THAN OR EQUAL TO 0.45
3.4. SLUMP: 4-INCH MAXIMUM
3.5. VOLUMETRIC AIR CONTENT: 6.0%±2% AFTER PLACEMENT FOR
1-INCH AGGREGATE
3.6. STRENGTH: COMPRESSIVE STRENGTH AS DETERMINED BY
ASTM C39, 4,500 PSI MINIMUM AT 28 DAYS
OVEREXCAVATED, MOISTURE-TREATED AND
RECOMPACTED SUBGRADE PER SPECIFICATIONS
CONCRETE
4" 4"
C1.0
TYPICAL TRENCH DETAIL
NTS
MAX COMPACTED
BACKFILL TO 95% STD
PROCTOR DENSITY
(SEE NOTE 1)
FINAL GRADE
SEE TABLE
8" LIFTS
WIDTH
EXISTING
12"
BASE COURSE
6"
NEW BASE COURSE
SURFACE
EXIST STREET
ASPHALT/CONCRETE
UNIFORM CUT LINE
NEW PAVEMENT SURFACE
WIDTHDIA WIDTH
1'-4"1.5" 2'-4"
MIN.PIPE MAX.
IN OPEN FIELD IN STREET
6"
7'
MI
N
CO
VE
R
PIPE
(DIP, PVC,
OR COPPER)GRANULAR
BEDDING
NOTES:
1. MINIMUM COVER TO BE 7' BELOW FINAL GRADE
2. COMPACTED BACKFILL TO 90% STD PROCTOR DENSITY IN NON-DRIVING SURFACES AND 95% UNDER
PAVEMENT
3. SHOULD THE TRENCH BE EXCAVATED WIDER THAN ALLOWED, A CONCRETE CRADLE SHALL BE
PLACED WITH 2500PSI CONCRETE FROM TRENCH BOTTOM TO PIPE SPRINGLINE. REFER TO DETAIL 4
ON SHEET CD1.0 FOR SITE CONCRETE SPECIFICATIONS.
4. TRENCH TO BE BRACED OR SHEETED AS NECESSARY FOR THE SAFETY OF THE WORKMEN AND THE PROTECTION OF OTHER UTILITIES IN ACCORDANCE WITH LOCAL, STATE, FEDERAL, & OSHA SAFETY
REGULATIONS
5. PAVING SHALL COMPLY WITH LOCAL AUTHORITY JURISDICTION
6. WARNING TAPE TO BE INSTALLED 18" ABOVE TOP OF PIPE
C1.0
SEDIMENT CONTROL LOG DETAIL
NTS
3' MAX
1'- 6"
2'- 6"
3" MIN
2" MIN
6" AT END LOGS
CONTROL LOG
12" DIA. SEDIMENT
A
A
SECTION A-A
FLOW
ENDS SHALL BE TIGHTLY ABUTTED
WOOD STAKES
SEDIMENT CONTROL LOG INSTALLATION NOTES:
1. SEE PLAN VIEW FOR LOCATION AND EXTENT OF SEDIMENT CONTROL LOGS.
2. SEDIMENT CONTROL LOGS SHALL BE INSTALLED PRIOR TO ANY LAND DISTURBING ACTIVITIES AND
AS REQUIRED DURING CONSTRUCTION.
3. SEDIMENT CONTROL LOGS SHALL CONSIST OF STRAW, COMPOST, EXCELSIOR, OR COCONUT FIBER.
4. NOT FOR USE IN CONCENTRATED FLOW AREAS.
5. THE SEDIMENT CONTROL LOG SHALL BE TRENCHED INTO THE GROUND A MINIMUM OF 2".
SCL
6"
FLOW
A B
SPACE LOGS SUCH THAT
POINTS A AND B ARE
OF EQUAL ELEVATION
SEDIMENT CONTROL LOG MAINTENANCE NOTES:
1. THE SEDIMENT CONTROL LOGS SHALL BE INSPECTED DAILY, DURING AND AFTER ANY STORM
EVENT, AND REPAIRED OR HAVE ANY UPSTREAM SEDIMENT REMOVED.
2. SEDIMENT ACCUMULATED UPSTREAM OF SEDIMENT CONTROL LOGS SHALL BE REMOVED WHEN
THE UPSTREAM SEDIMENT DEPTH IS WITHIN 1/2 THE HEIGHT OF THE CREST OF LOG.
3. ALL SEDIMENT CONTROL LOGS SHALL BE REMOVED AT THE END OF CONSTRUCTION. IF ANY
DISTURBED AREA EXISTS AFTER REMOVAL, IT SHALL BE DRILL SEEDED AND CRIMP MULCHED OR
OTHERWISE ACCEPTABLY STABILIZED.
WARNING
TAPE
CONCRETE JOINT DETAIL
NOTE:
CONTRACTION JOINTS AT INTERVAL TO MATCH
WIDTH OF SIDEWALK (TYP).
1/8"
TOOLED JOINT
OR SAWCUT1/8" R1/3 OF CONCRETE
THICKNESS
(ASI-305)
NOTES:
1. CURB EXPANSION JOINTS EVERY 100' MAX AND WHEREVER SIDEWALK ABUTS EXISTING & PROPOSED
CONCRETE STRUCTURES (TYP) - SEE PLAN
2. REMOVE PLASTIC FORMING MATERIAL ("ZIP STRIPS") FROM PREFORMED JOINT MATERIAL PRIOR TO
PLACING SEALANT
3. EXPANSION JOINT MATERIAL: 0.5-INCH THICK, ASTM D1751, ASPHALT IMPREGNATED FIBER BOARD, GLASS
FIBER OR SPONGE, OR CLOSED CELL POLYETHYLENE FOAM; TEXMASTIC “VINYLEX 3600,” SONNEBORN
“SONOFLEX F,” OR ACCEPTED SUBSTITUTIONS
SIDEWALK
AGAINST STRUCTURE AGAINST NON-UNIFORM SURFACE
6"
(MIN)
CONTRACTION/CONTROL JOINT
EXISTING BUILDING OR STRUCTURE
SEAL EXPANSION JOINT W/
POLYURETHANE JOINT SEALANT
1/2" DEEP X 1/2" WIDE
1/2" PREFORMED NON-EXTRUDING AND RESILIENT
TYPE JOINT MATERIAL TO MEET AASHTO M-213.
SEAL EXPANSION JOINT W/
POLYURETHANE JOINT SEALANT
1/2" DEEP X 1/2" WIDE
1/2" PREFORMED NON-EXTRUDING
AND RESILIENT TYPE JOINT
MATERIAL TO MEET AASHTO M-213.
1/8" R
SEAL EXPANSION JOINT W/
POLYURETHANE JOINT SEALANT
1/2" DEEP X 1/2" WIDE
1/2" PREFORMED NON-EXTRUDING AND RESILIENT
TYPE JOINT MATERIAL TO MEET AASHTO M-213.
5/ 7/
1:
L
JF
N :\2
8.
EN
V
- U
SD
A
FS
M
O N
U M
EN
T
FI
R
E C
EN
TE
R
W
AT
ER
T
R
EA
TM
EN
T
EV
AL
U
AT
IO
N \D
R
AW
IN
G
S\
.E N
V
- 0
1- C
SI
TE
-D
ET
-0 0.
D W
G
SHEET
OF
DESIGNER
STAMPS, LOGOS, AND SEALS
PROJECT NAME
DRAWING TITLE
CHECKED
ARCHIVE NO.
SUB SHEET NO.
DATENO.
REVISION / ISSUE
MONUMENT FIRE
CENTER
WATER TREATMENT
PIKE-SAN ISABEL
NATIONAL FORESTS &
CIMARRON AND COMANCHE
NATIONAL GRASSLANDS
PIKES PEAK RANGER DISTRICT
MONUMENT FIRE CENTER
R2
ROCKY MOUNTAIN REGION
05/2025 18
FOREST SERV I CE
DEP A R TMENT OF AGR I CU LT
UR
E
DATE
UNITED STATES
DEPARTMENT OF AGRICULTURE
FOREST SERVICE
C:\Users\tcmichael\Box\CDI\RIOG\Bldgs\SupvOffice-School\2019-Remodel\AE IDIQ\Provided-Info\DWG\CDILogo-BW.jpg
SITE DETAILS
CAP
KAT
CD1.0
28699
KE
V IN A . TONE
PROFESS I ONA L ENG I NEER
CO
LORADO L I CENSED
STAMPS, LOGOS, AND SEALS
SCALE OF FEET
0 1 2
TREATMENT BUILDING
1" = 1'-0"
P1.1 A
POWER DISTRIBUTION PANEL
4" MIN FLOOR PENETRATION
(SEAL PENETRATION)
BACKFLOW
PREVENTER
WTF CONTROL PANEL
RELOCATED
FLOW
METER 1.5" BALL VALVE
(TYP 8)
RELOCATED
PRE-FILTER
(PF-1)
RELOCATED ACID WASH
CARBON FILTER
(AWCF-1)
SAMPLE TAP
(TYP 8)
RELOCATED KDF FILTER
(KDF-1)
GREENSAND FILTER
(GS-1)
PHOSPHORIC ACID TANK CHLORINE TANK CAUSTIC TANK
PHOSPHORIC ACID PUMP
CHLORINE PUMP CAUSTIC PUMPSTATIC MIXER
RELOCATED BAFFLE
TANK NO. 1
RELOCATED BAFFLE
TANK NO. 2
4" MIN FLOOR PENETRATION
(SEAL PENETRATION)
1. CONTRACTOR TO INSTALL ALL EQUIPMENT LEVEL.
2. CARTRIDGES FOR FILTERS WILL BE PROVIDED AND
INSTALLED BY FOREST SERVICE. CONTRACTOR TO
COORDINATE AS NEEDED.
3. OWNER TO COORDINATE PENETRATION LOCATIONS
WITH PRE-MANUFACTURED BUILDING SUPPLIER
4. REFERENCE MECHANICAL SHEETS FOR EXHAUST FAN
AND LOUVER OPENING DIMENSIONS AND LOCATIONS
NOTE:
sc4500TRANSMITTER
PH SENSOR
WORK RAMP
4'
2'- 9"
PORTABLE EYE
WASH STATION
PRESSURE TRANSMITTER
PD1.0
'-0
18'-0"
24"x6" FLOOR PENETRATION FOR FOUR
ELECTRICAL CONDUITS
(RE: ELEC)
(SEAL PENETRATION)
RELOCATED FINAL FILTER
(FF-1)
P1.1 B
PRESSURE TRANSMITTER
INJECTION POINT FOR
CHLORINE TANK
CALIBRATION COLUMN
PANEL
(TYP 2)
9/
/2
:0
JC
D N
:\2
8.
EN
V
- U
SD
A
FS
M O
N U
M
EN
T
FI
R E
C
EN
TE
R
W
AT
ER
T R
EA
TM
EN
T
EV
AL
U
AT
IO
N
\D R
AW
IN
G S\
PL
AN
T 3D
\2
8.
EN
V
- M O
N U
M
EN
T
FI
R E
C
EN
TE
R
\O R
TH
O
S\ D
W G
S\ M
O N
U M
EN
T
O R
TH
O
S.
D
W G
MONUMENT FIRE
CENTER
WATER TREATMENT
PIKE-SAN ISABEL
NATIONAL FORESTS &
CIMARRON AND COMANCHE
NATIONAL GRASSLANDS
PIKES PEAK RANGER DISTRICT
MONUMENT FIRE CENTER
R2
ROCKY MOUNTAIN REGION
9/10/2025 18
SHEET
OF
DESIGNER
STAMPS, LOGOS, AND SEALS
PROJECT NAME
DRAWING TITLE
CHECKED
ARCHIVE NO.
SUB SHEET NO.
DATENO.
REVISION / ISSUE
FOREST SERV I CE
DEP A R TMENT OF AGR I CU LT
UR
E
DATE
UNITED STATES
DEPARTMENT OF AGRICULTURE
FOREST SERVICE
TREATMENT
BUILDING
WY
KAT
P1.0
N/A
28699
KE
V IN A . TONE
PROFESS I ONA L ENG I NEER
CO
SCALE OF FEET
0 1 2
POWER DISTRIBUTION PANEL
6" MIN FLOOR PENETRATION
(OWNER TO COORDINATE LOCATION WITH
PREMANUFACTURED BUILDING SUPPLIER)
WTF CONTROL PANEL
BALL VALVE
(TYP 8)
RELOCATED
PRE-FILTER
(PF-1)
SAMPLE TAP
(TYP 8)
GREENSAND FILTER
(GS-1)
PHOSPHORIC
ACID PUMP
CHLORINE PUMPCAUSTIC PUMP
STATIC MIXER
PIPE SUPPORT
(TYP)
4" MIN FLOOR PENETRATION
(OWNER TO COORDINATE LOCATION WITH
PREMANUFACTURED BUILDING SUPPLIER)
RELOCATED ACID WASH
CARBON FILTER
(AWCF-1)
RELOCATED FINAL FILTER
(FF-1)
BACKFLOW
PREVENTER
RELOCATED
FLOW
METER
9/
/2
:0
JC
D N
:\2
8.
EN
V
- U
SD
A
FS
M O
N U
M
EN
T
FI
R E
C
EN
TE
R
W
AT
ER
T R
EA
TM
EN
T
EV
AL
U
AT
IO
N
\D R
AW
IN
G S\
PL
AN
T 3D
\2
8.
EN
V
- M O
N U
M
EN
T
FI
R E
C
EN
TE
R
\O R
TH
O
S\ D
W G
S\ M
O N
U M
EN
T
O R
TH
O
S.
D
W G
MONUMENT FIRE
CENTER
WATER TREATMENT
PIKE-SAN ISABEL
NATIONAL FORESTS &
CIMARRON AND COMANCHE
NATIONAL GRASSLANDS
PIKES PEAK RANGER DISTRICT
MONUMENT FIRE CENTER
R2
ROCKY MOUNTAIN REGION
9/10/2025 18
ARV
A P1.0
SECTION
1" = 1'-0"
B P1.0
SECTION
1" = 1'-0"
RELOCATED BAFFLE
TANK NO. 2
RELOCATED BAFFLE
TANK NO. 1
CONNECTION W/
MALE ADAPTOR
(TYP 2)
BALL VALVE
(TYP 8)
WORK RAMP
sc4500
TRANSMITTER
PH SENSOR
PORTABLE EYEWASH STATION
(COORDINATE FINAL LOCATION
DURING CONSTRUCTION)
PRESSURE TRANSMITTER
PD1.0
PD1.0CHEMICAL INJECTION
(TYP 3)
RELOCATED KDF FILTER
(KDF-1)
PD1.0
PUMP SHELF
(TYP 3)
PRESSURE TRANSMITTER
CAUSTIC TANK CHLORINE TANK PHOSPHORIC ACID TANK
CALIBRATION COLUMN PANEL
(COORDINATE FINAL LOCATION
DURING CONSTRUCTION)
CALIBRATION COLUMN
(TYP 2)
BALL VALVE
(TYP 2)
CAM LOCK
(TYP 2)
FROM CHLORINE PUMP
TO INJECTION POINT
PRV, PRESSURE GAUGE, VALVES, ETC.
NOT SHOWN, PROVIDED IN SUBMITTAL
(RE: G1.1)
(TYP 2)
SHEET
OF
DESIGNER
STAMPS, LOGOS, AND SEALS
PROJECT NAME
DRAWING TITLE
CHECKED
ARCHIVE NO.
SUB SHEET NO.
DATENO.
REVISION / ISSUE
FOREST SERV I CE
DEPA R TMENT OF AGR I CU LT
UR
E
DATE
UNITED STATES
DEPARTMENT OF AGRICULTURE
FOREST SERVICE
N/A
P1.1
KAT
WY
TREATMENT
BUILDING
28699
KE
V IN A . TONE
PROFESS I ONA L ENG I NEER
CO
LORADO L I CENSED
CHEMICAL INJECTOR DETAIL
NTS
P1.0
BALL VALVE
NPT TUBE FITTING
FLEXIBLE TUBING
(SEE PLAN FOR
SIZE & MATERIAL)
SST SAFETY
CHAIN & LOCK
PIPE
(SEE PLAN FOR
SIZE & MATERIAL)
ELASTOMERIC
CHECK VALVE
SOLUTION
TUBE
1/3 TO 1/2
Ø OF PIPE
NPT TUBE FITTING
BALL CHECK VALVE
PACKING NUT
SOLUTION TUBE ADAPTOR
CORPORATION STOP
TAPPING SADDLE OR BOSS
FROM
METERING PUMP
1 PIPE
2 sc4500 CONTROLLER 3 pH PROBE
4 INSERTION MOUNT
NOTE
1. pH PROBE SHALL BE INSTALLED
VERTICALLY IN HORIZONTAL PIPE.
FLOOR PIPE SUPPORT DETAIL
NTS
PIPE
2", 3" 4"-12" 14"-16" 18"-24"
CLAMP
.375"x1.5" .5"x2"
.625"x3" .75"x4"
THREADED
.75" 1"
1.5" 2"
STUD ØSIZE SIZE
BASE
6"x6" 8"x8"
12"x12" 12"x12"
PLATE
BASE
2" 2" 3" 4"
PIPE
P1.0
TWO PIECE, FULL CIRCLE
SADDLE CLAMP TO MATCH
PIPE DIAMETER
BOLT BASE PLATE TO FLOOR W/
1/2"Ø EXPANSION OR
ADHESIVE ANCHORS, 1/2" EMBED
(UNLESS OTHERWISE NOTED)
NUT WELDED
TO BASE PIPE
THREADED STUD
1/2" NEOPRENE GASKET
GLUED TO SADDLE
NON-SHRINK GROUT
(1" MIN)
BASE PIPE WELDED
TO BASE PLATE
PAINT TO MATCH
PIPING
*USE MINIMUM 3" BASE PIPE FOR PIPE SUPPORT TALLER THAN 36"
PIPE HANGER DETAIL
NTS
PIPE SIZE
2" & SMALLER
2 1/2" 3" & 4"
6" THRU 12"
HANGER ROD Ø
3/8" 1/2" 5/8" 3/4"
P1.0
PIPE
(SEE PLAN FOR
SIZE & MATERIAL)
CLEVIS HANGER
ANVIL INTL FIG 260
OR ACCEPTED SUBSTITUTION
HANGER ROD
PAINT TO MATCH PIPING
NOTE:
TOTAL LOADING ON EACH CONCRETE INSERT SHALL NOT
EXCEED MANUFACTURER'S RECOMMENDED LOADINGS.
SEE PLANS
FOR CEILING TYPE
ANCHOR OR BEAM CLAMP
TO SUIT BUILDING
CONSTRUCTION
UNISTRUT WALL PIPE SUPPORT DETAIL
NTS
P1.0
1/2"Ø EXP BOLTS
W/ 1/2" EMBED
(TYP 2)
P1000 UNISTRUT
W/ PIPE CLAMP
@ 10' OC
PIPE
(SEE PLANS)
CONC WALL
90°
WALL PIPE SUPPORT DETAIL
NTS
VARIES
(SEE PLAN)
1/4" BOTH SIDES
P1.0
GALV STL ANGLE
OR BENT PLATE
P1.0 pH SENSOR DETAIL
NTS
9/ 9/
4:
J C
D N
:\2
8.
EN
V
- U
SD
A
FS
M O
N U
M
EN
T
FI
R E
C
EN
TE
R
W
AT
ER
T R
EA
TM
EN
T
EV
AL
U
AT
IO
N
\D R
AW
IN
G S\
.E
N V
- P R
O C
ES
S
D
ET
AI
LS
.D W
G
SHEET
OF
DESIGNER
STAMPS, LOGOS, AND SEALS
PROJECT NAME
DRAWING TITLE
CHECKED
ARCHIVE NO.
SUB SHEET NO.
DATENO.
REVISION / ISSUE
MONUMENT FIRE
CENTER
WATER TREATMENT
PIKE-SAN ISABEL
NATIONAL FORESTS &
CIMARRON AND COMANCHE
NATIONAL GRASSLANDS
PIKES PEAK RANGER DISTRICT
MONUMENT FIRE CENTER
R2
ROCKY MOUNTAIN REGION
9/10/2025 18
FOREST SERV I CE
DEPA R TMENT OF AGR I CU LT
UR
E
DATE
UNITED STATES
DEPARTMENT OF AGRICULTURE
FOREST SERVICE
WY
KAT
PD1.0
N/A
PROCESS DETAILS
28699
KE
V IN A . TONE
PROFESS I ONA L ENG I NEER
CO
MECHANICAL COVER SHEET
-0 9-
B
ID
S
ET
M0.1
SHEET NO. SHEET DESCRIPTION
SHEET INDEX
ISSUE
MECHANICAL PLANM1.0
MECHANICAL SCHEDULESM3.1
ABOVE FINISHED FLOORAFF
DESCRIPTION
MECHANICAL LEGEND
SYMBOLABBR
RA
SA
MVD
OA
EA
SUPPLY AIR
RETURN AIR
EXHAUST AIR
OUTSIDE AIR
MANUAL VOLUME DAMPER
UNO UNLESS NOTED OTHERWISE
EXISTINGE
DEMOD
POINT OF CONNECTION NEW TO EXISTING
T-STAT THERMOSTATT
S SPACE TEMP SENSOR W/ OVERIDE & LCD SETPOINT ADJUSTMENT
GENERAL NOTES
1. ALL WORK SHALL BE INSTALLED IN ACCORDANCE WITH ALL APPLICABLE STATE CODES, LOCAL CODES, AND
OWNER'S STANDARDS INDICATED BY THE CONSTRUCTION DOCUMENTS.
2. MECHANICAL DRAWINGS ARE DIAGRAMMATIC AND DO NOT NECESSARILY INDICATE EVERY REQUIRED OFFSET, FITTING, ETC. DRAWINGS ARE NOT TO BE SCALED FOR DIMENSIONS. TAKE ALL DIMENSIONS FROM ARCHITECTURAL DRAWINGS, CERTIFIED EQUIPMENT DRAWINGS AND FROM THE STRUCTURE ITSELF BEFORE FABRICATING ANY WORK, VERIFY ALL SPACE REQUIREMENTS COORDINATING WITH OTHER TRADES, AND
INSTALL THE SYSTEMS IN THE SPACE PROVIDED WITHOUT EXTRA CHARGES TO THE OWNER.
3. CONTRACTOR SHALL COORDINATE WORK INDICATED WITH PLUMBING, ELECTRICAL, FIRE PROTECTION, STRUCTURAL, AND ARCHITECTURAL DIVISIONS. VERIFY FIT OF MECHANICAL SYSTEMS PRIOR TO FABRICATION. COORDINATE ALL CHASE, SLEEVE, AND SLAB BLOCKOUT REQUIREMENTS BEFORE CONCRETE
IS POURED OR BLOCK IS SET.
4. PROVIDE ALL EQUIPMENT SCHEDULED OR INDICATED ON THE DRAWINGS BUT NOT INCLUDED WITHIN THE SPECIFICATIONS INCLUDING ANY REQUIRED BUT NOT LISTED MISC ITEMS NEEDED TO PROVIDE COMPLETELY OPERATIONAL SYSTEMS AS INDICATED WHETHER SPECIFICALLY CALLED FOR OR NOT. INSTALLATION SHALL CONFORM TO MANUFACTURERS RECOMMENDATIONS AND APPLICABLE CODES. PROVIDE SUBMITTALS FOR ALL PROPOSED EQUIPMENT AND MATERIALS TO BE UTILIZED. PROVIDE OPERATION AND MAINTENANCE
MANUAL FOR ALL SYSTEMS AND EQUIPMENT AT END OF PROJECT.
5. ELECTRICAL CHARACTERISTICS OF MECHANICAL EQUIPMENT SHALL BE VERIFIED WITH ELECTRICAL
DRAWINGS AND ELECTRICAL CONTRACTOR PRIOR TO EQUIPMENT ORDER RELEASE. ADDITIONAL
ELECTRICAL WORK RESULTING FROM EQUIPMENT SUBSTITUTION IS THE RESPONSIBILITY OF THIS
CONTRACTOR.
6. DRAIN PIPING FROM EQUIPMENT SHALL BE ROUTED SO AS NOT TO CREATE A TRIPPING HAZARD.
COORDINATE ACTUAL DRAIN CONNECTIONS WITH PLUMBING CONTRACTOR.
7. ITEM DESIGNATIONS INDICATED HEREON ARE FOR PURPOSES OF THESE DOCUMENTS ONLY. CONTRACTOR SHALL VERIFY WITH OWNERS REPRESENTATIVE ACTUAL "TAGGING" INFORMATION TO BE PROVIDED FOR
EACH ITEM OF MECHANICAL EQUIPMENT PRIOR TO NAMEPLATE ORDER RELEASE.
8. DUCT SIZES INDICATED ARE OUTSIDE SHEETMETAL DIMENSIONS, BRANCH RUNOUT DUCTS TO DIFFUSERS AND GRILLES TO BE SAME SIZE AS DIFFUSER OR GRILLE CONNECTION SIZE UNLESS OTHERWISE NOTED.
9. LENGTH OF FLEXIBLE DUCTWORK SHALL BE LIMITED TO 5'-0" MAX. HORIZONTAL RUN WITH ONLY ONE 90^ ELBOW PERMITTED. SECURE FLEXIBLE DUCTWORK WITH SCREWS & DRAWBANDS PER SMACNA STANDARDS.
10. AT THE COMPLETION OF WORK, PROVIDE TESTING AND BALANCING SERVICES FOR MECHANICAL SYSTEM.
SUBMIT WRITTEN REPORT TO ARCHITECT LISTING SYSTEM AIRFLOWS, ELECTRIC DATA, TEMPERATURES, AND
PRESSURE DROPS.
11. AT THE COMPLETION OF THE WORK AND PRIOR TO FINAL ACCEPTANCE, ALL PARTS OF THE WORK INSTALLED
UNDER THIS SPECIFICATION SHALL BE THOROUGHLY CLEANED.
12. ALL EQUIPMENT, MATERIALS, AND INSTALLATION IS TO BE WARRANTEED FOR ONE YEAR TO BE FREE FROM
DEFECT. PROVIDE WRITTEN WARRANTY TO OWNER.
13. THE OWNER AND ENGINEER ARE NOT RESPONSIBLE FOR THE CONTRACTOR'S SAFETY PRECAUTIONS OR TO MEANS, METHODS, TECHNIQUES, CONSTRUCTION SEQUENCES, OR PROCEDURES REQUIRED TO PERFORM
HIS WORK.
MECHANICAL SPECIFICATIONS
SUPPLY, RETURN, EXHAUST AND OUTSIDE AIR DUCTWORK SHALL BE CONSTRUCTED OF GALVANIZED STEEL PER SMACNA DUCT CONSTRUCTION STANDARDS. SUPPLY, RETURN, EXHAUST AND OUTSIDE AIR DUCTWORK SHALL BE CONSTRUCTED FOR 2" W.C. STATIC PRESSURE. SPIRAL LOCK-FORMED ROUND DUCT MAY BE UTILIZED WHERE SPACE ALLOWS.