A06_4_ITM_Hot_Work_Permit.pdf
PDF 84 KB Posted
- Attached to
- Replace the boilers and heat recovery ventilators Federal contract opportunity
- Solicitation number
- 140P9724Q0020
About this file
This document contains a hot work permit form and details for a related federal contract opportunity. The hot work permit form outlines safety precautions and procedures for performing hot work, such as welding or cutting, in both designated and non-designated areas. It requires inspection of the work area before and after hot work is conducted. The related federal contract opportunity is a solicitation from the National Park Service Alaska Region to replace boilers and heat recovery ventilator units in two Marion Creek Employee Housing units located in GAAR. The project involves replacing existing heating system equipment to maintain functionality of the housing facilities.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Sol_140P9724Q0020_Amd_0001.pdf | ||
| B08_6_Bid_Schedule_Example.pdf | ||
| B08_7_Performance_Bond.pdf | ||
| Sol_140P9724Q0020.pdf | ||
| A06_1_select_original_Construction_Drawings.pdf | ||
| A06_5_CM-16_Submittal_Form.pdf | ||
| A06_3_photos_of_residence_C2.pdf | ||
| B08_9_WD_AK20240001_2_23_24.pdf | ||
| A06_2_photos_of_residence_C1.pdf | ||
| B08_8_Payment_Bond.pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Hot Work Permit (Form HW-1)
Hot Work Permitting Hot work shall only be performed in designated or permit-required areas. Before hot work operations begin in a non-designated location, a signed Hot Work Permit, issued by the Permit Authorizing Individual or his/her designee, shall be issued.
Designated Area A designated area shall be a specific area designed for, or approved by the Permit Authorizing Individual or his/her designee for, such work. A designated area can be a maintenance shop or a detached outside location that is of noncombustible or fire-resistive construction, essentially free of combustible and flammable contents, and suitably segregated from adjacent areas. All designated areas shall have been inspected and approved by the Permit Authorizing Individual or his/her designee.
Permit-Required Area A permit-required area shall be an area that is made fire safe and authorized by the issuance of a signed NPS Hot Work Permit. The Hot Work Permit shall be signed by Permit Authorizing Individual or his/her designee.
Non-permissible Areas Hot work shall not be allowed in the following areas:
(a) In areas not authorized by the Permit Authorizing Individual or his/her designee
(b) In sprinklered buildings while such protection is impaired
(c) In the presence of explosive atmospheres (that is, where mixtures of flammable gases, vapors, liquids, or dusts with air exist)
(d) In explosive atmospheres that can develop inside unclean or improperly prepared drums, tanks, or other containers and equipment that have previously contained such materials
(e) In explosive atmospheres that can develop in areas with an accumulation of combustible dusts
GENERAL
Park: District: Building: Floor:
Work to be done:
Special precautions:
PERSON PERFORMING WORK
Contractor Business Name:
Contractor Representative:
Contractor Contact Number:
NPS Employee’s Name:
NPS Office:
NPS Employee’s Contact Number:
CHECK
Work area and all adjacent areas to which sparks and heat might have spread (including floors above and below and on opposite side of wall(s) were inspected every 20 minutes for 1 hour after the work was completed and were found fire safe.
ATTENTION
Before approving any hot work permit, the Permit Authorizing Individual or his/her designee shall inspect the work area and confirm that the proper precautions have been taken to prevent fire, in accordance with the NPS Hot Work Permit Form (Form HW-1) and the NPS Hot Work Policy.
PRECAUTIONS
Sprinklers in service Hot work equipment in good repair
WITHIN 35 FEET OF HOT WORK AREA
Floors swept, clean of combustibles Combustible floors wetted down, covered w/ damp sand or other shields in place All wall and floor openings covered
WORK ON WALLS OR CEILINGS
Combustibles moved away from opposite side of wall
WORK ON ENCLOSED EQUIPMENT (tanks, containers, ducts, dust collectors etc.)
Equipment cleaned of all combustibles Containers purged of all flammable vapors
FIRE WATCH
To be provided during and 60 minutes after operation Supplied with a fully charged and operable fire extinguisher Trained in use of equipment and activating fire alarm system
FINAL CHECK
To be made every 20 minutes for 60 minutes after completion of any operation unless fire watch is provided
Is a fire watch required? Yes No
The location where the work is to be done has been examined, necessary precautions taken, and permission is granted for this work.
Permit Issue Date: Permit Expires:
Permit Authorizing Individual or Designee:
Signature: Date:
File details come from the government source that posted it. Updated .