A04_RFQ_SOW_BPA_for_Fire_Alarm_Systems_DL.pdf
PDF 145 KB Posted
- Solicitation number
- 140FS225Q0085
About this file
This is a Blanket Purchase Agreement (BPA) for maintenance and monitoring of fire alarm systems at the Colorado Front Range National Wildlife Refuge Complex, specifically for the Rocky Mountain Arsenal National Wildlife Refuge in Commerce City, Colorado. The agreement covers three primary services: (1) critical 24/7/365 monitoring of fire alarm systems that will trigger emergency response agencies and designated refuge contacts, (2) annual fire alarm system inspections consistent with NFPA 25 Standards to ensure code compliance, and (3) general maintenance including unscheduled service calls.
The document details an extensive inventory of fire alarm systems across multiple buildings, including the Headquarters, Visitor Center, Communications Building, Maintenance Building, and Fire Building. The systems include control panels, indicators, heat/smoke/pull/dust detectors, and sprinkler system components. The contractor will be responsible for creating a comprehensive computer-based inventory of all fire alarm systems, conducting itemized testing during annual inspections, and providing quotes for any maintenance work prior to execution. Recent fire department connection services have been completed, with the next required 5-year services not due until April 2027 and October 2028 respectively.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Sol_140FS225Q0085_Amd_0002.pdf | ||
| A04_RFQ_Amended__SOW_BPA_for_Fire_Alarm_Systems_DL_0001.pdf | ||
| Sol_140FS225Q0085_Amd_0001.pdf | ||
| A04_Price_Sheet.xlsx | XLSX spreadsheet | |
| B03_Wage_Determination_2015-5419_REV_28_12232024.pdf | ||
| Sol_140FS225Q0085.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Blanket Purchase Agreement
Colorado Front Range National Wildlife Refuge Complex
Maintenance & Monitoring of Fire Alarm Systems
Refuge Locations where services are required:
1. Rocky Mountain Arsenal NWR; 6550 Gateway Road, Headquarters, Commerce City, CO 80022.
Please see below for listing of all alarms.
U.S. Fish and Wildlife Service Rocky Mountain Arsenal NWR 6550 Gateway Road, Headquarters Commerce City, CO 80022 303-289-0232
Scope of Agreement:
The intent of this agreement is to obtain three services: (1) critical monitoring of systems in the event of a fire; (2) required inspection and testing of fire alarm systems; and (3) general maintenance of fire alarm systems at the wildlife refuges of the Colorado Front Range Complex.
The Contractor is responsible for all equipment, materials, supplies, transportation and personnel necessary to meet or exceed the agreement specifications.
Critical Monitoring: The fire alarm systems of all buildings are required to be monitored 24 hours a day, seven days a week, and year-round. Monitoring will trigger emergency response agencies (South Adams County Fire Department and Adams County Dispatch) and designated contacts at the wildlife refuge.
Annual inspections: To meet local fire requirements, all fire alarm systems must be inspected and tested annually. The annual inspection will be completed consistent with NFPA 25 Standards and ensure all systems are code compliant and operate as designed. Annual inspection reports will be transmitted to the wildlife refuge and to South Adams County Fire Department.
Maintenance: Maintenance is generally associated with inspections but may also include unscheduled service calls. The Contractor will provide a quote for all maintenance work including the cost of materials and labor to repair the issue to USFWS Staff prior to any work be done.
Contractor shall use a computer system to create an inventory of all buildings and fire alarm systems (device type, location, model, quantities, installation date, etc). Annual inspections will include itemized testing of all required equipment and note any failures.
Colorado Front Range NWR Complex Fire Alarm Systems
Headquarters Quantity 6600 Gateway Road Control Panel 1 Commerce City, CO 80022 Indicators 3 (last inspection = 1/2/25] Initiating (Heat Detector) 5 Initiating (Pull Station) 6 Initiating (Smoke Detector) 27 Visitor Center 6550 Gateway Road Control Panel 1 Commerce City, CO 80022 Indicators 2 (last inspection = 1/2/25] Initiating (Heat Detector) 2 Initiating (Pull Station) 9 Initiating (Smoke Detector) 7 Initiating (Dust Detector) 2 Communications Bldg 7220 Lansing Street Control Panel 1 Commerce City, CO 80022 Indicators 3 (last inspection = 10/15/24) Initiating (Head Detector) 15 Initiating (Pull Station) 3 Initiating (Smoke Detector) 7 Maintenance Building 11125 E 73rd Place Control Panel 1 Commerce City, CO 80022 Indicators 5 (last inspection = 10/15/24) Initiating (Heat Detector) 4 Initiating (Pull Station) 3 Initiating (Smoke Detector) 0 Fire Building 11125 E 73rd Place Control Panel 0 (in Mtce Bldg) Commerce City, CO 80022 Indicators 5 (last inspection = 10/15/24) Initiating (Heat Detector) 0 Initiating (Pull Station) 2 Initiating (Smoke Detector) 0
Sprinkler System Visitor Center 6550 Gateway Road Waterflow Switch 1 Commerce City, CO 80022 Drain 1 (last inspection = 1/2/25) Gauge 2 Sprinkler Box 3
Control Valve 4 Fire Department Connection* 1 Maintenance Bldg 11125 E 73rd Place Waterflow Switch 1 Commerce City, CO 80022 Drain 1 (last inspection = 10/15/24) Gauge 2 Sprinkler Box 4 Control Valve 2 Fire Department Connection** 1 Fire Bldg 11125 E 73rd Place Waterflow Switch 1 Commerce City, CO 80022 Drain 1 (last inspection = 10/15/24) Gauge 2 Sprinkler Box 4 Control Valve 2 Fire Department Connection** 1 *Required 5-year service for the fire department connection was completed on 4/3/23 and will not be due until April 2027.
** required 5-year service for the fire department connection was completed on 10/15/24 and will not be due until October 2028.
File details come from the government source that posted it. Updated .