A0002 Att 3 MP101 REV 2.pdf

PDF 605 KB Posted

Attached to
Z2DA--Proj. # 502-16-104 Replace HVAC System in Bldg. 2 Federal contract opportunity
Solicitation number
Amendment0002
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 16

About this file

This document is an amendment to a solicitation for replacing the HVAC system in Building 2 at a Veterans Affairs medical center. The amendment provides additional instructions to offerors, including that no further questions will be accepted and no extensions granted, with proposals due by August 21, 2020 at 3:30 PM Central Time. A brand name justification is also attached. Offerors are responsible for obtaining all amendments and following submittal instructions. The Department of Veterans Affairs Veterans Health Administration is the contracting agency for replacing the HVAC system located at 2495 Shreveport Highway in Pineville, Louisiana under project number 502-16-10417-108.

View the file

Other files for this federal contract opportunity

Other files attached to Z2DA--Proj. # 502-16-104 Replace HVAC System in Bldg. 2, newest first.
File Type Posted
A0002 Att 1 M 601 REV 2.pdf PDF
A0002 Att 6 JA.pdf PDF
36C25620R0079 0002.docx DOCX document
A0002 Att 4 RFI Register.docx DOCX document
A0002 Att 2 MH104 REV 2.pdf PDF
A0002 Att 5 Sign in Sheet.pdf PDF

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

17'-10" 12'-9" 9'-0" 12'-9" 18'-6" 18'-6" 18'-3" 10'-6" 1'-2" 14'-9" 10'-8" 18'-4" 18'-3" 18'-3" 12'-7" 9'-3" 12'-8" 17'-9"

I RQP0NMLKJI.1HGFEDCBA

3.7

7.5

3.8

6.2

4.5

2.8

3.7

7.5

3.8

6.2

4.5

2.8

2-CP-2

(EX) HX 2-1

(EX) HWP 2-7

(EX) HWP 2-8

(EX) HX 2-2

2-ST-2 2-ST-1

3" PCR

P C

R

3" PCR

4" PCR

2" LPR

EX. 2 1/2" SVR

EX. 3" HPR

2" LPR

2" LPR

2" PCR

2" PCR

2" PCR

2" PCR

2-ST-42-ST-3

2-ST-5

2 1/2" MPR

4" PCR

4" PCR

2-CP-1

(EX) CWP 2-5

(EX) CWP 2-2

(EX) CWP 2-1

(EX) CHP 2-6

(EX) CHP 2-4

(EX) CHP 2-3

6" PCR

4" PCR

4" PCR

6" CHS

6" CHS

6" CHS

2-CWP-2

2-CWP-1

(EX) 2-CWP-4

(EX) 2-CWP-3

4" CHS

4" CHS

4" CHS

(EX) ET-1

(EX) ET-2

(EX) ET-3

(EX) ET-4

(EX) HWP2-10

(EX) HWP 2-9

CP-EX

EX. 4" LPS

3" HPS

6" HPS

1" HPS

4'' CHS/R UP

3 1/2'' CHS/R UP

EX. 4'' HWS/R UP

EX. 4'' CHS/R UP

EX. 3'' HWS/R UP

EX. 2 1/2'' CHS/R UP

EX. 2 1/2" SVR

EX. 4" HPR

EX. 8" CHR

EX. 8" CHS

EX. 6" HPS

EX. 2 1/2" SVR

EX. 4" HPR

EX. 8" CHR

EX. 6" HPS

EX. 8" CHS

E X

C H

R

E X

C H

S

E X

H P

S

E X

H W

S

E X

H W

R

EX. 4" HPS

E X

H P

S

6" CHS

6" CHS07 08

(TYP) (TYP)

EX. 4" HPS

EXIST. STEAM

SUPPLY TO

CONDENSATE

PUMP PACKAGE

P C

R

P H

A S

E

S

E E

S H

E E

T G

C

P H

A S

E

S

E E

S H

E E

T G

C

6" CHS

2-AS-1

6"

6"

C H

S

2-CF-1

3/4"

6" BUTTERFLY

VALVE W/

BLIND

FLANGE

2-AS-2

6" BUTTERFLY

VALVE W/

BLIND

FLANGE

6" CHS 6"

6" CHS

3/4"

2-CF-2

EX. 6" V

8" V

6" V

6" V

6" V 6" V

6" V

6" V

3/4"

MAIN STEAM LINE TO BOILER PLANT.

E X

D E

X

D

EX. 2" D

E X

D

EX. 2" D

1 1/4" LPR

2" HPS

4" HPR

EX. 4" HPR

EX. 2 1/2" MPR

2" HPS

1 1/4" LPR

1" HPR

1 1/4" LPR

2" HPS

1" HPR

1" HPR

1" HPR

1" HPR

1" HPR

1" HPR

10x8 NEW DUCT (INSIDE

DIMENSIONS: WIDTH X DEPTH)

EXISTING DUCT TO REMAIN

EXISTING DUCT TO BE

DEMOLISHED

LINE TYPE LEGEND

NEW PIPING

EXISTING PIPING TO REMAIN

EXISTING PIPING TO BE DEMOLISHED

NEW RECTANGULAR FRP BASIN

CONDENSATE PIPE

PUMPED CONDENSATE

DISCHARGE

4" CONCRETE BASE

PRESSURE POWERED STEAM

CONDENSATE PUMP PACKAGE.

UNIT LENGTH IS APPROXIMATELY

78 INCHES FOR TRIPLEX UNIT AND

100 INCHES FOR QUADRIPLEX UNIT.

3 FEET MIN FOR MAINTENANCE

I N

C H

E S

M A

X

IM

U M

F

E E

T D

E E

P

38 INCHES UNIT WIDTH

BASIS OF BASIN DESIGN

IS ORENCO COMPOSITES

(OR EQUAL).

DIRT CRAWLSPACE

FLOOR (FIELD VERIFY

CRAWLSPACE FLOOR

COMPOSITION).

01 PROVIDE NEW STEAM PUMP TRAP, SUPPORTS, AND

INSULATION COMPLETE.

02 PROVIDE NEW CONDENSATE PUMP, SUPPORTS, AND

INSULATION COMPLETE. DIG OUT AREA IN BASEMENT

"FLOOR" (CONSISTING OF DIRT AND CONCRETE).

REFER TO DETAIL 2/MP101.

03 PROVIDE NEW CHILLED WATER PUMP, SUPPORTS,

AND INSULATION COMPLETE.

04 PROVIDE CHILLED WATER PIPING, HANGERS, AND

INSULATION COMPLETE.

05 PROVIDE SHUTOFF VALVE. PREPARE FOR

CONNECTION TO CHILLED WATER DISTRIBUTION

SYSTEM.

06 PROVIDE PUMPED CONDENSATE PIPING, HANGERS,

AND INSULATION COMPLETE.

07 NEW SIEMENS DDC PROGRAMMABLE CONTROLLER

FOR 2-CWP-1 AND 2-CWP-2. FULLY INTEGRATE WITH

CAMPUS-WIDE SIEMENS DDC SYSTEM.

08 NEW SIEMENS DDC PROGRAMMABLE CONTROLLER

FOR 2-CWP-3 AND 2-CWP-4. FULLY INTEGRATE WITH

CAMPUS-WIDE SIEMENS DDC SYSTEM.

09 VFD FOR PUMP, INSTALLED ON UNISTRUT (PROVIDED

BY DIVISION 23, INSTALLED BY DIVISION 26).

10 EXISTING PRESSURE REDUCING STATION. INSTALL

NEW GATE VALVES, TRAPS AND DRIP LEG AS

INDICATED BY DETAIL 1 ON SHEET M-502.

11 INSTALL NEW BUTTERFLY VALVE IN EXISTING

CHILLED WATER PIPING.

12 INSTALL NEW GATE VALVE IN EXISTING STEAM AND

STEAM CONDENSATE PIPING. AFTER SHUTOFF

VALVES ON STEAM SUPPLY PIPES, PROVIDE A STEAM

CONDENSATE TRAP.

13 CONNECT TO CONDENSATE INLET OF CONDENSATE

RECEIVER IN EXISTING CONDENSATE PUMP

PACKAGE.

14 CONNECT TO EXISTING CONDENSATE PUMP

PACKAGE DISCHARGE CONNECTION.

15 CONNECT TO EXSITING STEAM CONDENSATE LINE

PENETRATING OUTER WALL.

16 ROUTE STEAM RECIEVER VENT PIPING TO EXISTING

12" STEAM VENT PIPE GOING TO ROOF.

17 GLOBE VALVE.

18 FILL (PRESSURE REGULATING) VALVE.

19 BALL VALVE (TYPICAL 2).

20 3/4" BACKFLOW PREVENTER FOR CONNECTION TO

DOMESTIC WATER. BACKFLOW PREVENTER SHALL

CONFORM TO NSF 61 AND NSF 372.

21 EXTEND TO CONNECT TO NEAREST 3/4" OR LARGER

DOMESTIC COLD WATER LINE, CONFIRM LOCATION IN

FIELD. ALL MATERIALS FROM DOMESTIC COLD

WATER LINE TO BACKFLOW PREVENTER SHALL BE

LEAD FREE.

22 AT EACH PAIR OF HEAT EXCHANGERS AND HOT

WATER PUMPS, REMOVE ALL GATE AND GLOBE

VALVES ASSOCIATED WITH STEAM, STEAM

CONDENSATE AND HOT WATER. REPLACE WITH THE

FOLLOWING: (9) 2" GATE VALVES, (3) 2" GLOBE

VALVES, (11) 3" GATE VALVES FOR STEAM AND STEAM

CONDENSATE; AND (10) 4" BUTTERFLY VALVES FOR

HOT WATER. CONFIRM QUANTITIES, LOCATIONS AND

SIZES OF EXISTING VALVES IN FIELD.

23 HIGH PRESSURE STEAM AND LOW PRESSURE

CONDENSATE UP TO ROOF. SEE MH105 FOR

CONTINUATION.

Scale: 1/8" = 1'-0"

BASEMENT PHASE 1 PIPING PLAN 0 4 8 16

N O

R

TH

TRUE

## KEY NOTES:

Revisions: Date

Drawing Title

Approved: Project Director

Project Title

Location

VA PROJECT NUMBER

Building Number

Drawing Number

Dwg of

VA FORM 08-6231

Office of Construction and Facilities Management

CONSULTANTS: PROJECT MANAGER

SHEET NOTES:

Date Checked Drawn

ACG Project Number

Headquarters:

Apogee Consulting Group, P.A.

1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.

WALL RATING LEGEND

1 HR - FIRE SEPARATION

2 HR - FIRE SEPARATION

SMOKE RESISTIVE HAZARDOUS AREA

N

KEY PLAN

SCALE: NO SCALE

BUILDING 2

TRUE

SCOPE OF WORK

FULLY SPRINKLERED

100% CONSTRUCTION

DOCUMENTS

S S S S

/3

/2

:1

:5

A

M

MP101

BASEMENT MECHANICAL PIPING PLAN

PHASE 1

12 21

TAMEKA J. TAYLOR

SWR

REPLACE HVAC SYSTEM

2495 SHREVEPORT HWY. PINEVILLE,

LA 71360

1-9-2020

502-16-10417-108

PLH

A CHILLED WATER SYSTEM TO BE PROVIDED

IN PHASE 1 SHALL BE INTEGRATED INTO

THE CHILLED WATER LOOP IN PHASE 2.

PREPARE CONNECTIONS IN PHASE 1 FOR

SWITCHOVER WHEN PHASE 2 BASEMENT

DEMOLITON TAKES PLACE.

B BASEMENT PHASE 1 AND PHASE 2 DOES

NOT RELATE TO THE GENERAL PHASING

PLAN. THE PHASES SHOWN ON MD101,

MD102, MP101, AND MP102 ARE TO PHASE

THE WORK OF THE BASEMENT

INDEPENDENTLY.

C COORDINATE SHUTDOWN OF CHILLED

WATER SYSTEM WITH ARCHITECTURAL

PHASES.

D REMOVE ALL INSULATION ON EXISTING

PIPING TO REMAIN IN BASEMENT AND

REPLACE WITH NEW INSULATION. THIS

INCLUDES CHILLED WATER, HEATING HOT

WATER, STEAM AND STEAM CONDENSATE

PIPING. FIELD VERIFY SIZES OF EXISTING

PIPING.

E DRAIN, REFILL AND PRESSURE TEST

CHILLED WATER PIPING SYSTEM.

STEAM RELIEF

VENT (TYP.)

2 PRE - BID RFI RESPONSES 7/31/2020

Scale: N.T.S.

NEW TRENCH AND BASIN FOR CONDENSATE PUMP PACKAGE DETAIL