A06-Test_Report_22-02-16_ESA_T_B_report.pdf
PDF 579 KB Posted
- Attached to
- WI LEOPOLD WMD HVAC Federal contract opportunity
- Solicitation number
- 140FC223Q0035
About this file
This report documents testing, balancing, and calibration of HVAC systems at the USFWS facility in Portage, Wisconsin under federal contract number 140FC223Q0035. Systems tested include air handlers AH-1 and AH-2 which serve the first floor, with fan information, diffuser and grille airflows, and instrument calibration data provided. Testing was performed by Environmental Systems Analysis, Inc. in accordance with NEBB standards and procedures to verify HVAC systems met design specifications.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| A06-Crawlspace_piping_to_water_softener_photo.JPG | JPG image | |
| B08-Table_of_Contents.pdf | ||
| Wage_Determination.pdf | ||
| B08-Leopold_Bid_Schedule_-_base_bid1.pdf | ||
| A06-UTILITY_ROOM_RELOCATES_Model_drawing.pdf | ||
| A06-Foundations_Drawing.pdf | ||
| A06-Return_air_box-typical_photo.JPG | JPG image | |
| B08-Pre-Con_Safety_FWS_Form_3-2199_(5-03).pdf | ||
| A06-Furnace_2_photo.JPG | JPG image | |
| B08-Submittals_Report.pdf | ||
| A06-Specifications.pdf | ||
| B08-York_Submittal.pdf | ||
| A06-Drawing_EXISTING-Proposed_HVAC_PAGE.pdf | ||
| A06-Furnance_1_photo.JPG | JPG image | |
| A06-Crawl_space_area_photo_example.JPG | JPG image | |
| Sol_140FC223Q0035.pdf |
Show all 16
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Environmental Systems Analysis, Inc.
4262 Argosy Court * Madison, WI 53714
ENVIRONMENTAL Phone: (608)221-8817 * Fax: (608)221-2444 * Email: esa@esa-wi.com SYSTEMS ANALYSIS Testing & Balancing * Air & Hydronics * System Analysis
ESA
ESA PROJECT NO. 22-144
PREPARED BY : Shane Otis
CONTRACTOR: USFWS
W10040 Cascade Mountain Rd.
Portage, WI 53901
ENGINEER: --
ARCHITECT: --
CERTIFIED TEST, ADJUST, AND
BALANCE REPORT
PROJECT: USFWS
W10040 Cascade Mountain Rd.
Portage, WI 53901
USFWS 22-144 Page 1 of 8
ENVIRONMENTAL Phone: (608)221-8817 * Fax: (608)221-2444 * Email: esa@esa-wi.com SYSTEMS ANALYSIS Testing & Balancing * Air & Hydronics * System Analysis
ESA
CERTIFICATION OF REPORT
PROJECT: USFWS
W10040 Cascade Mountain Rd.
Portage, WI 53901
ARCHITECT: --
ENGINEER: --
CONTRACTOR: USFWS
W10040 Cascade Mountain Rd.
Portage, WI 53901
ESA PROJECT NO: 22-144
This is to certify that the attached report is a true and accurate representation of the final operating conditions of the HVAC systems according to current NEBB Procedural Standards (2019 - Ninth Edition) for:
Plans Dated: 10/26/2018 Specification Section: None
CERTIFIED BY:
Environmental Systems Analysis, Inc.
DATE: February 17, 2022
Report prepared by: Shane Otis
USFWS 22-144 Page 2 of 8
ENVIRONMENTAL Phone: (608)221-8817 * Fax: (608)221-2444 * Email: esa@esa-wi.com SYSTEMS ANALYSIS Testing & Balancing * Air & Hydronics * System Analysis
ESA
4/23/2021 Evergreen Telemetry S-PVF-1 1300289 5/19/2021
1900493 5/19/2021
Evergreen Telemetry S-PVF-1 1300288
Pressure Evergreen Telemetry S-DP-250 2000113 11/2/2021 Differential and Evergreen Telemetry S-DP-250 2000104 3/8/2021
4/23/2021 1900181 4/23/2021
Rotation Shimp DT-207L D03A0686 9/7/2021
Temperature/Air Evergreen Telemetry RP-T-1 1900121
1900216 4/23/2021 Evergreen Telemetry S-PVF-1
4/8/2020
Evergreen Telemetry S-PVF-1 1800145 4/8/2021
Evergreen Telemetry S-PVF-1
Evergreen Telemetry S-PVF-1 1700241 5/19/2021
Evergreen Telemetry S-PVF-1 1900210 8/10/2021
Evergreen Telemetry S-PVF-1 1800142
Evergreen Telemetry S-PVF-1 1200216 4/23/2021
Evergreen Telemetry S-PVF-1 1500298 5/19/2021
1800155 4/8/2021 Evergreen Telemetry S-PVF-1 and Direct Hood 4/23/2021
Evergreen Telemetry S-PVF-1 1200214 4/8/2021 Reading Evergreen Telemetry S-PVF-1 1200215
4/23/2021
Evergreen Telemetry S-DP-250 2100211 10/11/2021
Pressure/Velocity Evergreen Telemetry S-PVF-1 1200185
Evergreen Telemetry S-DP-250 2000158 12/30/2021 Evergreen Telemetry S-DP-250 2000177 11/13/2020
Hydronic 2000098 12/6/2021
Humidity Sensor Evergreen Telemetry S-H-3-5" 1700305 4/23/2021
Evergreen Telemetry S-DP-125
9/7/2021Electrical Fluke 39
Evergreen Telemetry S-PVF-1 1700236 5/19/2021
FUNCTION MANUFACTURER / MODEL SERIAL NO.
CALIBRATION
DATE
DM7460027
INSTRUMENT CALIBRATION REPORT
PROJECT USFWS
ESA NO. 22-144
Temp/Immersion Evergreen Telemetry RP-T-2
USFWS 22-144 Page 3 of 8
ENVIRONMENTAL Phone: (608)221-8817 * Fax: (608)221-2444 * Email: esa@esa-wi.com SYSTEMS ANALYSIS Testing & Balancing * Air & Hydronics * System Analysis
ESA
All systems were measured and balanced as per design specifications, unless otherwise noted below.
BALANCE REPORT SUMMARY
PROJECT USFWS
W10040 Cascade Mountain Rd.
Portage, WI 53901
ESA PROJECT NO. 22-144
PREPARED BY Shane Otis
USFWS 22-144 Page 4 of 8
ENVIRONMENTAL Phone: (608)221-8817 * Fax: (608)221-2444 * Email: esa@esa-wi.com SYSTEMS ANALYSIS Testing & Balancing * Air & Hydronics * System Analysis
ESA
DIRECT DRIVE FAN EQUIPMENT TEST REPORT
PROJECT USFWS LOCATION Portage, WI 53901
ESA NO. 22-144
SYSTEM AH-1 EQUIPMENT LOCATION MECHANCICAL ROOM
FAN MANUFACTURER
MODEL OR SERIAL #
YORK
YP9C080C16MP12CB
DESIGN ACTUAL
TOTAL CFM 1400 1490
MIN O.A. CFM 100 110
RETURN CFM 1300 1380
SUCTION PRESSURE FREE
DISCHARGE PRESSURE +.34
TOTAL STATIC PRESSURE NOT LISTED .34
FAN RPM NOT LISTED *
MOTOR MANUFACTURER *
MODEL OR CATALOG # *
DESIGN / RATED ACTUAL
MOTOR H.P. NOT LISTED *
BHP NOT LISTED -
AMPERAGE 13.5 5.4
VOLTAGE * 121
RPM * *
* Due to physical restrictions this data is not obtainable.
REMARKS Fan tested on high speed.
DATE 2/16/2022 TECHNICIAN SMO SYSTEM PAGE 1 OF 2
USFWS 22-144 Page 5 of 8
ENVIRONMENTAL Phone: (608)221-8817 * Fax: (608)221-2444 * Email: esa@esa-wi.com SYSTEMS ANALYSIS Testing & Balancing * Air & Hydronics * System Analysis
ESA
DIFFUSER AND GRILLE TEST REPORT
SYSTEM AH-1 AREA SERVED FIRST FLOOR
Drawing -
Design Final Location No. Size Ak VEL CFM Test 1 Test 2 Test 3 VEL CFM Remarks
ENTRY 1 NOT LISTED 100 110 110
STORAGE 1 NOT LISTED 75 100 80
IT 1 NOT LISTED 100 80 100
CUBICLE AREA 1 NOT LISTED 175 180 180
2 NOT LISTED 175 200 190
3 NOT LISTED 175 160 180
OFFICE 1 1 NOT LISTED 175 200 190
CONFERENCE 1 NOT LISTED 225 250 240
BREAK 1 NOT LISTED 200 210 210
DATE 2/16/2022 TECHNICIAN SMO SYSTEM PAGE 2 OF 2
USFWS 22-144 Page 6 of 8
ENVIRONMENTAL Phone: (608)221-8817 * Fax: (608)221-2444 * Email: esa@esa-wi.com SYSTEMS ANALYSIS Testing & Balancing * Air & Hydronics * System Analysis
ESA
DIRECT DRIVE FAN EQUIPMENT TEST REPORT
PROJECT USFWS LOCATION Portage, WI 53901
ESA NO. 22-144
SYSTEM AH-2 EQUIPMENT LOCATION MECHANCICAL ROOM
FAN MANUFACTURER
MODEL OR SERIAL #
YORK
YP9C080C16MP12CB
DESIGN ACTUAL
TOTAL CFM 1400 1540
MIN O.A. CFM 100 110
RETURN CFM 1300 1430
SUCTION PRESSURE FREE
DISCHARGE PRESSURE +.33
TOTAL STATIC PRESSURE NOT LISTED .33
FAN RPM NOT LISTED *
MOTOR MANUFACTURER *
MODEL OR CATALOG # *
DESIGN / RATED ACTUAL
MOTOR H.P. NOT LISTED *
BHP NOT LISTED -
AMPERAGE 13.5 5.8
VOLTAGE * 121
RPM * *
* Due to physical restrictions this data is not obtainable.
REMARKS Fan tested on high speed.
DATE 2/16/2022 TECHNICIAN SMO SYSTEM PAGE 1 OF 2
USFWS 22-144 Page 7 of 8
ENVIRONMENTAL Phone: (608)221-8817 * Fax: (608)221-2444 * Email: esa@esa-wi.com SYSTEMS ANALYSIS Testing & Balancing * Air & Hydronics * System Analysis
ESA
DIFFUSER AND GRILLE TEST REPORT
SYSTEM AH-2 AREA SERVED FIRST FLOOR
Drawing -
Design Final Location No. Size Ak VEL CFM Test 1 Test 2 Test 3 VEL CFM Remarks
MECH 1 NOT LISTED 100 140 140 *
R.R.2 1 NOT LISTED 75 125 80
HALL 1 NOT LISTED 175 200 180
R.R.2 1 NOT LISTED 75 125 80
OFFICE 3 1 NOT LISTED 175 200 190
JANITOR 1 NOT LISTED 50 80 55
CUBICLE 1 NOT LISTED 250 240 270
2 NOT LISTED 250 250 275
ENTRY 1 NOT LISTED 75 85 80
OFFICE 2 1 NOT LISTED 175 200 190
DATE 2/16/2022 TECHNICIAN SMO SYSTEM PAGE 2 OF 2
* No access to damper and serving mechanical room.
USFWS 22-144 Page 8 of 8