A06-Test_Report_22-02-16_ESA_T_B_report.pdf

PDF 579 KB Posted

Attached to
WI LEOPOLD WMD HVAC Federal contract opportunity
Solicitation number
140FC223Q0035
Issued by
Department of the Interior Fish and Wildlife Service

About this file

This report documents testing, balancing, and calibration of HVAC systems at the USFWS facility in Portage, Wisconsin under federal contract number 140FC223Q0035. Systems tested include air handlers AH-1 and AH-2 which serve the first floor, with fan information, diffuser and grille airflows, and instrument calibration data provided. Testing was performed by Environmental Systems Analysis, Inc. in accordance with NEBB standards and procedures to verify HVAC systems met design specifications.

View the file

Other files for this federal contract opportunity

Other files attached to WI LEOPOLD WMD HVAC, newest first.
File Type Posted
A06-Crawlspace_piping_to_water_softener_photo.JPG JPG image
B08-Table_of_Contents.pdf PDF
Wage_Determination.pdf PDF
B08-Leopold_Bid_Schedule_-_base_bid1.pdf PDF
A06-UTILITY_ROOM_RELOCATES_Model_drawing.pdf PDF
A06-Foundations_Drawing.pdf PDF
A06-Return_air_box-typical_photo.JPG JPG image
B08-Pre-Con_Safety_FWS_Form_3-2199_(5-03).pdf PDF
A06-Furnace_2_photo.JPG JPG image
B08-Submittals_Report.pdf PDF
A06-Specifications.pdf PDF
B08-York_Submittal.pdf PDF
A06-Drawing_EXISTING-Proposed_HVAC_PAGE.pdf PDF
A06-Furnance_1_photo.JPG JPG image
A06-Crawl_space_area_photo_example.JPG JPG image
Sol_140FC223Q0035.pdf PDF
Show all 16

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Environmental Systems Analysis, Inc.

4262 Argosy Court * Madison, WI 53714

ENVIRONMENTAL Phone: (608)221-8817 * Fax: (608)221-2444 * Email: esa@esa-wi.com SYSTEMS ANALYSIS Testing & Balancing * Air & Hydronics * System Analysis

ESA

ESA PROJECT NO. 22-144

PREPARED BY : Shane Otis

CONTRACTOR: USFWS

W10040 Cascade Mountain Rd.

Portage, WI 53901

ENGINEER: --

ARCHITECT: --

CERTIFIED TEST, ADJUST, AND

BALANCE REPORT

PROJECT: USFWS

W10040 Cascade Mountain Rd.

Portage, WI 53901

USFWS 22-144 Page 1 of 8

ENVIRONMENTAL Phone: (608)221-8817 * Fax: (608)221-2444 * Email: esa@esa-wi.com SYSTEMS ANALYSIS Testing & Balancing * Air & Hydronics * System Analysis

ESA

CERTIFICATION OF REPORT

PROJECT: USFWS

W10040 Cascade Mountain Rd.

Portage, WI 53901

ARCHITECT: --

ENGINEER: --

CONTRACTOR: USFWS

W10040 Cascade Mountain Rd.

Portage, WI 53901

ESA PROJECT NO: 22-144

This is to certify that the attached report is a true and accurate representation of the final operating conditions of the HVAC systems according to current NEBB Procedural Standards (2019 - Ninth Edition) for:

Plans Dated: 10/26/2018 Specification Section: None

CERTIFIED BY:

Environmental Systems Analysis, Inc.

DATE: February 17, 2022

Report prepared by: Shane Otis

USFWS 22-144 Page 2 of 8

ENVIRONMENTAL Phone: (608)221-8817 * Fax: (608)221-2444 * Email: esa@esa-wi.com SYSTEMS ANALYSIS Testing & Balancing * Air & Hydronics * System Analysis

ESA

4/23/2021 Evergreen Telemetry S-PVF-1 1300289 5/19/2021

1900493 5/19/2021

Evergreen Telemetry S-PVF-1 1300288

Pressure Evergreen Telemetry S-DP-250 2000113 11/2/2021 Differential and Evergreen Telemetry S-DP-250 2000104 3/8/2021

4/23/2021 1900181 4/23/2021

Rotation Shimp DT-207L D03A0686 9/7/2021

Temperature/Air Evergreen Telemetry RP-T-1 1900121

1900216 4/23/2021 Evergreen Telemetry S-PVF-1

4/8/2020

Evergreen Telemetry S-PVF-1 1800145 4/8/2021

Evergreen Telemetry S-PVF-1

Evergreen Telemetry S-PVF-1 1700241 5/19/2021

Evergreen Telemetry S-PVF-1 1900210 8/10/2021

Evergreen Telemetry S-PVF-1 1800142

Evergreen Telemetry S-PVF-1 1200216 4/23/2021

Evergreen Telemetry S-PVF-1 1500298 5/19/2021

1800155 4/8/2021 Evergreen Telemetry S-PVF-1 and Direct Hood 4/23/2021

Evergreen Telemetry S-PVF-1 1200214 4/8/2021 Reading Evergreen Telemetry S-PVF-1 1200215

4/23/2021

Evergreen Telemetry S-DP-250 2100211 10/11/2021

Pressure/Velocity Evergreen Telemetry S-PVF-1 1200185

Evergreen Telemetry S-DP-250 2000158 12/30/2021 Evergreen Telemetry S-DP-250 2000177 11/13/2020

Hydronic 2000098 12/6/2021

Humidity Sensor Evergreen Telemetry S-H-3-5" 1700305 4/23/2021

Evergreen Telemetry S-DP-125

9/7/2021Electrical Fluke 39

Evergreen Telemetry S-PVF-1 1700236 5/19/2021

FUNCTION MANUFACTURER / MODEL SERIAL NO.

CALIBRATION

DATE

DM7460027

INSTRUMENT CALIBRATION REPORT

PROJECT USFWS

ESA NO. 22-144

Temp/Immersion Evergreen Telemetry RP-T-2

USFWS 22-144 Page 3 of 8

ENVIRONMENTAL Phone: (608)221-8817 * Fax: (608)221-2444 * Email: esa@esa-wi.com SYSTEMS ANALYSIS Testing & Balancing * Air & Hydronics * System Analysis

ESA

All systems were measured and balanced as per design specifications, unless otherwise noted below.

BALANCE REPORT SUMMARY

PROJECT USFWS

W10040 Cascade Mountain Rd.

Portage, WI 53901

ESA PROJECT NO. 22-144

PREPARED BY Shane Otis

USFWS 22-144 Page 4 of 8

ENVIRONMENTAL Phone: (608)221-8817 * Fax: (608)221-2444 * Email: esa@esa-wi.com SYSTEMS ANALYSIS Testing & Balancing * Air & Hydronics * System Analysis

ESA

DIRECT DRIVE FAN EQUIPMENT TEST REPORT

PROJECT USFWS LOCATION Portage, WI 53901

ESA NO. 22-144

SYSTEM AH-1 EQUIPMENT LOCATION MECHANCICAL ROOM

FAN MANUFACTURER

MODEL OR SERIAL #

YORK

YP9C080C16MP12CB

DESIGN ACTUAL

TOTAL CFM 1400 1490

MIN O.A. CFM 100 110

RETURN CFM 1300 1380

SUCTION PRESSURE FREE

DISCHARGE PRESSURE +.34

TOTAL STATIC PRESSURE NOT LISTED .34

FAN RPM NOT LISTED *

MOTOR MANUFACTURER *

MODEL OR CATALOG # *

DESIGN / RATED ACTUAL

MOTOR H.P. NOT LISTED *

BHP NOT LISTED -

AMPERAGE 13.5 5.4

VOLTAGE * 121

RPM * *

* Due to physical restrictions this data is not obtainable.

REMARKS Fan tested on high speed.

DATE 2/16/2022 TECHNICIAN SMO SYSTEM PAGE 1 OF 2

USFWS 22-144 Page 5 of 8

ENVIRONMENTAL Phone: (608)221-8817 * Fax: (608)221-2444 * Email: esa@esa-wi.com SYSTEMS ANALYSIS Testing & Balancing * Air & Hydronics * System Analysis

ESA

DIFFUSER AND GRILLE TEST REPORT

SYSTEM AH-1 AREA SERVED FIRST FLOOR

Drawing -

Design Final Location No. Size Ak VEL CFM Test 1 Test 2 Test 3 VEL CFM Remarks

ENTRY 1 NOT LISTED 100 110 110

STORAGE 1 NOT LISTED 75 100 80

IT 1 NOT LISTED 100 80 100

CUBICLE AREA 1 NOT LISTED 175 180 180

2 NOT LISTED 175 200 190

3 NOT LISTED 175 160 180

OFFICE 1 1 NOT LISTED 175 200 190

CONFERENCE 1 NOT LISTED 225 250 240

BREAK 1 NOT LISTED 200 210 210

DATE 2/16/2022 TECHNICIAN SMO SYSTEM PAGE 2 OF 2

USFWS 22-144 Page 6 of 8

ENVIRONMENTAL Phone: (608)221-8817 * Fax: (608)221-2444 * Email: esa@esa-wi.com SYSTEMS ANALYSIS Testing & Balancing * Air & Hydronics * System Analysis

ESA

DIRECT DRIVE FAN EQUIPMENT TEST REPORT

PROJECT USFWS LOCATION Portage, WI 53901

ESA NO. 22-144

SYSTEM AH-2 EQUIPMENT LOCATION MECHANCICAL ROOM

FAN MANUFACTURER

MODEL OR SERIAL #

YORK

YP9C080C16MP12CB

DESIGN ACTUAL

TOTAL CFM 1400 1540

MIN O.A. CFM 100 110

RETURN CFM 1300 1430

SUCTION PRESSURE FREE

DISCHARGE PRESSURE +.33

TOTAL STATIC PRESSURE NOT LISTED .33

FAN RPM NOT LISTED *

MOTOR MANUFACTURER *

MODEL OR CATALOG # *

DESIGN / RATED ACTUAL

MOTOR H.P. NOT LISTED *

BHP NOT LISTED -

AMPERAGE 13.5 5.8

VOLTAGE * 121

RPM * *

* Due to physical restrictions this data is not obtainable.

REMARKS Fan tested on high speed.

DATE 2/16/2022 TECHNICIAN SMO SYSTEM PAGE 1 OF 2

USFWS 22-144 Page 7 of 8

ENVIRONMENTAL Phone: (608)221-8817 * Fax: (608)221-2444 * Email: esa@esa-wi.com SYSTEMS ANALYSIS Testing & Balancing * Air & Hydronics * System Analysis

ESA

DIFFUSER AND GRILLE TEST REPORT

SYSTEM AH-2 AREA SERVED FIRST FLOOR

Drawing -

Design Final Location No. Size Ak VEL CFM Test 1 Test 2 Test 3 VEL CFM Remarks

MECH 1 NOT LISTED 100 140 140 *

R.R.2 1 NOT LISTED 75 125 80

HALL 1 NOT LISTED 175 200 180

R.R.2 1 NOT LISTED 75 125 80

OFFICE 3 1 NOT LISTED 175 200 190

JANITOR 1 NOT LISTED 50 80 55

CUBICLE 1 NOT LISTED 250 240 270

2 NOT LISTED 250 250 275

ENTRY 1 NOT LISTED 75 85 80

OFFICE 2 1 NOT LISTED 175 200 190

DATE 2/16/2022 TECHNICIAN SMO SYSTEM PAGE 2 OF 2

* No access to damper and serving mechanical room.

USFWS 22-144 Page 8 of 8