This is an electrical floor plan and specifications document for a project involving the State of Illinois, specifically for the installation of new air handling units at the LPU Print Shop in the North End Stratton Building located at 401 S. Spring Street, Springfield, Illinois. The project, designated as 25-049, requires the installation of new air handling equipment including a 50A-208V-1PH heat pump (HP-1) and two 0.68A-208V-1PH air handling units (AHU-1 and AHU-2) in the partial basement electrical area. The work scope includes extending electrical conductors from existing panels, installing new disconnects and control wiring, and making connections to existing federal pacific electrical infrastructure on the first floor. The project was dated August 7, 2025, with an expiration date of November 30, 2026, and utilizes a scale of 18" = 1'-0" for the electrical floor plan layout.
All electrical work must be performed by a certified electrician in strict accordance with the National Electrical Code, International Energy Code, and applicable state and local regulations and ordinances. The electrical subcontractor is responsible for providing all power wiring using copper conductors with THWN, THHW, or THHN insulation, installing EMT conduit for panel feeders, and coordinating with mechanical and architectural drawings to avoid conflicts. Additional requirements include verifying voltage and phase prior to installation, installing safety switches, providing a revised typed panel index for existing panels, sealing all electrical penetrations through exterior walls, and providing a one-year written guarantee covering all labor and materials from the date of substantial completion. The subcontractor is also responsible for all hangers, clips, mounting hardware, cutting, and patching work.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
E-1
BRH
© Evan Lloyd Associates, Inc.
TC
S
E
CRADE
IO
N
AT
TIMOTHY
B. SMITH
L
SN
E
IC
S
TIH
F
TE
O ILIL
001-017445
Date:
Drawn By:
Revised:
Revised:
Project No.
SHEET
OF SHEETS.
Date Signed:
Expiration Date:
S ou th Si xth S tre et
Sp rin gfi eld
, Il lin ois
Ph on e
7.7
.70
NE
W
A
IR
H
AN
DL
IN
G
UN
IT
S
FO
R
TH
E
LP
U
PR
IN
T
SH
OP
N
OR
TH
E
ND
ST
RA
TT
ON
B
UI
LD
IN
G
1 S . S
PR
IN
G
ST
SP
RI
NG
FI
EL
D, IL
LIN
OI
S
AUG. 7, 2025
25-049
AUG. 7, 2025
NOV. 30, 2026
SCALE: 18" = 1'-0"
PARTIAL BASEMENT ELECTRICAL PLAN
NO
RT
H
EXISTINGSTORAGE
EXISTING PRINTSHOP
EXISTING STORAGE
EXISTING SECURITYOFFICE EXISTING MECHANICALROOM
EXISTING LOADING/UNLOADING
EXISTING DOCKAREA
EXISTINGLOBBY
EXISTINGTOILET
EXISTING LOADINGDOCK
EXISTING ELEC.SHOP
EXISTING STORAGE
EXISTINGCORRIDOR
EXISTING POST OFFICE
EXISTING SECURITYOFFICE
EXISTINGCORRIDOR
NEW 50A-208V-1PH
HEAT PUMP (HP-1)
NEW 60/50A-208V-1PH
FUSED DISCONNECT.
EXTEND (4) #3 & (1) #8 GRD. IN 1 1/4" C.
UP TO THE EXISTING FEDERAL PACIFIC PANEL
LOCATED ON THE FIRST FLOOR ABOVE
AND CONNECT TO THE EXISTING 3P-100A
BREAKER IN PANEL.
EXISTING PANEL.
NEW .68A-208V-1PH AIR
HANDLING UNIT (AHU-1)
NEW .68A-208V-1PH AIR
HANDLING UNIT (AHU-2)
NEW LOW VOLTAGE CONTROL
WIRING RUN ALONG WALL.
(2) #4 & (1) #10
GRD. IN 1" C.
(2) #16 & (1) #10
GRD. IN 3/4" C.
AT CEILING
EXISTING ELECTRICAL
SHOP PANEL
SCALE: N.T.S.
KEY PLAN
NO
RT
H
PROJECT AREA
ALL WORK SHALL BE PERFORMED BY AN CERTIFIED ELECTRICIAN. ALL WORK SHALL BE IN STRICT ACCORDANCE WITH THE NATIONAL ELECTRICAL CODE, THE INTERNATIONAL ENERGY CODE AND ALL REGULATIONS, LAWS AND ORDINANCES WHICH MAY BE APPLICABLE. SEE COVER SHEET G-1 FOR LATEST
ADOPTED EDITIONS.
THE ELECTRICAL SUBCONTRACTOR SHALL REFER TO ARCHITECTURAL AMD MECHANICAL DRAWINGS DURING
BIDDING AND CONSTRUCTION TO AVOID ANY AND ALL CONFLICTS.
ALL POWER WIRE IS TO BE COPPER WITH "THWN", THHW" OR "THHN" INSULATION. TYPE "AC", "BX", "NM" CABLES WILL NOT BE PERMITTED ON THIS PROJECT. ALL EXPOSED CONDUIT SHALL BE "EMT" TYPE CONDUIT WITH SET SCREW OR COMPRESSION FITTINGS FOR ALL PANEL FEEDERS AND HOME RUNS BACK TO PANELS. ALL FLEXIBLE CONDUIT CAN BE "MC" OR NON-METALLIC FLEXIBLE CONDUIT WITH APPROVED FITTINGS AND BOXES.
THE ELECTRICAL SUBCONTRACTOR IS RESPONSIBLE FOR ALL HANGERS, CLIPS, MOUNTING HARDWARE, ETC.
THE ELECTRICAL SUBCONTRACTOR SHALL PROVIDE ALL POWER WIRING. COORDINATE WITH RESPECTIVE
CONTRACTOR FOR EQUIPMENT WIRING AND CONTROLS.
THE ELECTRICAL SUBCONTRACTOR SHALL INSTALL ALL SAFETY SWITCHES NOT FACTORY INSTALLED WITH
EQUIPMENT, AND MAKE FINAL CONNECTIONS TO EQUIPMENT.
ELECTRICAL SUBCONTRACTOR SHALL COORDINATE BREAKER AND WIRING SIZING WITH EQUIPMENT PRIOR TO INSTALLING, AND IF ANY DISCREPANCIES ARE FOUND, THE CONTRACTOR SHALL CORRECT AT NO COST TO THE
TENANT.
THE ELECTRICAL SUBCONTRACTOR SHALL VERIFY VOLTAGE AND PHASE OF EQUIPMENT PRIOR TO ROUGH-INS.
THE ELECTRICAL SUBCONTRACTOR SHALL PROVIDE A REVISED TYPED PANEL INDEX FOR THE EXISTING
PANELS.
THE ELECTRICAL SUBCONTRACTOR SHALL SEAL ALL ELECTRICAL PENETRATIONS THRU EXTERIOR WALL TO
MAINTAIN AN AIR AND WATER TIGHT SEAL.
THE ELECTRICAL SUBCONTRACTOR SHALL BE RESPONSIBLE FOR HIS OWN CUTTING AND PATCHING.
COORDINATE WITH THE GENERAL CONTRACTOR.
THE ELECTRICAL SUBCONTRACTOR SHALL INSTALL THE ELECTRICAL CONDUITS A MINIMUM OF 6" ABOVE CEILING
GRID.
PER THE NEC 408.4 ALL BRANCH CIRCUITRY SHALL BE IDENTIFIED WITH A TAG TO INDICATE THE CIRCUIT AND PANEL TO WHICH IT IS SERVED FROM, TYPICAL FOR ALL SWITCHES, JUNCTION BOXES, CONVENIENCE OUTLETS, ETC.
THE ELECTRICAL SUBCONTRACTOR SHALL PROVIDE THE USING AGENCY A WRITTEN ONE (1) YEAR GUARANTEE COVERING ALL LABOR AND MATERIALS FURNISHED AND INSTALLED AS PART OF THIS PROJECT. GUARANTEE
SHALL COMMENCE FROM THE DATE OF SUBSTANTIAL COMPLETION.
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
GENERAL ELECTRICAL NOTES
REMOVE THE EXISTING UNUSED
BREAKER AND REPALCE WITH
A NEW 2P-50A BREAKER.
J
REMOVE PORTIONS OF THE
EXISTING FEEDERS FROM THE
EXISTING SHOP PANEL.
PROVIDE A NEW JUNCTION BOX
AND CONNECT TO THE EXISTING
LPU PANEL FEEDERS WITH NEW.
THE EXISTING LPU
PANEL FEEDER
SHALL REMAIN.
THE EXISTING SHOP PANEL
FEEDER SHALL REMAIN.
EXISTING OPENING
IN CEILING.