This document is an appendix package containing reference materials, forms, and standards for a maintenance contract supporting five Defense Commissary Agency (DeCA) facilities in Italy: Aviano, Vicenza, Livorno, Naples, and Sigonella.
The appendices provide operational guidance including: a comprehensive list of equipment and building systems that may require repair across 150+ item codes organized by category (alarm systems, building infrastructure, refrigeration, electrical, mechanical, kitchen equipment, and material handling); emergency repair authorization procedures with specific criteria for refrigeration, HVAC, doors, electrical, roof, plumbing, and equipment failures; preventive maintenance scheduling requirements with inventory tracking templates; refrigerant use logging protocols; contractor work verification procedures; DeCA temperature quality standards for display cases, reach-in storage, and walk-in rooms; detailed lighting illumination standards by room type (50-100 footcandles for sales areas, 30 footcandles for storage); reporting data requirements for invoicing and work orders; and examples of preventive maintenance checks for evaporators, compressor units, and condensers. The materials establish standardized inventory tagging with blue background/white lettering, data entry formatting specifications, and facility-specific short codes (AVI, VIC, LIV, NAP, SIG). Object Class Codes 2512, 2516, and 2521 categorize items for maintenance tracking purposes. Documentation emphasizes compliance with host nation standards, original equipment manufacturer specifications, and emergency response protocols with EUR 3,000 threshold for Contracting Officer involvement.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Internal Store
Number
CONTRACT
AREA
LOCATION
COMMERCIAL ADDRESS
SHORT
CODE
HQCE5W MED-ZONE ITALY AVIANO COMMISSARY
BLDG 1411, AVIANO AB
33081 AVIANO ITALY
AVI
HQCE5Q MED ZONE ITALY VICENZA COMMISSARY
BLDG 2204 CASERMA EDERLE
36100 VICENZA ITALY
VIC
HQCE5J MED ZONE ITALY LIVORNO COMMISSARY
BLDG 56018 CAMP DARBY
56018 TIRRENIA PISA ITALY
LIV
HQCE5X MED-ZONE ITALY NAPLES COMMISSARY
BLDG 2957 US NAVAL SUPPORT SITE
81030 GRICIGNANO D’AVERSA CASERTA ITALY
NAP
HQCE5V MED-ZONE ITALY SIGONELLA COMMISSARY
US NAVAL AIR STATION NAS1
95040 SIGONELLA CATANIA ITALY SIG
APPENDIX 1 FACILITIES LISTING
APPENDIX 2
LIST OF ITEMS THAT MAY REQUIRE REPAIR
ITEM DESCRIPTION OBJECT
CLASS CODE (OCC)
AA Alarm System, Fire with Tableau 2516 AB Alarm System, Intrusion (IDS) Central 2516 AC Alarm System, Refrigeration Monitoring System (RMCS) 2512 AD Local Intrusion Alarm (IDS) (door alarm) 2516
ADR Administrative and Reporting Costs (Program Management) per PWS, including SOMS;
does not include INV costs
AE Personnel Safety Alarm, Restrooms 2516 AF Building / Facility Management System (BMS/FMS) 2512 AG Personnel Safety Alarm, Cold Rooms (per room) 2512 BA Ceilings 2516 BB Eyewash Station 2516 BC Flooring 2516 BD Gates and Fences 2516 BE Gutters and Downspouts 2516 BF Plumbing and Fixtures 2516 BG Roofing (repair of existing) 2516 BH Warehouse Shelving 2521
BI Walls 2516 BJ Doors and Windows 2516 BK Green Roof 2516 BL Skylights 2516 BM SMP Materials 2516 BN Décor and Signs (only Design Criteria standard signs, not mandatory or regulatory) 2516
BO Structual (Repair of existing, inspections and reports as needed) 2516 BP Exterior (Canopies, Columns, Building Walls, sidewalks, parking lot) (CONUS, OFF SITE
LOCATIONS ONLY)
CA Band Saw, Meat (CMPP and CONUS only) 2521 CB Bone Duster (CMPP and CONUS only) 2521 CC Fat Analyser (CMPP and CONUS only) 2521 CD Forming Machine (CMPP and CONUS only) 2521 CE Grinder, Meat (CMPP and CONUS only) 2521 CF Knife Sharpener, Electric 2521 CG Labeler, Tiro and Similar (CMPP and CONUS only) 2521 CH Molder, Meat (CMPP and CONUS only) 2521 CI Packing Machine (CMPP and CONUS only) 2521 CK Rotary Table (CMPP and CONUS only) 2521 CL Sanitizing Machine (CMPP and CONUS only) 2521 CM Tenderizer, Meat (CMPP and CONUS only) 2521 CN Vacuum Packing Machine (CMPP and CONUS only) 2521 CO Vacuum Station System, Centralized (CMPP and CONUS only) 2521 CP Grease/Oil Separators and Sludge Traps (CMPP + KCS) 2516 CQ Slicer, Meat (CMPP and CONUS only) 2521 CR Converger (CMPP and CONUS only) 2521 CS Meat Tumbler (CMPP and CONUS only) 2521 CT Box Maker (CMPP and CONUS only) 2521 CU Hydraulic Meat Lift (CMPP and CONUS only) 2521 CV Generator, Diesel (more than 50kW) (KCS, CMPP & CDG) 2521 CV Generator, Diesel (more than 50kW) (KCS, CMPP & CDG), Monthly (11 each) 2521 CW Packing Machine (purchased after 2012) (CMPP and CONUS only) 2521 CW Packing Machine (purchased after 2012) (CMPP and CONUS only), monthly (11 each) 2521
APPENDIX 2 - List of Items Than May Require Repair
ITEM DESCRIPTION OBJECT
CLASS CODE (OCC)
CX X Ray System, Food Processing (CMPP and CONUS only) 2521 DA Doors, Automatic Entrance and Exit 2521 DB Doors, Motor Driven & Manual (Warehouse, Sectional, Rollup or Sliding) 2521 DC Bumper Doors (Impact Doors) 2516 EA Electrical System 2516 EB Electronic Key Box 2521 EC Emergency Lighting, Central with Battery Control NOT Exit lights 2516 ED Emergency Lighting, Individual (battery operated) NOT Exit Lights 2521 EF Distribution Panel, Electrical 2516 EH Insect Light, UV 2521 EI Photovoltaic System 2521 EJ Lightning Arrestor 2516 EK Exit Light (total per store) 2516
EL Fixed Wire Testing (Regulatory requirement, 4 year interval) 2516 FA Fire Control Ventilation System 2516 FB Fire Extinguishers (portable & wheeled, DeCA owned only) 2516 FC Fire Protection and Flue Flap 2516
FD Fire Protection Door (only those connected to Fire Alarm System) 2516 FE Smoke Detector (NOT connected to Fire Alarm System 2521
FF Sprinkler System (Annual) 2516 FG Sprinkler System (monthly PMI) 2516 FH Wall Hydrant (each) 2516 FI Exhaust Hood with extingushers (Ansul & similar), includes cleaning 2516 FJ Smoke Extractor (each) 2516 FK Fire Rated Door (NOT connected to Fire Alarm System) 2516 GA Auto Door Armored (stores after 2007) 2521 GB Fire Alarm System (stores after 2007) 2516 GC Truck Retaining System, Hydraulic (Auto Chock Blocks) with interlock to door or dock leveler
GD Heating Distribution System (pumps & piping, includes radiators) (stores after 2007) 2512
GE Ventilation System (stores after 2007) 2512 GF Air Conditioning System (stores after 2007) 2512 GG Automatic Window Blinds (sensor controlled) 2516 HA Air Curtain 2512 HB Boiler Plant 2512 HC Boiler, Steam 2512 HD Heating Distribution System (pumps & piping, includes radiators) 2512 HE Oil or Natural Gas Burner 2512 HF Warm Air Blower 2512 HG Ventilation System (without heating or cooling coil), Exhaust Fans 2512 HH Air Conditioning System 2512 HI Split Unit Air Conditioning (includes indoor & outdoor unit) 2512 HJ Chimney 2516 HK Neutralizing System, Condensate (for chimney) 2521 HL Multisplit Unit Air Conditioning with up to 4 inside units (includes indoor & outdoor units) 2512
INV Inventory and Labelling Updates per PWS, not initial 100% 2516 LA Lighting, Outside 2521 LB Lighting, Sales Area 2521 LC Lighting, Warehouse 2521 LD Lighting, Interior (offices, bathrooms & technical rooms) 2521
ITEM DESCRIPTION OBJECT
CLASS CODE (OCC)
LE Lighting, Centrally Controlled (DALI, KNX, etc.) 2521 MA Charger, Battery 2521 MB Forklift 2521 MC Handicap Cart 2521 MD Hydraulic Elevating Platform (Dock Leveler/Loading Ramp) 2521 ME Pallet Jack, Electric 2521 MG Ramp, Mobile Loading 2521 MH Spinwrapper (CMPP, CDG & CDK only) 2521 MI Mobile Work Platform (Scissors lift & similar) 2521 MJ Pallet Jack, Manual (PM only) 2521 MK Pallet Jack, High Lift Electric 2521 ML Ladders, All 2521
MM Water Distilling System (forklift charging area) 2516 MN Platform Cart, Hydraulic (up to 300kg capacity) 2521 MO Mobile Personnel Lift 2521 OA Oven, Baking and Roasting 2521 OB Oven, Pizza 2521 OC Oven, Proofer 2521 OD Oven, Convection Countertop 2521 OE Oven, Convection Upright 2521 OF Oven, Baking Roll in 2521 OG Oven, Proofer Roll in 2521 RA Compound System with Compressors 2512 RB Condensing Unit 2512 RC Condenser (Fan Unit) < 2 sqm 2512 RD Display Case including Evaporator 2512 RE Display, Self Contained (Stand Alone Display) 2512 RF Refrigerated Trailer 2512 RG Retarder, Bakery (refrigerated) 2512 RH Walk-in including Evaporator, Chill (without Condensing Unit) 2512 RI Bakery Cabinet, Self Service 2521 RJ Misting or Fogging System (Produce) 2521 RK Ethylene Gas Filter (Produce) 2521 RL Compound System withCompressors, CO2 2512 RM Condenser (Fan Unit) > 2 sqm 2512 RN Walk-in including Evaporator, Freeze (without Condensing Unit) 2512 RO Refrigeration Leak Detection System 2512 RP Walk-in Doors, Insulated (slide or swing CONUS ONLY) 2512 SA Baler 2521 SC Cabinet, Food Warming 2521 SE Compressor, Air 2521 SF Conveyor Belt 2521 SG Cranes, Hoists and Elevator Systems 2521 SH Dispensers, Various 2521 SI Exhaust Hood with ventilation fan 2521 SJ Generator, Diesel 2521 SK Grill, Rotary Electric (Rotisserie) 2521 SM High Pressure Cleaner 2521 SN Ice Maker 2521 SO Intercom and Paging Systems (PA) 2521 SP Polisher, Floor or Burnisher 2521 SQ Safe 2521 SR Scale and Scale Labeler 2521 SS Scrubbing Machine 2521 ST Panini Grill 2521 SU Slicer (Bread, Deli, Bistro) 2521
ITEM DESCRIPTION OBJECT
CLASS CODE (OCC)
SV Sweeper, Warehouse 2521 SW Video Monitoring System (Security Cameras & CCTV) 2521 SX Water Heater, Electric 2521 SY Water Treatment System (building water supply) 2516 SZ IBM Register scale (annual calibration only) 2521 TA Kitchen Unit (including Appliances) 2521 TB Sales Area Shelving 2521 TC Locking System, Doors (with master key and security card) 2521 TD Disposal, Hazardous Waste and Accountable Equipment (requires DeCAF 40-108) 2516
TE Grease/Oil and Gas Separators and Sludge Traps 2516 TF Industrial Kitchen Equipment (Mixers etc., not fixed installation) 2521 TG Industrial Electrical Tools 2521 TH Labeler (without scale) 2521 TI Office Equipment (non electric) 2516 TJ Industrial Washer or Dryer 2521
TK
Electrical Isolation Test (also Electrical Resistance test, mobile government owned electrical devices only, no IT equipment, IAW Host Nation requirements, i.e. DGUV) 2521
TL Battery Backup System (UPS) (fixed installation) 2521 TM Loading Area Surfaces (sole DeCA use locations only) 2516 TO Facility Walk Through (visual inspection) (record & report to store staff) 2516 TP Electronic Hand Dryer (Airblade & similar) 2521 TQ Automatic Pressure Regulator 2521 TR Storage Container, Metal (shipping & similar, not storage sheds) 2521 TS Transportation, Oversized Items (only as authorized by HQ's staff) 2521 TT Scale, Pallet (larger than 30lbs capacity, less than 3000lbs) 2521 TU Scanner, 3D (for shipping operations) 2521 TV Heat Reclaim System 2512 TW Fall Protection System (located on roof) 2516 TX Vehicle Scale (for shipping operations) 2521 TY Water Heater, Natural Gas 2521 TZ Water Heater, High Pressure Steam 2521 UA Lobster Tank (CONUS ONLY) 2521 UB CEIP Installs (Used for new equipment installs where DeCA Equipment Branch has purchased via separate contract)
ZZ Diagnostic Center for Remote Monitoring & Alarms (only if no centralized monitoring contract is in place)
APPENDIX 4
EMERGENCY REPAIR AUTHORIZATION PROCEDURE AND
RESTRICTED PROTOCOL PROCEDURES
Criteria for Emergency Work Orders The situations/criteria identified in this document are considered to be emergencies. If a situation not included in the document arises at the store and the store firmly believes their situation meets the emergency criteria (potential for loss of perishable goods and potential harm to personnel or customers) then the store management needs to contact the respective store Field Engineer/Field Operations Specialist immediately. The Field Engineer/Field Operations Specialist will determine if an emergency work order needs to be opened.
PROCEDURE FOR EMERGENCY REPAIR AUTHORIZATION STEPS
1. Authorized Government personnel generates Emergency Order (SOMS) for only situations covered below.
2. KO will be involved if the quote exceeds EUR3,000.00
3. On-site personnel make initial contractor contact.
4. Authorized Government personnel provides KO/COR with the following information:
What needs repair? DECA INVENTORY NUMBER Status of the associated backup system(s) and mission priority.
Estimated total cost and schedule to repair to determine the approval authority.
5. Contractor performs diagnostic and develops estimated cost (Within 3 hours).
6. Contractor (by SOMS or e-mail) sends work order quote to KO, Field Engineer/Field
Operations Specialist
7. KO/COR review and approve work in writing (SOMS or e-mail).
8. Contractor completes the repair or mitigation.
Refrigeration Emergency Examples:
a. PHASE LOSS Power Failure
b. HIGH SUCT Equipment/Compressor Failure
c. LOST BOARDS, RELAYS or SENSORS
d. COMM FAIL Communication Failure within 4k/5k network.
e. Any noisy refrigeration fan
f. Any refrigeration leak
APPENDIX 4
EMERGENCY REPAIR AUTHORIZATION PROCEDURE AND
RESTRICTED PROTOCOL PROCEDURES
Note: Any call for repairs to any self-contained merchandiser cases must be placed only during normal work hours.
Heating Ventilation Air Conditioning
1. Air Conditioning failure in any area of the store
2. Any heating issue in the store
3. Any exhaust fan system failure.
Door
1. Any problem with exterior doors to include exterior sliding doors that compromises security, safety or customer access to the building.
2. Loading dock door not properly operating.
3. If a dock leveler malfunctions in a position that prevents the overhead door from closing and securing the building.
4. Inoperable Refrigerated walk-in cooler doors
Electrical
1. Loss of power in any area of the store.
Roof
1. Roof leaks in the administrative area, sales area, warehouse and deli bakery area.
Plumbing
1. Bathroom toilet, lavatories or sinks overflowing onto the floor
2. Store drains clogged up/backed up.
3. Hot water not available anywhere in the facility.
4. Any major water leaks (pipe breaks or major running water)
5. Any frozen water pipe situation or pipe or hose bib breakage
Alarms
1. Any fire alarm going off or findings by the Fire Chief (if covered by the Enterprise contract)
2. Any security alarm going off (if covered by the Enterprise contract)
Equipment
1. Ovens and Proofers –any fault that prevents operation
2. Central Meat Processing Plant processing Equipment (where applicable)
APPENDIX # 5-1
INVENTORY LIST AND PREVENTIVE MAINTENANCE SCHEDULE
(Example Form)
SHORT
CODE
INVENTORY
NUMBER
ITEM
CODE
OBJECT CLASS
CODE EQUIPMENT TYPE
MANUFACTURER
NAME MODEL # SERIAL #
YEAR
PURCHASED DeCA BARCODE
SUBLOCATION
(Physical)
PM
INTERVAL
CALENDAR WEEK(S) PM
SCHEDULED
BUD 123456 XZ 1234 Handicap Cart Sterling ZZ-000 1234567 1998 DE0000000 Warehouse 4 1.14.32.48
Instructions For Maintenance Contract Inventory Completion
Text 3 digits
Number 6 digits
Text 2 digits
Number 4 digits
Text Matches Item Code
List
Text
Text Exactly as on
Data Plate
Text Exactly as on
Data Plate
Date YYYY format
Text Exactly as on
Label
Text
Text 1 digit
Number each 2 digits.
By multiple separate with a comma
Correct cell formatting and required length. All formatting done using English (US) in data processing programs
APPENDIX #5-2
Detailed Instructions for Completing Consolidated Maintenance Contract Inventory
COLUMN INSTRUCTIONS FORMAT &
LENGTH
Short Code When printed on label, no space or dash shall be placed between this and the following 6 digit Inventory Number
Text, 3 letters, Uppercase
Inventory Number When printed on label, no space or dash shall be placed between this and the preceding 3 letter Short Code
Number, 6 digits
Item Code See details at right Text, 2 letters, Uppercase
Object Class Code See details at right Number, 4 digits
Equipment Type Use description from Item Code list. Normally this is Attachment #2 Text, length as needed
Manufacturer Name Enter exactly as on data plate to include spaces, slashes and similar Text, length as needed
Model Number Enter exactly as on data plate to include spaces, slashes and similar Text, length as needed
Serial Number Enter exactly as on data plate to include spaces, slashes and similar Text, length as needed
Year Purchased See details at right Date, 4 digits, YYYY
DeCA Barcode Purple & white or White tag with barcode on it. For ease of entry recommend use of a handheld scanner
Text, 2 letters & 7 digits
Sub Location (Physical)
Enter the actual location at the facility. For installed refrigerated units enter the case Position number or CAN bus address. Mobile items will need to be updated at regular intervals
Text, length as needed
PM Interval See details at right Text, 1 letter, Uppercase
Calendar Weeks PM Scheduled
When multiple are needed based on PM Interval then enter with a comma between each
Number, 2 digit
Appendix #5-2
Detailed Instructions for Completing Consolidated Maintenance Contract Inventory
SPECIFIC INSTRUCTIONS
Do not use the words Unknown or Missing; instead use Not Found when the data element could not be found and Unreadable if present but unable to correctly read
Blanks in the first nine columns are not permitted, for facility Item Codes enter the date of construction for the building
Under Equipment Type, use the exact description provided in Attachment #2
A Ventilation System is defined as those which have ductwork and controls (temperature, time, etc).
An Exhaust Fan is any fan installed with NO ductwork, regardless of size
For items you are unsure of ask the Field Engineer prior to entering data
DeCA barcode required for all accountable items, generally equipment only. Exception is the Display, Bakery Dry
Sub-location is the actual location in the facility. MHE should be assigned to Warehouse, Displays to Sales Area.
When possible add the Position Number or CAN address for refrigeration for ease of locating. In General logical descriptions to functional area. Examples: Technical Room, Deli, Bakery, Attic, Outer Receiving Area and similar.
Use room number if available. In Germersheim and KCS include the Building number and or Warehouse letter.
Appendix #5-2
APPENDIX #6
REFRIGERANT USE LOG
SERVICE
DATE
TECHNICIAN
NAME
COMPANY
NAME
REASON FOR
SERVICE
KGs REF.
ADDED
KGs REF.
REMOVED
DESTINATION
RECOVERED
REFRIGERANT
CORRECTIVE ACTIONS FOR
LOSSES/OTHER REMARKS
12-Sep-19 R. Smith Xiggle low refrigerant 5 n/a n/a
APPENDIX 6 Refrigeration Use Log.xlsx 1 2/25/2022 3:26 PM
APPENDIX #7
Example Inventory Tag
INVENTORY TAG FOR EQUIPMENT
LOCATED IN DECA FACILITIES.
DIMENSIONS ARE APPROXIMATE.
BUD123456
2.75 inches (7 cm)
1 inch (2.5 cm)
TAG SHALL HAVE A BLUE
BACKGROUND AND WHITE
LETTERS AND NUMBERS
REQUIRED REPORTING DATA
(Example Form)
Appendix # 8
INVOICE
NUMBER
REPAIR
DATE CALL TYPE
WORK ORDER OR PM
NUMBER
ITEM
CODE
SHORT
CODE
INVENTORY
NUMNER
OBJECT
CLASS
CODE PM COST
LABOR
COST
MATERIAL
COST
WORK ORDER
TOTAL
8 Digits 7 Digits 2 Digit 12 Digits 2 Digits 3 Digits 6 Digits 4 Digits 8 Digits 8 Digits 8 Digits 8 Digits
DDMMMYY
12506001 5-Mar-01 UM 123UM0000123 XZ BUD 123456 1234 123456.78 123456.78 123456.78 123456.78
12506001 EM 123EM0000124
OR
12506002 7-Mar-01 PM 123PM0000123 XZ BUD 123456 1234 123456.78 123456.78 123456.78 123456.78
12506002 PM 123PM0000124
REPORT TOTAL 123456.78
APPENDIX 08 Reporting Data Requirements.xlsx 1
APPENDIX 10
CONTRACTOR WORK VERIFICATION LOG (sign in sheet)
ENTER INFORMATION IN BLOCK LETTERS ONLY ALL FIELDS MUST BE COMPLETED
PERSON NAME COMPANY PHONE NUMBER
ORDER NUMBER(S) or REASON
FOR VISIT
ARRIVAL TIME
(DD/MMM/YYYY,
HHMM)
TIME
(DD/MMM/YYYY,
HHMM) SIGNATURE
J. Smith Xiggle 0152-12345678 234UM0000012 12-03-2019 0915 12-03-2019 1145
Appendix #11 DeCA Temperature Standards
DeCA QUALITY STANDARDS
TEMPERATURE
DESCRIPTION FAHRENHEIT (°F) CENTIGRADE (°C)
Display Case Entering Air Temperature Limits Produce +36 to +40 +2 to +4 Deli, Clerk Service +34 to +38 +1 to +3 Fresh Meat +22 to +26 -6 to-4 Milk Roll-in +26 to +30 -4 to -1 Multideck Dairy +30 to +36 -1 to +2 Chest, Ice Cream (includes Jumbo Wide Island)
-28 to -22 -33 to -30
Frozen Food (includes Jumbo Wide Island)
-12 to -5 -24 to -20
Multideck Frozen Food -8 to -3 -22 to -19 Multideck Pre-Pack Meat +28 to +32 -2 to 0 Multideck Meat +24 to +28 -4 to -2 Dual-Temp Meat -12 to -3 -24 to -19 Glass Door Frozen Food -6 to -1 -21 to -18 Bakery Display +36 to +40 +2 to +4 Egg Spot Merchandiser +36 to +40 +2 to +4 Multideck Deli, Self Service +32 to +35 0 to +2 Glass Door Ice Cream -15 to -10 -26 to -23 Multideck Ice Cream -15 to -12 -26 to -24 Glass Door Medium Temp. +25 to +29 -4 to -2 Fish Case +28 to +34 -2 to +1
Reach-In Storage Box Temperature Limits Blast Freezer -25 to -15 -32 to -26 Medium Temp Reach-in +36 to +40 +2 to +4 Low Temp Reach-in -6 to -2 -21 to -19
Walk-In Storage Room Temperature Limits Controlled Temp Storage +60 to +65 +15 to +18 Candy Storage +58 to +65 +14 to +18 Dairy Storage +34 to +37 +1 to +3 Frozen Food Storage -10,to 0 -23 to -18 Carcass Storage w/Hose Bib +32 to +36 0 to +2 Fresh Meat Chill Storage +28 to +32 -2 to 0 Meat Holding +28 to +32 -2 to 0 Meat Processing +46 to +50 +8 to +10 Meat Wrapping +46 to +50 +8 to +10 Deli Storage +34 to +37 +1 to +3 Produce Storage +34 to +40 +1 to +4
Appendix #11 DeCA Temperature Standards
DESCRIPTION
FAHRENHEIT (°F)
CENTIGRADE (°C)
Walk-In Storage Room Temperature Limits Produce Processing +55 to +68 +13 to +20 Produce Ambient Storage* +68 to +72 +20 to +22 Bakery Cooler +34 to +37 +1 to +3 Bakery Freezer -10 to 0 -23 to -18 Pre-Packaged Meat Cooler +32 to +36 0 to +2 Hard Chill Storage +26 to +30 -3 to -2 Fresh Fish Chill Storage +28 to +32 -2 to 0 Poultry Chill Storage +28 to +32 -2 to 0 Prepackaged/Poultry Chill Storage +38 to +32 -2 to 0 Ice Cream Freezer Storage -15 to -10 -26 to -23 *Bananas, Onions, Potatoes, and Tomatoes
Room Environmental Limits Sales Area and Checkout Area Cooling: 50% Maximum Relative Humidity* and 72 to 75OF (22 to 24C) Heating: 50% Maximum Relative Humidity* and 68 to 71F (20 to 22C)** ADP Room Cooling: 72 to 78F (22 to 26C) Heating: 68 to 72F (20 to 22C) All Other Areas** Cooling: 76 to 80F (24 to 27C) Heating: 68 to 72F (20 to 22C)
Set controls at a maximum of 40% relative humidity, but the environment is not deficient until 50% relative humidity is reached.
** If the system has night setback, let temperature fall to a minimum of 60F (16C) during hours that the commissary is closed.
Should the temperature rise above 72F (22C) during the winter due to internal load, the cooling, should not start until the temperature reaches the temperature requirements for summer.
DeCA Quality Standards
Appendix #12 DeCA Lighting Criteria
EUROPE – Local standards may be more stringent and therefore apply. In general the most stringent rule, regulation or requirement applies. These criteria only apply when replacing fixtures.
RM. NO. ROOM NAME FC
(LUX)
TYPE REMARKS
1 ENTRY VESTIBULE 20 (220) FLUORESCENT
2A/B/C EXIT VESTIBULE 20 (220) FLUORESCENT
3A/B CART RETURN VESTIBULE 20 (220) FLUORESCENT
4 CASHIER'S OFFICE 50 (550) FLUORESCENT NOTE 15
5 CASH COUNTING ROOM 50 (550) FLUORESCENT NOTES 9,15
6 CUSTOMER SERVICE
MANAGER'S OFFICE
50 (550) FLUORESCENT NOTES 9
7 CUSTOMER WAITING 30 (320) FLUORESCENT NOTES 2,15
8 CART STORAGE 75 (810) FLUORESCENT NOTES 2,15
9 CUSTOMER SERVICE
DESK/I.D.
75 (810) FLUORESCENT NOTES 2,15
10 CUSTOMER RESTROOM
(MEN)
30 (320) FLUORESCENT 50 FC (550 LUX)
ACCENT OVER
LAVATORIES; NOTES
9, 14, 15
10A CUSTOMER RESTROOM
VESTIBULE (MEN)
30 (320) FLUORESCENT NOTE 14, 15
11 CUSTOMER RESTROOMS
(WOMEN)
30 (320) FLUORESCENT 50 FC (550 LUX)
ACCENT OVER
LAVATORIES, NOTES
9, 14, 15
11A CUSTOMER RESTROOM
VESTIBULE (WOMEN)
30 (320) FLUORESCENT NOTE 14, 15
12 STORE DIRECTOR 50 (550) FLUORESCENT NOTE 9
13 ADMIN ENTRY VESTIBULE 20 (220) FLUORESCENT NOTES 15
14 ADMIN CORRIDOR 20 (220) FLUORESCENT NOTES 15
15 ADMIN AREA 50 (550) FLUORESCENT NOTES 15
16 EMPLOYEE BREAK ROOM
(MAIN)
50 (550) FLUORESCENT NOTES 9, 14, 15
17 TRAINING ROOM 50 (550) FLUORESCENT NOTES 7,9, 14, 15
18 STORE ADMINISTRATOR 50 (550) FLUORESCENT NOTE 9
19 STORE MANAGER'S OFFICE 50 (550) FLUORESCENT NOTE 9
20 JANITOR'S CLOSETS A/B/C/D 20 (220) FLUORESCENT NOTE 9
21A/B VESTIBULE (STAGING TO
SALES)
20 (220) FLUORESCENT
22 ADMIN STORAGE 30 (320) FLUORESCENT NOTE 9
23 DAMAGED MERCHANDISE 50 (550) FLUORESCENT
24 DAMAGED MERCH SALES
NICHE
75 (810) FLUORESCENT SWITCH WITH SALES
AREA LIGHTS.
25 LOCKER ROOM (WOMEN) 20 (220) FLUORESCENT NOTES 9,15
26 EMPLOYEE RESTROOM
(WOMEN)
20 (220) FLUORESCENT 50 FC (550 LUX)
ACCENT OVER
LAVATORIES, NOTES
9,15
26A RESTROOM VESTIBULE
(WOMEN)
20 (220) FLUORESCENT
27 EMPLOYEE RESTROOM
(MEN)
20 (220) FLUORESCENT 50 FC (550 LUX)
ACCENT OVER
LAVATORIES, NOTES
9,15
27A RESTROOM VESTIBULE
(MEN)
20 (220) FLUORESCENT
28 LOCKER ROOM (MEN) 20 (220) FLUORESCENT NOTE 15
MINIMUM COMMISSARY ILLUMINATION STANDARDS
29 CONTROLLED TEMP
STORAGE
30 (320) FLUORESCENT NOTES 10,13,14
30 CONTRACT STOCKER
STORAGE
50 (550) FLUORESCENT NOTES 9,15
31 MECHANICAL ROOM 30 (320) FLUORESCENT NOTE 15
31B CISIC (COMMUNICATIONS) 50 (550) FLUORESCENT NOTE 15
32 SENSITIVE STORAGE 30 (320) FLUORESCENT NOTES 9,15
33 OPERATING SUPPLY
STORAGE
30 (320) FLUORESCENT NOTES 9,15
34 MEDICAL FOOD INSPECTION
OFFICE (VET)
50 (550) FLUORESCENT NOTE 9
35 RECEIVING MANAGER'S
OFFICE
50 (550) FLUORESCENT NOTE 9
36 RECEIVING 30 (320) FLUORESCENT NOTE 15
37 STAGING AREA 30 (320) FLUORESCENT NOTE 15
38 MHE CHARGING AREA 30 (320) FLUORESCENT NOTE 15
39 MASS DISPLAY AREA 75 (810) FLUORESCENT NOTES 2,4
40 HBC SALES 75 (810) FLUORESCENT NOTES 2, 14, 15
41 PLANT DISPLAY AREA 75 (810) FLUORESCENT NOTES 2,4
42A/B PRODUCE SALES AREA 75 (800 FLUORESCENT 100 FC (1100 LUX)
ACCENT LTG. OVER
ISLAND PRODUCE
DISPLAY. NOTES
2,3,4,5, 14, 15,23
43 PRODUCE CHILLED
STORAGE
30 (320) FLUORESCENT NOTES 10,12,13,14
44 PRODUCE PROCESSING/
AMBIENT STORAGE
50 (550) FLUORESCENT NOTES 11,13,14
45 PRODUCE MANAGER'S
OFFICE
50 (550) FLUORESCENT NOTE 9
46 FISH DISPLAY 75 (810) FLUORESCENT NOTES 2,3,5
47 MEAT/PROD OP
SUPPLY STORAGE
30 (320) FLUORESCENT NOTES 9,15
48 BREAK ROOM (MEAT/PROD) 30 (320) FLUORESCENT NOTE 15
49 UNISEX RESTROOM 30 (320) FLUORESCENT NOTES 9,15
50 MEN'S LOCKER ROOM
(MEAT/PROD)
20 (220) FLUORESCENT NOTE 15
51 MEN'S RESTROOM
(MEAT/PROD)
20 (220) FLUORESCENT 50 FC (550 LUX)
ACCENT OVER
LAVATORIES, NOTES
9,15 &
52 WOMEN'S LOCKER ROOM
(MEAT/PROD)
20 (220) FLUORESCENT NOTE 15
53 WOMEN'S RESTROOM
(MEAT/PROD)
20 (220) FLUORESCENT 50 FC (550 LUX)
ACCENT OVER
LAVATORIES, NOTES
9,15
54 RECEIVING AISLE 30 (320) FLUORESCENT NOTE 15
55 MEAT PROCESSING 70 (750) FLUORESCENT NOTES 11,13,14
56 MEAT WRAPPING 70 (750) FLUORESCENT NOTES 11,13,14
57 MEAT MANAGER'S OFFICE 50 (550) FLUORESCENT NOTE 9
58 MEAT RESTOCKING AISLE 50 (550) FLUORESCENT 100 FC (1100 LUX)
ACCENT OVER
SINGLE DECK FRESH
MEAT DISPLAY
CASES, NOTES 2,3,4,5
59 MEAT CHILL STORAGE 30 (320) FLUORESCENT or LED NOTES 10,12,13,14
60 FAT AND BONES STORAGE 20 (220) FLUORESCENT or LED NOTES 10,12,13,14
61 PREPACKAGED MEAT CHILL
STORAGE
30 (320) FLUORESCENT or LED NOTES 10,12,13,14
62 POULTRY CHILL STORAGE 30 (320) FLUORESCENT or LED NOTES 10,12,13,14
63 MECH CHASE TO MEZZ 10 (110) FLUORESCENT
64 VESTIBULE-
RECEIVING/FROZEN FOOD /
DAIRY
20 (220) LED NOTE 19
65 AISLE (RECV'G TO SALES) 20 (220) FLUORESCENT NOTE 15
66 DAIRY SALES 75 (810) FLUORESCENT NOTES 2,3,4,15
67 DAIRY CHILL STORAGE 30 (320) FLUORESCENT or LED NOTES 10,12,13,14
68 FROZEN FOOD STORAGE 30 (320) LED NOTES 12,13,14,19
69 SALES 75 (810) FLUORESCENT NOTES 1,2, 14, 15, 22,
24. FC ON VERTICAL
PLANE AT 30" AFF AT
GONDOLA FACINGS
SHALL BE NOT LESS
THAN 50% OF
HORIZONTAL FC
INDICATED.
70 DELI SERVICE AREA 75 (810) FLUORESCENT NOTES 2,3,5,15
71 BAKERY/DELI DISPLAY AREA 75 (810) FLUORESCENT NOTES 2,3,5,15
72 BAKERY SERVICE AREA 75 (810) FLUORESCENT NOTE 15
73 DELI PREPARATION AREA 50 (550) FLUORESCENT NOTE 15
74 BAKERY PREPARATION
AREA
50 (550) FLUORESCENT NOTE 15
75 BAKERY CHILL STORAGE 30 (320) FLUORESCENT or LED NOTES 10,12,13,14
76 BAKERY FREEZER STORAGE 30 (320) LED NOTES 12,13,14,19
77 DELI CHILL STORAGE 30 (320) FLUORESCENT or LED NOTES 10,12,13,14
78 BAKERY/DELI DRY STORAGE 30 (320) FLUORESCENT
79 BAG STORAGE 30 (320) FLUORESCENT NOTE 9
80 BAGGER BREAK ROOM 30 (320) FLUORESCENT NOTE 15
81 CHECKOUT 60 (640) FLUORESCENT NOTES 2,15
82 SINGLE LINE QUEUING 60 (640) FLUORESCENT NOTES 2,15
83 MECHANICAL MEZZANINE 20 (220) FLUORESCENT NOTE15
84 VENDOR ROOM 50 (550) FLUORESCENT NOTES 9,15
85 SEAFOOD CHILL STORAGE 30 (320) FLUORESCENT or LED NOTES 10,13,14
86 BAGGER RESTROOM 30 (320) FLUORESCENT NOTES 9,15
87 PERISHABLE MANAGER 50 (550) FLUORESCENT NOTE 15
88 SEMI-PERISHABLE
MANAGER
50 (550) FLUORESCENT NOTE 15
89 ZONE MANAGER 50 (550) FLUORESCENT NOTE 15
90 REGION MGT. SUPPORT 50 (550) FLUORESCENT NOTE 15
91 REGION MGT. SUPPORT 20 (220) FLUORESCENT NOTE 15
STORAGE
92 CONFERENCE ROOM 50 (550) FLUORESCENT NOTES 7, 9, 15
--- TUNNELS 10 (110) FLUORESCENT LIGHTED PILOT
SWITCH AT TUNNEL
ENTRANCE
--- ABOVE WALK-IN
COOLERS/FREEZERS
10 (110) FLUORESCENT LIGHTED PILOT
SWITCH AT
OVERHEAD ACCESS
LOCATION
--- EXTERIOR CANOPIES 10 (110) FLUORESCENT OR LED LOW TEMPERATURE
BALLAST
--- PARKING LOTS
0-150 LF FROM BUILDING
MORE THAN 150 LF FROM
BUILDING
5 (55) 1 (11)
METAL HALIDE or LED
REFER TO ¶ 1.16
END OF TABLE
LIGHTING DESIGN REQUIREMENTS NOTES: For illumination standards.
1. Refer to DeCA Guide Spec 26 51 00, paragraph 7 for fluorescent lighting requirements.
2. Use fluorescent lighting for sales area illumination.. Except as specified by Note 20, 22, or 23, design Sales area and check out area general lighting so that it is controlled in two circuits by the RMCS controller, with RMCS manual switching on wall at customer service desk to over-ride the RMCS timer function (Refer to Design Standard Plate 26 51 00-02). Provide approximately half the required FC lighting level for night stocking on each lighting circuit. These two circuits are to be alternated nightly so that both groups of lamps will have approximately the same life expectancy. Display case lights and accent lights shall be controlled by the RMCS. Design sales area fluorescent lighting perpendicular to runs of gondola display shelving. Overall design shall provide for uniformity of illumination at both high and low-lighting levels. Both checkout and sales area shall have some lights that remain on at all times for night lighting (Refer to ¶ 14).
3. Design lighting above display cases to specifically enhance the product appearance and provide identity and personality to the department. Soft white fluorescent lighting (3000°K) is recommended for red meat displays.
4. Special accent highlighting of 100 FC is required over the island produce cases, island dairy cases, plant display, and mass display area. These shall be controlled by the accent lighting circuit on the RMCS, including manual override. Consider suspended parabolic louvered fluorescent fixtures or track lighting with ceramic metal halide lamps with filters to reduce UV and Infrared, and highlight yellows and reds while maintaining good green reproduction. Metal halide lamps should have 12,000 hour (minimum) average rated life. LED modules offering similar beam distribution, with 3500K color and minimum CRI of 82, may be utilized provided a 20-year life-cycle cost analysis indicates they are competitive with the other options.
5. Provide RMCS control and local switching for area overhead and accent lighting in meat, fish, deli, and bakery display areas.
6. All timer functions, manual override and reset switching for the sales area are provided under Division 23
RMCS.
7. In Training Room 17 and Conference Room 92, provide reduced light level capability to accommodate projection equipment, either separately switched fluorescent fixtures, dimmable fluorescent fixtures, or incandescent down lights.
8. Not used.
9. Occupancy sensors of the appropriate type shall be evaluated for use in office areas, storage rooms, restrooms, training rooms and areas subject to intermittent occupancy.
10. Cooler walk-in storage rooms require 0 deg F electronic ballasts and gasket sealed waterproof fixtures.
11. Produce Processing, Meat Processing and Meat Wrapping Rooms require 0 deg F electronic ballasts and gasket sealed waterproof fixtures.
12. Provide 3-way light switches with pilot lights on the exterior of cold storage rooms and other storage rooms as appropriate.
13. Provide vapor-tight seal at all wiring penetrations of walk-in boxes and process rooms. Seal conduits inside around wires as well as around the outside of the conduit. Run conduit (PVC) exposed inside refrigerated space from fixture to fixture to minimize the number of penetrations. Only one penetration for the lighting shall be made into the room.
14. Provide emergency lighting for egress and life safety. Use some of the fixtures normally operating on the POS system generator with minimal required supplementary battery-operated egress lighting. Batteries shall be remotely located outside of refrigerated areas. Provide fluorescent emergency lighting fixtures in restrooms. Emergency lights on emergency generator circuits should be switched with the normal lighting in the space, unless they are also designated unswitched "night lights". Unswitched night lights should be kept to a minimum (Ref. Criteria ¶ 14).
15. Provide fluorescent emergency lighting fixtures in these areas for occupant convenience and comfort that operate off the POS system generator. Provide supplemental battery-operated lighting in stairwells and hazardous areas, and where required for life safety egress.
16. Not Used.
17. Not used.
18. Not Used.
19. Frozen food storage rooms require LED lighting units..
20. Not Used.
21. Not used
22. Where "daylight harvesting" is authorized in individual project guidance, provide electronic dimming ballasts for sales floor lighting. Provide control circuit to dim lights to 50 percent upon signal (contact closure) from the RMCS (except in produce sales).
23. Accent lighting shall be provided over the produce display tables in accordance with Note 4.
24. Provide LED highlighting for the departmental graphics in the sales area. Provide wall-washing fixtures to avoid scalloping or dark areas on sales area walls.
END OF NOTES
SOMS OPEN ORDERS REPORT (Exceeding 35 Days) Appendix #13
Work Order Number
Store Short Code
Inventory Number
Item Code
Object Class Code Statement of Objective
Request for Service
Date
Expected Completion
Date Reason for Delay Te xt a s i n
SO
M
S
As in in ve nt or y lis t
As in in ve nt or y lis t
As in in ve nt or y lis t
As in in ve nt or y lis t
Te xt
En te r f ro m S
O M
S.
F or m at D
D/ M
M M
/Y
YY
Y
Fo rm at D
D/ M
M M
/Y
YY
Y
Te xt
APPENDIX #14
Examples of Preventive Maintenance Checks
Evaporators
Check the evaporators monthly for proper defrosting. Ice accumulation on the evaporator coil can cause inefficiencies in the operation of the system, and can be detrimental to the coil surface itself.
Every six months:
1. Tighten all electrical connections in the electrical panel.
• Check for frayed wiring insulation and corroded terminals, and make certain all spade connections are tight.
2. Check fan motors and blades.
• Do the blades turn freely? Check the blades for unusual wear patterns or stress fractures. Clean the surface of each fan blade. Replace any worn blades and tighten the fan set screws.
• On motors with lubrication fittings, apply the correct lubricant. Replace any motor that is hard to rotate or has worn bearings.
3. Check all defrost heaters.
• Make certain heaters are in the correct position for maximum heat transfer to the evaporator coil. Follow the manufacturer’s recommendations.
• Check each heater for correct amp draw.
• Check the voltage at each heater terminal.
• Make certain the heater terminals are in good condition.
4. Clean the drain pan and check for proper drainage.
• All foreign material should be removed from the drain pan. The pan should drain freely.
• The drain line should be free-draining with visible slope away from the evaporator.
• Check the drain line heater in applications below freezing.
5. Clean the evaporator coil surface.
The following are examples of Preventive Maintenance Checks but all work shall be performed to host nation standards for preventive maintenance and the original equipment manufacturer standards.
http://www.achrnews.com/articles/preventive-maintenance-keeping-refrigeration-equipment-in-shape http://www.achrnews.com/articles/preventive-maintenance-keeping-refrigeration-equipment-in-shape
• The coil should be washed periodically to remove dust and other foreign materials that might have been drawn into the fins. A commercial-grade cleaning foam can be used.
Follow the label directions of the appropriate cleaner to clean refrigerant coils.
Compressor Units
Every six months:
1. Tighten all electrical connections.
• Check for frayed wiring insulation and corroded terminals. Replace damaged wiring.
• Make certain all spade connections are tight.
2. Check all electrical components.
• Electrical contactors should be inspected closely for worn and pitted contact points. The points should be cleaned and polished. Check for any discoloration in the conductors, which may indicate a loose wire or a dangerous overcurrent condition. Any foreign material found in the contactor should be removed.
• Inspect the defrost timer motor. Clean the contact points and lubricate the gears of the clock. Make certain the entire clock mechanism rotates freely.
• Check all relays for worn points; replace relay if necessary.
• Check the electrical connections inside the compressor electrical box.
3. Check the operation of the control system.
• Check all pressure controls for proper operation and set points.
• Check the safety controls. Make certain the oil safety and high pressure controls are functioning.
• Check the operation of the room temperature thermostat. Make certain the liquid line solenoid valve closes completely and the compressor pumps down and cycles off.
4. Check the oil level in the compressor.
• The oil level should be at or between one-third and two-thirds of the sight glass.
• Check the operation of the crankcase heater.
5. Check the operation of the defrost controls.
• Under most conditions, the timer should initiate the defrost. Make certain the defrost termination temperature control stops the defrost cycle and allows the evaporator fans approximately 2 min of delay time before restart.
6. Check the condition of refrigerant line insulation.
• Open, torn, or waterlogged insulation provides little benefit to the system. If the insulation is in poor condition, replace it.
7. Check for the proper refrigerant level in the system.
• The liquid line sight glass should be clear and full of liquid refrigerant during normal operation. If not, find and repair the leak, then charge enough refrigerant into the system to maintain a clear sight glass.
8. Check the system superheat at the condensing unit.
• Suction superheat should be checked at the compressor as follows.
o Measure the suction pressure at the suction service valve of the compressor and determine the saturation temperature corresponding to this pressure from a temperature-pressure chart.
o Measure the suction temperature of the suction line about 1 foot back from the compressor using an accurate thermometer.
o Subtract the saturated temperature from the actual suction line temperature.
The difference is superheat.
• Too low a suction superheat can result in liquid being returned to the compressor. This causes dilution of the oil and eventual failure of the bearings, rings or, possibly, valve failure.
• Too high a suction superheat will result in excessive discharge temperatures, which cause the oil to break down and result in piston ring wear and piston and cylinder wall damage.
• For maximum system capacity, suction superheat should be kept as low as practical.
(some manufacturers recommend the superheat at the compressor be no lower than 30°F.) If adjustments to the suction superheat need to be made, the expansion valve at the evaporator should be adjusted. Follow the manufacturer’s recommendations.
9. Check all capillary and super hose lines for signs of wear.
• Make certain all capillary and super hose lines are secure and do not rub against objects that can cause refrigerant leaks.
10. Replace all missing valve caps and unit covers.
Condensers
Every six months (sooner if local conditions cause clogging or fouling of air passages through the finned surface), perform the following:
1. The condenser coil should be cleaned and washed.
• Clean periodically with a brush, vacuum cleaner, pressurized water, or commercially available coil cleaning foam. If a foam cleaner is used, it should not be acid based.
Follow the label directions of the appropriate cleaner.
2. Check the operation of the condenser fans.
• Check that each fan freely rotates.
• Tighten all fan set screws.
• Check the fan blades for signs of stress or other wear features. If any unusual wear is seen, replace the blade.
• Lubricate the motors if applicable. (Most condenser motors are permanently sealed and do not require lubricating.) Replace any motor that is worn.
Important: Fill out a maintenance log and leave it with the owner or with the equipment after each periodic inspection. This log should be available for future reference. It is also advisable to retain a copy of the operating parameters at the time of the inspection.
http://www.acca.org/