800 Wildwood Ave - Demolition
Solicitation number
2026-COMMUNITY DEVELOPMENT-018
Issued by
Kalamazoo County, Huntington Woods City, Michigan

About this file

This file comprises an email correspondence and asbestos-containing materials (ACM) inspection report prepared by Red Cedar Consulting for the City of Jackson, Michigan Community Development Department regarding the demolition of a commercial building located at 800 Wildwood Ave. The Chief Building Official initiated the request to place the property out for demolition bidding as a general fund project, with full completion required no later than July 7, 2026. The subject property is a 1,024 square-foot commercial building constructed in 1940 on a 0.12-acre parcel. The inspection was conducted on February 3, 2026, by a Michigan/EPA-certified asbestos building inspector and included comprehensive visual inspection and sampling of suspect asbestos-containing materials in accordance with USEPA NESHAP requirements (40 CFR Part 61) and OSHA standards (29 CFR 1926.1101).

The inspection identified regulated asbestos-containing materials requiring abatement prior to demolition activities, including friable window glazing containing up to 2 percent Chrysotile asbestos on six windows throughout the building, approximately 832 square feet of Category I non-friable brown vinyl floor tile with mastic containing up to 2 percent asbestos, and approximately 728 square feet of Category II drywall compound containing up to 2 percent asbestos. No hazardous materials were observed during the inspection. The report recommends that all identified friable and regulated asbestos-containing materials be abated by a certified asbestos abatement contractor prior to any demolition activities. The contractor must comply with OSHA and USEPA standards, and notification of intent to renovate/demolish must be filed with the Michigan Department of Environmental Quality at least 10 working days prior to commencement of demolition work.

Text of this file

800 Wildwood Ave. Jackson, MI

From
Brian Taylor
To
Kari Kerstetter
Cc
Shane LaPorte; Shannon Williams; Lee Rose
Recipients
KKerstetter@cityofjackson.org; slaporte@cityofjackson.org; swilliams@cityofjackson.org; lrose@cityofjackson.org

Kari, We need to place this property out for demolition bidding. This is a general fund demolition project.

Please list full completion no later than July 7th, 2026.

Lee, could you please forward a water sewer card for this property to Kari. I’ve lost my connection to the R drive and need to get Gardner to restore but wanted to get this out.

Any questions, please let me know

Thank you, Brian Taylor

Chief Building Official

517-795-9902- cell btaylor@cityofjackson.org

800 Wildwood Ave. Asbestos and Hazardous Contianing Materials Report 031226.pdf

P.O. Box 13216 Lansing, MI 48901 Phone: 888.449.4566 Fax: 888.448.8739 www.redcedarconsulting.net

March 12, 2026

Mr. Brian Taylor City of Jackson Community Development Department Jackson, MI 49202

RE: Asbestos Containing Material and Hazardous Materials Inspection 800 Wildwood Ave., Jackson, MI 49202 Parcel ID: Commercial

Dear Mr. Taylor:

Red Cedar Consulting has completed an asbestos-containing material (ACM) and hazardous materials inspection at 800 Wildwood Ave., Jackson, Michigan (Subject Property). This inspection was completed at the request of the City of Jackson to comply with the United States Environmental Protection Agency (USEPA) requirements for demolition and renovation set forth under the National Emissions Standards for Hazardous Air Pollutants (NESHAP, 40 CFR Part 61). This inspection was also completed to comply with the Occupational Safety and Health Administration (OSHA) Asbestos Standards for Construction (29 CFR 1926.1101) which limits employee exposure to asbestos.

SUBJECT PROPERTY

The Subject Property is comprised of a 0.12-acre commercial parcel which contains a 1,024 sq. ft.

commercial building (the Building) constructed in 1940. The Building was constructed on a concrete foundation with one aboveground floor. The exterior walls of the Building were constructed with concrete block and aluminum siding over fiberboard while the roof was sealed with asphalt rolled roof and asphaltic shingles over the entryways. The Building can be further divided into A1, Bath 1, Bath 2 and hallway.

VISUAL INSPECTION AND SAMPLING

Asbestos Containing Materials Inspection

Derek Linn of Red Cedar Consulting (Red Cedar), accredited State Of Michigan/EPA Asbestos Building Inspector (Accreditation Number A37624) who completed training per the Michigan Asbestos Workers Accreditation Act 440, completed an inspection of the Subject Property on February 3, 2026, for suspected asbestos containing building materials.

Project No.: 12-1027

Parcel ID: 800 Wildwood Ave.

This inspection, and subsequent sample collection was completed in accordance with the USEPA Asbestos Hazard Emergency Response Act (AHERA) (40 CFR Part 763) assessment and sampling protocol.

During the completion of the inspection, each area of the Subject Property was visually inspected for asbestos containing building materials (ACBM). Following the completion of the visual inspection, Red Cedar staff identified each suspect area of friable and non-friable ACBM and sorted them into one of three homogenous categories for sampling purposes. AHERA defines friable as a material that when dry, may be crumbled, pulverized, or reduced to powder by hand pressure. A homogenous area is defined by OSHA as an area of surfacing, thermal system insulation (TSI) or miscellaneous material that is uniform in color and texture. Surfacing materials are most commonly found in sprayed-on, troweled-on or otherwise applied to surfaces, such as acoustical plaster on ceilings and fireproofing materials on structural members. TSI refers to materials applied to pipes, fittings, boilers, ductwork, or other components to prevent heat loss or gain, or condensation. Any material that does not fall under the surfacing or TSI category, such as floor tile, drywall, and acoustical ceiling tile are placed into the miscellaneous materials category.

Following the completion of the visual inspection, Red Cedar staff identified the following materials as suspect ACBM:

• Asphalt Roofing

• Asphaltic Shingle

• Fiberboard

• Drywall

• 12”x12” Brown Vinyl Tile with Mastic

• 12”x12” Black & White Vinyl Tile

• Glazing

• Plaster

Red Cedar staff collected nine-teen samples of suspect ACBM separated into eight distinct homogenous groups for laboratory analysis. Samples were collected and submitted to APEX Research Inc.

Laboratories (APEX) (Accreditation Number 102118-0) for laboratory analysis. Analysis was completed utilizing polarized light microscopy (PLM) which is the Environmental Protection Agency (EPA) approved method for analysis of bulk materials for asbestos. PLM analysis completed pursuant to method (EPA 600/M4-82-020) identifies asbestos fiber bundles by the visual properties displayed when the sample is treated with various dispersion staining liquids. The laboratory report completed following the sample analysis indicates if asbestos is present, and at what percentage along with a description and percentage of other fibrous and non-fibrous materials and sample color. Chain-of-custody documentation was followed from sample collection through shipping and receiving of the samples at the designated laboratory. The documentation assures that samples will meet the quality assurance/quality control measures defined by AHERA. The laboratory analytical report prepared by APEX for the nine-teen samples is included as Attachment A.

Hazardous Materials Inspection

On February 3, 2026, the Subject Property was also inspected for the presence of hazardous materials which include but are not limited to polychlorinated biphenyls (PCBs) and potential mercury containing equipment and any items or containers that may contain or be classified as a hazardous or regulated material. Each material, if identified, was documented along with the approximate location. Any materials identified as hazardous are included in Table 1.

INSPECTION RESULTS AND RECOMMENDATIONS

During the completion of the asbestos inspection, nine-teen samples of suspect ACM were collected and are documented in Table 2 along with the Red Cedar sample number, description, friability, material type, ACM classification, sample location, material quantity and laboratory analytical results. A Site Diagram was prepared which provides the general building layout and sample locations and is included as Attachment B.

ACM, as defined by the USEPA NESHAP is “any material containing more than 1 percent asbestos as determined using the method specified in appendix E, subpart E, 40 CFR part 763 Section 1, Polarized Light Microscopy”.

Friable ACM is defined by NESHAP as any material containing more than 1 percent asbestos that, when dry, can be crumbled, pulverized, or reduced to powder by hand pressure. Friable ACM is a concern due to the ease of unintentionally disturbing the ACM which may result in “visible emissions” which is known as a Fiber Release Episode.

Non-friable asbestos-containing material is defined as “material containing more than 1 percent asbestos that, when dry, cannot be crumbled, pulverized, or reduced to powder by hand pressure. Non-friable ACMs are separated into Category I and Category II ACM. Category I ACM is any asbestos containing packing’s, gaskets, resilient floor coverings (vinyl floor tile and linoleum are examples of these) and asphalt roofing products. Category II ACM is stated by NESHAP as any material excluding Category I non-friable ACM such as drywall, plaster or fiberboard insulation.

Presumed Asbestos Containing Material

Presumed Asbestos Containing Materials (PACM) are suspect surfacing, TSI and miscellaneous materials found in buildings constructed prior to 1980 which are classified as and due to the age of the structure, are assumed to be ACM and do not require sample collection and analysis. OSHA dictates that PACM may be “rebutted” following a complete inspection pursuant to AHERA protocol.

No PACM was identified during the completion of this inspection. All suspect materials identified were sampled and analyzed for ACM.

Table 3 lists the location, material description, friability, condition, material type (surfacing, thermal or miscellaneous) and approximate quantity of all PACM documented at the Subject Property.

Table 4 provides a summary of all ACM documented at the Subject Property which includes the material location, description, and approximate quantity.

Friable ACM’s

A window glazing sample collected from a window in A1 was found to contain up to 2% Chrysotile asbestos following analysis. The assessment to quantify the extent of this material identified 6 windows at the following locations that would fall into the same homogenous group. The locations of the windows are listed below:

• A1 (2 windows 72” wide x 72” tall)

• A1, Bath 2 (3 windows 60” wide x 60” tall)

• Hall (1 window 36” wide x 84” tall)

Category I ACM

One type of resilient floor covering (12”x12" Brown Vinyl Floor Tile with Mastic) located within A1 are found to contain up to 2% Chrysotile asbestos. The assessment to quantify the extent of this material identified approximately 832 sq. ft. of this material within the Building.

Category II ACM

Drywall Compound samples, collected from the Hall and Bath 2 were found to contain up to 2% asbestos following analysis. The assessment to quantify the extent of this material identified approximately 728

sq. ft. of drywall compound within the Building.

RECOMMENDATIONS

Asbestos Containing Materials

Friable asbestos containing window glazing was identified on six windows throughout the Building. The locations of these windows that should be abated prior to demolition/renovation activities are listed below:

• A1 (2 windows 72” wide x 72” tall)

• A1, Bath 2 (3 windows 60” wide x 60” tall)

• Hall (1 windows 36” wide x 84” tall)

Please note: Other different sized windows are located throughout the Building but these windows were assessed and found to be constructed either without window glazing or were sampled and found to not contain asbestos and therefore are not required to be removed.

Drywall Compound identified on the interior of the Building must be abated prior to completion of any renovation/demolition activities at the Subject Property. Any Category II non-friable ACM that has a high probability of becoming or has become crumbled, pulverized, or reduced to powder by the forces expected to act on the material in the course of renovation or demolition operations must be properly abated.

The Category I resilient floor covering (12”x12” Brown Vinyl Tile) is a non-friable ACM that should be abated to mitigate any future exposure.

Please note: The location of samples obtained during this inspection were in a random fashion and areas that were not identified during this inspection may be damaged or have become damaged since the inspection was completed. If Category I or Category II friable materials are discovered prior to or during the demolition/renovation process, these materials must be abated prior to commencement of any demolition/renovation activities at the Subject Property.

Hazardous Materials

Hazardous Materials identified at the Subject Property and documented in Table 1 which require proper removal and disposal consist of the following items:

• No Hazardous Materials Observed During inspection

REGULATORY REQUIREMENTS

A Notification of intent to Renovate/Demolish form must be filed with the Michigan Department of Environmental Quality- Air Quality Division at least 10 working days prior to any renovation or demolition activities at a site.

The Notification of Intent to Renovate/Demolish form must also be completed and submitted to the MIOSHA-Asbestos Program whenever demolition, encapsulation and/or renovation activities at a site involving greater than ten lineal feet and/or fifteen square feet of ACM will be completed.

Regulated asbestos containing materials per NESHAP (40 CFR Part 61) which falls into any of the following categories are ACM’s that must be removed prior to any renovation/demolition activities at the Subject Property.

• Friable asbestos material.

• Category I non-friable ACM that has become friable.

• Category I non-friable ACM that will be or has been subjected to sanding, grinding, cutting, or abrading.

• Category II non-friable ACM that has a high probability of becoming or has become crumbled, pulverized, or reduced to powder by the forces expected to act on the material in the course of renovation or demolition operations.

Asbestos abatement should only be performed by a certified asbestos abatement contractor licensed to complete abatement work. The contractor must also follow the standards and requirements set forth per the OSHA Asbestos Standards for Construction (29 CFR 1926.1101) and the USEPA NESHAP (40 CFR Part 61).

Additional information regarding the OSHA Asbestos Standards for Construction (29 CFR 1926.1101) and the USEPA NESHAP (40 CFR Part 61) can be obtained by contacting the associated agency below.

NESHAP Asbestos Program MIOSHA-CSHD-Asbestos Program Department of Environmental Quality State of Michigan Phone: 517-284-6777 Phone: 517-284-7680 Email: asbestos@michigan.gov

DISCLAIMER

Red Cedar Consulting performed destructive testing methods in an attempt to access and inspect all areas of the Building. Unfortunately, due to the age of construction along with multiple additions/renovations that may have been completed on the Building, additional inspections may be required if suspect ACM material not documented within this report is encountered during renovation/demolition activities.

This report was prepared at the request and for exclusive use by the City of Jackson and may not be reproduced or sold without written permission from Red Cedar Consulting.

We appreciate the opportunity to provide the requested services. Please contact us at (888) 449-4566 with any questions or concerns.

Sincerely, Red Cedar Consulting

Aaron Paquet

Michigan/EPA Certified Asbestos Building Inspector (A30955)

©2026 Red Cedar Consulting, LLC.

Attachment A

APEX Research Laboratory Analytical Results

Certificate of Laboratory Analysis Test Method, Polarized Light Microscopy (PLM)

Report To: ARI Report # 26-122135 Mr. Aaron Paquet Date Collected: 02/03/26 Red Cedar Consulting Date Received: 02/04/26 P.O. Box 13216 Date Analyzed: 02/10/26 Lansing, MI 48901 Date Reported: 02/11/26

Sample Information Asbestos Type/Percent Non-Asbestos Material

Lab ID #: 122135 - 01 Asbestos Present: NO Fiberglass - 10%

Cust. #: WA-HM-01A No Asbestos Observed Synthetic - 50% Material: Asphaltic Roofing + Tar Other - 40% Location:

Appearance: black,fibrous,nonhomogenous Layer: 1 of 1

Lab ID #: 122135 - 02 Asbestos Present: NO Fiberglass - 10% Cust. #: WA-HM-01B No Asbestos Observed Synthetic - 40% Material: Asphaltic Roofing + Tar Other - 50% Location:

Lab ID #: 122135 - 03 Asbestos Present: NO Fiberglass - 30% Cust. #: WA-HM-02A No Asbestos Observed Other - 70% Material: White Shingle Location:

Layer: 1 of 3

For Layered Samples, each component will be analyzed and reported separately.

Robert T. Letarte Jr., Laboratory Director

Project: 800 Wildwood Ave Jackson

Test Method EPA 40 CFR - Part 763 and/or EPA 600/R-93/116 was used to analyze the above samples. Matrix interference and/or resolution limits may yield false/negative results in certain circumstances. Suspect floor tiles containing <1% should be tested with SEM or TEM. This certificate of analysis relates only to the samples as submitted and to insure the integrity of the results, may only be reproduced in full. This certificate must not be used by the customer to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the Federal Government. Liability limited to cost of analysis.

NVLAP Lab Code 102118-0

APEX Research Inc., 7717 Kensington Ct., Brighton, MI 48116

(734) 449-9990, Fax (734) 449-9991 Page 1 of 11

Red Cedar Consulting Date Received: 02/04/26

Lab ID #: 122135 - 03a Asbestos Present: NO Fiberglass - 30%

Cust. #: WA-HM-02A No Asbestos Observed Other - 70% Material: Red Shingle Location:

Layer: 2 of 3

Lab ID #: 122135 - 03b Asbestos Present: NO Cellulose - 60% Cust. #: WA-HM-02A No Asbestos Observed Other - 40% Material: Felt Location:

Appearance: brown,fibrous,homogenous Layer: 3 of 3

Lab ID #: 122135 - 04 Asbestos Present: NO Fiberglass - 30% Cust. #: WA-HM-02B No Asbestos Observed Other - 70% Material: White Shingle Location:

Layer: 1 of 3

Test Method EPA 40 CFR - Part 763 and/or EPA 600/R-93/116 was used to analyze the above samples. Matrix interference and/or resolution limits may yield false/negative results in certain circumstances. Suspect floor tiles containing <1% should be tested with SEM or TEM. This certificate of analysis relates only to the samples as submitted and to insure the integrity of the results, may only be reproduced in full. This certificate must not be used by the customer to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the Federal

(734) 449-9990, Fax (734) 449-9991 Page 2 of 11

Red Cedar Consulting Date Received: 02/04/26

Lab ID #: 122135 - 04a Asbestos Present: NO Fiberglass - 30%

Cust. #: WA-HM-02B No Asbestos Observed Other - 70% Material: Red Shingle Location:

Layer: 2 of 3

Lab ID #: 122135 - 04b Asbestos Present: NO Cellulose - 60% Cust. #: WA-HM-02B No Asbestos Observed Other - 40% Material: Felt Location:

Appearance: black,fibrous,homogenous Layer: 3 of 3

Lab ID #: 122135 - 05 Asbestos Present: NO Cellulose - 90% Cust. #: WA-HM-03A No Asbestos Observed Other - 10% Material: Fiberboard Location:

Test Method EPA 40 CFR - Part 763 and/or EPA 600/R-93/116 was used to analyze the above samples. Matrix interference and/or resolution limits may yield false/negative results in certain circumstances. Suspect floor tiles containing <1% should be tested with SEM or TEM. This certificate of analysis relates only to the samples as submitted and to insure the integrity of the results, may only be reproduced in full. This certificate must not be used by the customer to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the Federal

(734) 449-9990, Fax (734) 449-9991 Page 3 of 11

Red Cedar Consulting Date Received: 02/04/26

Lab ID #: 122135 - 06 Asbestos Present: NO Cellulose - 90%

Cust. #: WA-HM-03B No Asbestos Observed Other - 10% Material: Fiberboard Location:

Lab ID #: 122135 - 07 Asbestos Present: NO Cellulose - 2% Cust. #: WA-HS-01A No Asbestos Observed Other - 98% Material: Plaster Location:

Lab ID #: 122135 - 08 Asbestos Present: NO Cellulose - 2% Cust. #: WA-HS-01B No Asbestos Observed Other - 98% Material: Plaster Location:

Test Method EPA 40 CFR - Part 763 and/or EPA 600/R-93/116 was used to analyze the above samples. Matrix interference and/or resolution limits may yield false/negative results in certain circumstances. Suspect floor tiles containing <1% should be tested with SEM or TEM. This certificate of analysis relates only to the samples as submitted and to insure the integrity of the results, may only be reproduced in full. This certificate must not be used by the customer to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the Federal

(734) 449-9990, Fax (734) 449-9991 Page 4 of 11

Red Cedar Consulting Date Received: 02/04/26

Lab ID #: 122135 - 09 Asbestos Present: NO Cellulose - 2%

Cust. #: WA-HS-01C No Asbestos Observed Other - 98% Material: Plaster Location:

Lab ID #: 122135 - 10 Asbestos Present: NO Cellulose - 2% Cust. #: WA-HS-01D No Asbestos Observed Other - 98% Material: Plaster Location:

Lab ID #: 122135 - 11 Asbestos Present: NO Cellulose - 2% Cust. #: WA-HS-01E No Asbestos Observed Other - 98% Material: Plaster Location:

Test Method EPA 40 CFR - Part 763 and/or EPA 600/R-93/116 was used to analyze the above samples. Matrix interference and/or resolution limits may yield false/negative results in certain circumstances. Suspect floor tiles containing <1% should be tested with SEM or TEM. This certificate of analysis relates only to the samples as submitted and to insure the integrity of the results, may only be reproduced in full. This certificate must not be used by the customer to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the Federal

(734) 449-9990, Fax (734) 449-9991 Page 5 of 11

Red Cedar Consulting Date Received: 02/04/26

Lab ID #: 122135 - 12 Asbestos Present: NO Cellulose - 20%

Cust. #: WA-HM-04A No Asbestos Observed Other - 80% Material: Drywall Location:

Appearance: white,fibrous,nonhomogenous Layer: 1 of 2

Lab ID #: 122135 - 12a Asbestos Present: YES Other - 98% Cust. #: WA-HM-04A Chrysotile - 2% Material: Joint Compound Location:

Appearance: beige,fibrous,homogenous Layer: 2 of 2

Lab ID #: 122135 - 13 Asbestos Present: NO Cellulose - 20% Cust. #: WA-HM-04B No Asbestos Observed Other - 80% Material: Drywall Location:

Appearance: white,fibrous,nonhomogenous

Test Method EPA 40 CFR - Part 763 and/or EPA 600/R-93/116 was used to analyze the above samples. Matrix interference and/or resolution limits may yield false/negative results in certain circumstances. Suspect floor tiles containing <1% should be tested with SEM or TEM. This certificate of analysis relates only to the samples as submitted and to insure the integrity of the results, may only be reproduced in full. This certificate must not be used by the customer to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the Federal

(734) 449-9990, Fax (734) 449-9991 Page 6 of 11

Red Cedar Consulting Date Received: 02/04/26

Lab ID #: 122135 - 13a Asbestos Present:

Cust. #: WA-HM-04B Material: Joint Compound Location: NOT ANALYZED Appearance:

Lab ID #: 122135 - 14 Asbestos Present: YES Other - 98% Cust. #: WA-HM-05A Chrysotile - 2% Material: Window Glaze Location:

Appearance: beige,fibrous,homogenous

Lab ID #: 122135 - 15 Asbestos Present:

Cust. #: WA-HM-05B Material: Window Glaze Location: NOT ANALYZED

Test Method EPA 40 CFR - Part 763 and/or EPA 600/R-93/116 was used to analyze the above samples. Matrix interference and/or resolution limits may yield false/negative results in certain circumstances. Suspect floor tiles containing <1% should be tested with SEM or TEM. This certificate of analysis relates only to the samples as submitted and to insure the integrity of the results, may only be reproduced in full. This certificate must not be used by the customer to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the Federal

(734) 449-9990, Fax (734) 449-9991 Page 7 of 11

Red Cedar Consulting Date Received: 02/04/26

Lab ID #: 122135 - 16 Asbestos Present: YES Other - 98%

Cust. #: WA-HM-06A Chrysotile - 2% Material: 12x12 Brown Floor Tile Location:

Appearance: red,fibrous,homogenous

Lab ID #: 122135 - 16a Asbestos Present: YES Other - 95% Cust. #: WA-HM-06A Chrysotile - 5% Material: Mastic Location:

Appearance: black,fibrous,homogenous

Lab ID #: 122135 - 17 Asbestos Present:

Cust. #: WA-HM-06B Material: 12x12 Brown Floor Tile/Mastic Location: NOT ANALYZED

Test Method EPA 40 CFR - Part 763 and/or EPA 600/R-93/116 was used to analyze the above samples. Matrix interference and/or resolution limits may yield false/negative results in certain circumstances. Suspect floor tiles containing <1% should be tested with SEM or TEM. This certificate of analysis relates only to the samples as submitted and to insure the integrity of the results, may only be reproduced in full. This certificate must not be used by the customer to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the Federal

(734) 449-9990, Fax (734) 449-9991 Page 8 of 11

Red Cedar Consulting Date Received: 02/04/26

Lab ID #: 122135 - 18 Asbestos Present: NO Other - 100%

Cust. #: WA-HM-07A No Asbestos Observed Material: 12x12 White Floor Tile Location:

Appearance: white,nonfibrous,homogenous Layer: 1 of 4

Lab ID #: 122135 - 18a Asbestos Present: NO Other - 100%

Material: Glue Location:

Appearance: clear,nonfibrous,homogenous Layer: 2 of 4

Lab ID #: 122135 - 18b Asbestos Present: NO Other - 100%

Material: 12x12 Black Floor Tile Location:

Appearance: brown,nonfibrous,homogenous Layer: 3 of 4

Test Method EPA 40 CFR - Part 763 and/or EPA 600/R-93/116 was used to analyze the above samples. Matrix interference and/or resolution limits may yield false/negative results in certain circumstances. Suspect floor tiles containing <1% should be tested with SEM or TEM. This certificate of analysis relates only to the samples as submitted and to insure the integrity of the results, may only be reproduced in full. This certificate must not be used by the customer to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the Federal

(734) 449-9990, Fax (734) 449-9991 Page 9 of 11

Red Cedar Consulting Date Received: 02/04/26

Lab ID #: 122135 - 18c Asbestos Present: NO Other - 100%

Material: Glue Location:

Appearance: yellow,nonfibrous,homogenous Layer: 4 of 4

Lab ID #: 122135 - 19 Asbestos Present: NO Other - 100% Cust. #: WA-HM-07B No Asbestos Observed Material: 12x12 White Floor Tile Location:

Appearance: white,nonfibrous,homogenous Layer: 1 of 4

Lab ID #: 122135 - 19a Asbestos Present: NO Other - 100%

Material: Glue Location:

Appearance: clear,nonfibrous,homogenous Layer: 2 of 4

Test Method EPA 40 CFR - Part 763 and/or EPA 600/R-93/116 was used to analyze the above samples. Matrix interference and/or resolution limits may yield false/negative results in certain circumstances. Suspect floor tiles containing <1% should be tested with SEM or TEM. This certificate of analysis relates only to the samples as submitted and to insure the integrity of the results, may only be reproduced in full. This certificate must not be used by the customer to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the Federal

(734) 449-9990, Fax (734) 449-9991 Page 10 of 11

Red Cedar Consulting Date Received: 02/04/26

Lab ID #: 122135 - 19b Asbestos Present: NO Other - 100%

Material: 12x12 Black Floor Tile Location:

Appearance: brown,nonfibrous,homogenous Layer: 3 of 4

Lab ID #: 122135 - 19c Asbestos Present: NO Other - 100%

Material: Glue Location:

Appearance: yellow,nonfibrous,homogenous Layer: 4 of 4

Lab ID #: Asbestos Present:

Cust. #:

Material:

Location:

Layer: of

Test Method EPA 40 CFR - Part 763 and/or EPA 600/R-93/116 was used to analyze the above samples. Matrix interference and/or resolution limits may yield false/negative results in certain circumstances. Suspect floor tiles containing <1% should be tested with SEM or TEM. This certificate of analysis relates only to the samples as submitted and to insure the integrity of the results, may only be reproduced in full. This certificate must not be used by the customer to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the Federal

(734) 449-9990, Fax (734) 449-9991 Page 11 of 11

Attachment B Figure 1 Site Diagram

Figure 1 Site Diagram

Note: Figure created by Red Cedar Consulting Asbestos Sample Locations 800 Wildwood Ave.

-Not To Scale- Jackson, MI

Tables

Table 1 - Summary of Hazardous Materials, 800 Wildwood Ave., Jackson, Michigan

Hazardous Materials Description and Location

Location Material Description Quantity

No Hazardous Materials Observed During Inspection

Table 2 - Summary of Sample Descriptions and Asbestos Laboratory Results, 800 Wildwood Ave. Jackson, Michigan

Sample Number Sample Description Friable Material

Type Material

Classification

% Asbestos Laboratory

Result Sample Location Approx. Material

Quantity

WA-HM-01A Asphaltic Roofing & Tar No M Category I ND Northeast side of Building NA

WA-HM-01B Asphaltic Roofing & Tar No M Category I ND West side of Building NA

WA-HM-02A Asphaltic Shingles Multilayer No M Category I ND/ND/ND South side of Building NA WA-HM-02B Asphaltic Shingles Multilayer No M Category I ND/ND/ND West side of Building NA

WA-HM-03A Fiberboard Yes M Category I ND Southeast side of

WA-HM-03B Fiberboard Yes M Category I ND Northeast side of

WA-HM-04A Drywall & Joint Compound Yes M Category II ND/2% CH North side of Hallway 728 sq. ft.

WA-HM-04B Drywall & Joint Compound Yes M Category II ND/NA North side of Bath 2 NA

WA-HM-05A Window Glaze Yes M Category II 2% CH West side of A1 6 Windows

WA-HM-05B Window Glaze Yes M Category II NA North side of A1 NA

WA-HM-06A 12” x 12” Brown Floor Tile with Mastic No M Category I 2%CH/5%CH South side of A1 by entry to Hallway 832 sq. ft.

WA-HM-06B 12” x 12” Brown Floor Tile with Mastic No M Category I NA Center of A1 NA

WA-HM-07A 12” x 12” Black & White Floor Tile No M Category I ND/ND/ND /ND South side of Bath 2 NA

WA-HM-07B 12” x 12” Black & White Floor Tile No M Category I ND/ND/ND /ND Center of Hallway NA WA-HS-01A Plaster No S Category II ND South side of A1 NA

WA-HS-01B Plaster No S Category II ND South side of A1 by Hallway NA

WA-HS-01C Plaster No S Category II ND East wall of A1 NA WA-HS-01D Plaster No S Category II ND South side of Bath 2 NA

WA-HS-01E Plaster No S Category II ND South side of Hallway NA

Notes:

Material Types Abbreviations

M = Miscellaneous building material NQ = Not quantified TSI = Thermal System Insulation NA = Not Analyzed S = Surfacing Material ND = Not detected. Laboratory result is less than 1 % asbestos PC = Point Count Analysis lin. ft. = linear feet CH = Chrysotile Asbestos sq. ft. = square feet

Table 2 - Summary of Sample Descriptions and Asbestos Laboratory Results, 800 Wildwood Ave. Jackson, Michigan

Asbestos Containing Material (ACM) is defined as any material containing more than 1 percent asbestos as determined utilizing Polarized Light Microscopy.

Table 3 - Summary of Presumed Asbestos Containing Materials, 800 Wildwood Ave. Jackson, Michigan

Asbestos Containing Material Description and Location

Location Material Description Friable Condition Material Type Approx. Quantity

No Presumed Asbestos Containing Materials Identified

Material Types Abbreviations

M = Miscellaneous building material lin. ft. = linear feet TSI = Thermal System Insulation sq. ft. = square feet S = Surfacing Material

Table 4 - Summary of All Asbestos Containing Materials, 800 Wildwood Ave. Jackson, Michigan

Interior - Asbestos Containing Materials

Location Material Description Friable Approx. Quantity

Hall, Bath 1 & Bath 2 Drywall Joint Compound Yes 728 sq. ft.

Total 728 sq. ft.

A1 12” x 12” Brown VFT with Mastic No 832 sq. ft.

Total 832 sq. ft.

A1 (2 windows 72” wide x 72” tall) A1, Bath 2 (3 windows 60” wide x 60” tall) Hall (1 window 36” wide x 84” tall)

Glazing Yes 6 Windows

Total 6 Windows

Abbreviations lin. ft. = linear feet

sq. ft. = square feet

Shaded/Bolded = Friable ACM and any Category I and Category II non-friable ACM that has a high probability of becoming crumbled, pulverized, or reduced to powder by the demolition or renovation activities that must be properly abated prior to commencement of any demolition/renovation activities.

Demolition/renovation activities completed with intact Category I non-friable ACM are regulated by OSHA and must be completed following the OSHA Asbestos Standards for Construction (29 CFR 1926.1101) which limits employee exposure to asbestos.

Please note that a Negative Pressure Enclosure must be utilized during abatement when Site Conditions Warrant. Examples of these conditions include the abatement of Plaster and Vermiculite insulation, HVAC Duct Wrap in Poor Condition, and Air-O-Cell/Mag Pipe Wrap. Conditions outside of these should be assessed on a case by case basis during the Asbestos Abatement Contractors site walk and Work Plan Preparation.

800 Wildwood- Demolition Special Conditions.docx

To: Kari Kerstetter, Purchasing Department

From: Neighborhood & Economic Operations Dept.Community Development Department

Date: 05-0610-13-265

Re: Please solicit bids for demolition of the following property as soon as possible.

Property Address: 521 Wildwood Ave800 Wildwood

Parcel Number: 2-0768000002-006600000

Sq Ft: 10064947 sq. ft. (commercialhouse)

Special Conditions to include:

1) Hazardous materials must be abated in accordance with MIOSHA and DEQ regulations and the attached Pre-Demolition Compliance Survey assessment.

2) Compact all clean backfill material with a hoe-pack or vibrating roller compactor.

3) Remove: ( _ _21/2) of double wide approac: h_ curb(s) cut(s) and entry approach(s). (1-40’12 / 1-28’ lineal feet)

4) Install _ __7840 _ lineal feet of curb and gutter (44’ & 34’).(. to reduce W half of approach to single approach with 16’ throat as marked on site) If road is in disrepair will need to be cut street and have forms installed to form front gutter pan and then have road repaired with hot patch asphalt upon completion of concrete work.

5) Remove and replace _ 7078 lineal feet (6’ wide to match walks to E and W) _of cracked, heaved and broken public sidewalks.

See enclosed water and sewer service records for approximate location and any special instructions for shared services. If no service card is provided it is the contractor’s responsibility to insure that neighboring water and sewer services are operational at the conclusion of the demolition.

6)

7) Trees/shrubs: Remove all trees, brush overgrowth from south and trim along S chain link fence. Remove all brush/trees and overgrowth along E and W property line with exception of 1 large tree S of the home along the E line. Note remove brush from each side of fence to the SW. Leave 1 large tree to the NE corner. All other trees, stumps, brush and overgrowth to be removed to fully clean property along east and south property lines. . Remove stump from S ROW area. Plant 2 Japanese Lilac of 2 ½” caliper in

Wildwood ROW area

Trim remaining trees minimum 10’-12’ above grade. Plant 2 – 2 ½” caliper Japanese Lilac trees evenly spaced to the south side of the new sidewalk along Wildwood Ave. Center trees 3’ from back of sidewalk

8)

Miscellaneous: Remove chain link fencing to the east and south ex Saw cut driveway from north to south to allow for removal of all hard surfaces from 521 Wildwood. See paint markings on site. Note, any damage to adjacent W property will be the responsibility of the demolition contractor to replace. Use caution with trucks and equipment so as not to damage adjacent driveway areas. Remove rocks to NE corner. Level all grades to blend with adjacent grades. Provide 3” top soil, seed, straw and have final grade and soils verified by inspection prior to straw cover. Regrade full site to smooth all grades and to blend with all surrounding elevations. chain link fence to N and W. Remove all asphalt and concrete from full site to public walks. Saw cut along all walks to prevent damage. Obtain MDOT approval for work in the N. West ROW area and obtain any required permits or detour plans from MDOT for work in the MDOT ROW.