A05_PWS_BASIN_WELL_IMP.pdf
PDF 7 MB Posted
- Attached to
- BLM-CO TRFO BASIN WELL AND WATER SYSTEM Federal contract opportunity
- Solicitation number
- 140L1726R0005
About this file
This is a Performance Statement of Work (PSW) for the TRFO Basin Well Improvement project administered by the Bureau of Land Management (BLM) Tres Rios Field Office in Colorado.
The contractor must deliver a turnkey solar-powered well water system that automatically provides and maintains 500 gallons of water per day to a wildlife drinking tank with minimal human input except for winterization and annual maintenance. Key deliverables include: demolition of existing infrastructure (well house, stock tank, storage tank, and pump); investigation and improvement of the existing artesian well including pump testing, surface casing installation, well cap provision, and chlorine disinfection; and installation of a complete water system comprising a solar power array with livestock exclusion fence, a new submersible pump with pitless adapter, a 5,000-gallon buried storage tank with float switch control and livestock exclusion fence, a 1,000-gallon drinking tank with frost-proof hydrant and wildlife escape ramp, and associated piping and miscellaneous components buried minimum 36 inches deep. The system must maintain water within the top 6 inches of the drinking tank and be freeze-proof and operational in winter. The project location is near Naturita, Colorado (latitude 38.06529167° N, longitude -108.63154723° W). All work must comply with Colorado Division of Water Resources requirements and be performed by a licensed well contractor per Colorado Board of Examiners standards (2 CCR 402-14). The period of performance is 360 calendar days with all work to be completed within 90 days of starting (Monday through Friday, excluding federal holidays). Payment is structured in three line items covering demolition, well investigation and improvement, and water system installation. The contractor must comply with BLM wildlife environmental protection measures outlined in Appendix A, including noxious weed management, fire extinguisher and tool requirements on equipment, camping and worksite conditions, and hazardous materials handling.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Sol_140L1726R0005_Amd_0003.pdf | ||
| B11_Q_A_1_140L1726R0005_0003.pdf | ||
| Sol_140L1726R0005_Amd_0002.pdf | ||
| Q_A_140L1726R0005_0002.pdf | ||
| Sol_140L1726R0005_Amd_0001.pdf | ||
| B08_UPDATED_140L1726R0005__TERMS_AND_CONDITIONS_v_08_27_2026_0001.pdf | ||
| B03_WD__CO20260003.pdf | ||
| Sol_140L1726R0005.pdf | ||
| A04_BID_SCHEDULE_BASIN_WELL_IMP.pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
TRFO Basin Well Improvement Performance Statement of Work
PERFORMANCE STATEMENT OF WORK
Contents:
1. General Requirements
2. Project Specific Requirements
3. Drawings
4. Supplemental Site Pictures
5. Existing Well Information
6. Appendix A – TRFO Wildlife Protection Measures
General Requirements
Basin Well Improvement
1 GENERAL REQUIREMENTS
1.1 GENERAL
The contractor shall provide all personnel, equipment, supplies, facilities, transportation, tools, materials, supervision, and other items and non-personal services necessary to perform the work as defined in this Performance Work Statement.
1.2 PERIOD OF PERFORMANCE
The period of performance shall be 360 days. Contractor shall complete all work within 90 days of starting work. 360 days period of performance is provided to allow contractor to fit the work into their schedule. Work shall occur Monday thru Friday except Federal holidays.
1.3 QUALITY CONTROL
The contractor shall develop and maintain an effective quality control program to ensure services are performed in accordance with this performance statement of work. The contractor’s quality control program is the means by which the Contractor assures that the work complies with the requirements of the contract.
1.4 QUALITY ASSURANCE
The Government will assure quality of the contractor’s work.
1.5 POST AWARD CONFERENCE
The Contractor shall attend a post award, on site meeting, prior to starting work. The purpose of the meeting is to:
• Introductions.
• Site familiarization tour and verify existing conditions.
• Review and discussion of project requirements and schedule.
1.6 CONTRACTING OFFICER’S REPRESENTATIVE (COR)
The (COR) will be identified by separate letter. The COR monitors all technical aspects of the contract and assists in contract administration. A letter of designation issued to the COR, a copy of which is sent to the Contractor, states the responsibilities and limitations of the COR, especially with regard to changes in cost or price, estimates or changes in delivery dates. The COR is not authorized to change any of the terms and conditions of the resulting order.
Project Specific Requirements
2 PROJECT SPECIFIC REQUIREMENTS
2.1 SUMMARY OF WORK
Contractor shall provide a turnkey solar powered, well water system that automatically provides and maintains water to a wildlife drinking tank with minimal human input except winterization and annual maintenance. System shall be designed to have a solar pumping system at an existing water well. Provide water to an elevated buried storage tank. The buried storage tank will gravity feed the drinking tank. An additional tee and valve shall be provided for a future upgrade for a stockwater tank. System shall be designed to be freeze proof and operational in the winter to the frost free hydrant at the drinking tank.
2.2 PROJECT LOCATION
Latitude: 38.06529167° N Longitude: -108.63154723° W From Naturita, CO. Travel south on CO-141 for approximately 12 miles. Turn right (west) on County Road U29. Travel approximately 5 miles. The project is on the left (south).
2.3 REFERENCE INFORMATION
See attached for existing well information.
See attached for existing condition pictures.
The BLM has not operated the well pump in at least 20 years.
2.4 EXISTING ITEMS TO DEMOLISH
Existing items to demolish:
Well house (including all components associated with well house; cistern, loadout, foundation, utilities, piping, etc)
Stock tank.
Storage tank.
Well pump, if applicable.
The existing well and well casing shall be protected in place during demolition.
All materials demolished, shall become the property of the Contractor and shall be removed from Government property and disposed of in a legal manner.
2.5 GENERAL WORK REQUIREMENTS
All well work shall be in accordance with Colorado Division of Water Resources requirements.
Well contractor shall be licensed in accordance with Colorado Board of Examiners of Water Well Construction and Pump Installation Contractors, as outlined in the Colorado Revised Statutes and the Board’s rules (2 CCR 402-14)
All work shall be in accordance with Code of Colorado Regulations: 2 CCR 402-2.
2.6 WATER WELL INVESTIGATION AND IMPROVEMENT
Investigate existing conditions of the well and well casing.
Pump test the well.
o Verify the well is capable of producing water as required in WATER SYSTEM
REQUIREMENTS.
Notify the COR of any issues discovered during investigation that won’t allow completion of the work per this SOW.
Provide surface casing, well cap, and grout/well seal as needed.
o Extend steel surface casing above grade.
o Seal surface and well casings if needed to comply with CO DWR requirements.
o Prepare well casings for a pitless adapter (see Section 2.7.3) o Provide and install suitable well cap
Disinfect the well with chlorine solution (shock the well) per the requirements of 2 CCR 402-2 Rule 15
2.7 WATER SYSTEM
2.7.1 WATER SYSTEM DESIGN
Design a water system that provides 500 gallons of water per day to wildlife, delivered at the drinking tank.
Provide details (manufacturer, model, etc.) of all components (pump, solar panels, switches, tanks, etc.) installed.
2.7.2 SOLAR POWER
Provide a complete solar power system, as necessary, to power the water system.
Provide livestock exclusion fence, with man gate, to protect solar power system and well head from livestock.
2.7.3 WELL AND PUMP
Provide pump, sized appropriately for the water system.
Provide pitless adaptor compatible with an artesian well.
2.7.4 STORAGE TANK
Provide a new 5,000 gallon storage tank with the following features.
o Inlet and outlet.
o Vent.
o Overflow.
o Access riser.
o Rated for full bury depth as required.
Bury the storage tank to protect from freezing, per manufacturers installation requirements.
Provide a float switch or similar means of water level control in the storage tank.
Provide new livestock exclusion fence around storage tank.
o Contractor may reuse or repair existing fencing around existing storage tank after installation of new storage tank.
2.7.5 DRINKING TANK
Provide a 1,000 gallon drinking tank, approximate size 9’ diameter x 28” depth, with drain valve and escape ramp for wildlife.
Provide frost proof hydrant to fill the drinking tank.
Provide a wildlife friendly, livestock exclusion fence around the wildlife drinking tank, with man gate.
2.7.6 MISCELLANEOUS WATER SYSTEM COMPONENTS
Contractor shall provide any piping, floats, valves, switches, and other componets, as required, for a complete and functioning solar powered livestock and wildlife water system, including winterization and maintenance.
o Contractor not responsible for winterization and maintenance.
Water system shall maintain water within the top 6 inches of the drinking tank.
Water distribution pipes (between well and tanks) shall be buried a minimium of 36 inches.
Provide tee and curb stop with capped riser pipe for future addition of livestock drinking tank.
o Livestock drinking tank not required in this statement of work.
All provided water system components shall be new.
Contractor shall demonstrate proper functioning of the water system.
o Contractor shall train BLM operator on winterization and maintenance procedures.
2.8 PRICE AND PAYMENT
Payment items for the work of this contract for which contract payments will be made are listed in the SCHEDULE and described below. All costs for items of work, which are not specifically mentioned to be included in a particular job are included in the listed job item most closely associated with the work involved. The price and payment made for each item listed constitutes full compensation for furnishing all labor, materials, and equipment, and performing any associated Contractor quality control, environmental protection, meeting safety requirements, tests and reports, and for performing all work required for which separate payment is not otherwise provided.
2.8.1 DEMOLITION
Payment will be made for all costs associated with paragraph 2.4 EXISTING ITEMS TO DEMOLISH. Including transportation and disposal.
2.8.2 WATER WELL INVESTIGATION AND IMPROVEMENT
Payment will be made for all costs associated with paragraph 2.6 WATER WELL INVESTIGATION AND IMPROVEMENT, including sub-paragraphs.
2.8.3 WATER SYSTEM
Payment will be made for all costs associated with paragraph 2.7 WATER SYSTEM, including sub-paragraphs.
3 ADDITIONAL WORK REQUIREMENTS
The Contractor shall adhere to all conditions identified in Appendix A – BLM TRFO Wildlife Environmental Protection Measures.
Drawings
RIDGEWAY CANON
CORTEZ
DURANGO
ROCKY FORD
NEW MEXICO
CITY
ALAMOSA
TRINIDAD
WALSENBURG
OKLAHOMA
GUNNISON
SPRINGS
GLENWOOD
EAGLE
WYOMING
CRAIG
MONTROSE
GRAND
U
TA
H
CARBONDALE
RIFLE
JCT.
COLORADO
MEEKER
SALIDA
LEADVILLE
PUEBLO
COLORADO
SPRINGS
FT. COLLINS
WOLCOTT
STEAMBOAT SPRINGS
DENVER
LIMON
KA
N
SA
S
STERLING
NEBRASKA
PROJECT LOCATION
PROJECT LOCATION
NATURITA
U-29
NORWOOD
N A
TI
O
N A
L
SY
ST
EM
O F
PU
BL
IC
L
A N
D S
U .S
. D
EP
A
RT
M
EN
T O
F
TH
E
IN
TE
RI
O R
BU
RE
A U
O F
LA
N
D M
A N
A G
EM
EN
T
N
NOT TO SCALE
PROJECT LOCATION MAP
UNITED STATES DEPARTMENT OF INTERIOR
BUREAU OF LAND MANAGEMENT
TRES RIOS FIELD OFFICE
BASIN WELL AND WATER SYSTEM IMPROVEMENTS
1 TITLE SHEET
2 SCHEMATIC SITE PLAN
SHEET INDEX
N
NOT TO SCALE
PROJECT LOCATION REFERENCE MAP
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
CHK'D BY:
AutoCAD SHX Text
DESIGN OFFICE:
AutoCAD SHX Text
DESIGNED BY:
AutoCAD SHX Text
PROJECT NO:
AutoCAD SHX Text
DRAWN BY:
AutoCAD SHX Text
SHEET
AutoCAD SHX Text
APPROVED BY:
AutoCAD SHX Text
OF
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
DESCRIPTION
AutoCAD SHX Text
MARK
AutoCAD SHX Text
APPROVED
AutoCAD SHX Text
DATE
AutoCAD SHX Text
UNITED STATES DEPARTMENT OF THE INTERIOR
AutoCAD SHX Text
BUREAU OF LAND MANAGEMENT
AutoCAD SHX Text
TITLE SHEET
AutoCAD SHX Text
BASIN WELL AND WATER SYSTEM IMPROVEMENTS
AutoCAD SHX Text
SOUTHWEST DISTRICT
AutoCAD SHX Text
COLORADO
AutoCAD SHX Text
SOUTHWEST DISTRICT
AutoCAD SHX Text
P. RUSSELL
AutoCAD SHX Text
P. RUSSELL
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text E
AutoCAD SHX Text A
AutoCAD SHX Text h
AutoCAD SHX Text
AutoCAD SHX Text r
AutoCAD SHX Text a
AutoCAD SHX Text c
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text U.
AutoCAD SHX Text E
AutoCAD SHX Text S.
AutoCAD SHX Text D
AutoCAD SHX Text P
AutoCAD SHX Text M
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
"STUART, IS THAT YOU IN THERE?"
AutoCAD SHX Text
PAUL
AutoCAD SHX Text R
AutoCAD SHX Text N
AutoCAD SHX Text I
AutoCAD SHX Text T
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text O
AutoCAD SHX Text I
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text T
AutoCAD SHX Text M
AutoCAD SHX Text N
AutoCAD SHX Text T
AutoCAD SHX Text O
AutoCAD SHX Text H
AutoCAD SHX Text F
AutoCAD SHX Text T
AutoCAD SHX Text
BUREAU OF LAND MANAGEMENT
AutoCAD SHX Text
U.S. DEPARTMENT OF THE INTERIOR
COUNTY ROAD U-29 WEST
PRIVATE LAND - NORTH SIDE OF ROAD
PUBLIC LAND - SOUTH SIDE OF ROAD
EXISTING WELL HOUSE
PROPOSED SOLAR POWER SYSTEM
PROPOSED STORAGE TANK
(SAME LOCATION AS EXISTING STORAGE TANK)
PROPOSED STORAGE TANK
LOCATION IS APPROXIMATELY 50
FEET (CONTRACTOR TO VERIFY)
ELEVATION ABOVE THE WELL HOUSE
+/-500'
EXISTING FENCE
PROVIDE VALVE FOR FUTURE LIVESTOCK TANK ADDITION
PROPOSED WILDLIFE DRINKING TANK
PROPOSED WATER LINE
PROPOSED LIVESTOCK EXCLUSION FENCE
30'
SIZE FENCE AS REQUIRED FOR WELL AND SOLAR SYSTEM
N A
TI
O
N A
L
SY
ST
EM
O F
PU
BL
IC
L
A N
D S
U .S
. D
EP
A
RT
M
EN
T O
F
TH
E
IN
TE
RI
O R
BU
RE
A U
O F
LA
N
D M
A N
A G
EM
EN
T
N
0 50'
SCALE 1" = 50'
SCHEMATIC SITE PLAN
NOTE: DRAWING IS SCHEMATIC. EXACT LOCATIONS OF PROPOSED INFRASTRUCTURE SHALL BE COORDINATED ON SITE WITH THE CONTRACTING OFFICER'S REPRESENTATIVE
AutoCAD SHX Text
CHK'D BY:
AutoCAD SHX Text
DESIGN OFFICE:
AutoCAD SHX Text
DESIGNED BY:
AutoCAD SHX Text
PROJECT NO:
AutoCAD SHX Text
DRAWN BY:
AutoCAD SHX Text
SHEET
AutoCAD SHX Text
APPROVED BY:
AutoCAD SHX Text
OF
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
DESCRIPTION
AutoCAD SHX Text
MARK
AutoCAD SHX Text
APPROVED
AutoCAD SHX Text
DATE
AutoCAD SHX Text
UNITED STATES DEPARTMENT OF THE INTERIOR
AutoCAD SHX Text
BUREAU OF LAND MANAGEMENT
AutoCAD SHX Text
SCHEMATIC SITE PLAN
AutoCAD SHX Text
BASIN WELL AND WATER SYSTEM IMPROVEMENTS
AutoCAD SHX Text
SOUTHWEST DISTRICT
AutoCAD SHX Text
COLORADO
AutoCAD SHX Text
SOUTHWEST DISTRICT
AutoCAD SHX Text
P. RUSSELL
AutoCAD SHX Text
P. RUSSELL
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
1'-4"
2' 2'-6"
3'-6"
3'-6" (TYP)
4'-6" (TYP)
8' (TYP)
SMOOTH WIRE
SMOOTH WIRE
12" x 38" DIA. SPIKE (TYP) PILOT HOLE (TYP)
CORNER POSTEND POST
5" DIAMETER (TYP)COMPACT BACKFILL (TYP)
3'-6" (TYP)
4'-6" (TYP)
12" DIA. x 38" SPIKE (TYP)
PILOT HOLE (TYP)
5" DIAMETER (TYP)
COMPACT BACKFILL (TYP)
SMOOTH WIRE
NOTCH POSTS AT RAIL CONNECTION
16' 16'
8'
4'-6" (TYP)
2' (TYP)
END PANEL
METAL LINE POST
WIRE STAY
(INSTALLED BETWEEN ALL LINE POSTS)
END PANEL
16'
N A
TI
O
N A
L
SY
ST
EM
O F
PU
BL
IC
L
A N
D S
U .S
. D
EP
A
RT
M
EN
T O
F
TH
E
IN
TE
RI
O R
BU
RE
A U
O F
LA
N
D M
A N
A G
EM
EN
T
NOT TO SCALE
LINE POSTS
NOT TO SCALE
END PANEL
NOT TO SCALE
CORNER PANEL
AutoCAD SHX Text
CHK'D BY:
AutoCAD SHX Text
DESIGN OFFICE:
AutoCAD SHX Text
DESIGNED BY:
AutoCAD SHX Text
PROJECT NO:
AutoCAD SHX Text
DRAWN BY:
AutoCAD SHX Text
SHEET
AutoCAD SHX Text
APPROVED BY:
AutoCAD SHX Text
OF
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
DESCRIPTION
AutoCAD SHX Text
MARK
AutoCAD SHX Text
APPROVED
AutoCAD SHX Text
DATE
AutoCAD SHX Text
UNITED STATES DEPARTMENT OF THE INTERIOR
AutoCAD SHX Text
BUREAU OF LAND MANAGEMENT
AutoCAD SHX Text
WIRE FENCE - WILDLIFE FRIENDLY
AutoCAD SHX Text
BASIN WELL AND WATER SYSTEM IMPROVEMENTS
AutoCAD SHX Text
SOUTHWEST DISTRICT
AutoCAD SHX Text
COLORADO
AutoCAD SHX Text
SOUTHWEST DISTRICT
AutoCAD SHX Text
P. RUSSELL
AutoCAD SHX Text
P. RUSSELL
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
Supplemental Site Pictures
Existing well house
Existing well house
Inside well house.
Well pit filled with ~4’-4” of water. Well pit is maintained full by the artesian well.
Existing storage tank
Existing Well Information wR1x5 -7s
T0' E OR
PRINT IN BLACK INK.
COPY OF ACCEPTED
STATEMENT MAILED
ON REQUEST.
RECEIVED
0 r"T 1 8 1989
Wa FVSP t- CP
COLORADO DIVISION OF WATER RESOURCES
818 Centennial Bldg., 1313 Sherman St.
Denver, Colorado 80203
STATE OF COLORADO l
COUNTY OF _ San Miguel _ — r SS.
X _ STATEMENT OF BENEFICIAL USE OF GROUND WATER
AMENDMENT OF EXISTING RECORD
AFFIDAVIT
NAM RESOURCd LATE REGISTRATION
47ATL • ENGMU
0" PERMIT NUMBER 150834; Basin Well LOCATION OF WELL
THE AFFIANT( S)_ Bureau of Land Management i cn t,. San MieueL_ __ whose mailing address is 2465 South Townsend Ave, _ NE—
City Montrose, _ Colorado 81401 Tw P. -- 4_ C f T. TrI Inv)
4_- Rn9.
being duly sworn upon oath, deposes and says that he ( they) is ( are) the owner( s) of the well described hereon; the well is located as described above, at distances of _ 25Q feet from the North — section line and Ff)() feet from the IunRTp oa III IT
East section line; water from this well was first applied to a beneficial use for the purpose( s) described herein on the r... . P wr" T day of April _ , 19 -88_; the maximum sustained pumping rate of the well is 1. 5 0 gallons per minute, the pumping rate claimed hereby is _ 15. 0 ._ gallons per minute; the total depth of the well is 607 feet; the average annual amount of water to be diverted is 2. 0 acre -feet; for which claim is hereby made for dnrvocttr• and Brest,,, watering.
purpose( s), the legal description of the land on which the water from this well is used is of which acres are irrigated and which is illustrated on the map on the reverse side of this form; that this well was completed in compliance with the permit approved therefor; this statement of beneficial use of ground water is filed in compliance with law; he they) has ( have) read the statements made hereon; knows the content thereof; and that the same are true of his ( their) knowledge.
COMPLETE REVERSE SIDE OF THIS FORM)
Suuswibed and sworn V19to b"e( ore Me s / 6o day of 92'_Z • 1901
My Commission a Aires: Z— .vZ
ACCEPTED FOR FILING BY THE STATE ENGINEER OF COLORADO
PURSUANT TO THE FOLLOWING CONDITIONS:
PHAT THOSE CONDITIONS OF APPROVAL AS STATED 0)1 T9L
PERMIT AIM COMPLIED WITH.
FOR OFFICE USE ONLY
C.., t C.,. N.
Prior. _ Mo. D., Y, D. CIY. 5?
seq. -_._— _ -— A' w U Us< -.
D,,, Basln Man. Des
OCT 3 0 1989 AM - AaAnU c/
TE ER Y
Donald D. Janangs
Well drilled by Atlaa Water Wall Drilling Company Permanent
Pump installed by Do = U D. Jennings
Lic. No. N/ A
Lic. No
Meter Serial No. _ Flow Meter Date Installed 5- 3- 72
Owner of land on which water is being used Bureau of Land Mlnagemnt
THE LOCATION OF THE WELL MUST BE SHOWN AND FOR LARGE CAPACITY IRRIGATION WELLS THE AREA ON WHICH THE WATER IS USED MUST BE SHADED OR CROSSHATCHED ON THE DIAGRAM BELOW.
NORTH
This diagram represents nine ( 9) sections. Use the CENTER SQUARE one section) to indicate the location of the well, if possible.
WATER EQUIVALENTS TABLE ( Rounded Figures)
An acre - foot covers 1 acre of land 1 foot deep.
1 cubic foot per second ( cfs) ... 449 gallons per minute ( gpm).
1 acre - foot... 43, 560 cubic feet... 325, 900 gallons.
1, 000 gpm pumped continuously for one day produces 4. 42 acre - feet.
100 gpm pumped continuously for one year produces 160 acre - feet.
WHITE AND PINK COPY TO BE FILED WITH THE STATE ENGINEER
PINK COPY WILL BE RETURNED TO OWNER)
i c C
NORTH SE TION LI E
x w +
NMn J zo z m w
W
SOUTH SEC ION LI E
THE SCALE OFT E DIAGRAM IS TWO INCHES E UALS ONE -MI E
1 M i Ie
WATER EQUIVALENTS TABLE ( Rounded Figures)
An acre - foot covers 1 acre of land 1 foot deep.
1 cubic foot per second ( cfs) ... 449 gallons per minute ( gpm).
1 acre - foot... 43, 560 cubic feet... 325, 900 gallons.
1, 000 gpm pumped continuously for one day produces 4. 42 acre - feet.
100 gpm pumped continuously for one year produces 160 acre - feet.
WHITE AND PINK COPY TO BE FILED WITH THE STATE ENGINEER
PINK COPY WILL BE RETURNED TO OWNER)
i c C l wJR -2G -]] RECEIVED
COLORADO DIVISION OF WATER RESOURCES -
HIS FORM MUST BE SUBMITTED 1313 Sherman Street - Room 818 - r 1 f989 WITHIN 60 DAYS OF COMPLETION Denver, Colorado 80203 OF THE WORK DESCRI BED HERE- WATER RtSgUX4 ON. TYPE OR PRINT IN BLACK WELL COMPLETION AND PUMP INSTALLATION REPORT ZAM - Et
INK.
PERMIT NUMBER 150834; Basin Well R!
WELL OWNER gureau e€ Land MasLgemenr __- NE '% of the NE '/. of Sec. 21 , ADDRESS 246nTo;,Rse Ave, Montr. Qp_ CO 91401 T. 44_ N R. 16 W NM p. M, DATE COMPLETED , 19- 7-2- HOLE IQIAMETER
WELL LOG
in. from to ft.
From To Type and Color of Material
Water
Loc.
of 30' Clay, brown and gray
Steel from 0 to 440 ft.
30' 70' Mancos shale, gray
Steel from 544 _ to 607 ft.
70' 80' Gray shale grading to brown x clay grading to black coal
80' 100' Coal, black
100 280' Blue shale, probable mancos shale
280 450' Interbedded soft gray shale with hard brown sand and black coal
450 490' Hard brown sand, artesian x ground water
490 520' Hard brown or white sand; x increase in water yield
520 550' Hard brown sand; further x increase in water yield
550 607' Interbedded clay, shale, and sand
TOTAL DEPTH
Use additional F,(t117 , pages necessary to cohiplete log.
in, from to ft.
in, from to ft.
DRILLING METHOD
CASING RECORD: Plain Casing
Size 65/ 801& kind Steel from 0 to 440 ft.
Size / 9D& kind Steel from 418 to 607 ft.
Size 4V0 & kind Steel from 544 _ to 607 ft.
Perforated Casing
Size 1,_} "OD& kind Steel from 460 to 544 ft.
Size & kind _— from to ft.
Size & kind from to ft.
GROUTING RECORD
Material
Intervals
Placement Method
GRAVEL PACK: Size
Interval
TEST DATA
Date Tested
Static Water Level Prior to Test
Type of Test Pump
Length of Test
Sustained Yield ( Metered) —
Final Pumping Water Level ft.
PUMP INSTALLATION REPORT
Pump Make
Type
Powered by HP
Pump Serial No.
Motor Serial No.
Date Installeo
Pump Intake Depth
Remarks
WELL TEST DATA WITH PERMANENT PUMP
Date Tested — May 1, 1972
Static Water Level Prior to Test flowing artesian
Length of Test 1 Hours
Sustained yield ( Metered) 7U — GPM
Pumping Water Level 240 feet
Remarks
CONTRACTORSSTATEMENT
j{¢ lea+ annret_ Tnn ^ jy3$fl£ 1gi£ @H[f fl S3f1Y8i(ji7^ x.'3aStaiiII117] L - - - - -- 3hA'GhG 4?t'BE tP'•- r+^`'+ +' fl £f1d3[>i@_$ E.fflQtti 4Cii @£ @B ii
Signature License No.
State of Colorado, County of SS
Subscribed and sworn to betore me this Ao-'- day of 12/ 7 mien , 19 4i.
My Commission expires: 12— , 19 .
Notary Public I An*
FORM TO BE MADE OUT IN QUADRUPLICATE: WHITE FORM must be an original copy on both sides and signed.
WHITE AND GREEN copies must be filed with the State Engineer. PINK COPY is for the Owner and YELLOW COPY is for the Driller.
7/ 0 x wP.J- S; Rev.
76J
COLORADO DIVISION OF WATER RESOURCES
818 Centennial Bldg., 1313 Sherman St., Denver, Colorado 60203 r
RE R ED
PERMIT APPLICATION FORM
r7Application must -- "'•( 19' be complete whe E i`, - ( ) A PERMIT TO USE GROUND WATER applicable, Type ( ) A PERMIT TO CONSTRUCT A WELL WATER RESOURCES print in BLACK t "' FOR: ( ) A PERMIT TO INSTALL A PUMP SIATI - ENGINEER
INK. Nooverstrikes rJEF ` Ctrio.
or erasures unless ER RLgyUrsCL`; ( )
REPLACEMENT FOR NO.
initialed. A>: , Encu+ect ( x) OTHER permit to use an existing well 3TNV 0Ut'J WATER COURT CASE NO.
1) APPLICANT - mailing address
NAME
Bureau of Land Management
STREET
2465 South Townsend Avenue
CITY
Montrose, Colorado 81401
TELEPHONE NO
303) 249 - 7791
2) LOCATION OF PROPOSED WELL
County San Miguel
NE
of the
NE %,
Section
Two, 44 N , Rng. 16 W N. M. P. M.
h, S, kE, M
3) WATER USE AND WELL DATA
Proposed maximum pumping rate ( gpm) 1510
Average annual amount of ground water 2, 0 aC. - ft to be appropriated lacre- feet):
Number of acres to be irrigated:
none
Proposed total depth ( feet) : 607 feet
Aquifer ground water is to be obtained from:
Dakota Sandstone Formation
Owner' s well designation Basin Well
GROUND WATER TO BE USED FOR:
HOUSEHOLD USE ONLY
X) DOMESTIC ( 1)
X) LIVESTOCK ( 2)
COMMERCIAL ( 4)
OTHER ( 9)
no irrigation ( 0)
INDUSTRIAL ( 5)
IRRIGATION ( 6)
MUNICIPAL ( B)
DETAIL THE USE ON BACK IN 01)
4) DRILLER
Atlas Water Well Drilling Company
Name Donald D. Jennings
6411 South Marion Street Street
City Littleton, Colorado 80121
Btatel ( Z', P) i ic. No
FOR OFFICE USE ONLY: DO NOT WRITE IN THIS COLUMN
Receipt No. / 12049
Basin Dist.
CONDITIONS OF APPROVAL
This well shall be used in such a way as to cause no material injury to existing water rights. The issuance of the permit does not assure the applicant that no injury will occur to another vested water right or preclude another owner of a vested water right from seeking relief in a civil court action.
1 APPROVED FOR THE USE OF AN EXISTING WELL
STRUCTURE PURSUANT TO CRS 37- 92- 602( 3)( b)( II)
AS THE ONLY WELL ON A TRACT OF LAND OF 40 ACRES
DESCRIBED AS NE 1/ 4 OF THE NE 1/ 4 OF SECTION
21 T44N R16W OF THE N. M. P. M., SAN MIGUEL
COfJNTY. , 2 THE USE OF GROUND WATER FROM THIS WELL IS
LIMITED TO ORDINARY HOUSEHOLD PURPOSES INSIDE
ONE SINGLE FAMILY DWELLING FIRE PROTECTION
AND THE
AND LIVESATOCK ON
AFFPARIL
OR;' 6H
STIC ANIMAS,
3) THE RETURN FLOW FROM THE USE OF THE WELL
MUST BE THROUGH AN INDIVIDUAL WASTEWATER
DISPOSAL SYSTEM OF THE NON-- EVAPORATIVE TYPE
WHERE THE WATER IS RETURNED TO THE SAME STREAM
SYSTEM IN WHICH THE WELL IS LOCATED.
W.M. 3 --3/- W
APPLICATION APPROVED
PERMIT NUMBER 150834
DATE ISSUED APR 01 W
EXPIRATION DATE
APR 0 11990
5) THE LOCATION OF THE PROPOSED WELL and the area on which the water will be used must be indicated on the diagram below.
Use the CENTER SECTION ( 1 section, 640 acres) for the well location.
4- - +-- {- - + -- E, 4 1MILE, 5280 FEET —
l
NORTH SECTION LINE — + — 1
NORTH+
I X i z
II
I rn
LL
I u 4— 3
4-r I
I
I X i
I
I
II
I aVV I JCV IIVN LIN[
I !
I
Ir !
T + T t 4 i- +
I
4- --+— F- - +— —+
The scale of the diagram is 2 inches = 1 mile Each small square represents 40 acres.
WATER EQUIVALENTS TABLE ( Rounded Figures)
An acre - foot covers 1 acre of land 1 foot deep 1 cubic foot per second ( cts) ... 449 gallons per minute ( gpm) A family of 5 wilt require approximately 1 acre - foot of water per year.
1 acre - foot ... 43, 560 cubic feet ... 325, 900 gallons.
1, 000 gpm pumped continuously for one day produces 4. 42 acre - feet.
l'( 10) LAND 64 WHICH GROUND WATE' A Mu 8E USED:
6) THE WELL MUST BE LOCATED BEIQW
by distances from section lines.
ft. from
North sec. line north or south)
600 East
ft. from sec. line east or west)
LOT BLOCK FILING a
SUBDIVISION
7) TRACT ON WHICH WELL WILL BE
LOCATED4 wner
BLM
No. of acres - Will this be the only well on this tract?
Yes
8) PROPOSED CASING PROGRAM
Plain Casing ( 22' Casing Overlap
in. from 418 ft. to 461D.— ft.
in. from 544 ft. to 607 ft.
Perforated casing
4 ' 544
in. from ft, to ft.
in, from ft. to .` t.
9) FOR REPLACEMENT WELLS givedistance and direction from old well and plans for plugging it:
Owner( s):
Bureau of Land Management
No. of acres:
T 44 N R 16 W Section 21 NEt - NEB
Legal description: ° °
11) DETAILED DESCRIPTION of the use of ground water: Household use and domestic wells must indicate type of disposal system to be used.
livestock watering and domestic uses
12) OTHER WATER RIGHTS used on this land, including wells. Give Registration and Water Court Case Numbers.
Type or right Used for ( purpose) Description of land on which used
None
13) THE APPLICAN S) ' STATE( S) THAT THE INFORMATION SET FORTH HEREON IS
TRUE TO THE BEST'- QF HIS ', A` LEDGE. /
SIGNATURE OF APPLICANTIS) PauT W. rrasniitsh,' Uttrtc
1Burl' u o La , 14anagement
Use additional sheets of paper if more space is required.-rnHNmny — z zm T
I !
I
Ir !
T + T t 4 i- +
I
4- --+— F- - +— —+
The scale of the diagram is 2 inches = 1 mile Each small square represents 40 acres.
WATER EQUIVALENTS TABLE ( Rounded Figures)
An acre - foot covers 1 acre of land 1 foot deep 1 cubic foot per second ( cts) ... 449 gallons per minute ( gpm) A family of 5 wilt require approximately 1 acre - foot of water per year.
1 acre - foot ... 43, 560 cubic feet ... 325, 900 gallons.
1, 000 gpm pumped continuously for one day produces 4. 42 acre - feet.
l'( 10) LAND 64 WHICH GROUND WATE' A Mu 8E USED:
6) THE WELL MUST BE LOCATED BEIQW
by distances from section lines.
ft. from
North sec. line north or south)
600 East
ft. from sec. line east or west)
LOT BLOCK FILING a
SUBDIVISION
7) TRACT ON WHICH WELL WILL BE
LOCATED4 wner
BLM
No. of acres - Will this be the only well on this tract?
Yes
8) PROPOSED CASING PROGRAM
Plain Casing ( 22' Casing Overlap
in. from 418 ft. to 461D.— ft.
in. from 544 ft. to 607 ft.
Perforated casing
4 ' 544
in. from ft, to ft.
in, from ft. to .` t.
9) FOR REPLACEMENT WELLS givedistance and direction from old well and plans for plugging it:
Owner( s):
Bureau of Land Management
No. of acres:
T 44 N R 16 W Section 21 NEt - NEB
Legal description: ° °
11) DETAILED DESCRIPTION of the use of ground water: Household use and domestic wells must indicate type of disposal system to be used.
livestock watering and domestic uses
12) OTHER WATER RIGHTS used on this land, including wells. Give Registration and Water Court Case Numbers.
Type or right Used for ( purpose) Description of land on which used
None
13) THE APPLICAN S) ' STATE( S) THAT THE INFORMATION SET FORTH HEREON IS
TRUE TO THE BEST'- QF HIS ', A` LEDGE. /
SIGNATURE OF APPLICANTIS) PauT W. rrasniitsh,' Uttrtc
1Burl' u o La , 14anagement
Use additional sheets of paper if more space is required.-
6306 6293 ilE m 6fiP I)z' f ab o
6', 987 630] 4
BMA - - WATER RESOURCES
6300 _
8 STATE.• ENGINEER ;_ 6300 II _%
f, _ _ GDL0.
r 63/6
111, , 6313 ° c -"' aaa
V
16337 r:
411', 5'
E322 Dam ' p `` C11
63/ 9 Cil V WGI I-a5o, 600th 0-f 4)Te Na+h [ inf u k l and rc00 We[ sL, V- r Vle Na, sr, LTnc, C 1; 1 i ` Yke toF " Iq 0U, iq D 6e' Cb On 3L I 6303 =
T, 44U.) P. I( oO, 0 A) M.
4 TS:. ENGLdiE$ It- 17 f BM 16 . A 15 p aamb 83 a _ 6352 s
BM
V16
I 53 6410 2 T
I i Q
4215i
6 < p
VNg, Dam l and rc00 We[ sL, V- r Vle Na, sr, LTnc, C 1; 1 i ` Yke toF " Iq 0U, iq D 6e' Cb On 3L I 6303 =
T, 44U.) P. I( oO, 0 A) M.
4 TS:. ENGLdiE$ It- 17 f BM 16 . A 15 p aamb 83 a _ 6352 s
BM
V16
I 53 6410 2 T
I i Q
4215i
6 < p
VNg, CS CopY Available .
v P4plTMt , OP THE INTERIOR ` lac.
t-' ^• y, O..:r1 GCOLf =
AL SunvCY CLs t.f VL. D, e._ C / 1, w.. ee ounces amswn!'.
IZIsr01? D OF WELL WATER RESOURCtCCr 1 6 1W 7AToE • ENGIf1EE14 . S vv yOFyn n DOM WATER RESOURCES ( S ,C, roJ • /,... r
i. Name of wel!: ..
Y+' %/ Y iV _ SATE• ENGINEER
i. Name of site:
Site selected by " Lt- Date 19 iz
3. Ageney or owner:
BL"01 Address Sox 1264, COGd.
r, h{ SY °. ?` 4 r gaa„
4. Driller: 1 / - ALp ic.t'f_!,tJIS i' "
AddressfT_/T i >i7ce.:
5. Type of drilling rig used:
6. Date well started: , tJ00 • Y S 19 ' 71 Completed LA `/ 1 19 L
7. Topographic setting: ( In valley, on hill, etc.) NI91_=eY r
8. Altitude of land surface: 63 3 ft. Det. by ? _
9. Total depth: - ft. below 71--Land surface r Top of casing
10. Aquifers) and depths: ', 25.5 "'' /D J0 0141- 1)2A , 4fe5 5AI,,eC -E . C1-Z2 e .
450 i 1 &0 el /l.,L 5-„ rl 299 - 5-,o cvA S - „d , 5zo 1 - 20
11. Static water level: 9e -ZE,51A - ft. below Land surface Top of casting
12. Shut -In pressure: ( Flowing well) lO Py psi Det. by lex)/-5E0 Lw ' one 17 f ;; rye_•? g
13. Yield: 70 gpm after hrs. ® Pumping L Bailing L:] Flowing
14. Drowdown: Z-4 ft. after discharging at 70 au ^/ / X, Z 9 t) ft. after / Mi ”. discharging at C ` r / Tr. o
15. Quality of water: Color ZPOA/ 57AUJ Taste JL! / L''i T ^. -- r-
Odor _ ! lo /7e Hardness 7'1V iJAO/
16. Cosine.: Distance top E] above below land surface -
Type lCLL Diem.
rT 4 4. e ,"
14 b/ OD in. Wt. 8Ib I Depth ` t= 4' L^
Type Diem. 4 tz oD ' in. Wt. - d 1112 L Depth 41 t. to 1707 i
17. Perforations: Type L' /? r, fJG IrzGf q 5L, T' Size R t* . , 1 ^ ' l: . u + bpecir.g' nr4 PeuS 8, ton., 26 "c 50oCC Ge%uwn , 7e, 4, sl) epth 4 /(e0 R. to -spacing - -- Depth - -- it —ta —'— -- -•
18. PumpC ype 2:/ 17.` 1LE_ Capacity gpm Pownr / Et' 1 ft's'• C
19. Retard by:!.•, . D S- 5- ate
2C. Remark.:
Pk 74 C( , 2
Best Copy Available
II s
Kp EEiE V
7p 9 71K
CT 66 PPR7
AATER RRESp CCo d KK ° S ';;; 5 MMGM EER
O ° p a+ EEY 00.
C; e '- o 3 a t o e a ry dubJ cAIN , SS, U yy `
E
CC
o 1 ee s
O n ft" f u rV • rc 00.1
V
G
Q r n M, cz a
Best COPY Available l a
V
C
RE 0,. - 9V D
E
Q r ID
Caa FR R SOURC ES o a vT O 1
L d
Tom+
1 1 1 1 u S ti ic C c6.
C
E m .
t a r T
C C rl
C\ i fNNI R
NJ
n rl IN L\ ti i r a
Vi x .
I s 0 a
Z
Qn a
Cc N M '
T u_ O c.
J
S S V Y a
J
Best Conv
OC
Iz
C ^ V
O - E c° o ga a a n
M E C
VV •
O Y
I
V 9a S L
Y w
Y
Y
0 O
V
Oe rl
Y z I t.. l•:. C'; 1, Z'` L. t'?
S
United States Department of the Interior
RECEIVED
APR 19 1988
wAM xumm
VrAv nomm mm
BUREAU OF LAND MANAGEMENT
MONTROSE DISTRICT OFFICE
2465 SOUTH TOWNSEND
MONTROSE, COLORADO 81401
Mr. Mel A. Malley Colorado Division of Water Resources
Ground Water Wells
818 Centennial Building 1313 Sherman Street
Denver, Colorado 80203
Dear Mr. Malley:
PZ
IN REPLY REFER TO:
130)
P1? 18 1989
As per your conversation on April 14, 1988, with Nancy Lamm of our office, please find enclosed a statement of beneficial use of ground water completed for the Airstrip Well, permit number 150845, and for the Basin Well, permit number 150834. These statements of beneficial use are submitted to your office as the final step in the process of permitting these existing wells. If these statements are accepted by the State Engineer, we wish to request the return of the pink copy for our files.
We want to thank you for your time and assistance in the permitting of these wells. If you have any questions regarding the submitted forms, please feel free to contact Dennis Murphv or Nancy Lamm of this office at ( 303) 249 - 7791.
Sincerely, Alan L. Kesterke 7/ District Manager
Enclosures
ROrY RJMER
Governor
BOARD OF EXAMINERS OF WATER WELL CONSTRUCTION AND PUMP INSTALLATION CONTRACTORS
DIVISION OF WATER RESOURCES
1313 Sherman Street -Room 818
Denver, Colorado 80203
303) 866 -3581
March 30, 1988
Alan L. Kesterke, District Manager Bureau of Land Management Montrose District Office 2465 South Townsend Montrose, CO 81401
JERIS A DANIELSON
Secretary
RE: Exception to rules and regulations for well in the SW1 / 4 of the NW1 / 4 of
Section 25, Township 48 North, Range 17 West of the N. M. Principal Meridian, in Montrose County
Dear Mr. Kesterke:
Your March 28, 1988 request for an exception to Section 4( 3) of the rules and regulations for well construction for the above - referenced airstrip well, previously constructed and in use for livestock watering, has been reviewed.
The Board of Examiners of Water Well Construction and Pump Installation Contractors has granted your request to allow the well to be completed using
3. 5 - inch diameter casing which is compatable with your windmill pump connections pursuant to your March 28, 1988 request.
The Board is concerned with the fact that this well and several others in your District, former uranium exploration holes, were converted to water wells by unlicensed individuals. However, in light of the circumstances and the use of the wells being limited to livestock purposes, the Board waives the requirements of Section 3( 2) of their rules and regulations, requiring the work to be done by licensed contractors.
Sincerely, Bruce E. DeBrine, Acting Secretary Board of Examiners of Water Well
Construction and Pump Installation Contractors cc: Ground Water Section BED/ 11h
George Hier. Chairman, Castle Rock, Ken Rollin, Longmont, George Merncether_ Monte Vista, and Michael J. GuxYi, Denver
EW Of Mf United States Department of the Interior
A
BUREAU OF LAND MANAGEMENT
b " 3 "
MONTROSE DISTRICT OFFICE
2465 SOUTH TOWNSEND
MONIROSE, COLORADO 81401
RECEIVED
Ms. Melissa Long
OCT 1 C 1 °S9
Colorado Division of Water Resources MATER RMURC'LS Ground Water Division SM .ENGINEER 1313 Sherman Street am&
Denver, Colorado 80203
Dear Ms. Long:
INNS
IN
IN REPLY REFER TO:
7200 ( 130)
OCT 1 6 1989
We are submitting the attached information in response to a " Request for Correction or Additional Information on Statement of Beneficial Use" submitted to our office on September 22, 1989 for the Basin Well, permit # 150834 and the Airstrip Well, permit # 150845. We have completed a signed and notarized Statement of Beneficial Use of Ground Water" and a signed " Well Completion and
Pump Installation Report" for each well. We are providing this letter as some background information.
Airstrip Well, permit # 150845: As your records probably show, the Airstrip Well is a converted uranium test bore that was completed as a water well for livestock use only. The well was completed with 3Y,' PVC casing for which a waiver was given by your office on March 30, 1988. We have provided all of the information we have on file regarding well completion and pump testing. We regret the catch up nature of these submittals and will continue our efforts to bring these wells into compliance with state regulations.
Basin Well. permit # 150834: Again, we have provided the information we have on file concerning the well completion and pump installation. Our records show that the Basin Well was drilled by Donald D. Jennings of the Atlas Water Well Drilling Company in May of 1972. We are trying to locate Mr. Jennings and will request a submittal of the proper forms to your office, if we can locate him and if he has still maintained these records. In the meantime, please accept the enclosed information as the information we have on file.
Please note that we are signing the well completion statement as the land owner and not as the licensed drilling contractor. If you have any questions please feel free to call Dennis Murphy, District Hydrologist, at our office, ( 303)
249 - 7791.
Sincerely, Alan L. Kesterke
District Manager
Appendix A – TRFO Wildlife Protection Measures
Appendix A – BLM TRFO Wildlife Environmental Protection Measures Noxious Weeds
• Vehicles and heavy equipment are one of the primary agents for the spread of noxious weed seed to public lands. In eƯorts to mitigate the spread of weed seed to BLM lands the following actions are required for contractors prior to transport to a BLM project area.
The Contractor will be responsible for power-washing or comparable cleaning, to ensure that noxious weed seeds are removed from all equipment and vehicles used on the project prior to entering the project area. BLM will require a pre-implementation inspection to ensure compliance which would be arranged to occur before the equipment enters BLM lands. The Contractor is responsible for any additional transport or expenses associated with non-compliance.
Support vehicles (pickups, fuel/service vehicles, transports, dump trucks, etc.)
Pressure wash radiator to flush seeds.
Pressure wash undercarriage to remove accumulations of mud and soil that may contain seeds.
Heavy Equipment (dozers, road graders, excavators, backhoes, loaders, etc.)
Pressure wash radiator(s) to flush seeds.
Pressure wash tracks to remove accumulations of soil.
Pressure wash all areas of soil/debris accumulations (i.e. steps) Pressure wash blades and buckets where soil/mud is accumulated.
Empty pre-cleaners (air intake) before transport.
Fire Extinguisher and Tools on Equipment
• While in use, each internal combustion engine including tractors, trucks, dozers, hydro-axes, welders, generators, stationary engines, or comparable powered equipment shall be provided with at least the following:
1. One fire extinguisher, at least 5#ABC with an Underwriters Laboratory (UL) rating of 3A - 40BC, or greater. Extinguisher shall be mounted so as to be readily available for use (not locked in a tool box or chained to a seat, for example)
2. One shovel, sharp, size “O” or larger, round-pointed with an overall length of at least 48 inches.
3. One axe, sharp, double bit 3½#, or one sharp pulaski.
• It is prohibited to operate or use any internal or external combustion engine, on any timber, brush, or grass covered land, including trails traversing such land, without a spark arrester maintained in eƯective working order and meeting guidelines set forth in National Wildfire Coordinating Group Publication NFES 1363 and 2363.
CAMPING AND WORKSITE CONDITIONS
The contractor or his employees, upon documented permission from the CO/COR, may establish temporary work camps on public lands administered by the Bureau of Land Management. Camps shall be kept tidy and free of refuse. These camps may consist of mobile trailers, pickup campers, tent trailers, or tents. The contractor will be required to rehabilitate the camping area to the satisfaction of the CO/COR. Camps are subject to all fire restrictions placed by state, county or federal authorities.
Hazardous Materials
Use of Hazardous Materials and/or petroleum products requires that all appropriate State and Federal Regulations be complied with including, but not limited to, Material Safety Data Sheets (MSDS) on hand and use of necessary Personal Protective Clothing (PPE).
On-site disposal of Hazardous Materials or Waste including hydrocarbons is not authorized. On-site disposal will subject the contractor to at least the cost of reclamation and the appropriate disposal of contaminated soil.
Incidental (de minimus) leaks from fittings, gaskets or ruptured hoses will not subject the contractor to remedial requirements. They will be considered to be normal and unavoidable losses. Continual leaks will be noted on inspection reports and correction through maintenance required.
Maintenance and repair operations that require the draining of engines or hydraulic systems may be conducted on site only if the fluids are captured, containerized, and removed from public lands for proper disposal.
| TRFO Basin Well - Cover Sheet |
| General Requirements |
| Project Specific Requirements |
| 2 PROJECT SPECIFIC REQUIREMENTS |
| 2.1 SUMMARY OF WORK |
| 2.2 PROJECT LOCATION |
| 2.3 REFERENCE INFORMATION |
| 2.4 EXISTING ITEMS TO DEMOLISH |
| 2.5 GENERAL WORK REQUIREMENTS |
| 2.6 WATER WELL Investigation AND IMPROVEMENT |
| 2.7 WATER SYSTEM |
| 2.7.1 WATER SYSTEM DESIGN |
| 2.7.2 SOLAR POWER |
| 2.7.3 WELL AND PUMP |
| 2.7.4 STORAGE TANK |
| 2.7.5 DRINKING TANK |
| 2.7.6 MISCELLANEOUS WATER SYSTEM COMPONENTS |
| 2.8 PRICE AND PAYMENT |
| 2.8.1 DEMOLITION |
| 2.8.2 WATER WELL INVESTIGATION AND IMPROVEMENT |
| 2.8.3 WATER SYSTEM |
3 ADDITIONAL WORK REQUIREMENTS
| TRFO Basin Well DRAWINGS |
| TRFO Basin Well Supplemental Site Pictures |
| Existing Well Information |
| Appendix A - TRFO Wildlife Environmental Protection Measures |
| 02 site plan.pdf |
| Sheets and Views |
| 11X17 |
| 02 site plan.pdf |
| Sheets and Views |
| 11X17 |
| 03 FENCE.pdf |
| Sheets and Views |
| 11X17 |
File details come from the government source that posted it. Updated .