This document consists of construction drawings and specifications for the Emergency Coordination Center Server Room Cooling Upgrade project located at 3380 South 900 West, South Salt Lake, Utah 84119. The project is being managed by HHY Associates (consulting engineers located at 2180 South 1300 East Suite 210, Salt Lake City, Utah 84106) in coordination with David L. Jensen & Associates Mechanical Engineers (547 West 500 South Suite #140, Bountiful, Utah 84010). The scope of work involves removing existing Computer Room Air Conditioner (CRAC) units and installing new Computer Room Units (CRU) and associated Air Cooled Condensing Units (ACC) to upgrade cooling capacity and provide redundancy for the server room. The project includes mechanical HVAC work, refrigeration piping installation, ductwork modifications, control systems integration with Building Automation System (BAS) via BACnet communication, humidification assembly installation, and associated electrical work including new power distribution, disconnect switches, and fire alarm system integration. The construction documents include multiple bid alternates: Alternate #1 involves replacing an existing unit in the electrical/UPS room; Alternate #2 adds an additional CRU-2.2 unit; and Alternate #3 adds an additional CRU-1.4 unit with modified ductwork connections.
The project requires strict compliance with current state mechanical, plumbing, and building codes, with all work performed in accordance with the latest editions of applicable standards. Bidders are required to visit the site and become familiar with existing conditions prior to submission. All contractors must obtain necessary permits and pay associated fees. The work includes coordination with multiple disciplines including structural, electrical, fire protection, and data systems. Critical project requirements include maintaining server room operational status throughout construction with equipment replacement performed sequentially to prevent temperature excursions, coordinating all utility disconnections with facility operations in advance, and properly routing new refrigerant piping, condensate drains, and electrical conduits through existing penetrations while maintaining fire-rated assemblies. The electrical scope specifies 115V/1-phase power provision for HVAC control panels, new circuit breakers for equipment feeds (with voltage conversion from 480V existing units to 208V new units in some instances), and integration of new duct detectors and equipment monitoring into the existing fire alarm control panel.
View the file
Other files
Show all 13
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
DRAWING INDEX
SYMBOL LEGEND
VICINITY MAP
CONSULTANTS
3380 SOUTH 900 WEST, SOUTH SALT LAKE, UT 84119
June 26, 2026
Construction Documents
ABBREVIATIONS
EMERGENCY
COORDINATION CENTER
SERVER ROOM
COOLING UPGRADE
OWNER
BID INFORMATION
2180 South 1300 East Suite 210 Salt Lake City, Utah 84106 Phone: 801 466 3996 Fax: 801 466 6022 mail@hhyassoc.com
E M
E R
G E
N C
Y
C O
O R
D I N
A T
I O
N
C
E N
T E
R
S E
R V
E R
O O
M
C O
O L I N
G
U
P G
R A
D E
S
O U
T H
W
E S
T
S
O U
S
A L
K E
U
T
W
E S
T
W E
S T
2180 South 1300 East Suite 210 Salt Lake City, Utah 84106 Phone: 801 466 3996 Fax: 801 466 6022 mail@hhyassoc.com
E M
E R
G E
N C
Y
C O
O R
D I N
A T
I O
N
C
E N
T E
R
S E
R V
O
M
C O
O L I N
G
U
P G
R A
D E
S
O U
W
E S
T
S
O U
K E
U
T
CODE ANALYSIS
AC
C-
1.3
AC
C-
1.1
AC
C-
1.2
AC
C-
2.1
2180 South 1300 East Suite 210 Salt Lake City, Utah 84106 Phone: 801 466 3996 Fax: 801 466 6022 mail@hhyassoc.com
E M
E R
G E
N C
Y
C O
O R
D I N
A T
I O
N
C
E N
T E
R
S E
R V
O
M
C O
O L I N
G
U
P G
R A
D E
S
O U
W
E S
T
S
O U
K E
U
T
AC
C-
2.2
AC
C-
1.3
AC
C-
1.1
AC
C-
3.1
AC
C-
1.2
AC
C-
2.1
AC
C-
1.4
2180 South 1300 East Suite 210 Salt Lake City, Utah 84106 Phone: 801 466 3996 Fax: 801 466 6022 mail@hhyassoc.com
E M
E R
G E
N C
Y
C O
O R
D I N
A T
I O
N
C
E N
T E
R
S E
R V
O
M
C O
O L I N
G
U
P G
R A
D E
S
O U
W
E S
T
S
O U
K E
U
T
Phone: 801 466 3996 Fax: 801 466 6022 mail@hhyassoc.com
E M
E R
G E
N C
Y
C O
O R
D I N
A T
I O
N
C
E N
T E
R
S E
R V
O
M
C O
O L I N
G
U
P G
R A
D E
S
O U
W
E S
T
S
O U
K E
U
T
Phone: 801 466 3996 Fax: 801 466 6022 mail@hhyassoc.com
E M
E R
G E
N C
Y
C O
O R
D I N
A T
I O
N
C
E N
T E
R
S E
R V
O
M
C O
O L I N
G
U
P G
R A
D E
S
O U
W
E S
T
S
O U
K E
U
T
Phone: 801 466 3996 Fax: 801 466 6022 mail@hhyassoc.com
E M
E R
G E
N C
Y
C O
O R
D I N
A T
I O
N
C
E N
T E
R
S E
R V
O
M
C O
O L I N
G
U
P G
R A
D E
S
O U
W
E S
T
S
O U
K E
U
T
HVAC GENERAL NOTES
1. CONTRACTOR SHALL FURNISH AND INSTALL ALL ITEMS WHICH ARE
OBVIOUSLY AND REASONABLY NECESSARY TO COMPLETE THE
INSTALLATION.
2. THE CONTRACTOR SHALL TAKE OUT PERMITS, PROCURE
CERTIFICATES AND PAY FEES CONNECTED THEREWITH.
3. BIDDERS SHALL VISIT THE SITE AND BECOME FAMILIAR WITH
EXISTING CONDITIONS SURROUNDING THE PROJECT PRIOR TO
BIDDING.
4. THE CONTRACTOR IS REFERRED TO ARCHITECTURAL,
STRUCTURAL, ELECTRICAL PLANS AND SPECIFICATIONS. SUCH
PLANS AND SPECIFICATIONS ARE CONTRACT DOCUMENTS.
5. DRAWINGS ARE DIAGRAMMATIC AND INTENDED TO SHOW
APPROXIMATE LOCATIONS.
6. ALL MECHANICAL HVAC WORK SHALL BE PREFORMED IN STRICT
ACCORDANCE WITH THE LATEST EDITION OF THE PREVAILING
STATE MECHANICAL/PLUMBING AND BUILDING CODES AS WELL AS
ALL REGULATIONS THAT MAY APPLY. IN CASE OF CONFLICT
BETWEEN THE CONTRACT DOCUMENTS AND A GOVERNING CODE
OR ORDINANCE THE MORE STRINGENT SHALL APPLY.
7. DIFFUSER RUN OUTS SHALL BE THE SAME AS LISTED DIFFUSER
NECK SIZE, UNLESS OTHERWISE NOTED.
8. COORDINATE EXACT LOCATION OF AIR DISTRIBUTION DEVICES
WITH CEILING GRID AND LIGHT FIXTURE LAYOUT.
9. ALL RECTANGULAR SUPPLY DUCT ELBOWS SHALL HAVE TURNING
VANES.
10. RECTANGULAR DUCT SIZES SHOWN INDICATE REQUIRED AIRFLOW
SIZES. SHEETMETAL CONTRACTOR SHALL INCREASE SIZES TO
ALLOW FOR LINER.
11. NO DUCTWORK SHALL BE FABRICATED WITHOUT FIRST FIELD
VERIFYING THAT THE AVAILABLE SPACE UNDER ACTUAL JOB
CONDITIONS WILL PERMIT INSTALLATION OF THE DUCTWORK
WITHOUT STRUCTURAL OR OTHER CONFLICTS. DUCT SIZES THAT
REQUIRE ON THE JOB MODIFICATION DUE TO UNFORESEEN
OBSTRUCTIONS SHALL BE MADE WITHOUT ANY ADDITIONAL COST
TO THE OWNER.
12. MAINTAIN A 10'-0" BETWEEN OUTSIDE AIR INTAKES AND
PLUMBING/EXHAUST VENTS.
13. WHERE RATED ASSEMBLIES ARE PENETRATED BY DUCTS, PIPES
OR OTHER ITEMS, THE "F" AND "T" RATING SHALL BE MAINTAINED
WITH REQUIRED UL LISTED ASSEMBLIES OR SEALANTS AS
REQUIRED BY THE APPLICABLE CODE OR AUTHORITY HAVING
JURISDICTION.
BRANCH DUCT TAKE-OFF
DUCT FLEXIBLE CONNECTION
VOLUME DAMPER
SUPPLY AIR, RISE AND DROP
OUTSIDE AIR, RISE AND DROP
FIRE SMOKE DAMPER
FIRE DAMPER
RETURN AIR, RISE AND DROP
DUCT TRANSITION
AUTOMATIC DAMPER
TURNING VANES
DUCT TEE CONNECTION
DESCRIPTIONSYMBOL
SQUARE TO ROUND DUCT TRANSITION
X-#
X-#
X S#
KEYED NOTE
AIR DEVICE
CFM
AIR DEVICE
DUCT ACCESS DOOR
BACK-DRAFT DAMPER
T THERMOSTAT
EXHAUST AIR, RISE AND DROP
FSD
FD
SYMBOL DESCRIPTION
GLOBE VALVE
PIPE SUPPORT
SUCTION LINE
EXTERIOR PIPE SUPPORT
EXTERIOR PIPE SUPPORT
DIRECTION OF SLOPE DOWN
S
L LIQUID LINE
EXPANSION VALVE
REFRIGERANT SHUT-OFF VALVE
MOISTURE INDICATING SIGHT GLASS
FILTER DRIER
FLEXIBLE CONNECTION
F
ROUND DUCT, RISE AND DROP
FLAT OVAL DUCT, RISE AND DROP
AIR FLOW DIRECTION
INLINE PUMP
SYMBOL DESCRIPTION
REFRIGERANT PIPING - LIQUIDRL
REFRIGERANT PIPING - SUCTIONRS
S#
ROOM
NO
ROOM NAME
ROOM NUMBER
SECTION LETTER
SHEET NUMBER
LARGE SCALE NUMBER
SHEET LARGE SCALE APPEARS
MECHANICAL LEGEND NOTE: NEW ITEMS SHOWN DARK, EXISTING ITEMS SHOWN LIGHT.
ALL ITEMS MAY NOT APPEAR ON DRAWINGS.
WITH MANUAL DAMPER
BD
RELIEF AIR, RISE AND DROP
DETAIL NUMBER
SHEET DETAIL APPEARS
EQUIPMENT CALLOUTX-#
FM
J-BOXJ
ACCESS DOOR
AUTOMATIC 2-WAY VALVE
AUTOMATIC 3-WAY VALVE
AUTOMATIC BALL FLOAT VENT
BALL VALVE
CAPPED END W/BALL VALVE
CHECK VALVE
COMBINATION BALANCING VALVE/ SHUTOFF
DEVICE IN DROP
DIRECTION OF SLOPE
FLANGED BUTTERFLY VALVE
FLANGED ECCENTRIC REDUCER
FLANGED UNION
FLEXIBLE CONNECTION
FLOW DIRECTION
FLOW METER
GATE VALVE
TRAP. ONE PIECE FACTORY FABRICATED
CHILLED WATER RETURN
CHILLED WATER SUPPLYCHWS
CHWR
HOT WATER HTG. SUPPLY
HOT WATER HTG. RETURN
CONDENSER WATER RETURN
CONDENSER WATER SUPPLYCWS
CWR
HWR
HWS
HIGH PRESSURE STEAM PIPING
LOW PRESSURE CONDENSATE PIPING
HPS
LPC
LOW PRESSURE STEAM PIPINGLPS
GLYCOL HEATING SUPPLY PIPINGGHS
GLYCOL HEATING RETURN PIPINGGHR
IMMERSION WELL
MANUAL VENT WITH BALL VALVE
UNION
VENTURI
WATER FLOW SWITCHWFS
TOP
BOT
FLAT OVAL DUCTFO
FLEXIBLE DUCT
SENSORS
CO2 SENSORCO2
NEW CONNECTION
COMBUSTION AIR, RISE AND DROP
PNEUMATIC 2-WAY VALVE
P & T PLUG IN IMMERSION WELL
PIPE DROP
PIPE INLINE DROP
PIPE INLINE RISE
PIPE RISER
PRESSURE GUAGE
PRESSURE GAGE W/BALL VALVE
R
RELIEF VALVE
SCREWED CONCENTRIC REDUCER
STEAM TRAP
STRAINER
THERMOMETER
THREADED HOSE CONNECTION REVISION DELTA#
CONDENSATE DRAIN PIPINGD
MECHANICAL ABBREVIATIONS
AD ACCESS DOOR
DEMO DEMOLITION
HTG HEATING
PRV PRESSURE REDUCING VALVE
AFF ABOVE FINISHED FLOOR
DET DETAIL
HVAC HEATING, VENTILATING & AIR
CONDITIONING
PSI POUNDS PER SQUARE INCH
AHU AIR HANDLING UNIT
DH DUCT HEATER
ALT ALTERNATE
DIA DIAMETER HW HOT WATER
RA RETURN AIR
AMB ANBIENT
DIM DIMENSION HWR HOT WATER HEATING
RETURN
RAD RADIATED
AMP AMPERE
DIV DIVISION
HWS HOT WATER HEATING
SUPPLY RCP RECIRCULATION PUMP
ANSI AMERICAN NATIONAL STANDARDS
INSTITUTE DMPR DAMPER
HZ HERTZ REF ROOFTOP EXHAUST FAN
IN INCHES REQD REQUIRED
APD AIR PRESSURE DROP DRN DRAIN
INWC INCHES OF WATER COLUMN REV REVISION
APPROX APPROXIMATE DS DOWNSPOUT
INWG INCHES OF WATER GAUGE RH RELATIVE HUMIDITY
ASME AMERICAN SOCIETY OF
MECHANICAL ENGINEERS
EA EXHAUST AIR
IU INDOOR UNIT RL REFRIGERANT LIQUID
KW KILOWATT
EF EXHAUST FAN
LAT LEAVING AIR TEMPERATURE
RPBP REDUCED PRESSURE
BACKFLOW PREVENTER
AVG AVERAGE
EFF EFFICENCY
LB POUND
B BOILER
EQ EQUAL
LPC LOW PRESSURE
CONDENSATE
RPM REVOLUTIONS PER MINUTE
EQUIP EQUIPMENT
LPS LOW PRESSURE STEAM
SA SUPPLY AIR
ERV ENERGY RECOVERY
VENTILATION
LWT LEAVING WATER
TEMPERATURE
SCHED SCHEDULE
BTU BRITISH THERMAL UNIT ESP EXTERNAL STATIC PRESSURE
MAU MAKEUP AIR UNIT
SEN SENSIBLE
BTU BTU PER HOUR ET EXPANSION TANK
MAX MAXIMUM
SL SEA LEVEL
C COMMON EWT ENTERING WATER
TEMPERATURE
MBH THOUSAND BRITISH
THERMAL UNITS/HOUR
SPEC SPECIFICATION
C CONVECTOR
EXH EXHAUST
MECH MECHANICAL
SSHP SPLIT SYSTEM HEAT PUMP
CA COMBUSTION AIR
EXT EXISTING
MECH RM MECHANICAL ROOM
STD STANDARD
CAP CAPACITY
F FAHRENHEIT
MFR MANUFACTURER
TEMP TEMPERATURE
CC COOLING COIL
F FURNACE
MIN MINIMUM
TSP TOTAL STATIC PRESSURE
CEF CEILING MTD EXHAUST FAN
FCU FAN COIL UNIT
MISC MISCELLANEOUS
TSTAT THERMOSTAT
CFM CUBIC FEET PER MINUTE
FLR FLOOR
MTD MOUNTED
TW TEMPERED WATER
CHWR CHILLED WATER RETURN
FLEX FLEXIBLE
NC NOISE CRITERIA
TYP TYPICAL
CHWS CHILLED WATER SUPPLY
FO FLAT OVAL
NC NORMALLY CLOSED
UH UNIT HEATER
CO2 CARBON DIOXIDE
FPM FEET PER MINUTE
NIC NOT IN CONTRACT
V
VOLT
COMB COMBUSTION
FPVAV FAN POWERED VAV
NOM NOMINAL
VAV VARIABLE AIR VOLUME
CONTR CONTRACTOR
FT FEET
NTS NOT TO SCALE
VD VOLUME DAMPER
CU CONDENSING UNIT
GALV GALVANIZED
OA OUTSIDE AIR
VERT VERTICAL
CU FT CUBIC FEET
GPM GALLONS PER MINUTE
OBD OPPOSED BLADE DAMPER
VFD VARIABLE FREQUENCY DRIVE
CU YD CUBIC YARDS
GHR GLYCOL HEATING RETURN
OU OUTDOOR UNIT
VOL VOLUME DAMPER
CUH CABINET UNIT HEATER
GHS GLYCOL HEATING SUPPLY
PUMP
W/ WITH
CV CONSTANT VOLUME
H FUME HOOD
POUNDS PER CUBIC FEET
W/O WITHOUT
CW COLD WATER
HORIZ HORIZANTAL
WB WET BULB
CWR CONDENSOR WATER RETURN
HP HIGH PRESSURE
WPD WATER PRESSURE DROP
CWS CONDENSOR WATER SUPPLY
HP HORSEPOWER
PH PHASE
DB DRY BULB
HP HEAT PUMP
PLUM PLUMBING
DD DUAL DUCT BOX
PPM PARTS PER MILLION
ASL ABOVE SEA LEVEL
BOD BOTTOM OF DUCT
BOP BOTTOM OF PIPE RS REFRIGERANT SUCTION
P
PCF
PERF PERFORATE(D)
V
PD PRESSURE DROPHPS HIGH PRESSURE STEAM
HR HOUR
DI DIGITAL INPUT
DO DIGITAL OUTPUT
DEG DEGREE FAHRENHEIT
AI ANALOG INPUT
AO ANALOG OUTPUT
REFRIGERANT PIPING - HOT GASRHG
2180 South 1300 East Suite 210 Salt Lake City, Utah 84106 Phone: 801 466 3996 Fax: 801 466 6022 mail@hhyassoc.com
S O
U
TH
W
ES
T, S
O U
TH
S
AL
T
LA
KE
, U T
PHONE: (801) 294-9299
547 WEST 500 SOUTH SUITE #140
BOUNTIFUL, UTAH 84010
DAVID L. JENSEN & ASSOCIATES
MECHANICAL ENGINEERS
EM
ER
G
EN
C Y
C O
O R
D
IN
AT
IO
N C
EN
TE
R
SE
R
VE
R R
O O
M C
O O
LI
N
G U
PG
R
AD
E
EXP. 03/31/27
I:\
JO
BS
\2
\C
AD
\Z
LM
1.
dw g, /2
5/
:5 1:
A
M , l ke is el
/1
36"X18"
/1
36"X18"
12"Ø
16"Ø
12"Ø
14"Ø
FS
D
S
S
S
S
S
S C-5
R S/
R L
R S/
R L
R S/
R L
R S/
R L
R S/
R L
R S/
R L
R S/
R L
R S/
R L
R S/
R L
R S/
R L
R S/
R L
R S/
R L
RS
/R
L
RS
/R L
RS
/R
L
RS
/R L
RSRL
D
RSRL
RSRL
RSRL
RSRL
RSRL
D D
D
DD
D
D
D
D
F F
F
D
"X
"X
88"X14" 28"X10"
"X
" 38
"X
"X
54"X20"
50"X24"
"X
"X
38"X18" C-5
C-2
C-3
C-4
3/4"
1/2"
3/4"
3/4"
3/4"
1/2"
3/4"
1/2"
F F
F F
F
SD
12 8
C-1
FSD
BID ALT. #3
BID ALT. #1
2180 South 1300 East Suite 210 Salt Lake City, Utah 84106 Phone: 801 466 3996 Fax: 801 466 6022 mail@hhyassoc.com
S O
U
TH
W
ES
T, S
O U
TH
S
AL
T
LA
KE
, U T
PHONE: (801) 294-9299
547 WEST 500 SOUTH SUITE #140
BOUNTIFUL, UTAH 84010
DAVID L. JENSEN & ASSOCIATES
MECHANICAL ENGINEERS
EM
ER
G
EN
C Y
C O
O R
D
IN
AT
IO
N C
EN
TE
R
SE
R
VE
R R
O O
M C
O O
LI
N
G U
PG
R
AD
E
EXP. 03/31/27
KEYED NOTES FOR SHEET MD101
1 EXISTING EQUIPMENT (NOT HATCHED) TO REMAIN (TYP).
2 REMOVE EXISTING COMPUTER ROOM AIR CONDITIONER
INDOOR UNITS AND CONDENSERS (SHOWN HATCHED).
3 REMOVE DUCT SMOKE DETECTOR COMPONENTS AND
PATCH DUCTWORK AT PORT ENTRY TO DUCTWORK AS
NEEDED.
4 EXISTING EQUIPMENT DISCONNECT(S) - SEE DIV. 26
PLANS.
5 REMOVE EXISTING REFRIGERANT PIPING LINES AND
CONDENSATE LINES (SHOWN HATCHED) SERVING
REMOVED COMPUTER ROOM AIR CONDITIONER UNITS
(TYP).
6 EXISTING PIPE/CONDUIT STAND TO REMAIN. REMOVE
EXISTING REFRIGERATION PIPING FROM STAND.
7 EXISTING EQUIPMENT DISCONNECTS IN THIS AREA - SEE
DIV 26 PLANS.
8 EXISTING FIRE SPRINKLER PIPING TO BE MODIFIED AS
NECESSARY IN THIS AREA TO ACCOMMODATE
MECHANICAL DEMO/REMODEL. SEE DIV. 21
PERFORMANCE SPECIFICATIONS.
9 REMOVE SA/RA CONTROL DAMPERS AND SA/RA
DUCTWORK SERVING UNIT BACK TO MAIN CONNECTION.
10 (BID ALT. #1) REMOVE EXISTING CONDENSATE PUMP.
11 REMOVE WALL-MOUNTED DUCT SMOKE DETECTOR(S)
AND SENSORS/CONTROLLERS SERVING CRAC UNITS IN
THIS AREA.
12 REMOVE EXISTING SENSORS/CONTROLLERS SERVING
CRAC UNITS. FIELD VERIFY.
13 EXISTING DCW LINES TO REMAIN (TYP.)
14 EXISTING DCW LINES (ABOVE EQUIPMENT, BELOW
DUCTWORK) TO REMAIN. REMOVE PIPING BACK TO
SHUTOFF VALVE MAIN AND CAP, SEE MH1.1.
15 COMMON SA/RA DUCTWORK (NOT HATCHED) TO REMAIN
(LOCATED ABOVE EXISTING COMPUTER ROOM AIR
CONDITIONING UNITS)
16 (BID ALT. #1) EXISTING CONTROLLERS/SENSOR SERVING
THIS UNIT NOT OBSERVED DURING UNIT SITE VISIT FIELD
VERIFY AND REMOVE.
17 (BID ALT #1) REMOVE EXISTING REFRIGERANT PIPING
LINES AND CONDENSATE LINES (SHOWN HATCHED)
SERVING REMOVED COMPUTER ROOM AIR CONDITIONER
UNITS (TYP).
18 (BID ALT. #1) REMOVE EXISTING COMPUTER ROOM AIR
CONDITIONER INDOOR UNITS AND CONDENSERS (SHOWN
HATCHED). IF BID ALTERNATE #4 IS SELECTED AND BID
ALTERNATE #1 IS NOT SELECTED. COORDINATE WITH
ENGINEER/OWNER ON RELOCATION OF UNIT.
I:\
JO
BS
\2
\C
AD
\Z
LM
D
1.
dw g, /2 5/
:5
0:
A M
, l ke
/1
/1
/1
36"X18"
16"Ø
14"Ø
F F
F
"X
"X
88"X14"
28"X10"
"X
" 38
"X
"X
50"X24"
"X
"X
38"X18"
3/4"
1/2"
3/4"
F F
F F
F
"X
"X
CRU-1.1
CRU-1.2
CRU-1.3
CRU-1.4
CRU-2.2CRU-2.1
32"X18"32"X18"
FSD
(TYP.)
MATCHLINE MH1.2
MH1.1
H-111
BID ALT. #3
1/2"
3/4"
BID ALT. #2
DD
D
D
D
D DDDDD
D D
1/2"
R L
R H
G
R L
R H
G R
L R
H G
R L
R H
G R
L R
H G
RL
RHGRHG
RL
RL
RHGRHG
RL
RL
RHGRHG
RL
RL
RHGRHG
RL
13 14
3/4" 3/4"
S
H S H H-1
T CRU-1.1, 1.2, 1.3, 1.4
T CRU-2.1, 2.2
H
1/2"
1/2"
2180 South 1300 East Suite 210 Salt Lake City, Utah 84106 Phone: 801 466 3996 Fax: 801 466 6022 mail@hhyassoc.com
S O
U
TH
W
ES
T, S
O U
TH
S
AL
T
LA
KE
, U T
PHONE: (801) 294-9299
547 WEST 500 SOUTH SUITE #140
BOUNTIFUL, UTAH 84010
DAVID L. JENSEN & ASSOCIATES
MECHANICAL ENGINEERS
EM
ER
G
EN
C Y
C O
O R
D
IN
AT
IO
N C
EN
TE
R
SE
R
VE
R R
O O
M C
O O
LI
N
G U
PG
R
AD
E
EXP. 03/31/27
KEYED NOTES FOR SHEETS MH1.1-MH1.2
1 TRANSITION IN ELBOW FROM UNIT DISCHARGE OPENING
TO PLAN DUCT SIZE.
2 TRANSITION FROM 48"X18" DUCT DROP TO CONNECT TO
EXISTING RA OPENING IN COMMON DUCT, FIELD VERIFY.
3 (BID ALT. #3) 20"X20" SA TAKEOFF WITH BALANCING
DAMPER. DUCT OPEN TO SPACE. MATCH EXISTING
OPENINGS ON SITE.
4 CONTROL DAMPER TO MATCH UNIT DISCHARGE
OPENING. PROVIDE CONTROL DAMPER TO FIT IN SPACE
BETWEEN TOP OF UNIT AND BOTTOM OF EXISTING DUCT.
ONLY 6-7" OF VERTICAL SPACE IS AVAILABLE AT THIS
LOCATION. FIELD VERIFY AND INSTALL SIMILAR TO
EXISTING INSTALLATION.
5 TRANSITION FROM FACTORY RA FILTER BOX DUCT SIZE
TO 48"X18" DUCT DROP SIZE IN ELBOW. PROVIDE
FLEXIBLE CONNECTION AND CONTROL DAMPER IN RA
DUCTWORK DROP TO CONNECT TO EQUIPMENT.
6 DASHED LINE INDICATES REQUIRED MANUFACTURER
CLEARANCES NEEDED FOR EQUIPMENT (TYP).
7 NEW CONCRETE HOUSEKEEPING PAD TO MATCH
ELEVATION OF EXISTING, NEARBY PAD.
8 CONNECT DCW/CONDENSATE DRAIN TO EQUIPMENT
UTILITY CONNECTIONS, FIELD COORDINATE.
9 CONTROL DAMPER.
10 HVAC CONTROL PANEL(S) MOUNTED IN THIS AREA.
ENSURE THAT 115V/1 PH POWER IS PROVIDED AT THIS
LOCATION.
11 RELOCATE FIRE ALARM EQUIPMENT IN THIS AREA AS
NEEDED FOR INSTALLATION OF NEW EQUIPMENT. SEE
DIV.26 PLANS.
12 CRU-1.3 (BELOW) IS INCLUDED IN THE BASE BID.
13 DRAIN LINES THROUGH EXTERIOR WALL AT EXISTING
PIPE PENETRATION LOCATION. TURN DOWN AND
TERMINATE OUTDOORS (TYP).
14 MULTIPLE PIPES THROUGH WALL AT EXISTING
PENETRATION LOCATION. FIELD COORDINATE EXACT
ROUTING, SHOWN IS DIAGRAMMATIC.
15 ROUTE NEW REFRIGERANT PIPING FOR THESE SYSTEMS
ALONG EXISTING PIPE/CONDUIT SUPPORT.
16 MULTIPLE REFRIGERANT PIPES ROUTED ON EXISTING
EXTERIOR WALL, SEE DETAIL.
17 (BID ALT. #3) RS/RL LINES THROUGH WALL AT EXISTING
PIPE PENETRATION LOCATIONS, FIELD VERIFY.
18 DO NOT INSTALL PIPING ASSOCIATED WITH BID
ALTERNATE UNITS IF NOT ACCEPTED (TYP).
19 FACTORY HUMIDISTAT (TYP), BY HUMIDIFIER
MANUFACTURER.
20 TEMPERATURE SENSOR.
21 INSTALL NEW MANUAL VOLUME DAMPER TO MATCH SA
DUCT SIZE ON END OF EXISTING DUCT. DUCT END TO BE
OPEN TO SPACE.
22 BALANCE AND MEASURE UNIT AIRFLOW AT UNIT AND
MEASURE AIRFLOWS AT OUTLET(S). SEE SCHEDULE FOR
AIRFLOWS. FOR CRU-2.1, 2.2: BALANCE/MEASURE UNITS
SEPARATELY. UNITS ARE NOT TO OPERATE
SIMULTANEOUSLY. FOR CRU-1.1, 1.2, 1.3, 1.4: IN ADDITION
TO MEASURING INDIVIDUAL UNIT AIRFLOW SEPARATELY,
MEASURE SUPPLY AIRFLOWS WITH 2 UNITS RUNNING
SIMULTANEOUSLY.
23 HUMIDITY SENSOR.
24 FACTORY COMBINATION HUMIDISTAT/THERMOSTAT
SERVING THE EQUIPMENT INDICATED.
25 ROUTE REFRIGERANT PIPING ON EXISTING SUPPORTS AS
APPROPRIATE. DO NOT DISTURB CONDUIT THAT SHARES
THESE SUPPORTS (TYP). SEE 2/M5.2 AND COORDINATE
WITH DIVISION 26.
26 EXISTING FIRE SPRINKLER PIPING TO BE MODIFIED AS
NECESSARY IN THIS AREA TO ACCOMMODATE
MECHANICAL DEM0/REMODEL. SEE DIV. 21
PERFORMANCE SPECIFICATIONS.
I:\
JO
BS
\2
\C
AD
\Z
LM
H
1.
dw g, /2 5/
:1
1:
P M
, l ke
36"X18"
36"X18"
FS
D
S
S
F
CRU-3.1
FSD
MATCHLINE MH1.2
MH1.1
ACC-1.2
AC
C-
1.1
ACC-3.1
(TYP.)
3'- 6"
ACC-1.3
3'- 6"
3'-0" 3'-0"
3'- 0"
3'-0"
3'- 6"
3'- 6"
3'-0"
3'-0"
1'-0"
ACC-2.1 ACC-2.2
3'- 0"
3'- 6"
3'-0"
AC
C-
1.4
3'- 6"
3'-0"
D DDDDD
D
1/2"
BID ALT. #1
BID ALT. #3
R L
R H
G
TCRU-3.1
H
S
2180 South 1300 East Suite 210 Salt Lake City, Utah 84106 Phone: 801 466 3996 Fax: 801 466 6022 mail@hhyassoc.com
S O
U
TH
W
ES
T, S
O U
TH
S
AL
T
LA
KE
, U T
PHONE: (801) 294-9299
547 WEST 500 SOUTH SUITE #140
BOUNTIFUL, UTAH 84010
DAVID L. JENSEN & ASSOCIATES
MECHANICAL ENGINEERS
EM
ER
G
EN
C Y
C O
O R
D
IN
AT
IO
N C
EN
TE
R
SE
R
VE
R R
O O
M C
O O
LI
N
G U
PG
R
AD
E
EXP. 03/31/27
KEYED NOTES FOR SHEETS MH1.1-MH1.2
1 TRANSITION IN ELBOW FROM UNIT DISCHARGE OPENING
TO PLAN DUCT SIZE.
2 TRANSITION FROM 48"X18" DUCT DROP TO CONNECT TO
EXISTING RA OPENING IN COMMON DUCT, FIELD VERIFY.
3 (BID ALT. #3) 20"X20" SA TAKEOFF WITH BALANCING
DAMPER. DUCT OPEN TO SPACE. MATCH EXISTING
OPENINGS ON SITE.
4 CONTROL DAMPER TO MATCH UNIT DISCHARGE
OPENING. PROVIDE CONTROL DAMPER TO FIT IN SPACE
BETWEEN TOP OF UNIT AND BOTTOM OF EXISTING DUCT.
ONLY 6-7" OF VERTICAL SPACE IS AVAILABLE AT THIS
LOCATION. FIELD VERIFY AND INSTALL SIMILAR TO
EXISTING INSTALLATION.
5 TRANSITION FROM FACTORY RA FILTER BOX DUCT SIZE
TO 48"X18" DUCT DROP SIZE IN ELBOW. PROVIDE
FLEXIBLE CONNECTION AND CONTROL DAMPER IN RA
DUCTWORK DROP TO CONNECT TO EQUIPMENT.
6 DASHED LINE INDICATES REQUIRED MANUFACTURER
CLEARANCES NEEDED FOR EQUIPMENT (TYP).
7 NEW CONCRETE HOUSEKEEPING PAD TO MATCH
ELEVATION OF EXISTING, NEARBY PAD.
8 CONNECT DCW/CONDENSATE DRAIN TO EQUIPMENT
UTILITY CONNECTIONS, FIELD COORDINATE.
9 CONTROL DAMPER.
10 HVAC CONTROL PANEL(S) MOUNTED IN THIS AREA.
ENSURE THAT 115V/1 PH POWER IS PROVIDED AT THIS
LOCATION.
11 RELOCATE FIRE ALARM EQUIPMENT IN THIS AREA AS
NEEDED FOR INSTALLATION OF NEW EQUIPMENT. SEE
DIV.26 PLANS.
12 CRU-1.3 (BELOW) IS INCLUDED IN THE BASE BID.
13 DRAIN LINES THROUGH EXTERIOR WALL AT EXISTING
PIPE PENETRATION LOCATION. TURN DOWN AND
TERMINATE OUTDOORS (TYP).
14 MULTIPLE PIPES THROUGH WALL AT EXISTING
PENETRATION LOCATION. FIELD COORDINATE EXACT
ROUTING, SHOWN IS DIAGRAMMATIC.
15 ROUTE NEW REFRIGERANT PIPING FOR THESE SYSTEMS
ALONG EXISTING PIPE/CONDUIT SUPPORT.
16 MULTIPLE REFRIGERANT PIPES ROUTED ON EXISTING
EXTERIOR WALL, SEE DETAIL.
17 (BID ALT. #3) RS/RL LINES THROUGH WALL AT EXISTING
PIPE PENETRATION LOCATIONS, FIELD VERIFY.
18 DO NOT INSTALL PIPING ASSOCIATED WITH BID
ALTERNATE UNITS IF NOT ACCEPTED (TYP).
19 FACTORY HUMIDISTAT (TYP), BY HUMIDIFIER
MANUFACTURER.
20 TEMPERATURE SENSOR.
21 INSTALL NEW MANUAL VOLUME DAMPER TO MATCH SA
DUCT SIZE ON END OF EXISTING DUCT. DUCT END TO BE
OPEN TO SPACE.
22 BALANCE AND MEASURE UNIT AIRFLOW AT UNIT AND
MEASURE AIRFLOWS AT OUTLET(S). SEE SCHEDULE FOR
AIRFLOWS. FOR CRU-2.1, 2.2: BALANCE/MEASURE UNITS
SEPARATELY. UNITS ARE NOT TO OPERATE
SIMULTANEOUSLY. FOR CRU-1.1, 1.2, 1.3, 1.4: IN ADDITION
TO MEASURING INDIVIDUAL UNIT AIRFLOW SEPARATELY,
MEASURE SUPPLY AIRFLOWS WITH 2 UNITS RUNNING
SIMULTANEOUSLY.
23 HUMIDITY SENSOR.
24 FACTORY COMBINATION HUMIDISTAT/THERMOSTAT
SERVING THE EQUIPMENT INDICATED.
25 ROUTE REFRIGERANT PIPING ON EXISTING SUPPORTS AS
APPROPRIATE. DO NOT DISTURB CONDUIT THAT SHARES
THESE SUPPORTS (TYP). SEE 2/M5.2 AND COORDINATE
WITH DIVISION 26.
26 EXISTING FIRE SPRINKLER PIPING TO BE MODIFIED AS
NECESSARY IN THIS AREA TO ACCOMMODATE
MECHANICAL DEM0/REMODEL. SEE DIV. 21
PERFORMANCE SPECIFICATIONS.
I:\
JO
BS
\2
\C
AD
\Z
LM
H
1.
dw g, /2 5/
:1
2:
P M
, l ke
SCALE N.T.S.
#10 X 3/4" SELF-TAPPING
TIGHT AGAINST DUCT AND
SUPPORT MEMBERS. (TYP.)
CADMIUM PLATED SHEET METAL
SCREWS TO ANCHOR STRAPS TO
DUCT. ALL STRAPS ARE TO BE
DUCT STRAP HANGER DETAIL
NO POP RIVETS ALLOWED1"
HANGER STRAPS
ATTACH TO STRUCTURE
DUCT SHALL BE WRAPPED EXTERNALLY
AS PER THE SPECIFICATIONS
NOTE:
MAX.
SIDE
30"
38"
48"
60"
84"
HANGER
1"X18 GAGE STRAP
1/4" ROUND ROD
1/4" ROUND ROD
5/16" ROUND ROD
3/8" ROUND ROD
HORIZANTAL
SUPPORT ANGLE
NONE REQUIRED
1-1/2"X1-1/2"X1/8"
2"X2"X1/8"
2"X2"X1/8"
2"X2"X1/8"
MAXIMUM
SPACING
8'-0"
8'-0"
8'-0"
8'-0"
8'-0"
HANGER SIZES FOR
RECTANGULAR DUCT
ATTACH TO STRUCTURE
AGAINST CLAMP
BUTT INSULATION
HANGER RODS
INSULATION ON
SUCTION LINES
THIS DETAIL TO BE USED
FOR 2 OR MORE PIPES
RUNNING PARALLEL
NOTE:
OR EQUAL
1-5/8" P-1000
"UNISTRUT" CHANNEL ASSEMBLY
SCALE:
PIPE SUPPORT AT CEILING DETAIL
SUSPENDED REFRIGERANT
N.T.S.
SECURE PIPING TO
"CUSH-A-CLAMP" OR
SUPPORTS WITH
OR EQUAL
"HYDRA-ZORB".
SCALE:
PIPE HANGER DETAIL
N.T.S.
STANDARD CLEVIS ASSEMBLY
HANGER ROD
INSULATION
CONTINUOUS CALCIUM SILICATE
HYDRONIC WATER PIPE
DOUBLE NUT
PIPE HANGER "C" CLAMP
ROOF TRUSS
SADDLE INSULATION BELOW PIPE
WITH SHEET METAL SLEEVE.
SCALE:
REFRIGERANT PIPE COVER AT WALL DETAIL (PC)
N.T.S. OUTSIDE BUILDING
"HYDRA-ZORB" PIPE CLAMP (TYP.)
INSULATION (TYP.)
MASONRY EXTERIOR
UNISTRUT CHANNEL (GALVANIZED) (TYP.)
18 GAUGE GALVANIZED SHEET
METAL PROTECTIVE COVER.
POWDER COATED METAL COVER TO
MATCH BUILDING FASCIA (SUBMIT
FOR REVIEW).
BLOWER PACK (MOUNTED
SEPARATED FROM THE
STEAM HUMIDIFIER)
SCALE N.T.S.
HUMIDIFIER PIPING DETAIL5
STEAM LINE
- AS SHORT AS POSSIBLE
- ADEQUATE UPSLOPE
(MIN. 10°)/DOWNSLOPE
(2.0°)
- NO RESTRICTIONS
- CONDENSATE TRAP AT
THE LOWEST POINT
- HOSE OR FIXED PIPE
(WITH SAME INNER DIA.
AS STEAM OUTLET)
BLOWER PACK (MOUNTED
DIRECTLY ON STEAM
HUMIDIFIER
CONDENSATE TO DRAIN
CONDENSATE LINE
- MIN. DOWNSLOPE 1.2°
- NO RESTRICTIONS
- CONDENSATE TRAP
ØMIN 8"
- ROUTE TO
CONDENSATE PUMP
SCALE:6 REFRIGERATION PIPING SCHEMATIC
N.T.S. ACC-1.1,1.2,1.3,1.4, CU-1.1,1.2,1.3,1.4
LIEBERT MC
CONDENSER
COIL
INCLUDES FACTORY TRAPS
NO EXTERNAL TRAP REQUIRED
PRESSURE
TRANSDUCER
OPTIONAL FIELD INSTALLED
FUSIBLE PLUG
EVAPORATOR
COIL
LIQUID
SENSING
BULB
SUCTION
SERVICE VALVE
COMPRESSOR
CHECK
VALVE
EXPANSION
VALVE
SOLENOID
VALVE
SIGHT GLASS
FILTER
DRIER
EXTERNAL
EQUALIZER
HOT GAS DISCHARGE
LIQUID INTERCONNECTING
PIPING
3. TRAP AT
BASE OF
RISERS OVER
5'-0"
3. FIELD
INSTALLED
RELIEF VALVE
FACTORY REFRIGERANT PIPING
FIELD PIPING
NOTES:
1. SINGLE REFRIGERATION CIRCUIT SHOWN FOR CLARITY.
2. SCHEMATIC REPRESENTATION SHOWN. DO NOT USE FOR SPECIFIC CONNECTION LOCATIONS.
3. COMPONENTS ARE NOT SUPPLIED BY LIEBERT, BUT ARE REQUIRED FOR PROPER OPERATION AND
MAINTENANCE.
4. TRAPS MUST BE INSTALLED AND HORIZONTAL LINES PITCHED TO ENSURE PROPER OIL RETURN AND TO
REDUCE LIQUID FLOODBACK TO COMPRESSOR. PITCH HORIZONTAL HOT GAS PIPING AT A MINIMUM OF 1/2" PER 10 FEET SO THAT GRAVITY WILL AID IN MOVING OIL IN THE DIRECTION OF THE REFRIGERATION
FLOW.
5. DO NOT ISOLATE ANY REFRIGERATION CIRCUITS FROM OVER PRESSURIZATION PROTECTION.
2. FOR RISES OVER
25', TRAP EVERY 20'
OR EVENLY DIVIDED
EVAPORATOR
UNIT
CONDENSER
UNIT
SERVICE/SCHRADER (ACCESS) CONNECTION NO VALVE CORE
SERVICE/SCHRADER (ACCESS) CONNECTION WITH VALVE CORE
SCALE:
EXTERIOR REFRIGERANT PIPE SUPPORT DETAIL
N.T.S.
18 GAUGE GALVANIZED SHEET METAL
PROTECTIVE COVER. COVER TO BE POWDER
COATED WITH COLOR TO MATCH BUILDING
FASCIA (SUBMIT FOR REVIEW) IF UNIT IS NOT
LOCATED IN SOLID ENCLOSURE. RUN FROM
COND. UNIT TO BUILDING.
SECURE REFRIGERANT
PIPING TO SUPPORTS
WITH "HYDRA-ZORB"
"CUSH-A-CLAMP" OR
EQUAL (TYPICAL)
VA
RI
ES
UNISTRUT PIPE CLAMP (TYP.)
BUTT INSULATION OF SUCTION LINE
AGAINST CLAMP ASSEMBLY
ANGLE IRON UNISTRUT
P1026 TYPICAL OF 4
1-5/8" X 1-5/8" UNISTRUT
CHANNEL (GALVANIZED) (TYP.)
CONCRETE 4"
M
A X
4"
MA
X.
1/16" POP RIVET AT LEAST
EVERY 6" AT SUPPORTS
(TYP.)
ATTACH TO EXISTING
AGAINST CLAMP
BUTT INSULATION
HANGER RODS
INSULATION ON
SUCTION LINES
-THIS DETAIL TO BE USED
FOR 2 OR MORE PIPES
RUNNING PARALLEL
NOTE:
OR EQUAL
1-5/8" P-1000
"UNISTRUT" CHANNEL ASSEMBLY
SCALE:
AND COVER AT EXISTING EXTERIOR RACK
SUSPENDED REFRIGERANT PIPE SUPPORT
N.T.S.
SECURE PIPING TO
"CUSH-A-CLAMP" OR
SUPPORTS WITH
OR EQUAL
"HYDRA-ZORB".
-USE EXISTING STRUT,
ETC. AS AVAILABLE.
FIELD VERIFY
COVER. FINISH PER
POWDER COATED METAL
ARCHITECT
EXTERIOR RACK
2180 South 1300 East Suite 210 Salt Lake City, Utah 84106 Phone: 801 466 3996 Fax: 801 466 6022 mail@hhyassoc.com
S O
U
TH
W E
S T, S O
U
TH
S A
LT
L
A K
E , U
T
PHONE: (801) 294-9299
547 WEST 500 SOUTH SUITE #140
BOUNTIFUL, UTAH 84010
DAVID L. JENSEN & ASSOCIATES
MECHANICAL ENGINEERS
E M
E R
G E
N C
Y C
O O
R D
IN
A
TI
O
N C
E N
TE
R
S E
R V
E R
R O
O M
C O
O
LI
N G
U P
G R
A D
E
EXP. 03/31/27
I:\
JO
B S
\2
\C
A D
\Z
LM
1.
dw g, /3
0/
:1 7:
P
M , l ke
SCALE:1 REFRIGERATION PIPING SCHEMATIC
N.T.S. ACC-3.1, CU-3.1
CONDENSING UNIT WITH LOW AMBIENT KIT
INCLUDES FACTORY TRAPS
NO EXTERNAL TRAP REQUIRED
CONDENSER
COIL
HEAD PRESSURE
CONTROL VALVE
CHECK VALVE
RELIEF VALVE
RECEIVER TANK
LPS
DIGITAL SCROLL
COMPRESSOR
VIBRATION
ABSORBER
HPS
HPT
INTERCONNECTING
PIPING
FOR RISES OVER 25',
TRAP EVERY 20' OR
EVENLY DIVIDED
TRAP AT BASE OF
RISES OVER 5'
EVAPORATOR
COIL
EXPANSION VALVESOLENOID VALVE
FILTER DRIER
LPT
TEMPERATURE
SENSOR
FACTORY REFRIGERANT PIPING
FIELD PIPING
NOTES:
1. SCHEMATIC REPRESENTATION SHOWN. DO NOT USE FOR SPECIFIC CONNECTION LOCATIONS.
2. INTERCONNECTING PIPING IS NOT SUPPLIED BY VERTIV, BUT IS REQUIRED FOR PROPER CIRCUIT
OPERATION AND MAINTENANCE.
3. DO NOT ISOLATE ANY REFRIGERANT CIRCUIT FROM OVER PRESSURIZATION PROTECTION.
4. TRAPS MUST BE INSTALLED AND HORIZONTAL LINES PITCHED TO ENSURE PROPER OIL RETURN AND TO
REDUCE LIQUID FLOODBACK TO COMPRESSOR. PITCH HORIZONTAL HOT GAS PIPING AT A MINIMUM OF 1/2" PER 10 FEET SO THAT GRAVITY WILL AID IN MOVING OIL IN THE DIRECTION OF THE REFRIGERATION
FLOW.
EVAPORATOR UNIT
SERVICE/SCHRADER (ACCESS) CONNECTION NO VALVE CORE
SERVICE/SCHRADER (ACCESS) CONNECTION WITH VALVE CORE
SCALE:2 IMAGES OF EXISTING REFRIGERANT PIPING/SUPPORTS
N.T.S.
NOTE:
EXAMPLES OF EXISTING REFRIGERANT PIPING INSTALLATION ARE SHOWN AS INDICATED BY THE POINTERS IN THE IMAGES ABOVE. REUSE EXISTING PIPING
SUPPORTS AS POSSIBLE/APPLICABLE.
SCALE:3 REFRIGERATION PIPING SCHEMATIC
N.T.S. ACC-2.1,2.2, CU-2.1,2.2
LIEBERT MC
CONDENSER
COIL
INCLUDES FACTORY TRAPS
NO EXTERNAL TRAP REQUIRED
PRESSURE
TRANSDUCER
OPTIONAL FIELD INSTALLED
FUSIBLE PLUG
EVAPORATOR
COIL
LIQUID
SENSING
BULB
SUCTION
SERVICE VALVE
COMPRESSOR
CHECK
VALVE
EXPANSION
VALVE
SOLENOID
VALVE
SIGHT GLASS
FILTER
DRIER
EXTERNAL
EQUALIZER
HOT GAS DISCHARGE
LIQUID INTERCONNECTING
PIPING
2. TRAP AT
BASE OF
RISERS OVER
5'-0"
FACTORY REFRIGERANT PIPING
FIELD PIPING
NOTES:
1. SCHEMATIC REPRESENTATION SHOWN. DO NOT USE FOR SPECIFIC CONNECTION LOCATIONS.
2. COMPONENTS ARE NOT SUPPLIED BY LIEBERT, BUT ARE REQUIRED FOR PROPER CIRCUIT OPERATION
AND MAINTENANCE.
3. TRAPS MUST BE INSTALLED AND HORIZONTAL LINES PITCHED TO ENSURE PROPER OIL RETURN AND TO
REDUCE LIQUID FLOODBACK TO COMPRESSOR. PITCH HORIZONTAL HOT GAS PIPING AT A MINIMUM OF 1/2" PER 10 FEET SO THAT GRAVITY WILL AID IN MOVING OIL IN THE DIRECTION OF THE REFRIGERATION
FLOW.
4. DO NOT ISOLATE ANY REFRIGERATION CIRCUITS FROM OVER PRESSURIZATION PROTECTION.
CONDENSER
UNITLIQUID
HOT GAS
DISCHARGE
EVAPORATOR
UNIT
DIGITAL
SOLENOID
VALVE
2. FOR RISES OVER
25', TRAP EVERY 20'
OR EVENLY DIVIDED
SERVICE/SCHRADER (ACCESS) CONNECTION NO VALVE CORE
SERVICE/SCHRADER (ACCESS) CONNECTION WITH VALVE CORE
2180 South 1300 East Suite 210 Salt Lake City, Utah 84106 Phone: 801 466 3996 Fax: 801 466 6022 mail@hhyassoc.com
S O
U
TH
W E
S T, S O
U
TH
S A
LT
L
A K
E , U
T
PHONE: (801) 294-9299
547 WEST 500 SOUTH SUITE #140
BOUNTIFUL, UTAH 84010
DAVID L. JENSEN & ASSOCIATES
MECHANICAL ENGINEERS
E M
E R
G E
N C
Y C
O O
R D
IN
A
TI
O
N C
E N
TE
R
S E
R V
E R
R O
O M
C O
O
LI
N G
U P
G R
A D
E
EXP. 03/31/27
I:\
JO
B S
\2
\C
A D
\Z
LM
2.
dw g, /3
0/
:1 7:
P
M , l ke
Phone: 801 466 3996 Fax: 801 466 6022 mail@hhyassoc.com
S O
U
TH
W
ES
T, S
O U
TH
S
AL
T
LA
KE
, U T
PHONE: (801) 294-9299
547 WEST 500 SOUTH SUITE #140
BOUNTIFUL, UTAH 84010
DAVID L. JENSEN & ASSOCIATES
MECHANICAL ENGINEERS
EM
ER
G
EN
C Y
C O
O R
D
IN
AT
IO
N C
EN
TE
R
SE
R
VE
R R
O O
M C
O O
LI
N
G U
PG
R
AD
E
EXP. 03/31/27
I:\
JO
BS
\2
\C
AD
\Z
LM
1.
dw g, /2
5/
:5 0:
A
M , l ke
SPACE HUMIDISTAT
(PROVIDED BY
HUMIDIFIER
MANUFACTURER)
HINDEPENDENT
HUMIDITY SENSOR
S
CRU TEMPERATURE
SENSOR (PROVIDED
BY CRU
MANUFACTURER)
SINDEPENDENT
TEMPERATURE
SENSOR
HUMIDIFIER
CONTROL PANEL
(PROVIDED BY
HUMIDIFIER
MANUFACTURER)
H-1
CRU CONTROL
PANEL(PROVIDED BY
CRU MANUFACTURER)
CRU-1.1
CRU CONTROL
PANEL(PROVIDED BY
CRU MANUFACTURER)
CRU-1.2
CRU CONTROL
PANEL(PROVIDED BY
CRU MANUFACTURER)
CRU-1.3
CRU CONTROL
PANEL(PROVIDED BY
CRU MANUFACTURER)
CRU-1.4
BID ALTERNATE #3
DDC
CONTROLLER
BACnet
COMMUNICATION
SCALE:1 COMPUTER ROOM AIR CONDITIONERS / HUMIDIFIER
CONTROL DIAGRAM
N.T.S. CRU-1.1, 1.2, 1.3, 1.4; H-1
H
SPACE HUMIDISTAT
(PROVIDED BY CRU
MANUFACTURER)
HINDEPENDENT
HUMIDITY SENSOR 4
S
CRU TEMPERATURE
SENSOR (PROVIDED
BY CRU
MANUFACTURER)
S
INDEPENDENT
TEMPERATURE
SENSOR
CRU CONTROL
PANEL (PROVIDED
BY CRU
MANUFACTURER)
CRU-2.1
CRU CONTROL
PANEL (PROVIDED
BY CRU
MANUFACTURER)
CRU-2.2
BID ALTERNATE #2
DDC
CONTROLLER
BACnet
COMMUNICATION
SCALE:2 COMPUTER ROOM AIR CONDITIONERS
CONTROL DIAGRAM
N.T.S. CRU-2.1, 2.2
H
SPACE HUMIDISTAT
(PROVIDED BY CRU
MANUFACTURER)
HINDEPENDENT
HUMIDITY SENSOR 4
S
CRU TEMPERATURE
SENSOR (PROVIDED
BY CRU
MANUFACTURER)
S
INDEPENDENT
TEMPERATURE
SENSOR
CRU CONTROL
PANEL (PROVIDED
BY CRU
MANUFACTURER)
CRU-3.1
DDC
CONTROLLER
BACnet
COMMUNICATION
SCALE:3 COMPUTER ROOM AIR CONDITIONERS
CONTROL DIAGRAM
N.T.S. CRU-3.1
BID ALTERNATE #1
M 18
RETURN
AIR
DX COIL(S)
FAN
REHEAT
COIL
SUPPLY
AIR
M 19
RETURN
AIR
DX COIL(S)
FAN
REHEAT
COIL
SUPPLY
AIR
M 20
RETURN
AIR
DX COIL(S)
FAN
REHEAT
COIL
SUPPLY
AIR
M 21
RETURN
AIR
DX COIL(S)
FAN
REHEAT
COIL
SUPPLY
AIR
M 11
RETURN
AIR
DX COIL(S)
FAN
HUMIDIFICATION
ASSEMBLY
SUPPLY
AIR
REHEAT COIL
BID ALTERNATE #2 M 12
RETURN
AIR
DX COIL(S)
FAN
HUMIDIFICATION
ASSEMBLY
SUPPLY
AIR
REHEAT COIL
M 12
RETURN
AIR
DX COIL(S)
FAN
HUMIDIFICATION
ASSEMBLY
SUPPLY
AIR
REHEAT COIL
2180 South 1300 East Suite 210 Salt Lake City, Utah 84106 Phone: 801 466 3996 Fax: 801 466 6022 mail@hhyassoc.com
S O
U
TH
W
ES
T, S
O U
TH
S
AL
T
LA
KE
, U T
PHONE: (801) 294-9299
547 WEST 500 SOUTH SUITE #140
BOUNTIFUL, UTAH 84010
DAVID L. JENSEN & ASSOCIATES
MECHANICAL ENGINEERS
EM
ER
G
EN
C Y
C O
O R
D
IN
AT
IO
N C
EN
TE
R
SE
R
VE
R R
O O
M C
O O
LI
N
G U
PG
R
AD
E
EXP. 03/31/27
I:\
JO
BS
\2
\C
AD
\Z
LM
E7
.d w g, /2 5/
:4
9:
A M
, l ke
ELECTRICAL SYMBOLS LIST
SYMBOL DESCRIPTION
POWER SYMBOLS
DUPLEX CONVENIENCE OUTLET - 20 AMP
DUPLEX CONVENIENCE OUTLET - 20 AMP, GFCI PROTECTED.
DUPLEX CONVENIENCE OUTLET - 20 AMP ELECTRIC WATER COOLER
FOUR - PLEX CONVENIENCE OUTLET - 20 AMP
SPECIAL PURPOSE SINGLE PHASE OUTLET . COORDINATE TYPE OF OUTLETS AND RUN NEUTRAL
CONDUCTOR AS REQUIRED. COORDINATE NEMA CONFIGURATION WITH EQUIPMENT SUPPLIER.
SPECIAL PURPOSE THREE PHASE OUTLET. COORDINATE TYPE OF OUTLETS AND RUN NEUTRAL
CONDUCTOR AS REQUIRED. COORDINATE NEMA CONFIGURATION WITH EQUIPMENT SUPPLIER.
JUNCTION BOX - SIZE AND FUNCTION AS REQUIRED
EACH ARROW INDICATES A HOME RUN. RUN GROUND CONDUCTOR REGARDLESS OF CONDUIT TYPE.
NUMBER OF CONDUCTORS AS REQUIRED
FUSED DISCONNECT SWITCH - SIZE AS REQUIRED-STANDARD HEIGHT TO BE 66" AFF TO THE TOP
FLUSH TELEPHONE, DATA OUTLET
FLUSH TELEPHONE OUTLET
FLUSH DATA OUTLET
MOTOR LOCATION
MECHANICAL EQUIPMENT CALL OUT
MANUAL DISCONNECT WITH THERMAL OVERLOAD PROTECTION
ELECTRICAL PANEL LOCATION
TELEPHONE TERMINAL BOARD
ELECTRICAL METER LOCATION
RECESSED FLOOR BOX WITH METAL COVER PLATE, PROVIDE ONE DUPLEX OUTLET AND J-BOX FOR
VOICE/DATA
RECESSED FLOOR BOX WITH METAL COVER PLATE, PROVIDE ONE DUPLEX OUTLET
FURNITURE FEED POKE THROUGH DEVICE
J-BOX FOR TELEVISION. RUN 3/4" CONDUIT TO NEAREST ACCESSIBLE CEILING SPACE. COORDINATE
WITH ARCHITECT FOR EXACT LOCATION AND HEIGHT
EWC
J
XX-1
T
S
TTB
M
D1
DETAIL
NOT TO
SCALE
SCALE:
TYPICAL ROUGH-IN DETAIL
NOTES:
1. IN ACCORDANCE W/ IBC 711.3.2, OUTLETS ON OPPOSITE SIDES OF FIRE
RATED WALLS OR PARTITIONS IN THE SAME STUD SPACE MUST BE
SEPARATED BY MIN. OF 24" HORIZONTAL DISTANCE.
1. TYP. FOR WOOD & METAL STUD ROUGH-IN.
2. PLASTER RINGS NOT SHOWN.
3. LOCATE ALL OUTLET BOXES IN ACCORDANCE W/ ARCH.
& MECH. DWGS., AND W/ ALL APPLICABLE SHOP DWGS.
TYPICAL DUPLEX
OUTLET BOX
TYPICAL SWITCH
OUTLET BOX
BAR STRAPS
BAR
STRAPS
TYPICAL WALL
OUTLETS PROVIDE CONDUIT SUPPORTS IN
ACCORDANCE W/ NEC SPACING
REQUIREMENTS FOR THE TYPE OF
RACEWAY REQUIRED
AS REQUIRED FOR TYPE OF
CONSTRUCTION
STEEL CITY NO.
7501 BOX SUPPORT
NOTES:
1. THE CONTRACTOR MUST COORDINATE EXACT LOCATION OF THE DISCONNECT WITH THE MECHANICAL CONTRACTOR TO ELIMINATE ANY OBSTACLE (PIPE,CONCRETE PAD ETC.) IN FRONT OF THE DISCONNECT. IF THERE ARE ANY OBSTACLES, PROVIDE UNISTRUT AND INSTALL THE DISCONNECT NEXT TO MECHANICAL
EQUIPMENT IN ORDER TO PROVIDE THE REQUIRED CLEARANCE.
2. PROVIDE MINIMUM CLEARANCE AS FOLLOWS:
SYSTEM VOLTAGE
A B 42"
36" 30" 30"
DISCONNECT
SWITCH
FLEXIBLE LIQUID
TIGHT METALLIC
CONDUIT
MECHANICAL
EQUIPMENT
TYPICAL
CLEARED
SPACE
TYPICAL DISCONNECT CLEARANCE REQUIREMENTS
NOTE:
TYPICAL DETAILS SHOWING GENERAL FIRE
STOPPING PROCEDURE. ACTUAL PROCEDURE
DEPENDS UPON ANNULAR SPACE BETWEEN
PIPE AND/OR INSULATION AND OPENING.
FOLLOW MANUFACTURER'S INSTRUCTIONS.
DAMMING MATERIAL (BACKER ROD,
FIBERGLASS OR MINERAL WOOL)
3M FIRE BARRIER
CP 25WB CAULK
FIRE RATED CONCRETE
FLOOR SLAB
CONDUIT OR
INSULATED CABLES
TYPICAL FIRESTOP FOR CABLES/CONDUIT
THROUGH CONCRETE FLOORING
NOTE:
TYPICAL DETAILS SHOWING GENERAL FIRE
STOPPING PROCEDURE. ACTUAL PROCEDURE
DEPENDS UPON ANNULAR SPACE BETWEEN
PIPE AND/OR INSULATION AND OPENING.
FOLLOW MANUFACTURER'S INSTRUCTIONS.
CP 25WB CAULK ON
BOTH SIDES OF WALL
INSULATED CABLES OR CONDUIT
FIRE RATED CONCRETE/CONCRETE
BLOCK WALL
DAMMING MATERIAL
(BACKER ROD, FIBER-GLASS
OR MINERAL WOOL)
NON-METALLIC SLEEVE MAY
EXTEND A MAX 2" (51 mm)
BEYOND THE WALL SURFACE
TYPICAL FIRESTOP FOR CABLES/CONDUIT
THROUGH CONCRETE WALLS D5
DETAIL
NOTE:
1. TYPICAL DETAILS SHOWING GENERAL FIRE
STOPPING PROCEDURE. ACTUAL PROCEDURE
DEPENDS UPON ANNULAR SPACE BETWEEN
PIPE AND/OR INSULATION AND OPENING.
FOLLOW MANUFACTURER'S INSTRUCTIONS.
1/4" MINIMUM DIAMETER
BEAD OF 3M FIRE BARRIER CP
25 CAULK OR MP MOLDABLE
PUTTY
METALLIC
CONDUIT
1/4" MINIMUM DIAMETER
BEAD OF 3M FIRE BARRIER
CP 25 CAULK OR MP
MOLDABLE PUTTY
1 OR 2 HOUR FIRE RATED
GYPSUM WALL BOARD
WOOD OR STEEL STUD
FIRESTOP FOR METAL CONDUIT
THROUGH GYPSUM WALL BOARD NOT TO
SCALE
SCALE:
BRANCH PANEL
BREAKER SIZE
CIRCUIT LENGTH (REFER TO THE CHART ABOVE
FOR WIRE SIZE, PROPERLY UPSIZE THE
GROUND CONDUCTOR AND CONDUIT SIZE)
D8
DETAIL TYPICAL BRANCH CIRCUIT CONDUCTOR SIZE DETAIL
(BASED ON DISTANCE AND VOLTAGE DROP) NOT TO
SCALE
SCALE:
WIRE
SIZE
COPPER
120 VOLT
A
MP
BR
EA
KE
R
#12
LAST EQUIPMENT
DISTANCE
#10 #8 #6 #4 #3 #2 #1
#1/0
#4/0
60 FT
110 FT
170 FT
260 FT
410 FT
500 FT
640 FT
790 FT
910 FT
1600 FT
70 FT
110 FT
170 FT
270 FT
330 FT
430 FT
530 FT
600 FT
1060 FT
70 FT
100 FT
160 FT
200 FT
260 FT
320 FT
360 FT
640 FT
90 FT
130 FT
160 FT
210 FT
260 FT
300 FT
530 FT
110 FT
140 FT
180 FT
220 FT
260 FT
460 FT
#2/0 1080 FT 720 FT 430 FT 360 FT 310 FT
#3/0 1330 FT 890 FT 540 FT 450 FT 380 FT
208 VOLT
110 FT
190 FT
290 FT
460 FT
710 FT
870 FT
1120 FT
1370 FT
130 FT
190 FT
300 FT
470 FT
580 FT
740 FT
920 FT
110 FT
180 FT
280 FT
350 FT
450 FT
550 FT
150 FT
230 FT
290 FT
370 FT
460 FT
200 FT
250 FT
320 FT
390 FT
450 FT
620 FT 530 FT
520 FT630 FT
1250 FT 750 FT
1050 FT
1880 FT
1570 FT
150 FT
260 FT
390 FT
610 FT
950 FT
1160 FT
170 FT
260 FT
410 FT
630 FT
770 FT
990 FT
1220 FT
150 FT
240 FT
380 FT
460 FT
590 FT
730 FT
200 FT
310 FT
380 FT
490 FT
610 FT
270 FT
330 FT
420 FT
520 FT
1490 FT
1830 FT
270 FT
450 FT
680 FT
1070 FT
2010 FT
300 FT
450 FT
710 FT
1340 FT
270 FT
420 FT
800 FT
350 FT
670 FT 570 FT
A
MP
BR
EA
KE
R
A
MP
BR
EA
KE
R
A
MP
BR
EA
KE
R
A
MP
BR
EA
KE
R
277 VOLT 480 VOLT
1640 FT 1090 FT 650 FT 540 FT 470 FT
A
MP
BR
EA
KE
R
DISTANCE
A
MP
BR
EA
KE
R
A
MP
BR
EA
KE
R
A
MP
BR
EA
KE
R
A
MP
BR
EA
KE
R
A
MP
BR
EA
KE
R
DISTANCE
A
MP
BR
EA
KE
R
A
MP
BR
EA
KE
R
A
MP
BR
EA
KE
R
A
MP
BR
EA
KE
R
A
MP
BR
EA
KE
R
DISTANCE
A
MP
BR
EA
KE
R
A
MP
BR
EA
KE
R
A
MP
BR
EA
KE
R
A
MP
BR
EA
KE
R
LAST LIGHT FIXTURE
LAST OUTLET
NOTES:
1. UPSIZE WIRES AS NECESSARY TO MEET MAXIMUM
VOLTAGE DROP REQUIREMENTS TO THE END
DEVICE/EQUIPMENT AS REQUIRED BY NEC (3% DROP
TO PANEL + 2% DROP TO LAST DEVICE/EQUIPMENT)
2. FOR DISTANCES LONGER THAN SHOWN, UPSIZE
WIRES AS REQUIRED BY NEC TO COMPLY WITH THE
VOLTAGE DROP REQUIREMENTS.
3. UTILIZE THE SAME LOGIC TO UPSIZE CONDUCTORS
FOR BREAKER SIZES NOT SHOWN IN THE CHART.
COORDINATE WITH THE ENGINEER AS NECESSARY.
BREAKER SIZE
BREAKER SIZE
36" FOR 208 V
48" FOR 480 V
D9
DETAIL REQUIRED INDOOR INSTALLATION
SPACES FOR ELECTRICAL EQUIPMENT
WIDTH OF EQUIPMENT
(MINIMUM 30")
HEIGHT OF
EQUIPMENT
(6' MINIMUM)
6' OR CEILING
HEIGHT
EXHAUST DUCT
DEDICATED
ELECTRICAL
SPACE
SPRINKLER ALLOWED
6 1/2 FT
WORKING SPACE
NOT TO
SCALE
SCALE:
NOTES:
1. THE WIDTH OF THE WORKING SPACE SHALL BE AT LEAST 30" OR THE WIDTH OF THE PANEL BOARD, WHICHEVER IS GREATER.
2. WORKING SPACE HEAD ROOM SHALL BE A MINIMUM OF 6.5'.
3. THE MAXIMUM HEIGHT OF CIRCUIT BREAKERS/DISCONNECT SWITCH HANDLE SHALL NOT BE MORE THAN 6'6".
GENERAL NOTES:
1. ALL NEW WORK MUST MEET THE CURRENT ADOPTED NATIONAL ELECTRICAL CODE (NEC) AND ALL THE
LOCAL CODES.
2. NOT MORE THAN THREE (3) CIRCUITS SHALL BE INSTALLED IN A 3/4" CONDUIT.
3. RUN A NEUTRAL CONDUCTOR FOR EACH PHASE CONDUCTOR. DO NOT SHARE THE NEUTRAL CONDUCTOR
IN HOMERUNS. (NEC 210.4).
4. THE MINIMUM SIZE OF THE CONDUCTORS SHALL BE A NO. 12 AWG, THHN COPPER. UNLESS INDICATED
OTHERWISE ON THE DRAWINGS.
5. LIGHT FIXTURES, RACEWAYS AND OTHER ELECTRICAL DEVICES SHALL BE SUPPORTED FROM THE
STRUCTURE NOT FROM METAL OR WOOD CEILING DECK. UTILIZE UNISTRUTS IN BETWEEN STRUCTURE AS
NEEDED.
6. ALL J-BOXES SHALL BE RECESSED INTO THE FINISHED WALL/CEILING UNLESS THE FINISHED
WALL/CEILING IS CONCRETE AND IS NOT BEING FURRED OUT. ALL CONDUITS SHALL BE RUN THROUGH
THE STUDS BEHIND THE FINISHED WALL/CEILING. COORDINATE WITH ENGINEER/ARCHITECT PRIOR TO
ROUGH-IN FOR ANY EXPOSED CONDUITS/J-BOX THAT CAN NOT BE RUN INSIDE THE WALL/CEILING AND
NEED TO BE SURFACE MOUNTED ON THE FINISHED WALL/CEILING. SURFACE MOUNTED CONDUITS IN
EXPOSED CEILING SHALL BE INSTALLED CLOSE TO CEILING (AND NOT PENDANT MOUNTED BELOW THE
BEAMS/STRUCTURE).
7. PROVIDE GFCI PROTECTED OUTLETS FOR EVERY LOCATION SHOWN ON THE DRAWINGS. DO NOT USE
MULTIPLE LOCATION PROTECTION.
8. WHERE CIRCUIT CONDUCTORS ARE TO BE INCREASED IN SIZE TO MEET THE VOLTAGE DROP
REQUIREMENT, THE EQUIPMENT GROUNDING CONDUCTORS MUST BE INCREASED ACCORDINGLY (NEC
250.122)
9. ALL J-BOXES SHALL HAVE A MINIMUM DEPTH OF 2-1/8" UNLESS OTHER WISE SPECIFIED. SECURE ALL
J-BOXES AS SHOWN IN THE DETAILS. FURNISH AND INSTALL PROPER MUD
RINGS.
10. ALL THE HOMERUNS MUST BE ACCESSIBLE. DO NOT CARRY A HOMERUN FROM ONE DEVICE TO ANOTHER
WHICH IS TIED TO A SEPARATE HOMERUN INSIDE THE WALL. MARK ON ALL THE J-BOXES THE CIRCUIT
NAMES AND NUMBERS.
11. ALL J-BOXES IN FIRE RATED WALLS SHALL MEET THE FIRE RATING REQUIREMENT OF THE WALL AND
SHALL NOT BE INSTALLED LESS THAN 24" BACK TO BACK.
12. ALL DISCONNECTS SHALL BE OF A HEAVY DUTY TYPE.
13. ALL DISCONNECTS, J-BOXES, AND CONDUITS EXPOSED TO THE OUTSIDE WEATHER AND MECHANICAL
ROOMS SHALL BE OF A NON-CORROSIVE, WEATHER PROOF TYPE.
14. ALL NEW EXPOSED CONDUITS MUST RUN AGAINST THE WALL OR CEILING. DO NOT PENDANT MOUNT ANY
CONDUIT FROM THE CEILING. EXPOSED CONDUITS ARE ONLY ALLOWED IN EXPOSED CEILING AREA.
15. ALL MATERIALS USED IN INSTALLATION SHALL BE U.L. APPROVED AND NEW.
16. ALL ELECTRICAL WIRING MUST BE IN A CONDUIT (ROMEX NOT PERMITTED).
17. NO CONDUITS SHALL RUN IN DUCT WORK.
18. CABLES OR RACEWAYS INSTALLED IN EXPOSED OR CONCEALED LOCATIONS UNDER METAL-CORRUGATED
SHEET ROOF DECKING SHALL BE INSTALLED AND SUPPORTED SO THAT THE NEAREST OUTSIDE SURFACE
OF THE CABLE OR RACEWAY IS NOT LESS THAN 38 MM ( 1 1/2 IN.) FROM THE NEAREST SURFACE OF THE
ROOF DECKING.
19. PROVIDE LATERAL AND LONGITUDINAL BRACING FOR ALL CONDUIT RACKS, CABLE TRAYS, ETC., EXCEEDING 20 FEET IN LENGTH.
20. MINIMUM SIZE CONDUIT SHALL BE 3/4" FOR INTERIOR APPLICATION, AND 1" FOR CONDUIT BURIED BELOW
GRADE IN EXTERIOR APPLICATION.
21. LABELING IS REQUIRED FOR ALL PANELBOARDS, SWITCHBOARDS, MOTOR CONTROL CENTERS, MOTOR
STARTERS, TRANSFORMERS, MAJOR JUNCTION BOXES, DISCONNECT SWITCHES, BREAKERS, PUSH
BUTTONS, ETC., INTERLOCKS AND RELAY PANELS.
22. USE RIGID STEEL, SET SCREW TYPE FITTINGS ONLY. DIE CAST FITTING SHALL NOT BE USED.
23. USE EPOXY ANCHORS TO SUPPORT THE ELECTRICAL EQUIPMENT. EXPANSION ANCHOR BOLTS ARE NOT
ACCEPTABLE.
24. AT THE END OF THE JOB, PROVIDE BLANK, MATCHING COVER PLATES FOR ALL J-BOXES WHERE DEVICES
HAVE NOT YET BEEN INSTALLED.
25. SEAL AROUND ALL CONDUIT PENETRATIONS THROUGH WALLS AND CEILINGS WITH A FIRE RATED
MATERIAL. 3M IS AN APPROVED MANUFACTURER.
26. PRIOR TO SUBMITTAL FOR A BID THE ELECTRICAL CONTRACTOR SHALL INSPECT THE SITE AND INCLUDE
IN THEIR BID PACKAGE ALL CHARGES RELATED TO EXISTING CONDITIONS AND DEMOLITION WORK.
PROVIDE SHOP DRAWINGS AS REQUIRED BY CONSTRUCTION DOCUMENTS. ALL LABOR, MATERIALS AND
WORKMANSHIP SHALL BE GUARANTEED FOR A PERIOD OF 1 YEAR FROM THE DATE OF ACCEPTANCE BY
THE TENANT. REPLACE OR REPAIR ALL DEFECTS DURING THE GUARANTEED PERIOD.
27. THE ELECTRICAL CONTRACTOR SHALL TERMINATE THE ELECTRICAL CONNECTIONS TO ALL THE
EQUIPMENT BY PROVIDING THE NECESSARY MALE/ FEMALE CONNECTOR, RECEPTACLE, PLUG, ETC.
28. THE ELECTRICAL CONTRACTOR SHALL NOTIFY AND COORDINATE WITH THE MECHANICAL CONTRACTOR
SO THAT NO PIPING, DUCTS, OR OTHER EQUIPMENT SHALL BE INSTALLED IN THE ENTRY, PASS THROUGH
ELECTRICAL ROOM OR SPACES ABOVE OR BELOW ELECTRICAL PANELS.
29. THE ELECTRICAL CONTRACTOR SHALL VERIFY ALL ELECTRICAL LOADS (VOLTAGE, PHASE, CONNECTION
REQUIREMENT, ETC.) OF EQUIPMENT FURNISHED UNDER OTHER DIVISIONS WITH APPROVED SHOP
DRAWINGS.
30. THE CONTRACTOR SHALL INFORM THE ARCHITECT/ ENGINEER, IN WRITING, OF ANY DISCREPANCIES
FOUND BETWEEN THE INTENDED FUNCTION OF EQUIPMENT AND EQUIPMENT SPECIFIED IN THE CONTRACT
DOCUMENTS WITH A MINIMUM OF FIVE (5) WORKING DAYS PRIOR TO ISSUANCE OF THE FINAL ADDENDUM.
FAILURE TO REPORT ANY DISCREPANCY(CATALOG NUMBERS, DISCONTINUED ITEMS, ETC.) DOES NOT
RELIEVE THE CONTRACTOR FROM PROVIDING EQUIPMENT WHICH SHALL CONFORM TO AND FULFILL THE
INTENT OF THE CONTRACT DOCUMENTS. NOR SHALL IT BE USED AS A CONDITION TO OBTAIN ADDITIONAL
FUNDS FROM THE OWNER AFTER THE CONTRACT IS AWARDED. THE CONTRACTOR SHALL REQUEST ALL
CLARIFICATIONS OF CONTRACT DOCUMENT REQUIREMENTS, IN WRITING, TO THE ARCHITECT/ ENGINEER
WITH A MINIMUM OF FIVE (5) WORKING DAYS PRIOR TO ISSUANCE OF THE FINAL ADDENDUM.
31. CONTRACT DOCUMENTS SHALL TAKE PRECEDENCE OVER SHOP DRAWINGS UNLESS SPECIFICALLY NOTED
OTHERWISE.
32. DETAILS ARE SHOWN ON DIFFERENT SHEETS. THE CONTRACTOR SHALL REFER TO THOSE DETAILS
WHETHER OR NOT CALLED IN REFERENCE NOTES.
33. FEEDERS SHALL HAVE TYPE THHN/THWN INSULATION EXCEPT WHERE EXTREME HEAT OR WATER
CONDITIONS EXIST REQUIRING SPECIAL INSULATION.
34. THE OWNER MUST SCHEDULE INTERRUPTIONS OF SERVICE WHEN CONTRACTOR WISHES TO MAKE UTILITY
CONNECTIONS. NOTIFY IN WRITING, THE OWNER'S REPRESENTATIVE 72 HOURS PRIOR TO TIME WHEN
INTERRUPTION IS DESIRED. INTERRUPTION MUST BE AT THE COUNTY'S CONVENIENCE. OVERTIME, IF
REQUIRED FOR THIS WORK, IS TO BE AT CONTRACTORS EXPENSE.
35. RIGID METAL CONDUIT (RMC): PROVIDED ZINC-COATED, HOT-DIPPED GALVANIZED, RIGID METALLIC
CONDUIT IN WET LOCATIONS OR AREAS SUBJECT TO DAMAGE.
36. ALL CONDUCTORS SHALL BE IN CONDUIT (3/4" MINIMUM). MC CABLES ARE ONLY ALLOWED FOR
CONNECTION TO THE LIGHT FIXTURES. (MAXIMUM OF 6').
37. PROVIDE TYPED PANEL INDEX FOR EXISTING ELECTRICAL PANELS AFFECTED BY THE SCOPE OF THIS
WORK. EXISTING/UNAFFECTED CIRCUITS IN THE PANEL SHALL BE ITALICIZED AND CHANGED/ADDED
CIRCUITS SHALL BE TYPED BOLD.
E-001
GENERAL NOTES &
DETAILS
EM
ER
G
EN
C Y
C O
O R
D
IN
AT
IO
N C
EN
TE
R S
ER
VE
R R
O O
M
SE
R
VE
R C
O O
LI
N
G U
PG
R
AD
E
S O
U
TH
W
ES
T, S
O U
TH
S
AL
T
LA
KE
, U T
EELD
#1038
PIC 2- CONGESTED CEILINGPIC 1- CONGESTED CEILING EXISTING PANEL DPMB
ACC-2.2
ACC-1.3
ACC-1.1
ACC-1.2
ACC-2.1
ACC-1.4
UP
UP
DATA
ROOM
STORAGE/
SLEEPING
OFFICE/
SLEEPING
EMERGENCY
MAN. TRAINING
LINEN
STAIR
ST1-1
STAIR
VESTIBULE
CORRIDOR
CLASSROOM
ELECTRICAL
ROOM
STORAGE
ROOM
CORRIDOR
JANITOR
WOMEN'S TOILET
SHOWER
EQUIPMENT
REPAIR ROOM
MEN'S TOILET
SHOWER
MECHANICAL
ROOM
STORAGE
SECURE
017B
STORAGE
HALL
MACHINE
ROOM
001B
CORRIDOR
STORAGE
GENERATOR
015A
ROOM
OBSERVATORY
10D2
ROOM
EMT TRAINING
10D
ROOM
GYM
Pryco gal generator and pad
EF-101
MAIN FLOOR PLAN
- FIRE ALARM/
SYSTEMS
NORTH 0'
MAIN FLOOR PLAN - FIRE ALARM/SYSTEMS
1/8" = 1'
8'4'2'
EM
ER
G
EN
C Y
C O
O R
D
IN
AT
IO
N C
EN
TE
R S
ER
VE
R R
O O
M
SE
R
VE
R C
O O
LI
N
G U
PG
R
AD
E
S O
U
TH
W
ES
T, S
O U
TH
S
AL
T
LA
KE
, U T
EELD
#1038
REFERENCE NOTES: SYSTEM
DISCONNECT FIRE ALARM CONNECTION TO THE EQUIPMENT BEING
REMOVED. RECONNECT FIRE ALARM CONNECTIONS TO THE NEW UNITS.
COORDINATE WITH THE GC AND MECHANICAL CONTRACTOR FOR
PHASING AND MORE INFORMATION. PROVIDE NEW MONITORING AND
CONTROL MODULES AND PROPER PROGRAMMING. THE FIRE ALARM
SYSTEM SHALL BE OPERATIONAL AT ALL TIMES.
TIE THE NEW EQUIPMENT TO THE FIRE ALARM CONTROL PANEL FOR
MONITORING AND SHUT DOWN. PROVIDE NEW CONTROL MODULES,
MONITORING MODULES, PROGRAMMING, ETC. AS REQUIRED FOR A
COMPLETE INSTALLATION. COORDINATE THIS WORK WITH THE OWNER
IN ADVANCE.
RELOCATE EXISTING HORN/STROBE AND ASSOCIATED FEEDERS TO
ALLOW THE INSTALLATION OF NEW MECHANICAL EQUIPMENT. RUN
NEW CABLES TO AVOID SPLICING. DO NOT SPLICE THE CABLES. PROVIDE
ADDITIONAL CONDUIT, CONDUCTORS, ETC FOR A COMPLETE
INSTALLATION.
SHEET NOTES: SYSTEM
1. SUBMIT TO THE FIRE MARSHAL FOR APPROVAL. PROVIDE ADDITIONAL
DEVICES AS NEEDED BY THE FIRE MARSHAL TO MEET THE REQUIREMENT.
2. FIRE ALARM SYSTEM DESIGN, INSTALLATION, AND TESTING SHALL BE IN
ACCORDANCE WITH NFPA 72, CURRENT IFC EDITION, AND SHALL MEET THE
INSPECTION BY THE AUTHORITY HAVING JURISDICTION. PROVIDE
ADDITIONAL DEVICES, PROGRAMMING, ETC AS NECESSARY TO SATISFY
LOCAL AHJ'S REQUIREMENTS.
3. FURNISH AND INSTALL A DUCT DETECTOR WITH SAMPLER TUBE ON THE
RETURN DUCT. TIE THE DUCT DETECTOR TO THE FIRE ALARM CONTROL
PANEL. REFER TO MECHANICAL EQUIPMENT SCHEDULE ON SHEET E-002 FOR
EQUIPMENT REQUIRING DUCT DETECTORS AND EQUIPMENT NEEDING TO BE
TIED TO FACP FOR SHUT DOWN. COORDINATE WITH MECHANICAL
CONTRACTOR.
TYP
TYP
TYP
TYP
TYP
ACC-2.2
ACC-1.3
ACC-1.1
ACC-1.2
ACC-2.1
ACC-1.4
DATA
ROOM
STORAGE/
SLEEPING
OFFICE/
SLEEPING
EMERGENCY
MAN. TRAINING
LINEN
STAIR
ST1-1
STAIR
VESTIBULE
CORRIDOR
CLASSROOM
ELECTRICAL
ROOM
STORAGE
ROOM
CORRIDOR
JANITOR
WOMEN'S TOILET
SHOWER
EQUIPMENT
REPAIR ROOM
MEN'S TOILET
SHOWER
MECHANICAL
ROOM
STORAGE
SECURE
017B
STORAGE
HALL
MACHINE
ROOM
001B
CORRIDOR
STORAGE
GENERATOR
015A
ROOM
OBSERVATORY
10D2
ROOM
EMT TRAINING
10D
ROOM
GYM
Pryco gal generator and pad
CRU-1.1
CRU-1.2
CRU-1.3
CRU-1.4
CRU-2.1 CRU-2.2
CRU-3.1
ACC-1.1
ACC-1.2 ACC-1.3
ACC-1.4
ACC-2.2ACC-2.1
ACC-3.1
H-1
DPMB-1 DPMB-2
DPMB-3
DPMB-4
DPMB-5
OLA -28
OUPSE -29
1LB-1,3,5
1LB-2,4,6
EP-101
MAIN FLOOR PLAN
- POWER
NORTH 0'
MAIN FLOOR PLAN - POWER
1/8" = 1'
8'4'2'
EM
ER
G
EN
C Y
C O
O R
D
IN
AT
IO
N C
EN
TE
R S
ER
VE
R R
O O
M
SE
R
VE
R C
O O
LI
N
G U
PG
R
AD
E
S O
U
TH
W
ES
T, S
O U
TH
S
AL
T
LA
KE
, U T
EELD
#1038
SHEET NOTES: POWER
1. MECHANICAL EQUIPMENT WILL NEED TO BE REPLACED ONE AT A TIME TO
MAINTAIN THE DESIRED AIR TEMPERATURE IN THE DATA ROOM.
COORDINATE WITH THE GC, MECHANICAL CONTRACTOR, AND THE OWNER
IN ADVANCE PRIOR TO DISCONNECTING POWER TO ANY OF THE EQUIPMENT.
CONTRACTOR IS TO PROVIDE A MOP (METHOD OF PROCEDURE) TO THE
OWNER FOR APPROVAL PRIOR TO DISCONNECTING ANY OF THE EQUIPMENT.
2. THE EQUIPMENT IN THE DATA ROOM NEED TO REMAIN OPERATIONAL. IT IS
CRITICAL TO ENSURE ALL SERVERS ARE OPERATIONAL DURING THE
CONSTRUCTION. DO NOT DISCONNECT POWER TO ANY EQUIPMENT.
3. THE CEILING IN THE DATA ROOM IS VERY CONGESTED. REFER TO THE
PICTURES ON SHEET E-001.
REFERENCE NOTES: POWER
DISCONNECT THE POWER FOR EACH OF THE CRU (INDOOR) UNITS BEING
REPLACED. RE-CONNECT THE POWER AFTER THE EQUIPMENT IS
REPLACED. COORDINATE THIS WORK WITH THE GC AND THE
MECHANICAL CONTRACTOR. THIS WORK MAY HAVE TO BE DONE AFTER
HOURS. UTILIZE THE EXISTING DISCONNECT SWITCHES AND REPLACE
THE EXISTING FUSES WITH NEW FUSES. COORDINATE WITH THE
MANUFACTURER FOR THE FUSE SIZES RECOMMENDED. RUN NEW
CONDUIT AND CONDUCTORS FROM THE DISCONNECT SWITCH TO THE
CORRESPONDING NEW EQUIPMENT.
UTILIZE EXISTING 3 POLE CIRCUIT BREAKER IN PANEL "DPMB"(LOCATED
IN MECHANICAL ROOM 015) TO FEED THE NEW EQUIPMENT. REFER TO
THE MECHANICAL EQUIPMENT SCHEDULE ON SHEET E-001 FOR BREAKER
SIZE. PROVIDE A NEW FUSED DISCONNECT SWITCH IN THE
APPROXIMATE LOCATION SHOWN. MAKE FINAL CONNECTION TO THE
EQUIPMENT. COORDINATE WITH THE MANUFACTURER FOR THE FUSE
SIZES RECOMMENDED. PROPERLY LABEL THE DISCONNECT SWITCHES
TO INDICATE WHAT CIRCUIT THEY ARE TIED TO. ATTACH ON THE
DISCONNECT A 5"x7" LAMINATED FLOOR PLAN WITH THE LOCATION OF
PANEL DPMB HIGHLIGHTED.
DISCONNECT THE POWER FOR EACH OF THE ACC (OUTDOOR) UNITS
BEING REPLACED. RE-CONNECT THE POWER AFTER THE EQUIPMENT IS
REPLACED. COORDINATE THIS WORK WITH THE GC AND THE
MECHANICAL CONTRACTOR. THIS WORK MAY HAVE TO BE DONE AFTER
HOURS. UTILIZE THE EXISTING DISCONNECT SWITCHES AND REPLACE
THE EXISTING FUSES WITH NEW FUSES. COORDINATE WITH THE
MANUFACTURER FOR THE FUSE SIZES RECOMMENDED. RUN NEW
CONDUIT AND CONDUCTORS FROM THE DISCONNECT SWITCH TO THE
CORRESPONDING NEW EQUIPMENT.
UTILIZE EXISTING 20 AMP 3 POLE CIRCUIT BREAKER IN PANEL "DPMB"
TO FEED THE NEW EQUIPMENT. PROVIDE A NEW NEMA3R FUSED
DISCONNECT SWITCH IN THE APPROXIMATE LOCATION SHOWN.
SUPPORT THE DISCONNECT SWITCH FROM PIPES/UNISTRUTS AND
PROVIDE A PROPER CONCRETE BASE. MAKE FINAL CONNECTION TO THE
EQUIPMENT. COORDINATE WITH THE MANUFACTURER FOR THE FUSE
SIZES RECOMMENDED. PROPERLY LABEL THE DISCONNECT SWITCHES
TO INDICATE WHAT CIRCUIT THEY ARE TIED TO. ATTACH ON THE
DISCONNECT A 5"x7" LAMINATED FLOOR PLAN WITH THE LOCATION OF
PANEL DPMB HIGHLIGHTED.
FURNISH AND INSTALL A 120 VOLT, 20 AMP CIRCUIT BREAKER IN THE
EXISTING PANEL “OLA” TO FEED THE PUMP IN THE H-1 UNIT. THE NEW
BREAKER SHALL AIC RATING OF THE EXISTING BREAKERS IN THE
PANEL. SHUT DOWN, IF NECESSARY, SHALL BE KEPT TO A MINIMUM AND
BE COORDINATED WITH THE OWNER IN ADVANCE.
DISCONNECT THE POWER TO THE EXISTING UNITS BEING REPLACED.
THE EXISTING UNITS ARE 480 VOLT. THE NEW UNITS ARE 208 VOLT.
FURNISH AND INSTALL NEW CIRCUIT BREAKERS IN THE EXISTING PANEL
TO FEED THE NEW UNITS. RUN NEW CONDUIT, CONDUCTORS,
DISCONNECT SWITCH, ETC FOR A COMPLETE INSTALLATION. REMOVE
ALL EXISTING CONDUIT, CONDUCTORS, J-BOXES, ETC. THAT ARE NOT
BEING USED. ALSO REMOVE THE EXISTING DISCONNECT SWITCH
FEEDING THE EXISTING UNIT BEING REMOVED. PROPERLY CAP/ATER
SEAL ALL OPENINGS. REFER TO MECHANICAL DRAWINGS FOR MORE
INFORMATION.
4 4
BID ALTERNATES
1. BID ALTERNRE #1: ELECTRICAL WORK ASSOCIATED WITH REMOVING OF
EXIST CRU-3.1 (IN ELEC/UPS ROOM) AND ASSOCIATED OUTDOOR
CONDENSING UNIT, DUCTWORK, PIPING, AND UTILITIES; REPLACE WITH NEW
PER PLAN. REFER TO ARCHITECTURAL AND MECHANICAL CONSTRUCTION
DOCUMENTS FOR MORE INFORMATION.
2. BID ALTERNATE #2: ELECTRICAL WORK ASSOCIATED WITH ADDING CRU-2.2
AND ASSOCIATED OUTDOOR CONDENSING UNIT, PIPING, AND UTILITIES PER
PLAN. REFER TO ARCHITECTURAL AND MECHANICAL CONSTRUCTION
DOCUMENTS FOR MORE INFORMATION.
3. BID ALTERNATE #3: ELECTRICAL WORK ASSOCIATED WITH ADDING CRU-1.4
AND ASSOCIATED OUTDOOR CONDENSING UNIT, PIPING, AND UTILITIES PER
PLAN. REFER TO ARCHITECTURAL AND MECHANICAL CONSTRUCTION
DOCUMENTS FOR MORE INFORMATION.
| arch.pdf |
| Sheets and Views |
| ECC SR-Cover |
| ECC SR-A0.0 |
| ECC SR-A0.1 |
| ECC SR-A0.2 |
| ECC SR-A0.3 |
| ECC SR-A1.1 |
| ECC SR-A1.2 |
| ECC SR-A2.1 |
| mech.pdf |
| M001 |
| MD101 |
| MH101 |
| MH102 |
| M501 |
| M502 |
| M601 |
| ME701 |
| elec.pdf |
| Sheets and Views |
| E-001-E-001 |
| EF-101-EF-101 (24x36) |
| EP-101-EP-101 (24x36) |