This solicitation is for vertical construction services for the Moose-Wilson Road Granite Entry Station in Grand Teton National Park. The solicitation seeks a contractor to complete vertical structures, mechanical systems, electrical systems, IT systems, and some additional amenities as part of Phase IB of the project. The construction must meet Accessibility Standards and is estimated to be valued between $500,000 and $1,000,000. Offerors must be registered in SAM and have current online Representations and Certifications. Proposals are due via email by the specified deadline. The procurement is set aside for small businesses with a NAICS code of 236220 and size standard of $45 million. The contract performance period is 10 days after NTP to 150 days after NTP. Pre-proposal questions must be submitted at least 7 days before the proposal deadline.

View the file

Other files for this federal contract opportunity

Show all 13

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

PROJECT LOCATION

OR

OR

Design (Title I)

Prepared in Accordance with Preliminary by Preliminary Design (Title I)

Construction Drawing Not Preceded

Approved by Superintendent on

Variance from Preliminary Design (Title I)

Project Manager

Drawing No.

Date

Date

QUALITY DESIGN CERTIFICATIONSheetMark REVISION Date Initial

STATEREGION COUNTY

LOCATION WITHIN PARK

NAME OF PARK

TITLE OF DRAWING DRAWING NO.

DEPARTMENT OF THE INTERIOR

UNITED STATES

NATIONAL PARK SERVICE

DENVER SERVICE CENTER

PMIS

GOLDEN, CO 80401

ANDERSON HALLAS ARCHITECTS, PC

ARCHITECT

PMIS/PKG NO.

SHEET

OF11

/2

9/

:3 6:

P

M B

IM

-1

G

R T

E E nt ry

S ta tio n/

-1

G

R T

E v

_B

IM

0.

rv t

312456

312456

167343

1 43BASIC DATA: USGS TOPO MAP REVISED & REDRAWN 8/93. UPDATED 11/98. SGS.

INTERMOUNTAIN TETON WY

GRAND TETON NATIONAL PARK

DESIGN COMPONENTS OF MOOSE-WILSON RD

CONSTRUCTION DOCUMENTS

GRAND TETON NATIONAL PARK

GRANITE ENTRY STATION

3D VIEW SHOWN FOR VISUAL REFERENCE ONLY.

REFER TO PLANS AND DETAILS FOR ADDITIONAL

CONSTRUCTION INFORMATION.

N.T.S.

ISOMETRIC VIEW

GENERAL NOTES

1. DO NOT SCALE DRAWINGS

2. ALL WORK TO BE PERFORMED TO APPLICABLE BUILDING CODES (SEE LIST OF APPLICABLE CODES).

3. ALL DIMENSIONS ARE TO FACE OF STRUCTURE UNLESS OTHERWISE NOTED. ALL DIMENSIONS

INDICATING REQUIRED CLEARANCES ARE TO FACE OF FINISH UNLESS OTHERWISE NOTED.

4. THE CONTRACTOR SHALL BE RESPONSIBLE FOR FAMILIARIZING THEMSELVES WITH THE

CONTRACT DOCUMENTS, VERIFYING FIELD CONDITIONS AND DIMENSIONS, AND CONFIRMING THAT

THE WORK MAY BE ACCOMPLISHED AS SHOWN PRIOR TO PROCEEDING WITH CONSTRUCTION.

CONTRACTOR SHALL NOTIFY CO IN WRITING OF ANY DISCREPANCY WITHIN THE CONTRACT

DOCUMENTS AND REQUEST CLARIFICATION PRIOR TO PROCEEDING WITH CONSTRUCTION.

5. SHOULD THERE BE ANY QUESTIONS CONCERNING THE CONTRACT DOCUMENTS, EXISTING

CONDITIONS, AND/OR DESIGN INTENT, THE CONTRACTOR SHALL BE RESPONSIBLE FOR OBTAINING A CLARIFICATION FROM THE CO PRIOR TO PROCEEDING WITH THE WORK, OR RELATED WORK IN

QUESTION.

6. THE CONTRACTOR SHALL BE RESPONSIBLE FOR FAMILIARIZING THEMSELVES WITH THE PROJECT

SCOPE OF WORK, SCHEDULE, AND DEADLINES. THE CONTRACTOR SHALL BE RESPONSIBLE FOR

ADVISING THE CO OF ALL ITEMS REQUIRING A LONG LEAD TIME UPON NOTICE TO PROCEED THAT WILL AFFECT THE SCHEDULE, AND SHALL SUBMIT ORDER CONFIRMATIONS AND DELIVERY DATES

FOR THE ITEMS IN QUESTION TO THE CO

7. INSTALL ALL MANUFACTURED ITEMS, MATERIALS, AND EQUIPMENT IN STRICT ACCORDANCE WITH

THE MANUFACTURER'S RECOMMENDED SPECIFICATIONS, EXCEPT WHERE THE CONTRACT

DOCUMENTS ARE MORE STRINGENT. ANY MISCELLANEOUS ITEMS OR MATERIALS NOT

SPECIFICALLY NOTED, BUT REQUIRED FOR PROPER INSTALLATION SHALL BE FURNISHED AND

INSTALLED BY THE CONTRACTOR. THE CONTRACTOR SHALL FURNISH TO THE CO ALL

WARRANTIES AND GUARANTEES REQUIRED AT THE CONCLUSION OF THE PROJECT.

8. CONTRACTOR SHALL BE RESPONSIBLE FOR ALL HOOK UPS / UTILITY CONNECTIONS, ETC. TO

TEMPORARY TRAILERS.

A4.0

A8.0

ROOM

250 SF

A9.0

A5.0

FIRST FLOOR

100'-0"

5 1 6 75

KEY NOTE WALL TYPE WINDOW

TYPE/

NUMBER

DOOR

NUMBER

ELEVATION

MARK NORTH ARROW

DETAIL

REFERENCE

BUILDING

SECTION

EXTERIOR

ELEVATION

INTERIOR

ELEVATION ROOM TAG

SYMBOLS

BLDG

NORTH

T R U E

OD OUTSIDE DIAMETER

OH OPPOSITE HAND

OPNG OPENING

OPP OPPOSITE

OSB ORIENTED STRAND BOARD

OTS OPEN TO STRUCTURE

PLAM PLASTIC LAMINATE

PLAS PLASTER

PLUMB PLUMBING

PLY PLYWOOD

PT PAINT

PTD PAINTED

QT QUARRY TILE

RAD RADIUS

RB RUBBER BASE

RCP REFLECTED CEILING PLAN

RD ROOF DRAIN

RE REFER TO or REFERENCE

REINF REINFORCED

RELOC RELOCATE(D)

REQ REQUIRED

REV REVISE, REVISED or REVISION

RM ROOM

RO ROUGH OPENING

RS ROUGH SAWN

(S) SEALANT

S SOUTH

SCHED SCHEDULE

SF SQUARE FEET

SHTG SHEATHING

SIM SIMILAR

SOG SLAB ON GRADE

SPEC SPECIFICATION(S)

SQ SQUARE

SS STAINLESS STEEL

STD STANDARD

STL STEEL

STN STAIN

STRUC STRUCTURE or STRUCTURAL

(T) TEMPERED

T&G TONGUE AND GROOVE

T.O. TOP OF

TD THRESHOLD

TYP TYPICAL

UON UNLESS OTHERWISE NOTED

VB VAPOR BARRIER

VCT VINYL COMPOSITION TILE

VERT VERTICAL

VIF VERIFY IN FIELD

VIN VINYL

VTR VENT THROUGH ROOF

W WEST

W/ WITH

W/O WITHOUT

WD WOOD

WIN WINDOW

EXT EXTERIOR

FACP FIRE ALARM CONTROL PANEL

FD FLOOR DRAIN

FE FIRE EXTINGUISHER

FEC FIRE EXTINGUISHER CABINET

FF FINISH FACE

FIN FINISH(ED)

FIXT FIXTURE

FLR FLOOR(ING)

FO FACE OF

FP FIRE PROTECTION

FRP FIBERGLASS REINFORCED

PANEL(ING)

FT FEET

FTG FOOTING

FURR FURRING

GA GAUGE OR GYPSUM

ASSOCIATION

GALV GALVANIZED

GC GENERAL CONTRACTOR

GD GRADE

GL GLASS or GLAZING

GND GROUND

GWB GYPSUM WALLBOARD

HM HOLLOW METAL

HAZMAT HAZARDOUS MATERIAL

HDR HEADER

HDW HARDWARE

HORIZ HORIZONTAL

HT HEIGHT

HVAC HEATING, VENTILATION and AIR

CONDITIONING

IBC INTERNATIONAL BUILDING

CODE

ID INSIDE DIAMETER

INFO INFORMATION

INS INSULATION or INSULATED

INT INTERIOR

JT JOINT

LAV LAVATORY

LIN LINOLEUM

MATL MATERIAL

MAX MAXIMUM

MECH MECHANICAL

MEP MECHANICAL, ELECTRICAL and

PLUMBING

MFG MANUFACTURING

MFR MANUFACTURER

MIN MINIMUM

MISC MISCELLANEOUS

MO MASONRY OPENING

MTD MOUNTED

MTL METAL

<N> NEW

N NORTH

NA NOT APPLICABLE

NIC NOT IN CONTRACT

NO. NUMBER

NOM NOMINAL

NTS NOT TO SCALE

OC ON CENTER

# POUND(S) or NUMBER

& AND

< ANGLE

@ AT

A/V AUDIO VISUAL

ABA ARCHITECTURAL BARRIERS

ACT

ABV ABOVE

ACM ASBESTOS CONTAINING

MATERIAL

ACT ACCOUSTICAL CEILING TILE

ADD ADDENDUM

ADJ ADJACENT or ADJUSTABLE

AFF ABOVE FINISHED FLOOR

AHU AIR HANDLING UNIT

AL ALUMINUM

ALT ALTERNATE

APPROX APPROXIMATE(LY)

ARCH ARCHITECTURAL

ASPH ASPHALT

B.O. BOTTOM OF

BLDG BUILDING

BLKG BLOCKING

BR BACKER ROD

BTWN BETWEEN

C.O. CONTRACTING OFFICER

CAB CABINET

CJ CONTROL JOINT

CL CENTERLINE

CLG CEILING

CLR CLEAR

CMU CONCRETE MASONRY UNIT

COL COLUMN

CONC CONCRETE

CONST CONSTRUCTION

CONT CONTINUOUS

CORR CORRIDOR

CPT CARPET

CT CERAMIC TILE

CTBB CEMENTITIOUS TILE BACKER

BOARD

CTR CENTER

DBL DOUBLE

DEMO DEMOLITION

DET DETAIL

DF DRINKING FOUNTAIN

DIAM DIAMETER

DIM DIMENSION

DN DOWN

DS DOWNSPOUT

<E> EXISTING

E EAST

EA EACH

EG FOR EXAMPLE

ELEC ELECTRICAL

ELEV ELEVATION

EMER EMERGENCY

ENGR ENGINEER

EQ EQUAL

EQP EQUIPMENT

ETR EXISTING TO REMAIN

ABBREVIATIONS

TITLE OF SHEETSUB SHEET NO.DESIGNED:

TECH REVIEW:

DATE:

DRAWING NO.

PMIS/PKG NO.

SHEET

OF11

/2

9/

:3 6:

P

M B

IM

-1

G

R T

E E nt ry

S ta tio n/

-1

G

R T

E v

_B

IM

0.

rv t

G0.1

LB/BS

GRANITE ENTRANCE STATION

GRAND TETON NATIONAL PARK

167343

312456

LB

BS/EH/BS

11/30/2021 2 43

GENERAL

INFORMATION &

INDEX

ARCHITECTURAL

4 A1.0 FLOOR PLAN

5 A2.0 ROOF PLAN

6 A3.0 REFLECTED CEILING PLAN

7 A4.0 EXTERIOR ELEVATIONS

8 A5.0 BUILDING AND WALL SECTIONS

9 A5.1 WALL SECTIONS AND DETAILS

10 A6.0 SCHEDULES

11 A8.0 INTERIOR ELEVATIONS

12 A9.0 WINDOW DETAILS

13 A9.1 DOOR DETAILS

14 A9.2 FENCE DETAILS

15 A9.3 ROOF DETAILS

SHEET

SUB

SHEET SHEET NAME

GENERAL

1 G0.0 COVER SHEET

2 G0.1 GENERAL INFORMATION & INDEX

3 G0.2 CODE STUDY & WALL TYPES

INDEX

STRUCTURAL

16 S1.0 STRUCTURAL GENERAL NOTES

17 S2.0 WALL FRAMING PLAN

18 S2.1 ROOF FRAMING PLAN

19 S3.0 STRUCTURAL DETAILS

20 S3.1 STRUCTURAL DETAILS

MECHANICAL

21 MP0.0 MECHANICAL AND PLUMBING COVER SHEET

22 MP6.0 MECHANICAL AND PLUMBING SCHEDULES

23 M1.0 MECHANICAL DEMO PLAN

24 M1.1 MAIN BUILDING MECHANICAL NEW PLAN

25 M1.2 KIOSK MECHANICAL PLAN

26 M6.0 SEQUENCE OF OPERATIONS

PLUMBING

27 P1.0 PLUMBING PLAN

ELECTRICAL

28 E0.0 ELECTRICAL COVER SHEET

29 E0.1 ELECTRICAL GENERAL NOTES

30 E0.2 ELECTRICAL SITE PLAN

31 E1.0 ELECTRICAL POWER PLAN

32 E2.0 ELECTRICAL LIGHTING PLAN

33 E4.0 ELECTRICAL ONE-LINE DIAGRAM

34 E5.0 ELECTRICAL SCHEDULES

TECHNOLOGY

35 T0.0 TECHNOLOGY COVER SHEET

36 T0.1 TECHNOLOGY GENERAL NOTES

37 T0.2 TECHNOLOGY SITE PLAN

38 T1.0 TECHNOLOGY PLAN

39 T5.0 TECHNOLOGY SCHEDULES

40 T6.0 TECHNOLOGY DETAILS

41 T6.1 TECHNOLOGY DETAILS

42 T6.2 TECHNOLOGY DETAILS

43 T6.3 TECHNOLOGY DETAILS

LEGEND

EGRESS

PATH

DIRECTION OF

EGRESS TRAVEL

FIRE EXTINGUISHER

BRACKET

FEB

REQUIRED ACCESS OR

ACCESSIBILITY CLEARANCES

CODE ANALYSIS

2018 INTERNATIONAL BUILDING CODE WITH APPENDICES

2018 INTERNATIONAL MECHANICAL CODE

2018 INTERNATIONAL PLUMBING CODE

2020 NATIONAL ELECTRICAL CODE

2018 INTERNATIONAL FIRE CODE

INTERNATIONAL MECHANICAL CODE 2018

2018 INTERNATIONAL ENERGY CONSERVATION CODE

ARCHITECTURAL BARRIERS ACT ACCESSIBILITY STANDARDS

NPS SUSTAINABILITY GUIDELINES

BUILDING HEIGHT: 11' (MAX ALLOWABLE 40) PER

TABLE 504.3

NUMBER OF STORIES: 1 (MAX ALLOWABLE 2) PER TABLE

504.4

ALLOWABLE BUILDING AREA: 9,000 SF (TYPE VB, B OCCUPANCY)

PER TABLE 506.2

OCCUPANCY

B BUSINESS

CONSTRUCTION TYPE: VB, NOT SPRINKLED

BUILDING AREA

KIOSK 57 SF

OCCUPANT LOAD

BUSINESS 1 (57 SF/150)

FIRE EXTINGUISHERS REQUIRED PER SECTION 906, AND LOCATED

PER IFC TABLE 906.1

FIRE ALARM SYSTEM IS PROVIDED IN ACCORDANCE WITH 907.2.1

FIRE RATING: TYPE VB

PER TABLE 601 AND 602

IECC CODE ANALYSIS

OPAQUE THERMAL ENVELOPE INSULATION COMPONENT MINIMUM REQUIREMENTS, R-VALUE

METHOD PER TABLE C402.1.3

CLIMATE ZONE: 7

REQUIRED PROVIDED

ATTIC AND OTHER ROOFS R49 R50

WD FRAMED AND OTHER R20 + R3.8 CONTINUOUS R24 + R6 CONTINUOUS

UNHEATED SLAB ON GRADE R15 FOR 24" BELOW GRADE R15 ENTIRE SLAB AND

TO TOP OF FOOTING

BUILDING SEPARATION

TABLE 705.8 FIRE SEPARATION DISTANCE AND MAX AREA OF

EXTERIOR WALL OPENINGS: SEE EGRESS PLAN

ONLY ONE EXIT ACCESS DOOR PER BUILDING IS REQUIRED FOR THE

OCCUPANT LOAD IN ACCORDANCE WITH IBC 1015.1

NOTE: PREFABRICATED SHED IS ACCESSORY TO THE EXISTING

BUILDING (NONOCCUPIED) AND NOT PART OF THE CODE ANALYSIS.

WALL TYPES X

TYPE #

GRAPHIC

REPRESENTATION

1.0

/4

5/8" IMPACT RESISTANT GWB

5 1/2" WD FRAMING WITH 3-1/2" SPRAY

FOAM INSULATION

1" CONTINUOS RIGID INSULATION

7/8" GALV HAT CHANNEL FURRING AT 24"

OC (VERTICAL)

1X CEDAR CHANNEL LAP SIDING - STN

1/2" PLY SHEATHING

WEATHER BARRIER

EXT

INT

1.1

5/8" IMPACT RESISTANT GWB

3-1/2" WD FRAMING WITH FULL-DEPTH

ACOUSTIC BATT INSULATION

/4

COBBLE STONE VENEER, TAPERED FROM

3" AT TOP TO 6-1/2" AT GRADE

1" CONTINUOUS RIGID INSULATION

5/8" IMPACT RESISTANT GWB

5-1/2" WD FRAMING WITH 3-1/2" SPRAY FOAM

INSULATION

INT

EXT

/8

V A

R

IE

S

2.0

1-1/2" FULLY GROUTED CAVITY WITH MASONRY

TIES AT 16" OC ATTACHED THROUGH RIGID

INSULATION TO WD FRAMED WALL

1/2" PLY SHEATHING

WEATHER BARRIER

3/8" DRAINAGE MAT

KIOSK

FEE

COLLECTION

BREAK ROOM

RR

OUTBOUND

CHECK

REMIT

MECH

OFFICE

GENERAL

STORAGE

HALL

BIKE PATH

INBOUND LANE

INBOUND LANE

25% ALLOWABLE OPENINGS (UP,S)

18% ACTUAL

15% ALLOWABLE OPENINGS (UP,NS)

14.8% ACTUAL

IMAGINARY LOT LINE (SEE CODE ANALYSIS G0.1)

FEB

TITLE OF SHEETSUB SHEET NO.DESIGNED:

TECH REVIEW:

DATE:

DRAWING NO.

PMIS/PKG NO.

SHEET

OF11

/2

9/

:3 6:

P

M B

IM

-1

G

R T

E E nt ry

S ta tio n/

-1

G

R T

E v

_B

IM

0.

rv t

G0.2

LB/BS

GRANITE ENTRANCE STATION

GRAND TETON NATIONAL PARK

167343

312456

LB

BS/EH/BS

11/30/2021 3 43

CODE STUDY & WALL

TYPES

G0.2

EGRESS PLAN1

SCALE OF FEET

404 8 16

SCALE A

B L

D G

N O

R T

H

T R U E

SCALE A

<N> EXTERIOR WALL

WALL TYPE TAG,

REF: G0.1

WINDOW TYPE TAG, REF:

WINDOW SCHEDULE

DOOR TAG, REF:

DOOR SCHEDULE

LINE OF ROOF ABOVE

A4.0

A4.0

A5.0

A5.0

A5.0

A5.0

7 7

6 6

A5.0

A5.0

A5.0

A5.0

EQEQ

EQEQ

9' - 11 1/2"

/2 "7

/2

E Q

E Q

KIOSK

A

A

B

B

C

C

D

D

B.5

2.5

FEE

COLLECTION

BREAK ROOM

RR

OUTBOUND

CHECK

A4.0

A4.0

REMIT

MECH

OFFICE

GENERAL

STORAGE

HALL

106 101

116 120

/2

BIKE PATH

INBOUND LANE

INBOUND LANE

A8.0

A8.0

A8.0

A8.0

1.11.1

A9.2

A5.1

7' - 3" 5' - 6" 5' - 6" 5' - 6" 5' - 6"

5' - 6" 5' - 6" 5' - 6" 5' - 6"

1' - 3" 4' - 4 1/2" 2' - 10 1/2"

A9.2

1' - 10"

17' - 9"

A9.2

A5.1

/2

10' - 0" 4' - 0"

/8

2' - 6" 2' - 6"

108E

GENERAL NOTES

1. REFER TO SHEET G0.1 FOR WALL TYPES.

2. REFER TO SHEET A6.0 FOR WINDOW AND DOOR

ELEVATIONS.

3. DIMENSIONS ARE TO FACE OF STRUCTURE UON.

4. DOOR DIMENSIONS ARE TO CENTERLINE.

5. REFER TO STRUCTURAL, MECHANICAL, PLUMBING,

AND ELECTRICAL DRAWINGS FOR MORE

INFORMATION.

TITLE OF SHEETSUB SHEET NO.DESIGNED:

TECH REVIEW:

DATE:

DRAWING NO.

PMIS/PKG NO.

SHEET

OF1/

/2

1:

:5

P

M B

IM

-1

G

R T

E E nt ry

S ta tio n/

-1

G

R T

E v

_B

IM

0.

rv t

A1.0

LB/BS

GRANITE ENTRANCE STATION

GRAND TETON NATIONAL PARK

167343

312456

LB

BS/EH/BS

11/30/2021 4 43

FLOOR PLAN

KEYNOTES - FLOOR PLAN

101 INSTALL 10'X10' PREFABRICATED SHED ON <E> CONC

SLAB ON GRADE BY OTHERS (NIC). ANCHOR TO

FOUNDATION PER MANUFACTURER.

102 CONDENSATE DRAIN AND SPLASH BLOCK: REF. MECH.

103 WD SLAT FENCE WITH PREFINISHED MTL POSTS: REF.

A9.2.

106 OUTDOOR CONDENSING UNIT: REF. MECH.

108 18"X12" MECH CHASE: REF. MECH.

116 PROVIDE 30"X72" MOTORIZED ADJUSTABLE DESK;

BOD: EVODESK LIMITED; TOP: SQUARE RECYCLED

WOOD; BASE: CARBON BLACK

118 CONC LANDING BY OTHERS (NIC).

119 WD SLAT GATE WITH PREFINISHED MTL RAIL

CHANNELS AND HARDWARE, ATTACH TO WD POSTS:

REF. A9.2.

120 QUARTZ SILL WITH 6" SHELF EXTENSION ON HALF OF

WINDOW, REF TO 11/A8.0.

122 SITE IMPROVEMENTS BY OTHERS (NIC).

123 WALL-MOUNTED IT RACK: REF. TECH.

125 <E> ELEC PANEL: REF. ELEC.

126 <N> ELEC PANEL: REF. ELEC.

128 CONDUIT FOR KIOSK TO BE ROUTED TIGHT TO

CORNER: REF. ELEC.

132 LOCATION OF <N> BURIED PROPANE TANK: REF.

MECH.

133 LOCATION OF RELOCATED SECURITY EQUIPMENT:

REF. TECH.

139 PATCH WALL FINISH AS NEEDED AFTER WATER LINE

PROVIDED: REF. PLUMB.

140 PROVIDE BARRIER GATE OPERATOR BEYOND: REF.

1/E0.2.

142 FIRE EXTINGUISHER AND BRACKET.

143 PROVIDE <N> ROLLER SHADE AT <E> WINDOW.

144 PROVIDE <N> ROLLER SHADE AND SOLAR FILM AT <E>

WINDOW.

SCALE OF FEET

SCALE A

A1.0

FLOOR PLAN1

SCALE A

B L

D G

N O

R T

H

T R U

A4.0

A4.0

A5.0

A5.0

A5.0

A5.0

7 7

6 6

A5.0

A5.0

A5.0

A5.0

A B C D

B.5

2.5

A4.0

A4.0

16' - 8"

/2

2' - 6 1/2" 9' - 11 1/2" 4' - 2"

/2

A9.3

A9.3

LEGEND

<N> PREFINISHED

MTL STANDING SEAM

ROOFING

<E> CONC SHINGLE

ROOFING

PREFABRICATED

SHED MTL ROOFING

TITLE OF SHEETSUB SHEET NO.DESIGNED:

TECH REVIEW:

DATE:

DRAWING NO.

PMIS/PKG NO.

SHEET

OF11

/2

9/

:3 5:

P

M B

IM

-1

G

R T

E E nt ry

S ta tio n/

-1

G

R T

E v

_B

IM

0.

rv t

A2.0

LB/BS

GRANITE ENTRANCE STATION

GRAND TETON NATIONAL PARK

167343

312456

LB

BS/EH/BS

11/30/2021 5 43

ROOF PLAN

SCALE OF FEET

SCALE A

A2.0

ROOF PLAN1

SCALE A

B L

D G

N O

R T

H

T R U E

KEYNOTES

101 INSTALL 10'X10' PREFABRICATED SHED ON <E> CONC SLAB

ON GRADE BY OTHERS (NIC). ANCHOR TO FOUNDATION PER

MANUFACTURER.

104 PREFINISHED MTL STANDING SEAM ROOFING.

1. ALL EXPOSED MECHANICAL DUCTWORK SHALL BE PAINTED, TYP.

2. REFER TO STRUCTURAL, MECHANICAL, PLUMBING, AND

ELECTRICAL DRAWINGS FOR MORE INFORMATION.

3. COORDINATE WITH STRUCTURAL, MECHANICAL, PLUMBING, AND

ELECTRICAL DRAWINGS FOR LOCATIONS OF CEILING FIXTURES.

<N> GWB CLNG: REF.

FINISH SCHEDULE

WALL MOUNTED

LUMINAIRE: REF. ELEC

<E> T&G

CLNG

<E> GWB

CLNG

SURFACE MOUNTED

EMERGENCY

LUMINAIRE: REF. ELEC

SUPPLY GRILLE: REF.

MECH

SURFACE MOUNTED

LUMINAIRE: REF. ELEC

<N> SECURITY

CAMERA: REF. TECH

<N> MTL SOFFIT

PANEL

WALL MOUNTED

EMERGENCY

LUMINAIRE: REF. ELEC

7 7

6 6

108' - 0"

KIOSK

A B C D

B.5

2.5

108' - 8"

108' - 8"

2' - 6 1/2" 9' - 11 1/2" 4' - 2"

16' - 8"

/2

/2

EXTENTS OF MTL

FLASHING CLEAT:

REF. A9.3

1' - 11 1/2" 5' - 2 1/2" 2' - 4 1/2"

E Q

E Q

TITLE OF SHEETSUB SHEET NO.DESIGNED:

TECH REVIEW:

DATE:

DRAWING NO.

PMIS/PKG NO.

SHEET

OF11

/2

9/

:3 5:

P

M B

IM

-1

G

R T

E E nt ry

S ta tio n/

-1

G

R T

E v

_B

IM

0.

rv t

A3.0

LB/BS

GRANITE ENTRANCE STATION

GRAND TETON NATIONAL PARK

167343

312456

LB

BS/EH/BS

11/30/2021 6 43

REFLECTED CEILING

PLAN

SCALE OF FEET

SCALE A

SCALE AA3.0

REFLECTED CEILING PLAN1

KEYNOTES

107 WALL-MOUNTED FAN UNIT: REF. MECH.

108 18"X12" MECH CHASE: REF. MECH.

110 WALL MOUNTED COVE HEATER: REF. MECH.

111 CONDENSATE/REFRIGERANT PIPING: REF. MECH.

117 MECH DIFFUSER: REF. MECH.

124 SURFACE MOUNTED EMERGENCY LUMINAIRE: REF. ELEC.

128 CONDUIT FOR KIOSK TO BE ROUTED TIGHT TO CORNER: REF. ELEC.

129 STRUCTURAL 6"X6" WD KNEE BRACE, STN: REF. 4&5/A5.1 & STRUC.

B L

D G

N O

R T

H

T R U

A5.0

A B C DB.5

101129

114114

A5.0

7 6

A5.0

1' - 0" 7' - 7 1/2" 1' - 0"

129129

9' - 7 1/2"

A5.1

EQ EQ

A5.0

BC

4' - 2" 9' - 11 1/2" 2' - 6 1/2"

16' - 8"

GENERAL NOTES

1. REFER TO SHEET G0.1 FOR WALL TYPES.

2. REFER TO SHEET A6.0 FOR WINDOW AND DOOR

ELEVATIONS.

3. REFER TO STRUCTURAL, MECHANICAL,

PLUMBING, AND ELECTRICAL DRAWINGS FOR

MORE INFORMATION.

TITLE OF SHEETSUB SHEET NO.DESIGNED:

TECH REVIEW:

DATE:

DRAWING NO.

PMIS/PKG NO.

SHEET

OF11

/3

0/

0:

:4

A

MB

IM

-1

G

R T

E E nt ry

S ta tio n/

-1

G

R T

E v

_B

IM

0.

rv t

A4.0

LB/BS

GRANITE ENTRANCE STATION

GRAND TETON NATIONAL PARK

167343

312456

LB

BS/EH/BS

11/30/2021 7 43

EXTERIOR

ELEVATIONS

SCALE OF FEET

SCALE A

A4.0

SOUTH ELEVATION6

A4.0

KIOSK WEST ELEVATION1

KEYNOTES

119 WD SLAT GATE WITH PREFINISHED MTL RAIL CHANNELS AND HARDWARE, ATTACH

TO WD POSTS: REF. A9.2.

129 STRUCTURAL 6"X6" WD KNEE BRACE, STN: REF. 4&5/A5.1 & STRUC.

138 PREFINISHED MTL PLATE, TYP: REF. A9.0.

KEYNOTES

101 INSTALL 10'X10' PREFABRICATED SHED ON <E> CONC SLAB ON GRADE BY OTHERS

(NIC). ANCHOR TO FOUNDATION PER MANUFACTURER.

103 WD SLAT FENCE WITH PREFINISHED MTL POSTS: REF. A9.2.

104 PREFINISHED MTL STANDING SEAM ROOFING.

105 PRECAST STONE SILL: REF. 4/A9.0.

109 36"X16" RETURN-AIR LOUVER: REF. MECH.

114 COBBLE STONE VENEER BASE, TAPERED FROM 3" TO 6-1/2" AT BASE: REF. 3/A5.1.

115 WD CHANNEL LAP SIDING - STN.

A4.0

KIOSK EAST ELEVATION2

A4.0

KIOSK NORTH ELEVATION3

SCALE ASCALE ASCALE A

STATION FF

100' - 0"

T.O. EXISTING

FRAMING

108' - 8"

A5.03 5

T.O. STONE

103' - 3 1/2"

/2

A5.0B CB.5

/2

2' - 3 1/2"

STATION FF

100' - 0"

T.O. EXISTING

FRAMING

108' - 8"

A5.0 BC

T.O. STONE

103' - 3 1/2"

A8.0

A5.1

A8.0

2' - 6"

/8

STATION FF

100' - 0"

T.O. EXISTING

FRAMING

108' - 8"

7 6

A5.0

T.O. STONE

103' - 3 1/2"

A5.0

1 2

A9.3

A5.1

GENERAL NOTES

1. REFER TO SHEET G0.1 FOR WALL TYPES.

2. REFER TO SHEET A6.0 FOR WINDOW AND DOOR

ELEVATIONS.

3. DIMENSIONS ARE TO FACE OF STRUCTURE UON.

4. REFER TO STRUCTURAL, MECHANICAL, PLUMBING, AND

ELECTRICAL DRAWINGS FOR MORE INFORMATION.

CONC FOUNDATION

AND FOOTING BY

OTHERS (NIC): REF.

STRUC

CONC SLAB ON

GRADE BY OTHERS

(NIC): REF. STRUC

3-1/2" SPRAY FOAM

INSULATION

MTL CLAD WD

SLIDING SASH

WINDOW

5/8" GWB OVER 2X4

FRAMING

5/8" PLY SHEATHING

OVER 2X8

OVERFRAMING:

REF. STRUC

BASE AS

SCHEDULED: REF.

FINISH SCHEDULE

5/8" IMPACT

RESISTANT GWB

VAPOR RETARDER

BY OTHERS (NIC)

GRADE BY OTHERS

(NIC): REF. CIVIL

CONC CURB BY

OTHERS (NIC): REF.

CIVIL

A9.0

HIGH-HEAT

WATERPROOF

MEMBRANE OVER

ICE AND WATER

SHIELD - ENTIRE

ROOF

WALL MOUNTED

COVE HEATER: REF.

MECH

INSIDE MOUNT

ROLLER SHADES

WITH SOLAR SHADE

FABRIC, TYP ALL

WINDOWS

WEATHER BARRIER

2X TREATED STRUC

FASCIA: REF. STRUC

A9.3

1X CEDAR CHANNEL

SHIPLAP SIDING - STN

1X CEDAR FASCIA

BOARD - STN

7/8" GALV. HAT

CHANNEL FURRING

AT 24" OC (VERTICAL)

1" CONTINUOUS

RIGID INSULATION

5/8" GWB

PREFINISHED

MTL STANDING

SEAM ROOFING

FULL DEPTH SPRAY

FOAM INSULATION

EXPANSION JOINT

BY OTHERS (NIC)

LIQUID APPLIED

DAMPROOFING BY

OTHERS (NIC), TYP

R-15 MIN RIGID

INSULATION FROM

3" BELOW TOP OF

SLAB TO TOP OF

FOOTING BY

OTHERS (NIC)

R-15 MIN RIGID

INSULATION UNDER

ENTIRE SLAB BY

OTHERS (NIC)

1/2" PLY SHEATHING

OVER 2X6 FRAMING:

REF. STRUC

EPOXY BOLT: REF.

STRUC

MTL BASE FLASHING -

VERT LEG TO EXTEND

6" MIN UP WALL

BEHIND WEATHER

BARRIER

TITLE OF SHEETSUB SHEET NO.DESIGNED:

TECH REVIEW:

DATE:

DRAWING NO.

PMIS/PKG NO.

SHEET

OF11

/2

9/

:3 5:

P

M B

IM

-1

G

R T

E E nt ry

S ta tio n/

-1

G

R T

E v

_B

IM

0.

rv t

A5.0

LB/BS

GRANITE ENTRANCE STATION

GRAND TETON NATIONAL PARK

167343

312456

LB

BS/EH/BS

11/30/2021 8 43

BUILDING AND WALL

SECTIONS

SCALE OF FEET

4202 6

SCALE A

A5.0

N/S SECTION AT FEE COLLECTION1

A5.0

E/W SECTION AT FEE COLLECTION2

A5.0

E/W SECTION AT KIOSK3

A5.0

N/S SECTION AT KIOSK4

KEYNOTES

104 PREFINISHED MTL STANDING SEAM ROOFING.

107 WALL-MOUNTED FAN UNIT: REF. MECH.

109 36"X16" RETURN-AIR LOUVER: REF. MECH.

110 WALL MOUNTED COVE HEATER: REF. MECH.

116 PROVIDE 30"X72" MOTORIZED ADJUSTABLE DESK; BOD:

EVODESK LIMITED; TOP: SQUARE RECYCLED WOOD; BASE:

CARBON BLACK

118 CONC LANDING BY OTHERS (NIC).

121 BASEBOARD HEATER: REF. MECH.

126 <N> ELEC PANEL: REF. ELEC.

129 STRUCTURAL 6"X6" WD KNEE BRACE, STN: REF. 4&5/A5.1 &

STRUC.

136 QUARTZ SHELF WITH HEAVY DUTY MTL BRACKETS, LOCATE

BRACKET TO ATTACH TO FRAMING OR PROVIDE BLOCKING

WITHIN WALL: REF. 12/A8.0.

A5.0

WALL SECTION AT KIOSK TRANSACTION WINDOW5

SCALE B

SCALE OF FEET

C

6X6 BEAM AND BRACE - STN,

PROVIDE SEALANT AT ALL JOINTS

AND PENETRATIONS: REF. STRUC

WEATHER BARRIER OVER 1/2"

PLY SHEATHING: REF. STRUC

1X CEDAR CHANNEL SHIPLAP

SIDING - STN

7/8" GALV. HAT CHANNEL

FURRING AT 24" OC (VERTICAL)

1" CONTINUOUS RIGID

INSULATION

5/8" PLY SHEATHING OVER 2X8

LVLS: REF. STRUC WITH FULL

DEPTH SPRAY FOAM INSULATION

HIGH-HEAT WATERPROOF

MEMBRANE OVER ICE AND WATER

SHIELD - ENTIRE ROOF

2X TREATED STRUC FASCIA: REF.

STRUC

1X CEDAR FASCIA BOARD - STN

PREFINISHED MTL STANDING SEAM

ROOFING

2X6 WD TRIM - STN. PROVIDE

SEALANT AT ALL JOINTS AND

PENETRATIONS

PRE-FINISH RAISED MTL SEAM

ROOF RAKE FLASHING

6X6 POST: REF.STRUC

3"

FACE OF STUD

3' - 8 1/2"

2X6 TREATED BLOCKING

EXTEND 2X6 WD TRIM BELOW

KNEE BRACE - STN. PROVIDE

SEALANT AT ALL JOINTS AND

PENETRATIONS

2"

MIN

1/2"

PRE-FINISHED RAISED MTL

FLASHING AND CLEAT, ANCHOR

WITH GALVANIZED FASTENERS

WITH NEOPRENE WASHER

B

COBBLE STONE VENEER,

TAPERED FROM 3" AT TOP TO

6-1/2" AT GRADE

1-1/2" FULLY GROUTED CAVITY

WITH MASONRY TIES AT 16" OC

ATTACHED THROUGH RIGID

INSULATION TO FRAMED WALL

DRAINAGE MAT

1" CONTINUOUS

RIGID INSULATION

5/8" IMPACT

RESISTANT GWB

2X6 WD FRAMING

WITH 3-1/2" SPRAY

FOAM INSULATION

1X CEDAR CHANNEL SHIPLAP

SIDING - STN, SCRIBE SIDING

TO STONES

WEATHER BARRIER

OVER 1/2" PLYWD

SHEATHING

7/8" GALV. HAT CHANNEL

FURRING AT 24" OC (VERTICAL)

BACKER ROD AND SEALANT

6 1/2"

PREFINISHED MTL FLASHING AT

MITERED SIDING CORNER, TYP

MTL DRIP EDGE WITH WEEP HOLES -

VERT LEG OF FLASHING TO EXTEND 6"

MIN UP WALL

1" FACED, CLOSED CELL RIGID

INSULATION, TAPE ALL JOINTS

COBBLE STONE VENEER, TAPERED

FROM 3" AT TOP TO 6.5" AT GRADE

WEATHER BARRIER OVER 1/2" PLYWD

SHEATHING: REF. STRUC

1 1/2" FULLY GROUTED CAVITY WITH

MASONRY TIES AT 16" OC ATTACHED

THROUGH RIGID INSULATION TO

FRAMED WALL

DRAINAGE MAT, EXTEND OVER MTL

FLASHING

GRADE BY OTHERS (NIC): REF. CIVIL

LIQUID APPLIED DAMPROOFING BY

OTHERS (NIC), TYP

REF. 4/A9.0 FOR WINDOW SILL DTL

12" X 18" MECH ACCESS DOOR:

REF. MECH

3 CM THICK QUARTZ SHELF WITH

BEAD EDGE OVER 3/4" PLYWD

1 1/2"

18"X12" MECH CHASE: REF. MECH

INSULATED RECTANGULAR MECH

DUCT: REF. MECH

INSULATED ROUND MECH DUCT:

REF. MECH

CONC SLAB ON GRADE BY OTHERS

(NIC): REF. STRUC

BASE AS SCHEDULED: REF. FINISH

SCHEDULE

5/8" IMPACT RESISTANT GWB, TYP

5/8" IMPACT RESISTANT GWB, TYP

2X WD BLOCKING AS REQUIRED

ACCESS PANEL IN DUCTWORK

WITHIN FOOTPRINT OF CHASE

ACCESS PANEL: REF. MECH

3 3/8" 1' - 6" 5 1/4"

7"

6"X6" BEAM AND BRACE, STN;

PROVIDE SEALANT AT ALL JOINTS

AND PENETRATIONS: REF. STRUC

2X6 WD TRIM, STN; PROVIDE

SEALANT AT ALL JOINTS AND

PENETRATIONS

TITLE OF SHEETSUB SHEET NO.DESIGNED:

TECH REVIEW:

DATE:

DRAWING NO.

PMIS/PKG NO.

SHEET

OF11

/2

9/

:3 5:

P

M B

IM

-1

G

R T

E E nt ry

S ta tio n/

-1

G

R T

E v

_B

IM

0.

rv t

A5.1

LB/BS

GRANITE ENTRANCE STATION

GRAND TETON NATIONAL PARK

167343

312456

LB

BS/EH/BS

11/30/2021 9 43

WALL SECTIONS AND

DETAILS

SCALE A

SCALE OF FEET

1 0 1

SCALE B

A5.1

DTL AT KNEE BRACE5

A5.1

DTL AT STONE BASE CORNER1

A5.1

DTL AT BASE OF STONE VENEER3

SCALE OF INCH

606 3

SCALE A

SCALE B A5.1

DTL AT MECH CHASE2

N.T.S.

ISOMETRIC VIEW - KNEE BRACE

SCALE A

SCALE B

3D VIEW SHOWN FOR VISUAL

REFERENCE ONLY. REFER TO

PLANS AND DETAILS FOR

ADDITIONAL CONSTRUCTION INFO

WINDOW TYPES

TYPE A:

<N> SLIDING SASH

TYPE C:

<N> FIXED

TYPE D:

<N> PREFINISHED MTL

LOUVER: REF. MECH

5' - 0"

3' - 0"

TYPE B:

<N> SLIDING SASH

3' - 6"

5' - 0"

DOOR TYPES

TYPE A

HM DOOR

2" 3' - 0" 2"

3' - 4"

/2

" T

ROOM FINISH LEGEND

CT CERAMIC TILE

GWB GYPSUM WALL BOARD

PT PAINT

STN STAIN

RB RUBBER BASE

SF SHEET FLOORING

T&G WD TONGUE AND GROOVE, STAINED

1. CONTRACTOR TO PROVIDE 3/4" PLYWD PANEL SHUTTER AT WINDOW

TYPE B: REF. WINDOW DETAILS AND ELEVATIONS FOR ATTACHMENTS.

GENERAL NOTES

DOOR SCHEDULE

NUMBER FRAME TYPE

DOOR

TYPE

SIZE DETAILS

COMMENTSTHICKNESS WIDTH HEIGHT HEAD JAMB THRESHOLD

110 INSULATED HM A 1 3/4" 3' - 0" 7' - 0" 2/A9.1 1/A9.1 3/A9.1 TEMPERED GLASS AT GLAZED LIGHT

WINDOW SCHEDULE

NUMBER TYPE WIDTH HEIGHT HEAD DTL JAMB DTL SILL DTL COMMENTS

1 B 3' - 6" 4' - 0" 3/A9.0 2/A9.0 4/A9.0 PROVIDE <N> ROLLER SHADES

2 C 5' - 0" 4' - 0" 3/A9.0 2/A9.0 4/A9.0 PROVIDE <N> ROLLER SHADES

3 A 5' - 0" 4' - 6" 3/A9.0 2/A9.0 1/A9.0 PROVIDE <N> ROLLER SHADES

4 D 3' - 0" 1' - 4" PROVIDE MTL SCREEN AT INT

TITLE OF SHEETSUB SHEET NO.DESIGNED:

TECH REVIEW:

DATE:

DRAWING NO.

PMIS/PKG NO.

SHEET

OF11

/3

0/

0:

:4

A

MB

IM

-1

G

R T

E E nt ry

S ta tio n/

-1

G

R T

E v

_B

IM

0.

rv t

A6.0

LB/BS

GRANITE ENTRANCE STATION

GRAND TETON NATIONAL PARK

167343

312456

LB

BS/EH/BS

11/30/2021 10 43

SCHEDULES

ROOM FINISH SCHEDULE

NUMBER NAME

NEW/

EXISTING

FLOOR

FINISH

CEILING

FINISH

NORTH WALL EAST WALL SOUTH WALL WEST WALL

COMMENTSWALL FINISH BASE WALL FINISH BASE WALL FINISH BASE WALL FINISH BASE

101 OFFICE <E> <E> SF <E> T&G <E> GWB <E> <E> GWB <E> <E> GWB <E> <E> GWB <E>

102 OUTBOUND CHECK <E> <E> SF <E> GWB <E> GWB <E> <E> GWB <E> <E> GWB <E> <E> GWB <E>

103 GENERAL STORAGE <E> <E> SF <E> T&G <E> GWB <E> <E> GWB <E> <E> GWB <E> <E> GWB <E>

104 FEE COLLECTION <E> <E> SF <E> GWB <E> GWB <E> <E> GWB <E> <E> GWB <E> <E> GWB <E>

105 RR <E> <E> CT <E> <E> GWB, CT <E> <E> GWB, CT <E> <E> GWB, CT <E> <E> GWB, CT <E>

106 HALL <E> <E> SF <E> T&G <E> GWB <E> <E> GWB <E> <E> GWB <E> <E> GWB <E>

107 REMIT <E> <E> SF <E> T&G <E> GWB <E> <E> GWB <E> <E> GWB <E> <E> GWB <E>

108 BREAK ROOM <E> <E> SF <E> T&G <E> GWB <E> <E> GWB <E> <E> GWB <E> <E> GWB <E>

109 MECH <E> <E> SF <E> T&G <E> GWB <E> <E> GWB <E> <E> GWB <E> <E> GWB <E>

110 KIOSK <N> SF GWB-PT GWB-PT RB GWB-PT RB GWB-PT RB GWB-PT RB

SCALE OF FEET

2' - 10 3/4"

/2

2' - 3 1/2"

A5.0

8"

9"

A5.0

1' - 4"

1' - 11"

A8.0

2' - 6"2' - 2 1/2"

1' - 1"

A5.0

1' - 0" 1' - 0"

1' - 1 1/2" 4' - 10" 1' - 1 1/2"

A5.0

2' - 3"

1' - 4"

1' - 4"

1' - 8"

1' - 4" 1' - 4"

3' - 3"

9 1/2"

A5.1

LEGEND

<N> GWB - PT

<E> GWB

<E> CMU WITH

GWB FINISH

3 CM THICK

QUARTZ SHELF

WITH BEAD EDGE

MOTORIZED

ADJUSTABLE

WORK SURFACE

10 1/4"

7 1/2"

HEAVY DUTY MTL

SHELF BRACKETS

WITH VERTICAL

MOUNTING

FLANGE, LOCATE

TO ATTACH TO

FRAMING

3 CM THICK QUARTZ 6"

SHELF SILL EXTENSION

WITH BEAD EDGE ON

FIXED HALF OF CASEMENT

WINDOW, CONTINUOUS

WITH WINDOW SILL.

SUPPORT WITH HEAVY

DUTY SIDEWALL

COUNTERTOP SUPPORT

BRACKET

6"

3 CM THICK QUARTZ

WINDOW SILL, FLUSH WITH

WALL ON OPERABLE HALF

OF CASEMENT WINDOW

(CONTINUOUS WITH SHELF

EXTENSION BELOW)

TITLE OF SHEETSUB SHEET NO.DESIGNED:

TECH REVIEW:

DATE:

DRAWING NO.

PMIS/PKG NO.

SHEET

OF11

/2

9/

:3 5:

P

M B

IM

-1

G

R T

E E nt ry

S ta tio n/

-1

G

R T

E v

_B

IM

0.

rv t

A8.0

LB/BS

GRANITE ENTRANCE STATION

GRAND TETON NATIONAL PARK

167343

312456

LB

BS/EH/BS

11/30/2021 11 43

INTERIOR

ELEVATIONS

SCALE OF FEET

4202 6

SCALE A

A8.0

MECH 109 EAST10

A8.0

MECH 109 SOUTH9

A8.0

REMIT 107 SOUTH8

A8.0

REMIT 107 WEST7

A8.0

FEE 104 WEST6

A8.0

FEE 104 NORTH5

A8.0

KIOSK 110 EAST4

A8.0

KIOSK 110 SOUTH3

A8.0

KIOSK 110 WEST2

A8.0

KIOSK 110 NORTH1

KEYNOTES

131 INSIDE MOUNT ROLLER SHADES WITH SOLAR

SHADE FABRIC.

134 QUARTZ COUNTERTOP: REF. 2/A5.1.

135 12" X 18" MECH ACCESS DOOR: REF. MECH.

136 QUARTZ SHELF WITH HEAVY DUTY MTL

BRACKETS, LOCATE BRACKET TO ATTACH TO

FRAMING OR PROVIDE BLOCKING WITHIN WALL:

REF. 12/A8.0.

141 14" DEEP HEAVY DUTY ADJUSTABLE SHELVING,

LOCATE BRACKET TO ATTACH TO FRAMING OR

PROVIDE BLOCKING WITHIN WALL.

142 FIRE EXTINGUISHER AND BRACKET.

KEYNOTES

107 WALL-MOUNTED FAN UNIT: REF. MECH.

110 WALL MOUNTED COVE HEATER: REF. MECH.

111 CONDENSATE/REFRIGERANT PIPING: REF. MECH.

116 PROVIDE 30"X72" MOTORIZED ADJUSTABLE DESK;

BOD: EVODESK LIMITED; TOP: SQUARE

RECYCLED WOOD; BASE: CARBON BLACK

120 QUARTZ SILL WITH 6" SHELF EXTENSION ON HALF

OF WINDOW, REF TO 11/A8.0.

121 BASEBOARD HEATER: REF. MECH.

123 WALL-MOUNTED IT RACK: REF. TECH.

126 <N> ELEC PANEL: REF. ELEC.

127 BASE AS SCHEDULED: REF. A6.0 FINISH

SCHEDULE.

128 CONDUIT FOR KIOSK TO BE ROUTED TIGHT TO

CORNER: REF. ELEC.

130 12" DEEP HEAVY DUTY ADJUSTABLE SHELVING,

LOCATE BRACKET TO ATTACH TO FRAMING OR

PROVIDE BLOCKING WITHIN WALL.

SCALE A SCALE A SCALE A SCALE A SCALE A SCALE A

SCALE B SCALE B SCALE B SCALE B

SCALE OF FEET

SCALE B

A8.0

DTL AT KIOSK WORKSTATION12

SCALE OF FEET

1 0 1

SCALE C

SCALE C A8.0

DTL AT TRANSACTION SILL11

SCALE C

1/2" AL REVEAL TRIM

5/8" IMPACT RESISTANT GWB

2X6 WD FRAMING WITH 3-1/2" SPRAY

FOAM INSULATION

1" CONTINUOUS RIGID INSULATION

3 CM SOLID SURFACE COUNTERTOP

WITH EASED EDGE

MTL CLAD WD SLIDING SASH WINDOW

PROVIDE 3/8" MIN BACKER ROD AND

SEALANT, TYP EA SIDE AND PROVIDE

TREATED WD SHIM

WALL JAMB BEYOND

PROVIDE 3/8" MIN BACKER ROD AND

SEALANT

SELF-ADHESIVE WEATHER MEMBRANE -

INSTALL FROM UNDER WINDOW SHIM TO

EXTEND 6" MIN DOWN (OVER SHEATHING)

1 3/4"

2X TREATED WD BUCK

EXTERIOR INTERIOR

GRID LINE

SELF-ADHESIVE WEATHER MEMBRANE -

WRAP AROUND INSIDE OF RO AND

EXTEND 6" MIN OF FACE OF SHEATHING

1X CEDAR CHANNEL SHIPLAP SIDING - STN

WEATHER BARRIER OVER PLYWD

SHEATHING EXTEND OVER BLOCKING

AND UNDER FLASHING

FLASHING TAPE

7/8" GALV. HAT CHANNEL FURRING AT 24"

OC (VERTICAL)

PROVIDE PRE-FINISHED MTL FLASHING - SET

IN BED OF SEALANT, SLOPE TO DRAIN

PROVIDE PRE-FINISHED MTL J-TYPE

FLASHING CLEAT - ANCHOR WITH SS LOW

PROFILE FASTENERS WITH NEOPRENE

WASHERS

PROVIDE 2X TREATED BLOCKING, SHIM AT

TOP TO PROVIDE SLOPE

PROVIDE 3/8" MIN BACKER ROD AND

SEALANT, TYP EA SIDE OF STOREFRONT

SYSTEM, PROVIDE TREATED WD SHIM

PROVIDE PRE-FINISHED MTL FLASHING -

SET IN BED OF SEALANT - ANCHOR WITH

SS LOW PROFILE FASTENERS WITH

NEOPRENE WASHER

1" CONTINUOUS RIGID INSULATION

WINDOW SILL BELOW

EXTERIOR

INTERIOR

SELF-ADHESIVE WEATHER MEMBRANE -

WRAP AROUND INSIDE OF RO AND EXTEND

6" MIN OF FACE OF SHEATHING

5/8" IMPACT RESISTANT GWB

2X6 WD FRAMING WITH 3-1/2" SPRAY FOAM

INSULATION

1X CEDAR CHANNEL SHIPLAP SIDING - STN

WEATHER BARRIER OVER PLYWD

SHEATHING EXTEND OVER BLOCKING

AND UNDER FLASHING

MTL CLAD WD WINDOW: REF. A6.0

WINDOW SCHEDULE FOR TYPE

GRID LINE

PROVIDE TREATED BLOCKING

FLASHING TAPE

7/8" GALV HAT CHANNEL FURRING AT 24"

OC (VERTICAL)

1/2" AL REVEAL TRIM

1X WD TRIM RETURN

SELF-ADHESIVE WEATHER MEMBRANE -

OVER WINDOW MOUNTING FLANGE TO

EXTEND 4" PAST FLANGE

NOTE: CONTRACTOR TO PROVIDE 3/4"

PLYWD PANEL SHUTTER AND MTL

PLATE ANCHORS AS INDICATED ON

ELEVATIONS AT WINDOW TYPE B.

AT WINDOW TYPE B: (2) PREFINISHED

MTL PLATES - ANCHOR WITH THREADED

ROD AND HEAVY DUTY CONC

ADHESIVE - PROVIDE NEOPRENE AND

GALVANIZED STL WASHER - PROVIDE

HOLE IN PLATES FOR WINTERIZATION

PANEL SECURING BOLT

PROVIDE 3/8" MIN BACKER ROD AND

SEALANT, AT WOOD / MTL CLAD WINDOW

SYSTEM, PROVIDE TREATED WD SHIM

1" CONTINUOUS RIGID INSULATION

WALL JAMB BEYOND

GRID LINE

EXTERIOR INTERIOR

SELF-ADHESIVE WEATHER MEMBRANE -

WRAP AROUND INSIDE OF RO AND

EXTEND 6" MIN ON FACE OF SHEATHING

BACKER ROD AND SEALANT

WEATHER BARRIER OVER PLYWD

SHEATHING EXTEND OVER BLOCKING

AND UNDER FLASHING

5/8" IMPACT RESISTANT GWB

2X6 WD FRAMING WITH 3-1/2" SPRAY

FOAM INSULATION

7/8" GALV HAT CHANNEL FURRING AT

24" OC (VERTICAL)

MTL CLAD WD WINDOW: REF. A6.0

WINDOW SCHEDULE FOR TYPE

PROVIDE PRE-FINISHED MTL

FLASHING WITH DRIP EDGE, SET IN

BED OF SEALANT, ANCHOR WITH SS

LOW PROFILE FASTENERS WITH

NEOPRENE WASHER

FLASHING TAPE

PROVIDE 2X TREATED BLOCKING, SHIM

AT TOP TO PROVIDE SLOPE

1X CEDAR CHANNEL SHIPLAP SIDING -

STN

PROVIDE 1X TREATED BLOCKING,

SHIM AT TOP TO PROVIDE SLOPE

SEALANT

SELF-ADHESIVE WEATHER MEMBRANE

OVER WINDOW MOUNTING FLANGE TO

EXTEND 4" PAST FLANGE

1X WD TRIM RETURN

1/2" AL REVEAL TRIM

/2

/2

VENT STRIP

1/2" AL REVEAL TRIM

5/8" IMPACT RESISTANT GWB

2X6 WD FRAMING WITH 3-1/2" SPRAY

FOAM INSULATION

1" FACED, CLOSED CELL RIGID

INSULATION, TAPE ALL JOINTS

COBBLE STONE VENEER, TAPERED

FROM 3" AT TOP TO 6.5" AT GRADE

3 CM SOLID SURFACE COUNTERTOP

WITH EASED EDGE

MTL CLAD WD WINDOW: REF. A6.0

WINDOW SCHEDULE FOR TYPE

PRECAST STONE SILL WITH KERF DRIP

EDGE

PROVIDE 3/8" MIN BACKER ROD AND

SEALANT, TYP EA SIDE AND PROVIDE

TREATED WD SHIM

WALL JAMB BEYOND

PROVIDE 3/8" MIN BACKER ROD AND

SEALANT

SELF-ADHESIVE WEATHER MEMBRANE -

INSTALL FROM UNDER WINDOW SHIM

TO EXTEND 6" MIN DOWN (OVER

SHEATHING)

SLOPE

PREFINISHED MTL FLASHING WITH DRIP

EDGE EXTEND UNDER SELF-ADHESIVE

MEMBRANE TO BTTM OF WINDOW

2X TREATED WD BUCK

EXTERIOR INTERIOR

GRID LINE

1 1/2" FULLY GROUTED CAVITY WITH

MASONRY TIES AT 16" OC ATTACHED

THROUGH RIGID INSULATION TO

FRAMED WALL

DRAINAGE MAT

MIN

1"

3"

6"

WEATHER BARRIER OVER PLYWD

SHEATHING

TITLE OF SHEETSUB SHEET NO.DESIGNED:

TECH REVIEW:

DATE:

DRAWING NO.

PMIS/PKG NO.

SHEET

OF11

/3

0/

0:

:4

A

MB

IM

-1

G

R T

E E nt ry

S ta tio n/

-1

G

R T

E v

_B

IM

0.

rv t

A9.0

LB/BS

GRANITE ENTRANCE STATION

GRAND TETON NATIONAL PARK

167343

312456

LB

BS/EH/BS

11/30/2021 12 43

WINDOW DETAILS

SCALE OF INCH

606 3

SCALE A

A9.0

DTL AT TRANSACTION WINDOW SILL1

A9.0

DTL AT TYPICAL WINDOW JAMB2

A9.0

DTL AT TYPICAL WINDOW HEAD3

A9.0

DTL AT WINDOW SILL AT STONE4

HM FRAME - PT

EXTERIOR

INTERIOR

2X TREATED BUCK AROUND DR OPENING

TREATED WD SHIM

WEATHER BARRIER, EXTEND OVER

BLOCKING AND UNDER FLASHING

PROVIDE PRE-FINISHED MTL FLASHING CAP

HM INSULATED DR PANEL

PROVIDE 3/8" MIN. BACKER ROD AND

SEALANT - FILL ANY VOID WITH SEALANT

PROVIDE GALVANIZED CLEAT - ANCHOR

WITH STAINLESS STL FASTENERS WITH

NEOPRENE WASHER - CLEAT TO EXTEND

BEYOND HM FRAME

PROVIDE 2X TREATED BLOCKING

SELF-ADHESIVE WEATHER MEMBRANE -

WRAP AROUND INSIDE OF RO AND

EXTEND 6" MIN ON FACE OF SHEATHING

1" CONTINUOUS RIGID INSULATION

GRID LINE

1X CEDAR CHANNEL SHIPLAP SIDING -

STN

7/8" GALV HAT CHANNEL FURRING AT

24" OC (VERTICAL)

2X6 WD FRAMING WITH 3-1/2" SPRAY

FOAM INSULATION

5/8" IMPACT RESISTANT GWB

1/2" PLYWD SHEATHING: REF. STRUC

1" CONTINUOUS RIGID INSULATION

GRID LINE

2X6 WD FRAMING WITH 3-1/2"

SPRAY FOAM INSULATION

EXTERIORINTERIOR

1X CEDAR CHANNEL SHIPLAP SIDING - STN

7/8" GALV. HAT CHANNEL FURRING AT 24"

OC (VERTICAL)

HM INSULATED DR PANEL

PROVIDE 3/8" MIN. BACKER ROD AND

SEALANT - FILL ANY VOID WITH SEALANT

HM DOOR FRAME - PT

TREATED WD SHIM

SELF-ADHESIVE WEATHER

MEMBRANE - WRAP AROUND INSIDE

OF RO AND EXTEND 6" MIN ON FACE

OF SHEATHING

WEATHER BARRIER, EXTEND OVER

BLOCKING AND UNDER FLASHING

PROVIDE 1X TREATED BLOCKING - SHIM AT

TOP TO PROVIDE SLOPE

FLASHING TAPE

5/8" IMPACT RESISTANT GWB

PLYWD SHEATHING: REF/ STRUC

/2

VENT STRIP

PROVIDE GALVANIZED CLEAT, ANCHOR WITH

STAINLESS STL FASTENERS WITH NEOPRENE

WASHER, CLEAT TO EXTEND BEYOND HM

FRAME

PROVIDE PRE-FINISHED MTL FLASHING CAP

WITH DRIP EDGE, ANCHOR WITH SS

FASTENERS WITH NEOPRENE WASHER

PROVIDE 2X TREATED BLOCKING,

SHIM AT TOP TO PROVIDE SLOPE

HM DR FRAME BEYOND

HM INSULATED DR PANEL

AL THERMALLY-BROKEN THRESHOLD,

EXTEND ACROSS ISOLATION JOINT AT

INTERIOR SET IN SEALANT

CONC SLAB ON GRADE BY OTHERS (NIC)FLOOR FINISH AS

SCHEDULED: REF. A6.0

CONC FOUNDATION AND FOOTING: BY

OTHERS (NIC): REF. STRUC

VAPOR RETARDER AND RIGID

INSULATION BY OTHERS (NIC)

CONC SLAB ON GRADE BY

OTHERS (NIC)

EXTERIORINTERIOR

R-15 MIN RIGID INSULATION

FROM 3" BELOW TOP OF SLAB

BY OTHERS (NIC)

M A

X /2

TITLE OF SHEETSUB SHEET NO.DESIGNED:

TECH REVIEW:

DATE:

DRAWING NO.

PMIS/PKG NO.

SHEET

OF11

/2

9/

:3 5:

P

M B

IM

-1

G

R T

E E nt ry

S ta tio n/

-1

G

R T

E v

_B

IM

0.

rv t

A9.1

LB/BS

GRANITE ENTRANCE STATION

GRAND TETON NATIONAL PARK

167343

312456

LB

BS/EH/BS

11/30/2021 13 43

DOOR DETAILS

A9.1

DTL AT DOOR JAMB IN EXT STUD WALL1

A9.1

DTL AT DOOR HEAD IN EXT STUD WALL2

SCALE OF INCH

606 3

SCALE A

A9.1

DTL AT DOOR THRESHOLD3

2X4 CEDAR SLATS

BOLTED TO STL

ANGLES, TYP

HSS 4X4X1/4 POST,

PROVIDE POWDER

COAT FINISH

4X4X3/8 STL ANGLE

BOLTED TO STL

TUBE, PROVIDE

POWDER COAT

FINISH

1" 1"

EQ EQ

10X10X5/8 STL

PLATE, PROVIDE

POWDER COAT

FINISH

5/8"X13" DIAM SS

EPOXY BOLTS

WITH WASHER

CLEAR

3' - 4"

A9.2

A9.2

A9.2

7 11

A9.2

7' - 3" 5' - 6"

CONC SIDEWALK BY OTHERS

(NIC)

HSS 4X4X1/4 POST

BEYOND, ANGLE TOP OF

POST TO PROVIDE SLOPE

AND CAP WITH WELDED

1/4" STL PLATE, PROVIDE

POWDER COAT FINISH

18" DIAM CONC FOOTING

TO 36" MIN DEPTH BY

OTHERS (NIC), TYP

4X4X3/8 STL ANGLE

BOLTED TO STL TUBE,

PROVIDE POWDER COAT

FINISH

10X10X5/8 STL PLATE,

PROVIDE POWDER COAT

FINISH

4X2X1/4 STL TUBE FRAME,

PROVIDE POWDER COAT

FINISH

2X4 CEDAR SLATS BOLTED TO

STL FRAME, POWDER COAT

FINISH, 1" GAP IN BETWEEN

MEMBERS, TYP

(4) BARREL HINGES PER

GATE, TYP

/2

/2

/8

LOCKING MECHANISM GATE

INTO CONC SLAB

A9.2

2X2X1/4 STL ANGLE WELDED

TO BOTTOM STL TUBE,

PROVIDE POWDER COAT

FINISH

MECH DUCT BY OTHERS (NIC)

1/4" STL PLATE WELDED TO

TUBE STL FRAME - BOTH

SIDES, FOR MOUNTING

OPERABLE GATE LATCHING

HARDWARE (OPERABLE PARTS

AT 34" MIN - 48" MAX AFF): REF.

SPECIFICATIONS

2X2X1/4 STL ANGLE GATE

STOP ATTACHED TO TUBE

STL, PROVIDE POWDER

COAT FINISH

A9.2

A9.2

CLEAR

6' - 0"

A9.2

A9.2

A9.2

2X4 CEDAR SLATS

BOLTED TO STL

ANGLES, TYP

HSS 4X4X1/4 POST,

PROVIDE POWDER

COAT FINISH

4X4X3/8 STL ANGLE

BOLTED TO STL

TUBE, PROVIDE

POWDER COAT

FINISH10X10X5/8 STL

PLATE, PROVIDE

POWDER COAT

FINISH

4X2X1/4 STL TUBE

FRAME, PROVIDE

POWDER COAT

FINISH

(4) BARREL HINGES

PER GATE, TYP

HOLD

2"

HSS 4X4X1/4 POST,

PROVIDE POWDER

COAT FINISH

4X4X3/8 STL ANGLE

BOLTED TO STL

TUBE, PROVIDE

POWDER COAT

FINISH

10X10X5/8 STL

PLATE, PROVIDE

POWDER COAT

FINISH

4X2X1/4 STL TUBE

FRAME, PROVIDE

POWDER COAT

FINISH

2X2X1/4 STL ANGLE

GATE STOP

ATTACHED TO

TUBE STL,

PROVIDE POWDER

COAT FINISH

1"

5/8"X13" DIAM SS

EPOXY BOLTS

WITH WASHER

CONC SIDEWALK BY

OTHERS (NIC)

2X4 CEDAR SLATS BOLTED TO STL

ANGLES, 1" GAP IN BETWEEN

MEMBERS, TYP

HSS 4X4X1/4 POST BEYOND,

ANGLE TOP OF POST TO PROVIDE

SLOPE AND CAP WITH WELDED

1/4" STL PLATE, PROVIDE POWDER

COAT FINISH

18" DIAM CONC FOOTING TO

36" MIN DEPTH BY OTHERS

(NIC), TYP

4X4X3/8 STL ANGLE BOLTED TO

STL TUBE, PROVIDE POWDER

COAT FINISH

10X10X5/8 STL PLATE, PROVIDE

POWDER COAT FINISH

(4) BARREL HINGES PER GATE,

TYP

MECH DUCT BY OTHERS

(NIC)

4X2X1/4 STL TUBE FRAME,

PROVIDE POWDER COAT FINISH

OPERABLE GATE LATCHING

HARDWARE (OPERABLE

PARTS AT 34" MIN - 48" MAX

AFF)

2X2X1/4 STL ANGLE WELDED

TO BOTTOM STL TUBE,

PROVIDE POWDER COAT

FINISH

2X2X1/4 STL ANGLE GATE

STOP ATTACHED TO TUBE

STL, PROVIDE POWDER

COAT FINISH

2' - 10 1/2" 4' - 4 1/2" 1' - 3"

CONC FOOTING TO 36" MIN DEPTH

BY OTHERS (NIC), TYP

/2

/2

/8

A9.2

/2

/2

4X2X1/4 STL TUBE FRAME, PROVIDE POWDER

COAT FINISH

2X4 CEDAR SLATS BOLTED TO STL FRAME,

POWDER COAT FINISH, 1" GAP IN BETWEEN

MEMBERS, TYP

HSS 4X4X1/4 POST BEYOND, ANGLE TOP OF

POST TO PROVIDE SLOPE AND CAP WITH

WELDED 1/4" STL PLATE, PROVIDE POWDER

COAT FINISH

2X2X1/4 STL ANGLE WELDED TO BOTTOM STL

TUBE, PROVIDE POWDER COAT FINISH

4X2X1/4 STL TUBE FRAME, PROVIDE POWDER

COAT FINISH

1/4" STL PLATE WELDED TO TUBE STL FRAME -

BOTH SIDES

OPERABLE GATE LATCHING HARDWARE

(OPERABLE PARTS AT 34" MIN - 48" MAX AFF):

REF. SPECIFICATIONS

/8

10X10X5/8 STL PLATE BEYOND

3/4" GROUT PAD BEYOND

A9.2

4X2X1/4 STL TUBE

FRAME, PROVIDE

POWDER COAT

FINISH

2X2X1/4 STL ANGLE

GATE STOP

ATTACHED TO

TUBE STL,

PROVIDE POWDER

COAT FINISH

2X4 CEDAR SLATS

BOLTED TO STL

ANGLES, TYP

4"

1"

HSS 4X4X1/4

POST, PROVIDE

POWDER COAT

FINISH

10X10X5/8 STL PLATE,

PROVIDE POWDER

COAT FINISH

3/4" GROUT PAD

5/8"X13" DIAM SS

EPOXY BOLTS

WITH WASHER 18" DIAM CONC

FOOTING TO 36" MIN

DEPTH BY OTHERS

(NIC), TYP

HSS 4X4X1/4

POST, PROVIDE

POWDER COAT

FINISH

10X10X5/8 STL

PLATE, PROVIDE

POWDER COAT

FINISH

3/4" GROUT PAD

5/8"X13" DIAM SS

EPOXY BOLTS

WITH WASHER

18" DIAM CONC

FOOTING TO 36" MIN

DEPTH BY OTHERS

(NIC), TYP

CONC SLAB BY

OTHERS, TYP

TITLE OF SHEETSUB SHEET NO.DESIGNED:

TECH REVIEW:

DATE:

DRAWING NO.

PMIS/PKG NO.

SHEET

OF11

/2

9/

:3 5:

P

M B

IM

-1

G

R T

E E nt ry

S ta tio n/

-1

G

R T

E v

_B

IM

0.

rv t

A9.2

LB/BS

GRANITE ENTRANCE STATION

GRAND TETON NATIONAL PARK

167343

312456

LB

BS/EH/BS

11/30/2021 14 43

FENCE DETAILS

SCALE OF FEET

SCALE A

A9.2

DTL AT TYP FENCE POST3

A9.2

GATE PLAN - SOUTH9

A9.2

NORTH GATE AND FENCE ELEVATION10

SCALE OF FEET

1 0 1

SCALE B

SCALE B

SCALE B

SCALE A

A9.2

GATE PLAN - NORTH8

A9.2

DTL AT TYP GATE HINGE4

A9.2

DTL AT SOUTH GATE LATCH5

A9.2

SOUTH GATE AND FENCE ELEVATION7

A9.2

SECTION THROUGH TYP GATE1

SCALE B

SCALE B

SCALE A

SCALE A SCALE A

A9.2

DTL AT NORTH GATE LATCH6

SCALE B

A9.2

FENCE POST BASE DTL AT ISOLATED FOOTING2

SCALE B

A9.2

FENCE POST BASE DTL AT SLAB FOOTING11

SCALE B

PRE-FINISH RAISED MTL SEAM

ROOF RAKE FLASHING

PRE-FINISHED MTL RAKE Z

CLOSURE

5/8" TREATED PLYWD

SHEATHING

PRE-FINISHED RAISED MTL

FLASHING AND CLEAT, ANCHOR

WITH GALVANIZED FASTENERS

WITH NEOPRENE WASHER

PRE-FINISHED J-CHANNEL CLIP,

ANCHOR WITH GALVANIZED

FASTENERS WITH NEOPRENE

WASHER

2X TREATED STRUC FASCIA:

REF. STRUC

1X CEDAR FASCIA BOARD -

STN

ROOF MEMBRANE SPLICE

TAPE PREFINISHED MTL STANDING

SEAM ROOFING

HIGH-HEAT WATERPROOF

MEMBRANE, FROM BEHIND MTL

CLEAT

INSTALL LAYER ICE AND WATER

SHIELD ENTIRE ROOF; WRAP

UNDER CLEAT AND BEHIND

FASCIA BOARD AND OVER

BOTTOM FLASHING

5/8" PLYWD SHEATHING OVER 2X

OVERFRAMING: REF. STRUC

7/8" GALV. HAT CHANNEL

FURRING AT 24" OC (VERTICAL)

1X CEDAR CHANNEL LAP

SIDING - STN

R E

V E

A L

5/8" PLYWD SHEATHING OVER

2X8 LVL FRAMING WITH FULL

DEPTH SPRAY FOAM

INSULATION: REF. STRUC

FACE OF STUD

6 1/2"

/2

/2

1" CONTINUOUS RIGID

INSUALTION

WEATHER BARRIER, CONTINUE

OVER PLYWOOD SHEATHING

AND UNDER OVERFRAMING

FULL-DEPTH SPRAY FOAM

INSULATION

PRE-FINISHED MTL Z CLOSURE

CUT TO FIT, SET IN BUTYL TAPE

SEALANT AND FILL ANY VOIDS

WITH SEALANT

5/8" PLYWD OVER 2X WD

FRAMING: REF. STRUC

PREFINISHED MTL RIDGE

CAP

PREFINISHED MTL

STANDING SEAM ROOFING

HIGH-HEAT WATERPROOF

MEMBRANE

INSTALL LAYER ICE AND

WATER SHIELD ENTIRE ROOF

(2) 2X LVL RIDGE FRAMING: REF.

STRUC

MIN

2"

FASTENERS 16" OC WITH

BUTYL TAPE SEALANT

CAULK BETWEEN WEBS

7/8" GALV. HAT CHANNEL

FURRING AT 24" OC (VERTICAL)

1X CEDAR CHANNEL LAP SIDING -

STN

HIGH-HEAT WATERPROOF

MEMBRANE, FROM BEHIND

MTL CLEAT

PRE-FINISHED MTL SEAM ROOF

EVE CLOSURE FLASHING

PREFINISHED MTL STANDING

SEAM ROOFING

INSTALL LAYER ICE AND

WATER SHIELD ENTIRE ROOF;

WRAP UNDER CLEAT AND

BEHIND FASCIA BOARD AND

OVER BOTTOM FLASHING

ROOF MEMBRANE SPLICE TAPE

(1) LAYER SELF-ADHESIVE ROOF

MEMBRANE (OVER MTL

FLASHING) EXTEND ON TO

ROOF 12" MIN FROM EDGE OF

FLASHING

PRE-FINISHED J-CHANNEL CLIP,

ANCHOR WITH GALVANIZED

FASTENERS WITH NEOPRENE

WASHER

2X TREATED STRUC FASCIA:

REF. STRUC

1X CEDAR FASCIA BOARD - STN

1/2" TREATED PLYWD

SHEATHING

PRE-FINISHED RAISED MTL

FLASHING AND CLEAT, ANCHOR

WITH GALVANIZED FASTENERS

WITH NEOPRENE WASHER

5/8" PLYWD SHEATHING

OVER 2X LVL FRAMING: REF.

STRUC

FULL DEPTH SPRAY FOAM

INSULATION

FACE OF STUD

6 1/2"

/2

/2

MIN

6"

FULL-DEPTH SPRAY FOAM

INSULATION

5/8" PLYWD OVER 2X WD

FRAMING: REF. STRUC

CAULK BETWEEN WEBS

FILL PANEL HEM WITH BUTYL

SEALANT

FASTENER S 16" OC WITH

BUTYL TAPE SEALANT

HIGH-HEAT WATERPROOF

MEMBRANE

INSTALL LAYER ICE AND WATER

SHIELD ENTIRE ROOF

PREFINISHED MTL STANDING

SEAM ROOFING

PREFINISHED MTL VALLEY

FLASHING

TITLE OF SHEETSUB SHEET NO.DESIGNED:

TECH REVIEW:

DATE:

DRAWING NO.

PMIS/PKG NO.

SHEET

OF11

/2

9/

:3 6:

P

M B

IM

-1

G

R T

E E nt ry

S ta tio n/

-1

G

R T

E v

_B

IM

0.

rv t

A9.3

LB/BS

GRANITE ENTRANCE STATION

GRAND TETON NATIONAL PARK

167343

312456

LB

BS/EH/BS

11/30/2021 15 43

ROOF DETAILS

SCALE OF FEET

1 0 1

SCALE A

A9.3

DTL AT TYP RAKE3

A9.3

DTL AT ROOF RIDGE2

A9.3

DTL AT TYP EAVE4

A9.3

DTL AT ROOF VALLEY1

TITLE OF SHEETSUB SHEET NO.DESIGNED:

TECH REVIEW:

DATE:

DRAWING NO.

PMIS/PKG NO.

SHEET

OF

S1.0

JR

GRANITE ENTRANCE STATION

GRAND TETON NATIONAL PARK

167343

312456

JR

ASG

11/30/2021 16 43

STRUCTURAL

W1

TECH REVIEW:

DATE:

DRAWING NO.

PMIS/PKG NO.

SHEET

OF

W1

S3.0

B C

S2.0

JR

GRANITE ENTRANCE STATION

GRAND TETON NATIONAL PARK

167343

312456

JR

ASG

17 43

WALL FRAMING PLAN

S3.0

11/30/2021

DATE:

DRAWING NO.

PMIS/PKG NO.

SHEET

OF

B C

S3.0

S3.0

S3.1

S3.0

S2.1

JR

GRANITE ENTRANCE STATION

GRAND TETON NATIONAL PARK

167343

312456

JR

ASG

18 43

ROOF FRAMING PLAN

DATE:

DRAWING NO.

PMIS/PKG NO.

SHEET

OF

S3.0

JR

GRANITE ENTRANCE STATION

GRAND TETON NATIONAL PARK

167343

312456

JR

ASG

19 43

STRUCTURAL

DETAILS

DATE:

DRAWING NO.

PMIS/PKG NO.

SHEET

OF

S3.1

JR

GRANITE ENTRANCE STATION

GRAND TETON NATIONAL PARK

167343

312456

JR

ASG

20 43

STRUCTURAL

DETAILS

CHECK VALVE

2WAY ATC VALVE

3WAY ATC VALVE

BALANCING VALVE

BUTTERFLY VALVE

MECHANICAL LEGEND

PRESSURE REDUCING VALVE

EXISTING ITEMS TO

CONNECTION TO EXISTING

BE DEMOLISHED

EXISTING ITEMS

SAFTEY RELIEF VALVE

BACK FLOW PREVENTER

NEW WORK

PRESSURE SENSOR

THERMOSTAT

METER

P&T TAP

FLOW ARROW

IN LINE PUMP

THERMOMETER

AUTOMATIC AIR VENT

GAUGE

MANUAL AIR VENT

STRAINER

DRAIN VALVE

FLEXIBLE CONNECTION

UNION

CAP

PIPING SERVICES

PIPING SYSTEM COMPONENTS

TEE UP

TEE DOWN

RS/RL

CD

ELBOW DOWN

ELBOW UP

DRAWING NOTATION

CONDENSATE DRAIN

REFRIGERANT SUCTION/LIQUID GATE VALVE

PLUG VALVE

BALL VALVE

VALVES

ECCENTRIC REDUCER

HVAC SYSTEM COMPONENTS

MOTORIZED DAMPER

RECT. RETURN DUCT

RECT. SUPPLY DUCT

SUPPLY DIFFUSER/

DN

RETURN GRILLE

DUCT SLOPE

M

18x12 RECT.

12" ROUND

MANUAL DAMPER

(D) DEMO

(N) NEW

(E) EXISTING

THREE WAY CONTROL VALVE

M

T

P

(E) EXISTING

N.C. NORMALLY CLOSED

N.O. NORMALLY OPEN

RS

RL

GRADE

SIGHT GLASS

FILTER DRYER

COND. DRAINTRAP

CONDENSING

UNIT

AC-1

NOTES:

-ROUTE REFRIGERANT PIPING PER MANUFACTURER REQUIREMENTS

-PROVIDE PVC SLEEVE FOR ALL REFRIGERANT PIPING BELOW GRADE

AND UP TO +/- 2" ABOVE GRADE.

CONCRETE PAD

W A

L L

STRUCTURE

AUXILIARY DRAIN PAN WITH UL 508

APPROVED WATER LEVEL DETECTION

DEVICE TO SHUTDOWN UNIT PRIOR TO

OVERFLOW

WALL-MOUNTED INDOOR AIR

CONDITIONING UNIT

SOLENOID VALVE (TYP.) WIRED TO AND

CONTROLLED BY UNIT CONTROLLER

SUPPLY LINE

SUMP OVERFLOW

N.C.

N.O.

N.O.

PROVIDE WITH THREADED END FOR YARD

HYDRANT TYPICAL GARDEN HOSE CONNECTION

GRADE

CONCRETE PAD

SUMP DRAIN PIPE TO BE PROVIDED SO THAT

DISCHARGE IS BEYOND CONCRETE PAD

SCALE: NOT TO SCALE

SPLIT SYSTEM DETAIL1

M1.0 SCALE: NOT TO SCALE

EVAPORATIVE COOLER AUTO DRAIN AND FILL DETAIL2

M1.0

TITLE OF SHEETSUB SHEET NO.DESIGNED:

TECH REVIEW:

DATE:

DRAWING NO.

PMIS/PKG NO.

SHEET

OF11

/2

9/

:4 7:

P

M B

IM

-1

G

R T

E E nt ry

S ta tio n/

G R

T E

M

P M od el

.r vt

MP0.0

BG

GRANITE ENTRANCE STATION

GRAND TETON NATIONAL PARK

167343

312456

BG

TJR

11/30/2021 21 43

MECHANICAL AND

PLUMBING COVER

SHEET

GENERAL MECHANICAL NOTES

A. ALL WORK SHALL BE IN ACCORDANCE WITH SMACNA STANDARDS AND SPECIFICATIONS, AND AUTHORITY

HAVING JURISDICTION.

B. THESE DRAWINGS ARE DIAGRAMMATIC IN NATURE AND NOT INTENDED TO SHOW ALL TRANSITIONS, OFFSETS, ETC. CONTRACTOR SHALL FIELD VERIFY EXISTING CONDITIONS AND PROVIDE ALL NECESSARY FITTINGS TO COMPLETE THE INTENT OF THE DRAWINGS. ANY DISCREPANCIES BETWEEN DRAWINGS AND FIELD CONDITIONS SHALL BE REPORTED TO THE CONTRACTING OFFICER (C.O). FOR RESOLUTION. CONTRACTOR MAY LOCATE MECHANICAL EQUIPMENT DIFFERENTLY THAN SHOWN ON DRAWINGS DUE TO CONFLICTS, AS LONG AS

FUNCTION AND/OR APPEARANCE ARE NOT AFFECTED.

C. MECHANICAL WORK SHOWN IS INDICATED DIAGRAMMATICALLY ON THE DRAWINGS. COORDINATE SPACE REQUIREMENTS, SUPPORTS, AND INSTALLATION OF MECHANICAL WORK PRIOR TO INSTALLATION. FOLLOW ROUTING SHOWN FOR PIPES AND DUCTS AS CLOSELY AS PRACTICABLE; PLACE RUNS PARALLEL WITH LINES OF BUILDING. UTILIZE SPACES EFFICIENTLY TO MAXIMIZE ACCESSIBILITY FOR OTHER INSTALLATIONS, FOR

MAINTENANCE, AND FOR REPAIRS.

D. COMPLY WITH MANUFACTURER'S INSTRUCTIONS INCLUDING EACH STEP IN SEQUENCE. SHOULD MANUFACTURERS' INSTRUCTIONS CONFLICT WITH THE DRAWINGS REQUEST CLARIFICATION FROM THE C.O.

BEFORE PROCEEDING.

E. DUCT SIZES ARE INSIDE DIMENSION.

F. CONTRACTOR SHALL REVIEW THESE DOCUMENTS CAREFULLY. CONTRACTOR SHALL CONTACT C.O., FOR RESOLUTION OF ANY DISCREPANCIES, OMISSIONS, OR CLARIFICATIONS, BEFORE BID DATE. IN THE EVENT THAT AN INTERPRETATION OF BID DOCUMENTS IS NECESSARY AFTER THE BID DATE, THE DECISION OF THE C.O. SHALL

BE FINAL AND BINDING.

G. PRODUCT DELIVERY, STORAGE, AND HANDLING: PROVIDE EQUIPMENT AND PERSONNEL TO HANDLE PRODUCTS BY METHODS TO PREVENT DAMAGE. PROMPTLY INSPECT SHIPMENTS TO ENSURE THAT PRODUCTS ARE UNDAMAGED. STORE AND PROTECT PRODUCTS IN ACCORDANCE WITH MANUFACTURERS' INSTRUCTIONS.

H. IN THE CASE OF A CONFLICT, UNLESS OTHERWISE NOTED, KEYNOTES ON MECHANICAL PLANS SHALL

SUPERCEDE ANY GENERAL NOTES ON THE PLANS.

I. CONTRACTOR SHALL COORDINATE WORK WITH OTHER TRADES AND NOTIFY THE C.O. IF ANY CONFLICTS

OCCUR.

J. THERMOSTAT LOCATIONS AND HEIGHTS TO BE COORDINATED AND VERIFIED BY THE C.O. CONTRACTOR TO CALIBRATE ALL THERMOSTATS SHOWN ON THIS PLAN. IT SHALL BE THE GENERAL CONTRACTOR'S RESPONSIBILITY TO ENSURE THAT ALL EXISTING THERMOSTATS REMAIN INTACT DURING DEMOLITION. HEATING THERMOSTATS MUST REMAIN OPERATIONAL AT ALL TIMES. IF REQUIRED FOR BETTER PROTECTION, THERMOSTATS MAY BE TEMPORARILY MOUNTED IN THE CEILING PLENUM DURING DEMOLITION.

K. ALL TAKEOFFS, RUNOUTS, AND FLEX DUCTWORK TO DIFFUSERS SHALL BE THE SAME SIZE AS DIFFUSER

INLET UNLESS OTHERWISE NOTED.

GRILLES, REGISTERS, AND DIFFUSERS SCHEDULE

TAG

A

B

NOTES:

1.

2.

MANUFACTURER

PRICE

PRICE

PROVIDE WITH GYPSUM BOARD MOUNTING FRAME.

OPPSABLE BLADE DAMPER IN FACE OF GRILLE.

MODEL

AMCD

PFRF

SERVICE

SUPPLY

RETURN

MATERIAL

ALUMINUM

ALUMINUM

FACE SIZE

14x14

24x12

REMARKS

1,2

ELECTRIC HEAT SCHEDULE

GENERAL

TAG

ERH-1

EBB-1

NOTES:

1.

2.

3.

4.

MANUFACTURER

QMARK

QMARK

PROVIDE WITH WALL-MOUNTED LINE VOLTAGE THERMOSTAT.

PROVIDE WITH INTEGRAL ELECTRICAL DISCONNECT

PROVIDE WITH MANUFACTURER'S MOUNTING BRACKET AND HARDWARE

PROVIDE WITH NECESSARY EQUIPMENT TO ALLOW FLOOR MOUNTED INSTALLATION.

MODEL

RCC

QMKC

LOCATION

OVERHEAD

BASEBOARD

ARRANGEMENT

WALL-MOUNTED

FLOOR-MOUNTED

ELECTRICAL

VOLTAGE

[V]

PHASE

FREQ

[HZ]

60.0

60.0

POWER

[KW]

0.90

1.25

PHYSICAL

LENGTH

[IN]

WIDTH

[IN]

2-7/8

HEIGHT

[IN]

4-3/16

6-3/4

WEIGHT

[LBS]

15.5

REMARKS

1,2,3

1,2,4

SPLIT SYSTEM COOLING SCHEDULE

GENERAL

TAG

AC-1

CU-1

NOTES:

1.

2.

3.

4.

5.

6.

MANUFACTURER

MITSUBISHI

MITSUBISHI

PROVIDE WITH LOCAL THERMOSTAT FOR EQUIPMENT CONTROL.

PROVIDE WITH HAIL GUARDS.

PROVIDE WITH 120V MICROBLUE DIAMOND CONDENSATE PUMP WITH SENSOR AND RESERVOIR.

PROVIDE REFRIGERANT PIPING IN PVC SLEEVE WHEN ROUTED UNDERGROUND.

INSTALL ON 6" GRADE-MOUNTED CONCRETE PAD PROVIDED BY OTHERS.

PROVIDE AS SINGLE POINT POWER CONNECTION. INDOOR UNIT TO BE POWERED THROUGH OUTDOOR UNIT CONNECTION.

MODEL

PKA-A12HA7

PUY-A12NKA7

LOCATION

FEE COLLECTION

OUTDOOR

SUPPLY FAN (@ 7,000 FT)

TOTAL AIRFLOW

[CFM]

ESP

[IN WC]

N/A

N/A

DX COOLING (@ 7,000 FT)

REFRIG

R410A

R410A

SENSIBLE

MBH

9,240

9,240

ELECTRICAL

VOLTAGE

[V]

208/230

208/230

PHASE

FREQUENCY

[HZ]

60.0

60.0

MCA

[A]

1.0

11.0

MOCP

[A]

28.0

SEER

20.8

20.8

PHYSICAL

LENGTH

[IN]

35-3/8

31-7/8

WIDTH

[IN]

9-13/16

11-3/16

HEIGHT

[IN]

11-5/8

24-13/16

WEIGHT

[LBS]

NOTES

1,3,6

2,4,5,6

LOUVER SCHEDULE

GENERAL

TAG

L-1

NOTES:

1.

2.

3.

4.

MANUFACTURER

GREENHECK

PROVIDE WITH STAINLESS STEEL BIRDSCREEN.

PROVIDE WITH 2 COATS OF KYNAR PAINT AND MATCH COLOR TO EXTERIOR WALL.

PROVIDE WITH BAROMETRIC RELIEF DAMPER, MATCH LOUVER SIZE.

PROVIDE WITH EXTENDED SILL, FLANGED FRAME, AND WELDED CONSTRUCTION.

MODEL

ESD-403

LOCATION

KIOSK

SERVICE

RELIEF

PERFORMANCE

AIRFLOW

[CFM]

FREE AREA

[SF]

1.7

FACE VELOCITY

[FT/MIN]

PRESSURE DROP

[IN. W.C.]

0.08

PHYSICAL

HEIGHT

[IN]

WIDTH

[IN]

DEPTH

[IN]

NOTES

1,2,3,4

EVAPORATIVE COOLER SCHEDULE

GENERAL

TAG

EC-1

EC-2

NOTES:

1.

2.

3.

4.

5.

MFG

GREENHECK

GREENHECK

PROVIDE WITH 2" MERV 13 FILTER.

PROVIDE WITH FACTORY MOUNTED CONTROLS.

PROVIDE FACOTRY AUTHORIZED REP. START-UP.

UNIT IS COOLING ONLY.

PROVIDE WITH UNIT MOUNTED VFD.

MODEL

MSX-109-H12

DGX-P114-H12-MF

SERVICE

MAIN BUILDING

KIOSK

SUPPLY FAN (@ 7,000 FT)

TOTAL

[CFM]

OA

[CFM]

ESP

[IN. W.C.]

1.00

2.00

6.

7.

8.

9.

SPEED

[RPM]

PROVIDE WITH BOTTOM DISCHARGE.

PROVIDE WITH RECIRCULATING PUMP, AUTO DRAIN, AND FLUSH SEQUENCE.

PROVIDE WITH FIELD PROVIDED UNIT MOUNTED ELECTRICAL DISCONNECT.

PROVIDE WITH GRADE-MOUNTED CURB ON 6" CONCRETE PAD.

POWER

[BHP]

0.82

0.97

SIZE

[HP]

1-1/2

EVAPORATIVE COOLING (@ 7,000 FT)

EAT DB

[°F]

83.0

83.0

EAT WB

[°F]

54.3

54.3

LAT DB

[°F]

56.5

56.0

LAT WB

[°F]

54.3

54.3

GAS HEATING (@ 7,000 FT)

EAT DB

[°F]

-15.5

LAT DB

[°F]

70.0

10.

11.

12.

13.

INPUT

[MBH]

87.1

PROVIDE AS DIRECT GAS-FIRED HEATING.

PROVIDE WITH NECESSARY ACCESSORIES FOR PROPANE FUEL SOURCE.

PROVIDE WITH LINE VOLTAGE THERMOSTAT IN KIOSK FOR UNIT CONTROL

CONTROLLED BY EXISTING FURNACE THERMOSTAT.

OUTPUT

[MBH]

80.1

ELECTRICAL

VOLTAGE

[V]

PHASE

FREQ

[HZ]

60.0

60.0

MCA

[A]

13.7

11.2

MOCP

[A]

20.0

15.0

PHYSICAL

LENGTH

[IN]

82.76

104.89

WIDTH

[IN]

33.09

33.24

HEIGHT

[IN]

38.96

39.02

WEIGHT

[LBS]

NOTES

1,2,3,4,6,7,8,9,13

1,2,3,5,6,7,8,9,10,11,12

TITLE OF SHEETSUB SHEET NO.DESIGNED:

TECH REVIEW:

DATE:

DRAWING NO.

PMIS/PKG NO.

SHEET

OF11

/2

9/

:4 7:

P

M B

IM

-1

G

R T

E E nt ry

S ta tio n/

G R

T E

M

P M od el

.r vt

MP6.0

BG

GRANITE ENTRANCE STATION

GRAND TETON NATIONAL PARK

167343

312456

BG

TJR

11/30/2021 22 43

MECHANICAL AND

PLUMBING

SCHEDULES

A B C D

B.5

2.5

FEE

COLLECTION

GENERAL

STORAGE

OFFICE

REMIT

MECH

BREAK ROOM

RR

OUTBOUND

CHECK

CORRIDOR

"x

(D) EVAPORATIVE

COOLER

TITLE OF SHEETSUB SHEET NO.DESIGNED:

TECH REVIEW:

DATE:

DRAWING NO.

PMIS/PKG NO.

SHEET

OF11

/2

9/

:4 7:

P

M B

IM

-1

G

R T

E E nt ry

S ta tio n/

G R

T E

M

P M od el

.r vt

M1.0

BG

GRANITE ENTRANCE STATION

GRAND TETON NATIONAL PARK

167343

312456

BG

TJR

11/30/2021 23 43

MECHANICAL DEMO

PLAN

M1.0

MECHANICAL DEMO PLAN1

KEY NOTES:

EXISTING TO REMAIN UNCHANGED.

DEMOLITION AND REMOVAL OF EXISTING +/- 75' OF UNDERGROUND DUCTWORK FROM THIS

POINT BACK TO EXISTING EVAPORATIVE COOLER TO BE DONE BY OTHERS. DUCT STUB TO

REMAIN FOR NEW DUCT CONNECTION. OPEN END OF DUCT STUB TO BE CAPPED. SEE

SHEET M1.1 FOR NEW DUCTWORK CONNECTION.

DEMOLITION AND REMOVAL OF EXISTING EVAPORATIVE COOLER TO BE DONE BY OTHERS.

500-GALLON BURIED PROPANE TANK TO BE PROVIDED AND INSTALLED BY OTHERS.

SCALE OF FEET

8404 12

SCALE A

SCALE A

GENERAL NOTES:

1. CONTRACTOR TO MEASURE AND RECORD EXISTING SUPPLY AIRFLOWS AT EACH DIFFUSER.

DIFFUSERS TO BE BALANCED TO MATCH EXISTING AIRFLOWS.

2. THIS SHEET IS FOR REFERENCE ONLY. ALL DEMOLITION WORK IS TO BE DONE BY OTHERS.

B.5

2.5

"ø

"ø

FEE

COLLECTION

GENERAL

STORAGE

OFFICE

OUTBOUND

CHECK

RR

CORRIDOR

REMIT

MECH

BREAK ROOM

"x

20"ø

20"ø

16"ø

(N) AC-1

(N) CU-1

(N) EC-1

(N) EC-2

(E) BURIED

PROPANE TANK

RS/RL

3/4"…