8-24U005 ACCC One Stop MEP Bid Set.pdf

PDF 11 MB Posted

Attached to
BID 1883 - Atlantic City One Stop
Solicitation number
BID 1883
Issued by
Atlantic County, New Jersey

About this file

Atlantic City One Stop Interior Renovations - Bid Set

This is a mechanical, electrical, and plumbing (MEP) engineering bid set prepared by Consulting M/E/P Engineers for Atlantic Cape Community College's Atlantic City One Stop project located at 1535 Bacharach Boulevard, Atlantic City, New Jersey. The project encompasses comprehensive interior renovations including mechanical ductwork and piping demolition on the first and second floors, new mechanical ductwork and piping installation, plumbing system demolition and installation, fire protection system modifications, and complete electrical infrastructure upgrades. The bid set includes detailed floor plans, ventilation schedules specifying outdoor air rates and exhaust CFM requirements for multiple room types across two floors, lighting fixture specifications with multiple fixture types ranging from recessed LED fixtures to pendant and surface-mounted options, mechanical and plumbing equipment electrical data schedules, and panel schedules for electrical distribution. The project involves coordination among multiple trades including the general contractor, electrical contractor, security vendor, and owner, with clearly defined responsibility matrices for material provision, demolition, installation, and programming tasks.

The engineering documentation details specific electrical equipment requirements including multiple fan coil units (FCU-1 through FCU-15), air handling units (AH-1, AH-3b, AH-3e, AH-3f, AH-7a), condensate pumps, and various receptacles and lighting circuits distributed across three electrical panels (REM1, FCS1A, and FCS1B) with a total connected load of approximately 111.81 kVA across three phases. Lighting controls are specified with occupancy sensors, vacancy sensors, and daylight sensors implemented across nine distinct control zones. The ventilation schedule covers 40 distinct spaces including classrooms, conference rooms, offices, toilet rooms, and utility spaces with occupancy classifications per IMC 2021 standards. All design work is sealed by New Jersey Professional Engineer Richard L. Delp (PE No. GE45368), and the bid set includes comprehensive mechanical specifications, plumbing riser diagrams, and fire protection system modifications necessary for the complete renovation of the Atlantic City Campus interior.

View the file

Other files

Show all 11

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

M0.1

Consulting M/E/P Engineers

RICHARD L. DELP, P.E.

New Jersey Professional Engineer

NO. GE45368

DM1.1

RICHARD L. DELP, P.E.

New Jersey Professional Engineer

NO. GE45368

1/8"=1'-0"

MECHANICAL DUCTWORK DEMOLITION PARTIAL FIRST FLOOR PLAN

DM1.2

RICHARD L. DELP, P.E.

New Jersey Professional Engineer

NO. GE45368

1/8"=1'-0"

MECHANICAL DUCTWORK DEMOLITION PARTIAL SECOND FLOOR PLAN

DM2.1

RICHARD L. DELP, P.E.

New Jersey Professional Engineer

NO. GE45368

1/8"=1'-0"

MECHANICAL PIPING DEMOLITION PARTIAL FIRST FLOOR PLAN

M1.1

RICHARD L. DELP, P.E.

New Jersey Professional Engineer

NO. GE45368

1/8"=1'-0"

MECHANICAL DUCTWORK NEW WORK PARTIAL FIRST FLOOR PLAN

M1.2

1/8"=1'-0"

MECHANICAL DUCTWORK NEW WORK PARTIAL SECOND FLOOR PLAN

Consulting M/E/P Engineers

RICHARD L. DELP, P.E.

UP

M2.1

Consulting M/E/P Engineers

RICHARD L. DELP, P.E.

New Jersey Professional Engineer

NO. GE45368

1/8"=1'-0"

MECHANICAL PIPING NEW WORK PARTIAL SECOND FLOOR PLAN

1/8"=1'-0"

MECHANICAL DUCTWORK NEW WORK PARTIAL FIRST FLOOR PLAN

ROOM NAME

IMC 2021 OCCUPANCY

CLASSIFICATION

AREA (FT2)

Az

ROOM

HEIGHT (FT)

NUMBER OF

FIXTURES

IMC 2021 EXHAUST

CFM PER FIXTURE

IMC 2021

CFM PER

SQUARE

FOOT

TOTAL

ZONE

EXHAUST

CFM /

PERSON Rp

AREA

OUTDOOR

AIR RATE Ra

OCCUPANT

DENSITY

PER 1000

FT2

BREATHING SINGLE

ZONE OUTDOOR

AIR FLOW RATE

Voz=Vbz

ZONE AIR

DISTRIBUTION

EFFECTIVENESS

Ez

ZONE

POPULATION Pz

ZONE OUTDOOR

AIRFLOW CFM

Voz (SINGLE

ZONE)

ACTUAL OA CFM

PROVIDED TO

SPACE

(EXISTING)

SERVED BY REMARKS

1ST FLOOR

WAITING/RECEPTION AREA 134 RECEPTION AREAS 881 9.5 0 0 0 0 5 0.06 30 116 0.8 8 120 120 (E)RTU-1

CASHIER 134A OFFICE SPACES 89 9.5 0 0 0 0 5 0.06 5 13 0.8 1 15 20 (E)RTU-1

WORK SPACE 134C OFFICE SPACES 162 9.5 0 0 0 0 5 0.06 5 18 0.8 1 20 20 (E)RTU-1

CORRIDOR 134D OFFICE SPACES 1,095 9.5 0 0 0 0 5 0.06 5 120 0.8 6 120 120 (E)RTU-1

BREAKROOM 135 OFFICE SPACES 112 9.5 0 0 0 0 5 0.06 5 15 0.8 1 15 80 (E)RTU-1

OFFICE 139 OFFICE SPACES 131 9.5 0 0 0 0 5 0.06 5 16 0.8 1 20 20 (E)RTU-1

OFFICE 140 OFFICE SPACES 150 9.5 0 0 0 0 5 0.06 5 18 0.8 1 20 20 (E)RTU-1

HUDDLE 142 CONFERENCE ROOMS 83 9.5 0 0 0 0 5 0.06 50 37 0.8 5 40 40 (E)RTU-1

HUDDLE 143 CONFERENCE ROOMS 88 9.5 0 0 0 0 5 0.06 50 38 0.8 5 40 40 (E)RTU-1

HUDDLE 144 CONFERENCE ROOMS 83 9.5 0 0 0 0 5 0.06 50 37 0.8 5 40 40 (E)RTU-1

HUDDLE 145 CONFERENCE ROOMS 88 9.5 0 0 0 0 5 0.06 50 38 0.8 5 40 40 (E)RTU-1

CONFERENCE 146 CONFERENCE ROOMS 159 9.5 0 0 0 0 5 0.06 50 62 0.8 8 65 75 (E)RTU-1

STORAGE 147 STORAGE ROOMS 102 9.5 0 0 0 0 0 0.12 0 15 0.8 0 20 20 (E)RTU-1

TESTING WAITING AREA 148 RECEPTION AREAS 435 9.5 1 0 0 0 5 0.06 30 95 0.8 10 100 100 (E)RTU-1

FACULTY 148 OFFICE SPACES 139 9.5 0 0 0 0 5 0.06 5 17 0.8 1 20 50 (E)RTU-1

TESTING 149 CLASSROOMS (9 PLUS) 580 9.5 0 0 0 0 10 0.12 35 400 0.8 25 400 400 (E)RTU-1

STORAGE 150 STORAGE ROOMS 102 9.5 0 0 0 0 0 0.12 0 15 0.8 10 20 20 (E)RTU-1

PROCOTOR 151 OFFICE SPACES 151 9.5 0 0 0 0 5 0.06 5 18 0.8 1 20 20 (E)RTU-1

IT CLOSET 152 CORRIDORS & UTILITIES 197 9.5 0 0 0 0 0 0.06 0 15 0.8 0 15 20 (E)RTU-1

PRIVATE TESTING ROOM 153 OFFICE SPACES 103 9.5 0 0 0 0 5 0.06 5 14 0.8 1 15 20 (E)RTU-1 CFA RESOURCE ROOM 154 CLASSROOMS (9 PLUS) 369 9.5 0 0 0 0 10 0.12 35 143 0.8 7 145 150 (E)RTU-1

ACCESSIBLE TOILET ROOM 180 TOILET/JANITOR CLOSET (PUBLIC) 80 9.5 1 70 0 70 0 0 0 0 0.8 0 0 75 (E)RTU-1 CORRIDOR 100 CORRIDORS & UTILITIES 649 9.5 0 0 0 0 0 0.06 0 49 0.8 0 50 300 (E)RTU-1

MEN'S 126 TOILET/JANITOR CLOSET (PUBLIC) 9.5 2 70 0 140 0 0 0 0 0.8 0 0 150 (E)RTU-1 WOMEN'S 127 TOILET/JANITOR CLOSET (PUBLIC) 9.5 2 70 0 140 0 0 0 0 0.8 0 0 150 (E)RTU-1

2ND FLOOR

LANGUAGE LAB 249 CLASSROOMS (9 PLUS) 806 9.5 0 0 0 0 10 0.12 35 483 0.8 29 485 600 (E)RTU-1

CLASSROOM 251 OFFICE SPACES 295 9.5 0 0 0 0 5 0.06 5 35 0.8 2 35 80 (E)RTU-1

OFFICE 252 OFFICE SPACES 244 9.5 0 0 0 0 5 0.06 5 31 0.8 2 35 40 (E)RTU-1

OFFICE 254 OFFICE SPACES 131 9.5 0 0 0 0 5 0.06 5 16 0.8 1 20 80 (E)RTU-1

OFFICE 255 OFFICE SPACES 160 9.5 0 0 0 0 5 0.06 5 18 0.8 1 20 80 (E)RTU-1

CLASSROOM 256 CLASSROOMS (9 PLUS) 692 9.5 0 0 0 0 10 0.12 35 416 0.8 25 420 600 (E)RTU-1

OFFICE 259 OFFICE SPACES 155 9.5 0 0 0 0 5 0.06 5 18 0.8 1 20 220 (E)RTU-1

WOMEN TOILET 261 TOILET/JANITOR CLOSET (PUBLIC) 228 9.5 4 70 0 280 0 0 0 0 0.8 0 300 300 (E)RTU-1

OFFICE 264 OFFICE SPACES 235 9.5 0 0 0 0 5 0.06 5 30 0.8 2 35 80 (E)RTU-1

CLASSROOM 266 CLASSROOMS (9 PLUS) 328 9.5 0 0 0 0 10 0.12 35 199 0.8 12 200 270 (E)RTU-1 MEN TOILET 271 TOILET/JANITOR CLOSET (PUBLIC) 403 9.5 9 70 0 630 0 0 0 0 0.8 0 650 650 (E)RTU-1

CLASSROOM 274 CLASSROOMS (9 PLUS) 711 9.5 0 0 0 0 10 0.12 35 419 0.8 25 420 420 (E)RTU-1 CLASSROOM 275 CLASSROOMS (9 PLUS) 350 9.5 0 0 0 0 10 0.12 35 215 0.8 13 215 270 (E)RTU-1

CASINO 276 CLASSROOMS (9 PLUS) 3,070 9.5 0 0 0 0 10 0.12 35 1336 0.8 70 1,340 1,460 (E)RTU-1 1

OFFICE 277 OFFICE SPACES 202 9.5 0 0 0 0 5 0.06 5 28 0.8 2 30 220 (E)RTU-1

CLASSROOM 278 CLASSROOMS (9 PLUS) 379 9.5 0 0 0 0 10 0.12 35 232 0.8 14 235 250 (E)RTU-1 CLASSROOM 282 CLASSROOMS (9 PLUS) 489 9.5 0 0 0 0 10 0.12 35 298 0.8 18 300 300 (E)RTU-1 CLASSROOM 284 CLASSROOMS (9 PLUS) 350 9.5 0 0 0 0 10 0.12 35 215 0.8 13 215 270 (E)RTU-1

COMPUTER LAB 287 COMPUTER LAB 1,124 9.5 0 0 0 0 10 0.12 25 531 0.8 29 535 540 (E)RTU-1 DISTANCE EDUCATION 288 CLASSROOMS (9 PLUS) 746 9.5 0 0 0 0 10 0.12 35 449 0.8 27 450 450 (E)RTU-1

CLASSROOM 291 CLASSROOMS (9 PLUS) 370 9.5 0 0 0 0 10 0.12 35 218 0.8 13 220 225 (E)RTU-1 CLASSROOM 294 CLASSROOMS (9 PLUS) 422 9.5 0 0 0 0 10 0.12 35 251 0.8 15 255 270 (E)RTU-1

OFFICE 295 OFFICE SPACES 297 9.5 0 0 0 0 5 0.06 5 35 0.8 2 35 40 (E)RTU-1

CASINO 296 CLASSROOMS (9 PLUS) 1,132 9.5 0 0 0 0 10 0.12 35 570 0.8 32 570 630 (E)RTU-1 1

CLASSROOM 297 CLASSROOMS (9 PLUS) 1,311 9.5 0 0 0 0 10 0.12 35 597 0.8 32 600 630 (E)RTU-1 1

OFFICE 299 OFFICE SPACES 147 9.5 0 0 0 0 5 0.06 5 17 0.8 1 20 20 (E)RTU-1

OFFICE 303 OFFICE SPACES 971 9.5 0 0 0 0 5 0.06 5 104 0.8 5 105 120 (E)RTU-1

NOTES:

1. ACTUAL EXISTING OCCUPANCY USED FOR OUTSIDE AIR CALCULATIONS.

VENTILATION SCHEDULE - ATLANTIC CAPE COMMUNITY COLLEGE

Consulting M/E/P Engineers

RICHARD L. DELP, P.E.

New Jersey Professional Engineer

M3.1

NOT TO SCALE

FAN COIL UNIT CONTROL DIAGRAM

M4.1

Consulting M/E/P Engineers

RICHARD L. DELP, P.E.

M5.1

RICHARD L. DELP, P.E.

M5.2

RICHARD L. DELP, P.E.

P0.1

RICHARD L. DELP, P.E.

DP1.11/4"=1'-0"

PLUMBING DEMOLITION FLOOR PLAN

Consulting M/E/P Engineers

RICHARD L. DELP, P.E.

P1.1

RICHARD L. DELP, P.E.

New Jersey Professional Engineer

NO. GE45368

1/4"=1'-0"

SANITARY AND VENT PIPING NEW WORK FLOOR PLAN

P1.2

RICHARD L. DELP, P.E.

New Jersey Professional Engineer

NO. GE45368

1/4"=1'-0"

DOMESTIC WATER PIPING NEW WORK FLOOR PLAN

P2.1

RICHARD L. DELP, P.E.

New Jersey Professional Engineer

NO. GE45368

NOT TO SCALE

SANITARY WASTE RISER DIAGRAM

NOT TO SCALE

DOMESTIC WATER RISER DIAGRAM

MATERIAL PROVIDED BY DEMOLISHED BY INSTALLED BY LOW VOLTAGE WIRING BY

120V POWER, BACKBOX

AND CONDUIT BY

PROGRAMMING/ HEAD END

TERMINATIONS

CCTV CAMERAS, CCTV NETWORK SWITCHES, NVR, ETC. OWNER OWNER OWNER ELECTRICAL CONTRACTOR ELECTRICAL CONTRACTOR OWNER SECURITY CAMERA WALL RACK AND UPS ELECTRICAL CONTRACTOR ELECTRICAL CONTRACTOR ELECTRICAL CONTRACTOR - ELECTRICAL CONTRACTOR - CARD READERS, HARDWIRED SECURITY VENDOR ELECTRICAL CONTRACTOR ELECTRICAL CONTRACTOR ELECTRICAL CONTRACTOR ELECTRICAL CONTRACTOR SECURITY VENDOR

CARD READERS, WIRELESS SECURITY VENDOR - GENERAL CONTRACTOR - - SECURITY VENDOR

WIRELESS ACCESS CONTROL GATEWAYS SECURITY VENDOR - ELECTRICAL CONTRACTOR ELECTRICAL CONTRACTOR ELECTRICAL CONTRACTOR SECURITY VENDOR CABLE TRAY, LADDER RACK ELECTRICAL CONTRACTOR ELECTRICAL CONTRACTOR ELECTRICAL CONTRACTOR - ELECTRICAL CONTRACTOR - DATA RACKS, PATCH PANELS, PATCH CABLES ELECTRICAL CONTRACTOR ELECTRICAL CONTRACTOR ELECTRICAL CONTRACTOR ELECTRICAL CONTRACTOR ELECTRICAL CONTRACTOR ELECTRICAL CONTRACTOR

NETWORK SWITCHES OWNER OWNER OWNER - ELECTRICAL CONTRACTOR OWNER

FIBER CABLES, FIBER SHELVES, PATCH CABLES ELECTRICAL CONTRACTOR ELECTRICAL CONTRACTOR ELECTRICAL CONTRACTOR ELECTRICAL CONTRACTOR ELECTRICAL CONTRACTOR ELECTRICAL CONTRACTOR DATA JACKS, CAT6e CABLING, FACEPLATES, ETC. ELECTRICAL CONTRACTOR ELECTRICAL CONTRACTOR ELECTRICAL CONTRACTOR ELECTRICAL CONTRACTOR ELECTRICAL CONTRACTOR ELECTRICAL CONTRACTOR WIRELESS ACCESS POINTS OWNER OWNER OWNER ELECTRICAL CONTRACTOR ELECTRICAL CONTRACTOR OWNER

TELEPHONES OWNER OWNER OWNER ELECTRICAL CONTRACTOR ELECTRICAL CONTRACTOR OWNER

AUDIO/VISUAL (PROJECTORS, SCREENS, MONITORS, CABLES) OWNER OWNER OWNER ELECTRICAL CONTRACTOR ELECTRICAL CONTRACTOR OWNER POWER, LIGHTING, FIRE ALARM ELECTRICAL CONTRACTOR ELECTRICAL CONTRACTOR ELECTRICAL CONTRACTOR ELECTRICAL CONTRACTOR ELECTRICAL CONTRACTOR ELECTRICAL CONTRACTOR

NOTES:

CONTRACTOR RESPONSIBILITY CHART

1. THIS CHART SHALL SUPERSEDE ANY OTHER LOCATIONS DESCRIBING CONTRACTOR RESPONSIBILITIES.

OCCUPANCY

SENSOR

VACANCY

SENSOR

DAYLIGHT

SENSOR

AUTOMATIC

SHUT OFF BY

WALL CONTROLS LIFE SAFETY EMERGENCY LIGHTING SEQUENCE LOCATION

C01 YES - YES OCCUPANCY

SENSOR

1-BUTTON DIGITAL SWITCH (ON/OFF) IN SECURE LOCATION CONTROLLED WITH NORMAL LIGHTING, ON 24/7 FOR

SECURITY

LIGHTS ON AND OFF BY OCCUPANCY SENSOR. LIGHTS

DIMMED BY DAYLIGHT SENSOR.

MAIN LOBBY 122 AND LOBBY 100

C02 YES - - OCCUPANCY

SENSOR

1-BUTTON DIGITAL SWITCH (ON/OFF) IN SECURE LOCATION NOT CONTROLLED, ON 24/7 FOR SECURITY LIGHTS ON AND OFF BY OCCUPANCY SENSOR. CORRIDOR 100 AND WAITING/RECEPTION AREA 134

C03 - YES - VACANCY

SENSOR

2-BUTTON DIGITAL SWITCH(ES) (ON/OFF-RAISE/LOWER) - LIGHTS ON BY USER. LIGHTS OFF BY VACANCY SENSOR OR

USER.

OFFICES, FACULTY RM,

C04 YES - - OCCUPANCY

SENSOR

2-BUTTON DIGITAL SWITCH(ES) (ON/OFF-RAISE/LOWER) - LIGHTS ON BY OCCUPANCY SENSOR OR USER. LIGHTS OFF

BY OWNER. LIGHTS DIMMED BY USER.

OPEN OFFICE(S)

C05 - YES - VACANCY

SENSOR

2-BUTTON DIGITAL SWITCH(ES) (ON/OFF-RAISE/LOWER) CONTROLLED WITH NORMAL LIGHTING. ON TO 100%

DURING POWER OUTAGE.

LIGHTS ON BY OCCUPANCY SENSOR OR USER. LIGHTS OFF

BY OWNER. LIGHTS DIMMED BY USER.

BREAK ROOM

C06 YES - - OCCUPANCY

SENSOR

1-BUTTON DIGITAL SWITCH (ON/OFF) IN SECURE LOCATION CONTROLLED WITH NORMAL LIGHTING. ON TO 100%

DURING POWER OUTAGE.

LIGHTS ON BY USER. LIGHTS OFF BY VACANCY SENSOR OR

USER. LIGHTS DIMMED BY USER.

CORRIDOR 134D

C07 - YES - VACANCY

SENSOR

1-BUTTON DIGITAL SWITCH (ON/OFF) - LIGHTS ON BY USER. LIGHTS OFF BY VACANCY SENSOR OR

USER.

LARGE STORAGE ROOMS

C08 - YES - VACANCY

SENSOR

1-BUTTON DIGITAL SWITCH (ON/OFF) WITH INTEGRAL SENSOR

AT SWITCH.

- LIGHTS ON BY USER. LIGHTS OFF BY VACANCY SENSOR OR

USER.

SMALL STORAGE ROOM

C09 YES - - OCCUPANCY

SENSOR

1-BUTTON DIGITAL SWITCH (ON/OFF) WITH INTEGRAL SENSOR

AT SWITCH.

- LIGHTS ON BY USER. LIGHTS OFF BY VACANCY SENSOR OR

USER.

INDIVIDUAL TOILET RM.

C10 YES - - OCCUPANCY

SENSOR

KEYED SWITCH CONTROLLED WITH NORMAL LIGHTING. ON TO 100%

DURING POWER OUTAGE.

LIGHTS ON AND OFF BY OCCUPANCY SENSOR. MANUAL OFF

BY USER IF DESIRED.

GANG TOILET ROOMS

C11 YES - - - - - LIGHTS ON TO 100% BY OCCUPANCY SENSOR. DURING

UNOCCUPIED TIMES LIGHTS SHALL DIM FIXTURES TO 50%.

STAIRS

C12 - YES - VACANCY

SENSOR

2-BUTTON SWITCH (ON/RAISE-OFF/LOWER) WITH INTEGRAL

SENSOR AT SWITCH.

- LIGHTS ON BY USER. LIGHTS OFF BY VACANCY SENSOR OR

USER. LIGHTS DIMMED BY USER.

SMALL OFFICES

C13 YES - - OCCUPANCY

SENSOR

2-BUTTON DIGITAL SWITCH(ES) (ON/OFF-RAISE/LOWER) CONTROLLED WITH NORMAL LIGHTING. ON TO 100%

DURING POWER OUTAGE.

LIGHTS ON BY OCCUPANCY SENSOR OR USER. LIGHTS OFF

BY OWNER. LIGHTS DIMMED BY USER.

RECEPTION OFFICE

LIGHTING CONTROL SCHEDULE

LUMENS WATTS COLOR HOURS @L70 TYPE

A1 COOPER -

METALUX

24RLN-LD5-45-UNV-L840-CD1-U OR APPROVED EQUAL 120/277 4547 34 4000K 60,000 LED 0-10V DIMMING RECESSED 5 YEAR 2'X4' LED FIXTURE WITH SMOOTH FLAT FROSTED CENTER CHANNEL LENS, AND FULL HINGED DOOR. FIXTURE SHALL BE MAXIMUM 3-1/4" DEEP.

A2 COOPER -

METALUX

22RLN-LD5-36-UNV-L840-CD1-U OR APPROVED EQUAL 120/277 4044 30.6 4000K 60,000 LED 0-10V DIMMING RECESSED 5 YEAR SAME AS FIXTURE TYPE A1 EXCEPT FIXTURE TO BE 2'X2'

B1 VISUAL

COMFORT

HOUSING: E4PSF-L07DN-2

TRIM: E4PSF-RD-8408-XX

OR APPROVED EQUAL 277 802 7.8 4000K 50,000 LED 0-10V DIMMING RECESSED 5 YEAR 4" SQUARE LED RECESSED DOWNLIGHT. FIXTURE SHALL HAVE BEVEL TRIM AND FLANGE TRIM WITH REGRESSED LENS. FIXTURE SHALL BE LISTED FOR DRY/DAMP/WET LOCATIONS. FIXTURE TRIM AND FLANGE FINISH SHALL

BE SELECTED BY ARCHITECT.

C"XX" COOPER -

NEORAY

S124DR-S575D840-ETG-XXF0-1-UDD-F-W OR APPROVED EQUAL 120/277 575/FT 4.7/FT 4000K 100,000@L90 LED 0-10V DIMMING RECESSED 5 YEAR 4"W RECESSED DIRECT LED FIXTURE. NOMINAL FIXTURE LENGTH IS INDICATED BY "XX" IN THE FIXTURE TYPE, AS SHOWN ON DRAWINGS. INTENT IS FOR FIXTURES TO BE CONTINUOUS RUNS. FIXTURE SHALL BE CONSTRUCTED OF EXTRUDED ALUMINUM BODY, WITH SATIN FLUSH SNAP-IN LENS. COORDINATE FINAL CEILING TYPE WITH ARCHITECTURAL DWGS.

C84E COOPER -

NEORAY

S124DR-S350D840-ETG-84F0-1E-UDD-F-W OR APPROVED EQUAL 120/277 29,400 243.6 4000K 100,000@L90 LED 0-10V DIMMING RECESSED 5 YEAR SAME AS TYPE C"XX" EXCEPT FIXTURE TO BE 84' LONG, LOWER LUMEN PACKAGE, SHALL HAVE AN EMERGENCY CIRCUIT (FROM GENERATOR) AND SHALL ILLUMINATE 4' SECTIONS OF THE FIXTURE AS INDICATED ON DWG E1.1. EMERGENCY CIRCUIT TO BE 277V. COORDINATE FINAL CEILING TYPE WITH ARCHITECTURAL DWGS.

D"XX" COOPER -

NEORAY

S122DP-C485D840-C4XXXX-"XX"F0-1-UDD-F OR APPROVED EQUAL 120/277 485/FT 4.8/FT 4000K 61,000@L90 LED 0-10V DIMMING PENDANT 5 YEAR 2"W DIRECT SUSPENDED LED FIXTURE. NOMINAL FIXTURE LENGTH IS INDICATED BY "XX" IN THE FIXTURE TYPE, AS SHOWN ON DRAWINGS. INTENT IS FOR FIXTURES TO BE CONTINUOUS RUNS USING 8FT MAX SECTION LENGTH.

FIXTURE SHALL BE CONSTRUCTED OF EXTRUDED ALUMINUM BODY, WITH SATIN FLUSH SNAP-IN LENS. COORDINATE FINAL CEILING TYPE WITH ARCHITECTURAL DWGS. PROVIDE CUSTOM SPACING OF PENDANT SUPPORTS TO COORDINATE WITH CEILING SYSTEM, WHERE NOTED ON PLANS. REFER TO ARCHITECTURAL DWGS FOR FIXTURE MOUNTING HEIGHT.

D8E COOPER -

NEORAY

S122DP-C485D840-C4XX8F0-1-UDD-F OR APPROVED EQUAL 120/277 3880 38.4 4000K 61,000@L90 LED 0-10V DIMMING PENDANT 5 YEAR SAME AS FIXTURE TYPE D"XX" EXCEPT FIXTURE TO BE 8' LONG AND SHALL HAVE AN EMERGENCY CIRCUIT (FROM GENERATOR) AND ILLUMINATE A 4' END SECTION OF THE FIXTURE. EMERGENCY CIRCUIT TO BE 277V.

D12E COOPER -

NEORAY

S122DP-C485D840-C4XX12F0-1E-UDD-F OR APPROVED EQUAL 120/277 5820 57.6 4000K 61,000@L90 LED 0-10V DIMMING PENDANT 5 YEAR SAME AS FIXTURE TYPE D8E EXCEPT FIXTURE TO BE 12' LONG.

D16E COOPER -

NEORAY

S122DP-C485D840-C4XX16F0-1E-UDD-F OR APPROVED EQUAL 120/277 7760 76.8 4000K 61,000@L90 LED 0-10V DIMMING PENDANT 5 YEAR SAME AS FIXTURE TYPE D8E EXCEPT FIXTURE TO BE 16' LONG.

D24E COOPER -

NEORAY

S122DP-C485D840-C4XX24F0-1E-UDD-F OR APPROVED EQUAL 120/277 11640 115.2 4000K 61,000@L90 LED 0-10V DIMMING PENDANT 5 YEAR SAME AS FIXTURE TYPE D"XX" EXCEPT FIXTURE TO BE 24' LONG AND SHALL HAVE AN EMERGENCY CIRCUIT (FROM GENERATOR) AND ILLUMINATE A 4' END SECTION AT BOTH ENDS OF THE FIXTURE. EMERGENCY CIRCUIT TO

BE 277V.

E1 COOPER -

SURE-LITES

APX6RG OR APPROVED EQUAL 120/277 - 3 RED - LED - CEILING/WALL/

SURFACE

5 YEAR AC POWERED RED LED EXIT SIGN WITH, THERMOPLASTIC HOUSING AND SELECTABLE RED OR GREEN LED'S WITH UNIVERSAL MOUNT AND FIELD SNAP-OUT CHEVRONS. CONTRACTOR SHALL REFER TO THE CONTRACT DRAWINGS FOR THE MOUNTING REQUIREMENTS, NUMBER OF FACES AND ARROW REQUIREMENTS FOR EACH EXIT SIGN. UL DAMP LOCATION LISTED.

F"XX" COOPER -

NEORAY

S122DS-C675D840XX-"XX"F0-1-UDD-F OR APPROVED EQUAL 120/277 675/FT 6.7/FT 4000K 61,000@L90 LED 0-10V DIMMING SURFACE 5 YEAR 2"W DIRECT SURFACE LED FIXTURE. NOMINAL FIXTURE LENGTH IS INDICATED BY "XX" IN THE FIXTURE TYPE, AS SHOWN ON DRAWINGS. INTENT IS FOR FIXTURES TO BE CONTINUOUS RUNS. FIXTURE SHALL BE CONSTRUCTED OF EXTRUDED ALUMINUM BODY, WITH SATIN FLUSH SNAP-IN LENS. COORDINATE FINAL CEILING TYPE WITH ARCHITECTURAL DWGS. PROVIDE CUSTOM SPACING OF SUPPORTS TO COORDINATE WITH CEILING SYSTEM.

F8E COOPER -

NEORAY

S122DS-C675D840XX-8F0-1E-UDD-F OR APPROVED EQUAL 120/277 5400 53.6 4000K 61,000@L90 LED 0-10V DIMMING SURFACE 5 YEAR SAME AS FIXTURE TYPE F"XX" EXCEPT FIXTURE TO BE 8' LONG AND SHALL HAVE AN EMERGENCY CIRCUIT (FROM GENERATOR) AND ILLUMINATE A 4' END SECTION OF THE FIXTURE. EMERGENCY CIRCUIT TO BE 277V.

F12E COOPER -

NEORAY

S122DS-C675D840XX-12F0-1E-UDD-F OR APPROVED EQUAL 120/277 8100 80.4 4000K 61,000@L90 LED 0-10V DIMMING SURFACE 5 YEAR SAME AS FIXTURE TYPE F8E EXCEPT FIXTURE TO BE 12' LONG.

F18E COOPER -

NEORAY

S122DS-C675D840XX-18F0-1E-UDD-F OR APPROVED EQUAL 120/277 12150 120.6 4000K 61,000@L90 LED 0-10V DIMMING SURFACE 5 YEAR SAME AS FIXTURE TYPE F8E EXCEPT FIXTURE TO BE 18' LONG.

G1 COOPER -

PORTFOLIO

LSRS2B05FL408040D010RXX-2LBDLH-

R1505D010-2RCPSTANXX

OR APPROVED EQUAL 120/277 776 7.4 4000K 55,000@L90 LED 0-10V DIMMING SURFACE 5 YEAR 4" DIAMETER BY 6" LONG LED CYLINDER FIXTURE WITH 2-3/4" APERATURE. FIXTURE CYLINDER CONSTRUCTED OF EXTRUDED ALUMINUM WITH LENSED SPUN ALUMINUM TRIM. FIXTURE TO BE PROVIDED WITH CANOPY AND

REMOTE DRIVER. ARCHITECT SHALL SELECT FIXTURE FINISH.

G2 COOPER -

PORTFOLIO

LSRSPC2B05FL408040D010RXX-2LBDLH-

R1505D010-P236XXRM

OR APPROVED EQUAL 120/277 776 7.4 4000K 55,000@L90 LED 0-10V DIMMING PENDANT 5 YEAR 4" DIAMETER BY 6" LONG LED CYLINDER FIXTURE WITH 2-3/4" APERATURE. FIXTURE CYLINDER CONSTRUCTED OF EXTRUDED ALUMINUM WITH LENSED SPUN ALUMINUM TRIM. FIXTURE TO BE PROVIDED WITH CANOPY AND REMOTE DRIVER. ARCHITECT SHALL SELECT FIXTURE FINISH. REFER TO ARCHITECTURAL DWGS FOR FIXTURE MOUNTING HEIGHT.

ALTERNATE MANUFACTURERS

FIXTURE

TYPE MOUNTING

INTERIOR LIGHT FIXTURES

WARRANTY REMARKS

LIGHTING FIXTURE SCHEDULE

LIGHT ENGINE

DRIVERMANUFACTURER CATALOG NUMBER VOLTS

EQUIPMENT

NAME V-Ф-Hz HP/VA/A WIRE AND CONDUIT CIRCUIT

BREAKER PANEL;CKT #(S)

STARTER/

DISCONNECT

FURNISHED BY MC,

INSTALLED BY EC

STARTER/

DISCONNECT

FURNISHED BY EC,

INSTALLED BY EC

REMARKS

AH-1 120-1-60 7.2 MCA 3/4"C-2#12+1#12GND 1P-15A FCS1A;24 - UNIT MOUNT -

AH-3b 120-1-60 7.2 MCA 3/4"C-2#12+1#12GND 1P-15A FCS1A;26 - UNIT MOUNT -

AH-3e 120-1-60 7.2 MCA 3/4"C-2#12+1#12GND 1P-15A FCS1A;28 - UNIT MOUNT -

AH-3f 120-1-60 7.2 MCA 3/4"C-2#12+1#12GND 1P-15A FCS1A;30 - UNIT MOUNT -

AH-7a 120-1-60 9 MCA 3/4"C-2#12+1#12GND 1P-15A FCS1A;32 - UNIT MOUNT -

FCU-1 277-1-60 1.4 MCA 3/4"C-2#12+1#12GND 1P-15A LN1A;9 UNIT MOUNT - WIRE CONDENSATE PUMP ASSOCIATED WITH THIS FAN COIL UNIT TO SEPARATE 120V CIRCUIT FCS1A;34 VIA SEPARATE TOGGLE SWITCH DISCONNECT.

FCU-2 277-1-60 1.4 MCA 3/4"C-2#12+1#12GND 1P-15A LN1A;9 UNIT MOUNT - WIRE CONDENSATE PUMP ASSOCIATED WITH THIS FAN COIL UNIT TO SEPARATE 120V CIRCUIT FCS1A;34 VIA SEPARATE TOGGLE SWITCH DISCONNECT.

FCU-3 277-1-60 1.4 MCA 3/4"C-2#12+1#12GND 1P-15A LN1A;9 UNIT MOUNT - WIRE CONDENSATE PUMP ASSOCIATED WITH THIS FAN COIL UNIT TO SEPARATE 120V CIRCUIT FCS1A;34 VIA SEPARATE TOGGLE SWITCH DISCONNECT.

FCU-4 277-1-60 1.4 MCA 3/4"C-2#12+1#12GND 1P-15A LN1A;9 UNIT MOUNT - WIRE CONDENSATE PUMP ASSOCIATED WITH THIS FAN COIL UNIT TO SEPARATE 120V CIRCUIT FCS1A;34 VIA SEPARATE TOGGLE SWITCH DISCONNECT.

FCU-5 277-1-60 1.4 MCA 3/4"C-2#12+1#12GND 1P-15A LN1A;9 UNIT MOUNT - WIRE CONDENSATE PUMP ASSOCIATED WITH THIS FAN COIL UNIT TO SEPARATE 120V CIRCUIT FCS1A;34 VIA SEPARATE TOGGLE SWITCH DISCONNECT.

FCU-6 277-1-60 1.4 MCA 3/4"C-2#12+1#12GND 1P-15A LN1A;9 UNIT MOUNT - WIRE CONDENSATE PUMP ASSOCIATED WITH THIS FAN COIL UNIT TO SEPARATE 120V CIRCUIT FCS1A;34 VIA SEPARATE TOGGLE SWITCH DISCONNECT.

FCU-10 277-1-60 1.4 MCA 3/4"C-2#12+1#12GND 1P-15A LN1A;11 UNIT MOUNT - WIRE CONDENSATE PUMP ASSOCIATED WITH THIS FAN COIL UNIT TO SEPARATE 120V CIRCUIT FCS1A;36 VIA SEPARATE TOGGLE SWITCH DISCONNECT.

FCU-11 277-1-60 1.4 MCA 3/4"C-2#12+1#12GND 1P-15A LN1A;11 UNIT MOUNT - WIRE CONDENSATE PUMP ASSOCIATED WITH THIS FAN COIL UNIT TO SEPARATE 120V CIRCUIT FCS1A;36 VIA SEPARATE TOGGLE SWITCH DISCONNECT.

FCU-12 277-1-60 1.4 MCA 3/4"C-2#12+1#12GND 1P-15A LN1A;11 UNIT MOUNT - WIRE CONDENSATE PUMP ASSOCIATED WITH THIS FAN COIL UNIT TO SEPARATE 120V CIRCUIT FCS1A;36 VIA SEPARATE TOGGLE SWITCH DISCONNECT.

FCU-13 277-1-60 1.4 MCA 3/4"C-2#12+1#12GND 1P-15A LN1A;11 UNIT MOUNT - WIRE CONDENSATE PUMP ASSOCIATED WITH THIS FAN COIL UNIT TO SEPARATE 120V CIRCUIT FCS1A;36 VIA SEPARATE TOGGLE SWITCH DISCONNECT.

FCU-14 277-1-60 1.4 MCA 3/4"C-2#12+1#12GND 1P-15A LN1A;11 UNIT MOUNT - WIRE CONDENSATE PUMP ASSOCIATED WITH THIS FAN COIL UNIT TO SEPARATE 120V CIRCUIT FCS1A;36 VIA SEPARATE TOGGLE SWITCH DISCONNECT.

FCU-15 277-1-60 1.4 MCA 3/4"C-2#12+1#12GND 1P-15A LN1A;11 UNIT MOUNT - WIRE CONDENSATE PUMP ASSOCIATED WITH THIS FAN COIL UNIT TO SEPARATE 120V CIRCUIT FCS1A;36 VIA SEPARATE TOGGLE SWITCH DISCONNECT.

CC-1 208-1-60 - 3/4"C-3#10+1#10GND - - - - REFER TO DETAIL 1 THIS DRAWING. SERVED BY CU-1.

WC-1 208-1-60 - 3/4"C-3#10+1#10GND - - - - REFER TO DETAIL 1 THIS DRAWING. SERVED BY CU-2.

CU-1 208-1-60 13.4 MCA 3/4"C-2#12+1#12GND 2P-15A REM1;16,18 - STRUT MOUNTED REFER TO DETAILS 1&2 THIS DRAWING.

CU-2 208-1-60 16 MCA 3/4"C-2#10+1#10GND 2P-25A REM1;20,22 - STRUT MOUNTED REFER TO DETAILS 1&2 THIS DRAWING. WIRE WP/GFI RECEPTACLE CKT FCS1A;29 .

CP-1 120-1-60 1.5 FLA 3/4"C-2#12+1#12GND 1P-15A REM1;19 - ABOVE CEILING -

HWH-1 208-1-60 22 MCA 3/4"C-2#10+1#10GND 2P-20A FCS1B;38,40 - - LOCATED UNDER SINK IN TOILET ROOM 180. PROVIDED CIRCUIT BREAKER WITH PADLOCK HASP

208-1-60 41 MCA 3/4"C-2#6+1#10GND 2P-40A FCS1A;31,33 - - LOCATED UNDER SINK IN BREAK ROOM 135. PROVIDED CIRCUIT BREAKER WITH PADLOCK HASP.

208-1-60 41 MCA 3/4"C-2#6+1#10GND 2P-40A FCS1A;35,37 - - LOCATED UNDER SINK IN BREAK ROOM 135. PROVIDED CIRCUIT BREAKER WITH PADLOCK HASP.

MECHANICAL & PLUMBING EQUIPMENT - ELECTRICAL DATA SCHEDULE

HWH-2

1 1 20 (E) IT RACK RECPT. RM. 100 800 500 (E) FIRE ALARM PANEL 20 1 2

3 1 20 SPARE 0 750 (E) GEN. BATTERY CHARGER 20 1 4

5 1 20 (E) IT RACK RECPT. CHILLER RM.132 1000 1000 (E) GEN. COOLANT HEATER 20 1 6

7 1 20 (E) REF. LEAK DET. RECPT. RM.132 600 500 (E) GEN. ALT. HEATER 20 1 8

9 1000 1000 10

11 1000 1000 12

13 1 20 (E) IT RACK RECPT. RM.262 1000 1260 RECEPTACLES, DIRECTOR OFFICE 146 20 1 14

15 1 20 (E) ADT SEC. PANEL LOBBY 500 1608 16

17 1 20 (E) TELE. BD. AT SECC. DESK 500 1608 18

19 1 20 CP-1, SERVES WC-2 180 1920 20

21 1 20 RECEPTACLE, QUAD, IT CLOSET 360 1920 22

23 1 20 RECEPTACLE, QUAD, IT CLOSET 360 360 RECEPTACLE, QUAD, IT CLOSET 20 1 24

25 1 20 RECEPTACLE, QUAD, IT CLOSET 360 1000 26

27 1000 1000 28

29 1000 1000 30

31 1000 0 32

33 1000 1000 34

35 1 20 SPARE 0 1000 36

37 0 0 38

39 0 0 40

41 0 0 42

3940 3860 3860 5180 7278 5968

PHASE A: 9.12 kVA

PHASE B: 11.14 kVA

PHASE C: 9.83 kVA

TOTAL: 30.09 kVA

(E) TRANSFER SWITCH1503 200 3(E) PANEL "BR1A"

A A B C REMARKS

CKT

NOAMP

LOCATION:

MECHANICAL RM. 124

CKT

NO C

PANEL SCHEDULE FOR EXISTING PANEL: "REM1"

120/208V, 3PH, 4W, 400A BUS,

400A M.C.B.

SURFACE MOUNTED

CIRCUIT

POLE AMP B

CIRCUIT

POLEREMARKS

(E) UPS ROOM 219302 (E) SEC. VIDEO RACK CAMERAS 30 2

SPECIAL RECEPTACLE, DATA RACK, IT CLOSET 152 30 2

SECURITY CAMERA WALL RACK OFFICE 123 30

CU-1, SERVES OFFICE 123 15 2

CU-2, SERVES IT CLOSET 152 25

SPECIAL RECEPTACLE, DATA RACK, IT CLOSET 152

SPECIAL RECEPTACLE, DATA RACK, IT CLOSET 152

SPECIAL RECEPTACLE, DATA RACK, IT CLOSET 152 30 2

1 1 20 (E) FC RM 143, 144, CORRIDOR 136 0 0 (E) UV RM 134,135,137,141,142 20 1 2

3 1 20 (E) FC RM 147,148,149, CORRIDOR 140 0 0 (E) FC CORRIDOR 132 20 1 4

5 1 20 (E) FC RM 145,150,151,152 0 0 (E) MONITORS, SECURITY CAMERA 20 1 6

7 1 20 (E) ATC ACU1-2 0 0 (E) FCU-3, LOBBY-122 20 1 8

9 1 20 (E) FCU, RM 134 0 0 (E) 135C 20 1 10

11 1 20 (E) FC ENTRANCE 118 0 0 (E) 134A 20 1 12

13 1 20 (E) FCU'S RM 134-B, 134C 0 0 (E) RECEPTACLE, 133A COUNTERTOP 20 1 14

15 0 0 16

17 0 0 18

19 0 0 20

21 0 0 22

23 0 1080 AH-1, CORRIDOR 100 15 1 24

25 0 864 AH-3b, WORK SPACE 134C 15 1 26

27 1 20GFI (E) TV OUTLET 0 1080 AH-3e, OFFICE 140 15 1 28

29 1 20 (E) LOAD 0 1080 AH-3f, OFFICE 139 15 1 30

31 3375 1080 AH-7a, OPEN OFFICE 15 1 32

33 3375 1080 FCU-1 THRU FCU-6 CONDENSATE PUMPS 15 1 34

35 3375 1080 FCU-10 THRU FCU-15 CONDENSATE PUMPS 15 1 36

37 3375 12120 38

39 1 20 SPARE 0 10440 40

41 1 20 SPARE 0 7880 42

6750 3375 3375 14064 12600 11120

PHASE A: 20.81 kVA

PHASE B: 15.98 kVA

PHASE C: 14.50 kVA

TOTAL: 51.28 kVA

LOCATION:

MECHANICAL ROOM 133

PANEL SCHEDULE FOR EXISTING PANEL: "FCS1A"

120/208V, 3PH, 4W, 225A BUS,

225A M.L.O.

SURFACE MOUNTED

CKT

NO

CIRCUIT

POLE AMP REMARKS A B C

CKT

NO

(E) FRONT GUARD HOUSE 15 2

A C REMARKS AMP

CIRCUIT

POLEB

NOTE:

1. EXISTING CIRCUITS AND CIRCUIT BREAKERS TO BE

RELOCATED TO TOP OF PANEL.

HWH-2, BREAKER RM 135, MULTIPLE DISCONNECT MEANS

HWH-2, BREAK RM 135 MULTIPLE DISCONNECT MEANS

*40

(E) LOAD

*40

15 2(E) CU, RM 142, 141

2 30

PANEL "FCS1B" 3

2 15 (E) CU, RM 134

2 15 (E) CU, RM 137 (134C), 135 (134B)

1 1 20 RECEPTACLES, CORRIDOR 100, WAITING/RECEPTION 134 1080 360 RECEPTACLES, CASHIER 134A, VAULT 134B 20 1 2

3 1 20 RECEPTACLES, RECEPTION OFFICE 720 360 RECEPTACLES, CASHIER 134A, VAULT 134B 20 1 4

5 1 20 RECEPTACLE, REFRIGERATOR BREAK ROOM 135 360 180 RECEPTACLE, BREAK ROOM 135 20 1 6

7 1 20 RECEPTACLES, BREAK ROOM 135 360 1400 RECEPTACLE, OFFICE COPIER 20 1 8

9 1 20 RECEPTACLES, WORK SPACE 134C 1080 1080 RECEPTACLES, OPEN OFFICE 20 1 10

11 1 20 RECEPTACLES, OPEN OFFICE 1080 720 RECEPTACLES, OFFICE 139 20 1 12

13 1 20 RECEPTACLES, OFFICE 140 720 720 RECEPTACLES, CORRIDOR 134D, STORAGE 147 20 1 14

15 1 20 RECEPTACLES TESTING WAITING AREA 148 AND STORAGE 150 900 540 RECEPTACLES, TESTING WAITING AREA AND TV 20 1 16

17 1 20 RECEPTACLES, FACULTY ROOM 148 540 1400 RECEPTACLE, COPIER IN FACULTY ROOM 148 20 1 18

19 1 20 HAND DRYER, TOILET ROOM 180 1000 720 RECEPTACLES, TESTING ROOM 149 20 1 20

21 1 20 RECEPTACLES, TESTING ROOM 149 720 720 RECEPTACLES, TESTING ROOM 149 20 1 22

23 1 20 RECEPTACLE, (FLOOR BOX), TESTING ROOM 149 360 360 RECEPTACLE, (FLOOR BOX), TESTING ROOM 149 20 1 24

25 1 20 RECEPTACLES, TESTING ROOM 149 720 1080 RECEPTS., PROCTOR OFFICE 151, PRIVATE TESTING RM. 153 20 1 26

27 1 20 RECEPTACLES, CFA RESOURCE ROOM 154 540 720 RECEPTACLES, CFA RESOURCE ROOM 154 20 1 28

29 1 20 RECEPTACLE, ROOFTOP AT CU-2 180 900 RECEPTACLES, WELCOME AREA, MAIN LOBBY 122 20 1 30

31 1 20 RECEPTACLES, OFFICE 123 720 720 RECEPTACLES, WELCOME DESK, MAIN LOBBY 122 20 1 32

33 1 20 RECEPTACLES, DIGITAL DISPLAYS, MAIN LOBBY 122 360 360 RECEPTACLES, MAIN LOBBY 122 20 1 34

35 1 20 RECEPTACLES, DIGITAL DISPLAYS, MAIN LOBBY 122 & WAIT 134 360 720 RECEPTACLES, HUDDLE ROOMS 142 AND 143 20 1 36

37 1 20 RECEPTACLES, HUDDLE ROOMS 144 AND 145 720 1800 38

39 1 20 RECEPTACLES, CONFERENCE RM 146 540 1800 40

41 1 20 RECEPTACLES, CONFERENCE RM 146 AND FLOOR BOX 720 0 SPARE 20 1 42

43 1 20 SPARE 0 0 SPARE 20 1 44

45 1 20 SPARE 0 0 SPARE 20 1 46

47 1 20 SPARE 0 0 SPARE 20 1 48

49 1 20 SPARE 0 0 SPARE 20 1 50

51 1 20 SPARE 0 0 SPARE 20 1 52

53 1 20 SPARE 0 0 SPARE 20 1 54

5320 4860 3600 6800 5580 4280

PHASE A: 12.12 kVA

PHASE B: 10.44 kVA

PHASE C: 7.88 kVA

TOTAL: 30.44 kVA

A A B C

CIRCUIT

POLEREMARKS

HWH-1, TOILET RM 180 TANKLESS HOT WATER HEATER *20

REMARKS

CKT

NOAMP

LOCATION:

BREAK ROOM 135

CKT

NO C

PANEL SCHEDULE FOR NEW PANEL: "FCS1B"

120/208V, 3PH, 4W, 100A BUS,

100A MLO, 10,000A RMS

SURFACE MOUNTED

CIRCUIT

POLE AMP B

1 1 20 (E) LIGHTING, EXTERIOR ENTRANCE (E) LIGHTING, LOBBY 20 1 2

3 1 20 (E) LIGHTING, RMS. 102, 104, 105 (E) LIGHTING, LOBBY 20 1 4

5 1 20 (E) LIGHTING, GARAGE (E) LIGHTING, LOBBY 20 1 6

7 1 20 (E) LIGHTING, RMS. 108, 116 (E) LIGHTING, ENTRANCE 20 1 8

9 1 15 FCU-1 THRU FCU-6 (E) SPARE 20 1 10

11 1 15 FCU-10 THRU FCU-15 (E) EXIT LIGHTS 20 1 12

13 1 20 (E) LIGHTING, DRIVE-THRU (E) LIGHTING, STAIRS, TR'S, CORRIDOR 20 1 14

15 1 20 (E) SPARE (E) LIGHTING, RMS 111,112,113,114 - ON ALL TIME 20 1 16

17 1 20 (E) SPARE (E) SPACE - 1 18

19 1 - (E) SPACE (E)SPACE - 1 20

21 1 - (E) SPACE (E)SPACE - 1 22

23 1 - (E) SPACE (E)SPACE - 1 24

25 1 - (E) SPACE (E)SPACE - 1 26

27 1 - (E) SPACE (E)SPACE - 1 28

29 1 - (E) SPACE (E)SPACE - 1 30

31 1 - (E) SPACE (E)SPACE - 1 32

33 1 - (E) SPACE (E)SPACE - 1 34

35 1 - (E) SPACE (E)SPACE - 1 36

37 1 - (E) SPACE (E)SPACE - 1 38

39 1 - (E) SPACE (E)SPACE - 1 40

41 1 - (E) SPACE (E)SPACE - 1 42

43 1 - (E) SPACE (E)SPACE - 1 44

45 1 - (E) SPACE (E)SPACE - 1 46

47 1 - (E) SPACE (E)SPACE - 1 48

REMARKS

CKT

NOAMP

LOCATION:

MAINTENANCE 108

CKT

NO

PANEL SCHEDULE FOR EXISTING PANEL: "LN1A"

277/480V, 3PH, 4W, 100A BUS,

100A MCB

SURFACE MOUNTED

CIRCUIT

POLE AMP

CIRCUIT

POLEREMARKS

85 1 - (E) SPACE (E) SPACE - 1 86

87 1 - (E) SPACE (E) SPACE - 1 88

89 1 - (E) SPACE (E) SPACE - 1 90

91 1 - (E) SPACE (E) SPACE - 1 92

93 RECEPTACLE, SECURITY DESK 20 1 94

95 RECEPTACLE, SECURITY DESK 20 1 96

97 98

99 100

101 1 20 (E) RECEPTACLE, ELEVATOR WALL (E) LOAD 20 1 102

103 1 20 (E) RECEPTACLE, SECURITY WALL (E) LOAD 20 1 104

105 1 20 (E) LOAD (E) LOAD 20 1 106

107 1 20 (E) RECEPTACLE RM. 101 108

109 1 20 (E) HAND DRYER, WOMENS TR 110

111 1 20 (E) RECEPTACLE, FRONT DOOR (E) LOAD 20 1 112

113 1 20 (E) RECEPTACLE, BACK DOOR (E) LOAD 20 1 114

(E) EXTERIOR REC302

2 80 (E) SECURITY BUILDING (E) LOAD 30 2

(E) LOAD 20 2

LOCATION:

MAINTENANCE 108

CKT

NO

PANEL SCHEDULE FOR EXISTING PANEL: "PN1A1" SECT. 3

120/208V, 3PH, 4W, 400A BUS,

400A M.L.0.

SURFACE MOUNTED

CIRCUIT

POLE AMP

CIRCUIT

POLEREMARKS REMARKS

CKT

NOAMP

FP0.1

RICHARD L. DELP, P.E.

DFP1.1

FIRE PROTECTION DEMOLITION - FIRST FLOOR PLAN

Consulting M/E/P Engineers

RICHARD L. DELP, P.E.

FP1.1

FIRE PROTECTION NEW WORK - FIRST FLOOR PLAN

Consulting M/E/P Engineers

RICHARD L. DELP, P.E.

File details come from the government source that posted it. Updated .