80KSC026R0023 Questions and Responses 9-9-2026.pdf

PDF 130 KB Posted

Attached to
500-Ton Trailer-Mounted Air-Cooled Chiller
Solicitation number
80KSC026R0023
Issued by

About this file

This is a Questions and Responses document for RFQ 80KSC026R0023, issued by Kennedy Space Center (KSC) dated September 9, 2026. The document addresses clarifications regarding a chiller unit acquisition solicitation.

The RFQ pertains to the procurement of a commercial chiller product with specific technical requirements outlined in Attachment J-01 (Statement of Work). Key technical specifications include minimum performance of 1,250 GPM at 100 feet with 60 feet of head at 3,550 RPM, though the Government clarified the design point through SOW revisions released with Amendment 1. Questions addressed electrical interface requirements, including disconnect ratings and receptacle configurations, which the Government addressed by adding Section 6.0 (Electrical Schematics and Connection at PHSF) to the SOW. Regarding startup and commissioning, the Government indicated the SOW was revised for clarity but deferred specific determinations on on-site versus factory startup to the evaluation of actual quotations. The Government confirmed that Service Contract Labor Standards and Davis-Bacon Act wage determinations do not apply, as this is a commercial product acquisition. Submission requirements include three volumes with specified page limitations; Amendment 1 revised clarifications on volume page limits and foldout counting procedures. The Government declined to provide advance technical acceptability determinations on hypothetical equipment configurations (such as dual refrigerant circuits or trailer types), stating that quotations will be evaluated against stated requirements and evaluation criteria. Offerors must comply with all solicitation terms and conditions and assume responsibility for submission compliance.

View the file

Other files

Show all 13

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Question # RFQ Area Section Requirement/

Paragraph # Page # Question Response

1 Attachment J-01 SOW 3.0 Technical Requirements Section 3.3(a) 2 Attachment J-01 section 3.3(a) states minimum 1,250 GPM at 100 feet with minimum 60 feet of head at 3,550 RPM. Please confirm the intended design point and whether “at 100 feet” refers to total dynamic head, elevation, or another condition.

Attachment J-01, Statement of Work (SOW) was revised for clarity. See SOW Revision released with Amendment 1.

2 Attachment J-01 SOW 3.0 Technical Requirements Section 3.4 2

Please confirm whether on-site startup, performance verification, and familiarization at KSC are required, or whether factory startup/documentation with remote support is acceptable. If on-site work is required, please provide location, access/security process, duration, and any mandatory site visit or badging requirements.

Attachment J-01, SOW was revised for clarity. See SOW Revision released with Amendment 1.

3 Attachment J-01 SOW 3.0 Technical Requirements Section 3.1 1 Please confirm facility electrical interface details, including disconnect ratings, receptacle / termination configuration, short-circuit / overcurrent requirements, and whether the 125-amp requirement applies to each of two chiller cable sets.

Attachment J-01, SOW was revised to include the addition of section "6.0 Electrical schematics and connection at PHSF." See SOW Revision released with Amendment 1.

4 RFQ N/A N/A N/A

Please confirm whether any wage determination, labor standard, prevailing-wage, or site-specific labor requirement applies to delivery, startup, commissioning, or familiarization work. No wage determination was included in the package provided.

The Service Contract Labor Standards (SCLS) wage determination and Davis-Bacon Act wage determination are not applicable to this requirement. The solicitation is for the acquisition of a commercial product and does not require the performance of covered service work or construction, alteration, or repair of a public building or public work.

5 RFQ N/A N/A N/A Please confirm required insurance limits, bonding requirements, licenses, approved manufacturers / materials, domestic sourcing restrictions, or additional KSC forms beyond the RFQ and J-01. Offeror must comply with the terms and conditions of the solicitation.

6 Attachment J-01 SOW 3.0 Technical Requirements Section 3.1 d. 1 Is a chiller unit with two independent refrigerant circuits acceptable?

The Government will not provide an advance evaluation or determination of technical acceptability based on a hypothetical question. Quotations will be evaluated in accordance with the requirements and evaluation criteria contained in the solicitation.

7 Attachment J-01 SOW 3.0 Technical Requirements Section 3.2 a. 2 Is a standard flatbed trailer acceptable instead of a step-deck? See response to question number 6.

8 RFQ 1. GENERAL - Page Limitations and Instructions Section 1.1(a) 3

Could you please clarify the page limitation for Volume 3, Past Performance? Section 1.1(a) states that Volume 3 is limited to eight pages, while Section 1.1(c) states that Volumes 1 and 3 are not page limited. Please confirm whether Volume 3 is limited to eight pages or has no page limit.

Page Limitations and Instructions, Paragraph (c) was revised. See Amendment 1.

9 RFQ 1. GENERAL - Page Limitations and Instructions Section 1.3 4 Please confirm whether the quote volumes should be submitted as separate PDF files or combined into one electronic quote with clearly labeled sections in the required order.

Refer to 1.1, Page Limitations and Instructions for the page limitations of each volume. It is the offeror's responsibility to ensure it's quote is in compliance.

10 RFQ 1. GENERAL - Page Limitations and Instructions Section 1.1(b) 3

Section 1.1(b) states that foldouts count as an equivalent number of 8.5 × 11-inch pages. Please confirm whether an 11 × 17-inch page, folded to 8.5 × 11 inches, is permitted as a foldout for this electronic quote submission and, if permitted, how it will be counted toward the applicable page limitation.

Refer to 1.1, Page Limitations and Instructions, paragraph (b), which provides in part - Foldouts count as an equivalent number of 8 1/2' × 11' pages.

11 RFQ 1. GENERAL - Page Limitations and Instructions Section 1.3 4 Should each volume be submitted as a separate PDF, or should all volumes be combined into one PDF for submission? See response to question No. 9.

80KSC026R0023 Questions and Responses 9-9-2026