8-3202600075 Attachment 7 - Project Drawings.pdf

PDF 3 MB Posted

Attached to
RFP 3202600075 Trinity IT Closet HVAC
Solicitation number
3202600075
Issued by
Travis County, Austin City, Texas

About this file

This document is a set of project drawings for mechanical HVAC upgrades at the Texas Workforce Commission (TWC) Trinity Building located at 1117 Trinity Street, Austin, Texas 78701. The project involves the installation of Variable Air Volume (VAV) terminal units with associated control components across five floors of the facility to upgrade HVAC systems in IT rooms. The scope includes demolition of existing ductwork, installation of new medium and low-pressure ductwork, supply and return air diffusers, fire dampers, and integration of new VAV units into the existing Building Automation System (BAS). The drawings indicate installation of multiple VAV units per floor: Floor 1 includes 19 VAV units, Floor 2 includes 17 VAV units, Floor 3 includes 16 VAV units, Floor 4 includes 13 VAV units, and Floor 5 includes 13 VAV units, for a total of 78 VAV terminal units. The project drawings are preliminary and not intended for construction, bidding, or permit purposes as of the October 31, 2025 issue date. All ductwork from the air handling unit (AHU) to terminal units shall be medium-pressure ductwork, with low-pressure ductwork downstream of terminal units and medium-pressure return ductwork throughout.

The drawings specify that all fire dampers must have a 1.5-hour rating and be installed in strict accordance with manufacturer's instructions to maintain UL listing approval. An NEBB, TABB, or AABC certified contractor shall balance all airside and waterside systems to within +10% to -5% of quantities and flowrates shown, with a certified testing and balancing report required for engineer approval. All new thermostats shall be electronic, programmable type with time-of-day scheduling capabilities, minimum seven-day programs, four cycles per day, automatic heating/cooling changeover, and setpoint control, with WiFi capability where indicated. Each VAV terminal unit shall be controlled by a separate temperature sensor or thermostat, and the controls contractor is responsible for providing all control components, control and low-voltage wiring, and required conduit, with 120-volt power for the control system provided by the electrical contractor. The mechanical contractor must coordinate with TWC staff for required utility outages and coordinate terminal unit installation with 24 inches minimum clearance depth at controls access enclosures. The project references current Texas Workforce Commission Standard Construction Specifications and ASHRAE Guideline 36 for high-performing sequences of operation.

View the file

Other files

Show all 13

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

TRINITY - IT

ROOM HVAC

UPGRADES

1117 Trinity St.

Austin, TX.

78701

DRAWN BY:

CHECKED BY:

Mark E. Mikulin

107561

PRELIMINARY

Not Intended for Construction, Bidding or Permit. This document is released under the authority of:

Registrant's Name:

Serial No.

State of Registration Firm Registration No.

EEA Project No.

6615 Vaught Ranch Road #100 Austin, Texas 78730-2314 USA

512.744.4400 main - 512.744.4444 fax www.eeace.com

CONSULTING

ENGINEERS

P20250347

F-2497

TX

GENERAL MECHANICAL NOTES

1. COORDINATE LOCATION OF AIR DEVICES WITH ARCHITECTURAL REFLECTED CEILING PLANS. TO ACHIEVE THE BEST COMBINATION OF

PERFORMANCE AND AESTHETICS, THE FINAL LOCATIONS OF AIR DEVICES SHALL BE DETERMINED FROM THE ARCHITECTURAL REFLECTED CEILING PLANS. NO CHANGES TO AIR DEVICE LOCATIONS SHALL BE MADE WITHOUT PRIOR APPROVAL OF THE ARCHITECT AND ENGINEER. SPRAY PAINT INTERIOR OF DUCTWORK BEHIND OR ABOVE AIR DEVICES TO 12" INSIDE DUCTWORK OPENING WITH FLAT BLACK PAINT TO OBSCURE DUCT INTERIOR. LOCATE LOUVERED RETURN GRILLE BLADES SUCH THAT VISION INTO DUCT INTERIOR IS

RESTRICTED.

2. ALL DUCT SIZES ARE INSIDE CLEAR DIMENSIONS IN INCHES.

3. BALANCING DAMPERS ARE REQUIRED AT ALL SUPPLY, RETURN, AND EXHAUST BRANCH CONNECTIONS. REMOTE DAMPER OPERATOR

FOR ALL DAMPERS LOCATED ABOVE HARD OR INACCESSIBLE CEILINGS.

4. FLEX DUCT AND ROUND CONNECTIONS TO MAIN DUCT OR BRANCH DUCTS SHALL BE MADE VIA SPIN-IN OR DOVE-TAILED CONICAL TAPS

WITH DAMPERS. ALL RECTANGULAR DUCT BRANCHES TAP TO BE MADE WITH 45 DEG SMACNA TAP FITTING.

5. ROUTE ALL SUPPLY AIR DUCT TIGHT TO STRUCTURE UNLESS OTHERWISE NOTED. MAKE TRANSITIONS FLAT ON TOP.

6. FURNISH AND INSTALL ALL MITERED ELBOWS WITH TURNING VANES. RADIUSED RECTANGULAR ELBOWS SHALL HAVE CENTER LINE

RADIUS TO WIDTH RATIO (R/W) OF 1.5 UNLESS OTHERWISE SPECIFIED. ALL ROUND ELBOWS SHALL HAVE A CENTERLINE RADIUS TO DIAMETER RATIO (R/D) OF 1.5 UNLESS SHORT RADIUS ELBOWS ARE CALLED FOR ON THE PLANS IN WHICH CASE THE R/D RATIO SHALL

BE 1.0.

7. FLEXIBLE DUCTS SHALL NOT EXCEED 5' IN LENGTH. DUCT SHALL HAVE AN INTERNAL DIMENSION EQUAL TO THE CONNECTING ROUND

DUCT DIMENSION.

8. INSULATE EXTERIOR OF ALL SUPPLY AIR DIFFUSERS.

9. FLEXIBLE COLLARS SHALL BE FURNISHED AND INSTALLED AT ALL CONNECTIONS BETWEEN VIBRATING EQUIPMENT (FANS, AIR

HANDLERS, ROOFTOP UNITS, ETC.) AND DUCTS OR CASINGS. ALSO FURNISH AND INSTALL FLEXIBLE CONNECTIONS WHERE DUCTS

CROSS BUILDING EXPANSION JOINTS.

10. LINED RETURN AIR TRANSFER BOOTS SHALL BE INSTALLED THROUGH WALLS AS REQUIRED TO PROVIDE A CONTINUOUS RETURN AIR

PATH TO THE AIR HANDLING UNITS.

11. PROVIDE FIRE DAMPERS, SMOKE DAMPERS, AND COMBINATION FIRE/SMOKE DAMPERS WHERE SHOWN ON THE PLANS AND WHERE DUCTWORK PENETRATES FLOORS, FIRE WALLS AND HVAC CHASES REQUIRING PROTECTION IF NOT OTHERWISE SHOWN. ALL FIRE DAMPERS SHALL HAVE A 1.5 HOUR RATING UNLESS NOTED OTHERWISE. ENDS OF DAMPER SHAFTS SHALL BE SCORED TO INDICATE OPEN/CLOSED POSITION. PROVIDE FSD'S WITH OPTIONAL NO-FLOW RATED DUCT SMOKE DETECTOR. INSTALL FD'S, SD'S AND FSD'S IN STRICT ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS IN ORDER TO MAINTAIN THEIR UL LISTING. PROVIDE, INSTALL AND LABEL

MINIMUM 14" X 14" DUCT ACCESS DOORS WITHIN 12" OF ALL FD, SD, AND FSD LOCATIONS.

12. AN NEBB, TABB, OR AABC CERTIFIED CONTRACTOR SHALL BALANCE ALL AIRSIDE AND WATERSIDE SYSTEMS, INCLUDING ROOM PRESSURE CASCADE DIFFERENTIAL PRESSURES, TO WITHIN +10%/-5% OF THE QUANTITIES AND FLOWRATES SHOWN ON THE DRAWINGS. FURNISH A CERTIFIED TESTING AND BALANCING REPORT TO THE ENGINEER FOR REVIEW AND APPROVAL.

13. PROVIDE AND INSTALL A LABEL ON THE CEILING GRID OR WALL DIRECTLY UNDER OR ADJACENT TO ALL CONCEALED MECHANICAL EQUIPMENT, ISOLATION VALVES, AND CONTROL DEVICES. THE LABEL SHALL CONTAIN EQUIPMENT TAG NUMBER AND POWER SOURCE (IF APPLICABLE), ISOLATION VALVE SIZE AND SYSTEM, OR CONTROL ELEMENT IDENTIFICATION NUMBER.

GENERAL MECHANICAL DEMO NOTES

1. EXISTING EQUIPMENT, DUCTWORK & PIPING LOCATIONS AND SIZES HAVE BEEN OBTAINED FROM ORIGINAL CONSTRUCTION DRAWINGS

AND FIELD INVESTIGATIONS AND ARE SCHEMATIC IN NATURE. FIELD VERIFY LOCATIONS AND SIZES.

2. ITEMS SHOWN LIGHT ARE EXISTING TO REMAIN. ITEMS SHOWN BOLD AND DASHED ARE EXISTING TO BE REMOVED.

3. DEMOLITION OF ALL DUCTWORK SHALL INCLUDE ALL SUPPORTS, HANGERS, INSULATION, THERMOSTATS, AND FIRE DAMPERS UNLESS

OTHERWISE NOTED.

4. REMOVE MECHANICAL EQUIPMENT AND RETURN TO OWNER FOR RIGHT OF FIRST REFUSAL. DELIVER ACCEPTED ITEMS TO OWNER

DESIGNATED LOCATION. ITEMS NOT KEPT BY OWNER SHALL BE STORED AND DISPOSED OF OFF SITE ACCORDING TO LOCAL

REGULATIONS.

5. THE CONTRACTOR IS RESPONSIBLE FOR THE PROTECTION OF ALL EXISTING UTILITIES AND FINISHES NOT BEING REPLACED OR

REMOVED.

GENERAL CONTROLS NOTES

1. CONTROLS CONTRACTOR TO REVIEW DRAWINGS FOR ADDITIONAL BAS INTEGRATION REQUIREMENTS INCLUDING PROVISIONS IN DDC

PANEL LOCATIONS AND POWER.

2. ALL NEW THERMOSTATS SHOWN SHALL BE ELECTRONIC, PROGRAMMABLE TYPE CAPABLE OF TIME-OF-DAY SCHEDULING WITH

MINIMUM OF 7 DAY PROGRAMS AND 4 CYCLES PER DAY, AUTOMATIC HEATING/COOLING CHANGEOVER, AND SETPOINT CONTROL.

INCLUDE WIFI CAPABILITY WHERE SHOWN ON PLANS.

3. EACH VAV TERMINAL UNIT SHALL BE CONTROLLED BY A SEPARATE TEMPERATURE SENSOR/THERMOSTAT.

4. ALL WALL MOUNTED ROOM THERMOSTATS SHALL BE LOCATED 48" A.F.F. SO LONG AS OBSTRUCTIONS ARE 20" DEEP OR LESS. ALL

OTHER CONDITIONS TO BE REVIEWED. THEY SHALL BE CENTERED ADJACENT TO LIGHT SWITCHES WHERE BOTH OCCUR IN THE SAME LOCATION. WHERE LOCATED ON COLUMN, THERMOSTAT SHALL BE CENTERED. TEMPERATURE SENSORS SHALL BE MOUNTED AT 70" A.F.F. SENSORS MOUNTED ON EXTERIOR COLUMNS SHALL BE MOUNTED ON INSULATED BASES. CONFIRM EXACT LOCATIONS OF THERMOSTATS WITH OWNER. THE MECHANICAL CONTRACTOR IS TO COORDINATE WITH THE OWNER AND PROGRAM ALL

THERMOSTATS TO OWNER'S SPECIFIC SCHEDULE (IF APPLICABLE).

MECHANICAL ABBREVIATIONS

DESCRIPTION AAB DESCRIPTION AAB

ABOVE CEILING A/C HUB DRAIN HD

ABOVE FINISHED FLOOR AFF INCHES PER HOUR IN/HR

ABOVE GRADE. GROUND AG INDIRECT DRAIN/ RECEPTOR ID

ACCESS PANEL AP INDIRECT WASTE IW

ACRYLONITRILE BUTADIENE STYTENE ABS INVERT ELEVATION IE

AIR ADMITTANCE VALVE AAV LAVATORY LAV

ARCHITECT ARCH MAN HOLE MH

AUTHORITY HAVING JURISDICTION AHJ MAXIMUM MAX

BACKFLOW PREVENTER BFP MECHANICAL MECH

BELOW FINISHED FLOOR BFF MINIMUM MIN

BELOW FLOOR B/F MIXING VALVE MV

BELOW GRADE/ GROUND BG MOP SINK MS

BELOW SLAB B/S NORMALLY CLOSED NC

BOTTOM OF PIPE BOP NORMALLY OPEN NO

BRAKE HORSEPOWER BHP NOT IN CONTRACT NIC

BRITISH THERMAL UNIT BTUH NOT TO SCALE NTS

BTUH ( THOUSANDS ) MBH EXISTING TO BE PROTECTED IN PLACE (P)

CAST IRON CI POLYETHYLENE PE

CELCIUS C POLYETHYLENE CROSS-LINKED PEX

CHILLED WATER RETURN CHWR POLYVINYL CHLORIDE PVC

CHILLED WATER SUPPLY CHWS POLYVYLIDENE FLOURIDE/ DIOFLOURIDE PVDF

CHLORINATED POLYVINYL CHLORIDE CPVC POUND LB

CLEANOUT CO POUNDS PER SQUARE INCH PSI

CLEANOUT, FLOOR FCO POUNDS PER SQUARE INCH ABSOLUTE PSIA

CLEANOUT, GRADE GCO POUNDS PER SQUARE INCH GAUGE PSIG

CLEANOUT, GRADE TWO-WAY DGCO PRESSURE DROP PD

CLEANOUT, WALL WCO PRESSURE REDUCING VALVE PRV

CLEANOUT, YARD YCO PUMP, BOOSTER BP

CLEANOUT, YARD TWO-WAY DYCO PUMP, CHILLED WATER CHWP

CONDENSER RETURN CWR PUMP, CIRCULATION CP

CONDENSER SUPPLY CWS PUMP, HOT WATER HWP

COPPER CU REDUCED PRESSURE ZONE RPZ

CUBIC FEET CF EXISTING TO BE RELOCATED (R)

CUBIC FEET PER HOUR CFH REVOLUTION PER MINUTE RPM

CUBIC FEET PER MINUTE CFM SCHEDULE SCH

EXISTING TO BE DEMOLISHED/ REMOVED (D) SHOWER SH

DEGREE D SINK SK

DIAMETER DIA SQUARE FEET SF

DRAIN, AREA AD STRUCTURAL STRUC

DRAIN, FLOOR FD TEMPERATURE TEMP

DRAIN, ROOF PRIMARY RD TEMPERATURE, ENTERING WATER EWT

DRAIN, ROOF SECONDARY SRD TEMPERATURE, LEAVING WATER LWT

ELECTRICAL ELEC THERMOSTATIC MIXING VALVE TMV

ELEVATION ELEV TOP OF PIPE TOP

EXISTING EXIST, (E) TRAP PRIMER TP

FAHRENHEIT F TYPICAL TYP

FAT, OIL, AND GAS FOG ULTRAVIOLET UV

FOOT/ FEET FT UNDERGROUND UG

FEET PER MINUTE FPM UNIT, AIR HANDLING AHU

FEET PER SECOND FPS UNIT, FAN COIL FC

FIXTURE UNIT FU UNLESS NOTED OTHERWISE UNO

FLEXIBLE FLEX UP/ DOWN UP/DN

FLOOR FLR VACUUM BREAKER VB

FLOOR DRAIN FD VALVE FLOW COEFFICIENT CV

FLOOR SINK FS VENT THRU ROOF VTR

FUTURE (F) WATER GAUGE WG

GALLON GAL WATER CLOSET WC

GALLONS PER HOUR GPH WATER HAMMER ARRESTOR WHA

GALLONS PER MINUTE GPM WATER, OIL, AND GAS WOG

HEAD IN FEET FTHD

HEAD IN INCHES WATER COLUMN INWC ELECTRICAL

HEATING HOT WATER RETURN HWR VOLTAGE V, VOLT

HEATING HOT WATER SUPPLY HWS WATTAGE W, WATT

HEATING, VENTILATION, AIR CONDITIONING HVAC KILOWATT KW

HORSEPOWER HP PHASE PH

HOUR HR AMPERE A, AMP

CODE AND REGULATORIES ABBREVIATIONS

DESCRIPTION AAB DESCRIPTION AAB

AMERICAN NATIONAL STANDARDS ANSI INTERNATIONAL ENERGY CONSERVATION CODE IECC

AMERICAN SOCIETY OF CIVIL ENGINEERS ASCE INTERNATIONAL FIRE CODE IFC

AMERICAN SOCIETY OF HEATING, REFRIGERATING

AND

AIR-CONDITIONING ENGINEERS

ASHRAE INTERNATIONAL FUEL GAS CODE IFGC

AMERICAN SOCIETY OF MECHANICAL ENGINEERS ASME INTERNATIONAL MECHANICAL CODE IMC

AMERICAN SOCIETY OF PLUMBING ENIGNEERS ASPE INTERNATIONAL PLUMBING CODE IPC

AMERICAN SOCIETY OF SANITARY ENGINEERING ASSE INTERNATIONAL RESIDENTIAL CODE IRC

AMERICAN SOCIETY OF TESTING AND MATERIALS ASTM NATIONAL ELECTRICAL CODE NEC

AMERICAN WATER WORKS ASSOCIATION AWWA NATIONAL FIRE PROTECTION ASSOCIATION NFPA

CAST IRON SOIL PIPE INSTITUTE CISPI UNIFORM BUILDING CODE UBC

FACTORY MUTAL FM UNIFORM FIRE CODE UFC

INSTITUTE OF ELECTRICAL AND ELECTRONICS

ENGINEERS IEEE UNIFORM PLUMBING CODE UPC

INTERNATIONAL ASSOCIATION OF PLUMBING AND

MECHANICAL OFFICIALS IAPMO UNDERWRITERS LABORATORIES UL

INTERNATIONAL BUILDING CODE IBC

AutoCAD SHX Text

MECHANICAL GENERAL NOTES

AutoCAD SHX Text M0.0

AutoCAD SHX Text

CONFIDENCE AND SHALL NOT BE MADE AVAILABLE,

AutoCAD SHX Text

EXCEPT AS MAY BE OTHERWISE PROVIDED BY CONTRACT,

AutoCAD SHX Text

THESE DRAWINGS AND SPECIFICATIONS ARE PROPERTY

AutoCAD SHX Text

OF THE CLIENT LISTED, AND ARE ISSUED IN STRICT

AutoCAD SHX Text

REPRODUCED, OR COPIED, OR USED FOR ANY OTHER

AutoCAD SHX Text

INTENDED PURPOSE, OR AS BASIS FOR MANUFACTURE

AutoCAD SHX Text

OR SALE OF APARATUS WITHOUT WRITTEN PERMISSION.

AutoCAD SHX Text

CONFIDENTIAL AND PROPRIETARY

AutoCAD SHX Text

SHEET NUMBER:

AutoCAD SHX Text

SHEET NAME:

AutoCAD SHX Text

PROJECT NUMBER:

AutoCAD SHX Text

ISSUE DATE:

AutoCAD SHX Text

REVISIONS:

AutoCAD SHX Text

SEAL(S) / CONSULTANT:

AutoCAD SHX Text

CLIENT / PROJECT NAME:

AutoCAD SHX Text 21-1062.00

AutoCAD SHX Text

OCTOBER 31, 2025

MECHANICAL TWO-LINE DIAGRAM

SHORT ROUND ELBOW (45° & 90°)

RECTANGULAR ELBOW (45° & 90°)

LONG ROUND ELBOW (45° & 90°)

RECTANGULAR/ROUND RETURN DUCT UP

RECTANGULAR/ROUND RETURN DUCT DOWN

RECTANGULAR/ROUND SUPPLY DUCT UP

RECTANGULAR/ROUND SUPPLY DUCT DOWN

CONCENTRIC REDUCER, DUCT TRANSITION

DUCT TRANSITION (SQUARE TO ROUND)

DUCT CAP

SOUND ATTENUATOR

90° RECTANGULAR TURNING VANE

TRANSFER DUCT w/ INTERNAL LINING

(ROUND TO ROUND, SQUARE TO SQUARE)

ECCENTRIC REDUCER, DUCT TRANSITION

(ROUND TO ROUND, SQUARE TO SQUARE)

FITTING)

SIDEWALL REGISTER TAP

BRANCH DUCT TAP (w/ SMACNA 45°

SPIN-IN DUCT TAP

CONICAL DUCT TAP

INTERNAL DUCT LINING

IN DIRECTION OF AIRFLOW

CHANGE OF ELEVATION (RISE OR DROP)

D

R

DIRECTION OF FLOW

SHOWN (DIMENSIONS ARE INSIDE CLEAR)

DUCT SIZE, FIRST FIGURE IS SIDE

FLEXIBLE DUCT DIFFUSER DROP

CENTERLINE RADIUS = 1.5 * WIDTH

CENTERLINE RADIUS = 1.0 * WIDTH

X

30x12

DAMPERS

EQUIPMENT TAG

DIFFUSER TAG

MECHANICAL TAGS

EXISTING TO REMAIN (E)

NEW WORK

LINETYPE LEGEND

DEMOLITION (D)

SLOT DIFFUSER

GRILLES, REGISTERS, & DIFFUSERS

DUCTED EXHAUST/RETURN REGISTER, CEILING

RETURN GRILLE TO CEILING PLENUM

SUPPLY DIFFUSER, CEILING

EXHAUST/RETURN GRILLE OR REGISTER,

SIDEWALL

SUPPLY GRILLE OR REGISTER, SIDEWALL

HEPA FILTERS

SUPPLY DIFFUSER, CEILING, THERMAFUSER

VD

VD

X 500 X"

TYP. X

CFMTYPE

NECK

SIZE No. OF

DIFFUSERS

TYPE/MARK (SEE SCHEDULE)

EXISTING EQUIPMENT TO REMAIN

EXISTING EQUIPMENT TO BE RELOCATED

AREA OF

#/M#-#

DETAIL

ENLARGED

M-#

M#-#

GENERAL SYMBOLS

DETAIL NO.

LONGITUDINAL OR

CROSS SECTION NO.

SHEET NO. ON WHICH

CUTTING PLANE

DIRECTION OF

SECTION IS DRAWN

SHEET ON WHICH

DETAIL IS DRAWN

DETAIL NO.

SCALE OF SECTION, DETAIL OR DRAWING

SECTION OR DETAIL NO.

DRAWING TITLE

# 1/8" = 1'-0"

FLOOR PLAN

POINT OF DEMARCATION/ DISCONNECT

POINT OF CONNECTION

REVISION NUMBER

NEW CONSTRUCTION KEYED NOTE

INDICATED PLAN NORTH

ENLARGED CALL OUT

DETAIL REFRENCE CALL OUT

CROSS SECTION CALL OUT

SECTION/DETAIL CALL OUT

SHEET ON WHICH

ENLARGED DETAIL

IS DRAWN

M#-#

SURFACE SHOWN

SHEET ON WHICH

ELEVATION IS DRAWN

ELEVATION NO.

IN ELEVATION

ELEVATION CALL OUT

DIRECTION OF FLOW ARROW

SLOPE ARROW W/ PERCENTAGE

RISER DESIGNATION

PIPING TYPE

RISER NUMBER

P

PIPE CONTINUATION, SINGLE LINE

PIPE CONTINUATION, DOUBLE LINE

1%

HUMIDITY SENSOR

TEMPERATURE & CO2 SENSOR

TEMPERATURE & HUMIDITY SENSOR

TEMPERATURE SENSOR

THERMOSTAT

HUMIDISTAT

TS

HS

TC

TH

T

H

MECHANICAL DEVICES

M D

SMOKE DAMPER

FIRE DAMPER

COMBINATION FIRE/SMOKE

DAMPER

BACKDRAFT

DAMPER

MOTORIZED DAMPER

MANUAL DAMPER

MECHANICAL TWO-LINE DIAGRAM

CO2 SENSOR CO

SLOT DIFFUSER - CONTINUOUS

RECTANGULAR/ROUND EXHAUST DUCT UP

RECTANGULAR/ROUND EXHAUST DUCT DOWN

(ROUND TO SQUARE, SQUARE TO ROUND)

(ROUND TO SQUARE, SQUARE TO ROUND)

20"Ø (E)

20"Ø SA

20"Ø (D)

MECHANICAL SHEET INDEX

SHEET

NUMBER SHEET DESCRIPTION

M0.0 MECHANICAL GENERAL NOTES

M0.1 MECHANICAL SYMBOLS AND LEGENDS

M1.0 1ST FLOOR DEMO WORK PLAN

M1.1 2ND FLOOR DEMO WORK PLAN

M2.0 1ST FLOOR DEMO WORK PLAN

M2.1 2ND FLOOR NEW WORK PLAN

M2.2 3RD FLOOR NEW WORK PLAN

M2.3 4TH FLOOR NEW WORK PLAN

M2.4 5TH FLOOR NEW WORK PLAN

M3.0 MECHANICAL SCHEDULES & DETAILS

M4.0 MECHANICAL CONTROLS

X-1

(E)X-1

(R)X-1

SUPPLY AIR SA

DUCT ABBREVIATIONS:

RETURN AIR RA

OUTSIDE AIR OA

PRIMARY SUPPLY AIR COLD DECK PSAC

PRIMARY SUPPLY AIR HOT DECK PSAH

TRINITY - IT

ROOM HVAC

UPGRADES

1117 Trinity St.

Austin, TX.

78701

DRAWN BY:

CHECKED BY:

Mark E. Mikulin

107561

PRELIMINARY

Not Intended for Construction, Bidding or Permit. This document is released under the authority of:

Registrant's Name:

Serial No.

State of Registration Firm Registration No.

EEA Project No.

6615 Vaught Ranch Road #100 Austin, Texas 78730-2314 USA

512.744.4400 main - 512.744.4444 fax www.eeace.com

CONSULTING

ENGINEERS

P20250347

F-2497

TX

AutoCAD SHX Text

NORTH

AutoCAD SHX Text

CONFIDENCE AND SHALL NOT BE MADE AVAILABLE,

AutoCAD SHX Text

EXCEPT AS MAY BE OTHERWISE PROVIDED BY CONTRACT,

AutoCAD SHX Text

THESE DRAWINGS AND SPECIFICATIONS ARE PROPERTY

AutoCAD SHX Text

OF THE CLIENT LISTED, AND ARE ISSUED IN STRICT

AutoCAD SHX Text

REPRODUCED, OR COPIED, OR USED FOR ANY OTHER

AutoCAD SHX Text

INTENDED PURPOSE, OR AS BASIS FOR MANUFACTURE

AutoCAD SHX Text

OR SALE OF APARATUS WITHOUT WRITTEN PERMISSION.

AutoCAD SHX Text

CONFIDENTIAL AND PROPRIETARY

AutoCAD SHX Text

SHEET NUMBER:

AutoCAD SHX Text

SHEET NAME:

AutoCAD SHX Text

PROJECT NUMBER:

AutoCAD SHX Text

ISSUE DATE:

AutoCAD SHX Text

REVISIONS:

AutoCAD SHX Text

SEAL(S) / CONSULTANT:

AutoCAD SHX Text

CLIENT / PROJECT NAME:

AutoCAD SHX Text 21-1062.00

AutoCAD SHX Text

OCTOBER 31, 2025

AutoCAD SHX Text

MECHANICAL SYMBOLS AND LEGENDS

M0.1

Elev.

Elev.D ow nU p U p

D ow n

107T

7T

104CT 104DT

104BT

104T 114T 120T 124T

130T

119T

115T

113T111T

109T

101T

1C

T 144CT 144DT 144ET

144T

144AT 121AT

130FT

144T

1B

T

4F

T

4G T

4B

T

1A

T

0E

T

0A

T

0B T

0C

T

0D T

143T

101ET

6T

4A

T

4A

T

114BT

126AT

S1 90 6" Ø

S1 80 6" Ø

S2 80 8 X 6

S1 100 8" Ø

14x12 22x12

10x128x12 16 x1 x1 x1 x1 x2 x1 x1

8x

8x

1117 Trinity St.

Austin, TX.

78701

DRAWN BY:

CHECKED BY:

Mark E. Mikulin

107561

PRELIMINARY

Not Intended for Construction, Bidding or Permit. This document is released under the authority of:

Registrant's Name:

Serial No.

State of Registration Firm Registration No.

EEA Project No.

6615 Vaught Ranch Road #100 Austin, Texas 78730-2314 USA

512.744.4400 main - 512.744.4444 fax www.eeace.com

CONSULTING

ENGINEERS

P20250347

F-2497

TX

TRINITY - IT

ROOM HVAC

UPGRADES

A. REFER TO CURRENT TEXAS WORKFORCE COMMISSION

STANDARD CONSTRUCTION SPECIFICATIONS FOR ADDITIONAL

MATERIAL AND INSTALLATION INFORMATION.

B. REFER TO SCHEDULES, SEQUENCE OF OPERATION, AND DETAILS

FOR ADDITIONAL INFORMATION.

C. DEMOLISH EXISTING DUCTWORK, SUPPORTS, FLEX DUCT, AIR

DEVICES, AND SENSORS UNLESS OTHERWISE INDICATED.

GENERAL NOTES:

MECHANICAL DEMOLITION PLAN - 1ST FLOOR

SCALE: 1/8" - 1'-0"

KEYED NOTES: X

1. REMOVE EXISTING DUCTWORK IN ROOM 219 (IT) BACK TO MAIN DUCT.

CAP AT MAIN.

AutoCAD SHX Text

CONFIDENCE AND SHALL NOT BE MADE AVAILABLE,

AutoCAD SHX Text

EXCEPT AS MAY BE OTHERWISE PROVIDED BY CONTRACT,

AutoCAD SHX Text

THESE DRAWINGS AND SPECIFICATIONS ARE PROPERTY

AutoCAD SHX Text

OF THE CLIENT LISTED, AND ARE ISSUED IN STRICT

AutoCAD SHX Text

REPRODUCED, OR COPIED, OR USED FOR ANY OTHER

AutoCAD SHX Text

INTENDED PURPOSE, OR AS BASIS FOR MANUFACTURE

AutoCAD SHX Text

OR SALE OF APARATUS WITHOUT WRITTEN PERMISSION.

AutoCAD SHX Text

CONFIDENTIAL AND PROPRIETARY

AutoCAD SHX Text

SHEET NUMBER:

AutoCAD SHX Text

SHEET NAME:

AutoCAD SHX Text

PROJECT NUMBER:

AutoCAD SHX Text

ISSUE DATE:

AutoCAD SHX Text

REVISIONS:

AutoCAD SHX Text

SEAL(S) / CONSULTANT:

AutoCAD SHX Text

CLIENT / PROJECT NAME:

AutoCAD SHX Text 21-1062.00

AutoCAD SHX Text

OCTOBER 31, 2025

AutoCAD SHX Text

1ST FLOOR DEMO WORK PLAN

AutoCAD SHX Text

PLAN NORTH

M1.0

Elevator 1

ELEV. 1

Elevator 2 Elevator 3

LOBBY

CORR

CORR

OPEN OFFICE

OPEN OFFICE

202A

OFFICE

212A

OFFICE

212B

OFFICE 212C

OFFICE

234E

OFFICE

234D

OFFICE

234C

OFFICE

234B

OFFICE

234A

OFFICE

242D

OFFICE

252C

OFFICE

252A

OFFICE

242B

OFFICE

242A

OFFICE

252E

OFFICE

252D

OFFICE

OPEN OFFICE

OPEN OFFICE

ELEC

IT

MECHANICAL

STAIR207

STAIR

JAN

TELEPHONE

WOMEN

MEN

252B

OFFICE

CORR

OFFICE

226B

OFFICE

226A

BREAK

226C

CONFERENCE

226D

OPEN OFFICE

OPEN OFFICE

OPEN OFFICE

78701

DRAWN BY:

CHECKED BY:

Mark E. Mikulin

107561

PRELIMINARY

Not Intended for Construction, Bidding or Permit. This document is released under the authority of:

Registrant's Name:

Serial No.

State of Registration Firm Registration No.

EEA Project No.

6615 Vaught Ranch Road #100 Austin, Texas 78730-2314 USA

512.744.4400 main - 512.744.4444 fax www.eeace.com

CONSULTING

ENGINEERS

P20250347

F-2497

TX

TRINITY - IT

ROOM HVAC

UPGRADES

A. REFER TO CURRENT TEXAS WORKFORCE COMMISSION

STANDARD CONSTRUCTION SPECIFICATIONS FOR ADDITIONAL

MATERIAL AND INSTALLATION INFORMATION.

B. REFER TO SCHEDULES, SEQUENCE OF OPERATION, AND DETAILS

FOR ADDITIONAL INFORMATION.

C. DEMOLISH EXISTING DUCTWORK, SUPPORTS, FLEX DUCT, AIR

DEVICES, AND SENSORS UNLESS OTHERWISE INDICATED.

GENERAL NOTES:

MECHANICAL DEMOLITION PLAN - 2ND FLOOR

SCALE: 1/8" - 1'-0"

KEYED NOTES: X

1. REMOVE EXISTING DUCTWORK IN ROOM 219 (IT) BACK TO MAIN DUCT.

CAP AT MAIN.

AutoCAD SHX Text

CONFIDENCE AND SHALL NOT BE MADE AVAILABLE,

AutoCAD SHX Text

EXCEPT AS MAY BE OTHERWISE PROVIDED BY CONTRACT,

AutoCAD SHX Text

THESE DRAWINGS AND SPECIFICATIONS ARE PROPERTY

AutoCAD SHX Text

OF THE CLIENT LISTED, AND ARE ISSUED IN STRICT

AutoCAD SHX Text

REPRODUCED, OR COPIED, OR USED FOR ANY OTHER

AutoCAD SHX Text

INTENDED PURPOSE, OR AS BASIS FOR MANUFACTURE

AutoCAD SHX Text

OR SALE OF APARATUS WITHOUT WRITTEN PERMISSION.

AutoCAD SHX Text

CONFIDENTIAL AND PROPRIETARY

AutoCAD SHX Text

SHEET NUMBER:

AutoCAD SHX Text

SHEET NAME:

AutoCAD SHX Text

PROJECT NUMBER:

AutoCAD SHX Text

ISSUE DATE:

AutoCAD SHX Text

REVISIONS:

AutoCAD SHX Text

SEAL(S) / CONSULTANT:

AutoCAD SHX Text

CLIENT / PROJECT NAME:

AutoCAD SHX Text 21-1062.00

AutoCAD SHX Text

OCTOBER 31, 2025

AutoCAD SHX Text

2ND FLOOR DEMO WORK PLAN

AutoCAD SHX Text

PLAN NORTH

M1.1

Elev.

Elev.D ow nU p U p

D ow n

107T

7T

104CT 104DT

104BT

104T 114T 120T 124T

130T

119T

115T

113T111T

109T

101T

1C

T 144CT 144DT 144ET

144T

144AT 121AT

130FT

144T

1B

T

4F

T

4G T

4B

T

1A

T

0E

T

0A

T

0B T

0C

T

0D T

143T

101ET

6T

4A

T

4A

T

114BT

126AT

S1 90 6" Ø

S1 80 6" Ø

S2 80 8 X 6

S1 100 8" Ø

A3 600 14" X 10"

VAV-1-1

FD

R1 - 10" X 10"

FD

AHU-5

14x12 22x12

10x128x12 16 x1 x1 x1 x1 x2 x1 x1

8x

8x

10x10

R3 - 14" X 10" x1

Ø

78701

DRAWN BY:

CHECKED BY:

Mark E. Mikulin

107561

PRELIMINARY

Not Intended for Construction, Bidding or Permit. This document is released under the authority of:

Registrant's Name:

Serial No.

State of Registration Firm Registration No.

EEA Project No.

6615 Vaught Ranch Road #100 Austin, Texas 78730-2314 USA

512.744.4400 main - 512.744.4444 fax www.eeace.com

CONSULTING

ENGINEERS

P20250347

F-2497

TX

TRINITY - IT

ROOM HVAC

UPGRADES

MECHANICAL NEW WORK PLAN - 1ST FLOOR

SCALE: 1/8" - 1'-0"

A. REFER TO CURRENT TEXAS WORKFORCE COMMISSION STANDARD CONSTRUCTION

SPECIFICATIONS FOR ADDITIONAL MATERIAL AND INSTALLATION INFORMATION.

B. REFER TO SCHEDULES, SEQUENCE OF OPERATION, AND DETAILS FOR ADDITIONAL

INFORMATION.

C. COORDINATE WITH TWC STAFF FOR UTILITY OUTAGES REQUIRED FOR BUILDING

WORK.

D. 120V POWER FOR CONTROL SYSTEM TO BE PROVIDED BY ELECTRICAL

CONTRACTOR. CONTROLS CONTRACTOR IS RESPONSIBLE FOR PROVIDING AND

INSTALLING CONTROLS COMPONENTS, CONTROL AND LOW VOLTAGE WIRING AND

REQUIRED CONDUIT.

E. PROVIDE SINGLE INLET VAV UNITS WITH ONE NEW CONTROLLER AND DDC

THERMOSTAT EACH. INTEGRATE INTO EXISTING BAS SYSTEM.

F. ALL DUCTWORK FROM THE AHU TO A TERMINAL UNIT SHALL BE MEDIUM PRESSURE

DUCTWORK. ALL DUCTWORK AFTER THE TERMINAL UNIT SHALL BE LOW PRESSURE

DUCTWORK. RETURN DUCTWORK TO BE MEDIUM PRESSURE.

G. COORDINATE AND INSTALL TERMINAL UNITS WITH 24" MINIMUM CLEARANCE DEPTH

AT CONTROLS ACCESS ENCLOSURES.

GENERAL NOTES:

KEYED NOTES: X

1. COORDINATE AND INSTALL NEW VAV TERMINAL UNIT WITH ASSOCIATED CONTROL

COMPONENTS. INTEGRATE UNIT INTO EXISTING BUILDING AUTOMATION SYSTEM

(BAS).

2. ELECTRICAL CONTRACTOR TO CONNECT NEW VAV TERMINAL UNIT TO EXISTING

ELECTRICAL CIRCUIT ON THIS FLOOR.

3. MODIFY EXISTING SUPPLY DUCT PENETRATION. INSTALL 1.5-HR FIRE DAMPER IN

NEW RETURN AIR DUCT PENETRATIONS. PROVIDE ACCESS PANELS. INSTALL ALL

FIRE DAMPERS IN STRICT ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS IN

ORDER TO MAINTAIN U.L. APPROVAL OF THE ASSEMBLY. ASSEMBLY SHALL BE

RATED ACCORDING TO THE WALL RATING. INSTALL A FIRE DAMPER ACCESS DOOR

AT EACH DAMPER AND LABEL ACCESS DOOR.

4. INSTALL 1.5-HR FIRE DAMPER IN NEW SUPPLY AIR DUCT PENETRATIONS. SUPPLY

AIR DUCT PENETRATION SHALL BE COORDINATED AND INSTALLED BELOW

CONCRETE STRUCTURAL BEAM. PROVIDE ACCESS PANELS. INSTALL ALL FIRE

DAMPERS IN STRICT ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS IN

ORDER TO MAINTAIN U.L. APPROVAL OF THE ASSEMBLY. ASSEMBLY SHALL BE

RATED ACCORDING TO THE WALL RATING. INSTALL A FIRE DAMPER ACCESS DOOR

AT EACH DAMPER AND LABEL ACCESS DOOR.

AutoCAD SHX Text T

AutoCAD SHX Text

CONFIDENCE AND SHALL NOT BE MADE AVAILABLE,

AutoCAD SHX Text

EXCEPT AS MAY BE OTHERWISE PROVIDED BY CONTRACT,

AutoCAD SHX Text

THESE DRAWINGS AND SPECIFICATIONS ARE PROPERTY

AutoCAD SHX Text

OF THE CLIENT LISTED, AND ARE ISSUED IN STRICT

AutoCAD SHX Text

REPRODUCED, OR COPIED, OR USED FOR ANY OTHER

AutoCAD SHX Text

INTENDED PURPOSE, OR AS BASIS FOR MANUFACTURE

AutoCAD SHX Text

OR SALE OF APARATUS WITHOUT WRITTEN PERMISSION.

AutoCAD SHX Text

CONFIDENTIAL AND PROPRIETARY

AutoCAD SHX Text

SHEET NUMBER:

AutoCAD SHX Text

SHEET NAME:

AutoCAD SHX Text

PROJECT NUMBER:

AutoCAD SHX Text

ISSUE DATE:

AutoCAD SHX Text

REVISIONS:

AutoCAD SHX Text

SEAL(S) / CONSULTANT:

AutoCAD SHX Text

CLIENT / PROJECT NAME:

AutoCAD SHX Text 21-1062.00

AutoCAD SHX Text

OCTOBER 31, 2025

AutoCAD SHX Text

1ST FLOOR NEW WORK PLAN

AutoCAD SHX Text

PLAN NORTH

M2.0

ELEV. 1

Elevator 2 Elevator 3

LOBBY

CORR

CORR

OPEN OFFICE

OPEN OFFICE

202A

OFFICE

212A

OFFICE

212B

OFFICE 212C

OFFICE

234E

OFFICE

234D

OFFICE

234C

OFFICE

234B

OFFICE

234A

OFFICE

242D

OFFICE

252C

OFFICE

252A

OFFICE

242B

OFFICE

242A

OFFICE

252E

OFFICE

252D

OFFICE

OPEN OFFICE

OPEN OFFICE

ELEC

IT

MECHANICAL

STAIR207

STAIR

JAN

TELEPHONE

WOMEN

MEN

252B

OFFICE

CORR

OFFICE

226B

OFFICE

226A

BREAK

226C

CONFERENCE

226D

OPEN OFFICE

OPEN OFFICE

OPEN OFFICE

Ø

P

SA

C

Ø

P

SA

H

Ø

P

SA

H

Ø

P

SA

C

14Ø SA18Ø SA

14Ø PSAC

14Ø PSAH 10Ø PSAH

16Ø PSAH

18Ø PSAC

10Ø PSAH

14Ø PSAC

16Ø SA 14Ø SA 12Ø SA

18Ø PSAC16Ø PSAC

14Ø PSAH

A2 105 7" Ø

TYP. 6

VAV-2-4 VAV-2-2

VAV-2-5

VAV-2-6 VAV-2-7

VAV-2-8 VAV-2-9 VA

V- 2-

VAV-2-11

VAV-2-18

VAV-2-17 VAV-2-16 VAV-2-15 VAV-2-14

VAV-2-12

DDVAV-2-2

DDVAV-2-3

DDVAV-2-1

DDVAV-2-4

DDVAV-2-5 DDVAV-2-6

DDVAV-2-7

DDVAV-2-8

DDVAV-2-9

DDVAV-2-10

DDVAV-2-11

DDVAV-2-12

DDVAV-2-13DDVAV-2-14

DDVAV-2-15

A1 135 6" Ø

TYP. 6

R1 160 24" X 24"

R1 220 24" X 24"

R1 160 24" X 24"

R1 225 24" X 24"

R1 160 24" X 24"

R1 125 24" X 24"

R1 90 24" X 24"

R1 260 24" X 24"

R1 470 24" X 24"

R1 430 24" X 24"

R1 80 24" X 24"

TYP. 4

R1 300 24" X 24"

R1 250 24" X 24"

R1 360 24" X 24"

R1 290 24" X 24"

R1 250 24" X 24" R1 330

24" X 24"

R1 90 24" X 24"

A2 160 7" Ø

A2 160 7" Ø

A2 100 7" Ø

TYP. 2

A2 110 7" Ø

TYP. 2

A2 160 7" Ø

A2 125 7" Ø

TYP. 6

A2 135 7" Ø

A1 90 6" Ø

A1 85 6" Ø

TYP. 3

A2 215 7" Ø

TYP. 2

A2 150 7" Ø

TYP. 2 A1 170

6" Ø

A1 115 6" Ø

TYP. 6

A1 175

8" Ø

TYP. 4

A1 260 8" Ø

A1 165 8" Ø

TYP. 2

A1 160 8" Ø

TYP. 4

A1 80 6" Ø

TYP. 2

A1 125 6" Ø

A1 130 6" Ø

TYP. 3

A1 130 6" Ø

TYP. 6

A1 80 6" Ø

TYP. 4

A1 120 6" Ø

TYP. 7

A2 125 7" Ø

TYP. 2

A1 125 6" Ø

TYP. 3

A2 115 7" Ø

TYP. 7

A1 115 6"

R1 840 24" X 24"

A2 125 7" Ø

TYP. 2

A2 150 7" Ø

TYP. 2

A2 120 7" Ø

TYP. 3

A2 130 7" Ø

TYP. 8

A2 145 7" Ø

TYP. 2

A2 125 7" Ø

TYP. 2

A2 120 7" Ø

TYP. 2

A1 90 6" Ø

A1 155 6"

TYP. 6

VAV-2-13

A1 130 6" Ø

TYP. 6

R1 623 24" X 24"

TYP. 2

R1 623 24" X 24"

R1 330 24" X 24"

R1 435 24" X 24"

TYP. 2

VAV-2-3

VAV-2-1

A1 90 6" Ø

A1 90 6" Ø A1 90

6" Ø

DDVAV-2-4

DDVAV-2-3

DDVAV-2-2

DDVAV-2-1

DDVAV-2-15

DDVAV-2-14

DDVAV-2-13

DDVAV-2-12

DDVAV-2-11

DDVAV-2-10

VAV-2-12

VAV-2-13

VAV-2-2

VAV-2-3

VAV-2-1

VAV-2-4

VAV-2-16

VAV-2-17

VAV-2-18

VAV-2-14VAV-2-15

VAV-2-5

VAV-2-6

DDVAV-2-5

DDVAV-2-7

DDVAV-2-8

VAV-2-11

VAV-2-(9&10)

DDVAV-2-6

VAV-2-8

VAV-2-7

8x8 SA8x8 SA 8x8 SA 10x8 SA 10x10 SA

8x8 SA

10x8 SA

8x

SA

18x14 RA16x14 RA x1

R

A

10x10 SA 10x8 SA12x10 SA

6x

R A x1

R

A

14x12 RA

14x12

16x16 RA12x12 RA

16Ø SA14Ø SA

x1

SA

6x

8x

SA

x1

SA

16x16 RA 18x18 RA 14x12 12x12 RA x1

R

A x1

SA

x1

SA

x1

SA

12x12 SA 10x10 SA 8x10 SA

12x10 SA 8x8 SA

12x10 SA 8x8 SA8x8 SA

10x8 SA

14x12 RA

12Ø SA

16x16 RA x1

SA10

x8 S

A x1

SA

x1

SA10x10 SA x1

SA

x1

SA

Ø

S A x1

R

A

FSDFSD FSD FSD

FSDFSD FSDFSD

DDVAV-2-9

16Ø PSAH

20Ø PSAC

18Ø SA

6x

R A

R1 775 24" X 24"

TYP. 2

R1 90 24" X 24"

R1 390 24" X 24"

R1 885 24" X 24"

R1 500 24" X 24"

TYP. 3

R1 200 24" X 24"

R1 160 24" X 24"

R1 700 24" X 24"

R1 580 24" X 24"

TYP. 2

A1 120 6" Ø

A1 135 6" Ø

R1 135 24" X 24"

8x

SA

x1

SA

x1

SA

6x8 SA

A1 130 6" Ø

TYP. 4

R1 520 24" X 24"

TYP. 2

8x8 SA x1

12x10 SA x1

SA

8x

SA

x1

SA 8x8 SA x8

S A

6x

SA

x1 x1

SA

x1

SA

10Ø SA

6x

R A

10x8 RA

Ø

Ø

10Ø PSAC

8Ø 8Ø

12x12 RA

12x12 RA

16Ø PSAC

14Ø PSAH

Ø PSAC

Ø

Ø

10x10 RA

14x14 RA

6Ø SA

6x6 RA 10x10 RA

10x10 RA

8Ø 8Ø x1

SA

8x

SA

6x

SA

x8

R A

10Ø PSAH

10Ø PSAC14Ø

12Ø

14x12 RA 12x12 RA

12Ø SA

FSD

12x10 RA

8x8 RA

14x14 RA

Ø

S A x1

R

A

FSD

R1 623 24" X 24"

10x10

6x8 SA

8x10 SA

14x10 SA

Ø

Ø

Ø

Ø

8Ø

8Ø

Ø

Ø

8Ø 8Ø

Ø

Ø 14 Ø

Ø 12Ø

10Ø 10 x8 8x x8

10x8 x1 x1 x8 x88x

6x

6x

6x x1 x8 x1

8x

8x

8x 6 8x x1

8x x1

Ø

Ø

6Ø

6Ø

6Ø

Ø

Ø

Ø

8Ø x1 x1 x1

8x x1 x1

6x

6x x1 x1 x1

10x10

6Ø S

A

12Ø

10Ø x1

8Ø

Ø

Ø

VAV-2-19

VAV-2-19

10Ø

A3 600 14" X 10"

12x10

FSDFD

VAV-2-19

VAV-2-19

78701

DRAWN BY:

CHECKED BY:

Mark E. Mikulin

107561

PRELIMINARY

Not Intended for Construction, Bidding or Permit. This document is released under the authority of:

Registrant's Name:

Serial No.

State of Registration Firm Registration No.

EEA Project No.

6615 Vaught Ranch Road #100 Austin, Texas 78730-2314 USA

512.744.4400 main - 512.744.4444 fax www.eeace.com

CONSULTING

ENGINEERS

P20250347

F-2497

TX

TRINITY - IT

ROOM HVAC

UPGRADES

MECHANICAL NEW WORK PLAN - 2ND FLOOR

SCALE: 1/8" - 1'-0"

1 2

A. REFER TO CURRENT TEXAS WORKFORCE COMMISSION STANDARD CONSTRUCTION

SPECIFICATIONS FOR ADDITIONAL MATERIAL AND INSTALLATION INFORMATION.

B. REFER TO SCHEDULES, SEQUENCE OF OPERATION, AND DETAILS FOR ADDITIONAL

INFORMATION.

C. COORDINATE WITH TWC STAFF FOR UTILITY OUTAGES REQUIRED FOR BUILDING

WORK.

D. 120V POWER FOR CONTROL SYSTEM TO BE PROVIDED BY ELECTRICAL

CONTRACTOR. CONTROLS CONTRACTOR IS RESPONSIBLE FOR PROVIDING AND

INSTALLING CONTROLS COMPONENTS, CONTROL AND LOW VOLTAGE WIRING AND

REQUIRED CONDUIT.

E. PROVIDE SINGLE INLET VAV UNITS WITH ONE NEW CONTROLLER AND DDC

THERMOSTAT EACH. INTEGRATE INTO EXISTING BAS SYSTEM.

F. ALL DUCTWORK FROM THE AHU TO A TERMINAL UNIT SHALL BE MEDIUM PRESSURE

DUCTWORK. ALL DUCTWORK AFTER THE TERMINAL UNIT SHALL BE LOW PRESSURE

DUCTWORK. RETURN DUCTWORK TO BE MEDIUM PRESSURE.

G. COORDINATE AND INSTALL TERMINAL UNITS WITH 24" MINIMUM CLEARANCE DEPTH

AT CONTROLS ACCESS ENCLOSURES.

GENERAL NOTES:

KEYED NOTES: X

1. INSTALL NEW VAV TERMINAL UNIT WITH ASSOCIATED CONTROL COMPONENTS.

INTEGRATE UNIT INTO EXISTING BUILDING AUTOMATION SYSTEM (BAS).

2. ELECTRICAL CONTRACTOR TO CONNECT NEW VAV TERMINAL UNIT TO EXISTING

ELECTRICAL CIRCUIT SERVING TERMINAL UNITS ON THIS FLOOR.

3. INSTALL 1.5-HR FIRE DAMPER IN SUPPLY AIR DUCT PENETRATIONS. PROVIDE

ACCESS PANELS. INSTALL ALL FIRE DAMPERS IN STRICT ACCORDANCE WITH

MANUFACTURER'S INSTRUCTIONS IN ORDER TO MAINTAIN U.L. APPROVAL OF THE

ASSEMBLY. ASSEMBLY SHALL BE RATED ACCORDING TO THE WALL RATING.

INSTALL A FIRE DAMPER ACCESS DOOR AT EACH DAMPER AND LABEL ACCESS

DOOR.

AutoCAD SHX Text T

AutoCAD SHX Text T

AutoCAD SHX Text T

AutoCAD SHX Text T

AutoCAD SHX Text T

AutoCAD SHX Text T

AutoCAD SHX Text T

AutoCAD SHX Text T

AutoCAD SHX Text T

AutoCAD SHX Text T

AutoCAD SHX Text T

AutoCAD SHX Text T

AutoCAD SHX Text T

AutoCAD SHX Text T

AutoCAD SHX Text T

AutoCAD SHX Text T

AutoCAD SHX Text T

AutoCAD SHX Text T

AutoCAD SHX Text T

AutoCAD SHX Text T

AutoCAD SHX Text T

AutoCAD SHX Text T

AutoCAD SHX Text T

AutoCAD SHX Text T

AutoCAD SHX Text T

AutoCAD SHX Text T

AutoCAD SHX Text T

AutoCAD SHX Text T

AutoCAD SHX Text T

AutoCAD SHX Text T

AutoCAD SHX Text T

AutoCAD SHX Text T

AutoCAD SHX Text

CO

AutoCAD SHX Text T

AutoCAD SHX Text

CONFIDENCE AND SHALL NOT BE MADE AVAILABLE,

AutoCAD SHX Text

EXCEPT AS MAY BE OTHERWISE PROVIDED BY CONTRACT,

AutoCAD SHX Text

THESE DRAWINGS AND SPECIFICATIONS ARE PROPERTY

AutoCAD SHX Text

OF THE CLIENT LISTED, AND ARE ISSUED IN STRICT

AutoCAD SHX Text

REPRODUCED, OR COPIED, OR USED FOR ANY OTHER

AutoCAD SHX Text

INTENDED PURPOSE, OR AS BASIS FOR MANUFACTURE

AutoCAD SHX Text

OR SALE OF APARATUS WITHOUT WRITTEN PERMISSION.

AutoCAD SHX Text

CONFIDENTIAL AND PROPRIETARY

AutoCAD SHX Text

SHEET NUMBER:

AutoCAD SHX Text

SHEET NAME:

AutoCAD SHX Text

PROJECT NUMBER:

AutoCAD SHX Text

ISSUE DATE:

AutoCAD SHX Text

REVISIONS:

AutoCAD SHX Text

SEAL(S) / CONSULTANT:

AutoCAD SHX Text

CLIENT / PROJECT NAME:

AutoCAD SHX Text 21-1062.00

AutoCAD SHX Text

OCTOBER 31, 2025

AutoCAD SHX Text

2ND FLOOR NEW WORK PLAN

AutoCAD SHX Text

PLAN NORTH

M2.1

MECHANICAL CHASE

Elevator 2 Elevator 3

OFFICE

OPEN OFFICE

CORR

CORR

CORR

ELEC

OPEN OFFICE

OPEN OFFICE

LOBBY

332D

OFFICE

332C

OFFICE

332B

OFFICE

316B

OFFICE

316C

OFFICE-

OFFICE

304A

OFFICE

STORAGE

316A

STORAGE

324B

OFFICE

324A

OFFICE

316E

OFFICE

316D

OFFICE

IT

JAN

TELEPHONE

332A

OFFICE

342C

OFFICE

342A

OFFICE

350A

OFFICE

BREAK ROOM

BREAK

STAIR307

STAIR

WOMEN

MEN

OPEN OFFICE

OPEN OFFICE

CONFERENCE

OPEN OFFICE

Ø

P

SA

H

Ø

S A

Ø

P

SA

H

Ø

S A

14Ø SA16Ø SA14Ø SA

18Ø PSAC

16Ø PSAH

16Ø PSAC

14Ø SA

12Ø SA

16Ø PSAH

18Ø PSAC16Ø PSAC

14Ø PSAH

14Ø PSAC

12Ø PSAH

12Ø PSAC

VAV-3-5

VAV-3-1 VAV-3-4

VAV-3-2

VAV-3-3

VAV-3-6

VAV-3-7

VAV-3-8

VAV-3-9

VAV-3-10

VAV-3-11

VAV-3-12VAV-3-13VAV-3-14

VAV-3-15

VAV-3-16

DDVAV-3-1 DDVAV-3-2

DDVAV-3-3 DDVAV-3-4

DDVAV-3-5

DDVAV-3-6

DDVAV-3-7

DDVAV-3-8

DDVAV-3-9

DDVAV-3-10

DDVAV-3-11

DDVAV-3-12DDVAV-3-13

DDVAV-3-14

DDVAV-3-15

A2 110 7" Ø

TYP. 2

R1 260 24" x 24"

R1 120 24" x 24"

R1 300 24" x 24"

R1 90 24" x 24"

R1 250 24" x 24"

R1 190 24" x 24"

R1 100 24" x 24"

R1 90 24" x 24"

R1 90 24" x 24"

R1 580 24" x 24"

TYP. 2

R1 500 24" x 24"

TYP. 2

R1 300 24" x 24"

R1 460 24" x 24"

R1 390 24" x 24"

R1 300 24" x 24"

R1 440 24" x 24"

R1 90 24" x 24"

R1 340 24" x 24"

TYP. 2

A2 120 7" Ø

A2 130 7" Ø

A2 130 7" Ø

TYP. 2

A2 75 X"

TYP. 4

A2 125 7" Ø

TYP. 2

A2 110 7" Ø

TYP. 2

A2 190 7" Ø

A2 120 7" Ø

TYP. 4

A2 180 7" Ø

A1 100 6" Ø

A1 120 6" Ø

TYP. 4

A1 145 8" Ø

TYP. 2

A2 170 7" Ø

TYP. 6

R1 480 24" x 24"

DDVAV-3-2

DDVAV-3-1

DDVAV-3-3 DDVAV-3-4

DDVAV-3-5

DDVAV-3-6

DDVAV-3-8

DDVAV-3-7

A1 90 6" Ø

A1 90 6" Ø

A1 90 6" Ø

A1 250 8" Ø

A1 65 6" Ø

TYP. 4

A1 90 6" Ø

A1 105 6" Ø"

TYP. 6

A1 95 6" Ø

TYP. 4

A1 95 6" Ø

TYP. 4

VAV-3-7

VAV-3-6

VAV-3-1

VAV-3-5

VAV-3-2

VAV-3-3

A1 95 6" Ø

TYP. 6

A1 95 6" Ø

TYP. 6

A1 95 6" Ø

TYP. 6

A1 95 6" Ø

TYP. 6

A1 120

6" Ø

TYP. 6

A1 110 6" Ø

TYP. 4

VAV-3-12

VAV-3-13

VAV-3-14

VAV-3-15

VAV-3-16

VAV-3-4

A1 85 6" Ø

TYP. 6

A2 170 7" Ø

A2 115 7" Ø

TYP. 4

A2 110 7" Ø

TYP. 5

A2 150 7" Ø

TYP. 2

A2 140 7" Ø

TYP. 3

A2 145 7" Ø

TYP. 2

A2 130 7" Ø

TYP. 3

A2 150 7" Ø

TYP. 2

A2 125 7" Ø

TYP. 2

A2 120 7" Ø

TYP. 3

A2 115 7" Ø

DDVAV-3-15

R1 550 24" x 24"

R1 420 24" x 24"

DDVAV-3-14

DDVAV-3-13 DDVAV-3-12

DDVAV-3-11

DDVAV-3-10

VAV-3-8

A1 110 6" Ø

TYP. 6

A1 90 6" Ø

TYP. 6

A1 90 6" Ø

TYP. 6

VAV-3-9

VAV-3-10

VAV-3-11

R1 250 24" x 24"

FSD

x8

S A x8

S A x8

S A x8

S A x1

SA

x8

S A

8x

SA

12x12 RA 10x10 RA

12Ø

12Ø PSAH

16x14 RA12x10 RA 6x6 RA x8

R A

14x10 RA 16x12 RA 20x16 RA

12x12 x8

S A x8

8x

SA

12x12 SA 10x8 SA 12x10 SA 12x10 SA 10x8 SA 8x8 SA

12x12 RA 16x14 RA 18x16 RA 14x12 RA x1

R

A

16x12 RA14x12 RA x1

R

A x1

SA

x1

SA

12x12 SA

8x8 SA 10x8 SA

6x6 SA x8

S A

8x8 SA 8x8 SA 10x8 SA x1

SA

8x8 SA x8

S A

8x8 SA 8x8 SA 8x8 SA

10x10 RA x8

S A

8x

S A x1

SA

x8

S A

A1 75 6" Ø

FSD FSD FSD

R1 220 24" x 24"

A1 180 8"

A1 270 8"

FSDFSD FSD FSDFSD

R1 180 24" x 24"

R1 480 24" x 24"

R1 190 24" x 24"

R1 360 24" x 24"

R1 220 24" x 24"

R1 260 24" x 24"

R1 630 24" x 24"

R1 290 24" x 24"

R1 500 24" x 24"

TYP. 4

R1 580 24" x 24"

R1 760 24" x 24"

R1 130 24" x 24"

R1 655 24" x 24"

TYP. 2

R1 250 24" x 24"

18Ø SA 20Ø SA

10Ø SA

x8

S A

8x

SA

x8

S A

6x

SA

x1

SA

x1

SA

8x

8x

SA

6Ø SA

20x16 RA18x14 RA x8

S A

10Ø PSAH

14Ø PSAC

Ø

P

SA

H

Ø P

SA

C

Ø PSAC

8Ø

PSAH

12Ø PSAH

14Ø PSAH

12Ø SA

6x

R A x1

R

A

10Ø

8Ø x1

SA

x1

SA

8x8 SA 8x10 SA

10x8 RA

12Ø SA

x1

SA

x8

S A

12Ø SA

x1

R

A x8

S A x8

S A x8

S A x1

R

A

Ø

P

SA

C x1

R

A

18x14 RA

Ø P

SA

C x1

SA

12Ø

Ø

Ø

8Ø8Ø

8x8 SA

8x8

6x

6x

8x

Ø

Ø 10

Ø

Ø

8Ø 8Ø x1

8x

8x

8x 88x

8x8 SA

6x6

8x

8Ø R

A x1

6Ø

Ø

6Ø x1 x1

8x

8x

Ø

Ø8Ø12 Ø x1

6Ø SA

14x14 RA x8

S A

6Ø

12Ø SA

x1

12x10

8x6 x8

8x x8 x1 x8

Ø

Ø

Ø

Ø

Ø

Ø

Ø

Ø x1 x8 x1 x1

8Ø

12Ø x1

SA

x8

Ø

Ø

Ø

Ø

Ø x1 x1 x1 x1 x1 x1

R

A

14Ø

6x8 SA x1

DDVAV-3-9

FSD

VAV-3-17

VAV-3-17

10Ø

A3 600 14" X 10"

12x10

FSD

FD

VAV-3-17

78701

DRAWN BY:

CHECKED BY:

Mark E. Mikulin

107561

PRELIMINARY

Not Intended for Construction, Bidding or Permit. This document is released under the authority of:

Registrant's Name:

Serial No.

State of Registration Firm Registration No.

EEA Project No.

6615 Vaught Ranch Road #100 Austin, Texas 78730-2314 USA

512.744.4400 main - 512.744.4444 fax www.eeace.com

CONSULTING

ENGINEERS

P20250347

F-2497

TX

TRINITY - IT

ROOM HVAC

UPGRADES

MECHANICAL NEW WORK PLAN - 3RD FLOOR

SCALE: 1/8" - 1'-0"

A. REFER TO CURRENT TEXAS WORKFORCE COMMISSION STANDARD CONSTRUCTION

SPECIFICATIONS FOR ADDITIONAL MATERIAL AND INSTALLATION INFORMATION.

B. REFER TO SCHEDULES, SEQUENCE OF OPERATION, AND DETAILS FOR ADDITIONAL

INFORMATION.

C. COORDINATE WITH TWC STAFF FOR UTILITY OUTAGES REQUIRED FOR BUILDING

WORK.

D. 120V POWER FOR CONTROL SYSTEM TO BE PROVIDED BY ELECTRICAL

CONTRACTOR. CONTROLS CONTRACTOR IS RESPONSIBLE FOR PROVIDING AND

INSTALLING CONTROLS COMPONENTS, CONTROL AND LOW VOLTAGE WIRING AND

REQUIRED CONDUIT.

E. PROVIDE SINGLE INLET VAV UNITS WITH ONE NEW CONTROLLER AND DDC

THERMOSTAT EACH. INTEGRATE INTO EXISTING BAS SYSTEM.

F. ALL DUCTWORK FROM THE AHU TO A TERMINAL UNIT SHALL BE MEDIUM PRESSURE

DUCTWORK. ALL DUCTWORK AFTER THE TERMINAL UNIT SHALL BE LOW PRESSURE

DUCTWORK. RETURN DUCTWORK TO BE MEDIUM PRESSURE.

G. COORDINATE AND INSTALL TERMINAL UNITS WITH 24" MINIMUM CLEARANCE DEPTH

AT CONTROLS ACCESS ENCLOSURES.

GENERAL NOTES:

KEYED NOTES: X

1. INSTALL NEW VAV TERMINAL UNIT WITH ASSOCIATED CONTROL COMPONENTS.

INTEGRATE UNIT INTO EXISTING BUILDING AUTOMATION SYSTEM (BAS).

2. ELECTRICAL CONTRACTOR TO CONNECT NEW VAV TERMINAL UNIT TO EXISTING

ELECTRICAL CIRCUIT SERVING TERMINAL UNITS ON THIS FLOOR.

3. INSTALL 1.5-HR FIRE DAMPER IN SUPPLY AIR DUCT PENETRATIONS. PROVIDE

ACCESS PANELS. INSTALL ALL FIRE DAMPERS IN STRICT ACCORDANCE WITH

MANUFACTURER'S INSTRUCTIONS IN ORDER TO MAINTAIN U.L. APPROVAL OF THE

ASSEMBLY. ASSEMBLY SHALL BE RATED ACCORDING TO THE WALL RATING.

INSTALL A FIRE DAMPER ACCESS DOOR AT EACH DAMPER AND LABEL ACCESS

DOOR.

1 2

AutoCAD SHX Text T

AutoCAD SHX Text T

AutoCAD SHX Text T

AutoCAD SHX Text T

AutoCAD SHX Text T

AutoCAD SHX Text T

AutoCAD SHX Text T

AutoCAD SHX Text T

AutoCAD SHX Text T

AutoCAD SHX Text T

AutoCAD SHX Text T

AutoCAD SHX Text T

AutoCAD SHX Text T

AutoCAD SHX Text T

AutoCAD SHX Text T

AutoCAD SHX Text T

AutoCAD SHX Text T

AutoCAD SHX Text T

AutoCAD SHX Text T

AutoCAD SHX Text T

AutoCAD SHX Text T

AutoCAD SHX Text T

AutoCAD SHX Text T

AutoCAD SHX Text T

AutoCAD SHX Text T

AutoCAD SHX Text T

AutoCAD SHX Text T

AutoCAD SHX Text T

AutoCAD SHX Text T

AutoCAD SHX Text T

AutoCAD SHX Text

CO

AutoCAD SHX Text T

AutoCAD SHX Text T

AutoCAD SHX Text

CONFIDENCE AND SHALL NOT BE MADE AVAILABLE,

AutoCAD SHX Text

EXCEPT AS MAY BE OTHERWISE PROVIDED BY CONTRACT,

AutoCAD SHX Text

THESE DRAWINGS AND SPECIFICATIONS ARE PROPERTY

AutoCAD SHX Text

OF THE CLIENT LISTED, AND ARE ISSUED IN STRICT

AutoCAD SHX Text

REPRODUCED, OR COPIED, OR USED FOR ANY OTHER

AutoCAD SHX Text

INTENDED PURPOSE, OR AS BASIS FOR MANUFACTURE

AutoCAD SHX Text

OR SALE OF APARATUS WITHOUT WRITTEN PERMISSION.

AutoCAD SHX Text

CONFIDENTIAL AND PROPRIETARY

AutoCAD SHX Text

SHEET NUMBER:

AutoCAD SHX Text

SHEET NAME:

AutoCAD SHX Text

PROJECT NUMBER:

AutoCAD SHX Text

ISSUE DATE:

AutoCAD SHX Text

REVISIONS:

AutoCAD SHX Text

SEAL(S) / CONSULTANT:

AutoCAD SHX Text

CLIENT / PROJECT NAME:

AutoCAD SHX Text 21-1062.00

AutoCAD SHX Text

OCTOBER 31, 2025

AutoCAD SHX Text

3RD FLOOR NEW WORK PLAN

AutoCAD SHX Text

PLAN NORTH

M2.2

Elevator 2 Elevator 3 MECHANICAL CHASE

451A

STG

OPEN OFFICE

CORR

OPEN OFFICE

CORR

ELEC

STAIR

CORR

CONFERENCE

OFFICE

458B

OFFICE

458C

OFFICE

458D

OFFICE

452A

OFFICE

452B

OFFICE

440A

OFFICE

432B

OFFICE

432D

OFFICE

432A

OFFICE

OPEN OFFICE

424B

OFFICE

424A

OFFICE

416B

OFFICE

OPEN OFFICE

408A

OFFICE

404C

OFFICE

404B

OFFICE

404A

OFFICE

OPEN OFFICE

LOBBY

IT

JAN

TELEPHONE

STAIR

WOMEN

MEN

Ø

P

SA

C

Ø

P

SA

H

Ø

P

SA

H

Ø

P

SA

C

20Ø PSAC

18Ø PSAH16Ø PSAH12Ø PSAH

16Ø PSAC

14Ø PSAH

16Ø PSAC14Ø PSAC

12Ø PSAH

12Ø PSAH

14Ø PSAC

16Ø PSAH

18Ø PSAC

8Ø P

SA

H

Ø

P

SA

C x1

R

A

14x14 RA14x12 RA x1

R

A

18x16 RA14x14 RA

VAV-4-1 VAV-4-4

VAV-4-2

VAV-4-3

VAV-4-5 VAV-4-6 VAV-4-7

VAV-4-8

VAV-4-9

VAV-4-10VAV-4-11

VAV-4-12VAV-4-13

DDVAV-4-1

DDVAV-4-18

DDVAV-4-2

DDVAV-4-3

DDVAV-4-4

DDVAV-4-5 DDVAV-4-6 DDVAV-4-7

DDVAV-4-8

DDVAV-4-9

DDVAV-4-10DDVAV-4-11

DDVAV-4-12

DDVAV-4-13

DDVAV-4-14

DDVAV-4-15

DDVAV-4-16

DDVAV-4-17

R1 250 24" X 24"

R1 120 24" X 24"

R1 125 24" X 24"

R1 90 24" X 24"R1 560

24" X 24"

R1 140 24" X 24"

R1 110 24" X 24"

R1 680 24" X 24"

R1 90 24" X 24"

R1 90 24" X 24"

R1 190 24" X 24"

R1 260 24" X 24"

R1 280 24" X 24"

R1 150 24" X 24"

A2 125 7" Ø

TYP. 2

A2 125 7" Ø

TYP. 7

A2 150 7" Ø

TYP. 2

A2 140 7" Ø

TYP. 2

A2 130 7" Ø

TYP. 2

A2 190 7" Ø

A2 120 7" Ø

TYP. 4

A2 200 7" Ø

A1 100 6" Ø

A2 135 X"

TYP. 3

A2 150 7" Ø

TYP. 2

A2 120 7" Ø

TYP. 2

A2 115 7" Ø

TYP. 7

A2 120 7" Ø

TYP. 2

A2 120 7" Ø

TYP. 2

A2 130 7" Ø

TYP. 6

A2 115 7" Ø

TYP. 2

A1 80 6" Ø

A1 70 6" Ø

TYP. 2

A1 110 6" Ø

A2 160 7"

TYP. 3

A2 140 7"

TYP. 3

A1 140 8"

A1 155 8"

TYP. 2

A1 135 6" Ø

TYP. 6

A1 135 6" Ø

TYP. 6

A1 130 6" Ø

TYP. 6

A1 105 6" Ø

TYP. 6

A1 105 6" Ø

TYP. 6

A1 125 6" Ø

TYP. 6

A1 125 6" Ø

TYP. 6

A1 155 8" Ø

TYP. 6

A1 180 8" Ø

TYP. 2

R1 555 24" X 24"

TYP. 2

A1 120 6" Ø

TYP. 3

A1 165 8" Ø

TYP. 2A1 90

6" Ø

TYP. 9

A1 125 6"

DDVAV-4-17

DDVAV-4-16

DDVAV-4-15

DDVAV-4-14

DDVAV-4-13

DDVAV-4-12 DDVAV-4-11 DDVAV-4-10

DDVAV-4-9

DDVAV-4-8

DDVAV-4-7DDVAV-4-6DDVAV-4-5

DDVAV-4-4DDVAV-4-3

DDVAV-4-2

DDVAV-4-1

VAV-4-1

DDVAV-4-18

VAV-4-3

VAV-4-2

VAV-4-4

VAV-4-5 VAV-4-6 VAV-4-7

VAV-4-8

A1 90 6"

A1 45 X"

TYP. 2

A1 90 6"

VAV-4-9

VAV-4-10

VAV-4-11

VAV-4-12VAV-4-13

x1

R

A

8x

R A

12x12 RA 14x14 RA 16x16 RA 14x12 RA x1

R

A

16x16 RA

14x10 RA

8x8 SA

6Ø S

A

14x10 SA

10x8 SA 10x10 SA 10x10 SA 12x10 SA

8x8 SA

8x8 SA x1

SA

x1

SA

x1

SA

x1

SA

x1

SA

x8

S A x8

S A

8x

SA

x1

SA

x1 x1 x1

8x

SA

6x8 SA

12x12 RA

R1 680 24" X 24"

R1 385 24" X 24"

TYP. 2

R1 400 24" X 24"

TYP. 2

R1 300 24" X 24"

R1 405 24" X 24"

R1 300 24" X 24"

R1 690 24" X 24"

R1 485 24" X 24"

TYP. 5

R1 310 24" X 24"

R1 540 24" X 24"

TYP. 3

R1 790 24" X 24"

R1 440 24" X 24"

TYP. 2

R1 840 24" X 24"

R1 240 24" X 24"

16Ø SA 18Ø SA

14Ø SA 18Ø SA

FSD

FSD FSD FSD FSD

FSDFSD

FSD FSD FSD

6x8 SA x1

SA

8x8 SA 12x12 SA

R1 240 24" X 24"

R1 680 24" X 24"

A1 120 6"

A1 150 8" Ø

TYP. 2

10x10 SA

8x

SA

8x

S A x1

SA

10x8 SA

R1 240 24" X 24"

8x8 SA

8x x1 x1

8x

8x

8x

8x

8x8 SA

8x

SA

8x

8x

8x8 SA 14x10 SA

8x8 SA

6Ø S

A x1

10x10 SA 8x8 SA

10x8 SA 10x10 SA 8x8 SA

10x10 SA

8Ø S

A12Ø PSAH

14Ø PSAC

10Ø PSAH

12Ø PSAC

10x10 SA

8x

S A x8

S A x1

SA

16x16 RA

Ø

P

SA

C

10Ø PSAH

12Ø PSAC

10x8 RA 12x12 RA

14Ø SA

12Ø SA14Ø SA

12Ø SA

12x10 RA

12x12 SA

12x10 RA

14x14 RA x1

0 R A

Ø

S A x8 x1

10x8

Ø

Ø 10Ø PSAC

8Ø PSAH

Ø

Ø 8x x8 x8

Ø

Ø

Ø

Ø8x

8x

Ø

Ø x8 x8

8Ø

8Ø

Ø

8Ø x8

6x6

Ø

P

SA

H

6x

10Ø PSAH

12Ø PSAC

Ø

Ø

12Ø SA

x1

SA

6Ø x1

6x

R A

12x12 RA

Ø

8Ø10 Ø

Ø

Ø

8x

Ø

Ø

8x

8x

Ø

Ø

Ø

Ø x1

8Ø P

SA

H

8Ø P

SA

C

8Ø

8Ø

12x12

6x6 x1

R

A

6x6

8x8

12x8 x1 x1 x1

6x

8x

S A

18Ø PSAC

Ø

Ø

Ø

P

SA

H

Ø P

SA

C

6Ø

6Ø x8

14Ø SA

x1 x1 x1

8x x1

VAV-4-14

VAV-4-14

10Ø

A3 600 14" X 10"

12x10

FD

VAV-4-14

78701

DRAWN BY:

CHECKED BY:

Mark E. Mikulin

107561

PRELIMINARY

Not Intended for Construction, Bidding or Permit. This document is released under the authority of:

Registrant's Name:

Serial No.

State of Registration Firm Registration No.

EEA Project No.

6615 Vaught Ranch Road #100 Austin, Texas 78730-2314 USA

512.744.4400 main - 512.744.4444 fax www.eeace.com

CONSULTING

ENGINEERS

P20250347

F-2497

TX

TRINITY - IT

ROOM HVAC

UPGRADES

MECHANICAL NEW WORK PLAN - 4TH FLOOR

SCALE: 1/8" - 1'-0"

A. REFER TO CURRENT TEXAS WORKFORCE COMMISSION STANDARD CONSTRUCTION

SPECIFICATIONS FOR ADDITIONAL MATERIAL AND INSTALLATION INFORMATION.

B. REFER TO SCHEDULES, SEQUENCE OF OPERATION, AND DETAILS FOR ADDITIONAL

INFORMATION.

C. COORDINATE WITH TWC STAFF FOR UTILITY OUTAGES REQUIRED FOR BUILDING

WORK.

D. 120V POWER FOR CONTROL SYSTEM TO BE PROVIDED BY ELECTRICAL

CONTRACTOR. CONTROLS CONTRACTOR IS RESPONSIBLE FOR PROVIDING AND

INSTALLING CONTROLS COMPONENTS, CONTROL AND LOW VOLTAGE WIRING AND

REQUIRED CONDUIT.

E. PROVIDE SINGLE INLET VAV UNITS WITH ONE NEW CONTROLLER AND DDC

THERMOSTAT EACH. INTEGRATE INTO EXISTING BAS SYSTEM.

F. ALL DUCTWORK FROM THE AHU TO A TERMINAL UNIT SHALL BE MEDIUM PRESSURE

DUCTWORK. ALL DUCTWORK AFTER THE TERMINAL UNIT SHALL BE LOW PRESSURE

DUCTWORK. RETURN DUCTWORK TO BE MEDIUM PRESSURE.

G. COORDINATE AND INSTALL TERMINAL UNITS WITH 24" MINIMUM CLEARANCE DEPTH

AT CONTROLS ACCESS ENCLOSURES.

GENERAL NOTES:

KEYED NOTES: X

1. INSTALL NEW VAV TERMINAL UNIT WITH ASSOCIATED CONTROL COMPONENTS.

INTEGRATE UNIT INTO EXISTING BUILDING AUTOMATION SYSTEM (BAS).

2. ELECTRICAL CONTRACTOR TO CONNECT NEW VAV TERMINAL UNIT TO EXISTING

ELECTRICAL CIRCUIT SERVING TERMINAL UNITS ON THIS FLOOR.

3. INSTALL 1.5-HR FIRE DAMPER IN SUPPLY AIR DUCT PENETRATIONS. PROVIDE

ACCESS PANELS. INSTALL ALL FIRE DAMPERS IN STRICT ACCORDANCE WITH

MANUFACTURER'S INSTRUCTIONS IN ORDER TO MAINTAIN U.L. APPROVAL OF THE

ASSEMBLY. ASSEMBLY SHALL BE RATED ACCORDING TO THE WALL RATING.

INSTALL A FIRE DAMPER ACCESS DOOR AT EACH DAMPER AND LABEL ACCESS

DOOR.

1 2

AutoCAD SHX Text T

AutoCAD SHX Text T

AutoCAD SHX Text T

AutoCAD SHX Text T

AutoCAD SHX Text T

AutoCAD SHX Text T

AutoCAD SHX Text T

AutoCAD SHX Text T

AutoCAD SHX Text T

AutoCAD SHX Text T

AutoCAD SHX Text T

AutoCAD SHX Text T

AutoCAD SHX Text T

AutoCAD SHX Text T

AutoCAD SHX Text T

AutoCAD SHX Text T

AutoCAD SHX Text T

AutoCAD SHX Text T

AutoCAD SHX Text T

AutoCAD SHX Text T

AutoCAD SHX Text T

AutoCAD SHX Text T

AutoCAD SHX Text T

AutoCAD SHX Text T

AutoCAD SHX Text T

AutoCAD SHX Text T

AutoCAD SHX Text T

AutoCAD SHX Text T

AutoCAD SHX Text T

AutoCAD SHX Text T

AutoCAD SHX Text T

AutoCAD SHX Text

CO

AutoCAD SHX Text T

AutoCAD SHX Text

CONFIDENCE AND SHALL NOT BE MADE AVAILABLE,

AutoCAD SHX Text

EXCEPT AS MAY BE OTHERWISE PROVIDED BY CONTRACT,

AutoCAD SHX Text

THESE DRAWINGS AND SPECIFICATIONS ARE PROPERTY

AutoCAD SHX Text

OF THE CLIENT LISTED, AND ARE ISSUED IN STRICT

AutoCAD SHX Text

REPRODUCED, OR COPIED, OR USED FOR ANY OTHER

AutoCAD SHX Text

INTENDED PURPOSE, OR AS BASIS FOR MANUFACTURE

AutoCAD SHX Text

OR SALE OF APARATUS WITHOUT WRITTEN PERMISSION.

AutoCAD SHX Text

CONFIDENTIAL AND PROPRIETARY

AutoCAD SHX Text

SHEET NUMBER:

AutoCAD SHX Text

SHEET NAME:

AutoCAD SHX Text

PROJECT NUMBER:

AutoCAD SHX Text

ISSUE DATE:

AutoCAD SHX Text

REVISIONS:

AutoCAD SHX Text

SEAL(S) / CONSULTANT:

AutoCAD SHX Text

CLIENT / PROJECT NAME:

AutoCAD SHX Text 21-1062.00

AutoCAD SHX Text

OCTOBER 31, 2025

AutoCAD SHX Text

4TH FLOOR NEW WORK PLAN

AutoCAD SHX Text

PLAN NORTH

M2.3

MECHANICAL CHASE

Elevator 2 Elevator 3

JAN

CORR

OPEN OFFICE

STO

IT

CLOSET

504F

STO

OPEN OFFICE

506B

OFFICE

506A

OFFICE

504A

CONFERENCE

504B

OFFICE

504C

OFFICE

504K

WORK

504E

OFFICE

512A

OFFICE

512B

CONFERENCE

512C

OFFICE

512D

OFFICE

526A

OFFICE

526B

OFFICE

NETWORK

504G

OFFICE

504F

OFFICE

512I

BREAK

512H

OFFICE

512G

OFFICE

512F

OFFICE

512E

OFFICE

526D

OFFICE

CORR501

CORR

CORR

530B

OPEN OFFICE

530A

OPEN OFFICE

MECHANICAL

STAIR

LOBBY

STAIR

WOMEN

MEN

18Ø PSAH

20Ø PSAC18Ø PSAC

Ø P

SA

C

26Ø SA

Ø

S A

24Ø SA

Ø

P

SA

H

20x18 RA18x18 RA x2

R

A

16x12 RA

20x16 RA

VAV-5-1

VAV-5-4

VAV-5-2

VAV-5-3

VAV-5-5

VAV-5-6

VAV-5-7

VAV-5-8

VAV-5-10

VAV-5-11

VAV-5-9VAV-5-12 VAV-5-13

DDVAV-5-1

DDVAV-5-2

DDVAV-5-3

DDVAV-5-4

DDVAV-5-5 DDVAV-5-6 DDVAV-5-7

DDVAV-5-8

A1 190 8" Ø

A1 195 8" Ø

TYP. 2

A1 180 8" Ø

TYP. 2

A2 145 7" Ø

TYP. 6

A1 135 6"

TYP. 8

A1 110 6" Ø

TYP. 4

A1 130 6"

TYP. 2

A1 105 6" Ø

R1 390 24" X 24"

R1 360 24" X 24"

R1 1080 24" X 24"

R1 105 24" X 24"

R1 260 24" X 24"

A1 180 8" Ø

TYP. 2

R1 360 24" X 24"

A1 140 8" Ø

A2 90 7" Ø

TYP. 3

R1 270 24" X 24"

R1 180 24" X 24"

A2 130 7" Ø

TYP. 2

R1 260 24" X 24"

R1 300 24" X 24"

R1 620 24" X 24"

A2 155 7" Ø

TYP. 4

R1 250 24" X 24"

A2 115 7" Ø

TYP. 2

R1 230 24" X 24"

R1 260 24" X 24"

R1 195 24" X 24"R1 195

24" X 24"

A2 195 8" Ø

A1 195 8" Ø

A1 135 6"

R1 195 24" X 24"

R1 135 24" X 24"

A1 205 8"

R1 205 24" X 24"

A1 145 8" Ø

R1 145 24" X 24"

A1 200 8" Ø

R1 200 24" X 24"

A1 120 6" Ø

TYP. 2

R1 200 24" X 24"

A1 120 6" Ø

TYP. 2

R1 240 24" X 24"

A1 120 6" Ø

TYP. 2

A1 240 6" Ø

A2 270 X"

TYP. 5

R1 630 24" X 24"

TYP. 2

A2 335 10"

TYP. 4

R1 240 24" X 24"

R1 240 24" X 24"

R1 950 24" X 24"

R1 630 24" X 24"

DDVAV-5-1

DDVAV-5-2

VAV-5-7

VAV-5-5

VAV-5-6

DDVAV-5-3

DDVAV-5-4

DDVAV-5-5

DDVAV-5-6

DDVAV-5-7

DDVAV-5-8

VAV-5-2

VAV-5-3

VAV-5-4

VAV-5-1

VAV-5-8

VAV-5-10

VAV-5-11

VAV-5-9VAV-5-12 VAV-5-13

12x12 SA 10x10 SA

12x12 x8

S A x1

SA

x1

SA

x1

SA

8x

SA

x8

S A

10x8 SA 12x10 SA 8x8 SA 8x8 SA 8x8 SA 8x8 SA x8

S A x8

S A x8

S A x8

S A

6x

SA

12x12 SA 8x8 SA18x12 SA

12x12 SA

FSD

R1 1310 24" X 24" x3

SA

x3

R

A

6x8 SA

A1 90 6" Ø

8x8 SA x1

SA

A2 150 7" Ø

TYP. 2

x1

SA

8x8 SA

A2 125 7" Ø

TYP. 2

A2 130 7" Ø

TYP. 2

A2 125 7" Ø

TYP. 2

10x10 SA

A2 195 8" Ø

A1 90 6" Ø

16Ø PSAH

R1 250 24" X 24"

FSD

FSD FSD FSD

FSDFSD

FSD

R1 140 24" X 24" x1

R

A

12x10 RA

12x6 RA x1

R

A

20Ø SA

x3

PS

AH

x3

PS

AC

x3

R

A

18x12 SA18Ø SA

20Ø PSAH

22Ø PSAC

FSD

FSDFSD

FSD

x8

Ø

8x

Ø

Ø

8x

8x

Ø

Ø

8x8 RA

Ø x1

Ø

Ø

Ø

Ø

8x

8x

8x8

8x

8x

6x6

14x10

8x 66x

8x

10x8 8Ø

10Ø

8x6

8x8

8Ø

16x12

10Ø 12Ø

6x6

Ø

P

SA

H

Ø

P

SA

C

Ø

16Ø16x12 x1

R

A

8x8 RA x6

R A

10x8

Ø

S A 10

Ø S

A

Ø8Ø

14Ø SA

x1 x1

Ø

8x

SA

12x10

24x16 RA

Ø

8Ø SA

8x

8Ø

10x8

FSD

VAV-5-15

VAV-5-15

10Ø

A1 500 12" Ø

12Ø x1

FD

FD

VAV-5-14

VAV-5-14

A3 600 14" X 10"

FD

8Ø

Ø

10Ø x1

FD

R3 - 14" X 10"

VAV-5-14

VAV-5-15

R1 - 10" X 10"

R1 - 10" X 10"

78701

DRAWN BY:

CHECKED BY:

Mark E. Mikulin

107561

PRELIMINARY

Not Intended for Construction, Bidding or Permit. This document is released under the authority of:

Registrant's Name:

Serial No.

State of Registration Firm Registration No.

EEA Project No.

6615 Vaught Ranch Road #100 Austin, Texas 78730-2314 USA

512.744.4400 main - 512.744.4444 fax www.eeace.com

CONSULTING

ENGINEERS

P20250347

F-2497

TX

TRINITY - IT

ROOM HVAC

UPGRADES

MECHANICAL NEW WORK PLAN - 5TH FLOOR

SCALE: 1/8" - 1'-0"

A. REFER TO CURRENT TEXAS WORKFORCE COMMISSION STANDARD CONSTRUCTION

SPECIFICATIONS FOR ADDITIONAL MATERIAL AND INSTALLATION INFORMATION.

B. REFER TO SCHEDULES, SEQUENCE OF OPERATION, AND DETAILS FOR ADDITIONAL

INFORMATION.

C. COORDINATE WITH TWC STAFF FOR UTILITY OUTAGES REQUIRED FOR BUILDING

WORK.

D. 120V POWER FOR CONTROL SYSTEM TO BE PROVIDED BY ELECTRICAL

CONTRACTOR. CONTROLS CONTRACTOR IS RESPONSIBLE FOR PROVIDING AND

INSTALLING CONTROLS COMPONENTS, CONTROL AND LOW VOLTAGE WIRING AND

REQUIRED CONDUIT.

E. PROVIDE SINGLE INLET VAV UNITS WITH ONE NEW CONTROLLER AND DDC

THERMOSTAT EACH. INTEGRATE INTO EXISTING BAS SYSTEM.

F. ALL DUCTWORK FROM THE AHU TO A TERMINAL UNIT SHALL BE MEDIUM PRESSURE

DUCTWORK. ALL DUCTWORK AFTER THE TERMINAL UNIT SHALL BE LOW PRESSURE

DUCTWORK. RETURN DUCTWORK TO BE MEDIUM PRESSURE.

G. COORDINATE AND INSTALL TERMINAL UNITS WITH 24" MINIMUM CLEARANCE DEPTH

AT CONTROLS ACCESS ENCLOSURES.

GENERAL NOTES:

KEYED NOTES: X

1. INSTALL NEW VAV TERMINAL UNIT WITH ASSOCIATED CONTROL COMPONENTS.

INTEGRATE UNIT INTO EXISTING BUILDING AUTOMATION SYSTEM (BAS).

2. ELECTRICAL CONTRACTOR TO CONNECT NEW VAV TERMINAL UNIT TO EXISTING

ELECTRICAL CIRCUIT SERVING TERMINAL UNITS ON THIS FLOOR.

3. INSTALL 1.5-HR FIRE DAMPER IN SUPPLY AND RETURN AIR DUCT PENETRATIONS.

PROVIDE ACCESS PANELS. INSTALL ALL FIRE DAMPERS IN STRICT ACCORDANCE

WITH MANUFACTURER'S INSTRUCTIONS IN ORDER TO MAINTAIN U.L. APPROVAL OF

THE ASSEMBLY. ASSEMBLY SHALL BE RATED ACCORDING TO THE WALL RATING.

INSTALL A FIRE DAMPER ACCESS DOOR AT EACH DAMPER AND LABEL ACCESS

DOOR.

1 2

1 2

AutoCAD SHX Text T

AutoCAD SHX Text T

AutoCAD SHX Text T

AutoCAD SHX Text T

AutoCAD SHX Text T

AutoCAD SHX Text T

AutoCAD SHX Text T

AutoCAD SHX Text T

AutoCAD SHX Text T

AutoCAD SHX Text T

AutoCAD SHX Text T

AutoCAD SHX Text T

AutoCAD SHX Text T

AutoCAD SHX Text T

AutoCAD SHX Text T

AutoCAD SHX Text T

AutoCAD SHX Text T

AutoCAD SHX Text T

AutoCAD SHX Text T

AutoCAD SHX Text T

AutoCAD SHX Text T

AutoCAD SHX Text

CO

AutoCAD SHX Text

CO

AutoCAD SHX Text T

AutoCAD SHX Text T

AutoCAD SHX Text

CONFIDENCE AND SHALL NOT BE MADE AVAILABLE,

AutoCAD SHX Text

EXCEPT AS MAY BE OTHERWISE PROVIDED BY CONTRACT,

AutoCAD SHX Text

THESE DRAWINGS AND SPECIFICATIONS ARE PROPERTY

AutoCAD SHX Text

OF THE CLIENT LISTED, AND ARE ISSUED IN STRICT

AutoCAD SHX Text

REPRODUCED, OR COPIED, OR USED FOR ANY OTHER

AutoCAD SHX Text

INTENDED PURPOSE, OR AS BASIS FOR MANUFACTURE

AutoCAD SHX Text

OR SALE OF APARATUS WITHOUT WRITTEN PERMISSION.

AutoCAD SHX Text

CONFIDENTIAL AND PROPRIETARY

AutoCAD SHX Text

SHEET NUMBER:

AutoCAD SHX Text

SHEET NAME:

AutoCAD SHX Text

PROJECT NUMBER:

AutoCAD SHX Text

ISSUE DATE:

AutoCAD SHX Text

REVISIONS:

AutoCAD SHX Text

SEAL(S) / CONSULTANT:

AutoCAD SHX Text

CLIENT / PROJECT NAME:

AutoCAD SHX Text 21-1062.00

AutoCAD SHX Text

OCTOBER 31, 2025

AutoCAD SHX Text

5TH FLOOR NEW WORK PLAN

AutoCAD SHX Text

PLAN NORTH

M2.4

78701

DRAWN BY:

CHECKED BY:

Mark E. Mikulin

107561

PRELIMINARY

Not Intended for Construction, Bidding or Permit. This document is released under the authority of:

Registrant's Name:

Serial No.

State of Registration Firm Registration No.

EEA Project No.

6615 Vaught Ranch Road #100 Austin, Texas 78730-2314 USA

512.744.4400 main - 512.744.4444 fax www.eeace.com

CONSULTING

ENGINEERS

P20250347

F-2497

TX

TRINITY - IT

ROOM HVAC

UPGRADES

SUPPLY DUCT WITH EXTERNAL INSULATION (TYP.)

CONICAL BELL-MOUTH SPIN-IN FITTING

WITH VOLUME DAMPER & TRANSITION

VOLUME DAMPER WITH HORIZONTALLY MOUNTED SHAFT

SQUARE TO ROUND ADAPTER

WHERE REQUIRED

90 DEG. SMOOTH RADIUS

SHEET METAL ELBOW

INSULATED FLEXIBLE DUCT - INSIDE DIAMETER SAME AS

SCHEDULED DIFFUSER NECK SIZE MAX LENGTH = 5'-0"

1. IN LIEU OF SHEET METAL ELBOW,

FLEX DUCT MAY BE EXTENDED TO THE

DIFFUSER. USE THERMAFLEX

"FLEXFLOW" ELBOW HARNESS,

SUSPENDED FROM STRUCTURE.

KEYED NOTES:

AutoCAD SHX Text

CONFIDENCE AND SHALL NOT BE MADE AVAILABLE,

AutoCAD SHX Text

EXCEPT AS MAY BE OTHERWISE PROVIDED BY CONTRACT,

AutoCAD SHX Text

THESE DRAWINGS AND SPECIFICATIONS ARE PROPERTY

AutoCAD SHX Text

OF THE CLIENT LISTED, AND ARE ISSUED IN STRICT

AutoCAD SHX Text

REPRODUCED, OR COPIED, OR USED FOR ANY OTHER

AutoCAD SHX Text

INTENDED PURPOSE, OR AS BASIS FOR MANUFACTURE

AutoCAD SHX Text

OR SALE OF APARATUS WITHOUT WRITTEN PERMISSION.

AutoCAD SHX Text

CONFIDENTIAL AND PROPRIETARY

AutoCAD SHX Text

SHEET NUMBER:

AutoCAD SHX Text

SHEET NAME:

AutoCAD SHX Text

PROJECT NUMBER:

AutoCAD SHX Text

ISSUE DATE:

AutoCAD SHX Text

REVISIONS:

AutoCAD SHX Text

SEAL(S) / CONSULTANT:

AutoCAD SHX Text

CLIENT / PROJECT NAME:

AutoCAD SHX Text 21-1062.00

AutoCAD SHX Text

OCTOBER 31, 2025

AutoCAD SHX Text

MECHANICAL SCHEDULES & DETAILS

AutoCAD SHX Text

AutoCAD SHX Text

CEILING DIFFUSER CONNECTION

AutoCAD SHX Text N.T.S.

AutoCAD SHX Text

CEILING DIFFUSER - INSULATE DIFFUSER TOP

AutoCAD SHX Text X

AutoCAD SHX Text

AutoCAD SHX Text SECURE FLEXIBLE DUCT WITH S.S. SCREW CLAMP AND SEALER - BOTH INNER AND OUTER JACKETS

M3.0

78701

DRAWN BY:

CHECKED BY:

Mark E. Mikulin

107561

PRELIMINARY

Not Intended for Construction, Bidding or Permit.

This is the start of the file's text. The full file is on GovTribe.